1 /6 Glossary /8 Training Ordering notes /9 Logistics /11 Ordering special versions /11 Small orders /12 Further documentation Standards and approvals /13 Approvals, test certificates, characteristic curves /13 Safety characteristics /15 Standards / Approval requirements valid in different countries / Testing bodies, approval identification and approval requirements / Marine classification societies /17 CE marking /17 ALPHA/LOVAG /17 Accident prevention /18 Ex protection certificates for SIRIUS controls /18 Certificate of the AS-International Association for AS-Interface products /19 Special standards for the USA and Canada /19 Special standards for Russia, Australia and China /20 Quality management /21 Siemens contacts /22 Siemens Solution Partner Automation /23 External partners /24 Online services: Information and ordering in the Internet and on DVD /25 Service & Support: The unmatched complete service for the entire life cycle /27 Software licenses /28 Subject index /35 Order number index /58 Conditions of sale and delivery Siemens Siemens IC 10 IC

2 Glossary "a" release Short designation for a current-sensitive delayed overload release. "n" release Short designation for an instantaneous electromagnetic electronic release. 8US busbar adapters 8US busbar adapters enable the mechanical mounting and electrical contacting of motor starter protectors, load feeders or compact starters on a single busbar system. Adapters for screw fixing Adapters for screw fixing can be used for mounting a compact starter onto a flat surface. Approvals Approval of controls and switchgears on the basis of sometimes mandatory national standards which exist in addition to sets of rules such as "IEC", "CENELEC" and "CEE". For example, UL certification or CSA certification are required for the North American market (USA, Canada). Additional marking is also mandatory in such cases, i.e. the certification symbol must be applied as an inscription to the device. Arc quenching space During a control's switching operations, in particular during disconnection of highly inductive load currents or short-circuit currents, the ionized gases produced by the arc are forced out through the arc chute openings. To ensure that the concentration of these ionized gases does not reach a hazardous level, a certain clearance is required above or in front of the device. This arc quenching space is quoted by the manufacturer (normally on the dimensional drawings) and depends on the presence of exposed live conductors (e.g. busbars), conducting structures and insulation partitions at the control. Arc chute attachments can be mounted onto large motor starter protectors in order to reduce the clearance and therefore the space required in the control cabinet. No arc quenching space is required for vacuum circuit breakers and vacuum contactors because the arc does not leave the vacuum chute and no ionized gases are released. AS-Interface AS-Interface is an open, international standard according to EN and IEC for process and field communication. Leading manufacturers of actuators and sensors all over the world support the AS-Interface. Interested companies are provided with the electrical and mechanical specifications by the AS-Interface Association. Auxiliary switch blocks for compact feeders Optional auxiliary switch blocks in versions with 2 NO, 2 NC or 1 NO plus 1 NC. AWG (American Wire Gauge) A standard wire size used in the USA, which is based on the cross-sectional area of the conductor or wire. With each AWG number the cross-sectional area is incremented by 26 %. The thicker the wire, the smaller the AWG number. Basic module Function modules are comprised of at least one basic module, supplemented by coupling modules as required. The basic module includes the control logic and, in the case of wye-delta modules, the time setting for ramp-up in star mode, and a 10-pin plug connector for accommodating the plug of the coupling modules. Bypass operation When a motor ramp-up is completed, the thyristors on SIRIUS soft starters are fully operated and the complete mains voltage is applied therefore to the motor terminals. As no controlling of the motor voltage is necessary during operation, the thyristors are bridged by internal bypass contacts designed for AC1 current. The waste heat arising during uninterrupted duty due to thyristor power loss is thus reduced. This reduces heating of the switchgear environment. CLASS (time) see > Trip class (CLASS). Closed power This refers to the power consumption of a contactor's solenoid coil which results from the continuously absorbed current and is required to hold the magnetic system in the closed state. Connection methods SIRIUS offers the right connection method for every environment: Screw terminals, spring-type terminals or ring terminal lugs. Contactor A switching device with only one off position, usually without mechanical lock, which is not operated manually and which, under normal conditions, can switch on, transmit and switch off the circuit, including normal overload currents. Contactors are preferably used for high switching frequencies. A distinction is made between contactors for switching motors (motor load switches) and contactor relays for control. Control kit An aid for manually closing the main contacts by actuating a handle. Coupling module Function modules are comprised of at least one basic module, supplemented by coupling modules as required. The coupling module includes one NO contact and a 10-pole connecting cable with plugs to the coupling module and the basic module; it is used for the mutual interlocking of wye and delta operation. The communication-capable version transmits the signals of the other contactors and realizes the electrical interlocking (reversing/wye-delta starting); there is no integrated connecting cable. Current limiting with soft starters SIRIUS 3RW40 soft starters continuously measure the phase current (motor current) by means of integrated current transformers. During the start-up operation, the flowing motor current can be actively limited by the soft starter. The current limiting function is superimposed on the voltage ramp function. This means that as soon as a parameterized current limit value is reached, the voltage ramp is aborted and the motor is started with the current limiting function until the ramp-up is completed. On SIRIUS 3RW40 soft starters the current limiting is always active. If the current limiting potentiometer is set to the far right (maximum), the starting current is limited to the factor 5 of the set rated motor current. The current limit value is set as a factor of the rated motor current to the required current during start-up. Due to the current unbalance in the start-up operation, the set current corresponds to the arithmetic mean over the 3 phases. /2 Siemens IC

3 Glossary Current monitoring relay Current monitoring relays are used for underload monitoring and overload monitoring of motors or other loads. The level of current permits extensive conclusions to be drawn about the powered process or plant, e.g. a torn belt, no-load operation of a pump, tool wear, hoist overload or blockage. With multi-phase monitoring it is possible in addition to perform phase sequence, phase failure or residual current monitoring. If the measured current values lies outside the defined range there will follow an instant or time-delayed alarm or disconnection. Current setting range (of an electronic release) Range between the smallest and the biggest value of the current to which the release can be set. Door-coupling rotary operating mechanisms Door-coupling rotary operating mechanisms enable the operation of motor starter protectors and compact starters with closed control cabinet doors. Electrical interlock The electrical interdependence of controls through circuit-related measures. Customary for contactor controls: For example, a contactor is only allowed to be switched on when another contactor was switched off first. Auxiliary contacts or auxiliary switches are used to implement an electrical interlock. Endurance The period in which the control works problem-free under normal operating conditions. It is expressed in numbers of operating cycles (operating cycles), electrical endurance (contact erosion of the contacts) and mechanical endurance (operating cycles without load). Explosion protection Essential for the use of electrical equipment in potentially explosive atmospheres according to EN (VDE 0170 / 0171). Explosion protection requires equipment which is liable to produce ignition-capable electric arcs (plasma) during operation to be enclosed in a flameproof casing. The explosive mix can enter the enclosure, but an ignition-capable flame produced during an explosion inside the casing is prevented from escaping to the outside. Fast short-circuit trip unit A motor starter protector's release which provides short-circuit protection for the downstream load or cable. In the event of a short circuit, the fast short-circuit trip unit must disconnect all poles of the motor starter protector instantaneously or with a short-time delay. Function module Function modules are differentiated according to their use: For direct-on-line starting For reversing starting For wye-delta starting Function modules are also available in communication-capable versions with AS-i or IO-Link in order to create a link to a higherlevel control system. Function module for direct-on-line starting These function modules are used for the time-delayed switching of contactors. Function module for reversing starting Function modules for reversing starting are used for operating reversing starters. The version without a fieldbus interface is comprised of bridge modules, the version for AS-Interface or IO-Link has one basic module and one coupling module. In all three cases the electrical interlocks of the two directional contactors are already included. Function module for wye-delta starting Function modules for wye-delta starting are used for changing over from star mode to delta mode. They are comprised of one basic module and two coupling modules. The electrical interlocks are already included in the modules. Heavy starting Heavy starting exists if a motor requires more than 10 to 15 s from being switched on to reaching its rated speed on account of its special load conditions. When heavy starting exists, the load torque of the machine to be driven is greater during startup than in rated operation. It takes longer to reach the rated speed because large centrifugal masses need to be accelerated (e.g. on rolling mills, centrifuges, etc.). The protection of heavy-starting motors requires special overload relays (heavystarting relays, solid-state overload relays) or thermistor motor protection devices. Heavy starting with soft starters According to the specific boundary conditions, the SIRIUS soft starter has to be selected for heavy starting characteristics (CLASS 20 start-up) at least one power level higher than the rating of the motor used. Sample set values and device sizes are listed in tables in the product manual list. Infeed systems for 3RA6 The infeed system for 3RA6 enables several compact starters to be fed in through one modular infeed system with permanent wiring. Intrinsic device protection for soft starters SIRIUS 3RW40 soft starters have integrated intrinsic device protection which prevents thermal overloading of the thyristors. This is realized on the one hand by current measurement using transformers in the three phases and additionally by temperature measurement using thermal sensors on the thyristor heat sink. If the internal permanently set switch-off value is exceeded, the soft starter will switch off automatically. Inverse-time delayed overload trip unit ("a" release) A thermal overload release which works with a time delay that decreases as the current increases. IO-Link IO-Link is a new communication standard for sensors and actuators - defined by the PROFIBUS User Organization (PNO). IO-Link technology is based on the point-to-point connection of sensors and actuators to the control system. As such it is not a bus system but an upgrade of the classic point-to-point connection. Extensive parameter and diagnostics data are transmitted in addition to the cyclic operating data for the connected sensor and actuators. The connection method is based on a three-pole standard cable or 3 individual wires. Leakage current When the current flow is controlled by means of semiconductors, there can be no electrical separation in the device. A small residual current, i.e. leakage current, still flows therefore in the disconnected state when a load is connected. Low-voltage switchgear and controlgear assembly A switchgear and controlgear assembly is a combination of one or more low-voltage controls with related units for controlling, measuring and indicating, plus the related protective and control devices. It must be fully assembled under the manufacturer's responsibility, with all internal electrical and mechanical connections and structural parts. Siemens IC /3

4 Glossary Main control switch Every industrial machine covered by IEC Part 1 (VDE 0113, Part 1) must be fitted with a main control switch which disconnects the entire electrical equipment from the mains for the duration of cleaning work, maintenance, repairs and lengthy stoppages. Usually a switch which can be operated by hand is stipulated in order to prevent electrical or mechanical hazards. A main control switch can also be an emergency-stop device. The following requirements must be met: 1. Handle can be reached from the outside 2. Only one "Off" position and one "On" position with allocated stops 3. Identification of the two positions with "0" and "I" 4. "Off" can be locked 5. Mains terminals with cover to prevent touching by accident 6. The switching capacity must comply with AC-23 in the case of motor load switches and AC-22 in the case of load-break switches (utilization category) 7. Positive indication of the switch position Mirror contact for power contactors A mirror contact is an NC contact that cannot be closed simultaneously with an NO main contact (according to EN , F). Modular systems The SIRIUS modular system offers everything that you need for switching, starting, protecting and monitoring motors and industrial systems. It is a modular selection of standard components which are optimally coordinated, can be combined with ease and use the same accessories. Motor protection Protection of induction motors against overload and short circuit, i.e. protection of the winding insulation against unacceptable heating. Motor Starter Protectors Generally key-operated switching devices that switch on, control and switch off currents in circuits under normal operating conditions. Under prescribed conditions that are not normal through to short circuit, they can also switch on the current, control it for a specified interval and interrupt it. Mounting methods SIRIUS offers a maximum of configuration flexibility. The system components can be configured on a feeder-oriented or line-oriented basis. Off-delay The time span effected by a timing relay or timer (e.g. on contactors) between the opening command for the contacts of the timing relay or timer and the actual reaching of their original position. ON period in % The relative ON period in % is the ratio between load period and cycle duration for loads which are frequently disconnected and switched on. Operating range The range in which a contactor's actuating voltage is allowed to deviate from the rated actuating voltage without the reliable operation of the control being impaired (e.g. dropping out of the contactor). Overload release An overload trip unit is an electronic release for protecting against overload. Phase control for soft starters With phase control of two inverse-parallel switched thyristor pairs, the rms value of the motor voltage on SIRIUS soft starters is increased within a selectable starting time from a selectable starting voltage to the rated motor voltage. The motor current changes in proportion to the voltage applied to the motor. The starting current is thus reduced by the factor of the voltage applied to the motor. The torque changes in squared proportion to the voltage applied to the motor. The starting torque is thus reduced in squared proportion to the voltage applied to the motor. Phase failure sensitivity A product feature which enables a protective device to respond also during single-phase operation of a three-phase asynchronous motor before the motor suffers thermal damage (DIN VDE 0660 Part 102). Pick-up power The pick-up power is the power consumption of a contactor's solenoid coils which is required to set the magnetic system in motion. With alternating current operation this is usually higher than the closed power. With direct current operation on SIRIUS contactors, the pick-up power equals the closed power. Polarity balancing for soft starters On two-phase controlled SIRIUS 3RW30 and 3RW40 soft starters the current resulting from superimposition of the two controlled phases flows in the uncontrolled phase. The advantages of two-phase control lie in the more compact size, compared for example to a three-phase solution, and in the lower device costs. A negative physical effect of the two-phase control during startup is the occurrence of DC components due to the leading-edge phase and the superimposition of the phase currents, which can lead to severe noise generation on the motor. The SIEMENS patented "Polarity Balancing" control method was developed to prevent the DC components during start-up. "Polarity Balancing" reliably eliminates these direct current components during the ramp-up phase. It creates a motor ramp-up that is uniform in speed, torque and current rise. At the same time the acoustic quality of the starting operation comes close to the quality of a three-phase controlled starting operation. This is made possible by the on-going dynamic harmonizing or balancing of current half-waves of different polarity during the motor ramp-up. Positively-driven contact in contactor relays Positively-driven contact elements are a combination of "n" NO contact and "m" NC contact which are designed such that they cannot be closed simultaneously (EN , L). Preferred circuit for wye-delta starters In the preferred circuit for a clockwise rotating motor the motor terminals are correctly connected when phase L1 is connected to motor terminals U1 and V2, L2 to V1 and W2, and L3 to W1 and U2. This order should be observed during installation in order to minimize the changeover current peak in a clockwise rotating motor when switching over from wye to delta. /4 Siemens IC

5 Glossary Protection technology Basically a distinction is drawn between two current-based protection technologies: Thermal and solid-state protection. Motor starter protectors and thermal overload relays protect with bimetal trip units; solid-state overload relays, 3RW40 soft starters and 3RA6 compact starters protect on a solid-state basis. The solid-state options feature not only a far lower power loss but also a wide setting range of 1:4, which means that they offer a far smaller variance than the thermal releases. The SIRIUS modular system has the right solution for each switching technology. Ramp time With SIRIUS soft starters, the length of the set ramp time defines in which time the motor voltage is raised from a selected starting voltage to the mains voltage. This has an influence on the motor's acceleration moment, which drives the load during the ramp-up operation. As the result, a longer ramp time has a smaller acceleration moment throughout the motor ramp-up. The latter is therefore longer and smoother. The length of the ramp time should be selected such that the motor reaches its rated speed within this period. If the time selected is too short, i.e. if the ramp time ends before the motor ramp-up is finished, a very high starting current will arise at this moment and can reach the value of the direct-on-line starting current at this speed. Ramp-down time On SIRIUS 3RW40 soft starters the "ramp-down time" potentiometer can be used to define how long the power supply to the motor is to be upheld after the ON command is removed. During this ramp-down time the torque generated in the motor is reduced using a voltage ramp function and the application is brought to a smooth halt. Rated conditional short-circuit current I q Guaranteed short-circuit breaking capacity of controlgear assemblies and load feeders, also referred to as the rated conditional short-circuit current. Rated data of the control circuit The most important rated data of the control circuit for selecting a contactor are the rated control supply voltage U s (the voltage of the coil connection) with related frequency (e.g. 50 Hz) and the power consumption of the coil (pick-up power and closed power). Rated data of the main circuit The most important rated data of the main circuit for selecting a contactor are the rated operational current I e (the current which is defined by the conditions of use) or the rated power (motor rating) and the corresponding rated voltage U e. Rated impulse withstand voltage (U imp ) The peak value of a surge voltage of specified form and polarity to which, under specified test conditions, electrical equipment can be subjected without failing and to which the clearances refers. The rated impulse withstand voltage of a device must correspond to, or be greater than, the transient overvoltages that occur in the system in which the equipment is installed. Rated insulation voltage U i The voltage value which specifies the insulation resistance of the control or accessory part and to which the insulation tests and creepage and clearances refer. On no account must the highest rated operational voltage exceed the rated insulation voltage. Rated service short-circuit breaking capacity I cs Compared to the rated ultimate short-circuit breaking capacity I cu, the test conditions are more exacting and the short-circuit current is usually lower. Determined with test sequence II, switching sequence O-t-CO-t-CO (O = Open, t = Time, CO = Close-Open). After the test, the motor starter protector must be unrestricted in its functions. Rated short-circuit breaking capacity I cn The rated short-circuit breaking capacity of a motor starter protector is (according to IEC and EN ) the value of the short-circuit current that it can switch off at the rated operational voltage, rated frequency and specified power factor (or specified time constant). The value of the prospective current applies (in the case of alternating current: rms value of the AC components) as specified by the manufacturer. With AC motor starter protectors the rated short-circuit breaking capacity must be independent of the size of the DC components (DC component). The rated short-circuit breaking capacity means that the motor starter protector can disconnect any current up to the rated short-circuit breaking capacity at a line-frequency recovery voltage of 110 % of the rated operational voltage. This applies for alternating current with every value of the power factor, but not lower than specified in the respective testing guidelines, for direct current, unless otherwise stated by the manufacturer, with every time constant but not greater than defined in the respective testing directive. The short-circuit breaking capacity does not apply for line-frequency recovery voltage of more than 110 % of the rated operational voltage. Rated ultimate short-circuit breaking capacity I cu The maximum short-circuit current I k (limit value of the rated short-circuit breaking capacity) which the motor starter protector can disconnect under defined conditions. Determined with test sequence III, switching sequence O-t-CO (O = Open, t = Time, CO = Close-Open). After the test, the motor starter protector may be restricted in its functions. Recovery time After a protection function in a control (e.g. motor starter protector, soft starter, overload relay or current monitoring relay) has tripped, the motor cannot be restarted until a recovery time has elapsed. The recovery time varies in length according to the cause of the fault. Details can be found in the related product documentation. Response delay The response delay is the time from the beginning of a command's entry to the first making of the contact, e.g. at the contactor. RoHS EC Directive 2002 / 95 / EC concerning the restriction of certain dangerous substances in electrical and electronic devices regulates the use of hazardous substances in devices and components. The directive and its respective implementation in national law is known for short by the abbreviation RoHS (Restriction of the use of certain Hazardous Substances). Short-circuit strength Resistance of a control in the closed state with its parts (e.g. releases) or of a complete switchgear against the electrodynamic (dynamic short-circuit strength) and thermal (thermal short-circuit strength) stress that occurs in the event of a short circuit. The characteristic for the dynamic stress is the peak short-circuit current as the highest instantaneous value of the short-circuit current. The characteristic for the thermal stress of the short-circuit current is the rms value of the short-circuit current for its duration. SIL (Safety Integrity Level) A discrete level (one of three possible levels) for defining the requirements to be met by the safety integrity of safety-related control functions. SIL 3 is the highest and SIL 1 the lowest safety integrity level. Siemens IC /5

6 Glossary Smooth ramp-down The same principle is used during the ramp-down operation as for soft starting. This way the torque generated in the motor is slowly reduced, thus enabling a smooth ramp-down of the application. During a smooth ramp-down, the free or natural ramp-down of the load is prolonged. This function is set if there is a need to prevent the load from being stopped abruptly. Applications involving small mass inertia values or high counter-rotating torques are typical examples. Soft starters A motor starter which reduces the motor's starting torque (tightening torque) and starting current in order to reduce vibrations on the driven machine and current peaks in the line supply. The starting torque is reduced because the control supply voltage at the beginning is lower than the motor's rated voltage (the starting torque is proportional to the square of the applied voltage). The terminal voltage can be increased as soon as the motor is running. Classic methods for reducing the terminal voltage are for example wye-delta starting, start-up through resistors in the stator and starting with an autotransformer. The use of solid-state motor controllers with switched thyristor circuits for controlling the terminal voltage on squirrel-cage motors is becoming increasingly widespread. See also "Soft starting" and "Smooth ramp-down". Soft starting During the start-up operation, the absorbed starting current and the starting torque generated in the motor are regulated by a solid-state soft starter on the basis of the motor voltage control (phase control). Starting current Three-phase asynchronous motors have a high direct-on-line starting current. Depending on the motor version it can amount to between three times and fifteen times the rated operational current. Seven to eight times the rated motor current can be taken as a typical value. Starting voltage With SIRIUS soft starters, the level of the starting voltage defines the switch-on torque of the motor. A lower starting voltage results in a lower tightening torque and a lower starting current. The starting voltage should be selected such that the motor starts up immediately and smoothly once the start command goes to the soft starter. Start-up detection on soft starters SIRIUS 3RW40 soft starters feature internal start-up detection. When a motor ramp-up is detected, the motor voltage is increased immediately to 100 % of the mains voltage. The internal bypass contacts close and the thyristors are bridged. Switching frequency Number of operating cycles per unit of time (e.g. 15 operations per hour). To prevent thermal overloading of the SIRIUS soft starters, it is imperative to comply with the maximum permissible switching frequency. The switching frequency of SIRIUS soft starters size S0 to S3 can be increased by using an optional auxiliary fan. Switching technology Basically a distinction is drawn between two switching technologies: On the electromechanical side there are contactors, contactor assemblies and compact starters which can be used to implement solutions for direct-on-line starting, reversing starting and wye-delta starting. Frequent switching or reversing, soft starting and smooth ramp-down are performed on the other hand with solid-state controls: solid-state switching devices and soft starters. The SIRIUS modular system has the right solution for each switching technology. Temperature compensation On inverse-time (thermally) delayed overload releases and relays, the tripping time is influenced not only by the current but also by the ambient temperature. The effect of the ambient temperature is compensated by an additional bimetal strip which is not heated by the current. Solid-state compensation is possible for solid-state overload relays. Terminals for "Self-Protected Combination Motor Controller (Type E)" The terminals comply with the required clearance and creepage distances according to UL 508 (type E). Thermistor motor protection Protection of the motor through temperature sensors fitted in the windings (PTC sensors). These directly monitor the winding temperature. Three-phase busbars The three-phase busbar enables several motor starter protectors or compact starters to be fed in through one feeder terminal. Tightening torque The tightening torque and the breakdown torque can normally be assumed to amount to between two and four times the rated torque. For the loaded machine this means that the start-up and acceleration forces give rise to a higher mechanical load on the machine and the goods being conveyed than compared to operation at rated values. Time-delayed auxiliary switch A component which unites various auxiliary switch combinations and as a general rule can also be retrofitted to a control. Timing relays A control with solid-state time delay which opens or closes contacts after a delay according to the set time. Trip class (CLASS) The trip class of an inverse-time delayed overload relay (including thermal and solid-state overload relays and releases) indicates the maximum tripping time under a given load from cold. The trip class number (e.g. CLASS 10, 20, 30) stands for the maximum permissible tripping time in seconds when the relay is loaded with symmetrical 3-pole loading from cold with 7.2 times the current setting (IEC ; DIN VDE 0660 Part 107). Trip classes 20 and 30 are used for example for motor protection in heavy starting conditions. Tripping characteristic The graphical representation of the connection between the tripping time and the influencing variable is shown in the tripping characteristic curve. The time/current diagram shows for example how long the release or the tripping relay takes to respond to a specific current. Tripping current (of an overload release) Value of the current at which a trip releases within a specified time. Two-phase control Two of three active phases are controlled by means of semiconductors. With SIRIUS 3RW30 and 3RW40 soft starters, for example, two inverse-parallel switched thyristors lie in each of the phases L1 and L3. Phase L2 is passed through the starter as an uncontrolled phase using a copper link and is connected directly to the corresponding output terminal. /6 Siemens IC

7 Glossary Types of coordination EN (VDE 0660 Part 102) and IEC make a distinction between two different types of coordination which are referred to as type of coordination "1" and type of coordination "2". Any short circuits that occur are cleared safely by both types of coordination. The only differences concern the extent of the damage caused to the device by a short circuit. With type of coordination "1" the fuseless load feeder may be non-operational after a short circuit has been cleared. Damage to the contactor or to the overload release is permissible. For 3RA2 load feeders, the motor starter protector itself always achieves type of coordination "2". By contrast, with type of coordination "2" there must be no damage to the overload release or to any other component after a short circuit has been cleared. The 3RA2 fuseless load feeder can resume operation without needing to be partially renewed. At most, welding of the contactor contacts is permissible if they can be disconnected easily without any significant deformation. Utilization categories According to IEC , the intended use and stress of power contactors can be identified by specifying the utilization category in conjunction with the rated operational current or motor rating and the rated voltage. An example is utilization category AC-3 for starting and switching off squirrel-cage motors. Voltage ramp With SIRIUS 3RW30 and 3RW40 soft starters, soft starting is achieved using a voltage ramp. The motor's terminal voltage is raised during an adjustable starting time from a parameterizable starting voltage to the mains voltage. Wye-delta contactor assembly A contactor assembly which during start-up switches the motor into a star circuit (one third the starting current compared to delta starting) and after a while changes over to the delta circuit. Wye-delta contactor assemblies are used where a high starting current has to be prevented in order to reduce the effects on the mechanical components or mains. Wye-delta starter See wye-delta contactor assembly Siemens IC /7

8 Training Faster and more applicable know-how: Hands-on training from the manufacturer SITRAIN the Siemens Training for Industry provides you with comprehensive support in solving your tasks. Training by the market leader in automation and plant engineering enables you to make independent decisions with confidence. Especially where the optimum and efficient use of products and plants are concerned. You can eliminate deficiencies in existing plants, and exclude expensive faulty planning right from the beginning. First-class know-how directly pays for itself: In shorter startup times, high-quality end products, faster troubleshooting and reduced downtimes. In other words, increased profits and lower costs. Achieve more with SITRAIN Shorter times for startup, maintenance and servicing Optimized production operations Reliable configuration and startup Minimization of plant downtimes Flexible plant adaptation to market requirements Compliance with quality standards in production Increased employee satisfaction and motivation Shorter familiarization times following changes in technology and staff SITRAIN highlights Top trainers Our trainers are skilled teachers with direct practical experience. Course developers have close contact with product development, and directly pass on their knowledge to the trainers. Practical experience The practical experience of our trainers enables them to teach theory effectively. But since theory can be pretty drab, we attach great importance to practical exercises which can comprise up to half of of the course time. You can therefore immediately implement your new knowledge in practice. We train you on stateof-the-art methodically/didactically designed training equipment. This training approach will give you all the confidence you need. Wide variety With a total of about 300 local attendance courses, we train the complete range of Siemens Industry products as well as interaction of the products in systems. Tailor-made training We are only a short distance away. You can find us at more than 50 locations in Germany, and in 62 countries worldwide. You wish to have individual training instead of one of our 300 courses? Our solution: We will provide a program tailored exactly to your personal requirements. Training can be carried out in our Training Centers or at your company. The right mixture: Blended learning "Blended learning" means a combination of various training media and sequences. For example, a local attendance course in a Training Center can be optimally supplemented by a teachyourself program as preparation or follow-up. Additional effect: Reduced traveling costs and periods of absence. Contact Visit our site on the Internet at: or let us advise you personally. SITRAIN Customer Support Germany: Phone: +49 (911) Fax: +49 (911) info@sitrain.com /8 Siemens IC

9 Ordering notes Logistics General With regard to delivery service, communications and environmental protection, our logistics service ensures "quality from the moment of ordering right through to delivery". By designing our infrastructure according to customer requirements and implementing electronic order processing, we have successfully optimized our logistics processes. We are proud of our personal consulting service, on-time deliveries and 1-day transport within Germany. To achieve this, we supply the preferred types marked with } ex warehouse. We regard the DIN ISO 9001 certification and consistent quality checks as an integral part of our services. Electronic order processing is fast, cost-efficient and error-free. Please contact us if you want to benefit from these advantages. Packaging, packing units The packaging in which our equipment is dispatched provides protection against dust and mechanical damage during transport, thus ensuring that you receive our products in a perfect state. We select our packaging for maximum environmental compatibility and reusability (e.g. crumpled paper for protection during transport in packages up to 32 kg) and, in particular, with a view to reducing waste. With our multi-unit packaging and reusable packaging, we offer you specific types of packaging that are both kind to the environment and tailored to your requirements: Your advantages at a glance: Lower order costs. Cost savings through uniform-type packaging: low/no disposal costs. Reduced time and cost thanks to short unpacking times. "Just-in-time" delivery directly to the production line helps reduce stock: cost savings through reduction of storage area. cost savings through reduction of storage area. Fast assembly thanks to supply in sets. Standard Euro boxes - corresponding to the Euro pallet modular system - suitable for most conveyor systems. Active contribution to environmental protection. Unless stated otherwise in the "Selection and ordering data" of this catalog, our products are supplied individually packed. For small parts/accessories, we offer you economical packaging units as standard packs containing more than one item, e.g. 5, 10, 50 or 100 units. It is essential that whole number multiples of these quantities be ordered to ensure satisfactory quality of the products and problem-free order processing. The products are delivered in a neutral carton. The label includes warning notices, the CE mark and product description information in English and German. In addition to the (MLFB) and the number of items in the packaging, the Instr. is also specified for the operating instructions. It can be obtained from your local Siemens representative (you will find a list of your local Siemens representatives at The device of most devices can also be acquired through the EAN barcode to simplify ordering and storage logistics. The related master data are available from your local Siemens representative. Siemens IC /9

10 Ordering notes Multi-unit and reusable packagings The devices listed in the table on page /11 can be ordered in multi-unit or reusable packagings (further versions on request). If ordering multi-unit or reusable packagings for the first time, please first consult your local Siemens representative with regard to pack type, quantity, delivery time and the precise order designation. Use of the reusable packaging is reserved solely for customers that have signed a packaging return agreement with their Siemens representative in advance. Multi-unit and reusable packagings are not available as a pack type for all products. Some products are unsuited for this pack type and would only involve an increased risk of damage in transit. For both pack types, the quantity of devices ordered (per ) must be divisible by the pack quantity. If this is not the case, the electronic order processing system rounds up to the next integer multiple of packagings. Multi-unit packaging Reusable packaging (uniform type) Standard reusable packagings contain uniform-type, nonpacked individual products (1 device type) in a reusable standard Euro box (ENK) made of durable molded plastic with foam inserts for protection during transport. The standard Euro box (ENK) also serves as transport packaging. The reusable packagings (ENK) plus foam inserts are returned by the customer (free of charge) to the supply base. Please contact your Siemens representative (you will find Siemens representatives at to clarify the delivery details or conditions for delivery in reusable packagings (ENK). Suitable arrangements will then be agreed with you. Products in a quantity sufficient to fill a multi-unit packaging: 1/2 (W96) and 1/4 (W97) ENK As standard, multi-unit packs contain uniform-type, unpacked single devices (1 device type) in an appropriately sized carton made of recyclable cardboard. The products of the SIRIUS range can be ordered in units of 1/1, 1/2, 1/4 and 1/8 standard Euro boxes (ENK). Set deliveries (reusable, different devices) On request, we also deliver order-related packs of larger quantities of devices in a standard Euro box (ENK). Please contact your Siemens representative to clarify the delivery details or conditions for set supply or delivery in reusable packagings. Suitable arrangements will then be agreed with you. Packaging dimensions Packing material Length mm Height mm Width mm ENK W W W W /10 Siemens IC

11 Ordering notes Multi-unit and reusable packaging, quantity in units, supplied in indivisible pack quantities Devices Size Reusable Multi-unit Contactors 3RT A..1/2 3RT B..1/2 3RT A/B... 3RT A/B..0 3RT A/B..0 3RT10 3..A..0/4 3RT10 3..B..0 3RT10 3..B..4 S00 S00 S00 S0 S0 S2 S2 S2 X95 (1/1 ENK) W95 (1/1 ENK) W96 (1/2 ENK) W97 (1/4 ENK) W98 (1/8 ENK) On req. On req. On req. On req. On req. Snap-on auxiliary switch blocks 3RH F./GA/HA On req Contactor relays 3RH21.. 1A..0 3RH21.. 2A/B..0 Motor starter protectors 3RV /0/5 3RV /0/5 3RV /0/5 3RV /0/5 S00 S00 S00 S00 S0 S On req. On req. On req. On req. On req. On req RV /5 S2 24/24 24/ 12/12 5/ 2/ Thermally delayed overload relays 3RU21..B0 3RU21..C0 3RU B0 3RU C0 S00 S00 S0 S On req. On req. On req. On req. 3RU B0 S Solid-state timing relays 3RP RP RP15 1/2..A.30 3RP15 2..B.30 3RP15 4..B.31 3RP15 74.N Devices Reusable Multi-unit 3SB pushbuttons and indicator lights Complete units and actuators (except EMERGENCY-STOP, mushroom pushbuttons and key-operated switches) Complete units and actuators (EMERGENCY-STOP, mushroom pushbuttons and key-operated switches) Contact blocks Holder Supports, blanking plugs X95 X90 W95 W96 3TK28 safety relays When ordering products in multi-unit packagings, the of the product concerned must be supplemented with " Z" and, in addition, the order code X90, or for products from the SIRIUS range, the order code W9.. Example: 3RT AB00 Z W96 + quantity: 24 For products packed in reusable packaging, the must be supplemented with " Z" and the order code X95. Example: 3RT AB00 Z X95 + quantity: 48 Ordering special versions Small orders For ordering products that differ from the versions listed in the catalog, the order number specified in the catalog must be supple- processing are greater than the order value. We recommend When small orders are placed, the costs associated with order mented with " Z"; the required features must be specified by therefore that you combine several small orders. Where this is means of the alphanumeric order codes or in plain text. not possible, we unfortunately have to charge a processing supplement of 20. to cover our costs for order processing and invoicing for all orders with a net goods value of less than Siemens IC /11

12 Further documentation Overview Industrial controls We regard product support as just as important as the products and systems themselves. Visit our site on the Internet for a comprehensive range of material on SIRIUS Industrial Controls, such as Operating instructions and manuals for direct download Online registration for seminars and events Up-to-date answers to your queries and problems Software upgrades and updates for fast download Telephone assistance in more than 190 countries Photos and graphics for external use and much, much more - all conveniently and easily accessible at: Information and download center You will find information material such as catalogs, customer magazines, brochures and trial versions of software for Industrial Controls on the Internet at: You can order the available documents or download them in popular file formats (PDF, ZIP) from this site. eassistance SIRIUS eassistance offers you support in all project phases. From initial information about the configuration to start-up and service SIRIUS eassistance is there to help you 24/7. For example: My Documentation Manager Compile your documentation as you prefer! SIRIUS System Configurator Configure individual SIRIUS products or entire feeders conveniently, quickly and errorfree. Direct ordering through Industry Mall is possible. CAx Online Generator Comprehensive CAx data for your configuration at the press of a button (e.g. 3D models, 2D dimensional drawings, EPLAN electric P8 macros, certificates). Free, clearly arranged and updated daily. For up to 80% reduction in configuring times! For more information see: /12 Siemens IC

13 Standards and approvals Approvals, test certificates, characteristic curves Safety characteristics An overview of the certificates available for Industrial Control In the following standards, the so-called B10 values for calculating the safety integrity or safety integrity level (SIL) in functional products along with more technical documentation can be consulted daily on the Internet at: safety at a high or continuous demand rate are required also for electromechanical switchgear: IEC "Safety of machines - Functional safety of safety-related electrical, electronic and programmable electronic control systems", ISO "Safety of machines - Safety-related components of controls - Part 1: General principles". Failure rates of electromechanical components are required for calculating the safety integrity or safety integrity level (SIL) in functional safety: - in the manufacturing industry at a high demand rate - in the process industry at a low demand rate Further requirements are laid down in IEC "Functional safety - Safety instrumented systems for the process industry sector - Part 1: Framework, definitions, system, hardware and software requirements". The German versions of the above standards are: IEC (VDE ), October 2005, which since Dec. 31, 2005 has been harmonized as EN under the Machinery Directive, EN ISO :2008, IEC (VDE 810-1). The TÜV-tested Safety Evaluation Tool assists in calculating the safety function as verification for the machine documentation. It is available on the Internet at Product support: Approvals/certificates At you will also find examples of functions with calculations according to the current standards. Definitions λ (t) dt is the probability that a unit which has not failed by a certain time t will fail in the following interval (t; t +dt). Failure rates have the dimension 1/time unit, e.g. 1/h. Failure rates for components are often specified in FIT (failures in time unit): 1 FIT equals 10-9 /h. From the failure rate it is possible to derive a (mathematical) distribution function of the failure probability: F(t) = 1 - exp(-λt), with λ as constant failure rate The mean value of this exponential distribution is also referred to as: - Mean Time To Failure (MTTF) in the case of irreparable components; 63.2 % of components fail by the MTTF. - Mean Operating Time Between Failures (MTBF) in the case of reparable components. MTTF = 1/λ (MTTF is a statistical mean value but no guarantee for endurance) Electromechanical components are often irreparable components. In general, the failure rate of monitored units changes with age. Product support: Characteristic curves Siemens IC /13

14 Standards and approvals The B10 value for devices subject to wear is expressed in number of operating cycles: it is the number of operating cycles after which 10 % of the test specimens fail in the course of an endurance test (or: the number of operating cycles after which 10 % of the devices have failed). For low demand rates (mainly in the process industry), the failure rate and not the B10 value is used to determine the failure probability. Standard B10 values at a high demand rate With the help of the B10 value and a simplified formula (see section of IEC 62061), the user can then calculate the total failure rate of an electromechanical component: λ = 0.1 x C/B10 with C = operating cycles per hour. C is specified by the user. The failure rate is made up of safe (λ S ) and dangerous (λ D ) failures: λ = λ S + λ D or λ D = [share of dangerous failures in %] x λ λ S = [share of safe failures in %] x λ The failure rate of the dangerous failures λ D of the components used is needed for further calculations. Listed in the following table are the standard B10 values and the share of dangerous failures for SIRIUS product groups at a high demand rate. Standard B10 values (at a high demand rate) SIRIUS product group (electromechanical components) EMERGENCY-STOP control devices (with positive-opening contacts) - pulled to unlatch - rotated to unlatch (also with lock) Cable-operated switches for EMERGENCY-STOP function (with positive-opening contacts) Standard position switches (with positive-opening contacts) Position switches with separate actuator (with positive-opening contacts) Position switches with tumbler (with positive-opening contacts) Hinge switches (with positive-opening contacts) Pushbuttons (non-latching), with positive-opening contacts) Contactors / motor starters (with positively driven contacts in the case of 3RH/3TH and mirror contacts in the case of 3RT/3TF) Standard B10 value (operating cycles) Share of dangerous failures 20 % 20 % % % % % % % % The B10 d value used in EN ISO :2008 is determined as follows: B10 d = B10 Share of dangerous failures Calculation example A protective door is monitored by a position switch with a separate actuator. The protective door is opened 4 times an hour. The overall failure rate of the position switch is: λ = 0.1 C/B10 [failures/h] λ = 0.1 4/ = [failures/h] The dangerous failure rate is calculated with: λ D = 20 % of λ = [failures/h] λ D = [failures/h] Standard failure rates (at a low demand rate) On the basis of the failure rates it is possible to calculate the average probability of failure on demand (PFD avg ) of a PLT protective device. A so-called low demand rate is assumed, meaning the rate of demand on the safety-related system amounts to no more than once a year and is not greater than double the frequency of the repeat test. A repeat test once a year is recommended for electromechanical components in order to reveal passive faults. For special applications it is possible, in agreement with the inspecting institution (e.g. a technical inspectorate, government agency or the like) to extend the test intervals by using suitable solutions (e.g. a multi-channel version etc.). Under the above conditions and in compliance with the requirements laid down in IEC it is possible to achieve SIL 2 with a single-channel design and SIL 3 with a two-channel design. Listed in the following table are the standard failure rates and the share of dangerous failures for SIRIUS product groups at a low demand rate. Standard failure rates at a low demand rate SIRIUS product group (electromechanical components) Standard failure rates (in FIT) 1) Share of dangerous failures 2) EMERGENCY-STOP control devices % (with positive-opening contacts) Cable-operated switches for % EMERGENCY-STOP function (with positive-opening contacts) Standard position switches % (with positive-opening contacts) Position switches with separate actuator % (with positive-opening contacts) Position switches with tumbler % (with positive-opening contacts) Hinge switches % (with positive-opening contacts) Pushbuttons (non-latching) % (with positive-opening contacts) Contactors / motor starters (with 100 < 40 % positively driven contacts in the case of 3RH/3TH and mirror contacts in the case of 3RT/3TF) 1) The failure rates specified in the table were limited to 100 FIT. 2) Valid only under the previously mentioned conditions. /14 Siemens IC

15 Standards and approvals Standards IEC EN DIN VDE Title Low-voltage switchgear and controlgear - General rules Circuit-breakers Switches, disconnectors, switch-disconnectors and fuse-combination units Contactors and motor-starters - Electromechanical contactors and motor-starters Contactors and motor-starters - AC semiconductor motor controllers and starters Contactors and motor-starters - AC semiconductor controllers and contactors for non-motor loads Control circuit devices and switching elements - Electromechanical control circuit devices Control circuit devices and switching elements - Proximity switches Control circuit devices and switching elements - Requirements for proximity devices with defined behaviour under fault conditions Control circuit devices and switching elements - Electrical emergency stop device with mechanical latching function Control circuit devices and switching elements - DC interface for proximity sensors and switching amplifiers (NAMUR) Control circuit devices and switching elements - Requirements for proximity devices with analogue output Control circuit devices and switching elements - Three-position enabling switches Control circuit devices and switching elements - Flow rate switches Multiple function equipment - Transfer switching equipment Multiple function equipment - Control and protective switching devices (or equipment) (CPS) Ancillary equipment - Terminal blocks for copper conductors Ancillary equipment - Protective conductor terminal blocks for copper conductors Ancillary equipment - Safety requirements for fuse terminal blocks Control units for built-in thermal protection (PTC) for rotating electrical machines Controller-device interfaces (CDIs) - Actuator sensor interface (AS-i) Low-voltage fuses - General requirements Supplementary requirements for fuse-links for the protection of semiconductor devices International Electrotechnical Vocabulary. Switchgear, controlgear and fuses Low-voltage switchgear and controlgear assemblies - Type-tested and partially type-tested assemblies Protection against electric shock - Protection against unintentional direct contact with hazardous live parts Protection against electric shock - Common aspects for installation and equipment Insulation coordination for equipment within low-voltage systems - Principles, requirements and tests Safety of machinery - Electrical equipment of machines - General requirements Electronic equipment for use in power installations Explosive atmospheres - Electrical installations design, selection and erection Explosive atmospheres - Equipment protection by pressurized enclosures "p" Electromechanical elementary relays - General requirements Time relays for industrial and residential use - Requirements and tests Connecting devices - Electrical copper conductors - Safety requirements for screw-type and screwlesstype clamping units - General requirements and particular requirements for clamping units for conductors from 0,2 mm 2 up to 35 mm ) Safety of power transformers, power supplies, reactors and similar products Part 1: General requirements and tests 1) Part 2-1: Particular requirements and tests for separating transformers and power supplies incorporating separating transformers for general applications ) Part 2-2: Particular requirements and tests for control transformers and power supplies incorporating control transformers ) Part 2-4: Particular requirements and tests for isolating transformers and power supply units incorporating isolating transformers ) Part 2-6: Particular requirements and tests for safety isolating transformers and power supply units incorporating safety isolating transformers ) Part 2-9: Particular requirements and tests for transformers and power supply units for class III handlamps for tungsten filament lamps ) Part 2-12: Particular requirements and tests for constant voltage transformers and power supply units for constant voltage ) Part 2-13: Particular requirements and tests for auto transformers and power supply units incorporating auto transformers ) Part 2-15: Particular requirements and tests for isolating transformers for the supply of medical locations ) Part 2-20: Particular requirements and tests for small reactors ) Safety of transformers, reactors, power supply units and combinations thereof - EMC requirements Power transformers - Part 11: Dry-type transformers 0552 Specification for variable-ratio transformers having current collectors which are moved transversely to the direction of the windings Electromagnetic compatibility (EMC) - Testing and measurement techniques - Overview of IEC series Electromagnetic compatibility (EMC) - Generic standards - Immunity for industrial environments Electromagnetic compatibility (EMC) - Generic standards - Emission standard for residential, commercial and light-industrial environments Electromagnetic compatibility (EMC) - Generic standards - Emission standard for industrial environments Instrument transformers - Part 1: Current transformers 1) VDE classification. Siemens IC /15

16 Standards and approvals UL CSA C22.2 ASME JIS Title 506 Specialty transformers 508 Industrial control equipment Low-voltage switchgear and controlgear - Part 1: General rules A Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor starters - Electromechanical contactors and motor starters 489 Molded case circuit breakers, molded case switches, and circuit breaker enclosures 1012 Power units other than CLASS Dry-type general purpose and power transformers 5085 Low-voltage transformers Medical electrical equipment, Part 1: General requirements for safety (IEC 60601, EN 60601, VDE ) 04 Electrical equipment for use in CLASS I and II, Division 2 and CLASS III hazardous (Classified) locations 1059 Terminal blocks 486A-486B Wire connectors 486E Equipment wiring terminals for use with aluminum and/or copper conductors 50 Enclosures for electrical equipment, non-environmental considerations 50E Enclosures for electrical equipment, environmental considerations No. 66 Specialty transformers No. 14 Industrial control equipment No Low-voltage switchgear and controlgear - Part 1: General rules No A Low-voltage switchgear and controlgear - Part 4-1: Contactor and motor starters - Electromechanical contactors and motor starters No. 5 Molded case circuit breakers, molded case switches, and circuit breaker enclosures No General use power supplies A17.5 / B 44.1 Elevator and escalator electrical equipment C Low-voltage switchgear and controlgear; Contactors and motor-starters Approval requirements valid in different countries Siemens low-voltage switchgear and controlgear are designed, manufactured and tested according to the relevant German standards (DIN and VDE), IEC publications and European standards (EN) as well as CSA and UL standards. The standards assigned to the single devices are stated in the relevant parts of this catalog. As far as is economically viable, the requirements of the various standards valid in other countries are also taken into account in the design of the equipment. In some countries (see table below), an approval is required for certain low-voltage switchgear and controlgear components. Depending on the market requirements, these components have been submitted for approval to the authorized testing institutes. In some cases, CSA for Canada and UL for the USA only approve special switchgear versions. Such special versions are listed separately from the standard versions in the individual parts of this catalog. For this equipment, partial limitations of the maximum permissible voltages, currents and ratings can be imposed, or special approval and, in some cases, special identification is required. For use on board ship, the specifications of the marine classification societies must be observed (see table below). In some cases, they require type tests of the components to be approved. Testing bodies, approval identification and approval requirements Country Canada 1) USA 1) China Government-appointed or private, officially CSA UL UL CQC recognized testing bodies (USA) Mark of conformity s c u cu c UUS c uus More information about UL and CSA see page /19. Marine classification societies u U c UUS c uus Approval requirement Remarks UL and CSA are authorized to grant approval certificates in accordance with Canadian and North American regulations. Please note: These approvals are not recognized in many cases and must be covered by additional approvals issued by the national testing agency. CCC Country Germany United Kingdom Name Germanischer Lloyd Lloyds Register of Shipping 1) For guide numbers and file numbers for approvals, please visit and select "Product Support". France Norway CIS Italy Poland USA Bureau Veritas Det Norske Veritas Russian Maritime Register of Shipping Registro Italiano Navale Polski Rejestre Statków Codes GL LRS BV DNV RMRS RINA PRS ABS American Bureau of Shipping / Siemens IC

17 Standards and approvals CE marking Manufacturers of products which fall within the subject area to which EC directives apply must identify their products, operating instructions or packaging with a CE marking of conformity. By attaching the CE marking, the manufacturer confirms that the product conforms to the relevant basic requirements of all directives applicable to the product. The marking is a mandatory requirement for putting products into circulation throughout the EC. All the products in this catalog are in conformance with the EC directives and bear the CE marking of conformity. Low-voltage directive EMC directive Machinery directive Ex protection directive The CE marking: >. ALPHA/LOVAG Siemens AG sits in the ALPHA committee of "ALPHA im VDE". The responsibility of manufacturers and the high quality of products are promoted by "ALPHA im VDE" by means of supportive procedural guidelines for testing equipment according to the currently valid standards. Providing specific conditions are fulfilled, "ALPHA im VDE" can also issue officially recognized product certificates if required. As a member of LOVAG, "ALPHA im VDE" is also working towards obtaining international recognition for declarations of conformity and certificates. LOVAG (Low-Voltage Agreement Group) is a body comprising international specialists from certification bodies and industry who are working together to create a standardized European certificate. List of LOVAG members ALPHA im VDE ASEFA ACAE SGS BELGIUM NV Division SGS CEBE Intertek Semko AB APPLUSS + CTL VEIKI-VNL Germany France Italy Belgium Sweden Spain Hungary Accident prevention Test certificates and approvals from IFA (institute for occupational safety and health of the German social accident insurance), SUVA (Swiss institute for accident prevention), BG ETEM (German trade association for energy, textiles, electrical goods and media products) and VDE are available for some devices in safety control systems. For details, see the respective product descriptions. Siemens IC /17

18 Standards and approvals Ex protection certificates for SIRIUS controls Motor protection devices that protect a motor installed in a potentially explosive atmosphere against overloading must comply with certain special requirements. These requirements are laid down in the following standards: EN EN EN EN EN EN EN EN EN Certification July 1, 2003 saw the dawning of a new era in the field of explosion protection. Since this date, only those devices and protection systems that have been certified for operation in potentially explosive atmospheres according to directive 94/9/EC can be brought into circulation within the European Union. Only those motor protection devices that have been constructed according to the above-mentioned standards and which have a declaration of conformity from the manufacturer based on a prototype test certificate may be brought into circulation within the member states of the EC. The quality management system of the manufacturer is also subjected to certain requirements and a "QM certificate" must be obtained for the manufacturer from a recognized authority. Certification of the QM system A certificate of approval for quality assurance production has been issued by DEKRA EXAM GmbH 1) with the number BVS 08 ATEX ZQS/E111 of DEKRA EXAM GmbH 1) according to Directive 94/9/EC. This certificate is valid for equipment groups I and II and categories M2 and 2: Safety and control devices for electrical equipment. Certificates For the 3RV, 3RU, 3RB, 3UF, 3RN and 3RW motor protection devices, the corresponding declarations of conformity and prototype test certificates for Category 2G, and to some extent 2D, are available and can be supplied on request. Declarations of conformity and prototype test certificates are available at for viewing and downloading. Selection box Description of certificate with view and download option Identifying markings All equipment must be marked in according to the ATEX guideline. The ATEX identification code contains the equipment group, the approved environment, the number of the certification authority and other technical data that was determined from the type test. For more information about ATEX see 1) DEKRA EXAM GmbH The certification authority of the "DEKRA EXAM GmbH" numbered as authority number 0158 according to Article 9 of Directive 94/9/EC of the European Parliament and Council dated March 23, 1994, certifies that Siemens Amberg and Cham maintains a quality system for production that satisfies IV of this Directive. Certificate of the AS-International Association for AS-Interface products AS-Interface products are tested and certified by the AS-International Association. The products have been tested in an accredited test laboratory according to testing guidelines. /18 Siemens IC

19 Standards and approvals Special standards for the USA and Canada In the USA and Canada, for machine tools and processing machines in particular, supply lines are laid using rubber insulated cable enclosed in heavy-duty steel piping similar to that used for gas or water pipe systems. The tubing system must be completely watertight and electrically conductive (especially sleeving and elbows). Since the tubing system can also be grounded, the cable entries of enclosed units equipped with heavy-gauge or metric threads must be fitted with metal adapters between these threads and the tube thread. The necessary adapters are specified for the switchgear as accessories; they should be ordered separately unless otherwise specified. Low-voltage switchgear and controlgear for auxiliary circuits (e.g. contactor relays, commanding and signaling devices and auxiliary switches/auxiliary contacts in general) are generally only approved by CSA and UL for "Heavy Duty" or "Standard Duty" and are identified either with these specifications in addition to the maximum permissible voltage or by using an abbreviation. The abbreviations are harmonized with IEC Table A.1 and correspond to the stated utilization categories. For various switching devices detailed in the catalog, a note has been included to the effect that, above a certain voltage, the auxiliary switches/auxiliary contacts can only be used if they have the same polarity. This means that the input terminals can only be connected to the same pole of the actuating voltage, e.g. "600 V AC above 300 V AC same polarity". Different features of UL approvals (for USA and Canada) Recognized Component Listed Product Devices are identified on the rating plate Devices are identified using the "UL listing mark" on the rating plate using the "UL recognition mark": e.g. USA: u LISTED XXX Canada: cu LISTED XXX USA: U, cuus IND. CONT. EQ. IND. CONT. EQ. Canada: cu, cuus (XXX stands for: UL Code Classification Number) Devices are approved as modules for "factory wiring", i.e.: Devices are approved for "field wiring", i.e.: as devices for installation in control systems, which are selected, installed, As devices for installation in control systems, which are completely wired by wired and tested entirely by trained personnel in factories, workshops or trained personnel in factories, workshops or elsewhere. elsewhere, according to the operating conditions. As single devices for sale in retail outlets in the USA/Canada. If devices are u or cu approved as "listed products", they are also approved as U or cu "recognized components". More information about UL and CSA see page /. Special standards for Russia, Australia and China GOST approval for Russia CCC approval A GOST approval is required for all products that are to be sold in Russia. The GOST mark has been obligatory on the packaging of all devices since mid All devices delivered to any part of the Russian Federation must have this customs certification. Since August 1, 2003, CCC approval is required for many products that are marketed in China. C-Tick licensing for Australia The C-Tick license is required for marketing Siemens components in Australia. Electronic devices must provide proof of EMC clearance in Australia, similar to the CE marking of conformity laid down by the EMC directive applicable in the EC and bear the "C-Tick" mark. These requirements have been in force since October 1st, Siemens IC /19

20 Quality management Quality management Certificates The quality management system of our Industry Automation division complies with the international standard EN ISO The products and systems described in this catalog are sold under application of a quality management system certified by DQS according to ISO The certificates are recognized in all IQ Net countries. DQS Registered Certificate No.: Siemens AG Industry Sector, Industry Automation Division Control Components and Systems Engineering Registered Certificate No.: QM08 Information on the certificates available (CE, UL, CSA, FM, shipping authorizations) for low-voltage control products can be found on the Internet at: In the Entry List you can use the certificate type (general product approval, explosion protection, test certificates, shipbuilding,...) as a filter criterion. /20 Siemens IC

21 Siemens contacts Partner at Industry Automation and Drive Technologies At Siemens Industry Automation and Drive Technologies, more than people are resolutely pursuing the same goal: longterm improvement of your competitive ability. We are committed to this goal. Thanks to our commitment, we continue to set new standards in automation and drive technology. In all industries worldwide. At your service locally, around the globe for consulting, sales, training, service, support, spare parts... on the entire Industry Automation and Drive Technologies range. Your personal contact can be found in our Contacts Database at: You start by selecting a Product group, Country, City, Service. Siemens IC /21

22 Siemens Solution Partner Automation Overview Siemens Solution Partner Automation Solution Partner Finder Solution Partner: Highest quality - guaranteed The products and systems from Siemens Industry Automation and Drive Technologies offer the ideal platform for all automation applications. Under the name of Siemens Solution Partner Automation, selected system integrators around the world act as uniformly qualified solution providers for the Siemens range of products and services in the fields of automation and drives. Day after day, they utilize their qualified product and system know-how as well as their excellent industry expertise to your advantage for all requirements. The partner emblem is the guarantee and indicator of proven quality. The basis for this are defined quality features that identify Solution Partners as reliable and competent solution providers: Solution quality Always a good result with tried and tested solutions expertise. Expert quality Certified technical competence ensures maximum efficiency. Project quality With proven project experience straight to the target. Portfolio quality Comprehensive portfolio for state-of-the-art solutions from a single source. The Siemens Solution Partner Program helps you to find the optimum partner for your specific requirements. Support is provided by the Solution Partner Finder, a comprehensive online platform that showcases the profiles of all our solution partners. You can convince yourself of the competence of the respective Solution Partner by means of the references provided. Various search criteria are available for this purpose. Once you have located a partner, you are only one small step away from contacting them. Find the right partner here for your specific task and convince yourself of the solution competence provided: Additional information on the Siemens Solution Partner Program is available online at: /22 Siemens IC

23 External partners Our partner companies Your partners AXELENT GmbH Sigmaringer Straße 112 D Stuttgart Tel.: +49 (711) Fax.: +49 (711) Franz Binder GmbH & Co. Postfach 1152 D Neckarsulm Katalog Steckverbinder Tel.: +49 (7132) Fax: +49 (7132) Hans Georg Brühl GmbH Waldstraße 63 b D Netphen Tel.: +49 (2737) Fax: +49 (2737) info@schutzeinrichtungen.com EPHY-Mess GmbH Johannes-Gutenberg-Str. 2-6 D Hofheim-Wallau Tel.: +49 (6122) Fax: +49 (6122) info@ephy-mess.de FESTO AG & Co Ruiterstr. 82 D Esslingen Tel.: +49 (711) Fax: +49 (711) info@festo.de GMC-I Messtechnik GmbH, Thomas-Mann-Str. -20, D Nuremberg, Germany Tel.: +49 (911) Fax: +49 (911) info@gossenmetrawatt.com Harting Deutschland GmbH & Co. KG Simeonscarrè 1 D Minden Tel.: +49 (571) Fax: +49 (571) solution-partner@harting.com KnorrTec Kapellenbergstraße 34 D Beratzhausen Tel.: +49 (99493) Fax: +49 (99493) solution-partner@knorrtec.de Lumberg GmbH & Co. Im Gewerbepark 2 D Schalksmühle Tel.: +49 (2355) Fax: +49 (2355) info@lumberg.de mat Maschinen- und Anlagentechnik Dr. Becker GmbH Rudolf-Diesel-Straße Bargteheide Tel.: +49 (4532) Fax: +49 (4532) info@m-a-t.de Internet: mdexx GmbH Richard-Dunkel-Straße 120 D Bremen Tel.: +49 (421) Fax: +49 (421) Transformatoren@mdexx.com Internet: Murrplastik Systemtechnik GmbH Dieselstraße 10 D Oppenweiler Tel.: +49 (7191) Fax: +49 (7191) info@murrplastik.de Murrelektronik GmbH Falkenstraße 3 D Oppenweiler Tel.: +49 (7191) 47-0 Fax: +49 (7191) info@murrelektronik.com Pepperl+Fuchs Vertrieb Deutschland GmbH Lilienthalstraße 200 D Mannheim fa-info@de.pepperlfuchs.com Siebert Industrieelektronik GmbH P.O. Box 1180 D Eppelborn Tel.: +49 (6806) Fax: +49 (6806) Internet: WAGO Kontakttechnik GmbH & Co. KG Hansastraße 27 D Minden Tel.: +49 (571) Fax: +49 (571) info@wago.com KUPEK GmbH Beschaffung und Logistik Cortendorfer Straße 94 D Coburg Tel: +49 (9561) Fax: +49 (9561) info@kupek.de Weidmüller GmbH & Co. KG Ohmstraße 9 D Detmold Tel.: +49 (5231) Fax: +49 (5231) solution-partner@weidmueller.com WITTWER Industrielle Elektronik Hembacher Str. 4, Postfach 1147 D Schwarzenbruck-Lindelburg Tel.: +49 (9183) Fax: +49 (9183) info@wittwer.com Siemens IC /23

24 Online services: Information and ordering in the internet and on DVD Siemens Industry Automation and Drive Technologies in the WWW A detailed knowledge of the range of products and services available is essential when planning and configuring automation systems. It goes without saying that this information must always be fully up-to-date. Siemens Industry Automation and Drive Technologies has therefore built up a comprehensive range of information in the World Wide Web, which offers quick and easy access to all data required. Under the address you will find everything you need to know about products, systems and services. Product Selection Using the Interactive Catalog CA 01 of Industry Detailed information together with convenient interactive functions: The interactive catalog CA 01 covers more than products and thus provides a full summary of the Siemens Industry Automation and Drive Technologies product base. Here you will find everything that you need to solve tasks in the fields of automation, switchgear, installation and drives. All information is linked into a user interface which is easy to work with and intuitive. After selecting the product of your choice you can order at the press of a button, by fax or by online link. Information on the interactive catalog CA 01 can be found in the Internet under or on DVD. Easy Shopping with the Industry Mall The Industry Mall is the virtual department store of Siemens AG in the Internet. Here you have access to a huge range of products presented in electronic catalogs in an informative and attractive way. Data transfer via EDIFACT allows the whole procedure from selection through ordering to tracking of the order to be carried out online via the Internet. Numerous functions are available to support you. For example, powerful search functions make it easy to find the required products, which can be immediately checked for availability. Customer-specific discounts and preparation of quotes can be carried out online as well as order tracking and tracing. Please visit the Industry Mall on the Internet under: /24 Siemens IC

25 Service & Support The unmatched complete service for the entire life cycle Service Programs Technical Consulting Field Field Service Service Online Support Technical Support Training Spare Spare Parts Parts Engineering Support Modernization Services Optimization Services For machine constructors, solution providers and plant operators: The service offering from Siemens Industry, Automation and Drive Technologies includes comprehensive services for a wide range of different users in all sectors of the manufacturing and process industry To accompany our products and systems, we offer integrated and structured services that provide valuable support in every phase of the life cycle of your machine or plant - from planning and implementation through commissioning as far as maintenance and modernization. Our Service & Support accompanies you worldwide in all matters concerning automation and drives from Siemens. We provide direct on-site support in more than 100 countries through all phases of the life cycle of your machines and plants. You have an experienced team of specialists at your side to provide active support and bundled know-how. Regular training courses and intensive contact among our employees - even across continents - ensure reliable service in the most diverse areas. Online Support Technical Consulting The comprehensive online information platform supports you in all aspects of our Service & Support at any time and from any location in the world. automation/service&support Support in planning and designing your project: From detailed actual-state analysis, definition of the goal and consulting on product and system questions right through to the creation of the automation solution. Technical Support Expert advice on technical questions with a wide range of demand-optimized services for all our products and systems. automation/support-request Technical Assistance Expert technical assistance for Industrial controls. Tel.: +49 (911) Fax: +49 (911) Contact information is available in the Internet at: Siemens IC /25

26 Service & Support The unmatched complete service for the entire life cycle Engineering Support Support during project engineering and development with services fine-tuned to your requirements, from configuration through to implementation of an automation project. Modernization You can also rely on our support when it comes to modernization - with comprehensive services from the planning phase all the way to commissioning. Field Service Our Field Service offers you services for commissioning and maintenance - to ensure that your machines and plants are always available. Training Extend your competitive edge - through practical know-how directly from the manufacturer. Spare parts In every sector worldwide, plants and systems are required to operate with constantly increasing reliability. We will provide you with the support you need to prevent a standstill from occurring in the first place: with a worldwide network and optimum logistics chains. Service programs Our service programs are selected service packages for an automation and drives system or product group. The individual services are coordinated with each over to ensure smooth coverage of the entire life cycle and support optimum use of your products and systems. The services of a Service Program can be flexibly adapted at any time and used separately. Repairs Optimization Downtimes cause problems in the plant as well as unnecessary costs. We can help you to reduce both to a minimum - with our worldwide repair facilities. During the service life of machines and plants, there is often a great potential for increasing productivity or reducing costs. To help you achieve this potential, we are offering a complete range of optimization services. Examples of service programs: 7 Service contracts 7 Plant IT Security Services 7 Life Cycle Services for Drive Engineering 7 SIMATIC PCS 7 Life Cycle Services 7 SINUMERIK Manufacturing Excellence 7 SIMATIC Remote Support Services Advantages at a glance: 7 Reduced downtimes for increased productivity 7 Optimized maintenance costs due to a tailored scope of services 7 Costs that can be calculated and therefore planned 7 Service reliability due to guaranteed response times and spare part delivery times 7 Customer service personnel will be supported and relieved of additional tasks 7 Comprehensive service from a single source, fewer interfaces and greater expertise Contact information is available in the Internet at: /26 Siemens IC

For Operation in the Control Cabinet 3RW Soft Starters

For Operation in the Control Cabinet 3RW Soft Starters General Data Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations

More information

3RW Soft Starters. General data. 6/4 Siemens LV

3RW Soft Starters. General data. 6/4 Siemens LV General data Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of peaks Avoidance of mains voltage fluctuations during starting

More information

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options /2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /1 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions

More information

3RW Soft Starters. General data. 6/2 Siemens LV 1 N SIRIUS Soft Starters 01/2008. Siemens AG 2008

3RW Soft Starters. General data. 6/2 Siemens LV 1 N SIRIUS Soft Starters 01/2008. Siemens AG 2008 Siemens AG 2008 General data The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations

More information

Protection Equipment. Overload Relays. Reference Manual 04/2011. Industrial Controls. Answers for industry.

Protection Equipment. Overload Relays. Reference Manual 04/2011. Industrial Controls. Answers for industry. Protection Equipment Overload Relays Reference Manual 04/2011 Industrial Controls Answers for industry. Protection Equipment 2 3 7 7 8 9 14 1 16 17 18 18 19 20 2 26 27 28 29 30 32 37 38 40 42 Introduction

More information

SINAMICS GM150 IGCT version

SINAMICS GM150 IGCT version /2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /14 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions

More information

Air Circuit Breakers

Air Circuit Breakers Siemens AG 204 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23

More information

Air Circuit Breakers

Air Circuit Breakers Siemens AG 203 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Soft starters SIRIUS 3RW30 / 3RW40. Manual 01/2010. Industrial Controls. Answers for industry.

Soft starters SIRIUS 3RW30 / 3RW40. Manual 01/2010. Industrial Controls. Answers for industry. Soft starters Manual 01/2010 Industrial Controls Answers for industry. Introduction 1 Safety information 2 Industrial Controls Soft starters Manual Product description 3 Product combinations 4 Functions

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

SIRIUS 3RU2 Thermal Overload Relays

SIRIUS 3RU2 Thermal Overload Relays Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

Overload Relays. SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A for standard applications. 5/78 Siemens IC Overview

Overload Relays. SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A for standard applications. 5/78 Siemens IC Overview SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors.

More information

Application Description

Application Description -14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....

More information

SIRIUS Soft Starters Introduction

SIRIUS Soft Starters Introduction Introduction Overview Products at a glance 3RW30/3RW31 3RW40 3RW44 Class 73/74 Enclosed 16 CONTROL SIRIUS soft starters for standard applications SIRIUS 3RW30 soft starters SIRIUS 3RW40 soft starters for

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

Motor Starters, Soft Starters and Load Feeders

Motor Starters, Soft Starters and Load Feeders Motor Starters, Soft Starters and Load Feeders Industrial Controls Product Catalog 201 Section 3RW30 3RW40 3RW30 contents Introduction /2 For Operation in the Control Cabinet General data /3 3RW30 for

More information

Manual. Industrial Controls. Protection Devices. SIRIUS 3RV Motor Starter Protectors. Edition 12/2017. siemens.com

Manual. Industrial Controls. Protection Devices. SIRIUS 3RV Motor Starter Protectors. Edition 12/2017. siemens.com Manual Industrial Controls Protection Devices Edition 12/2017 siemens.com Introduction 1 Standards 2 Industrial Controls Protection devices SIRIUS 3RV Motor Starter Protectors Manual Product description

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Siemens AG RW BB14 3RW BB14 3RW BB14. per PU three-phase induction opera- Rated Rated power of three-phase

Siemens AG RW BB14 3RW BB14 3RW BB14. per PU three-phase induction opera- Rated Rated power of three-phase Siemens AG 2008 3RW Soft Starters Selection and ordering data 28-1BB14 38-1BB14 47-1BB14 Ambient temperature 40 C Ambient temperature 50 C Size DT Order No. Price Rated Rated power of Rated Rated power

More information

3TM Vacuum Contactors

3TM Vacuum Contactors Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents

More information

Motor Starters, Soft Starters and Load Feeders

Motor Starters, Soft Starters and Load Feeders Motor Starters, Soft Starters and Load Feeders Contents Pages Introduction................................... 7/2 For Operation in the Control Cabinet General data.................................. 7/3

More information

Softstarters Softstarters

Softstarters Softstarters , PSS & PST(B), PSS & PST(B) Low Voltage Products & Systems 6.1 General information PSR PSS From the moment the first electrical motors appeared, engineers have been searching for a way to avoid electrical

More information

For Operation in the Control Cabinet

For Operation in the Control Cabinet For Operation in the Cabinet 3RW30 for standard applications Overview The SIRIUS 3RW30 soft starters reduce the motor voltage through variable phase control and increase it in ramp-like mode from a selectable

More information

ZE motor-protective relay Overload monitoring of EEx e motors

ZE motor-protective relay Overload monitoring of EEx e motors Building Automation Industrial Automation Systems Hardware and Engineering ZE motor-protective relay Overload monitoring of EEx e motors 0/0 AWB300-5GB A Think future. Switch to green. All brand and product

More information

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J Protection Equipment Siemens AG 2015 Click on the Article No. in the catalog PDF to access it in the Industry Mall and get all related information. Article-No. 3RA1943-2C 3RA1943-2B 3RA1953-2B 3RA1953-2N

More information

Motor Starters, Soft Starters and Load Feeders

Motor Starters, Soft Starters and Load Feeders Motor Starters, Soft Starters and Load Feeders Contents Pages Introduction............................................................6/2 For Operation in the Control Cabinet General data........................................................6/3

More information

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4 CHAPTER ELECTRICAL 2 INSTALLATION Contents of this Chapter... 2.1 Warnings & Agency Approvals..................2 2 2.1.1 Isolation..............................................2 2 2.1.2 Electrical Power

More information

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD. DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN

More information

Unit Protection System for Pumped-Storage Power Stations

Unit Protection System for Pumped-Storage Power Stations Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve

More information

Selection Guide Motor Control Device Solutions

Selection Guide Motor Control Device Solutions Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements

More information

Industrial Controls. Load Feeder. Configuring SIRIUS Innovations Selection data for Fuseless and Fused Load Feeders. Configuration Manual 04/2011

Industrial Controls. Load Feeder. Configuring SIRIUS Innovations Selection data for Fuseless and Fused Load Feeders. Configuration Manual 04/2011 Load Feeder Selection data for Fuseless and Fused Load Feeders Configuration Manual 04/2011 Industrial Controls Answers for industry. Introduction 1 General information 2 Industrial switchgear Load feeders

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.0 008 Answers for energy. R-HG11-17.tif Siemens HG 11.0 008 Contents Contents Page SION Vacuum Circuit-Breakers Description General Construction

More information

Reliably Switching Highest Currents up to 2000 A

Reliably Switching Highest Currents up to 2000 A www.moeller.net Reliably Switching Highest Currents up to 2000 A The complete range for the motor circuit. From contactors to efficient motor-starters to controlled drives. New solutions that rely on communication.

More information

SIRIUS Configuration

SIRIUS Configuration SRUS Configuration Selection data for Fuseless Load Feeders Brochure January 2008 www.siemens.com/automation SRUS the Modular System Family for the Switching, rotecting and Starting of s n order to simplify

More information

3RW40/44 Catalog Supplement July sirius 3RW40 3RW44

3RW40/44 Catalog Supplement July sirius 3RW40 3RW44 RW40/44 Catalog Supplement July 2005 sirius RW40 RW44 Reduced Voltage Electronic Soft Starts Catalog Technical information SIRIUS soft starters /2 Introduction / General data For standard applications

More information

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads

More information

Sirius IE3/IE4 ready. White Paper January

Sirius IE3/IE4 ready. White Paper January www.siemens.com/ie3ready Sirius IE3/IE4 ready The effects of EU regulations 640/2009 and 04/2014 on the selection and operation of three-phase squirrel cage induction motors in line operation and their

More information

Industrial Controls. Load Feeders. SIRIUS - SIRIUS 3RA Load Feeders. Gerätehandbuch. Siemens Controls 09/2016. Edition. siemens.

Industrial Controls. Load Feeders. SIRIUS - SIRIUS 3RA Load Feeders. Gerätehandbuch. Siemens Controls 09/2016. Edition. siemens. Industrial Controls Load Feeders SIRIUS - SIRIUS 3RA Load Feeders Gerätehandbuch Manual Edition Siemens Controls 09/2016 siemens.com Introduction 1 Standards 2 Industrial Controls Load feeders Manual

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

Protection Equipment. 5/2 Introduction

Protection Equipment. 5/2 Introduction Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

Application Mini Contactors for Motors and Resistive Loads

Application Mini Contactors for Motors and Resistive Loads Delivery program Contactor, 4p, 4kW/400V/AC3 Part no. DILEM4-G(24VDC) Catalog No. 012701 Eaton Catalog No. XTMF9A00TD Product range Contactors Application Mini Contactors for Motors and Resistive Loads

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60470 Second edition 1999-10 High-voltage alternating current contactors and contactor-based motor-starters Contacteurs pour courants alternatifs haute tension et démarreurs

More information

THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS. MCD 3000 Soft starter

THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS. MCD 3000 Soft starter THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS MCD 3000 Soft starter THE PERFECT SOFTENER OF ROUGH STARTS The MCD Soft starter ranging from 7.5 to 800 kw is the optimum solution to a range of

More information

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.02 2011 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.02 2011 Contents SION Vacuum Circuit-Breakers Medium-Voltage Equipment Catalog

More information

Low-Voltage Controls and Distribution

Low-Voltage Controls and Distribution Motor Starters, Soft Starters and Load Feeders 3RW30 / 3RW40 Soft Starters Reference Manual April 2009 Low-Voltage Controls and Distribution Motor Starters, Soft Starters and Load Feeders 4 Introduction

More information

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00, Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS RV up to 00 A RV0-0DA5 CIRCUIT-BREAKER,

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Siemens AG Industrial Controls. SIRIUS 3R_1* in sizes S00/S0 to S12 SIRIUS. Catalog Add-On IC 10 AO. Edition Answers for industry.

Siemens AG Industrial Controls. SIRIUS 3R_1* in sizes S00/S0 to S12 SIRIUS. Catalog Add-On IC 10 AO. Edition Answers for industry. Industrial Controls SIRIUS 3R_1* in sizes S00/S0 to S12 SIRIUS Catalog Add-On IC 10 AO Edition 2014 Answers for industry. Related catalogs Miscellaneous Industrial Controls IC 10 SIRIUS Products for Automation

More information

E-12 Low-voltage Switchboard

E-12 Low-voltage Switchboard Guideline No.E-12 (201510) E-12 Low-voltage Switchboard Issued date: 20 October 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller A pre-engineered solution with an integrated circuit breaker disconnect and an Altistart 22 soft start in a stand-alone enclosure Make the

More information

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427 Data sheet CI-TI TM Contactors and Motor Starters Circuit Breakers November 2002 DKACT.PD.C00.L2.02 520B1427 Introduction Circuit breakers/manual motor starters cover the power ranges 0.09-12.5 kw This

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

System Manual 02/2008

System Manual 02/2008 System Manual 02/2008 SIRIUS Infeed System for 3RA6 sirius COMPACT STARTER Introduction 1 Product-specific information 2 SIRIUS industrial switchgear Load feeders, motor and soft starters System Manual

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2

More information

3RW Soft Starters. General data. 6/4 Siemens LV 1 T 2008

3RW Soft Starters. General data. 6/4 Siemens LV 1 T 2008 General data Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and smooth ramp-down 1) Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations

More information

Industry Automation Control Components

Industry Automation Control Components Industry Automation Control Components SIRIUS 3RV2 Motor Starter Protectors SIRIUS 3RV21 Motor Starter Protectors can be easily and flexibly combined with other SIRIUS devices to reduce space requirements

More information

ADS7 AC Contactor Starters

ADS7 AC Contactor Starters ADS7 AC Contactor Starters ADS7 starters fully comply with BS EN 60947-4-1, IEC 60947-4-1 and VDE 0660. The range offers a multitude of configurations and optional features including a complete choice

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Short form catalogue. Motor protection & control

Short form catalogue. Motor protection & control Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59

More information

RVS-AX Instruction Manual

RVS-AX Instruction Manual RVS-AX Analog Soft Starter 8-170A, 220-600V Instruction Manual Ver. 10/11/2009 2 Table of Content RVS-AX Instruction Manual 1. TABLE OF CONTENT 1. Table of Content...2 2. Safety & Warnings...3 2.1 Safety...3

More information

Reliably Switching Highest Currents up to 2200 A

Reliably Switching Highest Currents up to 2200 A www.moeller.net Reliably Switching Highest Currents up to 2200 A Product Information DIL M contactors DIL H contactors High Rated Contactors DIL: Switching High Currents Reliably Contactors DIL M from

More information

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting. DATASHEET - ZB12-2,4 Delivery program Overload relay, 1.6-2.4 A, 1N/O+1N/C Part no. ZB12-2,4 Catalog No. 278437 Eaton Catalog No. XTOB2P4BC1 EL-Nummer 0004131832 (Norway) Product range Overload relay ZB

More information

SIGNAL WORDS QUALIFIED PERSON

SIGNAL WORDS QUALIFIED PERSON SIGNAL WORDS The signal words Danger, Warning and Caution used in this manual indicate the degree of hazard that may be encountered by the user. These words are defined as: Danger - Indicates death or

More information

ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A

ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A ATyS d M Remotely operated Transfer Switching Equipment Transfer switches new The solution for > Applications with an external ATS/AMF controller > Building Management Systems (BMS) atys-md_002_b_1_cat

More information

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation Motor-protectivecircuit-breaker,3p,Ir=2.5-4A Partno. PKZM01-4 Articleno. 278482 CatalogNo. XTPB004BC1 Deliveryprogramme Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton

More information

Protective Devices: Circuit-Breakers 1 )

Protective Devices: Circuit-Breakers 1 ) Protective Devices: Circuit-Breakers 1 ) /2 Introduction SIRIUS circuit-breakers 1 ) up to 100 A / General data /20 For motor protection /22 For motor protection with overload relay function /23 For starter

More information

Overview. Contents. Overview

Overview. Contents. Overview 1/0 Overview 1 Contents Overview 3-pole Block Contactors and Motor Protection... 1/ 4-pole Block Contactors... 1/3 Contactors for Specific Applications... 1/4 Mini Contactors and Motor Protection... 1/

More information

Application example of a motor controlled by MCD100 and protected by a circuit breaker

Application example of a motor controlled by MCD100 and protected by a circuit breaker VLT T Soft Start Controller MCD 100 MCD 100 is a cost effective and extremely compact soft starter for AC motors up to 11 kw. Due to a unique semiconductor design MCD 100 is a true fit and forget product.

More information

S840, S845, S846 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D40.en

S840, S845, S846 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D40.en Snap-action switches S80, S85, S86 Series Single-break changeover, NC or NO contacts, positive opening operation and wiping action Catalogue D0.en Snap-action switches, S80, S85, S86 Series Single-break

More information

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer DATASHEET - ZB65-65 Delivery program Overload relay, 50-65A, 1N/O+1N/C Part no. ZB65-65 Catalog No. 278460 Eaton Catalog No. XTOB065DC1 EL-Nummer 0004131855 (Norway) Product range Overload relay ZB up

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

SIRIUS. Answers for industry.

SIRIUS. Answers for industry. s SIRIUS Datasheet 01 nswers for industry. Introduction Contactors and Contactor ssemblies SIRIUS RW Soft Starter Protection Equipment Load Feeders and Motor Starters for Use in the Control Cabinet Monitoring

More information

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France Contact us ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F-69687 Chassieu cedex / France You can find the address of your local sales organisation on

More information

Drive System Application

Drive System Application Drive System Application Example to calculate the limit values for SS1 and SLS Application description for SINAMICS G120 Warranty, liability and support Note The Application Examples are not binding and

More information

Braking Devices BR 230/ Assembly- and Commissioning Instructions

Braking Devices BR 230/ Assembly- and Commissioning Instructions electronic Braking Devices BR 230/400-10...400 Assembly- and Commissioning Instructions Quality is our Drive. BR 230/400-10...400 1 as per 04/10 11600.10001 Table of Contents Page 1. Safety notes 3 2.

More information

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals 25 to 55 A culus CE Application AF09... AF38 4-pole contactors are used for controlling power circuits up to 600 V AC and 240 V DC.

More information

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Motor Starter Protectors/Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Overview Enclosures For stand-alone installation of 3RV20

More information

Electronic Circuit Breaker ESS20-0..

Electronic Circuit Breaker ESS20-0.. Electronic Circuit Breaker ES-0.. Description Electronic circuit breaker type ES-0.. is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 4 V switch-mode

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

For Operation in the Control Cabinet

For Operation in the Control Cabinet As an option the thyristors can also be protected by SITOR semiconductor fuses from short-circuiting so that the soft starter is still functional after a short-circuit (type of coordination ). Three LEDs

More information

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Modular Standardized Electrical and Control Solutions for Fast Track Projects Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive

More information

Softstarter SAS SAS 11PUST, 22PUST Assembly- and Commissioning Instructions

Softstarter SAS SAS 11PUST, 22PUST Assembly- and Commissioning Instructions electronic Softstarter SAS 3...11 SAS 11PUST, 22PUST Assembly- and Commissioning Instructions Quality is our Drive. SAS 3...11, SAS 11PUST, 22PUST 1 Stand 03/17 10800.10002 Table of contents Page 1. Safety

More information

Power Electronics. Motor brake relay GA 9031 ministop

Power Electronics. Motor brake relay GA 9031 ministop Power Electronics Motor brake relay GA 90 ministop 0 Thyristor electronic brake relay for motors up to kw Adjustable braking current up to 0 A Adjustable braking time Automatic standstill monitoring (optional)

More information