On-load tap-changer OILTAP V

Size: px
Start display at page:

Download "On-load tap-changer OILTAP V"

Transcription

1 On-load tap-changer OILTAP V Technical Data TD 82/03

2

3 Table of Contents Table of Contents 1 General Summary of the technical data Survey Technical Data Rated through-current (I u ), rated step voltage (U i ) and step capacity (P StN ) On-load tap-changer V III 250 Y/D and V III 400 Y/D Restriction of the rated step voltage U i Contact life Rated withstand voltages of the internal insulation Appendix dimension and installation drawings NOTE These technical data are intended for the calculator and designer of the transformer. These type-specific data are only valid in connection with the information contained in the general section (TD 61) since this section contains important information on such subjects as potential connection, leakage inductance, current division, and so on. Dimensional drawings and connection diagrams are subject to change without prior notice. Drawings submitted during bidding and ordering are always binding. Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformer manufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirements of the transformer are met. TD 82/03 EN 3

4 1 General 1 General 1.1 Summary of the technical data On-load tap-changer V III 200 Y V III 200 D V III 350 Y V III 350 D V I 350 Number of poles and application neutral point at any point on neutral point at any point on the winding the winding Max. rated through-current I um (in A) Rated short-time withstand 4 5 current (in ka) Rated short-circuit duration 3 3 (in s) Rated peak withstand current (in ka) 10 12,5 Max. rated step 10 contacts voltage U im 12 contacts 1200 to to 1400 (in V) 14 contacts Step capacity 10 contacts (P StN ) 12 contacts (in kva) 14 contacts Rated frequency (in Hz) 50 to 60 Operating positions without change-over selector: max. of 14 with change-over selector: max. of 27 Rated insulation level Highest voltage for / / equipment U m (in kv) 1 Highest operating voltage U b (phase - phase) on diverter switch (in kv) Rated lightning impulse U m 40 U m 76 U m 123 U m 123/76 withstand voltage (in kv, 1,2 I 50) AC withstand voltage (in kv, 50 Hz, 1 min.) Rated withstand voltages of see table 4 internal insulation Oil compartment Pressure-proof up to 0.3 bar, continuous difference pressure (test pressure 0.6 bar), head and cover of the on-load tap-changer are vacuum-proof. Oil suction pipe Installed as standard (for details, see BA 18) Temperature range The on-load tap-changer OILTAP V can be operated in the rated load range with oil temperatures of -25 C to +105 C. Table 1a 4 TD 82/03 EN

5 1 General On-load tap-changer V III 200 Y V III 200 D V III 350 Y V III 350 D V I 350 Weight without oil (ca. in kg) Displacement without change volume over selcctor (ca. in dm 3 ) with change over selcctor Oil filling quantity V S and minimum volume ΔV 1 of the diverter switch oil compartment (in dm 3 ) V S ΔV V S ΔV V S ΔV V S ΔV V S ΔV without change over selector with over selector Table 1b Notes for table 1a: 1) In accordance with VDE 0111, part 1: R.m.s. value of the phase-phase voltage for which a piece of equipment is rated for its insulation. Notes for table 1b: 1) Applies to oil temperature ϑ = 30 C C TD 82/03 EN 5

6 1 General 1.2 Survey Fig. 1 Survey of the designs (no. of poles, change-over selector, and installation lengths) E 6 TD 82/03 EN

7 1 General Survey of the basic connection diagrams (fig. 2a, 2b, 2c) with designation of the tap selector terminal contacts in accordance with MR standards. This contact designation corresponds to the specifications in the on-load tap-changer dimension drawings. Fig. 2a excerpt from E_1 TD 82/03 EN 7

8 1 General Fig. 2b excerpt from E_2 8 TD 82/03 EN

9 1 General Fig. 2c excerpt from E_3 TD 82/03 EN 9

10 1 General Fig. 3 Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram TD 82/03 EN

11 1 General Fig. 4 Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram W TD 82/03 EN 11

12 1 General Fig. 5 Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram G 12 TD 82/03 EN

13 2 Technical Data 2 Technical Data 2.1 Rated through-current (I u ), rated step voltage (U i ) and step capacity ((P StN ) On-load tap-changer V III 200 Y/D V III 350 Y/D, V I 350 Contacts I u (A) U i (V) P StN (kva) Table 2 Rated through-currents (I u ), related rated step voltages (U i ) and step capacities (P StN ), at highest and lowest rated step voltage of the step capacity curve (see fig. 6) E Fig. 6 Step capacities (I u, U i ) 2.2 On-load tap-changer V III 250 Y/D and V III 400 Y/D On-load tap-changers V III 250 Y/D and V III 400 Y/D are available as special designs with a maximum rated through-current of I um = 250 A or 400 A. Dimensional drawings on request. TD 82/03 EN 13

14 2 Technical Data 2.3 Restriction of the rated step voltage U i Due to insulation, the rated step voltage is also limited by the dielectric strength of the tap-changer, i.e. by limitation of the total operating voltage across the contact circle. The total voltage must not exceed the limit values.: 10 contacts: Total U i = V, 12 contacts: Total U i = V, 14 contacts: Total U i = V. The rated step voltages Ui of these on-load tap-changers depend on the basic connection diagrams as shown in figures 2a, 2b and 2c and are valid under the condition that the rated step voltage is constant within the entire setting range. 2.4 Contact life The mean expected contact life of the arcing tap-changer contacts can be estimated based on the relative load (= I u / I um ) as shown in fig. 7. Since actual contact life in individual cases depends on many influencing factors while in service, only estimations can be given (not applicable to constant current service). The inspection regulations must be observed. Basic connection diagram Rated step voltage U i (in V) U i = V W W G W G G U i = V W W W G G G Fig. 7 Expected mean contact life under average load n Number of operations I u Rated through-current I um Max. rated through-current U i = V W G W W G G Table 3 Max. rated step voltage 14 TD 82/03 EN

15 2 Technical Data 2.5 Rated withstand voltages of the internal insulation Fig. 8 shows the specific voltage stresses present on the tap winding. When selecting the on-load tap-changer, a check must be made to determine whether the stress at the most unfavorable position on the on-load tap-changer does not exceed the related rated withstand voltages as shown in table 4. Insulation distances Voltage shape and V III 200 D V III 350 Y V I 350 period V III 350 D V III 200 Y a, a1 b c2 f 10 contacts 12 contacts 14 contacts U m = 40 kv U m = 76 kv U m = 123 kv/76 U m = 123 kv U m = 40 kv U m = 76 kv U m = 123/76 kv U m = 123 kv U m = 40 kv U m = 76 kv U m = 123/76 kv U m = 123 kv kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min b 1 b 2 b 3 kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min kv μs 200 kv 50 Hz 1min 70 c2 1 c2 2 kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min kv μs 350 kv 50 Hz 1min 140 f 1 f 2 f 1 f 2 f 1 f 2 kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min kv μs kv 50 Hz 1min Table 4 Rated withstand voltages (in kv) of the insulation distances (rated lightning impulse withstand voltage, AC withstand voltage) on the on-load tap-changer TD 82/03 EN 15

16 2 Technical Data Without change-over selector With reversing switch (+) - position With reversing switch ( ) - position With coarse tap selector (+) - position a1 = Between tap selector contacts of the winding of one tap position (connected or not connected) a = Between beginning and end of a tapped winding and, with coarse tap winding, between beginning and end of a coarse tap winding. Note for coarse tapping arrangement in (-) - position of the changeover selector: When stressed with impulse voltage, the permissible withstand voltage a must be adhered to between the end of a coarse tap winding connected with the K tap selector contact and the tap selector contact at the end of the tapped winding of the same phase. b = Between the tap selector contacts of different phases and between change-over selector contacts of different phases, which are connected with the beginning/end of a tapped winding or with a tap selector contact. With tap-changers for delta connection, the permissible voltages between the contacts depend on the positions of the change-over selector and the tap selector. This is why the various withstand voltages b 1, b 2 or b 3 must be adhered to for any insulation distance: b 1 = Between selected contacts of different phases b 2 = From the selected contact of one phase to the unselected contacts of other phases b 3 = Between unselected contacts of different phases f = To ground The following applies to designs without change-over selector. f 1 = Between selected tap selector contacts and ground f 2 = Between unselected tap selector contacts and ground The following applies to designs with change-over selector. f 1 = Between selected change-over selector contacts and ground f 2 = Between unselected change-over contacts and ground In addition, with coarse tapping arrangement in (+) - position of the change-over selector: c2 = Between (-) - change-over selector contacts of different phases and of one (-) -change-over selector and one (+) - change-over contact of another phase Different permissible values apply to tap-changers for delta connections. c2 1 = Between one (-) - change-over selector contact and one (+) - change-over selector contact of another phase c2 2 = Between one (-) - change-over selector contact of different phases With coarse tap selector ( ) - position E Fig. 8 Specific voltage stress of the tap winding 16 TD 82/03 EN

17 3 Appendix 3 Appendix Dimension drawings, U m = 40 kv and 123 kv On-load tap-changer OILTAP V III 200 Y Without change-over selector With change-over selector On-load tap-changer OILTAP V III 200 D Without change-over selector With change-over selector On-load tap-changer OILTAP V III 350 Y Without change-over selector With change-over selector On-load tap-changer OILTAP V III 350 D Without change-over selector With change-over selector On-load tap-changer OILTAP V I 350 Without change-over selector With change-over selector Installation drawings On-load tap-changer OILTAP V On-load tap-changer OILTAP V On-load tap-changer OILTAP V 200, tie-in resistors attached on the side On-load tap-changer OILTAP V 350, tie-in resistors attached on the side On-load tap-changer OILTAP V III 200 Y / V III 350 Y, tie-in resistors attached on the cylinder for 2, 3 or 4 tie-in resistors/phase Additional drawings On-load tap-changer head Special design for installation in bell-type tanks On-load tap-changer head with mounting flange for pressure relief valve Swivelling range of the gear unit, drive shaft left Swivelling range of the gear unit, drive shaft right Horizontal drive shaft (standard and special design) Directory of additional drawings for on-load tap-changer OILTAP V in acc. w. note in the dimension drawings TD 82/03 EN 17

18 E On-load tap-changer OILTAP V V III 200 Y - 40 to 123-0, dimension drawing 18 TD 82/03 EN

19 E On-load tap-changer OILTAP V V III 200 Y - 40 to W/G, dimension drawing TD 82/03 EN 19

20 E On-load tap-changer OILTAP V V III 200 D - 40 to 123/76-0, dimension drawing 20 TD 82/03 EN

21 E On-load tap-changer OILTAP V V III 200 D - 40 to 123/76 - W/G, dimension drawing TD 82/03 EN 21

22 E On-load tap-changer OILTAP V V III 350 Y - 40 to 123-0, dimension drawing 22 TD 82/03 EN

23 E On-load tap-changer OILTAP V V III 350 Y - 40 to W/G, dimension drawing TD 82/03 EN 23

24 E On-load tap-changer OILTAP V V III 350 D - 40 to 123/76-0, dimension drawing 24 TD 82/03 EN

25 E On-load tap-changer OILTAP V V III 350 D - 40 to 123/76 - W/G, dimension drawing TD 82/03 EN 25

26 E On-load tap-changer OILTAP V V I to 76-0, dimension drawing 26 TD 82/03 EN

27 E On-load tap-changer OILTAP V V I to 76 - W/G, dimension drawing TD 82/03 EN 27

28 E On-load tap-changer OILTAP V Installation drawing 28 TD 82/03 EN

29 E On-load tap-changer OILTAP V 350 Installation drawing TD 82/03 EN 29

30 E On-load tap-changer OILTAP V III 200 Y/D Tie-in resistors, attached on the side 30 TD 82/03 EN

31 E On-load tap-changer OILTAP V III 350 Y/D Tie-in resistors, attached on the side TD 82/03 EN 31

32 E On-load tap-changer OILTAP V III 200 Y / V III 350 Y Tie-in resistors, attached on the cylinder for 2, 3 or 4 tie-in resistors/phase 32 TD 82/03 EN

33 E On-load tap-changer OILTAP V On-load tap-changer head TD 82/03 EN 33

34 E On-load tap-changer OILTAP V Special design for bell-type tank installation Lifting device O-ring Lifting traverse (illustrated in turned position) Transformer cover Washer 8 Gasket Supporting flange Lifting traverse Z - Centering bolt Further dimensions of tap changer head see dwg Lifting traverse see dwg TD 82/03 EN

35 E On-load tap-changer OILTAP V Mounting flange for pressure relief valve TD 82/03 EN 35

36 E On-load tap-changer OILTAP V Design with flange for pressure relief valve Swivelling range of the gear unit, drive shaft left 36 TD 82/03 EN

37 E On-load tap-changer OILTAP V Design with flange for pressure relief valve Swivelling range of the gear unit, drive shaft right TD 82/03 EN 37

38 E On-load tap-changer OILTAP V Horizontal drive shaft (standard and special design) 38 TD 82/03 EN

39 E On-load tap-changer OILTAP V Directory of the additional drawings in acc. w. note in dimension drawings Installation drawing for on-load tap-changer OILTAP V Installation drawing for on-load tap-changer OILTAP V On-load tap-changer head On-load tap-changer head, bell-type tank Horizontal drive shaft TD 82/03 EN 39

40 Maschinenfabrik Reinhausen GmbH Phone Falkensteinstrasse 8 Fax Regensburg, Germany sales@reinhausen.com Please note: The data in our publications may differ from the data of the devices delivered. We reserve the right to make changes without notice. TD 82/03 EN F Printed in Germany

On-Load Tap changer Type V

On-Load Tap changer Type V Easun - MR Tap changers (P) Ltd., Chennai, India ON-LOAD TAP CHANGER TYPE V Easun - MR Tap Changers (P) Ltd., 612 (232), M.T.H. Road, Tiruninravur, Chennai - 602 024, India Phone : 91-44 - 26390863 ( Hunting

More information

VACUTAP RMV-II HIGHEST STANDARD IN ON-LOAD TAP-CHANGERS. IMPRESSIVE BY DESIGN. TRANSFORMER CONTROL

VACUTAP RMV-II HIGHEST STANDARD IN ON-LOAD TAP-CHANGERS. IMPRESSIVE BY DESIGN. TRANSFORMER CONTROL HIGHEST STANDARD IN ON-LOAD TAP-CHANGERS. IMPRESSIVE BY DESIGN. TRANSFORMER CONTROL THE POWER BEHIND POWER. For over 25 years, we have been testing and improving North America s most popular OLTC the VACUTAP

More information

On-Load Tap-Changer OILTAP MS

On-Load Tap-Changer OILTAP MS www.reinhausen.com On-Load Tap-Changer OILTAP MS Operating Instructions BA 65/04 Contents Contents 1 General... 5 1.1 Safety Instructions... 5 1.2 Specified Application... 5 2 Design/Types... 6 3 Shipment...

More information

On-Load Tap-Changer Type V

On-Load Tap-Changer Type V www.reinhausen.com On-Load Tap-Changer Type V Operating Instructions BA081/04 2 Contents Contents 1 General 1.1 Safety instructions 5 1.2 Specified application 5 2 Design 6 3 Shipment 6 4 Installation

More information

Shanghai Huaming Power Equipment Co.,Ltd.

Shanghai Huaming Power Equipment Co.,Ltd. HM 0.460.4101-03-02/2017 Shanghai Huaming Power Equipment Co.,Ltd. 1 General CV2 on load tap changer (herein referred as the tap changer) is of selector switch structure, which combines the functions

More information

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement. INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side

More information

Drive shaft Operating Instructions BA 42/07

Drive shaft Operating Instructions BA 42/07 www.reinhausen.com Drive shaft Operating Instructions BA 42/07 Contents Contents 1 General... 3 1.1 Safety labels... 3 1.2 Safety instructions... 3 1.3 Specified application... 3 2 Design/Types... 4 3

More information

SHZV Vacuum On-Load Tap Changer Operation Instructions

SHZV Vacuum On-Load Tap Changer Operation Instructions SHZV Vacuum On-Load Tap Changer Operation Instructions HM 0.460.1902 Shanghai Huaming Power Equipment Co.,Ltd. SHZV VACUUM ON-LOAD TAP CHANGER OPERATION INSTRUCTIONS HM0.460.1902 Attentions 1. Please read

More information

On-Load Tap-Changer Type CM Operating Instructions

On-Load Tap-Changer Type CM Operating Instructions HM0.60.30 On-Load Tap-Changer Type CM Operating Instructions HM 0.60.30-03.0/205 Shanghai Huaming Power Equipment Co., Ltd. 2 HM0.60.30 Thank you for choosing on-load tap-changer Prior to using the on-load

More information

SHZV Vacuum On-Load Tap Changer Operation Instructions

SHZV Vacuum On-Load Tap Changer Operation Instructions SHZV Vacuum On-Load Tap Changer Operation Instructions HM 0.460.1902 Shanghai Huaming Power Equipment Co.,Ltd. SHZV VACUUM ON-LOAD TAP CHANGER OPERATION INSTRUCTIONS HM0.460.1902 Attentions 1. Please read

More information

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK 1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv

3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv 3EP1 Surge Arrester Metal-oxide surge arrester without series gaps for high-voltage systems up to U m = 170 kv Rated voltage up to 180 kv Nominal discharge current 10 ka, 8/20 µs Line discharge class LD1,

More information

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide 1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide 1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

More information

CONTENTS. 1. Specification Details Description of the On Load Tap Changer Principal Parts of the On Load Tap Changer...

CONTENTS. 1. Specification Details Description of the On Load Tap Changer Principal Parts of the On Load Tap Changer... CONTENTS 1. Specification Details... 2 2. Description of the On Load Tap Changer... 4 3. Principal Parts of the On Load Tap Changer... 5 3.1 Diverter Switch Oil Tank... 5 3.2 Diverter Switch... 6 3.3 Transition

More information

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03 INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR469000 OR25 REV03 I II CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment

More information

Indoor switches for railway lines. single-pole design rated voltage up to 27,5 kv rated current up to 4000 A

Indoor switches for railway lines. single-pole design rated voltage up to 27,5 kv rated current up to 4000 A Indoor switches for railway lines single-pole design rated voltage up to 27,5 kv rated current up to 4000 A General These Driescher indoor switching devices are specifically designed for railway applications.

More information

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide 1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00

INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00 INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR469100 BR25AT REV00 I CONTENT: 1 SAFETY 1.1 Safety instructions 1 1.2 Specified applications 1 1.3 Safety notes on the equipment operation 1 2 BR 25

More information

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

Power Quality innovative SolutionS for industrial and distribution grids.

Power Quality innovative SolutionS for industrial and distribution grids. Power Quality innovative SolutionS for industrial and distribution grids. POWER QUALITY Power Quality - Solutions for grid efficiency improvement, loss reduction and voltage stabilization. 2 Improving

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench

More information

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear. Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear www.siemens.com/energy Technology s Contents Application Page Benefits 2 Typical uses 2 and 3 Technical

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses Main characteristics 450 TO 700VAC / 63 TO 2800A Recognized Exceptionally low I 2 T, Watt losses. Non-magnetic construction, Highly reliable low voltage Trip-indicator system, conformity to UL, IEC, DIN

More information

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

Throughout the years, various types of off circuit tap changers (OCTCs) have been developed in Hyundai Heavy Industries Co.

Throughout the years, various types of off circuit tap changers (OCTCs) have been developed in Hyundai Heavy Industries Co. Throughout the years, various types of off circuit tap changers (OCTCs) have been developed in Hyundai Heavy Industries Co. Bulgaria (HHIB): PBV PBVK PBVE PBVL PBVKL The OCTCs manufactured in HHIB are

More information

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide 1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer This document contains sample specifications for Liquid-Filled Type Drive Transformers You may

More information

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications Data Sheet System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications 2CDC021031S0011 2CDC021033S0011 The miniature circuit breaker S 200 M UC extends the established ABB System

More information

SERIES TAP-CHANGER

SERIES TAP-CHANGER SERIES 090 - TAP-CHANGER Main characteristics This is an off-circuit tap changer. It means DO NOT OPERATE WHILE THE TRANSFORMER IS ENERGISED. Main characteristics of this tap-changer series are: dimensional

More information

Transformer bushings, type GOH. Technical guide

Transformer bushings, type GOH. Technical guide Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

Prüffeld der Schaltwerke

Prüffeld der Schaltwerke Report No.: 16-043-MS Sheet: 2 Notes 1. The testing station of the Siemens switchgear factory (Prüffeld der Schaltwerke),, Berlin, has been approved by the DAkkS (German accreditation body) for rendering

More information

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.

tests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual

More information

3TM Vacuum Contactors

3TM Vacuum Contactors Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents

More information

CONTENTS About the company 1. Low-voltage arresters LVA type 2. Metal-oxide surge arresters for distribution systems. 3.

CONTENTS About the company 1. Low-voltage arresters LVA type 2. Metal-oxide surge arresters for distribution systems. 3. CONTENTS About the company 4 1. Low-voltage arresters LVA type 5 2. Metal-oxide surge arresters for distribution systems. 6 2.1 PA-DM type 6 Dimensions of arresters of PA-DM 9 2.2 PA-DH types 10 Dimensions

More information

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List ZSE 5492-33 en, Rev. 3, 2004-04-5 This document must not be copied without our written

More information

On-Load Tap-Changer VACUTAP VV

On-Load Tap-Changer VACUTAP VV On-Load Tap-Changer VACUTAP VV Operating Instructions 4349312/00 EN All rights reserved by Maschinenfabrik Reinhausen Dissemination and reproduction of this document and use and disclosure of its content

More information

TECHNICAL DATA TYPE WDG/WLG/WSG OFF- CIRCUIT TAP CHANGER

TECHNICAL DATA TYPE WDG/WLG/WSG OFF- CIRCUIT TAP CHANGER TECHNICAL DATA TYPE WDG/WLG/WSG OFF- CIRCUIT TAP CHANGER SHANGHAI HUAMING POWER EQUIPMENT CO., LTD. Contents 1. General 2 2. Technical specifications 3 3. Type designation 6 4. Terms and definitions 8

More information

Compact Integrated Distribution Substation (CIDS)

Compact Integrated Distribution Substation (CIDS) Compact Integrated Distribution Substation (CIDS) 1- INTRODUCTION SAVE SPACE 2.5m 2 footprint for CIDS up to 630kVA. SAVE THE ENVIRONMENT No SF6, No PCB. SAVE MONEY Save up to 50% from conventional package

More information

Scheda prodotto Relè Series B

Scheda prodotto Relè Series B Relè di Potenza All-or-Nothing Relays designed to meet high power switching applications with up to three changeover contacts, rated 4000 or 7500 VA - AC1. They are ideally suited for arduous duties where

More information

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide 1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench

More information

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A Gas-Insulated Switchgear Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A siemens.com/energy-management Table of content Gas-insulated switchgear Product portfolio 72.5 550 kv Vacuum interrupters for switching

More information

GRIDCON ACF ESS GREAT COMBINATION ACTIVE FILTER AND ENERGY STORAGE.

GRIDCON ACF ESS GREAT COMBINATION ACTIVE FILTER AND ENERGY STORAGE. GRIDCON ACF ESS GREAT COMBINATION ACTIVE FILTER AND ENERGY STORAGE. WWW.REINHAUSEN.COM SAMSUNG ESS INSIDE 1 GRIDCON ACF ESS 2 ENERGY STORAGE SYSTEMS IMPROVE FLEXIBILITY. Energy storage systems are an attractive

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Switchgear Type 8BT1, up to 24 kv, air-insulated.   Medium Voltage Switchgear Catalog HA 26. www.siemens.com/medium-voltage-switchgear Switchgear Type 8BT1, up to 24 kv, air-insulated Medium Voltage Switchgear Catalog HA 26.31 2012 Answers for infrastructure and cities. R-HA26-013. eps Contents

More information

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv Three-phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv 06B1-E-0020 Small Space Requirement, High Reliability and Safety ー 72.5 to 145kV GIS, SDH714 The number of application

More information

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec Catalog HA 41.43 Edition 2018 Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear siemens.com/simosec Application Typical uses R-HA41-135.tif R-HA40-112.tif R-HA41-115.tif

More information

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications 2CDC021031S0011 2CDC021033S0011 The miniature circuit breaker S 200 M UC extends the established ABB System pro M compact

More information

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv HS PEXLIM-P Metal Oxide Surge Arrester HS PEXLIM-P Surge Arresters are used for the protection of switchgear, transformers and other

More information

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314

More information

POWER QUALITY SOLUTIONS FOR INDUSTRIAL AND DISTRIBUTION GRIDS. W WW.R EINHAU S EN.COM

POWER QUALITY SOLUTIONS FOR INDUSTRIAL AND DISTRIBUTION GRIDS. W WW.R EINHAU S EN.COM POWER QUALITY SOLUTIONS FOR INDUSTRIAL AND DISTRIBUTION GRIDS. W WW.R EINHAU S EN.COM POWER QUALITY POWER QUALITY - SOLUTIONS FOR GRID EFFICIENCY IMPROVEMENT, LOSS REDUCTION AND VOLTAGE STABILIZATION.

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide 1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Cast resin transformers

Cast resin transformers Product catalogue Cast resin transformers according to IEC/EN 60076, VDE 0532, DIN 42523 Power range up to 8 MVA Voltage range up to 36 kv Conductor material: copper or aluminum Protection types: IP 00

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

JCAM SWITCHES. Model Ratings / Product Numbering System...J2 Technical Data...J3

JCAM SWITCHES. Model Ratings / Product Numbering System...J2 Technical Data...J3 Springer Controls is partnered with MERZ-PCE, a world leader in the manufacturing of switch gears. We offer complete line of Cam Switches with as many as 24 switch contacts. Each contact has two fixed

More information

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DCX-M changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES FOR COMMERCIAL BUILDINGS AND DCX-M In = 63 A Quality & design CONFORM TO EN/IEC

More information

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised

More information

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for

More information

medium voltage switchgear manufacturer VACUUM CIRCUIT-BREAKER SWITCHGEAR TYPE SIMOPRIME, UP TO 17.5kV, AIR INSULATED MEDIUM-VOLTAGE SWITCHGEAR. UNDER LICENSE BY SIEMENS. www.simosynergy.com/simoprime VACUUM

More information

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable www.siemens.com/medium-voltage-switchgear Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear Catalog HA 41.43 2012 Answers for infrastructure and cities. Neue Bilder

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

Zinc Oxide Surge Arrester PEXLIM Q

Zinc Oxide Surge Arrester PEXLIM Q Zinc Oxide Surge Arrester Protection of switchgear, transformers and other equipment in high voltage systems against atmospheric and switching overvoltages. in areas with high lightning intensity and high

More information

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...

More information

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv] BasisBlock MC 1 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC1-12 MC1-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage

More information

Benefits, typical uses

Benefits, typical uses R-HA26-013. eps Switchgear Type 8BT1, up to 24kV,Air-Insulated Contents Application Page Application Benefits 2 Typical uses 2 and 3 Technical Data Ratings 4 Classification, dimensions, 5 room planning

More information

Gas Insulated Metal-clad Switchgear, HMGS!

Gas Insulated Metal-clad Switchgear, HMGS! Medium Voltage HMGS-G10 HYUNDAI Medium Voltage Gas Insulated Metal-clad Switchgear, HMGS! SF6 Gas Insulated Metal-clad Switchgear is an integrated assembly of vacuum circuit breaker, 3-position switch,

More information

ABB STOTZ-KONTAKT GmbH

ABB STOTZ-KONTAKT GmbH ABB STOTZ-KONTAKT GmbH MULTIPLE 89 Motijheel C/A, Lucky Chamber (3rd floor, Room #61), Dhaka-1000, Bangladesh. Tel: (02) 9559692, Fax: (02)9566596 E-mail: info@multipletrading.net PAGE : 02 The ABB Line

More information

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability 3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability Power Transmission and Distribution 1 A perfect Combination of Cost-Savings, Safety and Reliability 3EQ Surge Arresters:

More information

Switchgear Type 8DJH 36 for Secondary

Switchgear Type 8DJH 36 for Secondary Catalog HA 40.3 Edition 2017 Switchgear Type 8DJH 36 for Secondary Distribution Systems up to 36 kv, Gas-Insulated Medium-Voltage Switchgear siemens.com/8djh36 Application Typical uses R-HA40-135.tif R_HA40-150a

More information

Medium voltage switchgear type W 12. rated voltage 12 kv rated current 630 A

Medium voltage switchgear type W 12. rated voltage 12 kv rated current 630 A Medium voltage switchgear type W rated voltage kv rated current 0 A General The metal-encapsulated, air-insulated medium voltage switchgears, type W are for universal application. They range from compact

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

IP20 degree of protection; IP40 degree of protection after installation in a distribution box

IP20 degree of protection; IP40 degree of protection after installation in a distribution box RI 50 RI 50 is used for the protection of installations and devices (overload and short circuit), and as a disconnector in case of electric shock Simple and quick fixing to a 35 mm mounting rail in accordance

More information

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv PASS M0S 252 kv Innovation In today s market, the HV substation is increasingly becoming a key element

More information

Medium voltage fuses - European Fuses

Medium voltage fuses - European Fuses HV Back-up Fuse-Links according to IEC 60 282- HV fuse-links have been used for reliable protection in medium-voltage switchgear and controlgear and systems for decades. They protect apparatus and equipment

More information

3EK7 Medium Voltage Silicone Insulated Surge Arresters

3EK7 Medium Voltage Silicone Insulated Surge Arresters 3EK7 Medium Voltage Silicone Insulated Surge Arresters Power Transmission and Distribution Setting new Standards The 3EK7 s mechanical features: Glass-collared MOV, Silicone rubber housing, FRP rods and

More information

Scheda prodotto Relè Series E

Scheda prodotto Relè Series E Relè Miniatura All-or-Nothing relays ideally suited for any electronic appliances demanding very compact design and low power consumption. Design includes a protective dust cover and a completete range

More information

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper

More information

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT SWITCHCRAFT Switchcraft Europe GmbH Switchgear Product Overview igis Gas Insulated Switchgear isis Solid Insulated Switchgear icb - Vacuum Circuit Breaker iair - Air insulated switchgear panel Switchcraft

More information

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable Medium-Voltage Switchgear Totally Integrated Power SIMOSEC Catalog HA 41.43 Edition Sept. 2014 Answers for infrastructure and cities. Neue

More information

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 Data Sheet System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 2CDC021026S0011 2CDC021016S0012 The S 200 PR is a high-performance supplementary protector with

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

Documents and Addresses

Documents and Addresses Report No.: 05-035-MS/E Sheet: 2 Documents and Addresses Accreditation The Prüffeld der Schaltwerke, Berlin has been approved by the DATech (German accreditation body for technology) according to EN ISO/IEC

More information

132/11 kv, 25 MVA MOBILE SUBSTATION

132/11 kv, 25 MVA MOBILE SUBSTATION File name: Mob EN katalog1 Zagreb, 11.11.2014. Page: 1 od 9 Summary Mobile substation consists of two semitrailers. One trailer is for 132 kv equipment (HV equipment) and another trailer is for medium

More information

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R High Voltage Surge Arresters Buyer s Guide Section PEXLIM R Zinc Oxide Surge Arrester PEXLIM R Protection of switchgear, transformers and other equipment in high systems against atmospheric and switching

More information

3EQ Composite Housed Surge Arresters

3EQ Composite Housed Surge Arresters Power Transmission and Distribution 3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability A perfect Combination of Cost-Savings, Safety and Reliability 3EQ Surge Arresters: Your

More information

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Catalog HA 40.2 Edition 2017 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated Medium-Voltage Switchgear siemens.com/8djh Application Typical uses R-HA40-111.tif R-HA40-112.tif

More information

694 Electric Machines

694 Electric Machines 694 Electric Machines 9.1 A 4-pole wound-rotor induction motor is used as a frequency changer. The stator is connected to a 50 Hz, 3-phase supply. The load is connected to the rotor slip rings. What are

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

DPX Thermal magnetic and trip-free switches DPX 3 -I 250 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 Reference(s) : 420 205/ 207/ 208/209/ 215/ 217/ 218/ 219/ 235/ 237/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

Metal Clad Air Insulated Switchgear

Metal Clad Air Insulated Switchgear Metal Clad Air Insulated Switchgear 1/ SecoGear Metal Clad Switchgear Features Fully metal-clad Equipped with Embedded pole VCB Full Front access (can be installed against wall) Perfect interlocking system

More information

SWITCHGEAR. 4G cam switches

SWITCHGEAR. 4G cam switches SWITCHGEAR 178 4G cam switches ENERGY SAFELY SWITCHED 179 SWITCHGEAR 180 GENERAL INFORMATION 4G-series cam switches are low voltage switches, designed according to the latest knowledge about switchgear

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance 2 Semi-pantograph

More information

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical

More information