1 Photo of NARM site here? Ground Monitoring System Fault Investigation North Antelope Rochelle Mine Lyle Hunt / Scott Svoboda - Peabody Energy David Shipp / Mike Peters - Eaton Electrical Engineering Services WMEA Spring Conference Denver, CO May 31, 2017

2 Background, Mine 2 Mines Combined Trains/Day Low Sulphur Coal Supplies Generation Industry 250T / 400T Trucks 13,000,000 lbs. Excavator Preceding Week Multiple Ground Faults (6) / GF Tripping Arc Flash Event Involving Ground and Personnel

3 General Background on NARM The North Antelope Rochelle Mine is the world s largest coal mine. The mine sold nearly 93 million tons of compliance coal during 2016 and more than 2 billion tons since the mine began. The complex uses 4 draglines and 15 shovels. Coal is currently delivered to more than 60 electricity generating customers throughout the United States. The complex currently has a workforce of approximately 1,145 people and annually injects approximately $2.3 billion into the regional economy in direct and indirect benefits.

4 Ground Fault Event On 2/8/16 there was a low level arc flash event at NARM on a stationary substation (PS34). 69 kv to 22.9 kv Sub was immediately removed from service Root Cause DCS Gary Sorenson Bruno Engineering Confirmed RCA WESCO Eaton Engineering Grounding Expert David Shipp

5 PS-34 Function 69kV / 22.9 kv Sub 15 MVA Txmr 25 Amp NGR 2 Ground Mats Grounding Conductor Monitor NGR Integrity Relay Feeds Excavator

6 Ground Fault Event Trouble-shooting Grd Fault Reclosed Breaker Grd Monitor Relay / Control Panel Failed on Reclosing Low Level Arc Flash Occurred. Approx. 1.2 Calorie Event

7 Ground Fault Event

8 Investigation; Involved Ground Mats On-Site Investigation Lightning? Installation Errors? MSHA Requirements Transferred Earth Potentials Transient Over Voltages Earth Megger Meas. Tripping Data Open Neutral in Txmr / NGR

9 MSHA Requirements at PS34 Protect Personnel Protect Equipment A Mine System is not an Industrial Plant! MSHA Design Involves Transferred Earth Potentials Transfer by Grounded Conductor 2 Ground Mats (+Safety Ground Mat/Borehole Grd Mat/Isolation Grd Mat) 100V GF Touch / Step Potential Max at Shovel (25A)(4 ohms Max in Trailing Cable Ground Conductor) = 100V MSHA Required Protection

10 Mining Installation - Without Safety Ground Bed Xfer by Grded Conductor Eg Eg = Vman = GMR = IgZm Remote Earth

11 Mining Installation - With Safety Ground Mat Xfer to Safety Ground Mat not to the Man Eg Eg = GMR = IgZm Vman Remote Earth

12 Mining Installation - With Safety Ground Mat Grd Fault at Shovel Vman = 100V Max Igf Eg Eg = Igf(Zgc) < 100V = Vgc drop = Vman Remote Earth Vmax = Vlg = Vng

13 On-Site Investigation NGR Monitor Cable Arced to control cables and Sub Frame Ground GC Monitor Failed / Arced to Sub Frame Ground Zm1 = Zm-sub = 0.68 ohms Zm2 = Zs-gm = 1.86 ohms Zm1-m2 = 2.24 ohms NGR = 528 ohms (no open Neutrals) All Grounds Installed Correctly

14 On-Site Investigation - Continued Trailing Cable Intact ( 20k feet) with Grds / shields Correct Arc Path was Between 2 Grd Mats via Frame Grd NGR Monitor Cable Smoked Fencing Grounding, etc. all Correct

15 NGR System Failure Partial 3-Line

16 NGR Monitor Cable Failure Smoked

17 Ground Monitor Relay Failure Front Rear

18 Grd Conductor Monitor Arced Thru Hinges to Main Sub Grd (Grded Frame) Arced Thru Hinges to Main Sub Ground

19 Substation Ground Design

20 Failure Analysis Investigated Everything that Could Cause This Type of Failure Open neutral in Txmr / NGR Open circuit ground wire to excavator Loose connections 1 or both ground mat issues such as too high of ohmic values Open ground wire to safety ground mat Excessive length of trailing cable (too much cable capacitance). Lightning strikes Improperly grounded lightning arresters Too much or too little ohms between the 2 ground mats. Wire routing? Path for current to flow bypassing neutral grounding resistor (NGR)

21 Failure Analysis Investigated Trailing Cable Lengths All Items in Black Were Found to be Correct (NGR, Txmr, Basic MSHA Required Components, etc.). Red were Found Deficient Transient Over Voltages Due to Arcing Grd Fault If Capacitive Charging Current (thru Insulation to grd) > Resistive Grd Fault Current, then Voltages can Escalate with Respect to Grd. About 700%V Burns into Massive fault. Icapac = Ingr at 24.3k feet still within limits at 20K ft

22 Failure Analysis Wire Routing NGR Monitor Wire Under GF, Vng Estimated to be between 6 kv and 13.2 kv (input to monitor voltage divider). This Wire entered Substation Instrument Room and was Tie Wrapped to the Control Wires for lights, etc. (MV wire tie wrapped to LV control Wires) When NGR Monitor relay was removed, this MV wire was not completely removed. This Conductor was involved to substation Grd Mat

23 Failure Analysis NGR Bypassed GC Monitor Relay Indicated High Current arced thru it to Sub Grd NGR Monitor is Tied to Safety Grd Mat but Physically Installed on Substation Grded Steel. NGR Monitor also Mounted on Sub Steel but ties to Txmr N point and to Safety Grd Mat. Both Relays Will Have Substantial voltages Across them Under GF Conditions (Between 2 Grd Mats)

24 Step 1 - Ground Fault Path; Then Arcs thru NGR Monitor Wire to Sub Grd Mat Vng 6.3 to 13.2 kv

25 Step 2; Current Bypasses NGR thru Zm1-m2; Eg now across GC Monitor

26 Step 2; Eg Exceeds GC Monitor Limits Eg Estimated at 2240V+ MOV Fails GF Current Estimated at 1000A s +/- GFCT Saturates and GF Relay never Operates. Relay Fails Internally

27 Step 3: Ground Monitor Relay Failure

28 Step 3: Ground Monitor Relay Failure Fault Path Bypasses Zm1-m2 (2.24 ohms) Current Increases greater than 1800A s Phase Instantaneous (device 50) trips (phase CTs do not saturate) Arc Blast from around GC Monitor Engulfs Personnel in Close Proximity Causing Arc Flash Incident

29 Conclusions Failure was Initiated by Wire Routing Initial Failure Allowed NGR to be Bypassed High Fault Current Resulted in CT Saturation / No GF Tripping Sustained and/or Repeated Voltages between 2 Ground Mats Caused GC Monitor to Fail Internally. Failed GC Monitor now Bypassed Zm1-m2 Ultimate Arc Flash Condition Occurred with Igf >1800A s

30 Recommendations ALWAYS separate MV / LV Wiring from Each Other. NGR and GC Relays Connect Both Grd Mats Together Be Aware that Grd Wires between 2 Grd Mats Must be Treated as MV Investigate Using a PT in Lieu of the Voltage Divider for NGR Monitor Redesign Substation Ground Monitoring System. Include Sustained Grd Fault and Lightning Conditions Survey other Substations Test Ground Mats Yearly

31 Solution Redesign substation ground monitoring system to prevent / improve personnel and safety and prevent recurrence of ground fault event. 1. Maintain the system grounding integrity a. Yearly Inspection of entire system (offline) b. Insure best practices are used in setting up system. c. Develop SOP s on how to maintain system/install grounding system. d. Monthly Testing of Protection functions 2. Educate Employees how to Maintain system and why. 3. Develop recommendations to minimize exposure to personnel

32 THANK YOU ANY QUESTIONS??

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

CHAPTER 4 PROTECTION REQUIREMENTS

CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.

More information

Transformer Protection

Transformer Protection Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com

More information

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In

More information

Washington, DC Area Low Voltage Disturbance

Washington, DC Area Low Voltage Disturbance Washington, DC Area Low Voltage Disturbance April 7, 2015 Robert W. Cummings Sr. Director of Engineering and Reliability Initiatives NASPI Working Group Meeting October 15, 2015 Overview April 7, 2015-12:39

More information

Electrical Safety. Introduction

Electrical Safety. Introduction Electrical Safety Introduction Electrical hazards 300 electrocutions every year in the U.S. Leading cause is insufficient training ALL were preventable What is Electricity? How Electricity Works Created

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

Zone Selective Interlocking

Zone Selective Interlocking Application Paper AP02602002EN Supersedes 08/2003 Zone Selective Interlocking Contents Description.... Page What is Zone Selective Interlocking?... 3 What is the purpose of Zone Selective Interlocking?....3

More information

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise Arc flash solutions catalogue Australia Safety solutions - Protecting employees and the enterprise The risk of an arc flash event is real An arc flash hazard is a proven significant and dangerous threat

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

Flanders Electric Engineering Division

Flanders Electric Engineering Division Flanders Electric Engineering Division Welcomes You to an Overview of Reconditioned Switchgear Lou York Bill Oxby Reasons for Reconditioning Switchgear Cost Savings Reuse material Buswork Building/enclosure

More information

UPPCO SERVICE MANUAL

UPPCO SERVICE MANUAL Revised 01/2015 Section 6 ELECTRIC SERVICE - GENERAL Page 1 of 10 Section 6 Electric Service - General 6-1 Number of Services and Voltages / Meter... 2 6-2 Energy Conversion Factors... 7 6-3 Lightning

More information

Surface Regulations and Policies

Surface Regulations and Policies Surface Regulations and Policies COAL FATALITIES 1970-2002 350 300 250 200 150 100 50 0 1970 1973 1976 1979 1982 1985 1988 1991 1994 1997 2000 From January 1, 1970 through today, a total of 240 coal miners

More information

Grounding Of Standby & Emergency Power Systems

Grounding Of Standby & Emergency Power Systems July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due

More information

Case Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI

Case Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI Case Study on On EHV Circuit Breaker Flashover AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT) BREAKER-FLASHOVER There has been a rising

More information

Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors

Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors Eilis M. Logan UPRR Marvin J. Frazier Corr. Comp Co. Electromagnetic Interference Magnet and Paper Clip

More information

Large Air Cooled Generator Failure

Large Air Cooled Generator Failure Large Air Cooled Generator Failure Henry Tarnecky AVP - Sr. Engineering Specialist, FM Global 2017 IRIS Rotating Machinery Conference FM Global Basics Commercial/Industrial Property Insurer Mutual Co.,

More information

Three days training program (Oct 5-7) on. Substation Earthing, Industrial earthing and Neutral earthing. at IEI Mysore, Karnataka India

Three days training program (Oct 5-7) on. Substation Earthing, Industrial earthing and Neutral earthing. at IEI Mysore, Karnataka India Three days training program (Oct 5-7) on Substation Earthing, Industrial earthing and Neutral earthing at IEI Mysore, Karnataka India Training program is helpful for students, Engineers working in Design

More information

Two Recent Case Studies in the Mining Industry

Two Recent Case Studies in the Mining Industry Two Recent Case Studies in the Mining Industry Remote Isolation Arc Flash Remediation David B. Durocher Senior Member, IEEE Global Industry Manager, Mining Eaton Corporation 26850 SW Kinsman Rd Wilsonville,

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

Motor Trouble-Shooting Chart Caution:. Disconnect power to the motor before performing service or maintenance.. Discharge all capacitors before servicing motor.. Always keep hands and clothing away from

More information

ADVISE DESIGN IMPLEMENT FOR ELECTROTECHNICAL EXCELLENCE

ADVISE DESIGN IMPLEMENT FOR ELECTROTECHNICAL EXCELLENCE ADVISE DESIGN FOR ELECTROTECHNICAL EXCELLENCE IMPLEMENT ADVISE DESIGN FOR ELECTROTECHNICAL EXCELLENCE Gemitech was founded in 1990 and, in just a few short years, grew to be recognized as medium and IMPLEMENT

More information

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012 POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 PREPARED BY: Electricity System Operations Planning and Performance DATE: 5 June 2012 FINAL

More information

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com TGOOD produces over 5000 switchgear units annually for projects around the globe SOLUTION OVERVIEW For use in affordable air insulated

More information

LA Motor Protection. A South African Company to be Proud of

LA Motor Protection. A South African Company to be Proud of LA Motor Protection Relay Physical Address: 298 Soutter Street, Pretoria West Tel: 083 454 6949, +27 12 327 1729 Fax: +27 (0)12 327 1733 Toll Assist: 0860 10 30 41 www.newelec.co.za sales@newelec.co.za

More information

Electrical Awareness and Considerations

Electrical Awareness and Considerations Electrical Awareness and Considerations By David Taylor FIHE MIET IEng Objectives Awareness of specifications. Awareness of Distribution Network Operators (DNO) earthing arrangements. Awareness of basic

More information

Worry Free High Voltage Couplers WMEA Conference, San Antonio November 19, 2009 Presented by Nick Turner of KonNx Inc.

Worry Free High Voltage Couplers WMEA Conference, San Antonio November 19, 2009 Presented by Nick Turner of KonNx Inc. Worry Free High Voltage Couplers WMEA Conference, San Antonio November 19, 2009 Presented by Nick Turner of KonNx Inc. KONNX KonNx Inc Office, Warehouse and North American Distribution Denver, Colorado

More information

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 PREPARED BY: Electricity System Operations Planning and Performance FINAL Disclaimer (a) Purpose - This report

More information

UNITED STATES DEPARTMENT OF LABOR MINE SAFETY AND HEALTH ADMINISTRATION Metal and Nonmetal Mine Safety and Health REPORT OF INVESTIGATION

UNITED STATES DEPARTMENT OF LABOR MINE SAFETY AND HEALTH ADMINISTRATION Metal and Nonmetal Mine Safety and Health REPORT OF INVESTIGATION MAI-2008-12 UNITED STATES DEPARTMENT OF LABOR MINE SAFETY AND HEALTH ADMINISTRATION Metal and Nonmetal Mine Safety and Health REPORT OF INVESTIGATION Underground Nonmetal Mine (Potash) Fatal Electrical

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

Substation inspection guidelines Mark B. Goff, P.E.

Substation inspection guidelines Mark B. Goff, P.E. Substation inspection guidelines Mark B. Goff, P.E. Tennessee Valley Authority, Chattanooga, Tennessee ABSTRACT We need to better understand what our infrared camera is really showing us. Without guidelines,

More information

Switchgear and Distribution Systems for Engineers and Technicians

Switchgear and Distribution Systems for Engineers and Technicians Switchgear and Distribution Systems for Engineers and Technicians WHAT YOU WILL LEARN: How to identify typical characteristics of an industrial distribution system Become familiar with the main components

More information

High Voltage Surge Arresters Buyer s Guide Section Transmission Line Arrester PEXLINK

High Voltage Surge Arresters Buyer s Guide Section Transmission Line Arrester PEXLINK High Voltage Surge Arresters Buyer s Guide Section Transmission Line Arrester PEXLINK Definitions Transmission Line Arresters Backflashover Occurs when lightning strikes the tower structure or overhead

More information

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are

More information

Arc-Flash Mitigation Technologies. Dennis Balickie

Arc-Flash Mitigation Technologies. Dennis Balickie Arc-Flash Mitigation Technologies Dennis Balickie The purpose of the session is to provide an overall understanding of the strategic impact of arc-flash. Special focus is on the tactical means to minimize

More information

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues Designing and Maintaining a Pollution-Resilient Electric Power System Tom McDermott IEEE/PES T&D Conference April 21-24, 2008 Chicago, IL Managing Pollution Issues Define the metrics, and measure them

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

Future Proof Your Arc Flash Assessment

Future Proof Your Arc Flash Assessment Future Proof Your Arc Flash Assessment 2017 ENERGY CONNECTIONS CONFERENCE TRADE SHOW Presented by: Keith Mullen, P.E. November 9, 2017 Agenda > Utility requirements > Study objectives > Applicable standards

More information

OSHA Update. Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926)

OSHA Update. Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926) OSHA Update Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926) 5/14/2014 Significant Changes to the Standards General Training Host Employer & Contractor Responsibilities

More information

Cost Benefit Analysis of Faster Transmission System Protection Systems

Cost Benefit Analysis of Faster Transmission System Protection Systems Cost Benefit Analysis of Faster Transmission System Protection Systems Presented at the 71st Annual Conference for Protective Engineers Brian Ehsani, Black & Veatch Jason Hulme, Black & Veatch Abstract

More information

Could also be a Near Hit

Could also be a Near Hit A near miss is an unplanned event that did not result in a fatal injury but had the potential to do so. Only a fortunate break in the chain of events prevented an injury, fatality or damage; in other words,

More information

Safe, fast HV circuit breaker testing with DualGround technology

Safe, fast HV circuit breaker testing with DualGround technology Safe, fast HV circuit breaker testing with DualGround technology Substation personnel safety From the earliest days of circuit breaker testing, safety of personnel has been the highest priority. The best

More information

POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO KV BUSBAR ON 30 OCTOBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO KV BUSBAR ON 30 OCTOBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO.1 275 KV BUSBAR ON 30 OCTOBER 2011 PREPARED BY: Electricity System Operations Planning and Performance

More information

MESG 12 / 17.5 / 24 / 36 KV

MESG 12 / 17.5 / 24 / 36 KV MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL

More information

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast. ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW High performance alternative to air

More information

Unrestricted. S.Mukhopadhyay

Unrestricted. S.Mukhopadhyay Unrestricted S.Mukhopadhyay 10.09.15 Electrical safety A report says that every year 5500 Indians die due to electric shock and 800 due to electric fire. 12% work place death due to electrocution ELECTRICAL

More information

Energy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy.

Energy Transmission & Distribution Services - Italy. SVEPPI laboratory...our services for your success. Answers for energy. Energy Transmission & Distribution Services - Italy SVEPPI laboratory...our services for your success. Answers for energy. ...our services for your success ENERGY - T&D Services Experience teaches us that

More information

ELECTRICAL SAFETY TRAINING

ELECTRICAL SAFETY TRAINING ELECTRICAL SAFETY TRAINING ELECTRICAL SAFETY TRAINING OVERVIEW Regulations & Standards Terms ELECTRICAL HAZARDS SAFETY MODEL Recognize hazards: work environment, electrical system, wrong PPE Evaluate hazards:

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

DO COMMERCIAL BUILDINGS HAVE POWER PROBLEMS? THE ANSWER IS - THEY CERTAINLY DO.

DO COMMERCIAL BUILDINGS HAVE POWER PROBLEMS? THE ANSWER IS - THEY CERTAINLY DO. DO COMMERCIAL BUILDINGS HAVE POWER PROBLEMS? THE ANSWER IS - THEY CERTAINLY DO. By Patrick J. Lynch, P.Eng. PROBLEMS CAN BE GENERATED BY THE ACTUAL BUILDING LOCATION, OTHERS BY EQUIPMENT WITHIN THE BUILDING

More information

Electrical Power Distribution (CDEE)

Electrical Power Distribution (CDEE) Lecturer: Ing. Martin Paar, Ph.D. paar@feec.vutbr.cz,www.ueen.feec.vutbr.cz Transmission and distribution networks in the Czech Republic Electrical Power Distribution (CDEE) e-power - Inovace výuky elektroenergetiky

More information

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 6545(Print), ISSN 0976 6545(Print) ISSN 0976 6553(Online)

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Modifying the exterior lighting of the Ram truck

Modifying the exterior lighting of the Ram truck Modifying the exterior lighting of the Ram truck The Ram truck has been designed and developed using standard incandescent lights. These lights are controlled by a computerized module called the Central

More information

Generation Interconnection Facilities Study For

Generation Interconnection Facilities Study For Generation Interconnection Facilities Study For Prepared for: Prepared by: SCE&G Transmission Planning May 27, 2015 TABLE OF CONTENTS General Discussion... Page 3 Generator Interconnection Specifications...

More information

BP OIL -- TOLEDO REFINERY

BP OIL -- TOLEDO REFINERY BP OIL -- TOLEDO REFINERY Document Type: Procedure Effective Date: August 31, 2017 Owner: Dane P. Clark Refinery Wide Electrical Distribution System Switching and Isolation Auth. By: Rick J. Chmelovski

More information

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers The National Electrical Code makes the following statement regarding ground fault conformance testing:

More information

IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series

IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series Designing Electrical Systems for On-Site Power Generation Apr 04 th /05 th, 2016, Calgary/Edmonton, Alberta,

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design Presented at the 2018 Transmission and Substation Design and Operation Symposium Revision presented at the

More information

CM52 Network Protector with Arc Flash Reduction Module

CM52 Network Protector with Arc Flash Reduction Module Contents Description Page 1: General.............................. 2 2: Maintenance Mode Settings.............. 2 3: Arming Maintenance Mode.............. 2 4: Remote Indicator....................... 2

More information

Title Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP)

Title Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category General Title Reference Number PMP 01 (RIC Standard: EP 00 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards and

More information

Actionpac LNS4. Panel Installation Datasheet. Actionpac LNS4 RELEASE 1.0 JUNE In partnership

Actionpac LNS4. Panel Installation Datasheet. Actionpac LNS4 RELEASE 1.0 JUNE In partnership Actionpac LNS4 Panel Installation Datasheet ELECTROSTATIC SENSITIVE DEVICE This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product will directly

More information

Unit 3 Lesson 3 Electric Circuits. Copyright Houghton Mifflin Harcourt Publishing Company

Unit 3 Lesson 3 Electric Circuits. Copyright Houghton Mifflin Harcourt Publishing Company A Complete Circuit What are the parts of an electric circuit? An electric circuit is a complete, closed path through which electric charges can flow. All electric circuits contain three basic parts: an

More information

SWITCHBOARDS (LV and MV)

SWITCHBOARDS (LV and MV) ELEC9713 Industrial and Commercial Power Systems SWITCHBOARDS (LV and MV) 1. Introduction Depending on the size of the building or factory site and whether the supply is high voltage or low voltage, there

More information

AVOIDING ELECTROCUTION HAZARDS

AVOIDING ELECTROCUTION HAZARDS Print AVOIDING ELECTROCUTION HAZARDS MODULE DESCRIPTION This module will provide information that helps you recognize and avoid common electrocution hazards in your work environment. OBJECTIVES After completing

More information

Health and Safety Keeping Pace with Technology. Thomas Novak, Ph.D., P.E. Professor and Alliance Coal Academic Chair University of Kentucky

Health and Safety Keeping Pace with Technology. Thomas Novak, Ph.D., P.E. Professor and Alliance Coal Academic Chair University of Kentucky Health and Safety Keeping Pace with Technology Thomas Novak, Ph.D., P.E. Professor and Alliance Coal Academic Chair University of Kentucky Outline Coal Mining and Accident Statistics in the U.S. Coal Workers

More information

Custom Medium and LV Switchgear 5-38kV Switchgear Power Systems

Custom Medium and LV Switchgear 5-38kV Switchgear Power Systems Custom Medium and LV Switchgear 5-38kV Switchgear Power Systems www.switchgearpower.com Generator Controls, Paralleling Switchgear, LV Switchboards States Mfg. www.statesmfg.com Transformers (Substation

More information

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY 2011-2020 P+ PowerPlus Engineering A Department of STAR Energy Services, LLC TEN YEAR PLANNING GUIDE 2011-2020 SHASTA LAKE ELECTRIC UTILITY CITY OF

More information

Grounding Systems. Resistance. Resistance Grounding Systems Contents

Grounding Systems. Resistance. Resistance Grounding Systems Contents Resistance Systems.0-1 Resistance Systems Contents Resistance Systems High Resistance System Medium Voltage...............1-1 High Resistance System Low Voltage..................2-1 Specifications See

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality Surabaya Seminar 2014 Ferdinand Sibarani, Surabaya, 30 th October 2014 Power Quality Content 1. Power quality problems 2. ABB s low voltage (LV) solution PCS100 AVC (Active Voltage Conditioner) PCS100

More information

NC PV DG Program SEPA Presentation. December 15, 2011

NC PV DG Program SEPA Presentation. December 15, 2011 NC PV DG Program SEPA Presentation December 15, 2011 Agenda PV Industry Background PV Solar Rooftop Incident Root Cause(s) Wiring Diagrams Remedy Fire Safety Brochure Findings/Observations Recommendations

More information

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

Extra-High-Voltage SF 6 Gas-Insulated Switchgear Extra-High-Voltage SF 6 Gas-Insulated Switchgear Shuichi Sugiyama Masahiko Fujita Takahiro Shinohara 1. Introduction Due to location criteria and toughened restrictions on transportation, it has become

More information

GENERAL REQUIREMENTS:

GENERAL REQUIREMENTS: Installation & Service Manual Slim Rack Bunk Lift System with Control Box 1510000199 or 1510000260 Content Copyright Power Gear Issued: January 2013 # 3010002675, Rev. 0D Installation and Service Manual

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT All electrical systems and electrically energized equipment

More information

Jaeshininformation Co., of Korea Distributor

Jaeshininformation Co., of Korea Distributor Earth Leakage Current Measurement and ELCB (RCD) trip analysis & Chemical Factory Inverter AC_DC_Battery_Temp Case study 2017. 09 Jaeshininformation Co., of Korea Distributor Our Goal We can follow IEEE1100

More information

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS El Paso Electric Company System Operations Department System Planning

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic July 26, 2016 Reliability Analysis Update MetEd Transmission Zone N-1 First Energy Planning Criteria (FERC Form 715): The North Boyertown West Boyertown 69 kv is

More information

Small wonder. Station service voltage transformers for small power requirements

Small wonder. Station service voltage transformers for small power requirements Small wonder Station service voltage transformers for small power requirements MATHEW PAUL An estimated 1.3 billion people worldwide have no access to electricity. In small communities, this is often due

More information

Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: conductors insulators extreme caution

Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: conductors insulators extreme caution Electrical Safety Electrical Hazard Three factors determine the resistance of a substance to the flow of electricity: What it is made of. Its size. Its temperature. Substances with very little resistance

More information

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer

Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals Mike Schmaderer Questions Feel free to interrupt There are no dumb questions Just what exactly is Switchgear? The

More information

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR FEBRUARY 14, 2001 REVISION 3 Publication: SE-125-M Document: S95-C125-00000 Printed in Canada. Copyright 2001 by Startco Engineering Ltd. All rights reserved.

More information

SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test)

SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test) ANNEXURE I SYLLABUS FOR ELECTRICAL SUPERVISOR CERTIFICATE OF COMPETENCY (SCC MV) Electrical Engineering Paper (Written Test) Paper I & Paper II for General Category of S.C.C. Examination Paper I & Paper

More information

2106 HDCT-DUAL Belt Tracker

2106 HDCT-DUAL Belt Tracker 2106 HDCT-DUAL Belt Tracker Features Stainless steel construction Two cylinders for added tracking power and neutral positioning External bearings Two mechanical remote sensors Filter regulator unit Tracker

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

Electrical Workplace Safety

Electrical Workplace Safety Electrical Workplace Safety Alan Kelly 23 rd September 2015 Objectives To provide an understanding of Electrical terms and the concepts of electricity To introduce Electrical Protective Devices and provide

More information

EEI Occupational Safety & Health Committee Conference Public Safety Issues and Trends

EEI Occupational Safety & Health Committee Conference Public Safety Issues and Trends EEI Occupational Safety & Health Committee Conference Public Safety Issues and Trends Anthony J. Calega Vice President, Loss Control October 7, 2008 A E G I S AssociatedElectric Gas Insurance Services

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

Energized Electrical Work

Energized Electrical Work Manitoba STANDARD PROCEDURE INSTRUCTION Title Energized Electrical Work Department Supersedes SPI Dated N/A SPI 32-4 Effective Date MAR 30, 2012 Energized Electrical Work SPI 32-4 Page 1 of 9 STANDARD

More information

ELECTRICAL AREA CONTROLLED ACCESS PROCEDURE SP-18 NATIONAL HIGH MAGNETIC FIELD LABORATORY NHMFL FLORIDA STATE UNIVERSITY SAFETY PROCEDURE SP-18

ELECTRICAL AREA CONTROLLED ACCESS PROCEDURE SP-18 NATIONAL HIGH MAGNETIC FIELD LABORATORY NHMFL FLORIDA STATE UNIVERSITY SAFETY PROCEDURE SP-18 NATIONAL HIGH MAGNETIC FIELD LABORATORY NHMFL FLORIDA STATE UNIVERSITY SAFETY PROCEDURE SP-18 CONTROLLED ACCESS PROCEDURE HEAD of MAGNET OPERATIONS Bryon Dalton EH&S MANAGER Angela Sutton HEAD OF FACILITIES

More information

STATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2013

STATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2013 Safety Services 16 th floor, Commerce Place Tel: 1-866-421-6929 10155 102 nd Street Fax: 780-427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS ELECTRICAL INCIDENTS IN ALBERTA January 1 to December 31,

More information

COGENERATION PLANT SWITCHGEAR REPLACEMENT IMPROVES SAFETY AND RELIABILITY WHILE MAINTAINING SERVICE TO CRITICAL LOADS

COGENERATION PLANT SWITCHGEAR REPLACEMENT IMPROVES SAFETY AND RELIABILITY WHILE MAINTAINING SERVICE TO CRITICAL LOADS COGENERATION PLANT SWITCHGEAR REPLACEMENT IMPROVES SAFETY AND RELIABILITY WHILE MAINTAINING SERVICE TO CRITICAL LOADS Rachel Mueller, Mayo Clinic Timothy Coyle, PCT, Inc. Presented to: Minnesota Power

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information