Section S7 - DC and AC auxiliary services installations

Size: px
Start display at page:

Download "Section S7 - DC and AC auxiliary services installations"

Transcription

1 S7/2 Section S7 - DC and AC auxiliary services installations Contents S7. Generalities...3 S7. Generalities...4 S7..1 Scope of work...4 S7..2 Dimensioning the auxiliary services equipment...4 S7.1 General requirements for equipment...5 S7.1.1 Standards...5 S7.1.2 Site specific conditions...7 S7.1.3 Parameters of the DC and AC installation...8 S7.1.4 Nameplates, labels...8 S7.1.5 Protective coatings...9 S7.1.6 Earthing...9 S7.2 General requirements for additional equipment...9 S7.2.1 Motors...9 S7.2.2 Low voltage switches...1 S7.2.3 Low voltage disconnectors...1 S7.2.4 Fuses...1 S7.2.5 Selection and control switches, indicating buttons and lamps...1 S7.2.6 Terminal strips...1 S7.3 Technical requirements for the equipment of DC auxiliary services installation...11 S7.3.1 Generalities...11 S7.3.2 Battery...12 S7.3.3 Rectifier...13 S7.4 Technical requirements for the equipment of AC auxiliary services installation...15 S7.4.1 Generalities...15 S7.4.2 Power transformer...15 S7.4.3 Technical requirements for emergency generating set (Diesel Unit)...16 S7.5 Technical requirements for the DC and AC auxiliary services cabinets...19 S7.6 Tests for DC and AC auxiliary services equipment...21 S7.7 TECHNICAL DATA SHEETS...23

2 S7/3 Table B7 Equipment and materials specification B7/1 B7/3 Table C7 Technical conditions and characteristics required and guaranteed for the equipment Table C7.1 Battery C7.1/1 C7.1/3 Table C7.2 Rectifier C7.2/1 C7.2/6 Table C7.3 Inverter C7.3/1 C7.3/3 Table C7.4 Main DC distribution board C7.4/1 C7.4/3 Table C7.5 Power transformer C7.5/1 C7.5/3 Table C7.6 Emergency generator (Diesel unit) C7.6/1 C7.6/4 Table C7.7 Main AC distribution board C7.7/1 C7.7/3 Table D7 Type, routine and site tests D7 / 1 Table E7.1 Spare parts - Recommended E7.1/1 Table E7.2 Maintenance tools and devices E7.2/1 Table F7 Technical documentation included in the contract F7 / 1 Table G7 Deviations from specifications G7 / 1 Record of document modifications: THE REPRODUCTION, LENDING OR EXPOSURE OF THIS DOCUMENT, AS WELL AS THE TRANSMISSION OF THE INFORMATION IT CONTAINS IS ALLOWED ONLY IN THE CONDITIONS STIPULATED IN THE CONTRACT. EXTRACONTRACTUAL USE REQUIRES THE WRITTEN AGREEMENT OF ISPE

3 S7/4 S7. Generalities S7..1 Scope of work These technical specifications includes the equipment needed for the execution of DC and AC auxiliary services installations of. This project provides modern auxiliary services installations in order to achieve the required safety and the integration of the auxiliary services installations into the substation s management system. The auxiliary services installation will have to meet the dimensioning and reliability requirements imposed by the receptors of the primary and secondary equipment of the substation, in accordance with the standard norms and regulations. This section of Tender book includes the technical requirements for the equipment necessary to accomplish the works related to the auxiliary services installation as followings: - 1 substation battery; - 1 rectifier; - 1 inverter; - 1 auxiliary services transformer; - 22 V DC auxiliary services distribution board; - 4 V AC auxiliary services distribution board; - DC and AC distribution cabinets in the control room; - emergency generating set (Diesel power unit). The inverter will feed computers, printers and other control equipment requiring 23 V, 5 Hz auxiliary voltage. An AC secondary distribution box will be included in the scope of supply. A DC terminal box, installed in the proximity of the battery, will be provided to create a separate feeding for the relay protection group 2. An associated DC secondary distribution box will be included in the scope of supply. S7..2 Dimensioning the auxiliary services equipment The sources of continuous current and alternating current and the supply and distribution boards will be dimensioned and equipped for the 11/3 kv substation final stage (including the spares). The Contractor must verify the capacity of the power supply sources: battery, rectifier, inverter, transformer, Diesel unit and dimensioning of the auxiliary services boards, for the

4 S7/5 consumptions of the substation s equipment and systems and considering the manufacturing tolerances and diversity factors of the installation. The Contractor will take into account that the switches of power supply sources (auxiliary services transformer, Diesel unit, battery, rectifier, inverter) will be controlled both remotely by the substation s control system as well as locally. S7.1 General requirements for equipment S7.1.1 Standards The equipment must meet the requirements of the applicable IEC regulations, the national standards and the attached requirements Table C. The following standards are considered applicable: - SR EN ISO 91:28 - Quality Management Systems. Requirements. - IEC 65(61) - International Electrotechnical Vocabulary. Electricity production, transportation and distribution. - IEC IT testing techniques; - IEC 671-1,2,3 - Coordination of insulation; - IEC Thermal evaluation and classification of electrical insulation; - IEC Climatic tests for equipment; - IEC , 2-2, Classification of environmental conditions; - IEC Selection and dimensioning of H. V. insulators for pollution conditions; - IEC Degrees of protection provided by cases (IP code); - IEC , 22 - plumb acid stationary batteries - sealed valve types; - IEC Semi-conductor converters - General requirements and switching converters; - IEC General common specifications of IT equipment; - IEC HV AC switches; - IEC Disconnectors and HV AC earthing switches; - IEC High voltage alternating current device in metallic tire, for voltages above 1 kv up to 52 kv inclusively; - IEC Prefabricated HV/LV substations; - IEC Current transformers; - IEC Voltage transformers; - IEC Surge arresters;

5 S7/6 - IEC Insulators for alternating voltage higher than 1V; - IEC 676-series - Power Transformers. - IEC Insulating liquids. Measurement of permittivity, dielectric dissipation and DC resistivity factor; - IEC Specification of new insulating oils for transformers and machines; - IEC Marking-out of the terminals and sockets for the power transformers; - IEC Rotating electrical machines; - ISO Alternating current power units operated by internal combustion engines; - ISO Internal combustion engines; - IEC LV device units; - IEC LV device; - EN Electronic equipment used in power substations; - IEC Electrical relays with a single measure input; - IEC Insulation tests for electrical relays; - IEC Measuring relays and protection equipment; - IEC Alternative components and power failures in the supply of electrical relays; - IEC Directional and power relays; - IEC Differential relays; - IEC Impedance measuring relays; - IEC Protection systems; - IEC Vibration tests; - IEC Shock tests; - IEC Seismic Testing; - IEC High frequency interference tests; - IEC Electrostatic discharge tests; - IEC Radiating electromagnetic fields tests; - IEC Fast transient interference tests; - IEC Contacts performance; - IEC Identification of the equipment terminals and general rules for an alphanumeric marking system; - IEC Identification of conductors by colors or numbers; - IEC Coordination of the equipment insulation within low voltage systems; - IEC Codes for color designation;

6 S7/7 - IEC Telecontrol equipment and systems; - IEC Connectors for cables and optical fibers; - IEC 61 - Electromagnetic compatibility; - IEC Preparation of documents used in Electrotechnology; - IEC Identification of systems, industrial installations and equipment; - IEC All-or-nothing electrical relays; - IEC Telecontrol equipment and systems. Standard transmission protocols for basic applications; - IEC Telecontrol equipment and systems. Communication protocols for the transmission of integrated totals in electric power systems; - IEC Communication networks and systems in power substations; - Law no. 68/21. - Law on Product Conformity Assessment, with subsequent implementations and completions. The equipment that meets the requirements of other approved standards will be accepted if they have provisions equal or better quality than those specified above, or those specified for each piece of equipment, when the Contractor shall clearly justify the differences between the adopted and reference standards within his bidding. The bidding must be accompanied by a copy of the adopted standard. The equipment which deviates from the technical specifications contained in the technical requirements of the tender book, tables, in which they will be highlighted, will be relieved. All equipment will be supplied with all accessories necessary for the assembly, operation and commissioning, control and monitoring. If there are materials or accessories that have not been mentioned in the specifications but are necessary for the proper operation of the equipment, it is the Contractor's obligation to deliver them without a prior request from the Contracting Authority. S7.1.2 Site specific conditions The equipment included in this contract is designed to operate indoors. Microclimate conditions will be provided in the room of the battery in order not to limit their operating performances or lifetime. All equipment must optimally operate under the following conditions: a. Climatic conditions for batteries of storage cells: - place of assembly indoors

7 S7/8 - maximum temperature +27 C - minimum temperature +18 C - relative humidity 2 C) 9% 4 C 5% - normal conditions of dust, smoke, fumes, salt. b. Climatic conditions for rectifier, inverter, distribution boards, emergency generating set: - place of assembly indoors - maximum temperature 4 C - minimum temperature -5 C - relative humidity 2 C) 9% 4 C 5% - normal conditions of dust, smoke, fumes, salt c. All equipment installed indoors and outdoors shall be protected against condensed water. d. Altitude 1 m f. Conditions for earthquake protection according to P1-1/26 (construction): - ground acceleration (ag).24 g - corner period (Tc).7 sec. according to IEC horizontal acceleration at ground level: 3 m/s² S7.1.3 Parameters of the DC and AC installation a) DC installation The DC consumers supply voltage is 22 V. The installation operates isolated from the earth. The power supply sources (the battery and rectifier) will ensure that the supply voltage (at their terminals) is maintained within the limits allowed by the receptors and the installation. b) AC installation The AC consumers supply voltage is 3x23/4 V. The installation will operate with the directly earthed neutral. In order to ensure the proper operation of the consumers, the supply voltage (at their terminals) will be maintained within the limits allowed by the receptors and the installation. S7.1.4 Nameplates, labels a) A nameplate made of a corrosion resistant material will be applied in a visible place on each equipment and auxiliary device. At least the following data regarding the equipment will be

8 S7/9 legibly written on the name plate: name of manufacturer, type of equipment, serial number, year of manufacture, product identification number and all technical data in accordance with the equipment s appropriate standard. b) Labels will be provided for the equipment and materials included in the bidding, and mounted their own or control cabinets and tiles on the connections from terminals to the interior and exterior of the cabinet and on the inner connection conductors for their fast identification or to give guidance on certain tasks (if and where appropriate). The labels and tiles for conductors will be thus written down in order not to be deleted and to maintain a good legibility in time. The standard ring-type tiles applied to conductors are preferred. c) In places provided by the labor protection regulations in force, and wherever deemed necessary, warning labels will be provided. d) The marking-out of the auxiliary services or control cabinets will be made according to IEC All labels will be written in Romanian. S7.1.5 Protective coatings a) All parts of equipment or materials involved in the Contract shall be protected against corrosion during transportation, storage, assembly and operation, by applying a surface treatment corresponding to each item. b) The Contractor will send data about the coating process including: - Type of coating proposed for each important surface of the equipment; - Methods of coating preparation, application and inspection; - Sequence and duration of operations; - Standards for the coating procedure and the coating material constituent elements. S7.1.6 Earthing All metal parts of the equipment, other than those included in the electrical circuits, will allow a smooth connection to the main earthing facility through special terminals provided with screws. S7.2 General requirements for additional equipment S7.2.1 Motors All motors will meet the requirements of IEC 634 and will be able to operate continuously under normal conditions, without dangerous overheating, at frequencies comprised between

9 S7/ Hz and a voltage between.85 U n 1.1 U n. S7.2.2 Low voltage switches The low voltage switches and mini-switches, with less than 1 kv voltage, must be manufactured and tested according to IEC They will be provided both with main and auxiliary contacts necessary for the distance signaling of the main contacts position of their operation mode (protection or deliberate activation). All DC and AC circuit switches will be thus chosen so that to ensure the selectivity of the protections. All switches will be equipped with thermal and electromagnetic protection. S7.2.3 Low voltage disconnectors The low voltage disconnectors for a voltage rating less than 1 kv (69 Vac) must be manufactured and tested according to IEC and IEC 624. They will be used for disconnecting or switching functions. The distance between open contacts must prevent the arc ignition and the drive lever position must always correspond with the main contacts. S7.2.4 Fuses The fuses must comply with the requirements of IEC 6269 and will be dimensioned so as to ensure their selective and indicated operation in relation to other protective devices within the respective circuit. S7.2.5 Selection and control switches, indicating buttons and lamps The switches must meet the requirements of IEC , 5. Their construction must not allow their incorrect activation or interlock, and the packages must be well tight and isolated. The control buttons and indicating lamps must be manufactured and tested according to IEC S7.2.6 Terminal strips The terminal strips must meet the requirements of IEC , 7 and will have electrical characteristics (ampere rating, voltage rating and holding voltage) corresponding to serviced circuits. The terminals will have a robust construction, and will be made of inflammable materials. The movement of the terminals along the rails should take place easily. For single-core conductors, with a cross section up to 6mm 2 and multi-core conductors with a cross section up

10 S7/11 to 16mm 2, pressing screw clips, which carries out the contact pressure, not directly on the conductor, but on a notched bridge which ensures a good contact on the conductor, will be used. The pressing screws will have a firm locking device and the area entering the clip will be protected from touching, so that no live metal part is exposed. For the single-core conductors with a cross section higher than 6 mm 2 and multi-core conductors with a cross section higher than 16mm 2, the terminals will be provided with bolts; the bolts will be blocked so as not to allow rotation. For this type of terminals, the conductors will have terminal ends provided with thimbles (connectors) fixed by crimping. For each cabinet, a terminal strip will be provided separately for the control system interface. The terminal strips will be thus executed so as to allow easy access to the terminals. They will be protected against direct touching. At least one terminal will be left free between the circuits with different polarities. The terminals will allow the connection of some testing devices without having to interrupt the circuit. A 2% reserve of line clips will be provided for each line of clips. S7.3 Technical requirements for the equipment of DC auxiliary services installation S7.3.1 Generalities All continuous current consumers related to the 11 kv and 3 kv substations as well as of the power transformer will be supplied from a stationary, sealed battery, without maintenance and gas emission. The battery will provide for a period of 3 hours (in case of failure of.4 kv network) the permanent consumption of the control installation - protection, telecommunications and emergency lighting, and at the end of this period it will provide the consumption necessary to simultaneously activate the 11 kv circuit breaker and 5 of 3 kv circuit breakers, followed by their successive switching in. At the end of this regime, the battery s voltage must not fall below 1.8 V / element. The DC installation diagram is with simple bus-bar. The continuous current consumers will be radially supplied. The battery will operate in "floating" conditions with an automatic voltage stabilization and current limitation rectifier. If necessary, the Contractor will be able to resize the continuous current auxiliary services equipment, in accordance with the consumptions of the delivered equipment, but by observing the solution and the operating condition described above.

11 S7/12 S7.3.2 Battery a) The Contractor will deliver a stationary acid battery for the 11/3 kv substation. The battery must provide the entire continuous current consumption of the respective installation in case of decommissioning of the rectifiers. The bidder shall submit the selection and verification calculations for the rectifiers and battery once with the bidding. b) The technical requirements of this paragraph are additional to the technical requirements outlined in the Technical Data Sheets - Table C. Type The battery will be with acid and Pb-Ca alloy plates, waterproof constructed, without gas emission and maintenance free. The entire quantity of electrolyte will be immobilized in gel. The battery must withstand the entire substation DC consumption for at least 3 hours. The casual charging of the battery (after a 3 hour discharging) will be done automatically. The duration of this charging will be determined taking into account that the maximum casual load voltage will be 2.3 V/element. Constructive characteristics The tank of each battery element will be fitted with a safety valve. The battery s elements will be arranged in multi-level racks, in an anti-seismic assembling. The racks will be made of steel profiles covered with an insulating and protective layer resistant to acid and will be provided with electric insulating spacers both between the racks and elements and between the racks and the floor. The racks will be mounted at minimum 15 mm above the floor, by support elements which are to be attached with bolts in the concrete floor. The connections between the elements will be protected and insulated in order to protect the operating personnel against touching the live parts. The connection between each battery and the corresponding supply and distribution cabinet will be achieved by 2 insulated cables (one for each polarity). Limit of supply The limit of the bidding complies with the specification list for the equipment - Table B. Each battery will be delivered in a functional anti-seismic assembly with: - supporting structures (racks) - the bolts for their fastening in the floor - a complete set of accessories for the battery s installation, connection and operation consisting of:

12 S7/13 connections between the battery s elements; cable insulating elements and their associated output terminals. S7.3.3 Rectifier a) The Contractor shall deliver an automatic rectifier for the "floating" operation with the battery. The rectifiers must provide the battery s charging in floating or occasional condition (permanent) and, at the same time, the supply all DC permanent consumers. The rectifier should have the ability to take over the entire continuous current consumption corresponding to the substation. b) The technical requirements of this paragraph are additional to the technical requirements outlined in the Technical Data Sheets - Table C. Type Automatic rectifier with automatic stabilization of the output voltage within the limits of ±1%, regardless of AC supply voltage variation and dual current limiting (of total current and the battery charging current). Constructive characteristics Design data a) Supply voltage rating 3 x 4 V, 5 Hz. The alternating voltage may contain transitional waves and impulses due to switching, or abnormal conditions. The rectifier must block these waves and impulses at the AC input with limiting filters. The rectified voltage will be filtered in order to reduce the ripple in DC below 2 V (1% Un); this value also corresponds to the case when the battery is disconnected. b) On the DC side, the rectifier must provide: - battery charging voltage in a normal operating condition (floating) - battery charging voltage in an occasional operating condition - consumers supply: * in continuous operating condition, the rectifier must provide the load related to the permanent consumers and the battery charging current; * the rectifier must provide the full recharge of the battery, after each maximum 3 h discharge, switching automatically to occasional charging. Construction: The rectifier will be fully automated, providing the output voltage adjustment and stabilization,

13 S7/14 compensating the supply voltage variations and the output current limiting in all operating conditions. The rectifier will be designed to be integrated into a telecontrol system and fitted with monitoring and measurement systems. The ventilation of the rectifier cabinet will be through natural convection. On the output (DC side) diodes will be provided for avoiding the battery discharging on the rectifier in case of failure of the AC power supply network. Protection devices such as automatic switches or wire fuses will be provided, with the necessary short-circuit and overload dimensioned protection. The rectifier will allow to choose the loading condition and adjust the charging parameters in floating or occasional condition. For the occasional charging of the battery, a timer will be provided with manual adjustment possibility, and at the end of this period the system must automatically return to its normal charging condition. For remote supervisory the rectifier will have the necessary facilities; minimum remote signaling with potential free contacts or ma signal for: - DC and AC current - DC and AC voltage - earthing in DC network; - rectifier s failure; - minimum and maximum DC voltage; - alternating voltage failure; - alarms at: * minimum voltage; * common alarms; * no supply voltage (AC side) * maximum voltage; * earthing Limit of supply The limit of the bidding complies with the specification list for the equipment - Table B3. The rectifier will be supplied with all necessary accessories.

14 S7/15 S7.4 Technical requirements for the equipment of AC auxiliary services installation S7.4.1 Generalities The supply voltage rating of the alternating current consumers is 3 x 23 / 4 V, 5 Hz. The installation will operate with the neutral connected directly to earth. The alternating current auxiliary services installations will ensure the consumption related to the final profile (including the spares) of the 11/3 kv substation. The supply of the.4 kv alternating current auxiliary services installation will be made out of two distinct sources: - the auxiliary services transformer - the emergency generating set (Diesel unit) The power supply diagram is with simple bus-bar. The AC consumers will be radially supplied. The alternating current auxiliary services installation will be provided with an automate switching to the emergency source. If necessary, the Contractor will resize the alternating current auxiliary services equipment in accordance with the consumptions of the delivered equipment but by observing the solution and the operating condition described above. The Contractor must submit the dimensioning calculations for the proposed auxiliary services equipment. S7.4.2 Power transformer a) The Contractor must deliver the power transformer, dry type, for the alternating current auxiliary services supply of the 11/3 kv substation. b) The technical requirements of this paragraph are additional to the technical requirements outlined in the Technical Data Sheets - Table C. Type Power three-phased transformers, with dry insulation and natural circulation cooling have been provided for the supply of the AC auxiliary services installations. The transformer will be mounted in the designated room. The core, arranged in three columns, will be made of siliceous steel sheets with oriented silicon crystals, cold lamination, and inorganic insulation on both sides. The coiling will be made of copper conductors with F class insulation according to IEC 685 with superior dielectric characteristics, low aging, fireproof, resistant to flame propagation (selfextinguishing). The tap changer will be connected to the HV winding inlets and intended for the change of the

15 S7/16 ratio of conversion in the load absence. The stiffening framing of the magnetic core and the basic frame will be made of steel, in a robust construction, in order to withstand the mechanical stress under operating and transporting condition. The metallic parts will have surface coatings for anti-corrosion protection. The LV winding neutral will be accessible to the terminals and will be dimensioned to the value of phase current. The MV connection at the transformer s terminals will be executed by insulated cable. The terminals will allow the cables connection in a completely isolated solution (plug-in). The temperature will be monitored by the sensors installed in the windings. The temperature will be remote monitored. The transformer will have reduced no-load losses, with the tolerances specified by IEC 676. The transformer must be able to withstand temporary overload according to IEC without damaging the windings, insulation, tap changer, insulated bushings, etc.. The transformer should withstand the short-circuit current under the conditions specified by IEC Limit of supply The transformer will be provided with at least the following items: - connection box for secondary circuits - HV and LV insulated bushings - earthing terminals (2 pieces) - nameplate - lifting eye - wheels - other accessories according to IEC 676. S7.4.3 Technical requirements for emergency generating set (Diesel Unit) a) The Contractor will ensure the delivery of a three-phased power Diesel unit, with automatic start as a source of backup power b) The technical requirements of this paragraph are additional to the technical requirements outlined in the Technical Data Sheets - Table C. Type Three-phased power unit, with automatic start, equipped with fuel supply system, with air compensator and intake pipes, pipes and acoustic absorbent silencer for the outside exhaust

16 S7/17 of gas and power-operated louver system for air intake and exhaust. The power unit together with the annexes will be indoor in a special designated room. The power unit and the annexes must form a functional installed and factory tested unit. Constructive characteristics The power unit will be constructed as a complete installation, where the engine and the generator are mounted on a common frame. The power unit will operate individually, being automatically activated, upon the loss of voltage on the AC bus-bars and will reach its maximum load within max. 15 sec. from receiving the start command. When the voltage returns in the network, the unit will stop automatically. The manual control of the unit is also provided for testing. The fuel supply is made from its own fuel tank (day). For the expansion of the power unit range, a storage tank will be installed in the same room. The transfer of fuel from the storage tank to the day tank will be automatically done. The group will be self-ventilated, with the engine s fan directly driven by the motor, with the exhaust of the entire quantity of heat given off by the unit during its operation. The generator will have no brushes, being provided with built-in automatic voltage regulator. The generator s voltage will be of 3~23/4 Vac, with the neutral accessible at the terminal box. The equipment will provide all the necessary functions by: - Diesel engine s preheating installation; - start battery charging rectifier; - fuel tank filling pump; - engine for the activation of air inlet and outlet louvers; - electric pump for pre-lubrication of Diesel engine; - automatic three-pole switch for the connection / disconnection of the generator within the circuit; - starter; - selection of the operating condition, with remote, local or testing control; - automatic/manual start of Diesel engine; - automatic/manual stop of Diesel engine; - control of normal operation of pre-lubrication, preheating and rectifier; - oil level control - control of generator s electrical parameters (voltage, frequency, intensity)

17 S7/18 - control of Diesel engine parameters (oil pressure, speed, oil temperature, water temperature); - generator s protection against external short-circuit, overcharge, overheating of Diesel engine; - coupling / uncoupling of the main switch; - the blocking in three failed attempts of start at the remote control, the release being made by hand; - distance transmission (in the control room) and triggering of the alarm signals. At least the following signals must be transmitted: - Diesel unit failure; - minimum 1% fuel level - day tank; - minimum 1% fuel level - external tank - rectifier s failure / start battery s minimum voltage; - operational Diesel unit: distance transmission (in the control room) of the values of the frequency and output current, voltage; local signaling of all operating parameters; alternator protection device; maximum voltage protection; reverse power protection; saturation protection. The Diesel engine will be equipped with a battery, without maintenance, for its startup. The rectifier for charging the battery will be an automatic rectifier supplied to the voltage of 23 V, 5 Hz. In order to ensure the start-up and operation of the Diesel engine, the unit will be equipped with a pre-lubrication, pre-heating, starting, air supply, fuel supply, cooling, ventilation, and gas exhaust installation. Its fuel tank (day) will have double walls and should provide the necessary amount of fuel to operate at least 8 hours. In order to fill the tank from an external tank, an electric pump (included in the scope of supply) will be used. The Diesel unit will stop automatically when the achieved values are more dangerous than the level at which the alarm signal has been reached. The unit must be equipped with an engine fuel supply stop system in case of fire detection. The power unit must be maintained in an "able for intervention" condition.

18 S7/19 The consumables deemed as necessary for the warranty period will be delivered together with the power unit. Limit of the bidding. The limit of the bidding complies with the specification list for the equipment - Table B. The unit will be delivered with the necessary accessories, at least those listed below: - electric pump for filling the tank; - own fuel tank and connecting pipes; - start battery and rectifier; - ventilation system for air intake and exhaust (flexible tube and wall grids) and electrically operated louvers; - fully equipped automation cabinet and power cables and secondary circuits between the unit and the cabinet; - accessories for fixing the unit on the concrete foundation. S7.5 Technical requirements for the DC and AC auxiliary services cabinets In order to build the LV cabinets, it must be met the execution and operation requirements of the auxiliary services installation and the following general conditions: - the steel sheet used for the construction of cabinets will be 1.5 mm thick; - the minimum enclosure (according to IEC 6529) of the cabinets will be IP42; - the cubicles will be provided with front windowed door and, if necessary, two back doors; - the window s size will be big enough in order to allow the outdoor visibility, even with the door closed, of the position or status of the equipment inside the cabinet; - the cabinets will be equipped with dismountable steel doors, which are air-tight closed and locked, fixed in the hinges so that they can be open at 15 º; - the cabinets will be equipped with vertical supports and horizontal supports for fixing the devices with front connections; - the metal (horizontal and vertical) clamps for mounting the equipment inside each cabinet will be galvanized and will ensure the continuity of the equipotential connections inside the cabinet; - the upper section of each cabinet will be designated for mounting the bus-bars; - each cabinet will be equipped indoors with the following: lamp (lamps) for lighting mounted in the upper part, controlled by the door position mini-

19 S7/2 switches, supplied in 23 Vac; a 23 Vac socket with a safety contact; a thermostatic-operated anti-condensation resistance. - each cabinet must be naturally ventilated; - the cabinets should allow their installation on the concrete floor; - in the bottom part, the cubicles will be provided with dismountable metal plates for cable entry; - the interior equipment and the terminal strips should be easily accessible, without affecting the neighboring equipment; - the interior wiring should be protected from mechanical damage by trough; - the minimum section of the interior secondary connections will be 2.5 mm²; the selection of the cross section of the conductor for internal connections from the bus-bar to the device and from it to the line of clips will be made in accordance with the applicable regulations, depending on the load of the circuit, the used protection device and the laying conditions; - the internal connection color codes will be: black feeders. blue signal circuits. red measuring circuits yellow-green AC neutral and protection neutral - all internal connections will be made with flexible multi-core conductors for fixed installations; - all cabinets will be delivered completely equipped and wired; - each cabinet will be properly labeled so as to allow an easy identification, both with the access door closed and open; - each indoor installed device must be properly labeled in accordance with the wiring diagram, so as to be easily identified either in front of the cabinet or from the connections (back of the cabinet or back of reversible frames); - the cabinets will be provided with fences for the protection against electrocution in the area of the bus-bars and the area of the danger of electric shock circuits, being labeled with warning inscriptions. Also, warning inscriptions will be placed on the front and back doors. - all cubicles will be corrosion protected by their electrostatic painting;

20 S7/21 - each cabinet must allow a smooth connection of the metal construction to the main earthing switch through special terminals equipped with screws; - in the bottom part, each cubicle will be provided with a copper bus-bar for the earthing, to which all devices and lines of clips provided in the cabinet will be electrically connected; - the external connection cables will be protected when passing through the lower metal plate of the cabinet by cable glands included in the scope of supply; - each cabinet will be equipped with envelope-type pocket for plans. S7.6 Tests for DC and AC auxiliary services equipment a) The type tests should be performed in an independent laboratory or if they are carried out in the laboratory of the manufacturer they will be performed in the presence of a neutral witness or confirmed by an established laboratory. b) The Contractor must provide the test results in accordance with the latest edition of IEC. c) The Contractor must submit the reports for the type tests performed for each type of equipment once with the technical documentation according to Table E. d) The Contracting Authority will decide whether it participates or not in individual tests. Battery a) Type and routine tests will be carried out in accordance with IEC , 22, BS 629, BS 6334 or DIN Type tests: - Verification of materials - Verification of the size and mass - Verification of voltage rating - Verification of rated capacity - Verification of loading - unloading cycle endurance - Verification of constant voltage endurance - Verification of loading conservation - Determination of short circuit current and internal resistance - Determination of the mechanical stress endurance - Determination of endurance in short-circuit conditions - Determination of terminal tightness

21 S7/22 Routine tests: - Verification of materials - Verification of size and mass - Verification of voltage rating - Verification of rated capacity b) For routine tests, the representatives will select a number of 12 elements from each battery to be tested. c) The acceptance tests should be performed according to IEC Rectifier At least the following tests will be performed in accordance with IEC : Type tests: - Insulation resistance measurement - Operating test, including no-load operation, earthing the DC pole, terminal short-circuit - Ampere rating loading test - Verification of measuring and signaling devices - Protection devices test - Heating Test Routine tests: - Insulation resistance measurement - Operating test - Verification of measuring and signaling devices - Protection devices test The acceptance tests will be performed in accordance with IEC Power transformer The test will be performed according to IEC 676 and shall include: a). Routine tests: - verification of the conversion ratio and the group of connections - Measurement of no-load losses and load current - Measurement of the short-circuit impedance and losses - Measurement of winding resistance - Insulation resistance measurement - Routine dielectric tests according to IEC 676-3

22 S7/23 b). Type tests: - Routine tests - Heating test (IEC 676-2) - Type dielectric tests (IEC 676-3). Diesel Unit At least the following tests will be performed: - Visual check - Inspection of mechanical unit - verification of connections continuity - functional tests for the power and automation cabinet and annexes, preheating, rectifier, louvers, fuel transfer pump - Operating under load test - Operational tests including tests in: Overload, 8% load step (from no-load) Surge Over-saturation Reverse power Over-temperature Short-circuit protection. The acceptance tests will be performed in accordance with the applicable ISO and IEC standards. DC/AC services boards Individual and type tests will be carried out for the LV component of the cabinets according to applicable IEC standards. The acceptance tests of cabinets and block terminals will be performed in accordance with IEC The required commissioning tests will be indicated by the contractor in Table D for each part of offered equipment. S7.7 TECHNICAL DATA SHEETS

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

045 : 2000 CEB STANDARD

045 : 2000 CEB STANDARD 045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This

More information

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers

More information

SPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W

SPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W Page 1 / 7 Full operation without need of battery Two independent 48Vdc outputs for switching and control Local monitoring with 8 LEDs Remote monitoring with 4 alarm relays Monitoring and configuration

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

.3 Section Waste Management and Disposal.

.3 Section Waste Management and Disposal. Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP United Nations Development Programme Recovery and Crisis Prevention برنامج األمم المتحدة اإلنمائي Iraq Technical Specification for Supply, installation and commissioning of Diesel Generators for UNDP February

More information

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS) About company The «Elektroapparat» plant starts its operation in 1922 as a plant manufacturing high-voltage electrical equipment. During the first two

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

N Daily Weekly Monthly Every 3 months. Every 6 months 1 Remove any materials not related

N Daily Weekly Monthly Every 3 months. Every 6 months 1 Remove any materials not related MV / LV cabins maintenance The operation and maintenance of the cabins are meant to ensure high reliability (i.e. the early detection of anomalies, the failure prevention and monitoring functional) and

More information

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:

More information

شركة كهرباء محافظة القدس المساهمة المحدودة

شركة كهرباء محافظة القدس المساهمة المحدودة Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories

More information

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants World Class Power Solutions Rectifiers For Stationary Battery Systems in Nuclear Power Plants General 2 1.1 Application Electronically controlled rectifier assemblies are used in conjunction with suitable

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60470 Second edition 1999-10 High-voltage alternating current contactors and contactor-based motor-starters Contacteurs pour courants alternatifs haute tension et démarreurs

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting

More information

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Issue 3 2012 SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) www.energynetworks.org 2012 Energy Networks

More information

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1

More information

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

with Vacuum Circuit Breaker HAF

with Vacuum Circuit Breaker HAF M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better

More information

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Modular Standardized Electrical and Control Solutions for Fast Track Projects Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

8DJ. Maintenance-free for lifetime

8DJ. Maintenance-free for lifetime 8DJ Maintenance-free for lifetime Energy Distribution Welcome! Page 2 October 1 st 2008 8DJ Main Applications for Medium-Voltage Switchgear Power generation Power stations G Power transmission High and

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Key features. DESIGNS: - Conservator type - Hermetically sealed

Key features. DESIGNS: - Conservator type - Hermetically sealed Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the

More information

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

GENERAL SPECIFICATION ELECTRICAL

GENERAL SPECIFICATION ELECTRICAL GENERAL SPECIFICATION ELECTRICAL GS ELE 152 AC Uninterruptible Power Systems (UPS) 02 09/03 Change of Group name and logo 01 10/02 Updated 00 03/01 First issue Rev. Date Notes GS ELE 152.doc Contents 1.

More information

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system. MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham

More information

CAST RESIN TRANSFORMERS CRT ED.: DEC.13 REV.00

CAST RESIN TRANSFORMERS CRT ED.: DEC.13 REV.00 CAST RESIN TRANSFORMERS CRT ED.: DEC.13 REV.00 1 HISTORY INESING SRL is a dynamic and modern company, very well known in the design and production of dry type (cast resin ) transformer up to 36kV -10MVA,

More information

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy. Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings

More information

AIR COOLED RECTIFIER SPECIFICATION S-50-A

AIR COOLED RECTIFIER SPECIFICATION S-50-A SPECIFICATIONS AIR COOLED RECTIFIER Spec50a1 5JAN1999 SPECIFICATION S-50-A HIGH VOLTAGE SINGLE TRANSFORMER AIR COOLED RECTIFIER Standard output power range: 250 to 600 volts at 100 to 1,200 amperes TECHNICAL

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

Uninterruptible power supply Supply MEg101.4

Uninterruptible power supply Supply MEg101.4 Uninterruptible power supply Supply MEg101.4 MEgA Měřící Energetické Aparáty, a.s. 664 31 Česká 390 Czech Republic Uninterruptible power supply Supply MEg101.4 Uninterruptible power supply MEg101.4 1/

More information

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION Electrical Energy Storage Tester EEST-511-S Semi-Automatic Charge-Discharge Battery Bench 1 channel 50 V / 100A (Ni-CD, Pb, Ni-Mh, Li-ion...) TECHNICAL DESCRIPTION To buy, sell, rent or trade-in this product

More information

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3 TITLE SPECIFICATION FOR MEDIUM VOLTAGE DATE: FEBRUARY 2015 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD... 2 INTRODUCTION... 3 1 SCOPE... 3 2 NORMATIVE S... 3 3 DEFINITIONS AND ABBIATIONS... 3 4 REQUIREMENTS...

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS INTER PLANT STANDARD STEEL INDUSTRY SOFT STARTER FOR VOLTAGE UP TO 690 V AC IPSS: 1-10-040-15 IPSS NO CORRESPONDING IS 0. FOREWORD 0.1 This interplant standard has been prepared by the Standard Committee

More information

INSTALLATION MANUAL. Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules

INSTALLATION MANUAL. Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules INSTALLATION MANUAL Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules ING TABLE OF CONTENTS 1. General information 2 1.1 Standards

More information

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual

More information

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV.CAPACITOR BANK 1.0 SCOPE: This specification covers

More information

Gas Insulated Metal-clad Switchgear, HMGS!

Gas Insulated Metal-clad Switchgear, HMGS! Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Distribution transformers Efficiency over life-cycle

Distribution transformers Efficiency over life-cycle Distribution transformers Efficiency over life-cycle ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting

More information

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations 1 IEEE1818-2017 Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations Sponsored by the IEEE Substations Committee Presented By Joe Gravelle Organization of the Guide 1. Scope

More information

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist

INTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist INTER PLANT STANDARD - STEEL INDUSTRY IPSS THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS Corresponding IS does not exist IPSS: 1-10-038-08 0 FOREWORD 0.1 This Inter Plant Standard has

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out) TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power

More information

SUBSTATION EQUIPMENT - Page 1 of 8

SUBSTATION EQUIPMENT - Page 1 of 8 BATTERY BANKS 1. GENERAL: JEA utilizes a 125 volt DC system for the control and operation of its transmission and distribution substations. JEA has standardized on lead acid type battery banks to supply

More information

Excitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR.

Excitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR. Turbo - Generator Type: QF Series 1. General The generator is a two pole, cylindrical rotor type synchronous machine, directly coupled with steam turbine. It has a closed-circuit cooling system to cool

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st Dry-type transformers Innovative Technology Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st 2014 Dry-type transformers Innovative Technology What is a dry transformer? ABB manufactures a transformer which does

More information

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW) Product datasheet Characteristics ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/400...440V(45kW) Complementary Assembly style Function available Supply voltage limits Main Range of product

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Dycon D2430 EN54-4 Fire Alarm Power Supply Series Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product

More information

Section V DC Nickel Cadmium Alkaline BATTERY

Section V DC Nickel Cadmium Alkaline BATTERY Section - 7 TECHNICAL SPECIFICATION OF 110V DC Nickel Cadmium Alkaline BATTERY TECHNICAL SPECIFICATIONS & REQUIREMENTS OF 110V DC Nickel Cadmium Alkaline Battery 7. 1 GENERAL This section of the document

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised

More information

Menu. Home About this portal Latest updates. Print Save Resource detail Citations. Table of Contents

Menu. Home About this portal Latest updates. Print Save  Resource detail Citations. Table of Contents Menu Home About this portal Latest updates Print Save Email Resource detail Citations AS/NZS 60898.1:2004 Electrical accessories - Circuit-breakers for overcurrent protection for household and similar

More information

32-SDMS-03 SPECIFICATIONS FOR

32-SDMS-03 SPECIFICATIONS FOR SPECIFICATIONS FOR EXTENSIBLE SF6 INSULATED RING MAIN UNIT, 17.5 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS PAGE 1.0 SCOPE 3 2.0 CROSS REFERENCES

More information

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines.

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines. 1 PAPER 4 Sample Questions - C&G 2382 17th Edition full paper D 1 o/c 1 - A recommendation for the interval to the first periodic inspection shall be made by: a the installation electrician. b the main

More information

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information