Technical Services Report

Size: px
Start display at page:

Download "Technical Services Report"

Transcription

1 SATRA Technology Centre Ltd Wyndham Way, Telford Way Industrial Estate Kettering, Northamptonshire NN16 8SD United Kingdom Tel: +44 (0) Fax +44 (0) Firm: Unit 6, Yarrow Business Centre Yarrow Road CHORLEY PR6 0LP For the attention of: Mr T McMahon Technical Subject: TESTING OF DEADWEIGHT ANCHOR IN ACCORDANCE WITH Firm: Our ref: Date: 2 February 2010 (Originally issued 20 February 2008) Conditions of Issue: This report may be forwarded to other parties concerned provided that it is not abbreviated or changed in any way. It must not be published, for example by including it in advertisements, without the prior, written permission of SATRA. Results given in this report refer only to the samples submitted for analysis and tested by SATRA. Comments are for guidance only and are not part of the reported results. All comments and interpretations are outside the scope of UKAS accreditation and are based on current SATRA knowledge. A satisfactory test report in no way implies that the product tested is approved by SATRA and no warranty is given as to the performance of the product tested. SATRA shall not be liable for any subsequent loss or damage incurred by the client as a result of information supplied in the report. Except where stated, an uncertainty has been applied to the results within this report, based on a standard uncertainty multiplied by a coverage factor k = 2, providing for a confidence level of approximately 95% Tests marked are not UKAS accredited. SATRA Technology Centre Ltd. A subsidiary of SATRA. Registered in England No Notified Body for testing and certification of PPE Reference No (Page 1 of 4)

2 INTRODUCTION Samples of deadweight anchor devices, in 6-point & 8-point types, were received by SATRA on 19 February 2008, for testing in accordance with for a class E device. Testing was carried out on 19 February 2008, in the presence of Mr Tony McMahon & Mr Andy McMahon of. CONCLUSIONS The samples of deadweight anchor devices, as received by SATRA on 19 February 2008, have been tested in accordance with for a class E device, and found to achieve the following requirements: SAMPLE / STANDARD REFERENCE (6-point) Asphalt roof surface Dynamic performance (6-point) Paving slabs roof surface Dynamic performance (6-point) Bitumen roof surface Dynamic performance (6-point) Stone chippings roof Dynamic performance surface 2 February 2010 (Page 2 of 4) Safety Product Centre

3 TEST RESULTS 4.2 General requirements for anchor devices REQUIREMENT Anchor device must accept the personal protective equipment and ensure that it is not possible for correctly connected personal protective equipment to become detached unintentionally RESULT / COMMENT Personal protective equipment attached to deadweight anchor device via closed loop on top of centre piece, thus detachment dependant on personal protective equipment only / Elements cannot appear to be correctly assembled without being positively locked together Incorrect assembly would be immediately obvious upon inspection Exposed edges or corners shall be relieved either with a radius of at least 0.5 mm or a 45º chamfer No rough or sharp edges in potential contact with user Dynamic performance All metallic parts shall comply with 4.4 of EN 362: 1992 corrosion protection When tested with a rigid steel mass of 100 kg, the test mass shall be arrested Not Roof type: Asphalt (wetted at Not Displacement, L, of the centre of mass of the deadweight anchor device shall not exceed 1 m Displacement, H, of the 100 kg mass shall not exceed 1 m after 3 minutes L = 0.95 m H = 0.95 m Roof type: Paving slabs (wetted at L = 0.36 m H = 0.39 m 2 February 2010 (Page 3 of 4) Safety Product Centre

4 4.3.5 Dynamic performance REQUIREMENT When tested with a rigid steel mass of 100 kg, the test mass shall be arrested RESULT / COMMENT Roof type: Bitumen (wetted at / Displacement, L, of the centre of mass of the deadweight anchor device shall not exceed 1 m Displacement, H, of the 100 kg mass shall not exceed 1 m after 3 minutes L = 0.35 m H = 0.41 m Roof type: Stone chippings (wetted at L = 0.86 m H = 0.89 m Figure 1 6-point deadweight anchor on stone chippings roof surface * * * * * * * * * * * * * * * * END OF REPORT * * * * * * * * * * * * * * * * 2 February 2010 (Page 4 of 4) Safety Product Centre

5 SATRA Technology Centre Ltd Wyndham Way, Telford Way Industrial Estate Kettering, Northamptonshire NN16 8SD United Kingdom Tel: +44 (0) Fax +44 (0) Firm: Unit 6, Yarrow Business Centre Yarrow Road CHORLEY PR6 0LP For the attention of: Mr T McMahon Technical Subject: TESTING OF DEADWEIGHT ANCHOR IN ACCORDANCE WITH Firm: Our ref: Date: 2 February 2010 (Originally issued 20 February 2008) Conditions of Issue: This report may be forwarded to other parties concerned provided that it is not abbreviated or changed in any way. It must not be published, for example by including it in advertisements, without the prior, written permission of SATRA. Results given in this report refer only to the samples submitted for analysis and tested by SATRA. Comments are for guidance only and are not part of the reported results. All comments and interpretations are outside the scope of UKAS accreditation and are based on current SATRA knowledge. A satisfactory test report in no way implies that the product tested is approved by SATRA and no warranty is given as to the performance of the product tested. SATRA shall not be liable for any subsequent loss or damage incurred by the client as a result of information supplied in the report. Except where stated, an uncertainty has been applied to the results within this report, based on a standard uncertainty multiplied by a coverage factor k = 2, providing for a confidence level of approximately 95% Tests marked are not UKAS accredited. SATRA Technology Centre Ltd. A subsidiary of SATRA. Registered in England No Notified Body for testing and certification of PPE Reference No (Page 1 of 4)

6 INTRODUCTION Samples of deadweight anchor devices, in 6-point & 8-point types, were received by SATRA on 19 February 2008, for testing in accordance with for a class E device. Testing was carried out on 19 February 2008, in the presence of Mr Tony McMahon & Mr Andy McMahon of. CONCLUSIONS The samples of deadweight anchor devices, as received by SATRA on 19 February 2008, have been tested in accordance with for a class E device, and found to achieve the following requirements: SAMPLE / STANDARD REFERENCE (6-point) Asphalt roof surface Dynamic performance (6-point) Paving slabs roof surface Dynamic performance (6-point) Bitumen roof surface Dynamic performance (6-point) Stone chippings roof Dynamic performance surface 2 February 2010 (Page 2 of 4) Safety Product Centre

7 TEST RESULTS 4.2 General requirements for anchor devices REQUIREMENT Anchor device must accept the personal protective equipment and ensure that it is not possible for correctly connected personal protective equipment to become detached unintentionally RESULT / COMMENT Personal protective equipment attached to deadweight anchor device via closed loop on top of centre piece, thus detachment dependant on personal protective equipment only / Elements cannot appear to be correctly assembled without being positively locked together Incorrect assembly would be immediately obvious upon inspection Exposed edges or corners shall be relieved either with a radius of at least 0.5 mm or a 45º chamfer No rough or sharp edges in potential contact with user Dynamic performance All metallic parts shall comply with 4.4 of EN 362: 1992 corrosion protection When tested with a rigid steel mass of 100 kg, the test mass shall be arrested Not Roof type: Asphalt (wetted at Not Displacement, L, of the centre of mass of the deadweight anchor device shall not exceed 1 m Displacement, H, of the 100 kg mass shall not exceed 1 m after 3 minutes L = 0.95 m H = 0.95 m Roof type: Paving slabs (wetted at L = 0.36 m H = 0.39 m 2 February 2010 (Page 3 of 4) Safety Product Centre

8 4.3.5 Dynamic performance REQUIREMENT When tested with a rigid steel mass of 100 kg, the test mass shall be arrested RESULT / COMMENT Roof type: Bitumen (wetted at / Displacement, L, of the centre of mass of the deadweight anchor device shall not exceed 1 m Displacement, H, of the 100 kg mass shall not exceed 1 m after 3 minutes L = 0.35 m H = 0.41 m Roof type: Stone chippings (wetted at L = 0.86 m H = 0.89 m Figure 1 6-point deadweight anchor on stone chippings roof surface * * * * * * * * * * * * * * * * END OF REPORT * * * * * * * * * * * * * * * * 2 February 2010 (Page 4 of 4) Safety Product Centre

EN 1154:1997 / A1:2002

EN 1154:1997 / A1:2002 Exova Warringtonapt Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com EN 1154:1997 / A1:2002

More information

BS EN :2011 BS :2002+A1:2013 UKSRG Guidelines-4:2011 EN124:1994 HA104\09

BS EN :2011 BS :2002+A1:2013 UKSRG Guidelines-4:2011 EN124:1994 HA104\09 PendulumTest(s) carried out in accordance with: BS EN 13036-4:2011 BS 7976-2:2002+A1:2013 UKSRG Guidelines-4:2011 EN124:1994 HA104\09 On behalf of: Fibrelite Limited. Prepared by: Phil Nolan GET-A-GRIP!

More information

Calibration Laboratory Assessment Service CLAS Certificate Number Page 1 of 5

Calibration Laboratory Assessment Service CLAS Certificate Number Page 1 of 5 National Research Council Conseil national de recherches Canada Canada Measurement Standards and Science Science des mesures et étalons Calibration Laboratory Assessment Service CLAS Certificate Number

More information

BS EN :2006. Windows and doors Product standard, performance characteristics. A Report To: Mila Hardware Ltd. Document Reference:

BS EN :2006. Windows and doors Product standard, performance characteristics. A Report To: Mila Hardware Ltd. Document Reference: Exova Warringtonapt Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com BS EN 14351-1:2006 Test

More information

Test Summary. Handling Tests on AlloyGator OE Alloy Wheel Rim Protectors

Test Summary. Handling Tests on AlloyGator OE Alloy Wheel Rim Protectors Test Summary 1210410#1a Customer: Authority: Curt Rathbone 61 Heming Road Washford Industrial Estate Redditch Worcestershire B98 0EA United Kingdom curt@alloygator.com Pro Forma Invoice SLIV/00085346 HORIBA

More information

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems

More information

CPM Technical Guide / Load Configuration. Safety for Life

CPM Technical Guide / Load Configuration. Safety for Life CPM Technical Guide / Load Configuration Safety for Life Technical Summary Please Note: The following information is purely for the customer to understand how CPM products can be loaded or unloaded safely

More information

United Kingdom Civil Aviation Authority. Specification No. 1. Issue: 6. Date: 12 March Safety Belts ISBN

United Kingdom Civil Aviation Authority. Specification No. 1. Issue: 6. Date: 12 March Safety Belts ISBN ISBN 1 904862 65 9 Specification No. 1 United Kingdom Civil Aviation Authority Issue: 6 Date: 12 March 2004 Safety Belts 1 Introduction 1.1 Although this Specification was written originally for aeroplanes,

More information

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c.

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c. 56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM Email: testing@inspec-international.com Website: www.inspec-international.com Tel: +44 (0) 16 17 37 06 99 Fax: +44 (0) 16 17 36 01 01

More information

Restriction of the use of certain hazardous substances (RoHS) Summary Report

Restriction of the use of certain hazardous substances (RoHS) Summary Report JJ Electronic S.R.O A. Hlinku 4 022 01 Čadca Slovak Republic Restriction of the use of certain hazardous substances (RoHS) Summary Report Test of: Vacuum Tube Model Number: EL34 Unique Identifier: None

More information

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist.

Testing of Baier Plasterboard to AS/NZS (Electronic copy (PDF format) original signed by author) Materials Scientist. DC1333 Testing of aier Plasterboard to AS/NZS 2588 (Electronic copy (PDF format) original signed by author) Author: Neil Lee Materials Scientist Reviewer: ryan Keen Senior Technician Contact: RANZ Limited

More information

Technical Information

Technical Information Subject Application of "Approved Method" to existing diesel engines under the provisions of Revised MARPOL ANNEX VI - Certification of an Approved Method for WÄRTSILÄ RTA engines - To whom it may concern

More information

TEST REPORT N

TEST REPORT N centro ricerche-sviluppo Date received: 05-10-10 Date of issue: 25-11-10 Report consists of 10 attached sheets. Defects before testing: one Sample name: SHIY 121264 Overall dimensions: 750 x 750 x 1060

More information

PETROLEUM MEASUREMENT MANUAL THE PERFORMANCE OF TURBINE METERS IN LOADING GANTRIES - A REVIEW OF PROVING AND TEST DATA

PETROLEUM MEASUREMENT MANUAL THE PERFORMANCE OF TURBINE METERS IN LOADING GANTRIES - A REVIEW OF PROVING AND TEST DATA THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL THE PERFORMANCE OF TURBINE METERS IN LOADING GANTRIES - A REVIEW OF PROVING AND TEST DATA Petroleum Measurement Paper No. 9 THE INSTITUTE OF PETROLEUM

More information

CPM Technical Guide / Load Configuration. Load configuration for customers. Concrete Safety for Life

CPM Technical Guide / Load Configuration. Load configuration for customers. Concrete Safety for Life CPM Technical Guide / Load Configuration Load configuration for customers Concrete Safety for Life Technical Summary In order to assist our customers in their preparation for off-loading our products from

More information

Verplas Self-Seal Coupling Leakage Test. Prepared for : Verplas Limited. 25 February Test report number Page 1 of 11

Verplas Self-Seal Coupling Leakage Test. Prepared for : Verplas Limited. 25 February Test report number Page 1 of 11 Verplas Self-Seal Coupling Leakage Test Prepared for : Verplas Limited 25 February 2013 Page 1 of 11 Prepared by Name M Swainson Position Principal Engineer Date 25 th February 2013 Signature Approved

More information

WP2 - CFD Private Network Meter Commissioning, Proving and Calibration Tests

WP2 - CFD Private Network Meter Commissioning, Proving and Calibration Tests WP2 - CFD Private Network Meter Commissioning, Proving and Calibration Tests EMRS Working Practice Public Version: 2.0 Date: 13 October 2017 Table of Contents Change Amendment Record 3 1. Introduction

More information

Informal Document N 20 (30th GRSP, 3-6 December 2001, agenda item 1.4) Insert in the "CONTENTS" the headlines of new annexes 10 & 11 to read:

Informal Document N 20 (30th GRSP, 3-6 December 2001, agenda item 1.4) Insert in the CONTENTS the headlines of new annexes 10 & 11 to read: 30 November 2001 Informal Document N 20 (30th GRSP, 3-6 December 2001, agenda item 1.4) Draft Amendments To Regulation No. 17: (Strength of Seats) page ii Insert in the "CONTENTS" the headlines of new

More information

Van Guard. Bulkhead Test Report

Van Guard. Bulkhead Test Report Van Guard Bulkhead Test Report A257S01 If you have any questions relating to this test please contact your Project Manager: Mr A Thompson direct line + 44 (0)1344 770050 fax: + 44 (0)1344 770356 email:

More information

FIRE TEST REPORT FH 5154

FIRE TEST REPORT FH 5154 1222 Moonshine Road Judgeford RD1 Porirua 5381 New Zealand T +64 4 237 1170 F +64 4 237 1171 branz@branz.co.nz www.branz.co.nz FIRE TEST REPORT FH 5154 CONE CALORIMETER TEST AND NCC SPECIFICATION C1.10

More information

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles

NCC Leisure Battery Verification Scheme. Leisure Accommodation Vehicles The UK trade body for the caravan, motorhome, caravan holiday and park home industry. NCC Leisure Battery Verification Scheme Leisure Accommodation Vehicles Page 1 of 11 1 Scope The NCC Battery Verification

More information

Evergreens UK Ltd. BS Slip Test Report. Addressee: Peter Footit. Evergreens UK Ltd. Evergreens UK Ltd 30/07/15 03/08/15

Evergreens UK Ltd. BS Slip Test Report. Addressee: Peter Footit. Evergreens UK Ltd. Evergreens UK Ltd 30/07/15 03/08/15 Evergreens UK Ltd BS 7976-2 Slip Test Report Addressee: Report carried out on behalf of: Tests conducted at: Test date(s): Report date: Peter Footit Evergreens UK Ltd Exton Blocks Market Overton Industrial

More information

THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS TO WITHSTAND SEVERE FIRES

THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS TO WITHSTAND SEVERE FIRES THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS TO WITHSTAND SEVERE FIRES THE INSTITUTE OF PETROLEUM GUIDELINES FOR THE DESIGN AND PROTECTION OF PRESSURE SYSTEMS

More information

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF FORCE METROLOGY:- CALIBRATION OF UNIAXIAL TESTING MACHINES

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF FORCE METROLOGY:- CALIBRATION OF UNIAXIAL TESTING MACHINES CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF FORCE METROLOGY:- CALIBRATION OF UNIAXIAL TESTING MACHINES Approved By: Chief Executive Officer: Ron Josias Executive - Accreditation: Mpho Phaloane

More information

Contact person Date Reference Page Michael Lindblad F025884B 1 (1) Sustainable Built Environment

Contact person Date Reference Page Michael Lindblad F025884B 1 (1) Sustainable Built Environment issued by an Accredited Testing Laboratory Contact person Michael Lindblad 2015-05-09 5F025884B 1 (1) Sustainable Built Environment +46 10 516 58 58 Michael.Lindblad@sp.se Accred. No. 1002 Testing ISO/IEC

More information

Sede: Via Antica, 24/ S. Giovanni al Nat. UD Tel r.a. Fax SAMPLE N

Sede: Via Antica, 24/ S. Giovanni al Nat. UD Tel r.a. Fax SAMPLE N Report consists of 7 test reports. CERATOLA S.P.A. VIA GIORGIOE 2-ZOA ID.LE 31037 RAMO DI LORIA (TV) Defects before testing: one Sample name: COZY swivel chair SAMPLE 180511 Overall dimensions: 660 x 660

More information

Test Report Current (Gen 2) Pendant Armor and Gen 3 Pendant Armor Polymer A Hanger and Polymer B Hanger March 16, 2016 (Q022516U1R2) Testing Location

Test Report Current (Gen 2) Pendant Armor and Gen 3 Pendant Armor Polymer A Hanger and Polymer B Hanger March 16, 2016 (Q022516U1R2) Testing Location Client Roboworld Molded Products, LLC 8216 Pricinceton-Glendale Road, Suite 246 West Chester, OH 45069 Test Report Current (Gen 2) Pendant Armor and Gen 3 Pendant Armor Polymer A Hanger and Polymer B Hanger

More information

INSTRUCTION LEAFLET FOR 3 TONNE HEAVY DUTY TROLLEY JACK IMPORTANT

INSTRUCTION LEAFLET FOR 3 TONNE HEAVY DUTY TROLLEY JACK IMPORTANT INSTRUCTION LEAFLET FOR 3 TONNE HEAVY DUTY TROLLEY JACK STOCK No.59300 IMPORTANT PART No.TJ3/HD It is important that you read this instruction manual before using your jack. Always ensure its correct use

More information

Equipotential Bonding of Rail Vehicles to Running Rail Potential

Equipotential Bonding of Rail Vehicles to Running Rail Potential Railway Group Standard Equipotential Bonding of Rail Vehicles to Running Rail Potential Synopsis This standard mandates the requirements for equipotenial bonding of rail vehicles to comply with the Electricity

More information

Understanding BS 1363 Amendment No.4

Understanding BS 1363 Amendment No.4 Intertek Hilton House, Corporation Street, Rugby, Warwickshire, CV21 2DN UK info.uk@intertek.com 01788 578435 www.intertek.com Introduction A new Amendment applying to several parts of the BS 1363 standard

More information

Intercomparison Between Trapil, France and NEL, UK Using Oil Flow Turbine Meters

Intercomparison Between Trapil, France and NEL, UK Using Oil Flow Turbine Meters Intercomparison Between Trapil, France and NEL, UK Using Oil Flow Turbine Meters A Report for NMSPU, DTI 151 Buckingham Palace Road London SW1W 9SS Project No: OI/3 (OSDC40300) Report No: 305/99 Date:

More information

Notification of a Proposal to issue an Airworthiness Directive

Notification of a Proposal to issue an Airworthiness Directive Notification of a Proposal to issue an Airworthiness Directive PAD No.: 18-143 Issued: 24 October 2018 Note: This Proposed Airworthiness Directive (PAD) is issued by EASA, acting in accordance with Regulation

More information

BS EN ISO :2006

BS EN ISO :2006 Exova (UK) Ltd Key Industrial Park Fernside Road Willenhall West Midlands WV13 3YA T : +44 (0) 1902 722 122 F : +44 (0) 1902 727 242 E : willenhall@exova.com W: www.exova.com BS EN ISO 10077-1:2006 Calculation

More information

SERVICE BULLETIN NUMBER: R DATE: 10/26/15 REVISED: 11/19/15. APPLICABILITY: MY Legacy and Outback Models SUBJECT:

SERVICE BULLETIN NUMBER: R DATE: 10/26/15 REVISED: 11/19/15. APPLICABILITY: MY Legacy and Outback Models SUBJECT: ATTENTION: GENERAL MANAGER q PARTS MANAGER q CLAIMS PERSONNEL q SERVICE MANAGER q IMPORTANT - All Service Personnel Should Read and Initial in the boxes provided, right. 2015 Subaru of America, Inc. All

More information

Test Report. Report No: BSTDG YRR-4 Date: Mar. 27, 2015 Page 1 of 7. :No.27, Shunsi Road, Ronggui Town, Shunde District, Guangdong Province

Test Report. Report No: BSTDG YRR-4 Date: Mar. 27, 2015 Page 1 of 7. :No.27, Shunsi Road, Ronggui Town, Shunde District, Guangdong Province Report No: BSTDG1503312211YRR-4 Date: Mar 27, 2015 Page 1 of 7 Applicant Address :FOSHAN BANGLISHI TRADING CO, LTD :No27, Shunsi Road, Ronggui Town, Shunde District, Guangdong Province The following sample(s)

More information

Dorman Long Technology Pinned climbing jack system Pinned climbing jacks, power packs and control systems

Dorman Long Technology Pinned climbing jack system Pinned climbing jacks, power packs and control systems Dorman Long Technology Pinned climbing jack system Pinned climbing jacks, power packs and control systems V3.0 Page 2 Introduction DLT Pinned climbing jack systems are very similar in principle to our

More information

Title: WF Report No: Prepared for: Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands, DY4 8TF. Date: 20 th April 2012

Title: WF Report No: Prepared for: Simonswerk UK Ltd. Burcott Works, Spring Street, Tipton, West Midlands, DY4 8TF. Date: 20 th April 2012 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance

More information

DIGITAL BATTERY TORQUE WRENCH (BC-RAD SELECT) USER GUIDE

DIGITAL BATTERY TORQUE WRENCH (BC-RAD SELECT) USER GUIDE DIGITAL BATTERY TORQUE WRENCH (BC-RAD SELECT) USER GUIDE W.CHRISTIE (INDUSTRIAL) LTD CHRISTIE HOUSE, MEADOWBANK ROAD, ROTHERHAM, SOUTH YORKSHIRE, S61 2NF, UK T: +44(0)1709 550088 F: +44(0)1709 550030 E:

More information

SOUTH AFRICAN NATIONAL STANDARD. Plug and socket-outlet systems for household and similar purposes for use in South Africa

SOUTH AFRICAN NATIONAL STANDARD. Plug and socket-outlet systems for household and similar purposes for use in South Africa ISBN 978-0-626-27016-2 SANS 164-1:2012 SOUTH AFRICAN NATIONAL STANDARD Plug and socket-outlet systems for household and similar purposes for use in South Africa Part 1: Conventional system, 16 A 250 V

More information

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF TORQUE METROLOGY (Torque Generating Device Calibration)

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF TORQUE METROLOGY (Torque Generating Device Calibration) CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF TORQUE METROLOGY (Torque Generating Device Calibration) Approved By: Chief Executive Officer: Ron Josias Executive - Accreditation: Mpho Phaloane Author:

More information

Contact person Date Reference Page Michael Lindblad F025884A 1 (1) Sustainable Built Environment

Contact person Date Reference Page Michael Lindblad F025884A 1 (1) Sustainable Built Environment issued by an Accredited Testing Laboratory Contact person Michael Lindblad 2015-05-09 5F025884A 1 (1) Sustainable Built Environment +46 10 516 58 58 Michael.Lindblad@sp.se Accred. No. 1002 Testing ISO/IEC

More information

Date of hosting on website: 26 th October 2017 Last date for comments: 25 th November 2017

Date of hosting on website: 26 th October 2017 Last date for comments: 25 th November 2017 Date of hosting on website: 26 th October 2017 Last date for comments: 25 th November 2017 CHECK LIST FOR PREPARING AUTOMOTIVE INDUSTRY STANDARD Draft AIS-146/D0 : Requirements applying to stands fitted

More information

PULLER KIT OPERATING INSTRUCTIONS

PULLER KIT OPERATING INSTRUCTIONS These instructions cover the whole range of Hi-Force puller kits. Not all kits contain all of the accessories described. SAFETY PRECAUTIONS. Always use the hand pump supplied with the kit, or ensure the

More information

Report No: Test of: Reversible aluminium/timber window. Tested to: BS :2009 Performance of windows & doors Part 2: Operation & strength

Report No: Test of: Reversible aluminium/timber window. Tested to: BS :2009 Performance of windows & doors Part 2: Operation & strength Report No: 181947 Test of: Reversible aluminium/timber window Tested to: BS 6375-2:2009 Performance of windows & doors Part 2: Operation & strength For: A/S Peder Nielsen Beslagfabrik Norregade 25 Bronderslev

More information

Service Bulletin HTXG6DF Lift Loops/Steering Cylinders/Fuel Lines/ Splash Guard Modifications

Service Bulletin HTXG6DF Lift Loops/Steering Cylinders/Fuel Lines/ Splash Guard Modifications Service Bulletin HTXG6DF Lift Loops/Steering Cylinders/Fuel Lines/ Splash Guard Modifications Product Group: Date Issued: Service Bulletin No. Ride-on Trowels Bulletin Type X Mandatory 09/25/5 TR2050820

More information

UK Weighing Federation Technical Articles

UK Weighing Federation Technical Articles 3.4 WEIGHTS Introduction It normally starts with a phone call from a potential customer, I need some weights. As with any enquiry for any piece of weighing equipment, the first and most important point

More information

Test Results. Tyre rim roll-off tests with alloy wheel protectors

Test Results. Tyre rim roll-off tests with alloy wheel protectors Test Results 1029427#2 Customer: Curt Rathbone Unit 3 Crooks Lane Business Park No. 7 Crooks Lane Studley Warwickshire B80 7QX MIRA Contact: Paul Lewis Vehicle Dynamics MIRA Ltd Watling Street Nuneaton

More information

A company of ThyssenKrupp Elevator. ThyssenKrupp Aufzugswerke. Operating Manual. Oil buffer

A company of ThyssenKrupp Elevator. ThyssenKrupp Aufzugswerke. Operating Manual. Oil buffer A company of ThyssenKrupp Elevator ThyssenKrupp Aufzugswerke Operating Manual Oil buffer OPERATING MANUAL Printer s imprint All rights reserved. Copyright by: THYSSENKRUPP AUFZUGSWERKE GMBH P.O. box 23

More information

Interface between Rail Vehicle Weights and Underline Bridges

Interface between Rail Vehicle Weights and Underline Bridges Interface between Rail Vehicle Weights and Synopsis This document sets out the requirements for managing the risk of overloading of underline bridges by rail vehicles Submitted by Signatures removed from

More information

Test Report For: EMECO INDUSTRIES INC Bar Stool

Test Report For: EMECO INDUSTRIES INC Bar Stool 4700 Broadmoor SE, Suite 200 Kentwood, MI 49512 Telephone: 616-- 656-- 7401 Facsimile: 616-- 656-- 2022 www.intertek-- etlsemko.com EMECO INDUSTRIES INC P.O. No. N / A Page 1 of 18 Test Report For: EMECO

More information

TECHNICAL SPECIFICATIONS FOR STEEL PLATES

TECHNICAL SPECIFICATIONS FOR STEEL PLATES TECHNICAL SPECIFICATIONS FOR STEEL PLATES 1.0 SCOPE: HINDUSTAN PETROLEUM CORPORATION LTD., GRESHAM HOUSE This specification covers requirement for Carbon Steel Plates of Structural Quality as per IS: 2062

More information

Creative Bus Dba Getaway Bus REPRESENTING New England Wheels

Creative Bus Dba Getaway Bus REPRESENTING New England Wheels Creative Bus Dba Getaway Bus REPRESENTING New England Wheels ORDER PACKET Contract #TRIPS-15-MB-GB MiniBus with ADA Option CONTRACT # TRIPS-15-MB-GB ORDER PACKET FOR MiniBus with ADA Option Creative Bus

More information

A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE EXAMINATION, TESTING, MAINTENANCE AND REPAIR OF PETROLEUM ROAD TANKERS

A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE EXAMINATION, TESTING, MAINTENANCE AND REPAIR OF PETROLEUM ROAD TANKERS A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE EXAMINATION, TESTING, MAINTENANCE AND REPAIR OF PETROLEUM ROAD TANKERS A MODEL SYLLABUS FOR THE TRAINING OF TECHNICIANS INVOLVED IN THE

More information

ARAI/TA(4G_RV)/SMS/D680/ Dated 21 st Mar 2015 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES

ARAI/TA(4G_RV)/SMS/D680/ Dated 21 st Mar 2015 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s SMS Autoline Equipments Pvt. Ltd. Plot No.AP215, 6 th Street, I Block, Vallalar Colony, Anna Nagar (West) Chennai 600 040 Cert Annex Drg

More information

COMPETITION TRIBUNAL OF SOUTH AFRICA ROADSPAN HOLDINGS (PTY) LTD

COMPETITION TRIBUNAL OF SOUTH AFRICA ROADSPAN HOLDINGS (PTY) LTD COMPETITION TRIBUNAL OF SOUTH AFRICA In the matter between: Case No: 79/LM/Nov09 WBHO CONSTRUCTION (PTY) LTD Acquiring Firm And ROADSPAN HOLDINGS (PTY) LTD Target Firm Panel : Norman Manoim (Presiding

More information

Test of child safety locking device for windows (1 appendix) Summary

Test of child safety locking device for windows (1 appendix) Summary issued by an Accredited Testing Laboratory Contact person Patrik Spånglund 2015-11-03 5P06869 1 (5) SP Structural and Solid Mechanics +46 10 516 56 00 Patrik.Spanglund@sp.se Ackred no. 1002 Testing ISO/IEC

More information

Maximum 20 ma, 24 VDC 825 ohms (see section 3.3) Supply voltage dependence

Maximum 20 ma, 24 VDC 825 ohms (see section 3.3) Supply voltage dependence ALPHASENSE USER MANUAL Page 1 4-20mA Transmitter for Oxygen Sensors 072-0126 Issue 2 1 INTRODUCTION The Transmitter PCB includes circuitry for an electrochemical oxygen sensor to convert the µa output

More information

Metallic materials Rockwell hardness test. Part 2: Verification and calibration of testing machines and indenters

Metallic materials Rockwell hardness test. Part 2: Verification and calibration of testing machines and indenters Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 6508-2 Third edition 2015-03-01 Metallic materials Rockwell hardness test Part 2: Verification and calibration of testing machines and indenters

More information

page 1/6 EN 16139:2013, test severity level 1 The sample submitted for test fulfils the requirements in above mentioned standards.

page 1/6 EN 16139:2013, test severity level 1 The sample submitted for test fulfils the requirements in above mentioned standards. page 1/6 and Verification Center Article: requested by: Neolite, armrests sledge Jan Jismyr Material AB Tranås Sweden s are carried out according to standard: Discrepancies: Result and observations: EN

More information

CPCS renewal test factsheet

CPCS renewal test factsheet CPCS renewal test factsheet Introduction to the CPCS renewal test The industry-led CPCS Management Committee has determined that key safety-related knowledge must be checked on each category prior to the

More information

1998 Addendum to the 1995 STANDARD FOR PROTECTIVE HEADGEAR. For Use With Bicycles. and to the 1994 STANDARD FOR PROTECTIVE HEADGEAR

1998 Addendum to the 1995 STANDARD FOR PROTECTIVE HEADGEAR. For Use With Bicycles. and to the 1994 STANDARD FOR PROTECTIVE HEADGEAR 1998 Addendum to the 1995 STANDARD FOR PROTECTIVE HEADGEAR For Use With Bicycles and to the 1994 STANDARD FOR PROTECTIVE HEADGEAR for Use in Non-Motorized Sports Introduction This document modifies the

More information

DMS-9202 Asphaltic Concrete Patching Material (Stockpile Storage or Bagged)

DMS-9202 Asphaltic Concrete Patching Material (Stockpile Storage or Bagged) Asphaltic Concrete Patching Material (Stockpile Storage or Bagged) Effective Date: May 2017 1. DESCRIPTION This Specification governs for crushed stone asphaltic concrete intended primarily as a cool-

More information

THE NETHERLANDS (N E D E R L A N D) COMMUNICATION. Approval number: E4-23R Extension number: 00

THE NETHERLANDS (N E D E R L A N D) COMMUNICATION. Approval number: E4-23R Extension number: 00 Vehicle Technology Division THE NETHERLANDS (N E D E R L A N D) COMMUNICATION Concerning (1) : - approval granted - approval extended - approval refused - approval withdrawn - production definitely discontinued

More information

NZQA registered unit standard version 1 Page 1 of 6

NZQA registered unit standard version 1 Page 1 of 6 Page 1 of 6 Title Demonstrate knowledge of theory and legislation for registration of electrical appliance servicepersons Level 3 Credits 3 Purpose This unit standard covers the theory assessment required

More information

Compatibility Between Electric Trains and Electrification Systems

Compatibility Between Electric Trains and Electrification Systems Compatibility Between Electric Trains and Electrification Systems Synopsis Process for managing change that affects the compatibility between electric trains and electrification systems Submitted by Signatures

More information

mga research corporation

mga research corporation mga research corporation UNDERGROUND TECHNOLOGIES MAN-HOLE CONSTRUCTION VERTICAL STATIC LOAD TEST SERIES (PO# 11521) 446 executive drive troy, mi 48083 248 / 577-5001 fax 248 / 577-5025 www.mgaresearch.com

More information

PERFORMANCE TEST REPORT. Rendered to: AIR VENT, INC. SERIES/MODEL: Hip Ridge Vent PRODUCT TYPE: Ridge Vent

PERFORMANCE TEST REPORT. Rendered to: AIR VENT, INC. SERIES/MODEL: Hip Ridge Vent PRODUCT TYPE: Ridge Vent Architectural Testing PERFORMANCE TEST REPORT Rendered to: AIR VENT, INC. SERIES/MODEL: Hip Ridge Vent PRODUCT TYPE: Ridge Vent This report contains in its entirety: Cover Page: 1 page Report Body: 6 pages

More information

DIVISION V SURFACINGS AND PAVEMENTS

DIVISION V SURFACINGS AND PAVEMENTS 36-3.01 GENERAL DIVISION V SURFACINGS AND PAVEMENTS 36 GENERAL 04-20-18 Replace section 36-3 with: 36-3 PAVEMENT SMOOTHNESS 36-3.01A Summary Section 36-3 includes specifications for measuring the smoothness

More information

Product Group: Date Issued: Service Bulletin No. Rollers. Item No. 1 MRH601LEVERKIT Travel Lever 1

Product Group: Date Issued: Service Bulletin No. Rollers. Item No. 1 MRH601LEVERKIT Travel Lever 1 Service Bulletin MRH601DS Travel Lever Replacement Product Group: Date Issued: Service Bulletin No. Rollers Bulletin Type X Mandatory Information Only Recommended Change 11/17/14 VR20140813 Models/Series

More information

2 TONNE TROLLEY JACK INSTRUCTIONS IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY TO ENSURE THE SAFE AND EFFECTIVE USE OF THIS TOOL.

2 TONNE TROLLEY JACK INSTRUCTIONS IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY TO ENSURE THE SAFE AND EFFECTIVE USE OF THIS TOOL. 2 TONNE TROLLEY JACK STOCK No.59341 PART No.TJ2B INSTRUCTIONS IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY TO ENSURE THE SAFE AND EFFECTIVE USE OF THIS TOOL. 11/2000 CAUTION CAUTION: Use only on

More information

Note: it is a criminal offence to give false information in this application.

Note: it is a criminal offence to give false information in this application. Note: it is a criminal offence to give false information in this application. Section 1 - Your contact details (Please read Guidance Note 1) 1a) Please give full details of the person that can be contacted

More information

MATERIAL AND EQUIPMENT STANDARD FOR FAST DRYING SYNTHETIC PRIMER TO BE USED WITH HOT APPLIED COAL TAR OR BITUMEN (ASPHALT) ENAMEL ORIGINAL EDITION

MATERIAL AND EQUIPMENT STANDARD FOR FAST DRYING SYNTHETIC PRIMER TO BE USED WITH HOT APPLIED COAL TAR OR BITUMEN (ASPHALT) ENAMEL ORIGINAL EDITION MATERIAL AND EQUIPMENT STANDARD FOR FAST DRYING SYNTHETIC PRIMER TO BE USED WITH HOT APPLIED COAL TAR OR BITUMEN (ASPHALT) ENAMEL ORIGINAL EDITION OCT. 1996 This standard specification is reviewed and

More information

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility Processed Date Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility Customer s Printed Name Installation Street Address Account Number Please note: Columbia Water & Light

More information

THE NETHERLANDS (N E D E R L A N D) COMMUNICATION

THE NETHERLANDS (N E D E R L A N D) COMMUNICATION Vehicle Technology Division THE NETHERLANDS (N E D E R L A N D) COMMUNICATION Concerning (1) - approval granted - approval extended - approval refused - approval withdrawn - production definitely discontinued

More information

ARAI/TA(4G_RV)/HORIBA/MEXA 584L/ Dated 25 Mar 2014

ARAI/TA(4G_RV)/HORIBA/MEXA 584L/ Dated 25 Mar 2014 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s Horiba India Pvt. Ltd. Room 1521, 15 th Floor, Eros Corporate Tower, Nehru Place New Delhi 110 019 Cert Annex Drg Total 1 7 0 8 pgs Exhaust

More information

REQUEST FOR PROPOSAL

REQUEST FOR PROPOSAL Palabora Copper REQUEST FOR PROPOSAL SUPPLY AND DELIVERY OF PIPES, FITTINGS AND FLANGES TO PALABORA COPPER TENDER NUMBER: RFP.PC.2015/144 PART 1 PROPOSAL INFORMATION AND CONDITIONS Page 1 Supply and Delivery

More information

ARAI/TA (4G)/AIRVISOR/AVG500/ Dated 17 th Apr 2017

ARAI/TA (4G)/AIRVISOR/AVG500/ Dated 17 th Apr 2017 Airvisor Technologies Pvt. Ltd. H-155, Adhyapak Nagar, Nangloi, New Delhi 110041. CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES Cert Annex Drg Total 1 7 0 8 pgs Exhaust Gas Analyzer Model

More information

Palabora Copper REQUEST FOR PROPOSAL SUPPLY AND DELIVERY OF BEARINGS AND ACCESSORIES RFP.PC.2017/18 PART 1 PROPOSAL INFORMATION AND CONDITIONS

Palabora Copper REQUEST FOR PROPOSAL SUPPLY AND DELIVERY OF BEARINGS AND ACCESSORIES RFP.PC.2017/18 PART 1 PROPOSAL INFORMATION AND CONDITIONS Palabora Copper REQUEST FOR PROPOSAL SUPPLY AND DELIVERY OF BEARINGS AND ACCESSORIES RFP.PC.2017/18 PART 1 PROPOSAL INFORMATION AND CONDITIONS THIS CONTRACTS IS FOR BIDDERS THAT ARE MORE THAN 26% BLACK

More information

Title: Fire Resistance Test In Accordance With BS EN : 1999 On A Glazed Screen Assembly. WF Report No: , Issue 2. Prepared for: Date:

Title: Fire Resistance Test In Accordance With BS EN : 1999 On A Glazed Screen Assembly. WF Report No: , Issue 2. Prepared for: Date: Title: Fire Resistance Test In Accordance With BS EN 1364-1: 1999 On A Glazed Screen Assembly WF Report No: 164311, Prepared for: AGC Flat Glass Europe. Chaussee de la Hulpe 166 1170 Brussels. Date: 19

More information

Contact person Date Reference Page Michael Lindblad F000833F 1 (1) Sustainable Built Environment

Contact person Date Reference Page Michael Lindblad F000833F 1 (1) Sustainable Built Environment issued by an Accredited Testing Laboratory Contact person Michael Lindblad 2015-06-25 5F000833F 1 (1) Sustainable Built Environment +46 10 516 58 58 Michael.Lindblad@sp.se 1002 ISO/IEC 17025 Martela AB

More information

FAIR WEAR & TEAR GUIDE

FAIR WEAR & TEAR GUIDE FAIR WEAR & TEAR GUIDE Developed by AITA members 2 0 0 6 What Is Fair Wear and Tear? General............. 4 Books and manuals Appearance Additional equipment Badges, labels and stickers Keys Exterior.............

More information

Title: Identification: Revision: Prepared by: Reviewed by: Approved by: Date effective: Page: D Uq Ar/AA AF AO Tr TB TS TE Kr/KN KI Fr/F Cr/C

Title: Identification: Revision: Prepared by: Reviewed by: Approved by: Date effective: Page: D Uq Ar/AA AF AO Tr TB TS TE Kr/KN KI Fr/F Cr/C CROATIAN REGISTER OF SHIPPING CIRCULAR Title: Identification: Revision: Information on availability of an "Approved Method" under MARPOL Annex VI as notified by the IMO Key words: "Approved Method" MARPOL

More information

Note: Please read through the entire guide before attempting any kind of installation.

Note: Please read through the entire guide before attempting any kind of installation. KIT-RSRTD Installation Guide Version 1.5 Auber Instruments, 730 Culworth Manor, Alpharetta, GA 30022 e-mail: info@auberins.com Tel: 770-569-8420 www.auberins.com This is a PID controller kit installation

More information

Branding of Wheels,Tyres and Axles

Branding of Wheels,Tyres and Axles Branding of Wheels,Tyres and Axles Signatures removed from electronic version Submitted by G A Clayton Nominated Responsible Manager Synopsis This standard details the branding requirements for all wheels,

More information

4. If applicable, name and address of manufacturer's representative: Not applicable

4. If applicable, name and address of manufacturer's representative: Not applicable VCA Headquarters 1 The Eastgate Office Centre Eastgate Road Bristol, BS5 6XX United Kingdom Switchboard: +44 (0) 117 951 5151 Main Fax: +44 (0) 117 952 4103 Email: enquiries@vca.gov.uk Web: www.vca.gov.uk

More information

ARAI/TA(4G)/GEN-MAINT/EXOSCAN-V/ Dated 26 th Mar 2009 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES

ARAI/TA(4G)/GEN-MAINT/EXOSCAN-V/ Dated 26 th Mar 2009 CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES CERTIFICATE FOR COMPLIANCE TO THE CENTRAL MOTOR VEHICLES RULES M/s Gen-Maint 106-107, New Diamond Premises Coop. Soc. Ltd. Off. Western Express Highway Goregaon (E) Mumbai 400 063 Cert Annex Drg Tot al

More information

Title: The Fire Resistance Performance of Modified Doorsets. WF Assessment Report No: Prepared for:

Title: The Fire Resistance Performance of Modified Doorsets. WF Assessment Report No: Prepared for: assessment report Title: The Fire Resistance Performance of Modified Doorsets WF Assessment Report No: 187254 Prepared for: Phoenix Door Panels Ltd. Westnewlands Ind. Estate Somersham Huntingdon Cambs

More information

SAP PCDB: Test method for central exhaust ventilation system packages used in a single dwelling

SAP PCDB: Test method for central exhaust ventilation system packages used in a single dwelling SAP PCDB: Test method for central exhaust ventilation system packages used in a single dwelling 1 Introduction This test method is based closely on the European Standard BS EN 13141-6:2004 and must be

More information

Report Issued: October 19, 2014 Project No.: 23942

Report Issued: October 19, 2014 Project No.: 23942 Report Number: 1052-14017 Report Issued: October 19, 2014 Project No.: 23942 Client: Showerstart LLC 15354 North 83 rd Way Suite 102 Scottsdale, AZ 85260 Contact: Mr. Jason Swanson Source of Samples: The

More information

Mercedes-Benz Van Road Care

Mercedes-Benz Van Road Care Mercedes-Benz Van Road Care Roadside Assistance Introduction We have always placed great emphasis on providing premium quality after sales care to our customers, care which truly matches the quality of

More information

DRAFT SOUTH AFRICAN STANDARD (DSS): PUBLIC ENQUIRY STAGE

DRAFT SOUTH AFRICAN STANDARD (DSS): PUBLIC ENQUIRY STAGE Document number 022/SANS 1496 Reference SANS 1496 DRAFT SOUTH AFRICAN STANDARD (DSS): PUBLIC ENQUIRY STAGE Date of circulation 2017-09-14 Closing date 2017-11-15 Number and title: SANS 1496:XXXX Wheel

More information

Photometric Test Report

Photometric Test Report Photometric Test Report Photometric and Optical Testing Services Cheltenham Film and Photographic Studios Hatherley Lane Cheltenham Gloucestershire GL51 6PN UK Tel: 01242 701300 Page 2 of 14 Photometric

More information

Weights And Measures (Sand And Other Ballast) THE WEIGHTS AND MEASURES ACT (CAP. 340) PART I PRERIMINARY PROVISIONS PART II BALLAST

Weights And Measures (Sand And Other Ballast) THE WEIGHTS AND MEASURES ACT (CAP. 340) PART I PRERIMINARY PROVISIONS PART II BALLAST GOVERNMENT NOTICE NO. 223 published on 19/07/2013 THE WEIGHTS AND MEASURES ACT (CAP. 340) REGULATIONS Section Title PART I PRERIMINARY PROVISIONS 1. Citation. 2. Interpretation. PART II BALLAST 3. Prescribed

More information

Contact person Date Reference Page Michael Lindblad F013838C 1 (1) Sustainable Built Environment

Contact person Date Reference Page Michael Lindblad F013838C 1 (1) Sustainable Built Environment issued by an Accredited Testing Laboratory Contact person Michael Lindblad 2015-09-17 5F013838C 1 (1) Sustainable Built Environment +46 10 516 58 58 Michael.Lindblad@sp.se 1002 ISO/IEC 17025 Johanson Design

More information

Contact person Date Reference Page Hans Eriksson F000838D 1 (3) Wood Technology

Contact person Date Reference Page Hans Eriksson F000838D 1 (3) Wood Technology issued by an Accredited Testing Laboratory Contact person Hans Eriksson 2015-03-26 5F000838D 1 (3) Wood Technology +46 516 54 28 hans.eriksson@sp.se 02 ISO/IEC 17025 Nordic Comfort Products A/S P.O. Box

More information

Draft for comments only Not to be cited as East African Standard

Draft for comments only Not to be cited as East African Standard EAST AFRICAN STANDARD CD/K/021:2008 ICS 43.040.50 Motor vehicle safety Steering mechanism of motor vehicles (Category M 1 only) Behaviour on impact EAST AFRICAN COMMUNITY EAC 2010 First Edition 2010 CD/K/021:2008

More information

This document is a preview generated by EVS

This document is a preview generated by EVS EESTI STANDARD EVS-EN 14066:2003 Natural stone test methods - Determination of resistance to ageing by thermal shock Natural stone test methods - Determination of resistance to ageing by thermal shock

More information

Towing TOWING A TRAILER. Trailer socket

Towing TOWING A TRAILER. Trailer socket Towing TOWING A TRAILER E90953 WARNINGS Never exceed the maximum weights for either the vehicle or trailer. Doing so can cause accelerated wear and damage to the vehicle. It can also adversely affect vehicle

More information

E-training. Operating characteristics and sizing of pneumatic actuators. The main types of pneumatic actuator

E-training. Operating characteristics and sizing of pneumatic actuators. The main types of pneumatic actuator Welcome to the K Controls e-training course designed to deliver useful Pneumatic Valve Actuation application information in small instalments. To unsubscribe or to register a colleague to receive these

More information