PowerFlex 700L. Technical Data. Catalog Number 20L. Original Instructions

Size: px
Start display at page:

Download "PowerFlex 700L. Technical Data. Catalog Number 20L. Original Instructions"

Transcription

1 Technical Data PowerFlex 700L Catalog Number 20L Topic Page Product Overview 2 Key Features/Benefits 2 Communication and Human Interface Options 4 Catalog Number Explanation 6 Standard Drive Product Selection 8 Factory Installed Options 9 User Installed Options 10 Product Dimensions 10 Installation Considerations 12 Cable Recommendations 18 Fuse and Circuit Breaker Ratings 19 Maximum Motor Cable Lengths 22 DPI Connections 22 Control Connections 26 Control Highlights 29 Standard Drive Specifications 34 Derating Guidelines 38 Watts Loss 39 Cooling Loop Options 39 Additional Resources 47 Original Instructions

2 Product Overview PowerFlex 700L Liquid-Cooled AC drives are responsive, high performance, regenerative industrial drives for installations requiring a compact footprint. The PowerFlex 700L drive offers two versions of control: either the PowerFlex 700 Vector Control or the PowerFlex 700S Phase II Control. This provides the PowerFlex 700L drive with exceptional and proven performance as well as the same interface, communications capabilities and programming tools of the aircooled drives. The many features allow the user to easily configure the drive for most application needs. Ratings presently available include: Hp ( kw) at 400V AC Hp ( kw) at 480V AC Hp ( kw) at 600V AC Hp ( kw) at 690V AC Frame 2 Frame 3B (shown with enclosure doors open) Key Features/Benefits Space Saving Features The PowerFlex 700L AC drive features a patented liquid-cooled heatsink design to transfer over 80% of the drive heat loss to the liquid coolant, resulting in the best drive power-to-size ratio in the market. The integral active converter and line filter translate to a fully regenerative drive that's over 60% smaller than typical air-cooled drives. Integrated Line Regenerative Braking For Precise Control and Energy Savings The Liquid-Cooled AC drive features regenerative braking which is ideal for precise, high-response speed and position control, continuous holdback, rapid deceleration and stopping of high inertia loads. Instead of wasting energy with resistor braking technology, regenerative braking actually puts the energy back into the system to be used by other equipment. Regenerative braking eliminates the need for large resistor banks. These resistors banks can create a lot of heat and must frequently be cleaned. Improved Power Quality with Regenerative Rectifier Compact and cost-effective means to achieve compliance with CE and IEEE 519 harmonic limits. Actively controls power factor regardless of motor speed which reduces input line currents and minimizes the size of upstream devices. Input Voltage Boost Integrated active converter and line-side filter allow input voltage boost to protect your system from power disturbances. Maintains consistent system performance in the event of power dips or other power quality issues. Provides full 480V AC to the motor even when operating on 380V AC power lines. 2 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

3 Flexible Control Platforms Designed for applications with requirements ranging from the simplest speed control to the most demanding torque control, the PowerFlex 700L drive is available with either PowerFlex 700 Vector Control or PowerFlex 700S Control. Outstanding open or closed loop speed regulation for applications ranging from fans and pumps to precise winder control. Excellent torque production and tight torque regulation for demanding applications like extruders, web process, and test stands. Fast update times of torque inputs are suitable for high performance applications. All of this flexibility is possible through multiple control modes: V/Hz control, Sensorless Vector, Vector Control with FORCE Technology, and Permanent Magnet Control (700S control only). Safe Off Option (1), the first offering available within the DriveGuard series of safety solutions, prevents a drive from delivering rotational energy to motors by integrating a safety circuit with the drive's power switching signals. This solution meets EN , Category 3. Packaging Options The PowerFlex 700L frame 2 is an IP00 (Open Style) panel mount drive that can be mounted in a variety of enclosures. The PowerFlex 700L frame 3A and 3B are available in a IP20 (NEMA 1) Rittal enclosure that includes the input circuit breaker. The majority of heat lost from the drive is transferred to the liquid coolant. Therefore, other enclosure options such as IP54 (NEMA/UL Type 12) or IP66 (NEMA/UL Type 4X) can be used and placed directly into dusty, dirty, and outdoor environments. Contact your local Rockwell Automation drive center for these packaging options. Cooling Loop Options A liquid-to-liquid or liquid-to-air heat exchanger, or a chiller can be used with the PowerFlex 700L drive. See page 39 for more information. (1) At time of publication, the Safe Off Option is available with the PowerFlex 700S Control Option in frame 3A and 3B PowerFlex 700L drives. Rockwell Automation Publication 20L-TD001C-EN-P - November

4 Communication and Human Interface Options Premier Integration with PowerFlex Drives and RSLogix 5000 Software For simplified AC drive start-up and reduced development time, we've integrated Allen-Bradley PowerFlex drive configuration with RSLogix 5000 software. This single-software approach simplifies parameter and tag programming while still allowing stand-alone drive software tool use on the factory floor. Communication Modules DPI communication modules provide fast and efficient control and/or data exchange over the following interfaces: DeviceNet ControlNet EtherNet/IP Serial Communications Other open control and communication networks Unsurpassed Capability in Network Communications PowerFlex drives are fully compatible with the wide variety of Allen-Bradley DPI communication adapters, offering the following benefits. DeviceNet ControlNet EtherNet/IP RS485 DF1 PROFIBUS DP CANopen Modbus RTU Modbus TCP Metasys N2 Siemens P1 FLN Description x x x Unconnected Messaging permits other network devices (for example, PanelView ) to communicate directly to a drive without routing the communication through the network scanner. x x x x x Adapter Routing Plug PC into one drive and talk to all other Allen-Bradley drives on same network, without being routed through the network scanner. x x x x x x x x x x Access to 100% of all parameters over the network. x x x AutoBaud capability makes initial connections less problematic. x Change of State significantly reduces network traffic by configuring control messages to be sent only upon customer defined states. Very flexible configuration for each node (Example: reference must change by more than 5% ). x x Peer Control provides master-slave type control between drives, where one or more slave drives (consumers) can run based on the status of a master drive (producer), which can also significantly reduce network traffic. x Automatic Device Replacement (ADR) saves significant time and effort when replacing a drive, by allowing the scanner to be configured to automatically detect a new drive and download the required parameter settings. x x x x x x x x x x Flexible Fault Configuration Adapters can be programmed to take fault based actions such as ramp to stop, coast-to-stop, and hold last state, as well as send user configurable logic control and speed reference values. In addition, different actions can be taken based on whether the network experienced a serious problem (broken cable, and so forth) versus a network idle condition (PLC set to Program ). 4 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

5 PowerFlex Architecture-Class LCD Human Interface Modules An LCD Human Interface Module (also used with the PowerFlex 70, PowerFlex 700, PowerFlex 700S, and PowerFlex 700H) provides multilingual text for startup, metering, programming, and troubleshooting. Large and easy to read 7 line x 21 character backlit display Alternate function keys for shortcuts to common tasks Calculator-like number pad for fast and easy data entry (Full Numeric version only) Control keys for local start, stop, speed, and direction Remote versions for panel mount applications PC-based Configuration Tools Connected Components Workbench software. A free, simple, and flexible on-line tool for monitoring and configuring while connected to a drive. DriveTools SP. A suite of software tools which provide an intuitive means for programming, troubleshooting, and maintaining Allen-Bradley AC and DC drives. Rockwell Automation Publication 20L-TD001C-EN-P - November

6 Catalog Number Explanation Position L E 800 A 0 E N N A N 1 0 W A a b c d e f g h i j k l m n Code 20L a Drive b Voltage Rating Type PowerFlex 700L Code Voltage Ph. C 400V AC 3 D 480V AC 3 E 600V AC 3 F 690V AC 3 c1 ND Rating 400V, 60 Hz Input Code Amps Hp (KW) Frame (200) (370) 3A 1K (715) 3B c2 ND Rating 480V, 60 Hz Input Code Amps Hp (KW) Frame (224) (445) 3A 1K (860) 3B c3 ND Rating 600V, 60 Hz Input Code Amps Hp (KW) Frame (345) 3A (650) 3B 1K (950) 3B Must operate at 2 khz PWM only, and only as a standalone inverter module ( K in position 13). c4 ND Rating 690V, 60 Hz Input Code Amps Hp (KW) Frame (355) 3A (657) 3B 1K (980) 3B Must operate at 2 khz PWM only, and only as a standalone inverter module ( K in position 13). d Enclosure Code Type Conformal Coating A NEMA/UL Type 1, IP20 No N Open-Chassis Style/IP00 No Frame 3 complete drive. Frame 2 drive and frame 3 input filter and power modules. HIM Code Operator Interface 0 No HIM/Blank Cover 3 Full Numeric LCD C Door-Mounted Full Numeric LCD Frame 2 and frame 3 power modules. Frame 3 complete drive only. e Documentation Code Documents Ship Carton E English Doc Set Yes N No Documentation Yes Q No Documentation No Code N Code N f g Brake h w/brake IGBT No Brake Resistor w/resistor No Equipment Type Code Description Frame A Complete Regenerative Drive - Std. Interrupt Rating 2, 3A, and 3B C Input Filter 3A and 3B E Combined Active Converter/ Inverter Power Module 3A only G Active Converter Power Module 3B only J Inverter Power Module - Coupled Version 3B only K Inverter Power Module - Common DC Bus Version 3B only L Dual Inverter Power Module 3A only P Active Converter Power Module - Stand Alone Version 3B only X Spare Power Module 3A and 3B No control cassettes. i j Comm Slot Code Communication Option DPI User- Installed Kit Cat. No. N None N C ControlNet (Coax) - DPI 20-COMM-C D DeviceNet - DPI 20-COMM-D E EtherNet/IP - DPI 20-COMM-E 1 DriveLogix Comm Option, ControlNet (Coax) 2 DriveLogix Comm Option, ControlNet Redundant (Coax) 3 DriveLogix Comm Option, ControlNet (Fiber) 4 DriveLogix Comm Option, ControlNet Redundant (Fiber) 5 DriveLogix Comm Option, DeviceNet (Open Connection) 6 DriveLogix Comm Option, DeviceNet (Twisted Pair) For 700S Phase II Control with DriveLogix5730, comm. slot option selections are mutually exclusive. For two communication adapters, (DPI and DriveLogix), select the DriveLogix comm. slot option and order the DPI user installed kit catalog number separately. 700 Vector Control uses DPI comm. slot options only. DriveLogix comm. slot options require 700S Phase II Control with DriveLogix Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

7 Position L E 800 A 0 E N N A N 1 0 W A a b c d e f g h i j k l m n k Control Option Code Control Cassette Logic Expansion Synch Link 1 700VC 24V I/ O Base N/A N/A 2 700VC 115V I/O Base N/A N/A A 700S Ph. II Expanded No No B 700S Ph. II Expanded No Yes C 700S Ph. II Expanded Yes No D 700S Ph. II Expanded Yes Yes W None N/A N/A N/A Frame 3 input filter, Active Converter Power Modules, and spare power modules. Requires DriveLogix5730. Feedback Code Control Option Type 0 All None 1 700VC Encoder 5V/12V A 700S Ph. II Resolver B 700S Ph. II Hi-Res. Stegmann Encoder C 700S Ph. II Multi-Device Interface E 700S Ph. II 2nd Encoder S 700S Ph. II Safe-Off (w/2nd Encoder) Requires expanded cassette. Multi-Device Interface allows the connection of the Stegmann and Temposonics linear sensors. The Temposonics sensor cannot be used to close motor control or speed loops. l m Additional 700S Configuration Code Logix Option Embedded Comm. W None E Phase II Control No K Phase II Control with DriveLogix5730 No L Phase II Control with DriveLogix5730 EtherNet/IP Coolant Type Code Coolant Frame N None 3 Input Filter only A Water All n Rockwell Automation Publication 20L-TD001C-EN-P - November

8 Standard Drive Product Selection 400V AC Three-phase Drives Output Amps (with 400V AC Induction Motor) (1) Nominal Power Ratings IP20, NEMA/UL Type 1 (2) Normal Duty Heavy Duty Normal Duty Heavy Duty Cat. No. Cont. 110% 150% Cont. 150% 200% kw Hp kw Hp 1 min 3 s 1 min 3 s LC360N0ENNAN10WA LC650A0ENNAN10WA 3A LC1K2A0ENNAN10WA 3B 4 (1) Frame 2 ratings are based on 50 C ambient and 50 C coolant. Frame 3A and 3B ratings are based on 40 C ambient and 40 C coolant. (2) Frames 3A and 3B only. Frame 2 drives are IP00, NEMA/UL Type Open. Frame Size PWM Freq. (khz) 480V AC Three-phase Drives Output Amps (with 480V AC Induction Motor) (1) Nominal Power Ratings IP20, NEMA/UL Type 1 (2) Normal Duty Heavy Duty Normal Duty Heavy Duty Cat. No. Cont. 110% 150% Cont. 150% 200% kw Hp kw Hp 1 min 3 s 1 min 3 s LD360N0ENNAN10WA LD650A0ENNAN10WA 3A LD1K2A0ENNAN10WA 3B 4 (1) Frame 2 ratings are based on 50 C ambient and 50 C coolant. Frame 3A and 3B ratings are based on 40 C ambient and 40 C coolant. (2) Frames 3A and 3B only. Frame 2 drives are IP00, NEMA/UL Type Open. Frame Size PWM Freq. (khz) 600V AC Three-phase Drives Output Amps (with 600V AC Induction Motor) (1) Nominal Power Ratings IP20, NEMA/UL Type 1 Frame Normal Duty Heavy Duty Normal Duty Heavy Duty Cat. No. Size Cont. 110% 150% Cont. 150% 200% kw Hp kw Hp 1 min 3 s 1 min 3 s LE425A0ENNAN10WA 3A LE800A0ENNAN10WA 3B LE1K1A0ENNAN10WA 3B 2 (2) (1) Frame 3A and 3B ratings are based on 40 C ambient and 40 C coolant. (2) Must operate at 2 khz PWM only, and only as a stand-alone inverter module ( K in catalog string position 13). PWM Freq. (khz) 690V AC Three-phase Drives Output Amps (with 690V AC Induction Motor) (1) Nominal Power Ratings IP20, NEMA/UL Type 1 Frame Normal Duty Heavy Duty Normal Duty Heavy Duty Cat. No. Size Cont. 110% 150% Cont. 150% 200% kw Hp kw Hp 1 min 3 s 1 min 3 s LF380A0ENNAN10WA 3A LF705A0ENNAN10WA 3B LF1K0A0ENNAN10WA 2 (2) (1) Frame 3A and 3B ratings are based on 40 C ambient and 40 C coolant. (2) Must operate at 2 khz PWM only, and only as a stand-alone inverter module ( K in catalog string position 13). PWM Freq. (khz) 8 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

9 Factory Installed Options Human Interface and Wireless Interface Modules IP20, NEMA/UL Type 1 (Position e) Documentation English Documentation Set No Documentation Description Internal Communication Adapters None Cat. Code: 0 No HIM (Blank Plate) Description ControlNet Communication Adapter (Coax) DeviceNet Communication Adapter EtherNet/IP Communication Adapter Cat. Code: 3 LCD Display, Full Numeric Keypad Cat. Code (Position f) E N Cat. Code (Position j) DriveLogix Comm Option, ControlNet (Coax) 1 DriveLogix Comm Option, ControlNet Redundant (Coax) 2 DriveLogix Comm Option, ControlNet (Fiber) 3 DriveLogix Comm Option, ControlNet Redundant (Fiber) 4 DriveLogix Comm Option, DeviceNet (Open Conn.) 5 DriveLogix Comm Option, EtherNet/IP (Twisted Pair) Vector Control uses DPI comm. slot options only. DriveLogix comm. slot option requires 700S Phase II Control with DriveLogix5730. Cat. Code: C Door Mounted Bezel LCD Display, Full Numeric Keypad NEMA/UL Type 1 N C D E Feedback Options Control Cat. Code Type Description (Position l) All No Encoder 0 700VC 12V/5V Encoder 1 Resolver, 10 26V, 10 khz, bit A 700S Phase II Stegmann - High Resolution Encoder Hyperface, 8.5V dc, 20 bit, 100k/r Multi-Device Interface - for Stegmann or Linear Temposonics 2nd Encoder, 5V or 12V Configurable by the Drive DriveGuard Safe-Off (w/2nd Encoder) Requires Expanded Cassette. Additional 700S Configuration Embedded Cat. Code Description Communication (Position m) None W P hase II C ontrol No E Phase II Control, with DriveLogix5730 Controller No K Phase II Control, with DriveLogix5730 Controller & EtherNet/IP EtherNet/IP L Coolant Options Water Description All Frame B C E S Cat. Code (Position n) A Control Options Control Option Description Cat. Code (Position k) 700VC - 24V I/O Base Cassette 1 700VC - 115V I/O Base Cassette 2 Expanded Cassette Only A Phase II Control Expanded Cassette w/synchlink B Phase II Control Expanded Cassette w/logix Expansion Board C Expanded Cassette w/logix Expansion Board & SynchLink D Requires DriveLogix5730. Rockwell Automation Publication 20L-TD001C-EN-P - November

10 POWER STS PORT MOD NET A NET B PowerFlex 700L User Installed Options For information on user installed options, see the PowerFlex Low Voltage AC Drives Selection Guide, publication PFLEX-SG002. Product Dimensions Frame 2 Drive (15.34) (13.82) Dimensions are in millimeters and (inches). See DETAIL A (22.29) Ground Terminal with 2 Clearance Holes for M8 Stud 66.6 (2.62) (16.68) (28.75) (23.28) (6.06) Motor W/T3 Output V/T2 Terminals U/T1 3x Clearance Hole for M8 Stud (37.63) 46.9 (1.85) See DETAIL B Coolant Outlet 37 Deg Flare -12 Coolant Inlet 37 Deg Flare -12 3x Clearance Hole for M8 Stud R/L1 S/L2 T/L3 AC Input Terminals Stirring Fan Housing BACK VIEW SIDE VIEW FRONT VIEW 4x Ø 8.5 (0.33) 8.6 (0.34) 4x 4x Ø 15.0 (0.59) 16 (0.63) 4x 14.9 (0.59) 4x DETAIL A DETAIL B Weight: 186 kg (410 lb) 10 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

11 Frame 3A/3B Drive C Dimensions are in millimeters and (inches). 38 (1.50) INPUT FILTER BAY POWER MODULE BAY G H 65 (2.56) J Ø35 (Ø1.38) 61 (2.39) D Max. B E OUTLET INLET A F Max. Frame Dimensions Weight kg (lb) Size A B C D E F G H J Complete Drive 3A 1200 (47.2) 2000 (78.7) 600 (23.6) 2078 (81.9) 1500 (59.1) 233 (9.2) 542 (21.3) 542 (21.3) 535 (21.1) 950 (2090) 3B 1600 (63.0) 2200 (86.6) 800 (31.5) 2278 (89.8) 1500 (59.1) 233 (9.2) 542 (21.3) 942 (37.1) 735 (28.9) 1361 (3000) Rockwell Automation Publication 20L-TD001C-EN-P - November

12 Installation Considerations Power Wiring The PowerFlex 700L has the following built-in protective features to help simplify installation: Ground fault protection during start up and running ensures reliable operation Electronic motor overload protection increases motor life AC Supply Source Considerations PowerFlex 700L Liquid-Cooled AC drives are suitable for use on a circuit capable of delivering up to a maximum of 200,000 rms symmetrical amperes. PowerFlex 700L Liquid Cooled AC drives should not be used on undersized or high-impedance supply systems. The supply system kva should be equal to or greater than the drive-rated kw, and the system impedance should be less than 10%. Operation outside these limits could cause instability resulting in drive shutdown. PowerFlex 700L Liquid Cooled AC drives have a built-in LCL filter which includes a 3% input line reactor. Additional input line reactors are not recommended. Unbalanced, Ungrounded or Resistive Grounded Distribution Systems Removable MOV to ground and common mode capacitors to ground ensure compatibility with ungrounded systems. These devices must be disconnected if the drive is installed on a resistive grounded distribution system, an ungrounded distribution system, or a B phase grounded distribution system. These devices must also be disconnected if a regenerative unit is used as a bus supply or brake. Input Power Conditioning Certain events on the power system supplying a drive can cause component damage or shortened product life. These events include the following: The power system has power factor correction capacitors switched in and out of the system, either by the user or by the power company. The power source has intermittent voltage spikes in excess of 6000 volts. These spikes could be caused by other equipment on the line or by events such as lightning strikes. The power source has frequent interruptions. There are many other factors that must be considered for optimal performance in any given application. Primary Installation Considerations on page 13 highlights the primary installation considerations. For detailed recommendations on input power conditioning, reflected wave protection, and motor cable types, see the Wiring and Grounding Guidelines for PWM AC Drives, Installation Instructions, publication DRIVES-IN001. EMC Requirements The 700VC control option for frame 2 comes with two common mode chokes one for input and one for output. The 700S control option for frame 2 requires a field-installed kit SK-L1-CHK2-F2. See the PowerFlex 700L User Manual, publication 20L-UM001, for other CE requirements. PowerFlex 700L frame 3A and 3B drives do not require common mode chokes for CE compliance. 12 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

13 POWER STS PORT MOD NET A NET B PowerFlex 700L Primary Installation Considerations (Frame 2 Drive Shown) LCD Human Interface Module - Page 9 EMC Requirements - Page 12 Reflected Wave Reduction - Page 9 Cable Recommendations - Page 18 Integral Class 10 Motor Overload Motor Recommendations -See Removable MOV and Caps (underneath cover) - See the PowerFlex 700L User Manual, publication 20L-UM001 EMC Requirements - See the PowerFlex 700L User Manual, publication 20L-UM001 Input Power Conditioning - Page 12 Power Ratings and Branch Circuit Protection - Page 19 Unbalanced, Ungrounded or Resistive Grounded Distribution Systems - Page 12 AC Supply Source Considerations - Page 12 Frame 2 Drive Recommended Mounting Clearances Specified vertical clearance requirements are intended to be from drive to drive. Other objects can occupy this space; however, reduced air flow may cause protection circuits to fault the drive. In addition, inlet air temperature must not exceed the product specification mm (4.0 in.) mm (4.0 in.) Mounting Requirements mm (4.0 in.) The PowerFlex700L frame 2 drive is a single integrated assembly consisting of a filter section and a power section. The filter section provides the mounting feet and represents greater than 50% of the approximately 186 kg (410 lb) total weight. Follow these mounting requirement guidelines: Mount the frame 2 drive into an enclosure that is designed according to Electrical Equipment Pollution Degree 2 requirements. Size and fasten any enclosure mounting panel appropriately to accommodate for the weight of the drive mm (4.0 in.) See the PowerFlex 700L User Manual, publication 20L-UM001, for detailed mounting instructions mm (4.0 in.) Rockwell Automation Publication 20L-TD001C-EN-P - November

14 Determining Wire Routing for Control, Ground, Drive Input, and Motor Output All wiring should be installed in conformance with the applicable local, national, and international codes (for example, NEC/CEC). Signal wiring, control wiring, and power wiring must be routed in separate conduits to prevent interference with drive operation. When hubs are not provided, use grommets to guard against wire chafing. Do not route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution can result in damage to, or destruction of, the equipment. Do not route more than three sets of motor leads through a single conduit. This minimizes cross-talk that can reduce the effectiveness of noise reduction methods. If more than three drive/motor connections per conduit are required, shielded cable must be used. If possible, each conduit should contain only one set of motor leads. Frame 2 Locations for Control Wire Routing, DPI Communication Port, and Coolant Connections 28.0 (1.10) Dimensions are in millimeters and (inches). DPI Communications Port Coolant Inlet Control Wire Conduit Plug 62.7 (2.47) Dia (8.79) (11.04) (8.74) (5.98) (4.41) 72.0 (2.83) 12.6 (0.50) Control Wire Conduit Plug 22.2 (0.87) Dia. Coolant Outlet Bottom View of Drive R/L1 S/L2 T/L (11.43) (9.68) (18.97) (7.87) (10.12) 14 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

15 Frame 2 Power Terminal Locations ➌ ➋ W/T3 V/T2 U/T1 DC+ Testpoint ➍ DC- Testpoint A A Section A-A R/L1 S/L2 ➊ T/L3 Frame 2 Power Terminal Specifications Item Name Description Recommended Tightening Torque (+10%) Terminal Bolt Size (3) ➊ Input Power Bus Bar (1) Input power 40 N m (354 lb in) M8 R/L1, S/L2, T/L3 ➋ Output Power Bus Bar (1) U/T1, V/T2, W/T3 Motor connections 40 N m (354 lb in) M8 ➌ PE, Motor Ground Bus Bar (1) Terminating point for wiring shields and grounds 40 N m (354 lb in) M8 ➍ DC Bus Test Point Socket (2) (2 Terminals; DC+, DC-) 4 mm socket for DC bus voltage measurement only (1) These connections are bus bar type terminations and require the use of lug connectors. (2) Use only to verify that DC bus capacitors are discharged before servicing the power module. No other external use is permitted. (3) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt to avoid damage to the terminal. Rockwell Automation Publication 20L-TD001C-EN-P - November

16 POWER STS DC POSITIVE TB5 DC NEGATIVE VAC 2 PRECHARGE COIL VAC NEUTRAL 24 VDC 5 PR HARGE FEEDBACK GATE ENABLE 7 INDUCTOR OVERTEMP WIRE RANGE: AWG (0.2-4 MM) STRIP LENGTH: 0.31 IN (8 MM) TORQUE: 8 IN-LB (0.9 N-M) PORT MOD NET A NET B PowerFlex 700L Frame 3A/3B Drive Recommended Mounting Clearances Verify that there is adequate clearance for air circulation around the drive enclosures. A 15 cm (6 in.) minimum clearance is required wherever vents in the cabinet are located. Determining Wire Routing for Control, Ground, Drive Input, and Motor Output All wiring should be installed in conformance with the applicable local, national, and international codes (for example, NEC/CEC). Signal wiring, control wiring, and power wiring must be routed in separate conduits to prevent interference with drive operation. When hubs are not provided, use grommets to guard against wire chafing. Do not route signal and control wiring with power wiring in the same conduit. This can cause interference with drive operation. Failure to observe this precaution can result in damage to, or destruction of, the equipment. Do not route more than three sets of motor leads through a single conduit. This minimizes cross-talk that can reduce the effectiveness of noise reduction methods. If more than three drive/motor connections per conduit are required, shielded cable must be used. If possible, each conduit should contain only one set of motor leads. Frame 3A Power Terminal Locations ➊ ➋ ➌ (Drive shown with doors removed) ➍ Coolant Outlet Coolant Inlet 16 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

17 DC POSITIVE DC NEGATIVE TB VAC 2 PRECHARGE COIL 24 VDC 4 PR HARGE FEEDBACK ATE ENABLE 6 INDUCTOR OVERTEMP WIRE RANGE: AWG (0.2-4 MM) STRIP LENGTH: 0.31 IN (8 MM) TORQUE: 8 IN-LB (0.9 N-M) POWER STS PORT MOD NET A NET B PowerFlex 700L Frame 3B Power Terminal Locations ➊ ➎ ➋ ➌ (Drive shown with doors removed) ➍ Coolant Outlet Coolant Inlet Frame 3A/3B Power Terminal Specifications Item Name Description Frame Size ➊ Input Power Wire Lugs R/L1, S/L2, T/L3 Wire Size Range (4) Maximum Minimum Input power connections on drive 3A 400 MCM 3/0 42 N m (375 lb in) 3B 1000 MCM 500 MCM 62 N m (550 lb in) Recommended Tightening Torque (+10%) ➋ PE Wire Lug Terminating point for ground wires 3A or 3B 600 MCM # 2 AWG 34 N m (300 lb in) ➌ Output Power Bus Bar (1) U/T1, V/T2, W/T3 Motor connections 3A or 3B 62 N m (550 lb in) ➍ DC Bus Test Point Socket (2) (2 Terminals; DC+, DC-) 4 mm socket for DC bus voltage measurement only 3A or 3B ➎ DC Power Bus Bar (1) (3) (2 Terminals; DC+, DC-) DC power from Converter Power Module to Inverter Power Module 3B 62 N m (550 lb in) (1) These connections are bus bar type terminations and require the use of lug connectors. (2) Use only to verify that DC bus capacitors are discharged before servicing the power module. No other external use is permitted. (3) Size DC power conductors for current carrying capacity as follows: 400/480V, 1000 Amps; 600/690V, 800 Amps. (4) Maximum/minimum sizes that the terminals will accept - these are not recommendations. Rockwell Automation Publication 20L-TD001C-EN-P - November

18 Cable Recommendations Cable Types Acceptable for Volt Installations A variety of cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 0.3 meters (1 foot) for every 10 meters (32.8 feet) of length. In all cases, long parallel runs must be avoided. Do not use cable with an insulation thickness less than or equal to 15 mils (0.4mm/0.015 in.). Use Copper wire only. Wire gauge requirements and recommendations are based on 75 C (167 F). Do not reduce wire gauge when using higher temperature wire. See the table on page 19. Unshielded Cable THHN, THWN, or similar wire is acceptable for drive installation in dry environments provided adequate free air space and/or conduit fill rate limits are used. Do not use THHN or similarly coated wire in wet areas. Any wire chosen must have a minimum insulation thickness of 15 mils (0.4mm/0.015 in.) and should not have large variations in insulation concentricity. Shielded Cable Shielded cable contains all of the general benefits of multi-conductor cable with the added benefit of a copper braided shield that can contain much of the noise generated by a typical AC drive. Strong consideration for shielded cable should be given in installations with sensitive equipment such as weigh scales, capacitive proximity switches, and other devices that may be affected by electrical noise in the distribution system. Applications with large numbers of drives in a similar location, imposed EMC regulations, or a high degree of communication/networking are also good candidates for shielded cable. Shielded cable may also help reduce shaft voltage and induced bearing currents for some applications. In addition, the increased impedance of shielded cable may help extend the distance that the motor can be located from the drive without the addition of motor protective devices such as terminator networks. See Reflected Wave in Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001. Consideration should be given to all of the general specifications dictated by the environment of the installation, including temperature, flexibility, moisture characteristics, and chemical resistance. Additionally, a braided shield should be included and be specified by the cable manufacturer as having coverage of at least 75%. An additional foil shield can greatly improve noise containment. A good example of recommended cable is Belden (AWG-1 through AWG-410). This cable has three XLPE insulated conductors plus ground with a spiral copper shield surrounded by a PVC jacket. Other types of shielded cable are available, but the selection of these types may limit the allowable cable length. Particularly, some of the newer cables twist 4 conductors of THHN wire and wrap them tightly with a foil shield. This construction can greatly increase the cable charging current required, and reduce the overall drive performance. These cables are not recommended. 18 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

19 Armored Cable Cable with continuous aluminum armor is often recommended in drive system applications or specific industries. It offers most of the advantages of standard shielded cable and also combines considerable mechanical strength and resistance to moisture. It can be installed in concealed and exposed manners and removes the requirement for conduit (EMT) in the installation. It can also be directly buried or embedded in concrete. Because noise containment can be affected by incidental grounding of the armor to building steel when the cable is mounted, we recommend that the armor cable have an overall PVC jacket. For details, see Wire Types in Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001. Interlocked armor is acceptable for shorter cable runs, but continuous welded armor is preferred. Best performance is achieved with three spaced ground conductors, but acceptable performance for drives below 200 Hp is provided by way of a single ground conductor. Location Cable Rating/Type Description Standard (Option 1) Standard (Option 2) Class I & II; Division I & II 1000V, 90 C (194 F) XHHW2/RHW-2 Anixter B29528-B29532, Belden , or equivalent Tray rated 1000V, 90 C (194 F) RHH/RHW-2 Anixter OLFLEX-76xxx03, or equivalent Tray rated 1000V, 90 C (194 F) RHH/RHW-2 Anixter 7VFD-xxxx, or equivalent Four tinned copper conductors with XLPE insulation. Copper braid/aluminum foil combination shield and tinned copper drain wire. PVC jacket. Three tinned copper conductors with XLPE insulation. Corrugated copper tape with three bare copper grounds in contact with shield. PVC jacket. Three bare copper conductors with XLPE insulation and impervious corrugated continuously welded aluminum armor. Black sunlight resistant PVC jacket overall. Three copper grounds. Cable Trays and Conduit If cable trays or large conduits are to be used, see the guidelines in Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001. Fuse and Circuit Breaker Ratings Most codes require that upstream branch circuit protection be provided to protect input power wiring. The frame 2 drive does not provide input power short circuit protection. The tables on the following pages provide recommended AC line input fuse and circuit breaker information. See below for UL and IEC requirements. Sizes listed are the recommended sizes based on 40 C (104 F) and the U.S. NEC. Other country, state or local codes may require different ratings. Tables with DC link fuse recommendations for DC input drives are also provided. Rockwell Automation Publication 20L-TD001C-EN-P - November

20 Fusing The recommended fuse types are listed below. If available current ratings do not match the tables provided, the next higher fuse rating should be chosen. IEC BS88 (British Standard) Parts 1 & 2, EN , Parts 1 & 2 (1), type gg fuses or equivalent should be used. UL UL Class T, J or L fuses should be used. Circuit Breakers The non-fuse listings in the following tables include inverse time circuit breakers, instantaneous trip circuit breakers (motor circuit protectors), and 140M self-protected combination motor controllers. If one of these is chosen as the desired protection method, the following requirements apply. IEC Both types of circuit breakers and 140M self-protected combination motor controllers are acceptable for IEC installations. UL Only inverse time circuit breakers and the specified 140M self-protected combination motor controllers are acceptable for UL installations. 400 Volt AC Input Protection Devices Drive Catalog Number Frame HP (kw) Rating Input Rating Dual Element Time Delay Fuse ND HD Amps Min. (1) Max. (2) Non-Time Delay Fuse Circuit Breaker (3) Min. Max. Max. (4) 20LC (200) (150) (1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. (2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum. (3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum (4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation. (5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are maximum Motor Circuit Protector (5) Max. 480 Volt AC Input Protection Devices Drive Catalog Number Frame HP (kw) Rating Input Rating Dual Element Time Delay Fuse ND HD Amps Min. (1) Max. (2) Non-Time Delay Fuse Circuit Breaker (3) Min. Max. Max. (4) 20LD (224) (175) (1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. (2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum. (3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum (4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation. (5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are maximum Motor Circuit Protector (5) Max. (1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH. 20 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

21 540 Volt DC Input Fusing Drive Catalog Number Frame HP (kw) Rating DC Input Rating Bussmann Fuse ND HD Amps Amps Catalog No. 20LC650 3A 500 (370) 365 (270) 1250 (1) M6621 (2) 20LC1K2 3B 960 (715) 700 (525) M6621 (2) (1) Only the Dual Inverter for PowerFlex 700L Frame 3A is available as a DC input inverter. (2) Two 1000A Bussmann 170M6614 fuses per phase can also be used. 650 Volt DC Input Fusing Drive Catalog Number Frame HP (kw) Rating DC Input Rating Bussmann Fuse ND HD Amps Amps Catalog No. 20LD650 3A 600 (445) 440 (325) 1250 (1) M6621 (2) 20LD1K2 3B 1150 (860) 845 (630) M6621 (2) (1) Only the Dual Inverter for PowerFlex 700L Frame 3A is available as a DC input inverter. (2) Two 1000A Bussmann 170M6614 fuses per phase can also be used. 810 Volt DC Input Fusing Drive Catalog Number Frame HP (kw) Rating DC Input Rating Bussmann Fuse ND HD Amps Amps Catalog No. 20LE425 3A 465 (345) 345 (255) 850 (1) M6701 (2) 20LE800 3B 870 (650) 640 (480) M6700 (3) 20LE1K1 3B 1275 (955) 935 (695) (2 per phase) 170M6697 (1) Only the Dual Inverter for PowerFlex 700L Frame 3A is available as a DC input inverter. (2) Two 700A Bussmann 170M6695 fuses per phase can also be used. (3) Two 630A Bussmann 170M6694 fuses per phase can also be used. 932 Volt DC Input Fusing Drive Catalog Number Frame HP (kw) Rating DC Input Rating Bussmann Fuse ND HD Amps Amps Catalog No. 20LF380 3A 475 (355) 350 (260) 760 (1) M6700 (2) 20LF705 3B 881 (657) 650 (485) M6699 (3) 20LF1K0 3B 1315 (980) 965 (720) (2 per phase) 170M6696 (1) Only the Dual Inverter for PowerFlex 700L Frame 3A is available as a DC input inverter. (2) Two 630A Bussmann 170M6694 fuses per phase can also be used. (3) Two 550A Bussmann 170M6693 fuses per phase can also be used. Rockwell Automation Publication 20L-TD001C-EN-P - November

22 Circuit Breakers for Frame 3A/3B Complete Drives Frame 3A/3B complete drives include an input power circuit breaker. The value of the circuit breaker provided with the drive is listed in the table below. Frame Size Input Voltage Circuit Breaker Provided Shunt Trip Rating 3A V AC 800 A 65 kaic V AC 800 A 35 kaic 3B V AC 1500 A 100 kaic V AC 1500 A 35 kaic Maximum Motor Cable Lengths See the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, Installation Instructions, publication DRIVES-IN001, for details on maximum motor cable lengths. DPI Connections Frame 2 Drive Connection Points The PowerFlex 700L frame 2 drive provides a number of cable connection points as shown in the illustration. If an additional external HIM is required for the application, the HIM can be connected to the DPI port on the bottom of the drive. Only one additional external HIM device may be connected. The use of two external HIM devices is not supported. If multiple external HIM devices are required, then install a user-supplied splitter cable or splitter box. 22 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

23 3 Drive HIM Option 1 External HIM Option 2 5 Communications Adapter Option 4 Active Converter PCB External DPI Cable Bottom View of Drive R/L1 S/L2 T/L3 Item Connector Description 1 DPI Port 1 HIM connection when installed in the drive. 2 DPI Port 2 Cable connection for handheld and remote options. 3 DPI Port 3 or 2 Splitter cable connection to DPI Port 2 provides additional port. 4 DPI Port 5 Cable connection for communications adapter. 5 DPI Port 6 Internal DPI connection to Active Converter pcb. External Door-mounted HIM Connection (Optional) For a frame 2 drive installed in a user-supplied enclosure, an optional external door-mounted HIM may be connected as an alternative to the external HIM option. The cable supplied with the door-mounted HIM option kit connects to the DPI port on the bottom of the drive (see drawing above). For additional installation information, see the instructions provided with the door-mount HIM option kit. Rockwell Automation Publication 20L-TD001C-EN-P - November

24 Frame 3A Drive Connection Points The PowerFlex 700L provides a number of cable connection points as shown in the drawing below. If an additional external HIM is required for the application, the HIM can be connected to the DPI port on the bottom of the power module. Only one additional external HIM device may be connected. The use of two external HIM devices is not supported. If multiple external HIM devices are required, then install a user-supplied splitter cable or splitter box. Combined Active Converter/Inverter Power Module ➎ Power Module HIM Option ➊ Communications Adapter Option ➍ External HIM Option External DPI Cable ➌ ➋ Active Converter PCB Internal DPI Cable Bottom View of Power Module No Connection Permitted ➋ Item Connector Description ➊ DPI Port 1 HIM connection when installed in power module. ➋ DPI Port 2 Cable connection for handheld and remote options. ➌ DPI Port 3 or 2 Splitter cable connected to DPI Port 2 provides an additional port. ➍ DPI Port 5 Cable connection for communications adapter. ➎ DPI Port 6 Internal DPI connection to Active Converter PCB. External Door-mounted HIM Connection (Optional) For complete drives, the door-mounted HIM is standard equipment. It is located in the door mount bezel on the door of the power module bay. 24 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

25 Frame 3B Drive Connection Points The PowerFlex 700L provides a number of cable connection points as shown in the drawing below. If an additional external HIM is required for the application, the HIM can be connected to the DPI port on the bottom of the power module. Only one additional external HIM device may be connected. The use of two external HIM devices is not supported. If multiple external HIM devices are required, then install a user-supplied splitter cable or splitter box. Active Converter Power Module Inverter Power Module ➎ Active Converter PCB Blank HIM No Connections Permitted No Communications Adapter Permitted Power Module HIM Option ➊ Communications Adapter Option ➍ Inverter-to-Converter DPI Cable External HIM Option External DPI Cable ➋ ➌ Internal DPI Cable Internal DPI Cable Inverter-to-Converter DPI Cable No Connection Permitted ➋ Bottom View of Power Modules Item Connector Description ➊ DPI Port 1 HIM connection when installed in power module. ➋ DPI Port 2 Cable connection for handheld and remote options. ➌ DPI Port 3 or 2 Splitter cable connected to DPI Port 2 provides an additional port. ➍ DPI Port 5 Cable connection for communications adapter. ➎ DPI Port 6 Internal DPI connection to Active Converter PCB. External Door-mounted HIM Connection (Optional) For complete drives, the door-mounted HIM is standard equipment. It is located in the door mount bezel on the door of the power module bay. Rockwell Automation Publication 20L-TD001C-EN-P - November

26 Control Connections Frame 2 Frame 2 Control Terminal Locations ➊ 1 SHLD P1 15 ➋ P2 7 1 SHLD ➌ ➍ TB1 PE2 PE1 1b15 1b14 1b13 1b12 1b11 1b10 1b9 1b8 PS+ 1a15 1a14 1a13 1a12 1a11 1a10 1a9 1a8 1b7 1b6 1b5 1b4 1b3 1b2 1b1 PS- 1a7 1a6 1a5 1a4 1a3 1a2 1a1 PS- PS+ PE1 PE2 Customer Connection Side Frame 2 Control Terminal Specifications Item Name Description Wire Size Range (1) ➊ PowerFlex 700 Vector Control or PowerFlex 700S Phase II Control Cassette Terminal Blocks Maximum See PowerFlex 700 Series B Technical Data, publication 20B-TD001 or PowerFlex 700S Technical Data, publication 20D-TD002 respectively for details. Minimum Recommended Tightening Torque (+10%) Wire Strip Length ➋ Active Converter Cassette Terminal Blocks P1 & P2 Active Converter AC power and control wiring 3.3 mm 2 (#12 AWG) 0.3 mm 2 (#22 AWG) 0.8 N m (7 lb in) 8 mm (0.31 in.) ➌ SHLD Terminal Terminating point for control wiring shields on the drive 2.1 mm 2 (#14 AWG) 0.3 mm 2 (#22 AWG) 1.4 N m (12 lb in) 10 mm (0.39 in.) ➍ Terminal Block TB1 1b 5: +12/+24V Cooling Loop 1b 6: Cooling Loop Return Drive control wiring: Output dry contact (12V DC/24V DC, 2 Amps max.) indicating the drive is powered and has completed precharge. 4.0 mm 2 (#10 AWG) 0.2 mm 2 (#24 AWG) 0.9 N m (8 lb in) 8 mm (0.31 in.) 1b 7: +24V (digin) Drive-supplied +24V DC 1b 8: Gate Enable Enables the firing of the IGBTs. Factory-installed jumper from terminal 1b 7 to terminal 1b 8 allows firing of the IGBTs. ➎ PS- Terminal PS+ Terminal 300V DC Auxiliary Control voltage 4.0 mm 2 (#12 AWG) 0.5 mm 2 (#22 AWG) 0.6 N m (5.3 lb in) 10 mm (0.39 in.) (1) Maximum/minimum sizes that the terminals will accept - these are not recommendations. 26 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

27 POWER STS DC POSITIVE TB5 DC NEGATIVE VAC 2 PRECHARGE COIL VAC NEUTRAL 24 VDC 5 PR HARGE FEEDBACK GATE ENABLE 7 INDUCTOR OVERTEMP WIRE RANGE: AWG (0.2-4 MM) STRIP LENGTH: 0.31 IN (8 MM) TORQUE: 8 IN-LB (0.9 N-M) PORT MOD NET A NET B PowerFlex 700L Frame 3 Frame 3A Control Terminal Locations ➊ ➋➌ (Drive shown with doors removed) ➍ Coolant Outlet Coolant Inlet Rockwell Automation Publication 20L-TD001C-EN-P - November

28 DC POSITIVE DC NEGATIVE TB VAC 2 PRECHARGE COIL 24 VDC 4 PR HARGE FEEDBACK ATE ENABLE 6 INDUCTOR OVERTEMP WIRE RANGE: AWG (0.2-4 MM) STRIP LENGTH: 0.31 IN (8 MM) TORQUE: 8 IN-LB (0.9 N-M) POWER STS PORT MOD NET A NET B PowerFlex 700L Frame 3B Control Terminal Locations ➋➌ ➊ (Drive shown with doors removed) ➍ Coolant Outlet Coolant Inlet Frame 3A/3B Control Terminal Specifications Item Name Description Wire Size Range (1) ➊ PowerFlex 700 Vector Control or PowerFlex 700S Phase II Control Cassette Terminal Blocks Maximum Minimum See PowerFlex 700 Series B Technical Data, publication 20B-TD001 or PowerFlex 700S Technical Data, publication 20D-TD002 respectively for details. Recommended Tightening Torque (+10%) Wire Strip Length Wire Terminal ➋ Active Converter Cassette Terminal Blocks P1 & P2 Active Converter AC power and control wiring 3.3 mm 2 (#12 AWG) 0.3 mm 2 (#22 AWG) 0.8 N m (7 lb in) 8 mm (0.31 in.) not applicable ➌ SHLD Terminal Terminating point for control wiring shields on power module 2.1 mm 2 (#14 AWG) 0.3 mm 2 (#22 AWG) 1.4 N m (12 lb in) 10 mm (0.39 in.) not applicable ➍ Terminal Blocks TB5 and TB6 Power module control wiring 4.0 mm 2 (#10 AWG) 0.2 mm 2 (#24 AWG) 1.4 N m (12 lb in) 8 mm (0.31 in.) not applicable (1) Maximum/minimum sizes that the terminals will accept - these are not recommendations. 28 Rockwell Automation Publication 20L-TD001C-EN-P - November 2015

29 Control Highlights Active Converter Control File Group Parameters Monitor Current Rated Amps 001 Monitor Input Current R 002 Input Current S 003 Voltage Rated Volts 010 Input Voltage RS 011 Power & Time Rated Power 020 AC Line kw 021 Motoring kwh 022 Input Current T 004 Ground Current 005 Active Current 006 Input Voltage ST 012 Input Voltage TR 013 Regen kwh 023 Lifetime kwh 024 Elapsed Run Time 025 Reactive Current 007 I Imbalance 008 IT Overload 009 DcLink Voltage 014 DcLink Ripple 015 Life Run Time 026 Life Power Time 027 Life Pwr Cycles 028 Temperature Ambient Temp 030 IGBT Base Temp 031 IGBT Junct Temp 032 Frequency Line Frequency 040 Min Line Freq 041 Max Line Freq 042 Min Max Persist 043 Change Line Freq 044 V Imbalance 016 Command Start/Stop Start Config 050 Option Select 051 Manual Control 052 Turn Off Delay 053 Command Setpoints DcLink Reference 060 kvar Reference 061 Extern Cml Ref 062 Modulation Index 063 Modulation Freq 064 Data Exchange Converter Control 070 Converter Status 071 Converter Min Vdc 072 Converter Fault 073 Limit Config Current Active I Lmt 100 Active OL I Lmt 101 AC Line Voltage Ride Through Ena 110 Ride Through Sec 111 Limit Config Temperature Ambnt Temp Alrm 120 Ambnt Temp Trip 121 Frequency PWM Frequency 130 AC Low Freq Lmt 131 Dynamic Control Current Loop Reduce Ilmt Sel 150 Dynamic Control Active I Cmd 151 Inductance 152 Voltage Loop Voltage Loop Sel 160 DcLink Command 161 Capacitance 162 Utility Drive Memory Param Access Lvl 196 Utility Reset to Defaults 197 Diagnostics Alarm Status 211 Start Inhibit 214 Fault Frequency 220 Fault Amps R 221 Fault Amps S 222 Fault Queue Fault Config 238 Fault Clear 239 Power Up Marker 242 Communication Datalinks Data In A1 300 Communication Data In A2 301 Data In B1 302 Data In B2 303 DPI Status Connect Status 320 DPI Error Out 321 CS Msg Rx Cnt 322 Masks & Owners Logic Mask 340 Start Mask 341 Reactive RateLmt 102 I Imbalance Lmt 103 Low Vac Lmt 112 Low Vac Time 113 Base Temp Alrm 122 Base Temp Trip 123 AC Low Freq Time 132 AC High Freq Lmt 133 CML Bandwidth 153 CML Damping 154 CML Ki 155 VML Bandwidth 163 VML Damping 164 VML Ki 165 Reset Meters 200 Language 201 Fault Amps T 223 Fault Amps Q 224 Fault Amps D 225 Fault Volts RS 226 Fault Volts ST 227 Fault 1 Code 243 Fault 1 Time 244 Fault 2 Code 245 Data In C1 304 Data In C2 305 Data In D1 306 Data In D2 307 CS Msg Tx Cnt 323 CS Timeout Cnt 324 CS Msg Bad Cnt 325 Fault Clr Mask 342 Stop Owner 343 I Imbalance Time 104 Regen I Lmt 105 High Vac Lmt 114 High Vac Time 115 Junct Temp Alrm 124 Junct Temp Trip 125 AC High Freq Time 134 AC Maximum df/dt 135 CML Kp 156 PF Bandwidth 157 Reactive I Lmt 158 VML Kp 166 VML Kf 167 VML Reset Level 168 Drive Checksum 203 Control SW Ver 204 Fault VoltsTR 228 Fault Volts Vdc 229 Fault Base Temp 230 Testpoint 1 Sel 234 Testpoint 1 Data 235 Fault 2 Time 246 Fault 3 Code 247 Fault 3 Time 248 Data Out A1 310 Data Out A2 311 Data Out B1 312 Data Out B2 313 PC Msg Rx Cnt 326 PC Msg Tx Cnt 327 PC Timeout Cnt 328 Start Owner 344 Fault Clr Owner 345 V Imbalance Lmt 116 V Imbalance Time 117 CldPlt Temp Alrm 126 Reactive I Cmd 159 Parallel Config 169 Bus Capacitance 170 Password 205 Testpoint 2 Sel 236 Testpoint 2 Data 237 Fault 4 Code 249 Fault 4 Time 250 Alarm Config 260 Data Out C1 314 Data Out C2 315 Data Out D1 316 Data Out D2 317 CAN Bus Off Cnt 329 Security Port Mask Act 346 Write Mask Cfg 347 Write Mask Act 348 Logic Mask Act 349 Inputs & Outputs Mux ed Temps IGBT NTC Temp1 330 Inputs & Outputs IGBT NTC Temp2 331 IGBT NTC Temp3 332 IGBT NTC Temp4 333 Coldplate Temp1 334 IGBT NTC Temp5 335 IGBT NTC Temp6 336 IGBT NTC Temp7 337 IGBT NTC Temp8 338 Digital Inputs Dig In Status 350 Dig In Frc Mask 351 Dig In Frc Data 352 Digital Outputs Dig Out Status 360 Dig Out Frc Mask 361 Dig Out Frc Data 362 Coldplate Temp2 339 Rockwell Automation Publication 20L-TD001C-EN-P - November

PowerFlex 700L TECHNICAL DATA LIQUID-COOLED ADJUSTABLE FREQUENCY AC DRIVES

PowerFlex 700L TECHNICAL DATA LIQUID-COOLED ADJUSTABLE FREQUENCY AC DRIVES PowerFlex 700L TECHNICAL DATA LIQUID-COOLED ADJUSTABLE FREQUENCY AC DRIVES Table of Contents Description.................................................. Page Product Overview.................................................3

More information

PowerFlex 700L TECHNICAL DATA LIQUID-COOLED ADJUSTABLE FREQUENCY AC DRIVES

PowerFlex 700L TECHNICAL DATA LIQUID-COOLED ADJUSTABLE FREQUENCY AC DRIVES PowerFlex 700L TECHNICAL DATA LIQUID-COOLED ADJUSTABLE FREQUENCY AC DRIVES Table of Contents Description............................................. Page Product Overview...........................................

More information

Technical Data. PowerFlex 700H Adjustable Frequency AC Drive

Technical Data. PowerFlex 700H Adjustable Frequency AC Drive Technical Data PowerFlex 700H Adjustable Frequency AC Drive Table of Contents Topic Page Product Overview.............................................. 3 Key Features and Benefits.......................................

More information

PowerFlex 70 Adjustable Frequency AC Drive

PowerFlex 70 Adjustable Frequency AC Drive Technical Data PowerFlex 70 Adjustable Frequency AC Drive Topic Page Product Overview 2 Catalog Number Explanation 5 Factory Installed Options 7 User Installed Options 8 Installation Considerations 16

More information

PowerFlex Digital DC Drive

PowerFlex Digital DC Drive Technical Data PowerFlex Digital DC Drive Table of Contents Topic Page Additional Resources 3 Product Description 3 Standard Drives Program 4 Catalog Number Explanation 6 Standard Drives Product Selection

More information

PowerFlex 700 Adustable Frequency AC Drive. Technical Data

PowerFlex 700 Adustable Frequency AC Drive. Technical Data PowerFlex 700 Adustable Frequency AC Drive Technical Data Product Overview The PowerFlex 700 AC drive offers outstanding performance in an easy-to-use drive that you have come to expect from Rockwell Automation.

More information

Technical Data. PowerFlex 700 Adjustable Frequency AC Drives

Technical Data. PowerFlex 700 Adjustable Frequency AC Drives Technical Data PowerFlex 700 Adjustable Frequency AC Drives Product Overview PowerFlex 700 Adjustable Frequency AC Drives Technical Data The PowerFlex 700 AC drive offers outstanding performance in an

More information

Selection Guide. PowerFlex Digital DC Drive

Selection Guide. PowerFlex Digital DC Drive Selection Guide PowerFlex Digital DC Drive PowerFlex Digital DC Drive The PowerFlex DC drive combines powerful performance with flexible control to produce a highly functional, cost effective drive and

More information

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors Unidrive M600 High performance drive for induction and sensorless permanent magnet motors 0.75 kw - 2.8 MW Heavy Duty (1.0 hp - 4,200 hp) 200 V 400 V 575 V 690 V Unidrive M600 features Easy click-in keypad

More information

PowerFlex 700 Adjustable Frequency AC Drive

PowerFlex 700 Adjustable Frequency AC Drive Technical Data PowerFlex 700 Adjustable Frequency AC Drive Topic Page Product Overview 2 Certifications and Specifications 7 Design Considerations 12 Drive, Fuse and Circuit Breaker Ratings 24 Cable Recommendations

More information

Unidrive M700 Class leading performance with onboard real-time Ethernet

Unidrive M700 Class leading performance with onboard real-time Ethernet Unidrive M Class leading performance with onboard real-time Ethernet. kw -.8 MW Heavy Duty (. hp -, hp) V V V 9 V Unidrive M features Easy click-in keypad connection Range of multi-language LCD keypads

More information

PowerFlex 700 User Manual Update

PowerFlex 700 User Manual Update DANGER REMOTE SOURCE(S) OF POWER. DISCONNECT ALL SOURCES OF POWER BEFORE OPENING THE DOOR. ENERGY STORAGE CAPACITORS. VERIFY LOW VOLTAGE DISCHARGE BEFORE SERVICING. SEE INSTRUCTION MANUAL. Document Update

More information

PowerFlex 700 Adjustable Frequency AC Drive

PowerFlex 700 Adjustable Frequency AC Drive Technical Data PowerFlex 700 Adjustable Frequency AC Drive Topic Page Product Overview 2 Certifications and Specifications 7 Design Considerations 12 Drive, Fuse and Circuit Breaker Ratings 24 Cable Recommendations

More information

Technical Data. PowerFlex 700S Drives with Phase II Control

Technical Data. PowerFlex 700S Drives with Phase II Control Technical Data PowerFlex 700S Drives with Phase II Control 2 Rockwell Automation Publication 20D-TD002J-EN-P - July 2013 Table of Contents Topic Page Product Overview Below Catalog Number Explanation 10

More information

PowerFlex AC Drives Portfolio

PowerFlex AC Drives Portfolio PowerFlex AC Drives Portfolio PUBLIC INFORMATION 1 Rev 5058-CO900E Copyright 2013 Rockwell Automation, Inc. All Rights Reserved. PUBLIC INFORMATION Copyright 2015 Rockwell Automation, Inc. All Rights Reserved.

More information

PowerFlex 700 Adjustable Frequency AC Drive

PowerFlex 700 Adjustable Frequency AC Drive Technical Data PowerFlex 700 Adjustable Frequency AC Drive Topic Page Product Overview 2 Certifications and Specifications 8 Design Considerations 13 Drive, Fuse and Circuit Breaker Ratings Cable Recommendations

More information

PowerFlex 755T Drive Solutions New Solutions for Low Harmonic, Regenerative & Common Bus Applications

PowerFlex 755T Drive Solutions New Solutions for Low Harmonic, Regenerative & Common Bus Applications PowerFlex 755T Drive Solutions New Solutions for Low Harmonic, Regenerative & Common Bus Applications May 2016 Copyright 2016 Rockwell Automation, Inc. All Rights Reserved. 1 Today s PowerFlex 750-Series

More information

BR Second Position Voltages. AA Fourth Position

BR Second Position Voltages. AA Fourth Position 1336S First Position Bulletin Number BR Second Position Voltage Letter AQ BR CW A B BP BX C Q R RX W Voltages 200-240V AC or 3V DC 380-480VAC or 513-620V DC 500-600V AC or 775V DC or 200-240V AC 380-480V

More information

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP Phoenix DX Sensorless AC Vector Drive 3 HP to 3500 HP Standard Features: * PRECISE CONTROL OF MOTOR SPEED AND TORQUE * BI-DIRECTIONAL FLYCATCHER (CATCH SPINNING MOTOR) * EASY TO USE, SIMPLE SETUP * POWER

More information

These documents contain additional information concerning related products from Rockwell Automation.

These documents contain additional information concerning related products from Rockwell Automation. Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Title PowerFlex 0-Series Drive Installation Instructions PowerFlex 0-Series Programming

More information

These documents contain additional information concerning related products from Rockwell Automation.

These documents contain additional information concerning related products from Rockwell Automation. Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Title PowerFlex 750-Series Drive Installation Instructions PowerFlex 750-Series

More information

Technical Data. PowerFlex 700S High Performance AC Drive

Technical Data. PowerFlex 700S High Performance AC Drive Technical Data PowerFlex 700S High Performance AC PowerFlex 700S AC s Technical Data The Allen-Bradley PowerFlex 700S AC drive, a version of PowerFlex 700 power platform, offers optimized integration for

More information

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications The Reliance Electric LiquiFlo AC drive combines high-performance variable speed drive technology with a patented liquid-cooling

More information

PowerFlex Common Bus Configuration Selection Guide

PowerFlex Common Bus Configuration Selection Guide PowerFlex Common Bus Configuration Selection Guide NOTE: This file is dated May 2017. It replaces the version from April 2017. 2 PowerFlex Common Bus Configuration Selection Guide Common Bus Solutions..................................

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

Drive, Fuse & Circuit Breaker Ratings

Drive, Fuse & Circuit Breaker Ratings Fuses 1, Fuse & Breaker s The tables on the following pages provide drive ratings (including continuous, 1 minute and 3 second) and recommended AC line input fuse and circuit breaker information. Both

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs

Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs Unidrive M400 Fast set-up and diagnostics with real-text display, integrated PLC and safety inputs 0.25 kw - 110 kw (0.33 hp - 150 hp) 100 V 200 V 400 V 575 V 690 V Unidrive M400 features Optional AI-485

More information

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand

More information

High performance Vector Control. Ratings. System configuration

High performance Vector Control. Ratings. System configuration System configuration High performance Vector Control Low harmonic or regenerative drive IP54 full range Compact design and robustness Built-in filter (according to C3 class) Built-in fuses (from 200 kw)

More information

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed

More information

Introduction to Variable Frequency Drives Louisiana User Group August 2018

Introduction to Variable Frequency Drives Louisiana User Group August 2018 Introduction to Variable Frequency Drives Louisiana User Group August 2018 Our presentation will begin at 12:00 pm CDT ReynoldsOnline.com Upcoming Events Users Group Sept 12 th User Group Hazardous Location

More information

CTi Automation - Phone: Fax: Web:

CTi Automation - Phone: Fax: Web: CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net The control & protection you expect in an innovative soft starter design... Flexibility

More information

PowerFlex 700S with Phase II Control

PowerFlex 700S with Phase II Control PowerFlex 700S with Phase II Control TECHNICAL DATA HIGH PERFORMANCE AC DRIVE 2 Table of Contents Description....................................Page Product Description.................................

More information

Drives in Common Bus Configurations with PowerFlex 755TM Bus Supplies

Drives in Common Bus Configurations with PowerFlex 755TM Bus Supplies Application Techniques Original Instructions Drives in Common Bus Configurations with PowerFlex 755TM Bus Supplies Important User Information Read this document and the documents listed in the additional

More information

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 050516 2002 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RL Line/Load Reactors are components

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

PowerFlex 750-Series AC Drives

PowerFlex 750-Series AC Drives Technical Data PowerFlex 7-Series AC Drives Original Instructions Topic Page Additional Resources 2 Product Overview 2 Certifications and Specifications 6 Design Considerations 11 Fuse and Circuit Breaker

More information

1321 Power Conditioning Products

1321 Power Conditioning Products Technical Data 1321 Power Conditioning Products Don t Ignore the Cost of Power Line Disturbance Topic Page Product Overview 2 1321-3R and 3RA Series Line Reactors 3 1321 Reflective Wave Reduction (RWR)

More information

UNIDRIVE M600. Manufacturing Automation drive. High performance drive for induction and sensorless permanent magnet motors

UNIDRIVE M600. Manufacturing Automation drive. High performance drive for induction and sensorless permanent magnet motors UNIDRIVE M600 Manufacturing Automation drive High performance drive for induction and sensorless permanent magnet motors Unidrive M100 Unidrive M200 Unidrive M300 Unidrive M400 Unidrive M600 Unidrive M700

More information

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors Unidrive M600 High performance drive for induction and sensorless permanent magnet motors 0.75 kw - 2.8 MW Heavy Duty (1.0 hp - 4,200 hp) 200 V 400 V 575 V 690 V Unidrive M Optimized throughput, open automation

More information

VFD Best Practices: Getting the Most from Your VFD Investment

VFD Best Practices: Getting the Most from Your VFD Investment TECH TOPICS VFD Best Practices: Getting the Most from Your VFD Investment The purpose of this document is to outline best practices for successful application and installation of VFDs. Following these

More information

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors Unidrive M600 High performance drive for induction and sensorless permanent magnet motors 0.75 kw - 2.8 MW Heavy Duty (1.0 hp - 4,200 hp) 200 V 400 V 575 V 690 V Unidrive M Optimized throughput, open automation

More information

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications LiquiFlo AC Drives A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications The Reliance Electric LiquiFlo AC drive combines high-performance variable speed drive technology with

More information

GS2 Series - Introduction

GS2 Series - Introduction GS2 Series - Introduction GS2 Series Drives Rating Hp.25.5 1 2 3 5 7.5 10 kw 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 Single-Phase 115 Volt Class Single/Three-Phase 230 Volt Class Three-Phase 230 Volt Class Three-Phase

More information

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA Honeywell CORE Drive SPECIFICATION DATA FEATURES APPLICATION The new Honeywell VFD CORE Drive addresses the need to save time for installation, and provides the lower total installed costs with years of

More information

Kinetix 7000 High Power Servo Drives

Kinetix 7000 High Power Servo Drives Kinetix 2000 Slot-filler Module This section contains dimensions and catalog numbers for the 2093-PRF slot-filler module. IMPORTANT The Kinetix 2000 slot-filler module (catalog number 2093-PRF) is compatible

More information

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz Catalog Number Explanation Open Controllers a Bulletin Number Solid-State Controller B H H B B B B B B B B B B B B B Solid-State Controller and Isolation Contactor (enclosed only) b Controller Ratings

More information

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING SineWave Guardian TM 380V 600V INSTALLATION GUIDE FORM: SWG-IG-E REL. October 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of

More information

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Softstarters. Softstarters Type SSM Medium voltage ,800V 1 Medium voltage 2300 13,800V 1 Description Fused disconnect switch with blown fuse indicators and door safety interlocks rated for load break/fault make with automatic grounding arm Inline isolation vacuum

More information

TECHNICAL DATA SHEET KVA UPS Systemss

TECHNICAL DATA SHEET KVA UPS Systemss Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 060628 2006 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n MATRIX FILTER SERIES B 380-415 Volts, 50HZ USER MANUAL PART NO. INSTR - 015 REL. 040709 2003 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter

More information

SINUS PENTA 2T/4T SINUS PENTA 2T/4T

SINUS PENTA 2T/4T SINUS PENTA 2T/4T SINUS PENTA 2T/4T SINUS PENTA 2T/4T Technical Highlights One product, 5 integrated functions - IFD (Inverter Frequency Drive): vector modulation function for general-purpose applications (V/F pattern).

More information

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual User s Manual ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual ii ACH550-CC/CD Packaged Drive with Classic Bypass ACH550 Drive Manuals GENERAL MANUALS ACH550-UH

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090529 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW Line/Load Reactors are components designed to improve the

More information

Delta Products VFD CP2000 Bypass Control Packages.

Delta Products VFD CP2000 Bypass Control Packages. Delta Products VFD CP2000 Bypass Control Packages www.deltaww.com Delta Products VFD CP2000 Bypass Control Packages The Delta Products VFD CP2000 Bypass Control Packages are designed for the Delta Products

More information

ABB standard drives ACS550, Hp

ABB standard drives ACS550, Hp ABB standard drives ACS550, 0.75-550 Hp Technical catalog BUSINESS PROFILE INDUSTRIES PRODUCTS APPLICATIONS EXPERTISE PARTNERS SERVICES Two ways to select your drive Choice 1: Simply contact your local

More information

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL FORM: MX-TRM-E REL. September 2014 REV. 002 2014 MTE Corporation WARNING High Voltage! Only a qualified electrician can carry out the electrical installation

More information

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 120628 REV. 007 2012 MTE Corporation Matrix Series D User s Manual 600VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation

More information

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:

More information

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation MATRIX FILTER SERIES D 600 Volts, 60HZ USER MANUAL PART NO. INSTR 026 REL. 080920 2008 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter is designed for harmonic mitigation

More information

PowerFlex 750-Series AC Drives

PowerFlex 750-Series AC Drives Technical Data PowerFlex 7-Series AC Drives Original Instructions Topic Page Summary of Changes 2 Additional Resources 2 Product Overview 3 Certifications and Specifications 8 Design Considerations 4 Fuse

More information

Datasheet VFD-CP2000. Type number key A B C S -XY VFD 007 CP 43. Option cards. Slot 3

Datasheet VFD-CP2000. Type number key A B C S -XY VFD 007 CP 43. Option cards. Slot 3 Type number key VFD 007 CP 43 Option cards A B C S -XY Y=0: UL open 1: NEMA1 X=0: IP00 2: IP20 Version number: A=Wall mount B=Higher rated current C=Cabinet S=Frame D0 Input voltage 23=230VAC 3φ 43=400VAC

More information

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors Unidrive M600 High performance drive for induction and sensorless permanent magnet motors 0.75 kw - 2.8 MW Heavy Duty (1.0 hp - 4,200 hp) 200 V 400 V 575 V 690 V Unidrive M Optimized throughput, open automation

More information

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 SECTION 1. 600V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 Soft Starters SECTION 2. LIQUID COOLED VFD I 3 Liquid Cooled

More information

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp VS1MX AC Micro Drive 1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp & Controls 115 VAC 230 VAC 230 VAC 460 VAC 1 Phase - 50/60 Hz 1 Phase - 50/60 Hz 3 Phase - 50/60 Hz 3 Phase - 50/60 Hz Applications:

More information

PowerOhm Installation Manual for LG ATV Series Braking Modules

PowerOhm Installation Manual for LG ATV Series Braking Modules PowerOhm Installation Manual for LG ATV Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal

More information

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you

More information

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation MATRIX FILTER SERIES D 480 Volts, 60HZ USER MANUAL PART NO. INSTR 024 REL. 120628 REV. 012 2012 MTE Corporation Matrix Series D User s Manual 480VAC IMPORTANT USER INFORMATION NOTICE The MTE Corporation

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Variable Frequency Drive (VFD) Cable Solutions

Variable Frequency Drive (VFD) Cable Solutions Variable Frequency Drive (VFD) Cable Solutions Be Certain with Belden the Original Developer of High Quality Performance VFD Cable Featured Brand Belden offers the most extensive line of VFD cables, as

More information

GV3000 AC Power Modules HP, V AC

GV3000 AC Power Modules HP, V AC Hardware Reference, Installation, and Troubleshooting Manual D2-3324-2 GV3 AC Power Modules 1-15 HP, 38-46V AC Version 4. Important User Information Solid-state equipment has operational characteristics

More information

Frequently Asked Questions. ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp

Frequently Asked Questions. ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp Copyright 2009, ABB Inc. All Rights Reserved Specifications subject to change without notice Contact ABB Inc, Low Voltage Drives ABB Inc - Low

More information

This manual is to be given to the end user. Optional RFI filter. Drive. Stop. Thermal protection device. Start / Reset +DC.

This manual is to be given to the end user. Optional RFI filter. Drive. Stop. Thermal protection device. Start / Reset +DC. 3943 en - 2013.12 / c Optional RFI filter This manual is to be given to the end user Main contactor power supply Start / Reset Stop Thermal protection device Drive +DC BR Braking resistor DIGIDRIVE SK

More information

MASTERYS IP+ 10 to 80 kva

MASTERYS IP+ 10 to 80 kva MASTERYS IP+ 10 to 80 kva OBJECTIVES The aim of these specifications is to provide: the information required to choose the right uninterruptible power supply for a specific application. the information

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

Chapter 1: Getting Started User Manual Overview...1 2

Chapter 1: Getting Started User Manual Overview...1 2 Getting Started Chapter 1 Table of Contents Chapter 1: Getting Started User Manual Overview.........................................1 2 Overview of this Publication.........................................

More information

Size for Size Best Value in the Industry

Size for Size Best Value in the Industry Size for Size Best Value in the Industry Overview for SMC -Flex and SMC -3 Soft ers 3...480A 200-460VAC...500-575VAC www.klinkmann.com Allen-Bradley Smart Motor Controllers... Providing Unmatched Intelligent

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Variable Frequency AC Motor Drive Units

Variable Frequency AC Motor Drive Units 14 Variable Frequency A Motor Drive Units ulletin 2162T and 2163T PowerFlex 40 Drive................................................. 171 These combination variable frequency A motor drive units are specifically

More information

LOW VOLTAGE WIND CONVERTERS. ABB wind turbine converters ACS880, 800 kw to 8 MW

LOW VOLTAGE WIND CONVERTERS. ABB wind turbine converters ACS880, 800 kw to 8 MW LOW VOLTAGE WIND CONVERTERS ABB wind turbine converters ACS880, 800 kw to 8 MW 2 ABB WIND CONVERTERS, ACS880 WIND TURBINE CONVERTERS ACS880 wind turbine converter Flexible solution The ACS880 converter

More information

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation M T E C o r p o r a t i o n MTE Series RL Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL. 060227 2006 MTE Corporation Important User Information NOTICE MTE Series RL Line/Load Reactors are components

More information

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings

More information

AC Line / Load Reactors

AC Line / Load Reactors AC Line / Load Reactors Table of Contents Delivery / Lead Time.PB03-1100 -2 Selection & Pricing PB03-1100 -4 Replacement Parts..PB03-1100-8 Product Modifications / Options..PB03-1100 -9 Product Specifications..PB03-1100

More information

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives. SECTION 230513 - MOTORS AND ADJUSTABLE SPEED DRIVES PART 1 - GENERAL 1.1 DESCRIPTION A. Provide labor, materials, equipment and services as required for the complete installation designed in Contract Documents.

More information

MATRIX FILTER USER MANUAL. SERIES D 400 Volts, 50HZ PART NO. INSTR 025 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 400 Volts, 50HZ PART NO. INSTR 025 REL REV MTE Corporation MATRIX FILTER SERIES D 400 Volts, 50HZ USER MANUAL PART NO. INSTR 025 REL. 110624 REV. 006 2011 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation Matrix Filter is designed for harmonic

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS WARNING: WARNING: www.altronicinc.com DEVIATION DEVIATION FROM THESE FROM INSTRUCTIONS THESE INSTRUCTIONS MAY LEAD MAY TO LEAD IMPROPER TO IMPROPER OP- ERATION OF ENGINE THE MACHINE

More information

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool

SD700FR. Regenerative Active Front End VARIABLE SPEED DRIVES POWER ELECTRONICS / SD700 SERIES 4 QUADRANT. icool FR VARIABLE SPEED DRIVES Regenerative Active Front End icool 4 QUADRANT POWER ELECTRONICS / SD700 SERIES FR SD700FR SERIES goes one step ahead keeping the family unique characteristics. Based on the latest

More information

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible

More information

ROBICON W120 enclosed drive

ROBICON W120 enclosed drive SINAMICS Drives ROBICON W120 enclosed drive 1 HP to 200 HP Introduction This technical data sheet provides a short overview of the most important characteristics of the ROBICON W120 enclosed standard 6-pulse

More information

SECTION VARIABLE FREQUENCY DRIVE UNITS

SECTION VARIABLE FREQUENCY DRIVE UNITS SECTION 26 29 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. General: The CONTRACTOR shall provide variable frequency drive (VFD) units, complete and operable, in accordance with the Contract Documents. It

More information

Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTP. Catalog. Edition 03/ / EN

Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTP. Catalog. Edition 03/ / EN Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTP Edition 03/2009 Catalog 16798015 / EN SEW-EURODRIVE Driving the world 1 Important Notes... 4 1.1 Structure of the safety

More information

ALTIVAR 58 AC Drives

ALTIVAR 58 AC Drives Class 8806 / 8839 / 8998 CONTENTS Schneider Electric Brands Page ALTIVAR 58 AC Drives............................................... 3 Drives Overview...................................................

More information

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible

More information

DPP/3DPP. Digital ProcessPower UPS INDUSTRIAL PWM UNINTERRUPTIBLE POWER SUPPLY SYSTEM SINGLE PHASE THREE PHASE

DPP/3DPP. Digital ProcessPower UPS INDUSTRIAL PWM UNINTERRUPTIBLE POWER SUPPLY SYSTEM SINGLE PHASE THREE PHASE DPP/DPP Digital Process INDUSTRIAL PWM UNINTERRUPTIBLE POWER SUPPLY SYSTEM SINGLE PHASE THREE PHASE PROVIDING CONTINUITY OF ELECTRICAL POWER DPP/DPP DIGITAL PROCESS POWER Industrial Pulse Width Modulated

More information

Hp V AC Current Rating [A] 230V AC 60 Hz

Hp V AC Current Rating [A] 230V AC 60 Hz Product Selection/Options Open Type Controllers Up to V AC kw Hp V AC Current Rating [A] V AC Hz V AC Hz V AC Hz V AC Hz V AC Hz / Hz Control V AC/DC Control.. -BNBD -BNBR. -BNBD -BNBR -BNBD -BNBR -BNBD

More information

SINAMICS GM150 IGCT version

SINAMICS GM150 IGCT version /2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /14 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions

More information

CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies

CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies Selection Checklist CENTERLINE 2500 Low Voltage Motor Control Centers and Switchgear Assemblies Use this checklist to help you configure your CENTERLINE 2500 Motor Control Center. You can type in the fields

More information