Utility Task Force Corrosion Pictures for IEEE C Fall 2018 & Submersible Transformer Galvanic Application Compatibility Chart (STGACC):
|
|
- Leonard Daniel
- 5 years ago
- Views:
Transcription
1 Utility Task Force Corrosion Pictures for IEEE C Fall 2018 & Submersible Transformer Galvanic Application Compatibility Chart (STGACC): This report contains pictures of underground submersible transformer CTQ (Critical to Quality) components that are exposed to galvanic corrosion whereby causing possible water or chemical entry into an oil filled transformer s compartment via bolted flanges and handhole covers or screwed on fitting via taper pipe threads e.g. thermal wells, drain valves, tap changer covers etc. Equipment: 1 ph submersible Issue: Rusted holding clamp bolt Manufactured: 2010 (in service 5 years) : mild steel is the hardware silicon bronze, zinc plated, or stainless for bolt, washer, and nut Suggestion: Use 300 series stainless bolts and washers with 400 series nuts to prevent galling and galvanic corrosion for bolted bushings in service less 10 years Glen Falls NY Issue: Rusted tap changer pipe with bronze cap seized Manufactured: 2002 : tap changer head s threads are carbon steel, and cover is silicon bronze Equipment: 1-ph submersible Issue: Rusted bushing holding clamp and bolts cover protruding Manufactured: 2010 (in service 5 years) : mild steel is the hardware silicon bronze or stainless or both or are the bolts welded stainless or mild steel protruding from cover with stainless or silicon bronze hardware attached Suggestion: Use 300 series stainless tap changer head (refer to galvanic chart below for either being passive or active application) with silicon bronze cap or carbon steel tap changer head with 304 stainless caps Welded tap changer head should not corrode before cap Suggestion: Use 300 series stainless bolts and washers with 400 series nuts to prevent galling and galvanic corrosion for bolted bushings
2 Issue: Rusted pipe flange threads, silicon bronze sampler seized Manufactured: 2002 : pipe flange is carbon steel, sampler is silicon bronze stainless pipe plug on carbon steel pipe flange and Teflon tape barrier Issue: Rusted pipe flange threads, silicon bronze sampler seized Manufactured: Pending : pipe flange is carbon steel, sampler is silicon bronze stainless pipe plug on carbon steel pipe flange with Teflon tape barrier between different metals welded flange should not corrode before fitting and or sampling device service since for past 10 years see good example below Issue: Rusted pipe flange threads, sensor seized Manufactured: Pending : pipe flange is carbon steel, sensor is stainless is the sensor 316 or 304 refer to galvanic chart stainless pipe plug on carbon steel pipe flange flange should not corrode before sampling device in service since for past 10 years same as above
3 Issue: Rusted carbon steel pad for decal plate Manufactured: Pending : pad is carbon steel, plate decal is silicon bronze Suggestion: Use 300 series stainless plate decal and screw being of same material (refer to galvanic chart below for either being passive or active application) Issue: Rusted pipe nipple where drain valve is installed Manufactured: Pending : pipe nipple is carbon steel, drain valve is silicon bronze Issue: Rusted nipple where drain valve is installed Manufactured: 2013 Application: Sludge/High Polluted : pipe nipple is carbon steel, drain valve and pipe plug is silicon bronze Issue: Galvanic corrosion all over tank and cover + leaking drain valve drain valve is brass (or equivalent), had leaks at the fitting with the tank or the pipe between the 2. Drain valve eliminated since few years and replaced with a plug on top of cover Manufactured: 8 years in service; primer with powder top coat and Devtar (asphalt) on bottom of tank about 1 foot high Installed: Canada Northeast Removed: N/A Application: dry vaults or with little drainage water but many covered with water for some time stainless globe valve on carbon steel pipe flange (refer to galvanic chart below for either being passive or active application) and silicon bronze globe valve on stainless steel pipe nipple should not have corroded before valve no tank welded components should corrode first. stainless globe valve on carbon steel pipe flange and silicon bronze globe valve on stainless steel pipe nipple should not have corroded before valve no tank welded components should corrode first. Suggestion: Use some epoxy coatings with zinc rich primer which are superior for underground applications. Use 304 stainless globe valve on carbon steel pipe flange and silicon bronze globe valve on stainless steel (continues next page)
4 : copper bearing steel tank and cover; no external accessories such as PRV, sight gage, thermometer; surrounded with bare copper grounding wire which accelerate galvanic corrosion on the tank Was the water in the vault stagnant and/or salty? What are the effects of Devtar (asphalt) in an aqueous salty solution does it affect the PH accelerating other types of corrosion e.g. pitting, chemical, bacterial, etc. Issue: Rust or other corrosion showing where the terminals were bolted to tin plated neutral Manufactured: 2013 Installed: 2013 : tin plated copper neutral was the connecting terminal tin plated Issue: None: No Rust showing where terminal was bolted to tin plated neutral Manufactured: 2015 Installed: 2016 : tin plated copper neutral, shows a tin plated 2-hole terminal lead
5 Issue: Rusted pipe flange threads, pipe plug possibly seized Manufactured: 2009 Installed: 2009 : pipe flange is carbon steel, pipe plug is silicon bronze stainless pipe plug on carbon steel pipe flange tank welded flange should not corrode before sampling device Equipment: 1-ph submersible Issue: None: No galvanic corrosion where dissimilar metals touching; only rusting at tank bottom Manufactured: 2009; powder coat Installed: Fossil Creek, Colorado ; no maintenance Application: Salt Water chloride : tank material mild steel with welded stainless nut provision and tin-plated bronze terminal; fitting barrier Teflon tape Equipment: 1-ph submersible Issue: Same as 1024 Fossil Creek only rusting at tank bottom Manufactured: 2001; powder coat Installed: Autumn Ridge, Colorado Removed: 2012; no maintenance Application: Salt Water chloride : tank material mild steel; unsure if fitting had Teflon tape as a barrier Equipment: 1-ph submersible Issue: None: No galvanic corrosion where dissimilar metals touching Manufactured: 1992; powder coat Installed: Alameda St. Colorado ; no maintenance Application: Salt Water : tank material mild steel with welded stainless nut provision and tin-plated bronze terminal; fitting barrier Teflon tape Perfect Recommendation: if user wants to continue to use bronze valves, terminals, etc. and/or there s no stainless version of those terminals or components that exist on the market. A copper bearing steel tank with welded stainless provision and tin-plated bronze terminals all having fitting barriers with Teflon tape Perfect Recommendation: if user wants to continue to use bronze valves, terminals, etc. and/or there s no stainless version of those terminals or components that exist on the market. A copper bearing steel tank with welded stainless provision and tin-plated bronze terminals all having fitting barriers with Teflon tape
6 Issue: Rust showing where terminals were bolted to neutral Manufactured: 2009 Installed: 2009 : copper neutral Was the neutral blade tin plated, was the connecting terminal tin plated, and what type of hardware was used Issue: Sever pitting of the temperature gauge s aluminum housing Manufactured: 2009 Installed: 2013 : Aluminum housing with stainless steel screws on faceplate with brass/silicon bronze or brass thermal well as part of assembly; thermal well screwed into welded steel tank pipe flange. Suggestion: Use stainless housing with stainless thermal well instead of aluminum with silicon bronze or brass thermal well screwing onto carbon steel tank pipe flange Issue: paint degradation flaking of the temperature gauge aluminum housing; severe rusting around pipe flange Manufactured: 2000 Installed: 2002 : Aluminum housing with stainless steel screws on faceplate with brass/silicon bronze or brass thermal well as part of assembly; thermal well screwed into welded steel tank pipe flange. Suggestion: Use stainless housing with stainless thermal well instead of aluminum with silicon bronze or brass thermal well screwing onto carbon steel tank pipe flange
7 Issue: Rusted pipe flange threads, pipe plug and sampler possibly seized Manufactured: 2001 Installed: 2002 : pipe flanges are carbon steel; pipe plug and sampler are silicon bronze stainless pipe plug on carbon steel pipe flange tank welded flange should not corrode before sampling device Issue: Sever pitting of the temperature gauge aluminum housing Manufactured: 2013 Installed: 2013 Application: Sludge/High Polluted : Aluminum housing with stainless steel screws on faceplate with brass/silicon bronze or brass thermal well as part of assembly; thermal well screwed into welded steel tank pipe flange. Suggestion: Use stainless housing with stainless thermal well instead of aluminum with silicon bronze or brass thermal well screwing onto carbon steel tank pipe flange
8 Issue: Sever pitting of the temperature gauge aluminum housing Manufactured: 2015 Installed: 2015 Application: Sludge/High Polluted : Aluminum housing with stainless steel screws on faceplate with brass/silicon bronze or brass thermal well as part of assembly; thermal well screwed into welded steel tank pipe flange Suggestion: Use stainless housing with stainless thermal well instead of aluminum with silicon bronze or brass thermal well screwing onto carbon steel tank pipe flange Issue: Rusted parking stands near hardware connection, bolts possibly seized Manufactured: 2009 Installed: 2009 Application: Sludge/High Polluted : parking stands are carbon steel; is the hardware silicon bronze, zinc plated, 316, or 304 stainless washers and bolts with 400 series nuts instead of zinc plated steel or silicon bronze on carbon steel Issue: Rusted parking stands near hardware connection, bolts possibly seized Manufactured: 2012 Application: Sludge/High Polluted : parking stands are carbon steel; is the hardware silicon bronze, zinc plated, 316, or 304 stainless washers and bolts with 400 series nuts instead of zinc plated steel or silicon bronze on carbon steel
9 Issue: Rusted ground flange assembly with bronze padlock, handle, lever, and shaft Manufactured: 2006 Installed: 2006 Application: Sludge/High Polluted : grounding welded assembly is carbon steel; padlock, lever, and shaft are bronze Suggestion: Use stainless ground flange assembly instead of carbon steel when paring with silicon bronze padlock, lever, and shaft (refer to galvanic chart below for either being passive or active application) Corrosion on tank below Devtar line. Corrosion on cooling radiator fin below Devtar line Equipment: 167kVA submersible Issue: drain valve is brass (or equivalent), had leaks at the fitting with the tank or the pipe between the 2. Drain valve eliminated since few years and replaced with a plug on top of cover Manufactured: 2004; e-coat and Devtar (asphalt) on bottom tank about 1 foot high Installed: Canada Northeast Removed: 2009 Application: dry vaults or with little drainage water but many covered with water for some time : copper bearing steel tank and cover; no external accessories such as PRV, sight gage, thermometer; surrounded with bare copper grounding wire which accelerate galvanic corrosion on the tank Was the water in the vault stagnant and/or salty? What are the effects of Devtar (asphalt) in an aqueous salty solution does it affect the PH accelerating other types of corrosion e.g. pitting, chemical, bacterial, etc. Suggestion: Suggestion: Use some epoxy coatings with zinc rich primer which are superior for underground applications No corrosion at tank grounding pad.
10 Issue: galvanic corrosion where dissimilar metals touching silicon bronze or brass thermal well screw into welded steel pipe flange Manufactured: 2005; 3mils of zincrich primer with 3mils of black epoxy finish top coat Installed: Boston, Massachusetts Northeast Removed: 2017 : tank flange material steel with silicon bronze or brass thermal well, padlock, pipe plug, and drain valve Suggestion: if user wants to continue to use bronze valves, terminals, etc. and/or there s no stainless version of those terminals or component that exist on the market. A copper bearing steel tank with welded stainless provision and tin-plated bronze terminals all having fitting barriers Teflon tape Another suggestion maybe thermal well, padlock, pipe plug, and drain valve being 304 stainless on welded steel pipe flange and nipple Issue: slight galvanic corrosion where dissimilar metals touching on parking stands Manufactured: 2005; 3mils of zincrich primer with 3mils of black epoxy finish top coat Installed: New England Northeast Removed: 2017 : tank material copper bearing steel
11 Issue: None: No rust around stainless bolt and washer in carbon steel cover weld nut Manufactured: 2013 Application: Not Coastal : carbon steel welded nut, bolt and washer hardware are stainless is the hardware 316 or 304 Issue: None: No rust around stainless bolt and washer in carbon steel cover weld nut Manufactured: 2006 Application: Not Coastal, ATL : pipe flange is carbon steel, bolt and washer hardware are stainless is the hardware 316 or 304 Issue: slight rust on tap changer threads having bronze cap Manufactured: 2006 Application: Not Coastal, ATL : what are the tap changer thread s material if stainless, was it cleaned or brushed with carbon steel Issue: Rusted network protector Manufactured: This one was in service at 2 locations in For the second installation, the last 10 years Application: in Providence Rhode Island at a transit station; sidewalk area that is typically heavily treated with salt in the winter time for foot traffic. : protector is carbon steel what are the paint requirements and did heating escalate the galvanic corrosion process Suggestion: Did protector have adequate radiation needed for the protector housing ensure test data was provided along with paint maps; temperature can accelerate galvanic corrosion Use some epoxy coatings with zinc rich primer which are superior for underground applications.
12 Submersible Transformer Galvanic Application Compatibility Chart (STGACC) Tank Misc. External Hardware (e.g. Bolts, nuts, washers) Valves and Gauges Screw on Fittings Plugs and Caps Bushing Flanges Parking Stands Copper Bearing Steel (Low Alloy Steel) (.35V) Tank will 304 (.55V) & 316 (.58V) (.35V) Tank will 304 (.55V) & 316 (.58V) (.35V) Tank will 304 (.55V) & 316 (.58V) (.35V) Tank will 304 (.55V) & 316 (.58V) 316 (.23V) Tank will 304 (.55V) & 316 (.58V) Tank will Same as Tank 304 (.13V) (stagnant 304 (.13V) (stagnant 304 (.13V) (stagnant 304 (.13V) (stagnant 304 (.13V) (stagnant (.2V) External Hardware will Threshold Not- (.2V) Valves and Gauges will Threshold Not- (.2V) Screw on Fittings will Threshold Not- (.2V) Plug and Caps will Threshold Not- 316 (.32V) Flange will 304 (Passive) (.42V) (stagnant External Hardware will (.42V) (stagnant Valves and Gauges will (.42V) (stagnant Screw on Fittings will (.42V) (stagnant Plug and Caps will corrode Not- 304 (OV) same as tank material Same as Tank 430 (.17V) 430 (.17V) 430 (.17V) 430 (.17V) 316 (.03V)
13 (.22V) Tank will (.22V) Tank will (.22V) Tank will (.22V) Tank will 316 (.45V) Tank will 304 (stagnant (.25V) Non- Tank will (.25V) Non- Tank will (.25V) Non- Tank will (.25V) Non- Tank will 304 (OV) same as tank material (stagnant Same as Tank 430 (0V) 430 (0V) 430 (0V) 430 (0V) 316 (.1V) 316 (Passive) (.23V) External Hardware will (.45V) (stagnant External Hardware will 430 (.2V) External Hardware will Threshold Not- (.23V) Valves and Gauges will (.45V) (stagnant Valves and Gauges will 430 (.2V) Valves and Gauges will Threshold Not- (.23V) Screw on Fittings will (.45V) (stagnant Screw on Fittings will 430 (.2V) Screw on Fittings will Threshold Not- (.23V) Plug and Caps will (.45V) (stagnant Plug and Caps will corrode Not- 430 (.2V) Plug and Caps will corrode Maybe Threshold Not- 304 (.45V) Flange will 316 (OV) same as tank material 304 (.03V) Same as Tank
14 316 (stagnant (.12V) (.15V) Non- 430 (.1V) (.12V) (.15V) Non- 430 (.1V) (.12V) (.15V) Non- 430 (.1V) (.12V) (.15V) Non- 430 (.1V) 304 (.32V) Tank will 316 (OV) same as tank material (stagnant 304 (.1V) Same as Tank 409 Non- (Passive) (.02V) 304 (.22V) & 316 (.25V) 304 (.2V) & 316 (.1V) External Hardware will Threshold Not (.02V) 304 (.22V) & 316 (.25V) 304 (.2V) & 316 (.1V) Valves and Gauges will Threshold Not (.02V) 304 (.22V) & 316 (.25V) 304 (.2V) & 316 (.1V) Screw on Fittings will Threshold Not (.02V) 304 (.22V) & 316 (.25V) 304 (.2V) & 316 (.1V) Plug and Caps will Threshold Not 409 (OV) same as tank material Non- 304 (.2V) & 316 (.1V) Flange will Threshold Not Same as Tank
15 409 (stagnant (.22V) Tank will 304 (.42V) & 316 (.45V) 304 (0V) & 316 (.1V) (.22V) Tank will 304 (.42V) & 316 (.45V) 304 (0V) & 316 (.1V) (.22V) Tank will 304 (.42V) & 316 (.45V) 304 (0V) & 316 (.1V) (.22V) Tank will 304 (.42V) & 316 (.45V) 304 (0V) & 316 (.1V) 409 (OV) same as tank material (stagnant 304 (0V) & 316 (.1V) Same as Tank Copper Bearing Steel (Low Alloy Steel) ~ -.63 ~ ~ ~ ~ ~ ~ ~ ~ ~ -.4 Reference:
16 Below shows the galvanic series measured in seawater for some common metals and alloys. When two metals are further apart in the list (e.g. a larger difference between the two numbers), the driving force for galvanic corrosion is increased. The most anodic (active) metals are at the top and most cathodic (noble) at the bottom. Both solid and hollow bars are shown for the stainless steels. The hollow bars represent actively corroding stainless steel, which has a different potential then passive (not corroding) stainless steel. In most applications, where dissimilar metals are combined, the passive (solid) bar should be used to determine the position of the stainless steel.
17
Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer
Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer This document contains sample specifications for Liquid-Filled Type Drive Transformers You may
More informationFloor Doors. Babcock-Davis Always right there.
Babcock-Davis Babcock-Davis floor, vault, and sidewalk doors provide reliable and safe access below ground and between building floors. With Babcock-Davis, we build our services around your specified needs.
More informationFord Brass Saddles Style 101B and 202B
101B Ford Brass Saddles 101B and 202B 101B, 3/4" and 1" Taps 202B, 3/4" through 2" Taps Specifications Body - 85-5-5-5 brass alloy as per ASTM B62, ASTM B584 and AW WA C800. Threads may be FIP, AW WA,
More information1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled
1500 kva Pad Mount Transformer - 24940GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled Part #: MT-PMO-3P-24940GRDY.14400-1500KVA-208Y.120-N3R Page: 1 The MT-PMO-3P-24940GRDY.14400-1500KVA-208Y.120-N3R
More informationSECTION PADMOUNT TRANSFORMER - OIL FILLED
SECTION 26 12 19.01 PADMOUNT TRANSFORMER - OIL FILLED PART 1 GENERAL 1.1 DESCRIPTION: Padmount Transformers and Insulating Oil with underground primary and secondary connections for use in distribution
More informationW91/W94 Series TEMPERATURE REGULATORS. Self-Operated Temperature Regulators. Design & Operation W91 Non-Indicating W94 Dial Thermometer
Design & Operation W91 Non-Indicating W94 Dial Thermometer Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company CAPILLARY
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More informationSTP887-EB/Mar Index. Subject
STP887-EB/Mar. 1986 A Subject Additives See also Inhibitors in antifreezes, 3, 78, 189, 249 depletion factors, 194 in diesel engine coolants, 189 organic, 3 Alloys A 03190 aluminum, 113, 256 AA3000 series,
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More information500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled
500 kva Pad Mount Transformer - 12470V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled Part #: MT-PDO-SS-3P-12.47KV-500KVA-208Y.120-FR3-CU Page: 1 The MT-PDO-SS-3P-12.47KV-500KVA-208Y.120-FR3-CU
More informationCartridge Filter Housings Nowata A Series
Cartridge Filter Housings Nowata A Series Customization May Change the Model Number Designation to B, D or F Series 1. Introduction All A series cartridge filter housings are designed for efficient liquid
More informationSECTION SWING CHECK VALVES
PART 1 GENERAL 1.1 DESCRIPTION This section includes materials, testing, and installation of swing check valves as shown in the Drawings and specified herein, in accordance with the requirements of the
More information25 kv Apparatus Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More information15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch
Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and
More informationA N Fittings versus JI C Fittings
A N Fittings versus JI C Fittings A N Fittings : AN fittings are a flare fitting, using 37 flared tubing to form a metal-metal seal. The A N thread is a particular type of fitting used to connect flexible
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic
More informationOperation and Maintenance. S100 Series Centrifugal Fire Pumps. Table of Contents. Visit us at F /22/02 6/21/18
S100 Series Centrifugal Fire Pumps Operation and Maintenance Form No. F-1031 Section 2117 Issue Date 02/22/02 Rev. Date 6/21/18 Table of Contents Safety Information-----------------------------------------------
More informationINSTALLATION INSTRUCTIONS For Model 855 Wolo Express TM
INSTALLATION INSTRUCTIONS For Model 855 Wolo Express TM 12-Volt Train Horn Your purchase of a WOLO EXPRESS TRAIN HORN is the choice that will complement your vehicle. Wolo s products are manufactured with
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationLoad Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount
Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA 5321-100 Technical Guide Nut Mount Weld Mount General Description The ABB Type LBOR-II switch is a manually operated, two position, load make
More informationTGK Prefabricated Substation Technical Data
TGK Prefabricated Substation Technical Data Ref Item Data 1 General Technical 1.1 Frequency (Hz) 50 1.2 Transformer Rating (kva) 315/750 1.3 Transformer Primary Voltage (kv) 11 1.4 Transformer Secondary
More informationSECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems.
SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS A. Section 099000
More informationProduct Specifications for Phase Over Phase GOABS(r)
1. General a) This specification covers the design, manufacture, and shipment of phase-over-phase, 1-way, 2-way, 3-way, and 4-way, gang-operated disconnecting switches, both air-break and load-break, for
More information35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 35 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,
More informationProduct Catalog. Rev. 612 r1
Product Catalog Rev. 612 r1 PIPE FITTINGS CONDUIT FITTINGS PRODUCT CATALOG Pipe Nipples Welded and Seamless Carbon Steel 2 Pipe Nipples Welded and Seamless Stainless Steel 3 Pipe Nipples End Finishes 4
More informationH1 H2 H3 X0 X1 X2 X3
H0 H H H H0 H H H X0 X X X X0 X X X S- S- S- S- FB H0 H H H X0 X X X H0 H H H X0 X X X 7 NOTES:. ITEMS REMOVED FOR SHIPMENT. TANK DESIGNED FOR FULL VACUUM. MANUFACTURED IN ACCORDANCE WITH ANSI
More informationSPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.
City of Cartersville Electric System P.O. Box 1390 320 S. Erwin St. Cartersville, GA 30120 770-387-5631 March 2006 SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS This specification provides standardization
More informationRemote Oil Filter Mount with Integrated Thermostat
Remote Oil Filter Mount with Integrated Thermostat Part No. ENV-170 Made in USA Important: Read these instructions in their entirety prior to installation. Rev 170922 Parts List ITEM QUANTITY PART # DESCRIPTION
More information35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Equipment Connection Bus Bar, or Grounded Metal Equipment Plate F Series Mounting Holes ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric
More informationNEW Solutions for Underground System Growth
NEW Solutions for Underground System Growth Cooper s Single-Phase Voltage Regulator Improved Power Quality More Economical Improved System Reliability Increased Safety Better Aesthetics Lower Maintenance
More informationLoadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.
3 Loadbreak Elbows 200 Amp 5-15 kv Industrial pg. 252 Loadbreak Elbows 200 Amp 25 kv Industrial pg. 254 Loadbreak Elbows 200 Amp Industrial pg. 255 Loadbreak Elbows Accessories 3 Loadbreak Elbows 3M 200
More informationInstructions for Installation, Operation Care and Maintenance
Model A Dry Pipe Valve Bulletin 353 Rev.K Bulletin 353 Rev.K Instructions for Installation, Operation Care and Maintenance 2 1 2 (65mm) Valve With Model A Trim Listed by Underwriters Laboratories, Inc.
More informationwww. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE
r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum
More informationProduct Specifications for Aluminum Vertical Break Switches
1. General a) This specification covers the design, manufacture, and shipment of aluminum vertical break switches, both air-break and load-break configurations, for substation and transmission switching
More information35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 35 kv Separable Insulated Connector (elbow) Bus Bar or Other Component Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other
More information15100 VALVES. E. Section Building Automation and Control System Guidelines
15100 VALVES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 15050 Basic Material and Methods B. Section 15545 Chilled Water System C. Section 15550 Heat Generation D. Section 15790 Coils E. Section 15955
More informationLONG TERM LIFE CYCLE EVALUATION OF TAYLOR DEVICES PRODUCTS
15 JANUARY 1993 REV 20 JANUARY 2000 REV 7 JULY 2017 LONG TERM LIFE CYCLE EVALUATION OF TAYLOR DEVICES PRODUCTS The purpose of this report is to study the long-term effect of environmental influences of
More informationProudly Made In America
Proudly Made In America VanTran Introduction VanTran Industries, Inc. is a manufacturer of liquid-filled transformers for the industrial, commercial, solar, and utility markets. We are known for engineering
More informationXeteX, Inc. All Rights Reserved.
Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular
More informationMETHOD OF TEST FOR DETERMINATION OF CATHODIC DISBONDMENT OF EPOXY-COATED REINFORCING BARS
Laboratory Testing Manual Date: 97 08 01 Page 1 of 5 METHOD OF TEST FOR DETERMINATION OF CATHODIC DISBONDMENT OF EPOXY-COATED REINFORCING BARS 1. SCOPE 1.1 This test method determines the resistance to
More informationGENERAL INFORMATION 1 B MAINTENANCE
GENERAL INFORMATION 1 B MAINTENANCE Table of Contents Page Maintenance Schedules................... 1B-1 Maintenance Intervals.................. 1B-1 Scheduled Maintenance That Can Be Performed By Owner/Operator.........
More information25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp
Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 15 kv or 25 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic
More informationPSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.
Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Sizes are available for all shielded cables in voltage classes from 15kV through 46kV.
More information15 kv and 25 kv Thru-Bushings
Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation
More information35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses
Page 1 2016 EPMR-35-311S-R2/ESW-CM9 Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton s CPS LRTPs 50 Amp (Max) 27 kv Clip-Mounted NX Fuse Provisions 21.1/36.6 kv Grounded Wye Max Design, 150 kv
More informationClay & Bailey Mfg. Co.
Clay & Bailey Mfg. Co. OIL EQUIPMENT PRICE LIST 2015 Effective: February 9, 2015 Applicable for Aboveground Storage Tank Equipment Underground Storage Tank Equipment Service Station Equipment D. O. T.
More information15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor
ulletin Page 1 2015 Cross-kinked roof prevents standing moisture Metering Transformer compartment label is visible with doors closed Heavy duty 11-gauge steel enclosure is all-welded construction for long
More informationClimas y Proyectos Leyco, S.A. de C.V.
GENERAL DESCRIPTION : FURNISH AND INSTALL MULTI COMPONENT ROOF MOUNTED LEYCO, MODEL CAH CUSTOM AIR HANDLER MADE SELF-CONTAINED, WEATHER RESISTANT, AIR HANDLING UNITS PER MODEL NUMBER, AND PERFORMANCE DATA
More informationSECTION VALVES
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections:
More informationPipe Size Pipe OD TwinSeal Hinged Design for IPS PVC Pipe MODEL 3402 BRONZE SADDLE FOR COPPER TUBING
MULTIPLIER SERVICE SADDLES MODEL 3401 BRONZE SADDLE FOR IPS PVC BODY CASTINGS: Waterworks Bronze (85-5-5-5) per ASTM B584 and AWWA C800. FASTENERS: Silicon Bronze per ASTM B98. GASKET: Patented SBR TwinSeal
More informationACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE
ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE hvgrid-tech designs and manufactures high voltage cable accessories for all types of cable systems, ranging from 69 kv to
More informationClay & Bailey Mfg. Co.
Clay & Bailey Mfg. Co. OIL EQUIPMENT PRICE LIST 2018 Effective: June 1, 2018 Applicable for Aboveground Storage Tank Equipment Underground Storage Tank Equipment Service Station Equipment D. O. T. Manholes
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationPipe Repair Products. A complete selection for all types of pipe
Pipe Repair Products A complete selection for all types of pipe Mueller Service Saddles Manufactured and tested in accordance with ANSI/AWWA C800 & NSF 61 certified. Mueller service saddles, available
More informationFord Service Saddles and Tapping Sleeves
DQS Inc. Section AA 09/2017 THE FORD METER BOX COMPANY, INC. CERTIFIED TO ISO 9001:2015 10004466 Ford Service Saddles and Tapping Sleeves Contents Recommended Product Application *Steel *C900/909*** Cast
More informationHIGH VELOCITY PUMP PUMP END
HIGH VELOCITY PUMP USFP pumps are designed for firefighting and high volume water supply in industrial, oil and gas, nuclear, municipal, and marine applications. The USFP High Velocity Pump is designed
More informationThe SWL Series Swing Check Valves Meets AWWA C Standards (Full Waterway) Accepts Air Cushions Cost-effective Swing Check Valve Solution
The Series Meets AWWA C-508-01 Standards (Full Waterway) Accepts Air Cushions Cost-effective Swing Check Valve Solution Crispin Since 1905 Crispin Multiplex Manufacturing Co. 600 Fowler Avenue Berwick,
More informationSection One. Steel Underground. PVC Accessories Bolt-on Dresser Fittings Solvent PVC Pipe Fittings Gasketed PVC Pipe Fittings
Page Steel Underground Section One Powder Coated Steel Fittings Galvanized Steel Fittings PVC Fittings Riser Valves Clampon Saddles, Couplers, Male Ends Repair Couplers PVC Accessories Bolton Dresser Fittings
More informationEmergency Response Kit (ERK) B-240/B-243 Series. Instructional Manual. P/N: B-240/B-243, Rev. 0
P/N: Issue Date: March 27, 2017 Supersedes: N/A Emergency Response Kit (ERK) B-240/B-243 Series Instructional Manual Visit www.midlandmfg.com for latest manual revision and revision history. Table of Contents
More informationmh-valve.com 129 HYDRANT AWWA C502 NSF 61/372 CERTIFIED UL LISTED FM APPROVED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY
mh-valve.com 129 HYDRANT AWWA C502 NSF 61/372 CERTIFIED UL LISTED FM APPROVED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY 129 HYDRANT YESTERDAY, TODAY, & TOMORROW For more than 85 years, the M&H
More informationEasy-On II Terminations
Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables, concentric neutral, metal tape shielded or wire shielded cables without need for additional
More informationTEMPERATURE REGULATORS W91/W94 Series
Self-Operated Temperature Regulators Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company Self-Operating Design Indicating
More informationConfidence with the global standard in pressure relief devices
QUALITROL LPRD Large pressure relief devices Confidence with the global standard in pressure relief devices Robust design and materials provide reliable protection and long life Widest array of options
More information35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor
35-kV Safefront 2 Amp SuperWell 5-33 Page 1 216 EPM-PMS-35-311P-R2/ESW Three Phase Two Ways per Phase 2 Amp 35 kv Class Eaton's CPS LRTPs NEMA Standard Outdoor Instrument Transformer Provisions 21.1/36.6
More informationChevy Suburban ABS Module Removal & Installation Instructions
1999-2008 Note: The 1999-2008 Suburban uses more than one type of ABS module. We can only rebuild the Kelsey Hayes 325 module (on right). The Series 30 is similar, but has a third connector as shown. Both
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More informationMATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****
Page 1 of 8 ****Supercedes BECo Standard E2.12-2.14 and ComElectric Spec 7-0895**** THREE-PHASE DEADFRONT PAD-MOUNTED DISTRIBUTION TRANSFORMERS, LOOP & RADIAL FEED DESIGNS 1.0 General Requirements 1.1
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationOperation and Maintenance. CG Series Centrifugal Fire Pumps. Illustrations
CG Series Centrifugal Fire Pumps Operation and Maintenance Form No. F 1031 Section 2102.2 Issue Date 04/28/95 Rev. Date 3/20/17 Illustrations IL 1932 1. CGVG Series Pump... 4 2. CGR Series Pump........................
More informationPART NUMBER BREAKDOWN CP A 70 1 W D H - 10
SERIES 70 EMI/RFI Shielding Backshell Non-Environmental Outer Shield Termination Series 70 Backshells provide EMI/RFI protection using ferrules to secure a cable s outer shield. They do not offer environmental
More informationMotorized Fire Dampers
Model : OMFD-611 (Fusible link and spring return actuator) GI steel sheet construction In accordance with UL555 & UL555S suitable for installation in walls and partitions having rating 2 Hrs. Static and
More informationSecurity Is So Square
D OWN TOW N R AC K Security Is So Square The Downtown Rack uses thick, square-tube construction that can t be cut with a pipe cutter. The extended width of the Downtown Rack makes for easy bike parking
More informationCUSTOM COMBINATION AIR VALVE
INSTALLATION / OPERATION / MAINTENANCE CUSTOM COMBINATION AIR VALVE INTRODUCTION This manual will provide you with the information to properly install and maintain this valve to ensure a long service life.
More informationContents Project: Model: Chk d: Date:
Contents Model DSHU6. DSHU6.7 DSHU6. DSU6. DSHU6. DSU6.7 DSHU6.7 8DSU6. 8DSHU6. 8DSU6.7 8DSHU6.7 DSU6. DSU67. Section Page Specifications -7, 8 Selection Chart -7., 8. Performance Curves -6 Outline Drawings
More information1TSF /CD Attachment B. City and County of San Francisco Office of Contract Administration
1TSF14000167/CD LINE ITEM 1: 37,5 KVA 1 PHASE PAD MOUNTED TRANSFORMER, ENVIROTEMP FR3 37.5 KVA, 10 Pad Mounted Transformer, AIMS! TYPE 2 SHRUBLINE insulating fluid 12470 Deita Two position ioadbreak switch
More informationA. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.
1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall
More informationPhone: (800) Fax: (775)
Heavy Duty Sealed Bearing Hinges and Commercial Hardware www.ultra-tec.com Phone: (800) 851-2961 Fax: (775) 885-2734 Email: info@ultra-tec.com Heavy Duty Sealed Bearing Hinges All Hinges have Horizontal
More informationThe Core Four Solutions
3M Tech Talk: The Core Four Solutions to Complete Corrosion Protection Have you ever seen a vehicle that has corrosion on only one panel? Do you then wonder why just one panel has corroded while the same
More informationYARWAY HANCOCK Y-PATTERN FORGED STEEL GLOBE STOP VALVES SERIES 4000
Direct contact and metal-to-metal seating make this Y-pattern globe stop valve ideal for most shut-off applications. FEATURES All valves feature integral Stellite hardfacing on both body and disc seating
More informationAluminum Vertical Break Switch 345 kv, 1300 kv BIL 2000 A A.
Bulletin DB-106AEH11 Type V2-CA Aluminum Vertical Break Switch 345 kv, 1300 kv BIL 2000 A.- 3000 A. Designed for Simplicity Testing of the 345 kv V2-CA to IEEE Standards. The Cleaveland/Price 345 kv V2-CA
More informationA. This Section includes piping and related specialties for general-service compressed-air systems operating at 150 psig or less.
SECTION 221513 - COMPRESSED-AIR PIPING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes piping and related specialties for general-service compressed-air systems operating at 150 psig or less. 1.2
More informationClampette Products NEW YORK TEXAS CALIFORNIA
Clampette Products NEW YORK TEXAS CALIFORNIA Standing For Quality For Over 45 Years MADE IN THE U.S.A. Clampette is a major United States manufacturer of stainless steel pipe repair products. We take great
More informationVALVES. A. Section HVAC Basic Materials and Methods. E. Section Building Automation and Control System Guidelines
230523 VALVES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230500 HVAC Basic Materials and Methods B. Section 230510 Chilled Water System C. Section 230520 Heat Generation D. Section 238216 Coils E.
More informationCABINET - CURRENT TRANSFORMER Indoor - Outdoor 240 Volts Amperes Maximum
PAGE 1 OF 5 USE: 1. For commercial and industrial installations purchased and installed by the Customer. 2. For use on the following services: 1 phase 3 wire 240 volts, 3 phase 3 wire 240 volts, 3 phase
More informationDSZ3. EBARA Submersible Propeller Pumps Contents Project: Model: Chk d: Date: Model
Contents Model A0553 C1125 V0494 A0713 C1285 V0554 A0843 C1455 V0754 A1003 C1605 V0854 C1915 V0974 C2185 V1154 C2905 Section Page Specifications 3-203 Model Designation 3-206 Impeller Data 3-208 Material
More informationImportant Information
Table of Contents Important Information Section 1C - Troubleshooting Troubleshooting 1 C Jetdrive Troubleshooting...1C-2 Jetdrive Unit Troubleshooting...1C-2 Performance Troubleshooting...1C-4 Hard Steering...1C-5
More informationTHROTTLE VALVES FOR RELAYS AND RADIATORS Series 2009
THROTTLE VALVES FOR RELAYS AND RADIATORS Series 2009 1General Features 1.1Characteristics The butterfly valves, metal to metal sealing withy thin blade(or full tightening type, with o-ring blade), are
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS
San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS 834.1 DESCRIPTION: This item shall consist of fire hydrant installations using joint restraints in accordance
More informationSpecification Data CY /10. Putting You In Control Series Actuators. for use with 525, 526, 535H and 536H Regulators
Putting You In Control Specification Data CY10900 06/10 10900 Series Actuators for use with 525, 526, 535H and 536H Regulators Dresser Masoneilan 10900 Series Actuators for use with 525, 526, 535H and
More informationSECTION 15. GROUNDING AND BONDING
9/27/01 AC 43.13-1B CHG 1 SECTION 15. GROUNDING AND BONDING 11-185. GENERAL. One of the more important factors in the design and maintenance of aircraft electrical systems is proper bonding and grounding.
More informationInstallation Instruction for Valve: DFPHY.ID Trim Application: Pressure Balance Tub & Shower
Installation Instruction for Valve: DFPHY.ID Trim Application: Pressure Balance Tub & Shower Since 1959 2937 North Ontario Street Burbank California 91504 (818) 955-7740 FAX (818) 955-7790 www.doralfe.com
More informationGeneral Information Hydrants and Flushing Valves
General Information Hydrants and Flushing Valves Product Categories 4.1 Underground Hydrants 4-4 4.2 Above Gound Hydrants 4-10 4.3 Flushing Valves 4-13 www.hawle.de 4-3 4.1 Underground Hydrants www.hawle.de
More informationReplacement Door Bottom for Pease style doors MD /16 Beige 6 $13.20
Triple fin vinyl seal Superior for uneven floors Triple Fin Aluminum & Vinyl Door Sweep MD05090 05090 36 Aluminum 6 $8.00 MD05173 05173 36 Dark Bronze 6 $10.20 Rigid vinyl with soft vinyl sweep Sticks
More informationB-1125 DANKO STOCK. DANKO XL SKID UNIT UPF Defender Poly Tank
FIRE PUMP DANKO XL SKID UNIT UPF Defender Poly Tank A Waterous 2515LE pump shall be provided and bolted directly to the specified engine and capable of the following performance: Max Pressure - 75 GPM
More informationSLP Single Pipe Set for 2007 Arctic Cat M1000
Single Pipe Set for 2007 Arctic Cat M1000 P.N. 09-876 Kit Contents: 1 - Silencer 1 - Spring Tab 1 - Large Head Rivet 1 - Short Spring 1 - Zip Tie 1-30 Reflective Heat Tape 1 - Y-Pipe 1 - Single Pipe Read
More informationInnovative Damper Products EXPERIENCE TRUE EXCELLENCE IN SERVICE, QUALITY, AND MAINTENANCE-FREE PERFORMANCE.
Innovative Damper Products AIR-FOIL CONTROL DAMPERS BACKDRAFT DAMPERS SMOKE DAMPERS THERMALLY INSULATED DAMPERS HEAVY-DUTY CONTROL DAMPERS MULTIZONE DAMPERS FACE & BYPASS DAMPERS INSECT SCREENS EXPERIENCE
More informationThe table below provides information on the five vacuum pump-out units evaluated in this study.
Page 63 of 117 ANNEX 4 Vacuum Units Annex 4.1 - General Information The table below provides information on the five vacuum pump-out units evaluated in this study. Manufacturer Model Chesapeake Bay Marine
More informationSERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES
SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT SUBMERSIBLE AND VAULT MOUNTED
More informationMODULAR AIR HANDLING UNITS GAH SERIES
MODULAR AIR HANDLING UNITS GAH SERIES 15 Models with Air Flows from 2,250 Cu.m/hr upto 77,800 Cu.m/hr Suitable for both Standard and District Cooling Applications GAH-TC-10-13 CONTENTS Design 2 Various
More information