ON-LOAD TAP-CHANGER RMV-II 1500 A / 2000 A / 2500 A Operating Instructions

Size: px
Start display at page:

Download "ON-LOAD TAP-CHANGER RMV-II 1500 A / 2000 A / 2500 A Operating Instructions"

Transcription

1 ON-LOAD TAP-CHANGER RMV-II 1500 A / 2000 A / 2500 A Operating Instructions

2 2010 All rights reserved, Maschinenfabrik Reinhausen Unauthorised copying and distribution of this document and the utilisation and communication of its contents are strictly prohibited unless expressly authorised. Offenders will be held liable for the payment of damages. All rights reserved in the case of registration of a patent, utility model or registered design. The product may have been modified after this document went to press. We expressly reserve the right to make changes to the technical data, the design or the scope of delivery. The information provided and the arrangements agreed during processing of the relevant quotations and orders are strictly binding. The original operating instructions were drawn up in German.

3 Content Content 1 Technical Data General Data Application Limits Equipment Standard Features Safety instructions Description Design Operation Tap Selector Change-over Selector (Reversing or Coarse/Fine) Vacuum Interrupter By-Pass Switch Monitoring System Drive Mechanism/Cam Switch Assembly Option Installation Receiving, Handling and Storage Mechanical Set-up Attaching the Oil Compartment Mounting the Drive Mechanism Air Compartment Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 3

4 Content 4.3 Electrical Connections Connecting the Tap Leads to the LTC Connecting the Monitoring System and the Drive Mechanism Test Procedures Manual Test Procedures Motorized Test Operations Monitoring System Tests Oil Filling/Transformer Vacuum Processing Maintenance-Free Schedules and Service Maintenance-Free Intervals Taking the LTC out of Service Draining the Oil Internal Examination Vacuum Interrupter Examination By-pass switch Preparing the LTC for Service Replacement of the Vacuum Interrupter Removing the Old Vacuum Interrupter Assembly Installing the New Vacuum Interrupter Dehydrating Breather Assembly Receiving Installation Operation VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

5 Content 7.4 Maintenance Vacuum Interrupter Monitoring (VIM) System Vacuum Interrupter Monitoring System Description Evolution of Design Installation and Wiring In-Service Monitoring System Verification In-Service Monitoring System Trip (Lockout / 86RL) Replacement, Spare or Upgrade Parts Monitoring System Vintage Identification Spare parts List Appendix Drive Mechanism, Standard Mounting Parts Designation: Drive Mechanism, Standard Mounting Drive Mechanism, Ground Level Mounting Parts Designation: Drive Mechanism, Ground Level Mounting RMV-II Load Tap Changer, Operational Sequence Schematic Dehydrating Breather, Dimensional and Installation Details Parts Designation: RMV-II Load Tap Changer, Vacuum Interrupter Assembly RMV-II Load Tap Changer, Vacuum Interrupter Assembly...84 Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 5

6 Content 10.9 Parts Designation: RMV-II Load Tap Changer, By-Pass Switch Assembly RMV-II Load Tap Changer, By-Pass Switch Assembly Parts Designation: RMV-II Load Tap Changer, Cam Switch Assembly RMV-II Load Tap Changer, Cam Switch Assembly VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

7 Figures Figures Figure 1 Three-phase RMV-II load tap changer...17 Figure 2 Tap changer oil compartment...18 Figure 3 Vacuum interrupter, schematic layout...19 Figure 4 Typical RMV-II winding layout (LTC on position 16 L)...20 Figure 5 Tap change from position 16 L to 15 L...20 Figure 6 Figure 7 Tap selector, by-pass switch and change-over selector, three-phase assembly...22 Vacuum interrupter, single-phase assembly...23 Figure 8 By-pass switch, single-phase assembly...24 Figure 9 Monitoring system schematic diagram...25 Figure 10 Figure 11 Figure 12 Drive mechanism cam switch assembly, hinged door open showing monitoring system and handcrank...27 Monitoring system. cover removed...35 Mechanical test procedure for good vacuum...40 Figure 13 Vacuum interrupter contact erosion indicator...41 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Location of P2 & P3, solid bus bar connector removed...42 Test circuits to be used for the Hi-Pot Test...45 Location of P2 & P3 busbars, solid and flexible bus bar connectors removed...46 By-pass switch, single-phase assembly, location of P2 & P3 bus bars...47 Measuring the by-pass switch arcing tip thickness...47 Figure 19 Dehydrating breather...49 Figure 20 Vacuum interrupter assembly...52 Figure 21 Removing the CT from the interrupter assembly...53 Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 7

8 Figures Figure 22 Figure 23 Loosen the lock hex nut on the operating rod bolt while holding the moving contact stem Use a 19 mm wrench to turn the bolt and a 24 mm wrench to hold the vacuum interrupter contact stem Figure 24 Unscrew the clamp on top of the vacuum interrupter Figure 25 Remove the clamp completely Figure 26 Drop bracket down Figure 27 Unscrew the vacuum interrupter completely Figure 28 Screw by hand until the lock nut is reached Figure 29 Bolt heads and nuts are aligned to bend locking tabs Figure 30 Reinstall clamp but do not tighten firmly yet Figure 31 Viewing the sight hole in the upper right hand corner Figure 32 Location for feeler gauge measurement between operating rod bolt (window) and drive dog of driftoff plate (anvil gap) Figure 33 Anvil gap measurement, schematic representation Figure 34 Adjustment of vacuum interrupter to the operating rod-bolt during feeler gauge measurement VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

9 Tables Tables Table 1 General data...11 Table 2 Application Limits...12 Table 3 Table 4 Table 5 Annual checks...37 Routine checks...37 Spare parts...75 Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 9

10

11 1 Technical Data 1 Technical Data The RMV-II load tap changer fulfills all requirements in IEC and ANSI/ IEEE C The Motordrive Mechanism complies to IEEE C General Data Design 3 phase, preventive autotransformer (reactor) switching principle (to break load current by vacuum interrupters) Tank Will withstand full vacuum (± 15 psi) Size (LxWxH) Tank:66 x 32 x 50 in.for 69 kv design, 66 x 29 x 43 in. for 15 and 25 kv design Air compartment:34 x 17 x 23.5 in. (250 lbs) Total weight (incl. oil) 5,500 lbs. for 69 kv design, 4,440 lbs. for 15 and 25 kv design Oil filling quantity 345 gals./2,590 lbs. for 69 kv design, 270 gals./2,025 lbs. for 15 and 25 kv design Time per operation Approx. 2 seconds Table 1 General data Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 11

12 1 Technical Data 1.2 Application Limits The maximum allowable recovery voltage across the reversing switch during its operation is 20 kv. Tie-in resistors are necessary in case 20 kv are exceeded. Tap changer type Operating voltage phase-to-phase and to ground Three phase kva of regulation RMV-II RMV-II RMV-II RMV-II RMV-II RMV-II RMV-II kv 26.4 kv 72.5 kv 15 kv 26.4 kv 72.5 kv 72.5 kv 36,000 kva 36,000 kva 72,000 kva 48,000 kva 48,000 kva 96,000 kva 120,000 kva LTC through-current 1,500 A 1,500 A 1,500 A 2,000 A 2,000 A 2,000 A 2,500 A Tap-to-tap voltage 1,000 V 1,000 V 2,000 V 1,000 V 1,000 V 2,000 V 2,000 V Impulse withstand voltage (full wave) phase-to-phase and to ground 125 kv 150 kv 400 kv 125 kv 150 kv 400 kv 400 kv Power-frequency test voltage phase-tophase and to ground Impulse withstand voltage (full wave) across tap range Power-frequency test voltage across tap range Impulse withstand voltage (full wave) tap-totap Power-frequency test voltage tap-to-tap Number of positions (standard) Regulating winding sections Table 2 40 kv r.m.s. 50 kv r.m.s. 140 kv r.m.s. 40 kv r.m.s. 50 kv r.m.s. 140 kv r.m.s. 140 kv r.m.s. 75 kv 75 kv 250 kv 75 kv 75 kv 250 kv 250 kv 26 kv r.m.s. 26 kv r.m.s. 70 kv r.m.s. 26 kv r.m.s. 26 kv r.m.s. 70 kv r.m.s. 70 kv r.m.s. 45 kv 45 kv 125 kv 45 kv 45 kv 125 kv 125 kv 15 kv r.m.s. 15 kv r.m.s. 50 kv r.m.s. 15 kv r.m.s. 15 kv r.m.s. 50 kv r.m.s (8 effective) Application Limits 9 (8 effective) 9 (8 effective) 9 (8 effective) 9 (8 effective) 9 (8 effective) 50 kv r.m.s. 9 (8 effective) 12 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

13 1 Technical Data 1.3 Equipment Standard Features Finish: light gray epoxy solid resin primer Oil gauge with low level SPDT contacts Provision for pressure relief device Drain valve, 1 in. globe with sampler Guide pins for access door Non-corrosive hardware Dehydrating breather Handcrank with interlocking switch Cam switch control: tap changer pilot shaft 10 cams, tap changer limit shaft 4cams Position indicator: 16L-N-16R, 33 positions/32 steps Wiring: 12 pt. terminal blocks, PVC-insulated wire, preinsulated terminals Air compartment heater with thermostat Stainless steel access door studs Vacuum interrupters with monitoring system Drive motor: single-phase, V, 60 Hz, 1,725 r.p.m. (standard, other available on request) Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 13

14

15 2 Safety instructions 2 Safety instructions All personnel involved in installation, commissioning, operation, maintenance or repair of the equipment must: be suitably qualified strictly observe these Operating Instructions. Improper operation or misuse can lead to a reduction in the efficiency of the equipment damage to the equipment serious or fatal injury to personnel. Safety instructions in this manual are presented in three different forms to emphasize important information. WARNING This information indicates particular danger to life and health. Disregarding such a warning can lead to serious or fatal injury. CAUTION This information indicates particular danger to the equipment or other property of the user. Serious or fatal injury cannot be excluded. These notes give important information on a certain subject. The instructions contained in this manual apply for tap changers with standard position designation 16L...N...16R only. For LTC s with a different position designation please refer to the LTC sequence chart supplied for each order. Drawings and illustrations contained in this instruction manual are subject to change without notice and are for reference only. For specific details refer to drawings submitted with each individual customer order. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 15

16

17 3 Description 3 Description The RMV-II Load Tap Changer is used in conjunction with oil-immersed power transformers, regulators and phase shifting transformers to change taps under load thereby controlling voltage magnitude or phase angle, Figure 1. Figure 1 Three-phase RMV-II load tap changer The tap changer works on the preventive autotransformer (reactor) switching principle with vacuum interrupters to accomplish the tap change. Vacuum interrupters are used to interrupt the circuit within a half cycle. The interruption takes place in a vacuum of approximately 10-6 torr instead of the usual arcing under oil. Thus, oil contamination is eliminated. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 17

18 3 Description 3.1 Design The RMV-II load tap changer is a three-phase design with full insulation between phases and to ground, Figure 2. Figure 2 Tap changer oil compartment It consists of an oil compartment containing tap and change-over selectors (reversing or coarse/fine), vacuum interrupters and by-pass switches, a separately housed drive mechanism/cam switch assembly and other accessories as required by customer specifications. Each phase consists of a tap and changeover selectors positioned on an epoxy molded terminal board and a vacuum interrupter and by-pass switch on a separate vertical insulating panel mounted rigidly from the top of the tap changer oil compartment. All switching elements involved in the tap change operation, selector and change-over selectors, vacuum interrupters and by-pass switches of all phases, are driven by one main shaft from the drive mechanism. The vacuum interrupter drive assembly is a cam action spring driven mechanism which impacts an operating rod, when opening and closing. The operating rod is connected to the vacuum interrupter moving contact. 18 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

19 3 Description The vacuum interrupter consists of a stationary and a moving contact enclosed in a vacuum-tight ceramic insulating envelope, Figure 3. Figure 3 Vacuum interrupter, schematic layout The moving contact is sealed through a flexible metal bellows protected from the arc by a shield. A metal shield surrounds the contacts forming an arc chamber and condensing surface to collect vaporized contact material which arises during arcing. The entire tap changer mechanism except the motor drive is housed in an oiltight, flat finished steel tank which is designed to be welded onto the transformer main tank, Chapter This tap changer oil compartment has a gasketed, hinged access/service door. The motor drive/cam switch assembly is normally housed in a separate air compartment and is accessible through a weather-proof hinged door. Optionally, the compartment can be mounted at a lower level. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 19

20 3 Description 3.2 Operation Figure 4 Typical RMV-II winding layout (LTC on position 16 L) Figure 5 Tap change from position 16 L to 15 L 20 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

21 3 Description The tap changer operation is divided into three major functions, Figure 4 and Figure 5: 1. Arc interruption and reclosing by use of the vacuum interrupters in conjunction with the associated by-pass switches. 2. Selection of the next tap position by the tap selector assemblies in proper sequence with the operation of the vacuum interrupters and by-pass switches. 3. Operation of reversing or coarse/fine selector in order to double the number of tap positions. The tap changer is operated by a motor drive mechanism which drives the main insulating drive shaft through a reduction gear. A bevel gear assembly drives the horizontal insulating drive shafts between selector switches. The tap selector geneva gears, vacuum interrupter and by-pass switch assemblies of each phase are driven through crossed helical gears to assure a precise operational sequence of the switching components. When moving from one tap position to the next, one set of by-pass switch contacts opens, while the second set stays closed, routing the current through the vacuum interrupter just prior to its operation. The vacuum interrupter opens by a spring-operated mechanism before the tap selector moving contact selects the next tap. The vacuum interrupter then closes under spring force and locks in place followed by the by-pass switch reclosing to shunt the vacuum interrupter, thus completing the tap change operation. The tap selector connects the preventive autotransformer alternately into a bridging or a non- bridging position. The change-over selector operates only when changing from position 1 L to N or N to 1 L. 3.3 Tap Selector The tap selector consists of two contact arms operated alternately by geneva gears, Figure 6. The geneva gears also lock the movable contacts on position between operations. The stationary contact bus bars are cast into the epoxy molded terminal board. They provide support for the double-deck stationary contacts. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 21

22 3 Description Each moving contact assembly consists of parallel contact fingers. The number of contact fingers used depends on the through-current ratings of the LTC. The stationary contacts and the inner collecting ring are silverplated. The moving contact assemblies are springloaded to provide safe contact force for both the normal load current and the excessive current during short-circuit conditions. Figure 6 Tap selector, by-pass switch and change-over selector, three-phase assembly 3.4 Change-over Selector (Reversing or Coarse/Fine) The silverplated stationary contact assemblies of the change-over selector are mounted on bus bars cast into the epoxy terminal board adjacent to the tap selector assembly. The moving contact arm is operated by an insulating shaft and linked through a double-lever mechanism to the geneva gear assembly. The change-over selector moving contact assembly is of the same design as the tap selector contacts but uses an increased number of parallel contact fingers. 22 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

23 3 Description 3.5 Vacuum Interrupter The vacuum interrupter assembly is mounted vertically on the front of the insulating panel, Figure 7. Vacuum filling is, therefore, not required when oil is replaced in the field. Cam action drives the vacuum interrupter through a spring mechanism which latches in at its end positions. The mechanism provides a direct drive by its operating rod to the vacuum interrupter contact, both moving in the same action line. The interrupter is locked in the open position while the selector switch changes taps. Upon completion of the tap selection the interrupter mechanism unlocks and the moving contact recloses under positive spring force. Opening and closing speeds of the vacuum interrupter are dashpot controlled. Figure 7 Vacuum interrupter, single-phase assembly Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 23

24 3 Description 3.6 By-Pass Switch The by-pass switch is located on the opposite (back) side of the insulating panel from the vacuum interrupter mechanism and is operated from the same drive shaft, Figure 8. It consists of two contact assemblies with parallel springloaded contact fingers that close on a silver-plated contact rod. The moving contacts are cam operated to open and reclose. The by-pass switch normally bridges between the legs of the preventive autotransformer, thus by-passing the vacuum interrupter. During a switching operation the bypass switch opens one set of contacts allowing current to be directed by the remaining closed set of contacts through the vacuum interrupter before it operates. Figure 8 By-pass switch, single-phase assembly 24 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

25 3 Description 3.7 Monitoring System WARNING Do not operate the LTC without this monitoring system properly connected and functional if the transformer is energized. Follow the test procedures outlined in Chapter During operation, if the monitoring system trips, do not reset until the LTC has been inspected and the cause of the trouble corrected. Failure to adhere to these requirements can lead to property damage and/or personal injury. Please contact Reinhausen Manufacturing for assistance and refer to Chapter 8 for further details. A unique monitoring system is utilized to protect the LTC in the unlikely event that a vacuum interrupter fails to interrupt and transfer the load current during a tap change operation, Figure 9. Figure 9 Monitoring system schematic diagram Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 25

26 3 Description Three saturating current transformers in the stationary contact leads of the vacuum interrupters are provided. The electrical signal from the current transformer is transmitted by fibre optic cable to the monitoring circuit board. These cables must be handled with reasonable care. DO NOT BEND OR COIL these cables to a radius smaller than 100 mm (3.94 ). Overbending will damage the cable and destroy its ability to carry a light pulse. The system monitors the current in all three phases at a threshold of less than 20 amperes after the interrupters are open but prior to the movement of the tap selector contacts. The logic circuit evaluates these signals and protects the LTC in case of vacuum interrupter failure by operating a bistable output relay. This relay operation returns the LTC to the original position before the tap selector opens the circuit and prevents further operations. CAUTION The monitoring system is functional only when the RMV-II load tap changer is operated by control power (either by manual control switch raise/ lower or automatically). It does not function if the unit is operated by hand cranking. Therefore, never hand crank the unit if the transformer is energized as damage to the transformer and/or personal injury may result if any of the vacuum interrupters fails to interrupt. An optional mechanical interlock is available to prevent hand cranking if a vacuum interrupter failure occurs or upon loss of control power. As with any safety device, the mechanical interlock should not be intentionally defeated or tampered with. The monitoring system s control and indicating components are located inside the door of the drive mechanism cabinet. It contains the electronic circuitry, power supply, 86 L, 86 C and 86 R trip relays, SP supervision power relay, 3 red and 3 yellow LEDs and a green LED, a TEST push-button (green) and a RESET push-button (red). The red LEDs indicate energizing of the associated trip relays. The yellow LED s indicate energizing of the SP relay denoting loss of CT signal for the associated phase. The green LED indicates operability of the system. The green TEST push-button is used to test the internal circuitry of the monitoring system. Pressing the TEST push-button simulates a failure condition of all three phases, energizes the trip relays and lights the three red LEDs. After testing the monitoring system must be reactivated by pressing the red RESET push-button. 26 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

27 3 Description The system should be tested at installation and scheduled examination intervals. The physical layout of the monitoring system circuit board is shown in Chapter 4.4.3, Figure Drive Mechanism/Cam Switch Assembly Figure 10 Drive mechanism cam switch assembly, hinged door open showing monitoring system and handcrank The drive mechanism and cam switch control assembly are housed in a separate air compartment attached to the bottom of the tap changer oil compartment, Figure 10. The entire assembly, together with the position indicator, motor capacitors and terminal blocks, is mounted to a detachable mounting plate affixed to the rear wall of the motor drive housing. The drive mechanism is powered by a single-phase, volt, 60 Hertz, permanent split capacitor motor which is flange-mounted to a self-contained reduction gear unit. This gear unit is grease filled and sealed at the factory to eliminate the need for subsequent lubrication. Its output shaft couples directly to the tap changer main shaft which extends through the tap changer oil compartment bottom. An auxiliary reduction gear driven from this gear unit operates the factory preset cams and the position indicator. The air compartment is accessible through a front mounted, weather-proof, hinged door. The LTC tap position indicator is visible through a viewing port in the door. The position indicator has two red drag hands indicating the maximum and minimum positions (raise and lower) of the actual operating range. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 27

28 3 Description Option A handcrank coupling with interlocking switch is provided at the main gear unit and can be used with the air compartment door open. A modified version of the drive mechanism/cam switch assembly with weatherproof drive shaft seal on top of the housing allows for separate attachment of the air compartment to the transformer main tank at a lower level, if required. In this case, a single drive shaft couples tap changer and drive mechanism. Its length may be varied according to customer specifications (max. shaft length 2,500 mm (98.4 in.). The drive mechanism requires a separate customer supplied control cabinet with appropriately sized motor control relays and protective circuit breaker. On request this control cabinet can be supplied by Reinhausen. Please consult wiring diagram supplied with each order for specification guidelines concerning motor control relays and protective circuit breaker. The drive mechanism assembled on the mounting plate including cam switch assembly, monitoring system circuit board, position indicator, drive shaft and required fittings is also available to be mounted into the transformer control cabinet by the customer. 28 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

29 4 Installation 4 Installation 4.1 Receiving, Handling and Storage Before mounting on the transformer the tap changer oil compartment and the drive mechanism air compartment should be opened and inspected for damage which may have occurred in shipment due to rough handling. If shipping damage is evident, file a claim with the transporting company. The sales office of Reinhausen Manufacturing should be notified promptly of damage occurring during shipment from its plant. No special handling of the tap changer is required other than that accorded the transformer in general. The tap changer is shipped from Reinhausen Manufacturing filled with dry nitrogen under positive pressure. If the tap changer is opened and the nitrogen fill is lost the tap changer oil compartment must be purged and filled with dry nitrogen at a pressure not exceeding 4 psi, when stored again indoors. The LTC and drive mechanism are not prepared for storage in an unheated building or outdoors. Such conditions require: filling the LTC tank with clean, dry oil and the gas space with dry nitrogen, weather protecting of the exterior of the tank and terminal board, heating the drive mechanism air compartment by connecting the built-in space heater to power. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 29

30 4 Installation 4.2 Mechanical Set-up Attaching the Oil Compartment WARNING Welding adjacent to the epoxy terminal board may distort its mounting surface and cause damage to the terminal board or its oil seal. Check the size of the opening in the transformer main tank. For minimum tank opening dimensions see customer dimensional arrangement drawing. Weld the LTC compartment to the transformer main tank taking care that the weld is oiltight, pressure and vacuum resistant. The transformer manufacturer is responsible for mounting the LTC on a transformer tank wall that is designed to withstand normal test and operating pressures (15 psi maximum). A 0.25-in. oil tight weld is required around the outside perimeter of the LTC mounting flange. Welding on the transformer side of the LTC is not required Mounting the Drive Mechanism Air Compartment WARNING Do not turn the LTC input shaft nor the drive mechanism output shaft until they are coupled with each other. Coupling LTC and motor drive in non-matching positions may cause mechanical damage. The LTC and motor drive are shipped on separate pallets in the neutral position. The LTC and motor drive serial numbers should be checked prior to assembly to ensure they match. Prior to shipment the LTC is locked in the neutral position by a cotter pin which is inserted through the boss and the drive shaft extension on the bottom of the tank. This cotter pin should not be removed until the motor drive is ready for assembly to the LTC. 30 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

31 4 Installation The motor drive unit is also shipped in the neutral position. Confirm this by checking that: 1. the position indicator is on neutral 2. the cam switch timing wheel is at zero degrees Standard Mounting (Attachment to the LTC oil compartment) The LTC and motor drive must be coupled in the neutral position per drawing 4D32012 (see appendix) Detached (Ground Level) Mounting (Attachment to the transformer main tank) This version requires, provided by the transformer manufacturer, a mounting support on the transformer main tank. The support is fastened to the rear of the drive mechanism housing. The LTC and motor drive must be coupled in the neutral position per drawing 4D32009 (see appendix). 4.3 Electrical Connections Connecting the Tap Leads to the LTC Connect tap leads to the proper LTC terminal on the epoxy terminal board. For terminal location and designation see dimensional arrangement drawing Connecting the Monitoring System and the Drive Mechanism The drive mechanism is to be wired according to the wiring diagram which is supplied with each order. To connect the monitoring system, insert the cable plug from the motordrive cabinet into the receptacle on the bottom of the LTC tank per drawing 4D32012 (see appendix). Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 31

32 4 Installation 4.4 Test Procedures Manual Test Procedures Open the LTC compartment and the drive mechanism. Insert the handcrank into the guide lever and engage the motor drive. Sequence check the LTC operation by hand cranking one step in the lower direction, position N to 1L, see sequence chart in drawing of appendix, Chapter This movement requires 7.5 handcrank revolutions. While hand cranking from N to 1L (counter-clockwise) observe that the by-pass switch P2 opens, then the vacuum interrupter trips open and the tap selector moving contact P1 (nearest to the terminal board) moves from M to 11. At the same time as the tap selector, the changeover selector will move from B to A. Continue cranking and the vacuum interrupter will reclose and finally the bypass switch P2 closes, positioning the tap changer in on position. Observe the engagement of selector switch and reversing switch moving contacts for smooth, non-binding operation. Observe closure of bypass switch. Hand crank in the raise direction (clockwise) back to neutral (position N). The same events should take place in the same order as above except that the movement is from 11 to M and from A to B. Then check the LTC operation by hand cranking from position N to 1R. While hand cranking in the raise direction (clockwise) observe that the by-pass switch P3 opens, then the vacuum interrupter trips open, followed by the tap selector moving contact P4 (furthest from the terminal board) moving from M to 4. Continue hand cranking and the vacuum interrupter will reclose, then the by-pass switch P3 will reclose, positioning the LTC in on position. Observe the engagement of tap selector moving contacts for smooth, nonbinding operation. Observe closure of by-pass switch. Hand crank in the lower direction (counter-clockwise) back to neutral (position N). The same events should take place in the same order as above except that the movement is from 4 to M. Withdraw the handcrank and place it in the storage holder provided. 32 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

33 4 Installation Motorized Test Operations Operate the tap changer with the drive mechanism connected to electrical power. Do not run more than 120 consecutive operations or damage to the motor may occur. Extended operation of the LTC without oil in air is not recommended. However, the LTC may be run once to both limits and back to neutral position for test purposes. When running the LTC electrically it typically stops between 0 to 18 on the timing wheel. This is a normal condition. Make sure that both the monitoring system and the drive mechanism are connected to power. Make sure that the motor control breaker is closed and the handcrank is in its storage holder. Place the monitoring system into Maintenance Mode as per Chapter 8.1 of this manual. Operate the LTC by closing the raise/ lower switch one step from neutral position toward the lower limit. Check the movement of the position indicator to confirm that the motor is connected properly. The drive mechanism should operate and stop on position. Operate the LTC one step of at a time from position 1L toward the lower limit. Open the handcrank interlock switch by lifting the handcrank guide lever while operating the LTC. The tap changer should not operate. Continue with the operation toward the lower limit. Stop on the lowest limit position (position 16L). With one hand on the motor control breaker, close the raise/lower switch in the lower direction. The drive mechanism should not run. If it does, turn off the circuit breaker at once because either the limit switch timing or connections are wrong. Remove the handcrank from its storage holder and insert. Try to hand crank the tap changer in lower direction. The mechanical stop should operate in approximately 2.5 handcrank revolutions. This can be felt readily on the handcrank. Do not force the handcrank. Run the tap changer one step at a time in the raise direction and repeat the checks as above in the raise limit (position 16R). 0.5 handcrank revolutions in the raise direction should engage the mechanical stop. Upon completion of the checks return the tap changer to the assembly position (position N), return the handcrank to its storage holder. Close the drive mechanism air compartment. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 33

34 4 Installation Monitoring System Tests CAUTION The monitoring system is functional only when the RMV-II load tap changer is operated by control power (either by manual control switch raise/ lower or automatically). It does not function if the unit is operated by hand cranking. Therefore, never hand crank the unit if the transformer is energized as damage to the transformer and/or injury to the operator may result if any of the vacuum interrupters fails to interrupt. Open the drive mechanism door for access to the monitoring system. There is a green LED which indicates operability of the system. Two push-buttons are provided, one red to reset and one green to test. Figure 11 shows the layout of these items. Check the green LED to ensure that the monitoring system is operative Power-off Test at the Transformer Control Cabinet Open the transformer control cabinet. The green lamp 86 GL in the control cabinet should be on indicating that the monitoring system is energized. Drop control power. Remove cover from monitoring system circuit board. Interrupt the power supply to the circuit board by removing the 0.25 A fuse. Reinstate control power. The 86 GL lamp should then be off and the red lamp 86 RL, on. Try to operate the LTC drive mechanism. It should not start. Reinstall the monitoring system fuse and it s cover. Close the transformer control cabinet. 34 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

35 4 Installation Green push button=test Red push button=reset 3 red and 3 yellow LEDs Right, Center, Left Green LED Figure 11 Monitoring system. cover removed Operational Tripping Test Connect a variable CT to busbar P2 and the stationary contact A of one of the vacuum interrupter assemblies, Figure 20, for example left phase. The CT should be able to drive a current of at least 20 Amperes. A monitoring system trip test set is available; reference spare parts list in Chapter 9 of this manual. Place monitoring system into Maintenance Mode so that all three yellow LED s are flashing slowly, Chapter 8.1. Raise the CT input voltage to drive a primary current of approximately 20 A. Start the drive mechanism in one direction. The 86 L relay should trip, the associated red LED should light, the drive mechanism should stop and return to its previous position. The moving selector contact must not disconnect from the stationary during the process. The drive mechanism must not be operable in either direction, until the monitoring system is reset. Perform same test procedure with the vacuum interrupter assemblies of center and right phase. Observe tripping of 86 C and 86 R relays. Be sure to reset the monitoring system so that all 86 relays are untripped and all red lights out. Close the LTC compartment access door. Do not overtighten the LTC access door nuts. These nuts should be tightened to a maximum torque of 15 Nm (11.1 ft. lbs.), which corresponds to a compression of the gasket to 5/16 thickness. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 35

36 4 Installation 4.5 Oil Filling/Transformer Vacuum Processing During transformer vacuum processing (drying) the LTC should be considered part of the transformer. Therefore, the tap changer and transformer gas spaces should be connected together through the vent plug. The differential pressure across the terminal board and its gasket system will then be zero during the entire processing cycle. Auxiliary devices, e.g. dehydrating breather, sudden pressure relay, etc., must be removed or disconnected during processing or filling to prevent damage due to oil flooding. The sudden pressure relay can also be damaged by rapid pressure changes (consult the instruction leaflet). The vacuum should always be broken with dry, inert gas to prevent moisture contamination. In preparation for factory testing of the transformer at the maximum tap changer voltage rating (15 kv, 25 kv or 69 kv), vacuum fill the LTC tank with oil to the proper level prior to initiating any transformer tests. 1. Make the oil input and vacuum connections to the compartment. Remove and plug the 1/4-in. coupling to the dehydrating breather system. 2. Hold a vacuum of 1 torr, or better, on the tap changer compartment for 2 hours prior to filling. Continue to hold this vacuum during filling. Degassed oil will facilitate this process. 3. Break the vacuum with dry, inert gas. 4. Take three oil samples from the LTC oil compartment and test for breakdown voltage. All three samples should have a minimum breakdown voltage of 30 kv by ASTM D 877 or 28 kv by ASTM D Moisture content should not exceed 20 ppm by ASTM D Run the tap changer with motor power through the complete range limitto-limit, 16 L to 16 R. 6. Reclose the compartment openings. The RMV-II tank is designed to withstand a full vacuum. The terminal board is designed to withstand a maximum differential pressure of 18 psi. This allows for full vacuum in the LTC tank with a maximum positive pressure of 3.3 psi from the transformer side of the terminal board. 36 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

37 5 Maintenance-Free Schedules and Service 5 Maintenance-Free Schedules and Service Prior to initial energization of the transformer, perform tests and examinations per Chapter and Because of its basic design, the RMV-II Load Tap Changer will require a minimum of maintenance. However, as with any mechanical device, it should receive periodic examination. 5.1 Maintenance-Free Intervals The RMV-II is a Maintenance-Free Load Tap Changer through 500,000 operation count intervals or through 7 year time spans, whichever occurs first. The Maintenance-Free interval can become strictly operation count based regardless of time span by use of the Model 'B' monitoring system. Refer to Chapter 8 for detailed information. The Maintenance-Free intervals, whether time-based or operations countbased, will only need complementing by checks (annually) as follows: Test Check Reference Oil Sampling Check for dielectric, combustible gases and water content VIM System Test Check circuit board test & reset function; simulated monitoring runback & power off test Motor drive condition Check heater & accessory operation; general mechanical condition Table 3 Annual checks Chapter 4.5 Chapter 8.4, Chapter Routine site visits should include as good practice the following: Test Check Reference Dehydrating Breather check Check for oil leaks Table 4 Routine checks Check for oil level and desiccant material color All areas with seals or gaskets that retain oil should be examined. Chapter 7.3, 7.4 Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 37

38 5 Maintenance-Free Schedules and Service 5.2 Taking the LTC out of Service 1. De-energize the transformer and ground all external bushings. 2. Open the drive mechanism motor control breaker. 3. Record the number of operations shown on the tap changer operations counter. 5.3 Draining the Oil CAUTION Transformer oil should always be handled as a flammable liquid. LTC tanks may, under some conditions, accumulate explosive gasses. Filtering and handling the oil may generate static electricity. A damaging explosion could result if any electrical discharge takes place in an explosive gas mixture. Safety precautions should include purging the gas space with dry nitrogen before filtering and grounding the transformer, its bushings, and all oil handling equipment. 1. Take a tap changer oil sample. 2. Test and record the breakdown voltage. 3. Remove the vent plug on top of the LTC compartment and drain oil. If the drained oil is to be reused it should be pumped through a filter press to remove the small amount of carbon and metallic particles produced by the switching duty of the by-pass switch and the normal wear of the mechanism. Oil should be stored in clean, dry containers if reused. Open the LTC access door. Check the door gasket for signs of deterioration. Replace with a new gasket if necessary. 38 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

39 5 Maintenance-Free Schedules and Service 5.4 Internal Examination CAUTION The monitoring system uses FIBRE OPTIC CABLES inside the LTC to transmit signals to the electronic control box. These cables must be handled with reasonable care. DO NOT BEND OR COIL these cables to a radius smaller than 100 mm (3.94-in.). Overbending will damage the cable and destroy its ability to carry a light pulse. 1. Check the LTC compartment floor and horizontal surfaces for debris that might indicate abnormal wear or trouble developing. 2. Check all sliding surfaces for signs of excessive wear. 3. Make a general examination of the tightness of bolts and nuts on those parts which are subject to mechanical shock and vibrations during tap change operation Vacuum Interrupter Examination Check the condition of the flexible connector for broken strands Mechanical Test With the tap changer in on position lift the connector on the moving contact by means of a large screwdriver and pull the contact open about 6 mm, Figure 12. Let it snap close. A good vacuum interrupter will require an opening force of approx. 35 to 40 pounds. The moving contact should close freely and impact with a short metallic ring. If an interrupter were completely full of oil, due to bellows failure, it would not flash over on the hi-pot test but the pull to separate the contacts would not be more than 5 to 10 pounds or the contact would not snap close quickly. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 39

40 5 Maintenance-Free Schedules and Service Figure 12 Mechanical test procedure for good vacuum Contact Erosion Indicator The vacuum interrupter is rated for one million operations at full load. (Overload conditions may reduce the operational life of the vacuum interrupter). However, when the erosion indicator is near the F (finish) line of the index, turn the handcrank slightly until the upper pawl can latch in. The vacuum interrupter has to be replaced when the gap between the operating rod bolt and drive dog of the drift-off plate is smaller than 0.5 mm (Figure 32 and Figure 33 show a gap of 5.3 mm when the vacuum interrupter is in the new condition). A contact erosion indicator consisting of a stationary pointer and movable scale is provided. This indicator is located behind a viewing port of the drive mechanism cover plate, Figure 13. A scale showing the start (S) and the finish (F) points is engraved. This scale is a visual indication which gives a rough estimate 40 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

41 5 Maintenance-Free Schedules and Service of contact wear. The anvil gap, Figure 32 and Figure 33, is the governing factor for worn vacuum interrupter replacement. Recording the anvil gap at receipt and subsequent maintenance intervals will provide the best estimate of remaining contact life. At installation the indicator should be checked to confirm that the pointer is on the S (start) line. When the load tap changer is opened for the first time and at subsequent examinations (see Chapter 5.1) the indicator should be checked so that contact wear can be evaluated. By observing the position of the pointer on the scale and the number of actual tap changer operations, a rough estimate of the remaining life can be made. Figure 13 Vacuum interrupter contact erosion indicator Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 41

42 5 Maintenance-Free Schedules and Service Hi-Pot Test Due to the high reliability we have experienced with our products over many years in service, we recommend the Hi-Pot Test only as a means of troubleshooting in the unlikely event of a specific suspicion that a vacuum interrupter might be defective. With the tap changer off position (180 on the cam switch timing wheel) test each vacuum interrupter by applying a hi-pot test of 25 kilovolts AC or 30 kilovolts DC for one minute as follows: 1. Ground all transformer windings. 2. Ground bus bars P2 and P3 (see Figure 14 and Figure 16). 3. Temporarily remove the solid bus bar connector, Figure 14, to the vacuum interrupter stationary contact (bottom side). 4. This will also require disconnecting the fibre optic cable from the saturating current transformer. P3 P2 Figure 14 Location of P2 & P3, solid bus bar connector removed Note the insulating panel between vacuum interrupter and support 42 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

43 5 Maintenance-Free Schedules and Service Be sure to note the color code and location of the leads for reinstallation (the green lead is closest to the CT, the blue lead is in the center, and the orange lead is farthest from the CT). Attach the fiber optic cable to the panel support at the top of the tank prior to performing the hipot test. Locate an insulating panel 6.25 in. x 6.25 in. x in. between vacuum interrupter and support, Figure Perform the hi-pot test using one of the listed test circuits as described and referenced in Figure Reattach the bus bar shunt connector(s). Use new lock nuts M6 (see hi-pot Spare Parts Kits RM Part No , Chapter 9), max. torque 9.5 Nm (71 in. lbs.). Remove the insulating panel. Attach the fibre optic cable. Operate the tap changer to on position. Remove the grounds. The vacuum interrupter must be free of surface films and clean before hi-pot or a false failure result may be achieved. A - Testing with an asymmetrical test transformer, Figure 15 A (A test set with one hot lead and one ground lead) Connect the ground test lead to the vacuum interrupter moving contact (top) and the hot test lead to the stationary contact (bottom). Perform the hi-pot test. B - Testing with a symmetrical centertapped test transformer, Figure 15 B (A test set with two hot leads and with max. test voltage of 50 kv or higher) Connect the ground test lead to the vacuum interrupter moving contact (top) and the hot test lead to the stationary contact (bottom). Perform the hi-pot test. C - Testing with a symmetrical centertapped test transformer, Figure 15 C (A test set with two hot leads and with max. test voltage lower than 50 kv) Special method if the maximum voltage of the test transformer is less than 50 kv. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 43

44 5 Maintenance-Free Schedules and Service CAUTION Before performing this hi-pot test (C) the flexible connector assy must be disconnected. Push back the screws on the vacuum interrupter moving contact. Connect the ground test lead to P2 and P3, Figure 16. Connect one hot test lead to the vacuum interrupter moving contact (top) and the other hot test lead to the stationary contact (bottom). 44 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

45 5 Maintenance-Free Schedules and Service Figure 15 Test circuits to be used for the Hi-Pot Test A B C Test transformer without center tap Test transformer with grounded center tap and with max. test voltage of 50 kv or higher Test transformer with grounded center tap, max. test voltage lower than 50 kv Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 45

46 5 Maintenance-Free Schedules and Service A vacuum Interupter Hi-Pot Test Set is available; reference spare parts list in Chapter 9 of this manual. P3 P2 Figure 16 Location of P2 & P3 busbars, solid and flexible bus bar connectors removed Note the insulating panel between vacuum interrupter and support 46 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

47 5 Maintenance-Free Schedules and Service By-pass switch P3 P2 Figure 17 By-pass switch, single-phase assembly, location of P2 & P3 bus bars Figure 18 Measuring the by-pass switch arcing tip thickness Check the condition of the by-pass switch contacts P2 and P3, Figure 17. These contacts see light arcing as they switch the tap changer current through the vacuum interrupter during a tap change operation. Therefore arcing tips are provided which separate shortly after the moving finger contact assembly opens. Normally, the life of these contacts will by far exceed the vacuum interrupter life. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 47

48 5 Maintenance-Free Schedules and Service With the moving contact finger assembly closed measure the total thickness of both arcing tips, Figure 18. The thickness should not be less than 10.5 mm when eroded. A replacement of the stationary arcing contact tip becomes necessary when the total thickness of both arcing tips is 10.5 mm or less. 5.5 Preparing the LTC for Service Perform vacuum interrupter examination as per Chapter Wipe the LTC compartment down to remove all dirty oil, carbon deposits, metallic fall-out and moisture that may have condensed, during the open time, on the walls and insulating surfaces. Check that drive mechanism and monitoring system are operating properly. Perform test operations of the drive mechanism and a monitoring system test according to Chapter 4.4. Close the LTC compartment. Do not overtighten the LTC access door nuts. These nuts should be tightened to a maximum torque of 15 Nm (11. 1 ft. lbs), which corresponds to a compression of the gasket to 5/16" thickness. Make the oil input connections to the LTC drain valve. Remove and plug the 1/4-in. coupling to the dehydrating breather system. Fill the LTC compartment with clean, dry oil through a filter press to the proper level. Vacuum filling is not required during field service. After oil filling reclose the LTC compartment openings and reconnect the dehydrating breather system. Run the Tap Changer with motor power from the neutral (or assembly position) to position 16L (or the lowest position) for approximately 100 operations without pausing. Return to the neutral position. Let the tap changer sit de-energized for one hour to allow gas bubbles to dissipate from the oil. Take three oil samples and test for break-down voltage. All three should have a minimum breakdown voltage of 30 kv by ASTM D877 or 28 kv by ASTM D1816. Moisture content should not exceed 20 ppm by ASTM D VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

49 5 Maintenance-Free Schedules and Service The dehydrating breather should be checked to confirm that the desiccant is dry and the oil level in the clear plastic oil collection cell is between the two fill level lines on the cell, Figure 19. Remove grounds from external bushings. Flare nut 3/8" Bracket Pad (on transformer wall) Protective grate Oil Collection Cell Figure 19 Dehydrating breather Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 49

50

51 6 Replacement of the Vacuum Interrupter 6 Replacement of the Vacuum Interrupter 6.1 Removing the Old Vacuum Interrupter Assembly CAUTION The Fibre Optic Cables must be handled with reasonable care. DO NOT BEND OR COIL these cables to a radius smaller than 100 mm (3.94-in.). Overbending will damage the cable and destroy its ability to carry a light pulse. If removal of the vacuum interrupter is for any reason other than replacement, the anvil gap measurement, see Chapter 6.2, must be taken for reinstallation and proper setting of the vacuum interrupter erosion indicator. When removing the old vacuum interrupter carefully observe the configuration of the parts and hardware during disassembly so that reinstallation can be made easily and correctly. To remove the old vacuum interrupter proceed as indicated below, Figure 20. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 51

52 6 Replacement of the Vacuum Interrupter 1. Disconnect the fiber optic cable connecting to the CT located to the right hand side of the vacuum interrupter being replaced. Be sure to note the color code and location of the leads for reinstallation (the green lead is closest to the CT, the blue lead is in the center and the orange lead is farthest from the CT). P3 P2 A Figure 20 Vacuum interrupter assembly 2. Remove the CT using a 10 mm socket and wrench for the M6 mounting hardware, Figure VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

53 6 Replacement of the Vacuum Interrupter Figure 21 Removing the CT from the interrupter assembly Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 53

54 6 Replacement of the Vacuum Interrupter CAUTION If the vacuum interrupter is being removed for reasons other than replacement DO NOT TWIST the moving contact. This may damage the bellows and cause the vacuum interrupter to fail. 3. Loosen the hex jam nut M12 on the operating rod-bolt using a 19 mm wrench to turn the nut and a 28 mm wrench to hold the vacuum interrupter moving contact stem, Figure 22. Figure 22 Loosen the lock hex nut on the operating rod bolt while holding the moving contact stem 54 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

55 6 Replacement of the Vacuum Interrupter 4. Remove the M12 hex bolt from the stationary contact stem using a 19 mm wrench to turn the bolt and a 24 mm wrench to hold the vacuum interrupter contact stem, Figure 23. Figure 23 Use a 19 mm wrench to turn the bolt and a 24 mm wrench to hold the vacuum interrupter contact stem Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 55

56 6 Replacement of the Vacuum Interrupter 5. Unscrew the clamp on top of the vacuum interrupter, which holds the interrupter to the bracket. Using a 7 mm socket remove the clamp completely, Figure 24. Figure 24 Unscrew the clamp on top of the vacuum interrupter 6. Remove brass support L-bracket by bending back locking tabs. Loosen the four M8 nuts using a 13 mm wrench, Figure 25. While holding the bracket, slide the four M8 bolts out to drop the bracket down, Figure 26. Note: Replace locking tabs with new ones during reassembly. 56 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

57 6 Replacement of the Vacuum Interrupter Figure 25 Remove the clamp completely Figure 26 Drop bracket down 7. Unscrew the vacuum interrupter completely by turning it off from the operating rod, Figure 27. Make sure to retain the Belleville washer under the hex jam nut in place for reinstallation. Do not change the position of the cam disk by hand cranking the LTC. Figure 27 Unscrew the vacuum interrupter completely Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 57

58 6 Replacement of the Vacuum Interrupter 6.2 Installing the New Vacuum Interrupter Lock tabs and lock nuts should not be used twice for reasons of reliability. Always use new lock tabs and lock nuts when reassembling the unit. Sufficient spare tabs and nuts are contained in our Spare Parts Kits, Chapter 9. To install the new vacuum interrupter follow the steps previously described but in reverse order. 1. Locate the operating rod bolt and slip on the Belleville washer (concave side down) and the bus bar connector with flexible shunts under the hex jam nut. Thread the vacuum interrupter moving contact stem by hand on to the operating rod bolt until the hex jam nut M12 is reached, Figure 28. Do not tighten yet. Figure 28 Screw by hand until the lock nut is reached 58 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

59 6 Replacement of the Vacuum Interrupter 2. Reinstall brass support L-bracket with the four M8 bolts and nuts using new locking tabs. Be sure to orientate the hardware properly (flat ends of the bolt heads and nuts) to allow bending of the locking tabs on to the hardware, Figure 29. Attach the vacuum interrupter stationary contact stem (bottom end) to the solid bus bar connector using the M12 hex bolt and a M12 lock washer. If a lock tab was originally used, replace it with the 19 mm lock washer supplied with the vacuum interrupter kit, refer to Chapter Tighten slightly but do not lock yet. Figure 29 Bolt heads and nuts are aligned to bend locking tabs Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 59

60 6 Replacement of the Vacuum Interrupter 3. Reinstall the clamp on top of the vacuum interrupter. Do not tighten firmly yet, Figure 30. Figure 30 Reinstall clamp but do not tighten firmly yet If reinstalling a used vacuum interrupter, use the previously measured value to adjust the interrupter. Chapter Turn the handcrank slightly until the upper pawl (latch-rod) can latch onto the by-pass drive mechanism. You can identify this action by viewing the sight hole in the upper right corner of the by-pass cover plate, Figure VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

61 6 Replacement of the Vacuum Interrupter 5. Insert a feeler gauge from the left side into the oval opening formed by the operating rod bolt (window) and the drive dog of the drift-off plate, Figure 32, Figure 33. The feeler gauge is to be set to 5.3 mm thickness. 5.3 mm Figure 31 Viewing the sight hole in the upper right hand corner Figure 32 Location for feeler gauge measurement between operating rod bolt (window) and drive dog of driftoff plate (anvil gap) Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 61

62 6 Replacement of the Vacuum Interrupter Figure 33 Anvil gap measurement, schematic representation 6. Turn the vacuum interrupter and thread it until the feeler gauge measures firmly. Check the position of the feeler gauge through the viewing port while turning, Figure VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

63 6 Replacement of the Vacuum Interrupter Figure 34 Adjustment of vacuum interrupter to the operating rod-bolt during feeler gauge measurement. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 63

64 6 Replacement of the Vacuum Interrupter CAUTION Although a guide with parallel flats is provided for the moving contact stem, we recommend to avoid excessive twisting of the bellows which is attached to it. Excessive twisting will reduce the mechanical life of the bellows or will fracture the bellows, which destroys the vacuum making the vacuum interrupter inoperative. 7. Tighten the clamp to a torque of 2.5 Nm (22 in. lbs.). Hold the moving contact stem with a 24 mm wrench and tighten the hex head bolt M12 using a 19 mm wrench to a maximum torque of 30 Nm ( 22.1 ft. lbs.). Tighten the vacuum interrupter stationary contact stem with a 19 mm wrench, maximum torque of 45 Nm (33 ft. lbs.). 8. Perform several test operations between two tap positions to ensure the correct stroke of the vacuum interrupter moving contact. Perform the operations by hand cranking and observe the vacuum interrupter opening and closing. Finally set the load tap changer to "on position". 9. Check to ensure all locking tabs are bent in place and all hardware is tight and properly torqued. Refer to Chapter 4.4 and Chapter 5.5 for testing requirements prior to placing the LTC back in service. 64 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

65 7 Dehydrating Breather Assembly 7 Dehydrating Breather Assembly The dehydrating breather is designed to remove moisture from the air breathed into the load tap changer. It consists of a cylindrical glass body, top connecting flange, bottom breather/trap and an exterior protective grate with three observation ports. 7.1 Receiving The breather is shipped detail with the dehydrating material placed in separate containers. 7.2 Installation (For dimensional and general installation details see drawing DD10008 in the appendix). To mount the disassembled breather: 1. Fill the breather chamber with dry dehydrating material (approx. 2.2 lbs.) through the opening in the flange on the breather top. 2. Place the flange gasket on top of the flange followed by the mounting bracket, aligning the threaded hole with the flange opening. Secure with two M10 x 35 hex head bolts, washers and locking nuts. Mount the dehydrating chamber to the pad (provided by the user) on the transformer tank wall. See sketch "A" on drawing DD10008 for recommended mounting pad dimensions. Secure with two M10 x 35 hex bolts, washers and locking nuts. Connect the tubing between the top of the breather and one of the 0.25" half couplings provided on the LTC side walls. All connections must be air tight. Use of a high temperature grease on the screw joints helps prevent rust and permits the parts to be removed easily when necessary. 3. Remove the clear plastic oil collection cell by squeezing the retaining bracket. Fill it with clean transformer oil until the oil level is between the two fill level lines on the cell. Carefully place the filled oil collection cell back onto the breather housing bottom. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 65

66 7 Dehydrating Breather Assembly 7.3 Operation The breather permits in- and out-breathing when there is a difference in pressure between the LTC gas space and the atmosphere exceeding the head of oil in the breather/trap. The dehydrating material is protected from the ambient humidity by the oil in the collection cell which also serves to trap any particles in the air during in-breathing. The cylindrical body is filled with dehydrating material which is orange in color when in the dry state. When it becomes saturated with moisture, its color changes to green or colorless. The color change can be observed through the observation ports in the protective grate. The dehydrating material should be replaced when 75% of the material has changed from orange to green or colorless. 7.4 Maintenance Two dehydrating materials (desiccant) are available: 1. Silica gel (6 to 16 mesh) which is orange in color when in dry state. It turns green when saturated. 2. Sorbead ORANGE (4 to 8 mesh) which is orange in color when in dry state. It turns colorless when saturated. The time between subsequent changes of the dehydrating material depends upon the load cycle of the transformer and the ambient conditions. It is advisable to check the color of the material frequently at first, to determine the approximate time interval for replacement of the desiccant for the particular application. A recommended method is to have a second charge of dry dehydrating material on hand in a sealed container. This allows a quick renewal of the dehydrating breather filling. The removed saturated desiccant can later be dried out and stored for the next change. To replace the desiccant, carefully remove and empty the oil collection cell and remove the dehydrating breather from its holder by loosening the two M10 x 35 hex bolts. Empty the saturated material through the hole in the top flange into a pan. Refill the breather with a fresh charge and fill the oil collection cell with clean transformer oil to the level indicated on the cell. Reinstall the breather on its holder, making sure the flange gasket is in place. Finally, place the oil collection cell in its bracket. 66 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

67 7 Dehydrating Breather Assembly The saturated desiccant can be placed in an open pan and dried at a temperature of 130 C to 160 C (266 F to 320 F) for about 2-3 hours. When dry, the material regains its orange color. Since the particles dry from the outside towards the center, the outer surface will change its color first. This initial change in color should not be considered as a complete reactivation of the desiccant. It should be allowed to dry as specified above. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 67

68

69 8 Vacuum Interrupter Monitoring (VIM) System 8 Vacuum Interrupter Monitoring (VIM) System Refer to Chapter 3.7 for safety instructions. 8.1 Vacuum Interrupter Monitoring System Description The RMV LTC utilizes a unique monitoring system to abort the tap change operation in case a vacuum interrupter has failed to interrupt the current just prior to the opening of the tap selector contacts or in the event of monitoring system supply power loss. The system is the only one of its kind on a load tap changer. Utilizing bias resistant fiber optic signals, which move through the LTC tank for a portion of each tap change, the RMV provides self-examination of each and every operation. Special DC logic within the monitoring system electronics interprets current sensing optical signals as trigger input is received from a precisely timed cam-operated microswitch (186). Should current be flowing through the vacuum interrupter circuit when it normally would be open, the LTC is immediately stopped and returned to the position from whence it came. Latching alarm relays prevent further operation until the system has been reset. System verification must always take place prior to resetting and placing the LTC back in operation. Specific components utilized in the monitoring scheme are as follows: SP supervisory power indication relay located on the printed circuit board; 86L, 86C, 86R latching alarm relays located on the printed circuit board; 86X, 86XL & 86XR control relays located within customer s control cabinet; 86GL (green/ power on) & 86RL (red/alarm) status pilot lights located within customer s control cabinet. Any alarm condition, whether vacuum interrupter failure, abnormal CT signal, or loss of monitoring supply power, will cause the 86RL pilot light <alarm condition> to illuminate. Additionally, any single or combination of the latching relays will energize the 86X relay blocking the function of the raise/lower switch while bringing the LTC back to the position from whence it came via the 86XL or 86XR relays, depending on which direction the LTC was moving. Additionally the function of the CT-Light Conductor circuit within the LTC is continuously verified. Utilizing the input from the AIW ( All is Well ) microswitch, the circuit checks for signals between the time that the Bypass opens until the Vacuum Interrupter opens. In this situation, CT signals should be present to indicate that the devices (CTs, Light Conductors) and wiring are functional and Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 69

70 8 Vacuum Interrupter Monitoring (VIM) System all is normal. If any component is not working properly, the associated input terminal would not have signals present, and the system would recognize the fault condition. The appropriate phase LED (Yellow) would be illuminated, and the (SP) trip relay would be latched causing the 86RL pilot light to illuminate and locking out the LTC. If the LTC is to be operated while being out-of-service, the Monitoring System is able to ignore the CT-Light Conductor condition allowing tap change without a CT signal. Temporary bypass of the CT-Light Conductor integrity check (Maintenance Mode) can be initiated with the TEST (Green) and RESET (Red) pushbuttons using the following sequence: 1. Press and hold the RESET button for 5-6 seconds to disable the verification system for 10 hours (three yellow LEDs flash slowly). At the end of the 10 hours, the LED's go out and the unit returns to normal function. 2. Push the TEST button to manually exit Maintenance Mode and return to normal function again, as opposed to waiting for the time to expire. The monitoring system electronics are protected from over-voltage and transient conditions on the power supply by varistor technology and against inadvertent improper power supply by a traditional in-line replaceable fuse. The monitoring system is completely functional between 90 & 140 VAC supply voltage. 8.2 Evolution of Design The original RMV-I vacuum interrupter monitoring system is triggered by a reed switch RSW with input to its circuit board at terminal points 19 & 24. This system remained in production until superseded by the 186 microswitch design in August The 186 microswitch input to the circuit board was then changed to terminal points 6 & 7. The circuit board at that time was changed to service either construction (universal) by making terminal points 6 common to 19 and 7 common to 24. A dedicated input circuit board with microprocessor based logic (Model A ) was introduced in September 2002, to supersede the universal input circuit board. It has the 186 microswitch input only at terminal points 6 & 7. In addition an optional Model B circuit board with a secondary microswitch AIW input at terminal points 8 & 9 was also introduced in September 2002, to base the Maintenance-Free schedule strictly on operation count intervals regardless of time in service. The Model B circuit board was made standard in July 2005 for all RMV s. 70 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

71 8 Vacuum Interrupter Monitoring (VIM) System 8.3 Installation and Wiring Due to the close proximity of the terminal points on the circuit board, care must be taken to insure that no loose strands of adjacent circuit wires contact one another. Using wire ferrules or twisting and soldering strands together will help insure that no loose strands contact other conductors. Conductor capacity for the terminal blocks is as follows: Single stranded conductor - 26 to 14 AWG; double stranded conductor (jumpers; sharing) - 26 to 16 AWG. If larger conductors must be used with the ends reduced by cutting away strands, care must be taken to insulate the cut back strands so they do not short to adjacent conductors! (heat shrink tubing is recommended). Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 71

72 8 Vacuum Interrupter Monitoring (VIM) System 8.4 In-Service Monitoring System Verification Verification of the monitoring and runback systems can be accomplished while the transformer is energized, with or without load. With the transformer energized, bring the LTC to any bridging position. On a standard position indicator 16L-N-16R, this would be any odd numbered position. In this position there will be enough circulating current to generate a signal through the CT-Light Conductor circuit. By simply simulating the closure of the RSW or 186 switch while the LTC is on the bridging position, a three phase vacuum interrupter alarm can be generated. This test confirms the LTC internal components are functional. For reed switch RSW triggered units momentarily jump terminals 19 & 24 and for 186 microswitch triggered units jump terminals 6 & 7 while the LTC is on a bridging position to perform the test. All three red LEDs must come on and the RESET (red) pushbutton on the circuit board must clear or turn the three red LEDs back off. The runback circuit may then be checked by initiating a tap change and pushing the TEST (green) button during the movement of the LTC. This test usually requires two people; one at the control cabinet and one at the monitoring circuit board. This should be performed in both the raise and lower direction to verify the runback system. The RESET (red) pushbutton will need to be pushed to clear the alarm condition prior to testing in the opposite direction. 8.5 In-Service Monitoring System Trip (Lockout / 86RL) If an in-service installation experiences a vacuum interrupter alarm on its own (one, two or three phases), call Reinhausen Manufacturing for support and instruction at VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

73 8 Vacuum Interrupter Monitoring (VIM) System 8.6 Replacement, Spare or Upgrade Parts Original Reed Switch RSW Triggered System Fuse for circuit board (1/8A 250V) Reed Switch RSW Upgrade for RSW units 1A68859 Model A Printed Circuit Board 8993C70H01* Model B Upgrade (AIW) 1A68858* 186 Microswitch Triggered System (Time-Based Maintenance-Free Interval) Fuse for circuit board (1/4A 250V) 8991C00H Microswitch 1A67580H02 Model A Printed Circuit Board 8993C70H01 Model B Upgrade (AIW) 1A plus AIW Microswitch Triggered System (Operation Count-Based Maintenance-Free Interval) 186 or AIW Microswitch 1A67580H02 Model B Printed Circuit Board 8999C51H01 It is recommended that the printed circuit board be replaced every 15 years, regardless of the vintage or model type. *Note: If reed switch trigger is retained, the circuit board will require jumpers from 6 to 19 and 7 to 24. Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 73

74 8 Vacuum Interrupter Monitoring (VIM) System 8.7 Monitoring System Vintage Identification Original Reed Switch RSW Triggered (Dedicated) Circuit The circuit board for this version of the system has an enclosed signal transformer which is blue in color and has relay covers that are transparent. This circuit board has one green and three red LEDs. 186 Microswitch or Reed Switch RSW Triggered (Universal) Circuit The circuit board for this version of the system has an open signal transformer which is yellow in color and has relay covers that are transparent. This circuit board has one green and three red LEDs. 186 Microswitch Triggered (Dedicated) Circuit - Model A The circuit board for this version of the system has an open signal transformer which is black in color and has relay covers that are also black. This circuit board has one green and three red LEDs. 186 plus AIW Microswitch Triggered (Dedicated) Circuit - Model B The circuit board for this version of the system has an open signal transformer which is black in color and has relay covers that are also black. This circuit board has one green, three red, and three yellow LEDs. 74 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

75 9 Spare parts List 9 Spare parts List No. Quantity Designation of Parts/Kits RM-item No Set of Hi-Pot Test Spare Parts (miscellaneous hardware including one Hi-Pot Test insulating panel 6.25 x 6.25 x in.) Vacuum Interrupter Kit, 1500 A / 2000 A / 2500 A Flexible Connector Assembly, 1500 A / 2000 A / A By-Pass Switch Kit 1500 A / 2000 A / 2500 A Access door gasket (single door), 69 kv design Access door gasket (flanged single door), 69 kv design Access door gasket (single door), 15 kv / 25 kv design Access door gasket (flanged single door), 15 kv / 25 kv design LTC Drive Shaft Flange Assembly Gear Box Drive Shaft Seal (large) Endplug (large) Gear Box Drive Shaft Seal (Small) Endplug (Small) Motor V, 60 Hz, single phase Motor with Thermo Switch (special design) V, 60 Hz, single phase Motor 120 V, 60 Hz, single phase A67701H C01H01 1A67701H02 1A67799G C54H C01H Motor Capacitor (Cylindrical) Brake Capacitor Set Brake Relay (4 Pole) Brake Relay (3 Pole) Brake Relay Dust Cover (4 Pole) Brake Relay Base (3 Pole) 8207C39H21 1A68742H C39H22 1A68742H Test Set: Monitoring System Tripping Device 4D Test Set: Vacuum Interupter Hi-Pot Device 4D36277 Table 5 Spare parts Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 75

76

77 10 Appendix 10 Appendix 10.1 Drive Mechanism, Standard Mounting Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 77

78 10 Appendix 10.2 Parts Designation: Drive Mechanism, Standard Mounting 78 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

79 10 Appendix 10.3 Drive Mechanism, Ground Level Mounting Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 79

80 10 Appendix 10.4 Parts Designation: Drive Mechanism, Ground Level Mounting 80 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

81 10 Appendix 10.5 RMV-II Load Tap Changer, Operational Sequence Schematic Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 81

82 10 Appendix 10.6 Dehydrating Breather, Dimensional and Installation Details 82 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

83 10 Appendix 10.7 Parts Designation: RMV-II Load Tap Changer, Vacuum Interrupter Assembly Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 83

84 10 Appendix 10.8 RMV-II Load Tap Changer, Vacuum Interrupter Assembly replaced by RMV-II LOAD TAP CHANGER Vacuum Interrupter Assembly : 1E 84 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

85 10 Appendix 10.9 Parts Designation: RMV-II Load Tap Changer, By-Pass Switch Assembly Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 85

86 10 Appendix RMV-II Load Tap Changer, By-Pass Switch Assembly 86 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

87 10 Appendix Parts Designation: RMV-II Load Tap Changer, Cam Switch Assembly Maschinenfabrik Reinhausen /00 EN VACUTAP RMV-II 87

88 10 Appendix RMV-II Load Tap Changer, Cam Switch Assembly 88 VACUTAP RMV-II /00 EN Maschinenfabrik Reinhausen 2010

VACUTAP RMV-II HIGHEST STANDARD IN ON-LOAD TAP-CHANGERS. IMPRESSIVE BY DESIGN. TRANSFORMER CONTROL

VACUTAP RMV-II HIGHEST STANDARD IN ON-LOAD TAP-CHANGERS. IMPRESSIVE BY DESIGN. TRANSFORMER CONTROL HIGHEST STANDARD IN ON-LOAD TAP-CHANGERS. IMPRESSIVE BY DESIGN. TRANSFORMER CONTROL THE POWER BEHIND POWER. For over 25 years, we have been testing and improving North America s most popular OLTC the VACUTAP

More information

Motor-drive mechanism, type BUL. Technical guide

Motor-drive mechanism, type BUL. Technical guide Motor-drive mechanism, type BUL Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax Network Protector Instruction Manual Type 316NP ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1232-001B DISCLAIMER OF WARRANTIES

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual 1ZSE 5492-155 en, Rev. 4 On-load tap-changers, type UC User s manual Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Type VRLTC load tap changer Installation and maintenance guide

Type VRLTC load tap changer Installation and maintenance guide Type VRLTC load tap changer Installation and maintenance guide i VRLTC load tap changer Installation and maintenance guide Recommended practices ABB recommends careful consideration of the following factors

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

1ZSC ABH en, Rev. 1. Motor-drive mechanisms, types BUE and BUL2 Maintenance guide

1ZSC ABH en, Rev. 1. Motor-drive mechanisms, types BUE and BUL2 Maintenance guide 1ZSC000498-ABH en, Rev. 1 Motor-drive mechanisms, types BUE and BUL2 Maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List ZSE 5492-33 en, Rev. 3, 2004-04-5 This document must not be copied without our written

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised

More information

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com INSTRUCTIONS INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall

More information

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD

More information

Three-Phase Pole Mounted Recloser

Three-Phase Pole Mounted Recloser Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

On-Load Tap-Changer Type V

On-Load Tap-Changer Type V www.reinhausen.com On-Load Tap-Changer Type V Operating Instructions BA081/04 2 Contents Contents 1 General 1.1 Safety instructions 5 1.2 Specified application 5 2 Design 6 3 Shipment 6 4 Installation

More information

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers Instructions for Load Break Air Switch, Type LBF, for Power Centers The Westinghouse Type LB 1 F Switch is an air insulated, gang operated, three pole, two position link type load interrupter switch. The

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03 INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR469000 OR25 REV03 I II CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment

More information

Shanghai Huaming Power Equipment Co.,Ltd.

Shanghai Huaming Power Equipment Co.,Ltd. HM 0.460.4101-03-02/2017 Shanghai Huaming Power Equipment Co.,Ltd. 1 General CV2 on load tap changer (herein referred as the tap changer) is of selector switch structure, which combines the functions

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive Vacuum Circuit-Breakers, Type HVX 12 24 kv, of cassette design, cassette with motor drive Operating Instructions No. 531 321, Edition 09/00 Table of Contents 1 General 4 1.1 Operating Conditions 4 2 Design,

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,

More information

Transformer Components & Accessories

Transformer Components & Accessories Transformer Components & Accessories Brian Brinson Mechanical Design Manager brian.brinson@spx.com Agenda 1. Standards / Equipment Overview 2. Bushings 3. Arresters 4. Cooling Equipment 5. Instrument Transformers

More information

INSTRUCTION MANUAL #103

INSTRUCTION MANUAL #103 INSTRUCTION MANUAL #103 www.ermco eci.com THREE PHASE PAD MOUNT DISTRIBUTION TRANSFORMER General instruc ons for installa on and opera on of Three Phase Pad Mount Distribu on Transformer. 2 INTRODUCTION

More information

MOTOR DRIVE UNIT MA General Technical Data Design Control Circuit Assembly... 7

MOTOR DRIVE UNIT MA General Technical Data Design Control Circuit Assembly... 7 MOTOR DRIVE UNIT MA 2 Contents Page 1. General... 3 2. Technical Data... 3 3. Design... 4 4. Control Circuit... 7 5. Assembly... 7 6. Putting in to operation... 9 7. Maintenance... 9 8. Special Designs...

More information

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required! DB 750-205 January 2007 Supercedes: December 2006 Now available with Vacuum Interrupter Monitor VBT Switch 15kV - 69kV VBU-T Switch 69kV - 230kV Longest Life Product for Electric Furnace Applications!

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00 INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR469100 BR25AT REV00 I CONTENT: 1 SAFETY 1.1 Safety instructions 1 1.2 Specified applications 1 1.3 Safety notes on the equipment operation 1 2 BR 25

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual

More information

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised

More information

GE CONSUMER & INDUSTRIAL

GE CONSUMER & INDUSTRIAL GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B

More information

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment Use load interrupter attachments to enable loop sectionalizing, line dropping, load breaking and transformer-magnetizing current interruption. Increase the capability of your disconnect switches by adding

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

HexPro Series Low Profile Wrenches

HexPro Series Low Profile Wrenches HexPro Series Low Profile Wrenches Operation and Maintenance Manual Model 2HP 4HP 8HP 14HP 30HP www.torquetoolsinc.com Use the HEXPRO Series Low Profile Wrenches Model 2HP 4HP 8HP 14HP 30HP to install

More information

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

OLYMPIAN MODEL 740 Operation and Service Manual

OLYMPIAN MODEL 740 Operation and Service Manual OLYMPIAN MODEL 740 Operation and Service Manual P/N 133911-102 FCI MANUAL P/N 133865-001 Data herein has been verified and validated and believed adequate for the intended use. If the machine or procedures

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

On-Load Tap-Changer OILTAP MS

On-Load Tap-Changer OILTAP MS www.reinhausen.com On-Load Tap-Changer OILTAP MS Operating Instructions BA 65/04 Contents Contents 1 General... 5 1.1 Safety Instructions... 5 1.2 Specified Application... 5 2 Design/Types... 6 3 Shipment...

More information

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK --------------------------------------------------------------------------------------------------------------- Sub. Code : EE2402 Semester

More information

Transformer Installation, Operation, and Maintenance Manual

Transformer Installation, Operation, and Maintenance Manual Transformer Installation, Operation, and Maintenance Manual CONTENTS INTRODUCTION......................................... 2 INSPECTION UPON RECEIVING... 2 STORAGE...............................................

More information

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage. Voltage Regulators QD8 Movable Contact Board Replacement Procedure Kit 5742895B01 Service Information S225-50-38 Contents General..................................... 1 Parts Supplied...............................

More information

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing

More information

VARNA Products 15 GPM (57 LPM) Prelube Kit for MTU 4000 Series Marine Engines

VARNA Products 15 GPM (57 LPM) Prelube Kit for MTU 4000 Series Marine Engines VARNA Products 15 GPM (57 LPM) Prelube Kit for MTU 4000 Series Marine Engines Installation and Users Manual For the following Prelube Kits: VARNA Products P/N 6423 Kit for 208 VAC 3 Phase VARNA Products

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

On-Load Tap changer Type V

On-Load Tap changer Type V Easun - MR Tap changers (P) Ltd., Chennai, India ON-LOAD TAP CHANGER TYPE V Easun - MR Tap Changers (P) Ltd., 612 (232), M.T.H. Road, Tiruninravur, Chennai - 602 024, India Phone : 91-44 - 26390863 ( Hunting

More information

Operation and Maintenance Manual http://www.torsionx.eu Use the MaxDrv Series Square Drive Torque Wrench Model.75, 1, 3, 5, 8, 10, 20, 25, 35, 50 to install and remove threaded fasteners requiring precise

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored

More information

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION

SECTION 3.00 WARNING WARNING ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION SECTION 3.00 ENGINE STARTUP AND SHUTDOWN PRESTART INSPECTION Be sure that the clutch, circuit breaker, or other main power transmission device is disconnected. Generators develop voltage as soon as the

More information

Low Profile Wrenches Operation and Maintenance Manual

Low Profile Wrenches Operation and Maintenance Manual Low Profile Wrenches Operation and Maintenance Manual http://www.torquetoolsinc.com Use the HEXPRO Series Low Profile Wrenches Model 2HP 4HP 8HP 14HP 30HP to install and remove large bolts that have minimal

More information

INSTRUCTION AND REPAIR MANUAL MODELS 341A, 342A AND 344A 6

INSTRUCTION AND REPAIR MANUAL MODELS 341A, 342A AND 344A 6 SECTION 6 ITEM 0 DATED JUNE 1998 SUPERSEDES ITEMS 1, 2, DATED MARCH 1992 INSTRUCTION AND REPAIR MANUAL MODELS 1A, 2A AND A 6 NOTE This repair manual is applicable to pump Models 1A, 2A and A. All photos

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL The High Performance Company Table Of Contents: page Safety instructions: Definitions of Terms... 2 Introduction principle of operation...

More information

100 / 110 DRYWELL FUSE SPECIFICATION

100 / 110 DRYWELL FUSE SPECIFICATION 100 / 110 DRYWELL FUSE SPECIFICATION 15KV & 25KV SUBMERSIBLE VACUUM LOAD INTERRUPTERS AND DRYWELL FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED SUBMERSIBLE SWITCHGEAR WITH LOAD INTERRUPTING SWITCHES

More information

Maintenance Instructions

Maintenance Instructions General Note These instructions contain information common to more than one model of Bevel Gear Drive. To simplify reading, similar models have been grouped as follows: GROUP 1 Models 11, 0, 1,, (illustrated),,

More information

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Class 6065 Instruction Bulletin 6065-13 11/2011 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully and look

More information

MOREHOUSE INSTRUMENT COMPANY, INC. 60,000 LBS CAPACITY AIRCRAFT PART NUMBER SCALE S FORCE CALIBRATION PRESS PART NO.

MOREHOUSE INSTRUMENT COMPANY, INC. 60,000 LBS CAPACITY AIRCRAFT PART NUMBER SCALE S FORCE CALIBRATION PRESS PART NO. INDEX 1. GENERAL SPECIFICATION AND DRAWING 804000-03... 2 2. ASSEMBLY INSTRUCTIONS... 5 3. OPERATING INSTRUCTIONS... 6 4. MAINTENANCE INSTRUCTIONS... 7 5. CERTIFICATE OF CAPACITY LOAD TEST AND OVERLOAD...

More information

RUFNEX Series Low Profile Wrenches Operation and Maintenance Manual

RUFNEX Series Low Profile Wrenches Operation and Maintenance Manual RUFNEX Series Low Profile Wrenches Operation and Maintenance Manual http://www.torsionx.com Use the RUFNEX Series Ultra-Low Profile Wrenches to install and remove large bolts that have minimal wrench clearance.

More information

DeZURIK R1 AND R2 POWERRAC ACTUATORS

DeZURIK R1 AND R2 POWERRAC ACTUATORS R1 AND R2 POWERRAC ACTUATORS Instruction D10268 July 2016 Instructions These instructions provide installation, operation, and maintenance information for R1 AND R2 POWERRAC Actuators. They include procedures

More information

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version Optimal Series Automatic Transfer Switch Installation and User Manual for the OPT2225 Automatic Transfer Switch Full Version File: OPT2225 Rev2.5.doc November, 2004 2 Thank You For Purchasing This DynaGen

More information

Underground Distribution Switchgear

Underground Distribution Switchgear Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,

More information

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center

More information

GT-200 GATE VALVES PN16, Screwed end

GT-200 GATE VALVES PN16, Screwed end Document No. : MD-QO-04-281 Date : 2009/07 /17 Version : 1.0 GT-200 GATE VALVES PN16, Screwed end USER MANUAL Modentic Industrial Corporation 14F-1,No.57Taya Rd.,Taichung,Taiwan,R.O.C. Email:modentic@ms9.hinet.net

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

IBT Series Square Drive Torque Wrenches

IBT Series Square Drive Torque Wrenches IBT Series Square Drive Torque Wrenches Operation and Maintenance Manual Model.75, 1, 3, 5, 8, 10, 20, 25, 35, 50 http://www.torsionx.com Use the IBT Series Square Drive Torque Wrenches Model.75, 1, 3,

More information

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view) Figure 1: Types CA-16 Relay (front view) Photo Figure 2: Types CA-16 Relay (rear view) Photo 2 Sub 5 185A419 Sub 6 185A443 Figure 3: Internal Schematic of the Type CA-16 bus Relay or CA-26 Transformer

More information

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

Type CRN-1 Reverse Power Relay 50 and 60 Hertz ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-251.2P Effective: June 1991 Supersedes I.L. 41-251.2N Dated April 1988 ( )Denotes Change

More information

DeZURIK R1 POWERRAC ACTUATOR ON 1/2-3" PEC ECCENTRIC VALVES

DeZURIK R1 POWERRAC ACTUATOR ON 1/2-3 PEC ECCENTRIC VALVES R1 POWERRAC ACTUATOR ON 1/2-3" PEC ECCENTRIC VALVES Instruction D10381 August 2012 Instructions These instructions provide information about the R1 PowerRac actuator. They are for use by personnel who

More information

BUSWAY Low Voltage (Pow-R-Flex)

BUSWAY Low Voltage (Pow-R-Flex) BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

PATENT PENDING. Phone: (877) Operation and Service Manual

PATENT PENDING.   Phone: (877) Operation and Service Manual PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product

More information

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL SERIES 35-72 120 VAC Microprocessor Based Direct Spark Ignition Control 35.72.03 FEATURES Two Mounting Configurations Open Board With Stand-Off's - saves space and cost Potted - protection for washdown

More information

Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana

Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana Supersedes Descriptive Bulletin, pages 1-8, dated January, 1976 Mailed to: E, D, C/38-000F Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana

More information

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,

More information

OPERATION AND MAINTENANCE MANUAL

OPERATION AND MAINTENANCE MANUAL WREN IBT SERIES HYDRAULIC TORQUE WRENCHES IBT SQUARE DRIVE SERIES OPERATION AND MAINTENANCE MANUAL FOR WREN Products: POINT 75, 1IBT, 3IBT, 5IBT, 8IBT, 10IBT, 20IBT, 25IBT, 35IBT, 50IBT SQUARE DRIVE HYDRAULIC

More information

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) Inspection Recommendations for Switchgear with Type AT-3 Source- Transfer Controls Table of Contents Section

More information

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy. Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings

More information

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION SERIES 1000-X OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION Publication S1000X-110 VER0215-1 For information on this product and

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

Company Switch Installation Instructions and User Manual

Company Switch Installation Instructions and User Manual Lex Products Corporation 15 Progress Drive Shelton, CT 06484 203.363.3738 203.363.3742 Fax Lex West 11847 Sheldon Street Sun Valley, CA 91352 818.768.4474 818.768.4040 Fax www.lexproducts.com info@lexproducts.com

More information

On-load tap-changer OILTAP V

On-load tap-changer OILTAP V www.reinhausen.com On-load tap-changer OILTAP V Technical Data TD 82/03 Table of Contents Table of Contents 1 General... 4 1.1 Summary of the technical data... 4 1.2 Survey... 6 2 Technical Data... 13

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information