Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals. Mike Schmaderer
|
|
- Ethan Alexander
- 6 years ago
- Views:
Transcription
1 Switchgear Arrangement, Torque Requirements, Insulation Systems & Maintenance Intervals Mike Schmaderer
2 Questions Feel free to interrupt There are no dumb questions
3 Just what exactly is Switchgear?
4 The term switchgear, used in association with the electric power system, or grid, refers to the combination of electrical disconnects, fuses and/or circuit breakers used to isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream.
5 Substation vs Switchgear Substation Easier to maintain Easier to modify Lower arc flash incident energy Switchgear (Substation in a box) Smaller footprint Better at keeping animals out Build off sight Out of weather (maybe)
6 Open Switchgear
7 Traditional Switchgear Breakers all in the bottom May require a ramp
8 Enclosure Side View
9 Two High Construction Takes up less space Lift is required for breakers in top row
10 Combination Lift is required
11 Typical One Line
12 Switchgear One Line
13 Laid Out to Minimize Load on the Bus
14 Laid Out to Meter Generation
15 Laid Out to Facilitate Maintenance
16 Laid Out to Facilitate Maintenance
17 Fused Switches
18 Outdoor Metal Clad Switchgear
19 Arc Resistant Designed to vent energy from an arc safely away from operators Extra support Costs about 30% more
20 Arc Reduction Techniques Bus Differential Protection Instantaneous Tripping With blocking Arc Relaying Strategically placed fiber Combined with overcurrent Remote Switching
21 Things to Consider Before Ordering Gear Number of Feeders Generators Tie(s) and Bus Tie Bus Ampacity Entrance Top Entrance Bottom Entrance Throat Connected Bastard
22 Things to Consider Before Ordering Gear CTs PTs For Relaying For Metering Location For Metering For Relaying For Synchronizing Location
23 Things to Consider Before Ordering Gear Breaker Arrangement Single high Two high Location of feeders, generators, tie Continuous Current Rating of the Breaker Interrupting Capability of the breaker Must be able to interrupt max fault current Arc Flash
24 Insulation Porcelain (glass) Glastic Indoor only Polymer Skirts
25
26 Breaker -Interrupters How does the Breaker extinguish the arc? Air Blast Under Oil SF6 Vacuum
27 Torqueing Requirements
28 Torque τ = torque σ y = yielding stress of material D = bolt diameter c = coefficient of friction Yield Strength (Mpa) Aluminum 241 Steel 248 Brass 200
29 Torque US Recommended Bolt Torque Recommended Torque Size Grade 2 Grade 5 Grade S/S Bronze Brass Coarse Fine Coarse Fine Coarse Fine Coarse Fine Coarse Fine Coarse Fine #4* #6* #8* #10* / / / / / / / / /
30 Torque Torque Values = inch-lbs Bolt Size 18-8 Stainless Steel Brass Aluminum 2024-T4 316 Stainless Steel Nylon /4" /4" /16" /16" /8" " /16" /16" /2" /2" /16" /16" /8" /8" /4" /4" /8" /8" " "
31 Maintenance Cleaning Relay Testing Breakers Ductor High potential Function Testing
32 Switchgear Maintenance When is the last time that the bus and bus supports were cleaned Are the heaters working Do they get turned off Dirt and Moisture Most are hard to get out of service Even with generation Ethanol Plant Example
33 Switchgear Maintenance Moving parts seldom operate Switching load Clearing faults Generator breakers operate more often Breakers/Switches Battery Relays
34 Functional Trip Testing Electrical mechanical relays Spin the disk Microprocessor based relays Force a trip Inject current Through test switches Inject primary current Through the CT s
35 Breakers Heaters Year round Trip/Close coils Rewind motors Exercise the breaker Lubricate the Mechanism
36 Relays Monitor current and voltage Overcurrent Directional overcurrent Voltage Impedance Etc.
37 Relays Relays should be tested periodically Suggest generator and tie relays every three years Suggest feeder relays every five to six years Function of the value of the asset they are protecting Test should include a functional test of the breaker
38 Types of Relays Ice cube Interposing Lockout Electromechanical Solid state (Static) Microprocessor-based (Digital/Numerical)
39 DC/Battery System Stored Energy Battery Charger Trip coils Close coils Rewind Motors?
40 Battery Check it once a month Turn off AC breaker for one hour Monitor voltage drop Compare to previous months Don t let the voltage drop more than 10% DC rewind motors
41 Common Switchgear and Substation Issues
42 Mechanism gummed up Caused by dirt and inactivity Will not trip Common during the winter Especially in outdoor breakers Often causes a blown fuse or a trip coil to burn up
43 Rewind motor will not stop winding Broken or misaligned gear Often causes motor to burn up Pull motor rewind fuses
44 Rewind motor winds up, unwinds, and rewinds continuously Latch does not catch Caused by dirt and grim Common during the winter Especially in outdoor breakers Often causes motor to burn up Pull motor rewind fuses and lubricate latch
45 Breaker will not close after a trip Blown fuse in close circuit Burnt up close coil Lockout relay not reset Sync switch not turned on
46 Broken Pole or linkage One or more phases not making contact Current imbalance Voltage imbalance Hard on generators
47 Check voltage and current often Voltage Use voltmeter to check all three phases Use sync scope to check sync PT Current Use ammeter to check current on all three phases Multifunction meters Microprocessor based relays
48 Other things to consider Record faults Phase Time Weather conditions Interrupting rating Fault study Arc Flash
49 Once again, if you are not 100% sure, get help
50 Questions?
ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position
LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationPretest Module 29 High Voltage Unit 1
Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition
More informationSchool of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering
University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear
More informationSF 6 gas insulated RMU SafePlus 24 kv. ABB SafePlus 24 kv SF6 gas insulated RMU 1
SF 6 gas insulated RMU SafePlus 24 kv 25.03.2010 SafePlus 24 kv SF6 gas insulated RMU 1 Secondary distribution 400 kv Transmission substation Transformer 40-70 kv 130 kv Main Substation Secondary distribution
More informationExtensible Unit - VCE2a
ELECTRICAL INDUSTRIAL COMPANY (EICo) LUCY SWITCHGEAR Extensible Unit - VCE2a (Sabre) Electrical Industrial Company (EICo) Lucy Switchgear Extensible Unit VCE2a Front Panel: ELECTRICAL INDUSTRIAL COMPANY
More informationNEW Solutions for Underground System Growth
NEW Solutions for Underground System Growth Cooper s Single-Phase Voltage Regulator Improved Power Quality More Economical Improved System Reliability Increased Safety Better Aesthetics Lower Maintenance
More informationArc-Flash Mitigation Technologies. Dennis Balickie
Arc-Flash Mitigation Technologies Dennis Balickie The purpose of the session is to provide an overall understanding of the strategic impact of arc-flash. Special focus is on the tactical means to minimize
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationwww. ElectricalPartManuals. com lncoming-6900 through 69,000 volts Outgoing-2400 through 13,800 volts Ratings:
PRIMARY UNIT SUBSTATIONS SECTION 2701 PRIMARY UNIT SUBSTATIONS Ratings: lncoming-6900 through 69,000 volts Outgoing-2400 through 13,800 volts PAGE 1 ---JUNE 1, 1959 DESIGNED AND BUILT TO MEET YOUR OWN
More information6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton
Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are
More informationZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.
ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW High performance alternative to air
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used
More information16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12
16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting
More informationTransformer Protection
Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com
More informationSolar Power Switchgear & Energy Storage Renewable Energy Systems
7 Solar Power Switchgear & Energy Storage Renewable Energy Systems - Solution Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433 APPROACH
More informationAIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE
AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly
More informationOutdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications
Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers
More informationECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits
ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Text Book: Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai Lin, Professor
More informationSWITCHGEAR DIVISION PRODUCT PROFILES
SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationSolid Dielectric, Triple Option Reclosers Catalog O-vlt14
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationSwitchgear and Distribution Systems for Engineers and Technicians
Switchgear and Distribution Systems for Engineers and Technicians WHAT YOU WILL LEARN: How to identify typical characteristics of an industrial distribution system Become familiar with the main components
More informationBGE STRATEGIC CUSTOMER ENGINEERING
TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND
More informationA comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear
Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More information5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application
The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1
More informationINESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation
MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing
More informationIntroduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)
S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) Inspection Recommendations for Switchgear with Type AT-3 Source- Transfer Controls Table of Contents Section
More informationIntegrated Power Solutions
Integrated Power Solutions Low & Medium Voltage Distribution Power Distribution Centers Skid-Mounted Substations Custom Control & Automation ESS Metron Proposal 64000V1 DATE: PAGES (including cover): 7
More informationSectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications
Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications History Early 1970 s Small Substation Transformers
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationMEDIUM VOLTAGE AIS ANSI SWITCHGEAR Advance and Advance 27. Non-arc-resistant MV ANSI switchgear
2018 MEDIUM VOLTAGE AIS ANSI SWITCHGEAR Non-arc-resistant MV ANSI switchgear Agenda Ratings, dimensions and qualifications MV ANSI circuit breakers for Design features Auxiliary compartments Enclosures
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationDigitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers
Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin
SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive
More information1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.
RC SCOPE This test procedure covers the testing and maintenance of Westinghouse RC relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to
More informationMotor Protection. Voltage Unbalance & Single-Phasing
For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants
More informationSolid Dielectric, Triple Option Reclosers Catalog O-vlt14
Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical
More informationAdvance 27 ANSI 27 kv switchgear
Advance 27 ANSI 27 kv switchgear Table of contents Advance 27...3 AMVAC breaker...4 Instrument transformers...5 Current transformers...5 27 kv voltage transformers...6 Distribution protection and control...7
More informationBHARAT HEAVY ELECTRICALS LIMITED, JHANSI
BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause
More informationA. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.
SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationInstallation and Construction Notes for EVSE4
Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process
More informationNEXT STEP B) SAFETY :
SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply
More informationSolid Dielectric, Three Phase Reclosers CATALOG VS11
Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance
More informationSolid Dielectric, Three Phase Reclosers Catalog O-vs18
Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance
More informationCobra-S. Catalog Cobra-S
Cobra-S Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5/16kA symmetrical interrupting Control
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationIntroduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv)
S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv) Inspection Recommendations for Switchgear Equipped with Type AT-2 Source-Transfer Controls Table of Contents
More information7. SERVICES OVER 600 VOLTS
7. SERVICES OVER 600 VOLTS 7.1 GENERAL The Company shall always be consulted to obtain required design criteria where service is contemplated.preliminary plans of the Customer shall be submitted for review
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationThe safest, most reliable Switchgear in the market today
February 2008 MV Metal-Clad Switchgear The safest, most reliable Switchgear in the market today January 4, 2015 Slide 1 Arc-Resistant Standards Introduction Today s Topics What is Arc Flash and the risks
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationPROTECTION OF THE BRANCH CIRCUIT
PROTECTION OF THE BRANCH CIRCUIT Branch circuit should always be protected from over current. Hence, an overall current devices shall be installed in all branch circuitries. Function of the over-current
More informationMEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES
MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications
More informationWind Power Solutions. Make Energy Renewable and Reliable!
Wind Power Solutions Make Energy Renewable and Reliable! Reliable Thomas & Betts Products for Clean, Green, Thomas & Betts makes all the products that connect and protect a wind farm and its power distribution
More informationClose-Open (Short-Circuit) Time Results Interpretation
Application Note Close-Open (Short-Circuit) Time Results Interpretation Close-Open (C-O, trip-free) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection
More informationLow Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear
13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of
More informationMEDIUM VOLTAGE PRODUCTS
MEDIUM VOLTAGE PRODUCTS Anything is possible with MYERS POWER PRODUCTS PROTECT Protect your equipment and personnel from the elements and unforeseen electrical events with Myers Medium Voltage Products
More information16.13 Unit Substation to 15kV Construction Standards Page 1 of 7
Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected
More informationB-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE
B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE Duty B: Power Distribution (600V and below) B-03: Troubleshoot 480V System Issued 06/01/98 Task Preview Troubleshoot 480V System The 480V distribution
More informationS&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv
TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection
More informationCLIENT: PROJECT: PO#: ESTIMATOR:
GENERATOR CONTROL DATA SHEET CLIENT: PROJECT: PO#: ESTIMATOR: PRIME MOVER FUEL: RPM: GOVERNOR SPEED ADJUST RHEOSTAT SUPPLIED WITH GOVERNOR: LOAD SHARING: REMOTE: PRIME MOVER PROTECTION LOW OIL PRESSURE
More informationSIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac
0000 00000 0000 000 0000 000000 00000 0000 00000 0000 000 0000 000000 00000 SIMOVAC and SIMOVAC-AR Medium-voltage controllers 2.3 kv - 6.9 kv usa.siemens.com/simovac 2 SIMOVAC and SIMOVAC-AR - the latest
More informationTransmission & Distribution Glossary of Electrical Terms
Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The
More informationBasics of Medium Voltage Motor Control Starter Power Components & Starter Types
Basics of Medium Voltage Motor Control Starter Power Components & Starter Types Larry Dalton Lead Operation Specialist Jude Hernandez - Application Engineer GE Industrial Solutions Slide # 1, Rev 3, 11/8/16
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More informationMedium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.
Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More informationDescriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear
Descriptive bulletin ReliaGear ND ANSI narrow frame metal-clad switchgear Table of contents Introduction...3 Vmax/A breaker...4 Instrument transformers...5 Potential transformers...6 15 kv potential transformers...6
More informationOTEC Transfer switch open transition
Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator
More informationCOOPER POWER CA280012EN
Reclosers Catalog Data CA280012EN Supersedes May 2014 (290-25) COOPER POWER SERIES Type VSA20B air-insulated, vacuum, electronically Description The Type VSA20B electronically controlled, vacuum circuit
More informationMAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI
MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK --------------------------------------------------------------------------------------------------------------- Sub. Code : EE2402 Semester
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationTIME REQUIREMENT GUIDE (TRG)
CAT SWITCHGEAR TIME REQUIREMENT GUIDE (TRG) This warranty repair time requirement guide is designed to: Provide detailed guidance on troubleshooting Determine possible solutions Guide the technician to
More informationCOLDWATER LAKE FACILITIES DUPLEX PUMP STATION
COLDWATER LAKE FACILITIES DUPLEX PUMP STATION TROUBLESHOOTING GUIDE REFERENCE: Operation Instructions Ladder Schematic Diagrams SCOPE The following troubleshooting guide has been specifically prepared
More informationCase Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI
Case Study on On EHV Circuit Breaker Flashover AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT) BREAKER-FLASHOVER There has been a rising
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction
SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor
More informationwww. ElectricalPartManuals. com outdoor oillnaken type GC aingle tank descrlpllve bullella page l 14.4 lev 100,380 and BOO mva 23 lev 280 mva
October, 1959 supersedes db 33-ZSl dated November, 1956 mailed to: E/Z75,Z79/DB: D64-5C: CZ6-5Z,b :::....... outdoor oillnaken type GC aingle tank 14.4 lev 1,38 and BOO mva 23 lev 28 mva appucatioa descrlpllve
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear
More informationUsing new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines
Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Abstract: The development of the magnetically actuated vacuum interrupter
More informationShippensburg University
Shippensburg University 1871 Old Main Drive Shippensburg, PA 17257 SUPPLEMENT 1 Electrical Coordination Study Professional: Entech Engineering, Inc. 4 South Fourth Street P.O. Box 32 Reading, PA 19603
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationTexas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives
Texas A&M Microgrid and Electrical System Study Cushing Memorial Library & Archives Introduction of Texas A&M Microgrid Study Purpose Why are we studying the TAMU electrical system? Process How do we want
More informationWhen power interruptions happen.
When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage
More informationZone Selective Interlock Module. For GE Circuit Breakers
GE Zone Selective Interlock Module For GE Circuit Breakers Table of Contents 1. Introduction... 4 What is Zone-Selective Interlocking (ZSI)?...4 What is a Zone-Selective Interlock Module?...4 2. Description...
More informationSolid Dielectric, Single Phase Reclosers
Solid Dielectric, Single Phase Reclosers Providing electronic overcurrent protection for single phase operation on systems rated through 38kV, 800A continuous current,12.5ka symmetrical interrupting Reliable
More informationichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax
Network Protector Instruction Manual Type 316NP ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1232-001B DISCLAIMER OF WARRANTIES
More informationELECTRICAL HAZARD EXAMPLES
ELECTRICAL HAZARD EXAMPLES UNFORTUNATELY, THE EVENTS LISTED BELOW ARE MORE COMMON THAN YOU WOULD EXPECT Circuit breaker does not open the circuit when operated manually or remotely. The contacts within
More information