INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00

Size: px
Start display at page:

Download "INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00"

Transcription

1 INSTRUCTION MANUAL BR 25 FOR RAILWAY APPLICATION 5COR BR25AT REV00 I

2 CONTENT: 1 SAFETY 1.1 Safety instructions Specified applications Safety notes on the equipment operation 1 2 BR 25 FOR RAILWAY APPLICATION 2.1 Drawing Operating principle Technical features Tests 3 3 INSTALLATION 3.1 Assembly Mechanical test Electrical connection 5 4 CONNECTION 4.1 Electrical contacts layout 5 5 OPERATION AND MAINTENANCE 5.1 Maintenance Storage 5 0

3 1. Safety 1.1 Safety instructions Make sure that any persons installing, taking into operation and operating the relay for OLTC : are technically qualified and competent. Fully comply with these assembling instructions. Improper operations or misuse could cause danger to: life and limb; to the equipment and other assets of the operator; to the equipment proper function. Safety instructions in this manual are shown in three different forms to emphasize important information. WARNING This information indicates particular danger to life and health. Disregarding such a warning can lead to serious or fatal injury CAUTION This information indicates particular danger to equipment or other property of the user. Serious or fatal injury cannot be excluded. NOTE This notes give important or specific information concerning the equipment or as to work with the equipment. 1.2 Specified applications The relay for OLTC is used to protect the on-load tap-changer and the transformer when a malfunction occurs in the diverter switch or selector switch oil compartment. It is important to observe the limit values indicated on the nameplate and in the operating instruction before commissioning the device. 1.3 Safety notes on the equipment operation Electrical installation is subject to the relevant national safety rules. It is mandatory to connect the grounding cable because of safety reason. CAUTION Installation, electrical connection and fitting the device may only be carried out by qualified personnel and only in accordance to this instruction manual. It is responsibility of the user to make sure that the device is used for specified application only. For safety matters, please avoid any unauthorized and improperly works. WARNING All relevant fire protection regulation must be strictly observed. 1

4 2. BR25 FOR RAILWAY APPLICATION 2.1 Drawing In the figure 1 there are the external dimensions for the relay type BR-25: Fig.1 2 Fig.2

5 2.2 Operating principle The Buchholz relay is sited in the pipework between the transformer and its conservator and it is filled with oil during normal transformer operation. When gas is generated in the transformer it rises towards the conservator and collects in the upper chamber of the relay. The oil level drops and the top float triggers alarm switch. Gas shall not freely pass from the relay body and escape into the pipewoek before the alarm contact has operated. Moreover this relay operate if oil occurs from the transformer tank to the oil conservator. If it happens the flow vent moves the support of magnets that switches the alarm reeds. The housing consists of powered painted aluminum parts and it is provided with flanges for the connection of the transformer tank pipe and the oil conservator pipe. The terminals of the reed switches are positioned in the terminal box and the perfect sealing is guaranteed by an OR gasket. The terminal box cover is fixed to the terminal box with 4 unloosable screws. 2.3 Technical features General data Overall dimension See chapter 2.1 Material Color Ambient temperature All the external part are resistant to transformer oils, salt fog and UV rays RAL7001* C Oil temperature C Degree of protection Weight Oil flow speed (oil temperature 20 C) Switch electrical data (according to EN /2) IP65 in accordance with EN60529 ~3 Kg 1.50 ± 0.20 m/s Breaking capacity Voltage Current Breaking capacity Dielectric strength of contacts 24 d.c. to 220 V d.c. 2 A for 1000 maneuvers 250 W L/R<40 ms 230 V a.c. 2 A for 1000 maneuvers 400 VA cosф>0.5 Short duration power frequency withstand voltage 1 min kv (r.m.s.) Lightning impulse withstand voltage kv (peak) Between circuits and earth 2 4 Between contacts in open positions 1 3 *For critical environmental conditions please contact COMEM 2.4 Tests Type test: Relevant Standard: Routine test Relevant Standard: Vibration test EN EN Oil leakage test in hot oil (90 C for 30 minutes at 100kPa) EN Vacuum test (2.5 kpa for 24 hours) EN Operation test Leakage test (250 kpa for 2 minutes at 100 C) EN Mechanical test EN Salt fog test (500 hours) UNI EN ISO 9227 Flow vent test EN Degree of protection IP65 EN Dielectric test EN

6 3. INSTALLATION 3.1 Assembly Install the relay in the pipe leading from the transformer tank to oil conservator. Install the relay in a horizontal position and the test button upwards. The red arrow on the relay must point towards the conservator. Use a pipe of at least 25 mm nominal diameter between relay and transformer tank / oil conservator. Take care to install the relay well supported and protected against vibrations in this pipe connection. Between the relay flanges and pipe flanges put the plane gasket that you can find in the box device. NOTE The pipe from the relay to the oil conservator must be placed with an inclination to ensure free escape of switching gas. COMEM recommends an angle of 2.5 degree from the horizontal (at maximum 5 degree). Provide a stop valve between relay and oil conservator. NOTE Install the relay in a place where the influence of magnetic fields is felt as little as possible. After the installation check the function of the relay. The contacts (alarm and trip) can be tested manually moving the rod (mechanical test chapter 3.2). 3.2 Mechanical test Unscrew the plug (Fig.3/A) then slowly push the button (Fig.3/B) following the red arrow direction (figure below). In this way the floats has moved and the magnets have switched the trip reeds. The button, after been released, automatically comes back to original position. As well the inner movements do. This test does not give the conformity of the electrical scheme. In case of trip switching by the flow valve (by increasing fluid speed) is necessary to operate on the mechanical test push button following the previous indication. This operation is necessary to rearm the flow valve on the normal working position D C B A Fig.3 4

7 3.3 Electrical connection The reed switch of the relay can either be provided as NC contacts. The type of contacts wiring diagram are available in the chapter 4.3. CAUTION Connect the relay into the tripping circuit of the circuit breakers of the transformer to be protected so that the transformer is immediately disconnected by the circuit breakers when the relay of the transformer is tripped. Remove the terminal box cover (3/C) un-screwing the four M5 screws (3/D). Entering with the wire through the cable gland M20x1.5 (standard solution. Other cable glands are available, for further information contact COMEM). The cable gland M20x1.5 is adequate for leads with an outside diameter of 8 14 mm. Connect the leads (terminal bolts M6, max torque 2 Nm) following the electrical scheme showed on the label under the terminal box cover. Connect the protective conductor to the ground screw M4 in the terminal box (max torque: 5 Nm). Fix the terminal box cover on the terminal box. During this phase check the terminal box cover gasket, the surface has to be clean. The relay responds to oil flow, not to gas accumulated. It is not necessary to discharge air from the relay when filling oil into the transformer tank. Gas accumulation in this type of relay is normal. 4. CONNECTION 4.1 Electrical contacts layout 5. Maintenance 5.1 Maintenance During regular check of the transformer, we recommend performing the following checks on the BR25 for railway application: Check the exterior condition of the device. To verify the contacts function following the chapter 3.2 (Mechanical test) Check the gaskets condition and if any leakage exists. 5.2 Storage The BR25 for railway application storage has to be done in its packaging, in dry place with temperature in the range -10 C +40 C. Upon receiving the BR25, please check: the outer surface of the packaging to check that it is intact; that there are no breakages. If damages are found, please contact Comem, quoting the data provided in the shipping list and the serial number of the BR25 for railway application. 5

8 Strada Regionale 11, Signolo Montebello Vic.No (VI) - Italy Tel Fax comem@comem.com 6

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03

INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR OR25 REV03 INSTRUCTION MANUAL RELAY FOR ON LOAD TAP CHANGER APPLICATIONS OR-25 5COR469000 OR25 REV03 I II CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment

More information

INSTRUCTION MANUAL Oil level with pointer indicator

INSTRUCTION MANUAL Oil level with pointer indicator INSTRUCTION MANUAL Oil level with pointer indicator 5COL868200 REV.B I II CONTENTS 1. SAFETY... 1 1.1 Safety instructions... 1 1.2 Specified applications... 1 1.3 Safety notes on the equipment operation...

More information

INSTRUCTION MANUAL CRS Combined insulation bushing

INSTRUCTION MANUAL CRS Combined insulation bushing INSTRUCTION MANUAL CRS Combined insulation bushing 5COH020200 CRS REV03 2 TABLE OF CONTENTS 1 SAFETY... 5 1.1 SAFETY INSTRUCTION... 5 1.2 SPECIFIED APPLICATION... 5 1.3 SAFETY NOTES ON THE EQUIPMENT OPERATION...

More information

Shanghai Huaming Power Equipment Co.,Ltd.

Shanghai Huaming Power Equipment Co.,Ltd. HM 0.460.4101-03-02/2017 Shanghai Huaming Power Equipment Co.,Ltd. 1 General CV2 on load tap changer (herein referred as the tap changer) is of selector switch structure, which combines the functions

More information

On-Load Tap-Changer OILTAP MS

On-Load Tap-Changer OILTAP MS www.reinhausen.com On-Load Tap-Changer OILTAP MS Operating Instructions BA 65/04 Contents Contents 1 General... 5 1.1 Safety Instructions... 5 1.2 Specified Application... 5 2 Design/Types... 6 3 Shipment...

More information

On-Load Tap-Changer Type V

On-Load Tap-Changer Type V www.reinhausen.com On-Load Tap-Changer Type V Operating Instructions BA081/04 2 Contents Contents 1 General 1.1 Safety instructions 5 1.2 Specified application 5 2 Design 6 3 Shipment 6 4 Installation

More information

Pressure Relief Device Comem PRD Order sheet

Pressure Relief Device Comem PRD Order sheet J U N E 2 017 Pressure Relief Device Comem PRD Order sheet ABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo 22 36054 Montebello Vicentino (VI) - ITALY The information contained

More information

Buchholz Relay MBP Gas and Oil Actuated Relay

Buchholz Relay MBP Gas and Oil Actuated Relay Buchholz Relay MBP Gas and Oil Actuated Relay Reed switches for detection of gas formation and dropping oil level Flap valve to protect in case of excessive high oil flow rate Separated oil and switching

More information

Transformer bushings, type GOH. Technical guide

Transformer bushings, type GOH. Technical guide Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

Transformer Protection Relay MCHD

Transformer Protection Relay MCHD Protects Hermetically Sealed, Oil Filled Distribution Transformers and Reactors in Accordance with EN 50216-3 Reed switch for gas formation and oil level detection Adjustable pressure switch Bimetal thermometer

More information

ABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY

ABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo Montebello Vicentino (VI) - ITALY ABB SpA COMEM Operating Unit Power Grids Division Strada Regionale 11, Signolo 22 36054 Montebello Vicentino (VI) - ITALY www.abb.com/transformercomponents The information contained in this document is

More information

On-Load Tap-Changer Type CM Operating Instructions

On-Load Tap-Changer Type CM Operating Instructions HM0.60.30 On-Load Tap-Changer Type CM Operating Instructions HM 0.60.30-03.0/205 Shanghai Huaming Power Equipment Co., Ltd. 2 HM0.60.30 Thank you for choosing on-load tap-changer Prior to using the on-load

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Type 5282 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation 1 OPERATING INSTRUCTIONS The operating instructions contain

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Type 5282 2/2-Way Solenoid Valve 2/2-Wege-Magnetventil Électrovanne à 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation Contents 1 Operating Instructions... 2 2 Authorized use...

More information

GAS ACTUATED RELAYS FOR OIL FILLED TRANSFORMERS EN

GAS ACTUATED RELAYS FOR OIL FILLED TRANSFORMERS EN GAS ACTUATED RELAYS FOR OIL FILLED TRANSFORMERS EN 50216-2 Nome file : RELE EN50216 REV 04 DTD 23/04/2007 Pagina 1 di 22 1. General Features 1.1 Characteristics The gas-actuated protective relay is designed

More information

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Type 5404 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation Contents 1 Operating instructions...2 2 Intended use...3 3

More information

BUCHHOLZ RELAYS EE Series

BUCHHOLZ RELAYS EE Series BUCHHOLZ RELAYS EE Series The newest Buchholz relay release for use in oil-immersed power transformers www.cedaspe.com 1. General Features 1.1 Characteristics The gas-actuated protective relay is designed

More information

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide 1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation. 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Type 6027 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation 1 OPERATING INSTRUCTIONS The operating instructions contain

More information

Read and understand this manual for safely usage.

Read and understand this manual for safely usage. TS02-0183 INSTRUCTION MANUAL FOR GUARD TYPE LEVEL SENSOR MODEL:FC Read and understand this manual for safely usage. This manual describes the product of standard specification. Read the other manual for

More information

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide 1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK 1ZSC563-AAA en, Rev. 2 Resin Impregnated Paper Bushing, Oil to SF 6, Type GSBK Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

Transformer bushings, type GOA 250. Installation and maintenance guide

Transformer bushings, type GOA 250. Installation and maintenance guide Transformer bushings, type GOA 250 Installation and maintenance guide This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor

More information

Angle seat valve with piston actuator VZXA-...-K

Angle seat valve with piston actuator VZXA-...-K Angle seat valve with piston actuator VZXA-...-K Festo AG & Co. KG Postfach 73726 Esslingen Germany +49 711 347-0 www.festo.com 3 Further information Accessories www.festo.com/catalogue Spare parts www.festo.com/spareparts

More information

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide 1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide 1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Operating instructions Solenoid interlock EX-AZM About this document. Content

Operating instructions Solenoid interlock EX-AZM About this document. Content EX-AZM 161 1. About this document Operating instructions.............pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information

More information

USE AND INSTALLATION HANDBOOK

USE AND INSTALLATION HANDBOOK Date : 10/02/14 Rev. 01 PR.T : FG006172 USE AND INSTALLATION HANDBOOK DUPLEX-UP CONTROL PANEL FOR 2 ELECTRIC PUMPS WITH CURRENT CONTROL. DUPLEX-UP Via Enrico Fermi 8-35020 Polverara PD Tel.049/9772407

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

Flow Meter Terminal Boxes

Flow Meter Terminal Boxes Shutter Flow Meter Terminal Boxes Shutter Flow meter Terminal boxes 02 07 11 1 Shutter Valve DAROC Description and general specifications Production range and operating conditions Operation Installation,

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 120-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 120-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 120-0.3

More information

Mounting and Operating Instructions EB 5868/5869 EN

Mounting and Operating Instructions EB 5868/5869 EN Electric Control Valves Types 3213/5857, 3213/5824, Types 3214/5824, 3214/3374, 3214/3274 with safety function: Types 3213/5825, 3214/5825, 3214/3374, 3214/3274 Pneumatic Control Valves Types 3213/2780-1,

More information

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions

Solar Thermal. Grant Solar Pump Station Installation & Servicing Instructions Solar Thermal Grant Solar Pump Station Installation & Servicing Instructions Part No. DOC 96. Rev 02. October 2012 Important Note Important Note for Installers The Pump Station supplied with your Grant

More information

UniGear. Technical Guide

UniGear. Technical Guide UniGear Technical Guide CONTENTS 0 CONTENTS 1.1 Compartments 1/2 1.2 Components of the structure 1/3 1.2.1 Hot-galvanized steel sheet 1/3 1.2.2 Painted steel sheet 1/4 1.2.3 Copper 1/5 1.2.4 Insulating

More information

TIDALFLUX 2300 F Quick Start

TIDALFLUX 2300 F Quick Start Quick Start Electromagnetic flow sensor for partially filled pipes The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS

More information

Type 6213 EV, 6281 EV

Type 6213 EV, 6281 EV Type 6213 EV, 6281 EV 2/2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation 1 OPERATING INSTRUCTIONS The operating instructions

More information

On-load tap-changer OILTAP V

On-load tap-changer OILTAP V www.reinhausen.com On-load tap-changer OILTAP V Technical Data TD 82/03 Table of Contents Table of Contents 1 General... 4 1.1 Summary of the technical data... 4 1.2 Survey... 6 2 Technical Data... 13

More information

PISTON ACCUMULATOR. Installation and operation manual Revision

PISTON ACCUMULATOR. Installation and operation manual Revision PISTON ACCUMULATOR Installation and operation manual Revision 2014-4 Content 1.0 INTRODUCTION 4 2.0 GENERAL SAFETY INSTRUCTIONS 5 3.0 WARRANTY 6 3.1 Limitation of the liability 6 4.0 TECHNICAL SPECIFICATIONS,

More information

RF Point Level Control with Sensor Monitor

RF Point Level Control with Sensor Monitor The 681 Point Level Control utilizes DPDT relays to provide switching for peripheral devices (such as pumps) in level applications. A sensor attached to the control acts as an antenna to transmit the process

More information

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide 1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 60-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 60-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 60-0.3

More information

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide 1ZSE 2750-102 en, Rev. 7 Transformer bushings, type GOB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical

More information

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web:  - MAKING MODERN LIVING POSSIBLE Quick Setup VLT FCM 300 Series Factory setting Motors type B14 & B34 mounting Reset (pushbutton) Start Jog Speed reference Fig. 1 - Reset to be closed short time for resetting

More information

LV Capacitor CLMD03 Power Module Instruction manual

LV Capacitor CLMD03 Power Module Instruction manual LV Capacitor CLMD03 Power Module Instruction manual Table of Contents 1 Safety... 3 2 Upon reception... 3 2.1 Inspection on reception... 3 2.2 Storage- transportation handling... 3 3 Hardware Description...

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

Assembly and operating Instructions. Bypass Flow Meter DST

Assembly and operating Instructions. Bypass Flow Meter DST Assembly and operating Instructions Bypass Flow Meter 2 Contents 1. Foreword... 3 2. Safety... 3 2.1. Symbol and meaning... 3 2.2. General safety directions and exemption from liability... 3 2.3. Intended

More information

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN

Electropneumatic Converters i/p Converters Type 6111 Mounting and Operating Instructions EB 6111 EN Electropneumatic Converters i/p Converters Type 6111 Fig. 1 Type 6111 in standard version Fig. Type 6111 mounted on a supply air manifold Fig. 3 Type 6111 in field enclosure Mounting and Operating Instructions

More information

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide 1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve

Mounting and Operating Instructions EB 8111/8112 EN. Series V2001 Valves Type 3321 Globe Valve Series V2001 Valves Type 3321 Globe Valve Type 3321 Globe Valve with rod-type yoke and Type 3372 Electropneumatic Actuator (350 cm²) Mounting and Operating Instructions EB 8111/8112 EN Edition June 2013

More information

Oil level gauges Series IL

Oil level gauges Series IL Oil level gauges Series IL Cat: 11ILCATR04-E Rev: 04 08/2009 Catalogue N 11ILCATR01-E Rev. N 01 13.10.2002 11 Oil Level Gauges Series IL Page N 1 of 3 1 General Information It is necessary to measure the

More information

Visual comparison of Plain & Hazy PP Film

Visual comparison of Plain & Hazy PP Film ECOVAR High Voltage Power Capacitors are manufactured at our Sinnar Plant in India which is an ISO 9001 accredited facility & houses a computer aided design manufacturing processing and testing infrastructure

More information

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers ABB PTTR SPAIN Zaragoza. The product: Cast coil transformers ABB BA Transformers - 1-5/7/2007 Dry Type Vacuum Cast Coil Transformer INTRODUCTION ABB BA Transformers - 2 - Product Portfolio II Dry Type

More information

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013. 172-65177M-02 (TATSU2) 7 August 2013 ISO 9001/ ISO 14001 Manufacturer Kakogawa, Japan is approved by LRQA LTD. to ISO 9001/14001 Air Trap TATSU2 Copyright 2013 by TLV CO., LTD. All rights reserved 1 Contents

More information

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation Type 0131 2/2- or 3/2-way solenoid valve 2/2- oder 3/2-Wege-Magnetventil Électrovanne 2/2 ou 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation 1 OPERATING INSTRUCTIONS The operating

More information

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil Type 3535 Three-way Valve with bellows seal and rod-type yoke (partial view) Mounting and Operating Instructions EB 8135/8136 EN Edition

More information

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2. Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.12 Product Overview ABB's type-tested ring main unit (RMU) is an SF 6 insulated RMU utilising the latest developments

More information

WATERFLUX 3070 Quick Start

WATERFLUX 3070 Quick Start WATERFLUX 3070 Quick Start Battery powered electromagnetic water meter Electronic Revision ER 4.3.0_ up to ER 4.3.4_ (SW.REV 4.2.2_ up to 4.2.5_) KROHNE CONTENTS WATERFLUX 3070 1 Safety instructions 4

More information

VQ400M SERIES CLASS A COMBINATION VALVES INSTRUCTION SHEET APPLICATION

VQ400M SERIES CLASS A COMBINATION VALVES INSTRUCTION SHEET APPLICATION VQ400M SERIES INSTRUCTION SHEET APPLICATION The VQ400M Series class A safety combination valves are used for control and regulation of gaseous fluids in gas power burners, atmospheric gas boilers, melting

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

GENERAL WARNING. General instructions. Technical assistance. Doseuro S.r.l. Liability

GENERAL WARNING. General instructions. Technical assistance. Doseuro S.r.l. Liability Diaphragm interposed fluid head Use and maintenance manual Model Model BR Model UK Positive displacement metering pump PDP Series Type B I 250 I 350 SD GENERAL WARNING General instructions We thank you

More information

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual 1ZSE 5492-155 en, Rev. 4 On-load tap-changers, type UC User s manual Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List

On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List On-load tap-changers, types UCG, UCL, UCC and UCD with motor-drive mechanisms, types BUE and BUL Spare Parts List ZSE 5492-33 en, Rev. 3, 2004-04-5 This document must not be copied without our written

More information

Assembly and Maintenance Manual Type ASNU

Assembly and Maintenance Manual Type ASNU Assembly and Maintenance Manual Type ASNU Hatschekstr.36 69126 Heidelberg Germany Tel +49(0)6221 30470 Fax +49(0)6221 304731 info@stieber.de www.stieber.de Date of issue: 30.05.2018 GB Revision: 0 U:\EngUsers\!ProduktDoku\1AAA_Einbauerklaerung_Wartungsanleitung_Konformitaetserklaerung\1AAA_Wartungsanleitungen\Orginal_Worddatei\_ASNU.docx

More information

Bushings for High Voltage AC Applications

Bushings for High Voltage AC Applications Bushings for High Voltage AC Applications Selection guide 1ZSE 2750-100 en, Rev. 3, 2006-03-15 During selection of for high voltage applications several important factors have to be considered to ensure

More information

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when

More information

Operating and installation instructions

Operating and installation instructions DP30 DP32 DP33 DP34 Contents 1.0 General information on operating instructions... 2-2 2.0 Notes on possible dangers... 2-2 2.1 Significance of symbols... 2-2 2.2 Explanatory notes on safety information...

More information

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report Test report Type VRLTC load tap changer VRLTC 1500A Type test summary report Date: 10 October 2012 Type Test Summary Report Type VRLTC Vacuum/Reactance Load Tap Changer ABB has tested the Type VRLTC, vacuum

More information

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv 06B1-E-0002 Small Space Requirement, High Reliability and Safety ー 72.5 to 145 kv GIS, SDH314/SDHa314

More information

Electrobar Elite. Instruction Manual. Conductor Bar System. ELITE-03A October 2011 Part Number: R3 Copyright 2011 Electromotive Systems

Electrobar Elite. Instruction Manual. Conductor Bar System. ELITE-03A October 2011 Part Number: R3 Copyright 2011 Electromotive Systems Electrobar Elite Conductor Bar System Instruction Manual ELITE-03A October 2011 Part Number: 005-1054-R3 Copyright 2011 Electromotive Systems 2011 MAGNETEK All rights reserved. This notice applies to

More information

ZB0050 / ZB0051 ZB0070 / ZB0071

ZB0050 / ZB0051 ZB0070 / ZB0071 Operating instructions Safety Rope Emergency Stop Switches UK ZB0050 / ZB0051 ZB0070 / ZB0071 7390877 / 02 08/2013 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4 2.2

More information

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated

More information

OPTIFLUX 2000 Quick Start

OPTIFLUX 2000 Quick Start OPTIFLUX 2000 Quick Start Electromagnetic flow sensor The documentation is only complete when used in combination with the relevant documentation for the signal converter. KROHNE CONTENTS OPTIFLUX 2000

More information

Operating Instructions for Polysulfone Paddle Monitor. Model: PPS-..

Operating Instructions for Polysulfone Paddle Monitor. Model: PPS-.. Operating Instructions for Polysulfone Paddle Monitor Model: -.. 1. Contents 1. Contents... 2 2. Note... 3 3. Regulation Use... 3 4. Operating Principle... 3 5. Instrument Inspection... 4 6. Mechanical

More information

Installation Instructions Spector compact Conductivity Transmitter System LRGT 16-1

Installation Instructions Spector compact Conductivity Transmitter System LRGT 16-1 Installation Instructions 810701-00 Spector compact Conductivity Transmitter System LRGT 16-1 IMPORTANT NOTES...4 SAFETY NOTES...4 Danger...4 EXPLANATORY NOTES...4 Scope of supply...4 System description...4

More information

1. Safety practices General Introduction Standards...3

1. Safety practices General Introduction Standards...3 1. Safety practices...2 2. General...3 2.1 Introduction...3 2.2 Standards...3 3. Technical data...3 3.1 Designation...3 3.2 Electrical ratings and dimensions...4 3.3 Fixation...6 3.4 Connecting terminals...6

More information

CP Automatic capacitor bank

CP Automatic capacitor bank CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor

More information

*(1(5$/7(&+1,&$/63(&,),&$7,2162) +9/9 ',675,%87,2175$16)250(56

*(1(5$/7(&+1,&$/63(&,),&$7,2162) +9/9 ',675,%87,2175$16)250(56 T *(1(5$/7(&+1,&$/63(&,),&$7,2162) +9/9 ',675,%87,2175$16)250(56 TUNISIE TRANSFORMATEUR S.A :ULWWHQE\ M. BOUMALLA Adel Checked by : Mll. LAOUINI Radhia Approved by : M.LARIBI Mohamed Kamel %XVLQHVV'HSDUWPHQW,PP(O+DELE%XUHDX1ƒ%ORF%/HV%HUJHVGXODF$RXLQD

More information

Assembly instructions

Assembly instructions Please carefully read the assembly instructions before beginning the installation, operation and maintenance of the solar facility. Noncompliance could cause injury to persons or damage to the equipment.

More information

OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES

OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES OFFICINE OROBICHE S.p.A. 1/7 INSTRUCTION MANUAL FOR FLOW SWITCHES PL SERIES 1.INSTRUMENT DESCRIPTION Flow switches PL series are designed to be mounted in an upright position along horizontal pipes. These

More information

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION

VQ400M SERIES CLASS A COMBINATION VALVES PRODUCT HANDBOOK APPLICATION VQ400M SERIES PRODUCT HANDBOOK APPLICATION The VQ400M Series class A safety combination valves are used for control and regulation of gaseous fluids in gas power burners, atmospheric gas boilers, melting

More information

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321

Mounting and Operating Instructions EB 8111/8112 EN. Valve Series V2001 Globe Valve Type 3321 Valve Series V2001 Globe Valve Type 3321 Fig. 1 Type 3321 Valve with mounted rod-type yoke for pneumatic or electric actuators (partial view) Mounting and Operating Instructions EB 8111/8112 EN Edition

More information

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device) Types: KA208S KA212S KA216S KA220S KA325S KA332S KA440S KA212H KA216H KA220H KA316H KA320H

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING VACUUM PUMPS

DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING VACUUM PUMPS (Rev. 2.0_10-2010) DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING VACUUM PUMPS TRVK 2003 to 5003 TRSK 2005 to 5005 INTRODUCTION These instructions are for the maintenance staff in case of repair

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F

2.7. IT system floor-standing distribution cabinet Series -IPS-F Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 07-0 Fax: 0640 07-25 IT system floor-standing distribution cabinet Series -IPS-F for supplying power to medical locations

More information

Operating instructions Pull-wire emergency-stop switches EX-ZQ About this document. Content

Operating instructions Pull-wire emergency-stop switches EX-ZQ About this document. Content Pull-wire emergency-stop switches 1. bout this document Operating instructions.............pages 1 to 6 Original 1.1 Function This operating instructions manual provides all the information you need for

More information

KV4-300 mk2. KV5-200 mk2. KV5-100T mk2. KV3-250 mk2

KV4-300 mk2. KV5-200 mk2. KV5-100T mk2. KV3-250 mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: High Voltage AC Test Set KV3-250 mk2 KV4-300 mk2 KV5-100 mk2 KV5-100T mk2 KV5-200 mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge

More information

Operating manual Separator

Operating manual Separator Operating manual Separator Sheet no. AS/4.1.141.1.1 issue 20.08.2014 Contents Section Title Page 0 Introduction... 1 1 Intended use......1 2 Marking of the fitting... 1 3 Safety instructions... 2 4 Transport

More information

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Issue 3 2012 SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) www.energynetworks.org 2012 Energy Networks

More information

Operating instructions Solenoid interlock AZM 161../.. 1. About this document. Content

Operating instructions Solenoid interlock AZM 161../.. 1. About this document. Content Solenoid interlock AZM 11../.. 1. About this document Operating instructions.............pages 1 to ranslation of the original operating instructions 1.1 Function his operating instructions manual provides

More information

VERSAFLOW MAG 4000 Quick Start

VERSAFLOW MAG 4000 Quick Start VERSAFLOW MAG 4000 Quick Start Electromagnetic flow sensor The documentation is only complete when used in combination with the relevant documentation for the signal converter. CONTENTS VERSAFLOW MAG 4000

More information

UV- TECHNOLOGY. Technical Documentation ELC N6 / ELC N8 / ELC N10

UV- TECHNOLOGY. Technical Documentation ELC N6 / ELC N8 / ELC N10 our name is our principle UV- TECHNOLOGY Technical Documentation ELC N6 / ELC N8 / ELC N10 GB eta plus electronic gmbh Lauterstraße 29, D-72622 Nürtingen, Telefon +49 (0) 70 22-60 02-80, Fax +49 (0) 70

More information

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany PTFE-lined Rotary plug valves Series 23e, with packing with lever for 90 operation with worm gear

More information

Operating instructions Solenoid interlock TKM/TKF. 1. About this document. Content

Operating instructions Solenoid interlock TKM/TKF. 1. About this document. Content 1. About this document Operating instructions.............pages 1 to 6 Original 1.1 Function This operating instructions manual provides all the information you need for the mounting, set-up and commissioning

More information

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper GE Grid Solutions PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper PNO bushings are capacitance graded bushings with an oil impregnated paper core. PNO bushings are conform

More information

QS20.241, QS C1

QS20.241, QS C1 QS2.21, QS2.21C1 QSeries 27. APPLICATION NOTES 27.1. REPETITIVE PULSE LOADING Typically, a load current is not constant. It varies over time. For pulse load compatibility, following rules must be met:

More information

User Manual Rittal PMC UPS 6kVA

User Manual Rittal PMC UPS 6kVA User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Tel.: ++49-27 72-5 05-0 Fax: ++49-27 72-5 05-23 19 Internet: www.rittal.de 26 Contents 1. Introduction...

More information