1 MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI QUESTION BANK Sub. Code : EE2402 Semester : VII Subject : PROTECTION AND SWITCHGEAR Unit : IV PART A 1. What is resistance switching? It is the method of connecting a resistance in parallel with the contact space(arc). The resistance reduces the restriking voltage frequency and it diverts part of the arc current. It assists the circuit breaker in interrupting the magnetizing current and capacity current. 2. What do you mean by current chopping? When interrupting low inductive currents such as magnetizing currents of the transformer, shunt reactor, the rapid deionization of the contact space and blast effect may cause the current to be interrupted before the natural current zero. This phenomenon of interruption of the current before its natural zero is called current chopping. 3. What are the methods of capacitive switching? Opening of single capacitor bank Closing of one capacitor bank against another 4. What is an arc? Arc is a phenomenon occurring when the two contacts of a circuit breaker separate under heavy load or fault or short circuit condition. 5. Give the two methods of arc interruption? High resistance interruption:-the arc resistance is increased by elongating, and splitting the arc so that the arc is fully extinguished Current zero method:-the arc is interrupted at current zero position that occurs100 times a second in case of 50Hz power system frequency in ac. 6. What is restriking voltage? (nov/dec 2011) It is the transient voltage appearing across the breaker contacts at the instant of arc being extinguished. 7. What is meant by recovery voltage? (nov/dec 2011) The power frequency rms voltage appearing across the breaker contacts after the arc is extinguished and transient oscillations die out is called recovery voltage. PROTECTION AND SWITCHGEAR Page 1

2 8. What is RRRV? It is the rate of rise of restriking voltage, expressed in volts per microsecond. It is closely associated with natural frequency of oscillation. 9. What is circuit breaker? It is a piece of equipment used to break a circuit automatically under fault conditions. It breaks a circuit either manually or by remote control under normal conditions and under fault conditions. 10. What is the main problem of the circuit breaker? When the contacts of the breaker are separated, an arc is struck between them. This arc delays the current interruption process and also generates enormous heat which may cause damage to the system or to the breaker itself. This is the main problem. 11. Mention the details circuit breaker rating Rated voltage & rated current Rated Frequency Rated breaking capacity, symmetrical & asymmetrical Rated making capacity Rated short time current Rated operating duty 12. What are the factors the ARC phenomenon depends upon? The nature and pressure of the medium The external ionizing and de-ionizing agent present Voltage across the electrodes and its variation with time The nature shape & separation of electrodes The nature and shape of vessel and its position in relation to the electrodes 13. What are the factors the arc resistance depends upon? Degree of ionization Length of the arc Cross section area of the arc 14. What is breaking current? The breaking current of a circuit breaker of a circuit breaker is the current in that pole at the instant of contact separation. 15. What is symmetrical breaking current? R.M.S Value of the A.C component of the current in the pole at the instant of contact separation 16. What is asymmetrical breaking current? R.M.S Value of the A.C & D.C component of the current in the pole at the instant of contact separation PROTECTION AND SWITCHGEAR Page 2

3 17. What are breaking capacities? The symmetrical value of breaking capacity is the value of the symmetrical breaking current which the circuit breaker is capable of breaking at the stated recovery voltage and restriking voltage under prescribed condition 18. What are the factors the recovery voltage depends upon? (nov/dec 2011) Power factor, Armature reaction & Circuit condition 19. What is rated making current? The making current a circuit breaker when closed on a short circuit is the RMS value of the total current which is measured from the envelope of the current wave at the time of its first major peak. 20. What is the basic requirement of DC circuit breaking? Lengthening of the arc is basic requirements of D.C circuit breaker. Loss of energy increases with increasing length of arc and more power will be required to maintain the arc. 21. What are the problems associated with DC circuit breakers? Natural current zero does not occur as in the case of A.C circuit breakers The amount of energy to be dissipated during the short interval of breaking is very high as compared to conventional A.C circuit breakers. 22. What is the purpose of protective spark gap? A protective spark gap can be used across the circuit breaker to reduce the size of commutation capacitor. The spark gap acts as an energy dissipating device for high frequency currents 23. What is the purpose of arc chute? By breaking the arcs into number of smaller arcs and by increasing the space between two walls of arc chute the deionization of the arc can be increased 24. What are the factors RRRV depends upon? Active recovery voltage & Natural frequency of oscillation 25. Differentiate between the static and dynamic characteristics of the arc? If the current changes rapidly with time the characteristics are known as dynamic characteristics. If the rate of change of current is small the characteristics are known as static characteristics. PROTECTION AND SWITCHGEAR Page 3

4 PART B 1)Explain Double Frequency Transient. PROTECTION AND SWITCHGEAR Page 4

5 PROTECTION AND SWITCHGEAR Page 5

6 PROTECTION AND SWITCHGEAR Page 6

7 PROTECTION AND SWITCHGEAR Page 7

8 6) Explain Resistance switching with circuit diagram. PROTECTION AND SWITCHGEAR Page 8

9 PROTECTION AND SWITCHGEAR Page 9

10 PROTECTION AND SWITCHGEAR Page 10

11 7)Explain Arc Extinction and types of Extinction. PROTECTION AND SWITCHGEAR Page 11

12 PROTECTION AND SWITCHGEAR Page 12

13 8)Explain air break circuit breakers. PROTECTION AND SWITCHGEAR Page 13

14 All circuit breakers have common features in their operation, although details vary substantially depending on the voltage class, current rating and type of the circuit breaker. The circuit breaker must detect a fault condition; in low voltage circuit breakers this is usually done within the breaker enclosure. Circuit breakers for large currents or high voltages are usually arranged with protective relay pilot devices to sense a fault condition and to operate the trip opening mechanism. The trip solenoid that releases the latch is usually energized by a separate battery, although some high-voltage circuit breakers are selfcontained with current transformers, protective relays and an internal control power source. Once a fault is detected, contacts within the circuit breaker must open to interrupt the circuit; some mechanically-stored energy (using something such as springs or compressed air) contained within the breaker is used to separate the contacts, although some of the energy required may be obtained from the fault current itself. Small circuit breakers may be manually operated, larger units have solenoids to trip the mechanism, and electric motors to restore energy to the springs. The circuit breaker contacts must carry the load current without excessive heating, and must also withstand the heat of the arc produced when interrupting (opening) the circuit. Contacts are made of copper or copper alloys, silver alloys and other highly conductive materials. Service life of the contacts is limited by the erosion of contact material due to arcing while interrupting the current. Miniature and molded-case circuit breakers are usually discarded when the contacts have worn, but power circuit breakers and high-voltage circuit breakers have replaceable contacts. When a current is interrupted, an arc is generated. This arc must be contained, cooled and extinguished in a controlled way, so that the gap between the contacts can again withstand the voltage in the circuit. Different circuit breakers use vacuum, air, insulating gas or oil as the medium the arc forms in. Different techniques are used to extinguish the arc including: Lengthening / deflection of the arc Intensive cooling (in jet chambers) Division into partial arcs PROTECTION AND SWITCHGEAR Page 14

15 Zero point quenching (Contacts open at the zero current time crossing of the AC waveform, effectively breaking no load current at the time of opening. The zero crossing occurs at twice the line frequency, i.e. 100 times per second for 50 Hz and 120 times per second for 60 Hz AC) Connecting capacitors in parallel with contacts in DC circuits. Finally, once the fault condition has been cleared, the contacts must again be closed to restore power to the interrupted circuit. Arc interruption Low-voltage MCB uses air alone to extinguish the arc. Larger ratings have metal plates or non-metallic arc chutes to divide and cool the arc. Magnetic blowout coils or permanent magnets deflect the arc into the arc chute. In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to blast a jet of oil through the arc. Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride (SF6) to quench the stretched arc. Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than the contact material), so the arc quenches when it is stretched a very small amount (less than 2 3 mm ( in)). Vacuum circuit breakers are frequently used in modern mediumvoltage switchgear to 38,000 volts. Air circuit breakers may use compressed air to blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air thus blowing out the arc. Circuit breakers are usually able to terminate all current very quickly: typically the arc is extinguished between 30 ms and 150 ms after the mechanism has been tripped, depending upon age and construction of the device. PROTECTION AND SWITCHGEAR Page 15

16 Short-circuit current: Circuit breakers are rated both by the normal current that they are expected to carry, and the maximum short-circuit current that they can safely interrupt. Under short-circuit conditions, a current many times greater than normal can exist (see maximum prospective short circuit current). When electrical contacts open to interrupt a large current, there is a tendency for an arc to form between the opened contacts, which would allow the current to continue. This condition can create conductive ionized gases and molten or vaporized metal, which can cause further continuation of the arc, or creation of additional short circuits, potentially resulting in the explosion of the circuit breaker and the equipment that it is installed in. Therefore, circuit breakers must incorporate various features to divide and extinguish the arc. In air-insulated and miniature breakers an arc chute structure consisting (often) of metal plates or ceramic ridges cools the arc, and magnetic blowout coils deflect the arc into the arc chute. Larger circuit breakers such as those used in electrical power distribution may use vacuum, an inert gas such as sulfur hexafluoride or have contacts immersed in oil to suppress the arc. The maximum short-circuit current that a breaker can interrupt is determined by testing. Application of a breaker in a circuit with a prospective short-circuit current higher than the breaker's interrupting capacity rating may result in failure of the breaker to safely interrupt a fault. In a worst-case scenario the breaker may successfully interrupt the fault, only to explode when reset. MCB used to protect control circuits or small appliances may not have sufficient interrupting capacity to use at a panel board; these circuit breakers are called "supplemental circuit protectors" to distinguish them from distribution-type circuit breakers. PROTECTION AND SWITCHGEAR Page 16

17 9)Explain T-1 series circuit Breaker. T-1 Series Circuit Breakers SftMt 25 Amp ~ 150 Amp 5000 Ampere interrupt capacity meets primary circuit protection requirements for large DC systems. Vapor Proof (conforming to SAE J1171) safe for installation aboard gas-powered boats Weatherproof Combines switching and circuit breaker functions into one unit Trip Free designed to trip when subjected to a fault current, even if the reset lever is held in the ON position. Agency Specifications Meets SAE J553 & J1625 Circuit Breaker Standards for Surface Vehicles. PROTECTION AND SWITCHGEAR Page 17

18 Meets SAE J1171 Marine Circuit Breaker Standards Including External Ignition Protection PN Description 7120 T-1 Circuit Breaker 25 Amp 7121 T-1 Circuit Breaker 30 Amp 7122 T-1 Circuit Breaker 35 Amp 7123 T-1 Circuit Breaker 40 Amp 7124 T-1 Circuit Breaker 50 Amp 7125 T-1 Circuit Breaker 60 Amp 7126 T-1 Circuit Breaker 70 Amp 7127 T-1 Circuit Breaker 80 Amp 7128 T-1 Circuit Breaker 90 Amp 7129 T-1 Circuit Breaker 100 Amp 7130 T-1 Circuit Breaker 110 Amp 7131 T-1 Circuit Breaker 120 Amp 7132 T-1 Circuit Breaker 135 Amp 7133 T-1 Circuit Breaker 150 Amp PROTECTION AND SWITCHGEAR Page 18

19 Specifications Circuit Breaker Class Type III Switchable / Manual Reset Trip Free Type Thermally Responsive Bi-Metal Blade Body Material Thermoset Polyester UL Rated 94V-0, 338 F (170 C) Amperage Range 25 to 150 Amperes Voltage Rating 48 Volt DC Maximum Interrupt Rating DC 5, Volts 3, Volts 1, Volts Weight 0.50 Lb / 0.23 Kg Panel Mount PROTECTION AND SWITCHGEAR Page 19

20 0.58 Lb / 0.26 Kg Surface Mount T-1 Series Circuit Breakers Panel Mount 25 Amp ~ 150 Amp 5000 Ampere interrupt capacity meets primary circuit protection requirements for large DC systems Vapor Proof (conforming to SAE J1171) safe for installation aboard gas-powered boats Weatherproof Combines switching and circuit breaker functions into one unit Trip Free designed to trip when subjected to a fault current, even if the reset lever is held in the ON position. PROTECTION AND SWITCHGEAR Page 20

21 Agency Specifications Meets SAE J553 & J1625 Circuit Breaker Standards for Surface Vehicles. Meets SAE J1171 Marine Circuit Breaker Standards Including External Ignition Protection PN Description 7020 T-1 Circuit Breaker 25 Amp 7021 T-1 Circuit Breaker 30 Amp 7022 T-1 Circuit Breaker 35 Amp 7023 T-1 Circuit Breaker 40 Amp 7024 T-1 Circuit Breaker 50 Amp 7025 T-1 Circuit Breaker 60 Amp 7026 T-1 Circuit Breaker 70 Amp 7027 T-1 Circuit Breaker 80 Amp 7028 T-1 Circuit Breaker 90 Amp 7029 T-1 Circuit Breaker 100 Amp 7030 T 1 Circuit Breaker 110 Amp 7031 T 1 Circuit Breaker 120 Amp 7032 T 1 Circuit Breaker 135 Amp 7033 T 1 Circuit Breaker 150 Amp PROTECTION AND SWITCHGEAR Page 21

22 Specifications Circuit Breaker Class Type III Switchable / Manual Reset Trip Free Type Thermally Responsive Bi-Metal Blade Body Material Thermoset Polyester UL Rated 94V-0, 338 F (170 C) Amperage Range 25 to 150 Amperes Voltage Rating 48 Volt DC Maximum Interrupt Rating DC 5, Volts 3, Volts 1, Volts Weight 0.50 Lb / 0.23 Kg Panel Mount PROTECTION AND SWITCHGEAR Page 22

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series Learning Module 6: Medium Voltage Power Circuit Breakers 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Components 4 Frame 5 Operating Mechanism

More information

Introduction to Circuit Breaker. Working Principle of Circuit Breaker

Introduction to Circuit Breaker. Working Principle of Circuit Breaker Definition of Circuit Breaker : - Electrical Circuit Breaker is a switching device which can be operated manually as well as automatically for controlling and protection of electrical power system respectively.

More information

Miniature circuit breaker Application guide

Miniature circuit breaker Application guide Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current

More information

HD4. Gas insulated MV circuit-breakers kv A ka

HD4. Gas insulated MV circuit-breakers kv A ka HD4 Gas insulated MV circuit-breakers 12... 40.5 kv - 630... 3600 A - 16... 50 ka 1 DESCRIPTION Autopuffer breaking technique Electric arc extinction without chopped current No restriking after breaking

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications Outdoor live tank SF 6 circuit breaker Type OHB for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers

More information

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite

More information

Learning Module 5: Fundamentals of Circuit Breakers. 101 Basic Series

Learning Module 5: Fundamentals of Circuit Breakers. 101 Basic Series Learning Module 5: Fundamentals of Circuit Breakers 101 Basic Series What You Will Learn We will step through each of these topics in detail: Introduction 4 Definition 4 Characteristics 4 Frame 5 Metal

More information

RBA Catalog Numbers and Information

RBA Catalog Numbers and Information 50 RBA s and Information Type RBA Expulsion Fuses for Use Indoors or in an Enclosure Ampere Rating Standard Speed (Fuse Refills) Curve Reference 36-635 Time-Lag (Fuse Refills) Curve Reference 36-635 Approx.

More information

Close-Open (Short-Circuit) Time Results Interpretation

Close-Open (Short-Circuit) Time Results Interpretation Application Note Close-Open (Short-Circuit) Time Results Interpretation Close-Open (C-O, trip-free) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection

More information

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing Introduction A contactor is an electrical device which is used for switching an electrical circuit on or off. It is considered to be a special type of relay. However, the basic difference between the relay

More information

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses) .7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

CX-Series. Circuit Breaker

CX-Series. Circuit Breaker CX-Series Circuit Breaker The CX-Series circuit breaker features a unique and innovative arc-quenching configuration that allows the breaker to safely handle high amperage and high DC voltage applications

More information

Control Relays Overview

Control Relays Overview Control Relays Overview DESIGN FEATURES Among the advances Agastat Control Relays offer over existing designs is a unique contact operating mechanism. An articulated arm assembly amplifies the movement

More information

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram:

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram: Question Set(2017) Switch Gear & protection(5 th SEm) 1. What is fault in power system? Classify the fault. What are the bad effects of fault? 2. Define with example: Symmetrical fault and unsymmetrical

More information

OHB Outdoor sulphur Hexafluoride circuit-breaker

OHB Outdoor sulphur Hexafluoride circuit-breaker 1-2002 OHB Outdoor sulphur Hexafluoride circuit-breaker ABB T&D Divisione Sace T.M.S. -01.05.15 - Fields of application outdoor installations control and protection of distribution lines control and protection

More information

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment Use load interrupter attachments to enable loop sectionalizing, line dropping, load breaking and transformer-magnetizing current interruption. Increase the capability of your disconnect switches by adding

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING 1.What is resistance switching? EE 6702 PROTECTION AND SWITCHGEAR UNIVERSITY QUESTIONS AND ANSWERS PART A It is

More information

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required! DB 750-205 January 2007 Supercedes: December 2006 Now available with Vacuum Interrupter Monitor VBT Switch 15kV - 69kV VBU-T Switch 69kV - 230kV Longest Life Product for Electric Furnace Applications!

More information

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction

More information

Government Polytechnic Muzaffarpur Name of the Lab: Electric Traction-II Lab

Government Polytechnic Muzaffarpur Name of the Lab: Electric Traction-II Lab Government Polytechnic Muzaffarpur Name of the Lab: Electric Traction-II Lab Subject Code: 1620609A Experiment-1 Aim: Study of various traction systems. Theory: A traction system is of mainly two type

More information

MINIATURE CIRCUIT BREAKER

MINIATURE CIRCUIT BREAKER Technical Article MINIATURE CIRCUIT BREAKER T 146 PURCHASE he Spaceage MCB protects wires and cables automatically against overload and short-circuits in domestic, commercial and industrial installations.

More information

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV December, 1975 New nformation and Supersedes DB 38-131 Pages 1-4, dated May 1972, and 38-121 D WE A, Pages 1-4, dated April1974 E, D, C/1981/ DB Westinghouse Electric Corporation Distribution Apparatus

More information

CMU medium voltage power fuses

CMU medium voltage power fuses Fusing Equipment Catalog Data C132038EN Supersedes 240-94 December 2013 COOPER POWER SERIES General Eaton s Cooper Power series CMU power fuse is a boric acid, expulsion-style fuse. Suitable for both indoor

More information

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses) .7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants

Breaking new ground. A circuit breaker with the capacity to switch 15 large power plants Breaking new ground A circuit breaker with the capacity to switch 15 large power plants Helmut Heiermeier, Reto Karrer The power networks that span the landscape and bring electrical energy to cities and

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012 SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Electropneumatic Timing Relays Series 7000 Industrial

Electropneumatic Timing Relays Series 7000 Industrial DESIGN FEATURES Available in On-Delay, True Off-Delay, and On/Off-Delay. Timing from 0.1 seconds to 60 minutes, fully calibrated in linear increments. Oversize time-calibrated adjustment knobs, serrated

More information

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition) 1. Which drawing type shows physical details as seen by the eye? 2. Which drawing is similar to a pictorial drawing but has

More information

DYNACOMP. The top-class reactive power compensator

DYNACOMP. The top-class reactive power compensator DYNACOMP The top-class reactive power compensator Dynacomp vs Electromechanical switching of capacitors Electromechanical switching of capacitors The Dynacomp : the top-class dynamic compensator Transients

More information

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59.

Single Pole Circuit Protectors 55. Multi-Pole Circuit Protectors 56. Configurations 58. Operating Characteristics 59. Single Pole Circuit Protectors 55 Multi-Pole Circuit Protectors 56 Configurations 58 Operating Characteristics 59 Delay Curves 60 Specifications 61 Decision Tables 62 SINGLE POLE CIRCUIT PROTECTORS The

More information

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV. DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them

More information

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Abstract: The development of the magnetically actuated vacuum interrupter

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor

More information

Pretest Module 29 High Voltage

Pretest Module 29 High Voltage Pretest Module 29 High Voltage 1. Is a person qualified to work on high-voltage installations when this module is completed? No 2. What is the code definition of high-voltage? Greater than 750V 3. What

More information

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB Annexure-V (Under Two Part Bid System) Tender No: NFV/ PUR/ BEC 160546 K for VCB Technical specification for NIT SL NO 1 S.No. Description NFL requirement as per NIT Vendors Comment [Agreed / If not agreed,

More information

Vacuum Circuit-Breaker Modules

Vacuum Circuit-Breaker Modules Vacuum s Medium-Voltage Equipment Catalog HG.5 998 Vacuum s Medium-Voltage Equipment Description Catalog HG.5 998 Siemens AG 998 NXACT Vacuum vacuum circuit-breaker module, kv Features DIN EN ISO 900

More information

Switchgear. Low Voltage

Switchgear. Low Voltage January 2001 Vol. 1, Ref. No. [0923] -1 Low Voltage Switchgear Contents Description Page Magnum DS Metal-Enclosed Product Description........................................... -2 Application Description........................................

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Power System Solutions (PSS)

Power System Solutions (PSS) About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Boric Acid Fuse Links

Boric Acid Fuse Links Boric Acid Fuse Links BBU Fuse Link Mount Construction Bird proof design insulator provides insulation characteristics higher than ANSI distribution cut-out standards and equal in most cases to ANSI switch

More information

Most home and business appliances operate on single-phase AC power. For this reason, singlephase AC motors are in widespread use.

Most home and business appliances operate on single-phase AC power. For this reason, singlephase AC motors are in widespread use. Chapter 5 Most home and business appliances operate on single-phase AC power. For this reason, singlephase AC motors are in widespread use. A single-phase induction motor is larger in size, for the same

More information

Live Tank Circuit Breakers Buyer s Guide

Live Tank Circuit Breakers Buyer s Guide Live Tank Circuit Breakers Buyer s Guide Live Tank Circuit Breakers Buyer s Guide Edition 2, 2003-06 0-1 Contents Table of Contents Products Chapter-Page Introduction A-2 Explanations B-1 Puffer, Auto-Puffer

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING 1 DEPARTMENT OF ELECTRICAL ENGINEERING Introduction to High Voltage Testing It is essential to ensure that the electrical equipment is capable of withstanding the overvoltages that are met within the service.

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Electric Motor Controls BOMA Pre-Quiz

Electric Motor Controls BOMA Pre-Quiz Electric Motor Controls BOMA Pre-Quiz Name: 1. How does a U.P.S. (uninterruptable power supply) work? A. AC rectified to DC batteries then inverted to AC B. Batteries generate DC power C. Generator, batteries,

More information

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E. MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E

More information

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy.

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy. Gas-insulated medium-voltage switchgear For the metal industry Answers for energy. Full power even under extreme conditions All over the world, the demand for raw materials and energy is increasing dramatically.

More information

The Evolution of Arc Fault Circuit Interruption

The Evolution of Arc Fault Circuit Interruption 51 st IEEE HOLM Conference on Electrical Contacts The Evolution of Arc Fault Circuit Interruption John A. Wafer Electrical Group Eaton Corporation 2003 Eaton Corporation. All rights reserved. 2 Residential

More information

AP/UP, AP/MIL Series Magnetic Circuit Protectors

AP/UP, AP/MIL Series Magnetic Circuit Protectors AP/UP, AP/MIL AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction 68 Single Pole 69 Multi-Pole 70 Configurations 72 Operating Characteristics 73 Delay Curves 74 Specifications 75 Decision Tables

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL SERIES 35-72 120 VAC Microprocessor Based Direct Spark Ignition Control 35.72.03 FEATURES Two Mounting Configurations Open Board With Stand-Off's - saves space and cost Potted - protection for washdown

More information

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation

INESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing

More information

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...

More information

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times.

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times. The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted power supply is a must. Modern systems are power dependent.

More information

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers Instructions for Load Break Air Switch, Type LBF, for Power Centers The Westinghouse Type LB 1 F Switch is an air insulated, gang operated, three pole, two position link type load interrupter switch. The

More information

Gas-insulated medium-voltage switchgear. For marine and offshore applications. Answers for energy.

Gas-insulated medium-voltage switchgear. For marine and offshore applications. Answers for energy. Gas-insulated medium-voltage switchgear For marine and offshore applications Answers for energy. Full power on the high seas This much is certain: whatever happens on the surface and on the floors of the

More information

TIME SCHEDULE MODULE TOPICS PERIODS. On completion of this course the student will be able:

TIME SCHEDULE MODULE TOPICS PERIODS. On completion of this course the student will be able: COURSE TITLE : ELECTRICAL POWER UTILIZATION & SYSTEM PROTECTION COURSE CODE : 6031 COURSE CATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 75 CREDITS : 5 TIME SCHEDULE MODULE TOPICS PERIODS 1 2 3 4 Fuse

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

MERCURY CONTACTORS & RELAYS

MERCURY CONTACTORS & RELAYS MERCURY CONTACTORS & RELAYS PHONE: 704-399-4248 FAX: 704-399-4167 WWW.SETHERMAL.COM INDEX GLOSSARYOFTERMS&EXPRESSIONS...1 GENERALINFORMATIONFEATURES&SELECTIONFACTORS...13 MERCURY TO METAL CONTACTORS AND

More information

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Descriptive Bulletin R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv Introduction The R-MAG TM is truly the next generation in medium voltage vacuum circuit breaker

More information

SDC,Inc. SCR-Regenerative Ac Drive

SDC,Inc. SCR-Regenerative Ac Drive SDC,Inc WWW.STEVENSDRIVES.COM APPLICATION NOTE #: AN_REG_GEN000 EFFECTIVE DATE: 12 MAR 02 SUPERSEDES DATE: Original NO. OF PAGES: 10 SCR-Regenerative Ac Drive Using a regeneration controller with adjustable-frequency

More information

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB

More information

EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting

EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting EE064D: Circuit Breakers & Switchgears: Design, Testing, Commissioning, Maintenance, Repair & Troubleshooting EE064-D Rev.002 CMCT COURSE OUTLINE Page 1 of 7 Training Description: This intensive five-day

More information

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation agenda Fundamentals Compelling value Product line overview VerSaVac (VSV) Product features and benefits Design Ratings Applications

More information

Ultra Fast Earthing Switch UFES retrofit Overview

Ultra Fast Earthing Switch UFES retrofit Overview Gordon van der Linde ABB PTMV - Service Ultra Fast Earthing Switch UFES retrofit Overview May 20, 2013 UFES Slide 1 Ultra Fast Earthing Switch UFES retrofit Content 1. Effects of an internal arc 2. The

More information

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters Text Book: Chapter 6, Electric Motors and Control Systems, by Frank D. Petruzella, published by McGraw Hill, 2015. Paul I-Hai

More information

INSTRUCTIONS. Delco Systems

INSTRUCTIONS. Delco Systems INSTRUCTIONS FOR THE CARE OF 6-24 Delco Systems The Dayton Engineering Laboratories Co. Dayton, Ohio This is a description of the 6-24 volt system as applied to the following cars: 1912 Cadillac 1913 Cole

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Bolted contact switches. Pringle switches

Bolted contact switches. Pringle switches Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial

More information

Cutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame

Cutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame Cutler-Hammer January 200 Vol., Ref. No. [077] s Molded Case s 5-00 Amperes 2- 2-2 Product Line Overview January 200 Vol., Ref. No. [068] 2 Product Line Description Cutler-Hammer Molded Case s are designed

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

Temperature Controllers

Temperature Controllers SCR Power Controllers Introduction to Silicon Controlled Rectifier (SCR) Power Controllers Features and Benefits of SCRs High reliability Because the SCR power controller is a solid-state device, it provides

More information

(Miniature Circuit Breaker)

(Miniature Circuit Breaker) (Miniature Circuit Breaker) Features : l Uniform 10KA breaking capacity for B and C Curve l Low power consumption, thus cost effective & energy saving l Suitable for DC and for a wide frequency range of

More information