Increasing Wanzhou Power Transfer Capability by 550kV Fixed Series Capacitor FSC Fengjie

Size: px
Start display at page:

Download "Increasing Wanzhou Power Transfer Capability by 550kV Fixed Series Capacitor FSC Fengjie"

Transcription

1 1 Increasing Wanzhou Power Transfer Capability by 550kV Fixed Series Capacitor FSC Fengjie Lutz Kirschner, Quan Bailu, Ding Yansheng, Wang Zuli, Zhou Yan, Karl Uecker Abstract-- In summer of 2005 the Fengjie Series Compensation System located in the Wanzou 500kV ac-network has been ordered and designed for delivery, erection and commissioning. The power demand of the growing chinese industries requires an economical solution for an increase of power transfer capability with the existing lines. Fixed series compensation has been found as the appropriate choice not only to enable the desired power increase but also to stabilize the interconnected networks by reducing the connecting line impedance. Starting of commercial operation of two capacitors located in two serial lines is scheduled for August This paper will give an overview of the design philosophy of the capacitor system and for the choice of the component rating. Commercial operation is planned for summer The ac-network at Wanxian is coupled through this corridor to the Three Gorges HVDC converter station in Longquan by two parallel lines with connections in Fengjie substation (Fig. 2). Index Terms-- FSC-Fixed Series Capacitor, Fengjie, MOV Metal Oxide Varistor, Spark Gap, Dynamic Stability, PSCAD/EMTDC T I. INTRODUCTION HE Chuanyu Grid-to-Central China Mains project actually consist of two circuits of 500 kv lines, which start in the west from Wanxian 500 kv Substation and extend to the east to Longquan 500 kv HVDC Converter Station. Each circuit has a line length of 360km. Fengjie 500 kv Series Capacitor Station is located about 130km away from Wanxian substation of the above two circuits, with the site at Fengjie County, Wanzhou District, Chongqing City (Fig. 1). Due to the demanding power increase the implantation of transmission reinforcements in Wanzhou area is foreseen. Fengjie 500kV Series Compensation Station is an important station for Chuanyu Grid-to-Central China Mains Interconnection Project planned by the State Grid Corporation of China. It has a capacity of MVar and compensation level of 35% and its compensation equipment will be of Fixed Series Capacitor type (FSC) protected by metal oxide varistors and spark gaps. Lutz Kirschner, MIEEE, is with SIEMENS, Department. PTD H166, Erlangen, PO Box 3220, Freyeslebenstr. 1, Germany ( lutz.kirschner@siemens.com). Quan Bailu, (???), is with CSEPDI-Chinese South-East Power Design Institute, (your address), ( quanbailu@cs.cpecc.net). Ding Yancheng (address), ( ???). Wang Zuli (address), ( ???). Zhou Yan (address), ( ???). Karl Uecker is with SIEMENS, Department. PTD H16M, Erlangen, PO Box 3220, Freyeslebenstr. 1, Germany ( karl.uecker@siemens.com). Fig. 1. Location of FSC Fengjie (China) 35kV 220kV Neutral point grounded directly Wanxian 500kV 140km 140km Fengjie Fengjie 220km 220km Fig. 2. Electrical Equivalent for FSC Fengjie ac-network Longquan Converter Station 500kV 220kV HVDC 35kV Neutral point grounded directly The FSC system consists of two capacitors, one in each of the parallell lines located in Fengjie substation entering from Wanxian and Longquan. Both have an identical design and have identical impedances at the same compensation degree of 35%. In the following the data for one of both will be given being valid for the other one as well. The most economical design has been found for a gap protected MOV scheme with an MOV total energy capability of 35MJ per phase. External faults are covered by the installed metal oxide varistors (MOV) without bypassing the capacitor. In case of internal faults, the capacitor is immediately bypassed by the gap and temporarily locked out by a switch. Future ac system configurations have been investigated during the final design to find the necessary energy requirements of

2 2 the MOV. The calculations are based on a PSCAD/EMTDC model of the ac-system corridor with both different actual and future ac-system configuration stages including the detailed representation of the capacitors and their control and protection features. The damping circuit -consisting of a reactor and a parallel small gap and resistor series connection- is connected in series with the spark gap and bypass switch. Sufficient damping must be provided to limit the high frequency discharge current of the capacitor. To safely insert and bypass the installation motorized disconnectors and earthing switches are provided. II. SINGLE LINE AND MAIN DATA The fault calculation is the basis for the type of protection for the series capacitor bank. For FSC Fengjie, a MOV and Gap protected series capacitor has been found to be the most economical solution that meets all ac-system fault requirements. The single line diagram comprising the main components is shown in Fig. 3. The capacitive reactance is 35.3 ohms for each of the two parallel series capacitors corresponding to µf. The degree of compensation is 35% of line impedance. The nominal continuous current both capacitor banks are designed for is 2400 A rms with temporary overload currents up to 3600 A rms for 10 min. Under normal condition the ac-line current flows through the capacitor resulting in a steady state voltage drop across capacitor and varistor. In case of ac-line faults the short circuit currents increases the voltage drop across the capacitor until it is clipped by the MOV. In this way the capacitor units are therefore protected by voltage clipping. During voltage clipping the MOV dissipates energy. To protect the MOV against excessive energy dissipation a fast operating spark gap is connected in parallel to the capacitor performing a immediate bypass after gap triggering. To protect the gap against excessive arcing stresses the bypass switch closes about 50msec after gap firing. Depending on the severity of the ac-line fault the capacitor units can be protected by different bypassing strategies. A. Component Ratings For a cost and performance optimized design, various studies with different system conditions have been carried out. To determine the component ratings under worst case conditions, not only steady state voltage and current stresses need to be examined but also the transient stresses during severe acsystem faults have to be investigated in detail. 1) Capacitor The series capacitor consists of one segment with a differential protection detecting capacitor unit unbalances. It is built up of 480 capacitor units per phase. 6 units are connected in series to cover the 85 kv rms total nominal voltage. Four racks constitute such a configuration. The units are of outdoor type without fuses. Fuseless capacitor unit technology offers the lowest losses during operation and therefore contribute to the high efficiency of series capacitor installations. The 424 kvar capacitor unit has a rated voltage of kv rms with a nominal current of 30 A rms. Due to insulation requirements double bushings are used per unit. 2) Metal Oxide Varistor MOV Due to the overload conditions after an ac system fault, the rated voltage of the MOV has been chosen to 143 kv rms. To determine the number of MOV housings which have to be installed on the platform, ac-system fault calculations have been carried out. Different ac-system configurations as well as different fault types and point on wave fault inceptions need to be considered for the design, to establish the proper operation of the capacitor system also for future stages of the growing ac-network. There are two different types of faults which have to be considered for the design of the number of MOV housings: Fig. 3 Fixed Series Capacitors Fengjie Single Line Diagram External Faults: External faults are those occurring outside the series compensated line terminated by breakers. The MOV must be designed to withstand external faults without damages, as the series capacitor will not be bypassed during external faults. The fault is applied and normally cleared by a line protection breaker within 100 msec. Considering an unsuccessful line clearing this duration increases by another 100 msec until final tripping of the line. For the rating calculation of the series capacitor main components a line breaker failure in one phase after unsuccessful reclosure has been considered, increasing the total fault time by additional 350 msec. The analysed external fault locations taking into account different fault types like single and multi phase faults show that this type of fault leads to the highest MOV current stress

3 3 without any allowed bypassing action. According to this simulations a MOV current of 8 ka has been stated for the protection system parameter to detect internal faults. energy, capacitor current, gap current as well as bypass switch current traces for this fault. 15% spare energy has been added for the final energy rating of the MOV. Fig. 5. Internal Fault with maximum. voltage stress Fig. 4. MOV bank on a platform Internal Faults: Internal faults are those occurring within the series compensated line terminated by breakers. If an internal fault is detected, the series capacitor is allowed to be bypassed by the triggered spark gap. This type of fault leads to the maximum overvoltage stress of MOV and capacitor. As soon as the instantaneous value of the MOV current exceeds 8 ka the protection issues a signal to trigger the gap within 1 msec. The associated graphs can be found in Fig. 5. These show capacitor voltages, MOV current and MOV energy stresses during the fault. The highest voltage has been found to occur for a three phase internal fault directly at the terminals of the capacitor. This voltage is, however, limited to a protective level of 275 kv = 2.3 pu by the MOV, resulting in a MOV current of 13 ka. The highest energy consumption for the MOV has been found to be 30MJ per phase considering a single phase acfault with unsuccessful line reclosing and a stuck breaker condition in one phase at an internal fault. This case occurs when the fault is not detected as internal due to a MOV current slightly lower than the protection setting of 8kA. It appears if the fault location is near the end of a line. Fig. 6 shows capacitor voltage, MOV current, MOV dissipated The MOV housings are of polymere type. They are equipped with a pressure relief membrane and a flange with a gas diverter nozzle. In case of an MOV failure and internal short circuit, the pressure relief system must release the pressure inside the housing which is caused by the arc heat before the housing is violently destroyed by the pressure shock wave.

4 4 Fig. 6. MOV Energy Rating due to not detected Internal Fault 3) Spark Gap The spark gap has to protect the MOV against overload in case of internal faults. The protection fires the gap within 1 msec as soon as a threshold value of 8 ka is exceeded. It is absolutely necessary that the gap bypasses the MOV as soon as possible because of the high rate of rise energy dissipation in MOV during internal faults. The gap consists of two housings installed on top of each other. The main trigger circuit is located in the lower housing while the upper one is passive. It fires successively after the lower gap has been triggered. 4) Damping Circuit The damping circuit is designed to discharge the capacitor in case of an internal fault when the voltage across the capacitor reaches the protective level. For both capacitors the same components and their ratings are chosen. It is located in series to the spark gap and bypass switch and is therefore stressed by line current only in case of bypass. To limit the peak current value of the discharging capacitor, a reactor of 600 µh has been chosen for both series capacitors. This results in a discharge frequency of about 684 Hz. The appropriate damping is achieved by a resistor of 6 ohms located in parallel to the damping reactor. The discharge characteristic can be found in Fig. 9, where capacitor voltage, current and dissipated energy in the damping resistor is given.. To avoid a steady state current drain in the resistor, a small spark gap is also included in series with the resistor: The small gap fires for voltages exceeding the overload requirements of the capacitor. Therefore the resistor need not be rated for steady state conditions. The impulse energy rating of the resistor is sufficient for a duty cycle of two consecutive discharges. Fig. 8. Inside view into the damping reactor Fig. 7. Spark Gap flashover during high current short circuit type test The flashover voltage can be adjusted from 248 to 303 kv peak. The thermal fault current carrying capability is 40 ka rms. To avoid excessive arcing the spark-gap is always triggered in conjunction with a closing impulse to the bypass switch. Therefore the arcing stresses only occur for about 50 msec on the gap electrodes. Closing the bypass switch will extinguish the arc immediately. 5) Bypass Switch The 550kV SF6-bypass switch is designed as three singlephase units, one for each phase with a rated voltage of 245kV across the open switch coils and a closing time of 50 ms. It consists of porcelain insulator columns with a hydraulic opening mechanism. The switch is used for insertion and disconnection of the bank. In case of internal faults, it also closes so the spark gap current commutates to the switch releasing the gap from further current stress. Initiated by the protection system it also closes if the rated MOV energy is exceeded. Due to this requirements the switch is designed for high frequency capacitor discharges as well as power frequency currents and dynamic short circuit currents up to a thermal limit of 50 ka rms.

5 nominal power rating of 610 MVA the Fengjie series capacitors will provide stable and increased power transfer in the Wanzhou 550kV ac system area. 5 Fig. 9. Capacitor Discharge of FSC Fengjie Fig. 10. Layout Drawing of FSC Fengjie III. LAYOUT CONSIDERATIONS The SC components are installed on a platform which is connected to the high potential of the ac-transmission line. This design leads to the lowest creepage distances and flashover voltages across the components. The platform itself is built up on reinforced structures of porcelain insulators to provide an appropriate line to earth creepage distance with a height of approximately 6 meters. The capacitor is built up in four racks in an differential protection scheme to detect capacitor unit unbalances. The damping circuit resistor is located within the damping reactor coil. The two spark gap housings are installed on top of each other to save platform space. The MOV housings including the spares per phase are built up in two stacks. The bypass switch is not installed on the platform but located beneath the platform on the ground. Due to the optimized design the platform size is only 15m x 8m and has a total weight of about 40 tons. Fig. 10 shows the platform layout and associated bypass switch for one phase. IV. CONCLUSION 550kV Fengjie series capacitor project consists of two series capacitor installations connected in parallel on two parallel lines entering Fengjie substation. The design of the components has been carried out by intensive studies to find an optimized solution for power transfer increase and stabilization of the existing network. The details of the component design are discussed in this paper. The layout as well as the single line diagram is object of discussion. With a V. REFERENCES [1] Anderson, Farmer Series Compensation of Power Systems; ISBN , 1996 [2] Kirschner, Baoshu, Gong, Breuer - Design Aspects of the Chinese 500kV Thyristor Controlled Series Compensation Scheme TCSC Tian Guang, DRPT Conference April 2004, Hongkong [3] Bohn, Kirschner, Kuhn TPSC: Thyristor Protected Series Compensator: Design and Control Concepts, CIGRE-XERLAC Conference May 2003, Iguazu Argentina VI. BIOGRAPHY Lutz Kirschner, Senior Project Engineer, MIEEE, received his Diploma in Electrical Engineering 1992 from the university of Aachen, Germany. He joined SIEMENS company in the HVDC Department as a system design engineer. He was involved with technical and commercial design of HVDC converter stations. Since 1995 he is responsible for Fixed and Thyristor Controlled Series Capacitor design and was busy in several series capacitor projects worldwide carrying out the basic design studies. He is working on the design of Thyristor Protected Series Capacitor systems (TPSC) and FACTS devices. In the FSC Fengjie project he carried out the Final Basic Design Studies comprising the transient fault calculation and main component ratings. His special fields are time domain digital simulations and system studies. Since 1998 he is a member of IEEE. Quan Bailu was born (short Bio needed) Ding Yansheng (short Bio needed)

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems Advanced Power Transmission Solutions Power Transmission and Distribution Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in Systems s Development of Power Markets Increasing

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

Capacitor Related Definitions

Capacitor Related Definitions Capacitor Related Definitions July 2005 This is an assembly of definitions used in various standards related to power capacitors. The listing is intended to include all of the definitions in IEEE Standards

More information

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment 2012 2nd International Conference on Power and Energy Systems (ICPES 2012) IPCSIT vol. 56 (2012) (2012) IACSIT Press, Singapore DOI: 10.7763/IPCSIT.2012.V56.2 Wind Power Plants with VSC Based STATCOM in

More information

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks Product Selection & Application Guide Product Description GE's Thyristor Switched Harmonic Filter Banks (TSC), are custom designed

More information

Surge Arresters. Supply Program. Answers for energy.

Surge Arresters. Supply Program.   Answers for energy. Surge Arresters Supply Program www.siemens.com/energy/arrester Answers for energy. Always the Best Solution We offer an extensive range of surge arresters suitable for every application economical and

More information

High Voltage Surge Arresters Station Class

High Voltage Surge Arresters Station Class Power Transmission and Distribution High Voltage Surge Arresters Station Class Product Overview High Voltage High Protection Just as the Golden Gate Bridge has successfully defied all winds, weather and

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 120-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 120-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 120-0.3

More information

3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv

3EP1 Surge Arrester. Metal-oxide surge arrester without series gaps for high-voltage systems up to U m. = 170 kv 3EP1 Surge Arrester Metal-oxide surge arrester without series gaps for high-voltage systems up to U m = 170 kv Rated voltage up to 180 kv Nominal discharge current 10 ka, 8/20 µs Line discharge class LD1,

More information

3EP6 porcelain surge arrester

3EP6 porcelain surge arrester www.siemens.com/energy/arrester 3EP6 porcelain surge arrester Safe, reliable, long-lasting, and stable Answers for energy. Compact design high mechanical stability Sealing system Spring Maximum values

More information

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Day 2 - Session V-B 299 Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank Murali Kandakatla, B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Thane Introduction

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

AIR CORE REACTORS. Phoenix Electric Corporation

AIR CORE REACTORS. Phoenix Electric Corporation AIR CORE REACTORS Phoenix Electric Corporation PHOENIX ELECTRIC CORPORATION designs and manufactures Dry Type Air Core Reactors for operation on systems rated through 800 kv. All reactors are custom designed

More information

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng.

First Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng. First Applications on AltaLink s Network Roggero Ciofani, P. Eng. Colin Clark, P. Eng. Overview Technology Overview Applications and Alternatives Advantages Alberta Special Considerations Operational Implications

More information

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION Surge Arresters UltraSIL Housed VariSTAR Station Class Surge Arresters Electrical Apparatus 235-88 GENERAL Cooper Power Systems has set a new standard of excellence for polymerhoused station class surge

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 60-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 60-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 60-0.3

More information

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm Downloaded from orbit.dtu.dk on: Apr 07, 2019 Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm Arana Aristi, Iván; Johnsen, D. T.; Soerensen, T.; Holbøll, Joachim Published

More information

Review paper on Fault analysis and its Limiting Techniques.

Review paper on Fault analysis and its Limiting Techniques. Review paper on Fault analysis and its Limiting Techniques. Milap Akbari 1, Hemal Chavda 2, Jay Chitroda 3, Neha Kothadiya 4 Guided by: - Mr.Gaurang Patel 5 ( 1234 Parul Institute of Engineering &Technology,

More information

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect

More information

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Breaker Technology Operational Advantages Development Schedule Dave Richardson, Ph.D.,P.E. Powell Power Electronic

More information

Electrical Test of STATCOM Valves

Electrical Test of STATCOM Valves 21, rue d Artois, F-75008 PARIS 619 CIGRE 2016 http : //www.cigre.org Electrical Test of STATCOM Valves Baoliang SHENG 1, Christer DANIELSSON 1, Rolf NEUBERT 2, Juha TURUNEN 3, Yuanliang LAN 4, Fan XU

More information

Impulse Voltage Test System, Q Structure, kV

Impulse Voltage Test System, Q Structure, kV TCDYQ Series Impulse Voltage Test System, Q Structure, 200-3600kV Applications: Shunt reactors Power transformers Distribution transformer Instrument transformers Cables (type tests) Bushings Arresters

More information

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF Power IT MV Live Tank Vacuum Circuit Breaker Model VBF ABB - a global leader in power and automation technologies ABB (www.abb.com) is a global leader in power and automation technologies that enable utility

More information

Unrestricted. Air Core Reactor Applications Current Limiting Reactors

Unrestricted. Air Core Reactor Applications Current Limiting Reactors Unrestricted Air Core Reactor Applications Current Limiting Reactors Faults on Electrical System - Basic Concepts Three major concerns arise from this scenario: 1- The mechanical stresses on the transformer

More information

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2 Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2 Table of Contents 1 Introduction... 4 2 Description of retrofit circuit-breaker 8DN8... 5 3 Technical data for retrofit circuit-breaker

More information

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks

An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks D. M. Nobre W. L. A. Neves B. A. de Souza Departamento de Engenharia Elétrica - UFPB Av. Aprígio Veloso, 882 Bodocongó 58.109-970,

More information

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor > 57 < 1 Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor Masaki Yagami, Non Member, IEEE, Junji Tamura, Senior Member, IEEE Abstract This paper

More information

HVDC Solutions. for Integration of the Renewable Energy Resources. Marcus Haeusler HVDC Lead Engineer. siemens.com/energy/power-transmission

HVDC Solutions. for Integration of the Renewable Energy Resources. Marcus Haeusler HVDC Lead Engineer. siemens.com/energy/power-transmission HVDC Solutions for Integration of the Renewable Energy Resources Marcus Haeusler HVDC Lead Engineer siemens.com/energy/power-transmission Agenda Principles of HVDC operation HVDC converter types HVDC configurations

More information

Nissin s Products for Electric Railway System

Nissin s Products for Electric Railway System Ref. No. EKF120927-PRWS Nissin s Products for Electric Railway System KYOTO, JAPAN September, 2012 Introduction of Nissin Electric as Prime Supplier of Equipment for Electric Railway System in Japan Nissin

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper

More information

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map EH2741 Communication and Control in Electric Power Systems Lecture 3 Lars Nordström larsn@ics.kth.se 1 Course map 2 1 Outline 1. Repeating Power System Control 2. Power System Topologies Transmission Grids

More information

EMPAC Metal enclosed capacitor bank for wind applications

EMPAC Metal enclosed capacitor bank for wind applications EMPAC Metal enclosed capacitor bank for wind applications Introduction The EMPAC is a Metal Enclosed Capacitor Bank suitable for voltages between 1 kv and 36 kv for reactive compensation in MV networks

More information

A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission

A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission Longchen Liu 1, Ke Yue 2, Lei Pang 2, Xinghai Zhang 1, Yawei Li 1 and Qiaogen Zhang 2 1 State Grid Sichuan

More information

Thyristors for >10 GW Power Transmission

Thyristors for >10 GW Power Transmission Thyristors for >10 GW Power Transmission A new thyristor platform with voltage ratings 6.7 kv, 7.2 kv and 8.5 kv was developed to enable an optimal design of converter valves with DC link voltages above

More information

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best. Medium Voltage Power Factor Correction Reactive Compensation Harmonic Filters POWER QUALITY Electrical Power Quality Management at its best. From electricity generation, transmission, thru its distribution

More information

Study of 345 kv Transient Recovery Voltages on the Illinois Power System

Study of 345 kv Transient Recovery Voltages on the Illinois Power System Study of 345 Transient Recovery Voltages on the Illinois Power System R. A. Niemerg, Member, IEEE, T. E. Grebe, Senior Member, IEEE Abstract--Illinois Power will be installing twenty-two new 345 breakers

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection

Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection Evaluation of the Performance of Back-to-Back HVDC Converter and Variable Frequency Transformer for Power Flow Control in a Weak Interconnection B. Bagen, D. Jacobson, G. Lane and H. M. Turanli Manitoba

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

Publication No.: PSG

Publication No.: PSG TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06

More information

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Experience on Technical Solutions for Grid Integration of Offshore Windfarms Experience on Technical Solutions for Grid Integration of Offshore Windfarms Liangzhong Yao Programme Manager AREVA T&D Technology Centre 18 June 2007, DTI Conference Centre, London Agenda The 90MW Barrow

More information

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET) INTERNATIONAL International Journal of JOURNAL Electrical Engineering OF ELECTRICAL and Technology (IJEET), ENGINEERING ISSN 0976 & TECHNOLOGY (IJEET) ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume

More information

The 1,400-MW Kii-Channel HVDC System

The 1,400-MW Kii-Channel HVDC System The 1,4-MW Kii-Channel HVDC System The 1,4-MW Kii-Channel HVDC System 114 Hiroyuki Nakao Masahiro Hirose Takehisa Sakai Naoki Kawamura Hiroaki Miyata Makoto Kadowaki Takahiro Oomori Akihiko Watanabe OVERVIEW:

More information

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) Nazneen Choudhari Department of Electrical Engineering, Solapur University, Solapur Nida N Shaikh Department of Electrical

More information

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability

3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability 3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability Power Transmission and Distribution 1 A perfect Combination of Cost-Savings, Safety and Reliability 3EQ Surge Arresters:

More information

Safe, fast HV circuit breaker testing with DualGround technology

Safe, fast HV circuit breaker testing with DualGround technology Safe, fast HV circuit breaker testing with DualGround technology Substation personnel safety From the earliest days of circuit breaker testing, safety of personnel has been the highest priority. The best

More information

POWER QUALITY SEMINAR OF IRAN, 2 ND MARCH 2017 Power Quality Seminar. Abel-Zhang,Power Quality Center Manager

POWER QUALITY SEMINAR OF IRAN, 2 ND MARCH 2017 Power Quality Seminar. Abel-Zhang,Power Quality Center Manager POWER QUALITY SEMINAR OF IRAN, 2 ND MARCH 2017 Power Quality Seminar Abel-Zhang,Power Quality Center Manager Contents Capacitor Unit Capacitor Shunt Bank Type Solution of Filter March 7, 2017 Slide 2 Contents

More information

Excitation systems for high power synchronous generators with redundant configurations

Excitation systems for high power synchronous generators with redundant configurations Excitation systems for high power synchronous generators with redundant configurations Zvonimir Jurin, Blaženka Brkljač, Marin Kolić KONČAR Elektronika i informatika Fallerovo šetalište 22, Zagreb, Croatia

More information

3EK7 Medium Voltage Silicone Insulated Surge Arresters

3EK7 Medium Voltage Silicone Insulated Surge Arresters 3EK7 Medium Voltage Silicone Insulated Surge Arresters Power Transmission and Distribution Setting new Standards The 3EK7 s mechanical features: Glass-collared MOV, Silicone rubber housing, FRP rods and

More information

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran Effect of Increasing the Grounding Grid Resistance of a Ground System at a Substation on the Safety and Transient Overvoltage on the Interior Equipments M. Bashir M.Sc student, Student Member, IEEE Ferdowsi

More information

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn Surge arresters UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters electrical apparatus 235-75 General Cooper Power Systems has set a new standard of excellence for polymerhoused

More information

2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant

2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited

More information

The Application of Power Electronics to the Alberta Grid

The Application of Power Electronics to the Alberta Grid The Application of Power Electronics to the Alberta Grid Peter Kuffel, Michael Paradis ATCO Electric APIC May 5, 2016 Power Electronics Semiconductor devices used in power transmission systems Types: Thyristor

More information

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues

Designing and Maintaining a Pollution-Resilient Electric Power System. Managing Pollution Issues Designing and Maintaining a Pollution-Resilient Electric Power System Tom McDermott IEEE/PES T&D Conference April 21-24, 2008 Chicago, IL Managing Pollution Issues Define the metrics, and measure them

More information

POSSIBILITIES OF POWER FLOWS CONTROL

POSSIBILITIES OF POWER FLOWS CONTROL Intensive Programme Renewable Energy Sources June 2012, Železná Ruda-Špičák, University of West Bohemia, Czech Republic POSSIBILITIES OF POWER FLOWS CONTROL Stanislav Kušnír, Roman Jakubčák, Pavol Hocko

More information

GENERAL. CONSTRUCTION External

GENERAL. CONSTRUCTION External Surge Arresters VariSTAR Type AZG4 Surge Arresters for Systems through 400 kv IEC 20-kA; Line Discharge Class 4 Electrical Apparatus I235-84 GENERAL VariSTAR AZG4 Surge Arresters incorporate the latest

More information

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi

More information

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Journal of American Science 2015;11(11)   Integration of wind Power Plant on Electrical grid based on PSS/E Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity

More information

Eskom s unique type test requirements for lightning surge arrester ground lead disconnectors

Eskom s unique type test requirements for lightning surge arrester ground lead disconnectors Eskom s unique type test requirements for lightning surge arrester ground lead disconnectors Author & Presenter: R Theron M.Eng Chief Engineer Co-author: H Geldenhuys Phd Corporate Specialist (Technology

More information

Unit Protection System for Pumped-Storage Power Stations

Unit Protection System for Pumped-Storage Power Stations Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve

More information

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 01 July 2015 ISSN (online): 2349-784X Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC Ravindra Mohana

More information

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK --------------------------------------------------------------------------------------------------------------- Sub. Code : EE2402 Semester

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

CP Automatic capacitor bank

CP Automatic capacitor bank CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor

More information

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV December, 1975 New nformation and Supersedes DB 38-131 Pages 1-4, dated May 1972, and 38-121 D WE A, Pages 1-4, dated April1974 E, D, C/1981/ DB Westinghouse Electric Corporation Distribution Apparatus

More information

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING 1 DEPARTMENT OF ELECTRICAL ENGINEERING Introduction to High Voltage Testing It is essential to ensure that the electrical equipment is capable of withstanding the overvoltages that are met within the service.

More information

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv HS PEXLIM-P Metal Oxide Surge Arrester HS PEXLIM-P Surge Arresters are used for the protection of switchgear, transformers and other

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation agenda Fundamentals Compelling value Product line overview VerSaVac (VSV) Product features and benefits Design Ratings Applications

More information

SOFE

SOFE KOREAN R&D ON THE 6-PULSE CONVERTER UNIT FOR ITER AC/DC CONVERTERS SOFE 2011 2011. 06. 27 J. S. Oh 1), J. Choi 1), J. H. Suh 1), H. Liu 2), S. Lee 2), H. Park 2), W. Jung 2), S. Jo 2), H. Tan 3), J. Tao

More information

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

43-SDMS-04 REV. 00 SPECIFICATIONS FOR 43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without

More information

Dual Power. Protection. Protection

Dual Power. Protection. Protection 54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result

More information

Modelling of Hybrid DC Circuit Breaker Based on Phase-Control Thyristors

Modelling of Hybrid DC Circuit Breaker Based on Phase-Control Thyristors Modelling of Hybrid DC Circuit Breaker Based on Phase-Control Thyristors Aliakbar Jamshidi Far School of Engineering, University of Aberdeen Aberdeen, UK ajamshidifar@abdn.ac.uk Abstract This paper presents

More information

3EQ Composite Housed Surge Arresters

3EQ Composite Housed Surge Arresters Power Transmission and Distribution 3EQ Composite Housed Surge Arresters Saving Money and Space, Gaining Reliability A perfect Combination of Cost-Savings, Safety and Reliability 3EQ Surge Arresters: Your

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

Modular Capacitor Systems Reactive Compen. sation. Copyright 2002 ABB. All rights reserved.

Modular Capacitor Systems Reactive Compen. sation. Copyright 2002 ABB. All rights reserved. Modular Capacitor Systems Reactive Compen sation Copyright 2002 ABB. All rights reserved. 12/12/2002 Needs Customer A solution to suit Modular Substations Relocatable assets More value for money ABB A

More information

Transformer bushings, type GOH. Technical guide

Transformer bushings, type GOH. Technical guide Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

Gas-insulated switchgear up to 420 kv, 63 ka, 5000 A Type 8DQ1. siemens.com/energy. Answers for energy.

Gas-insulated switchgear up to 420 kv, 63 ka, 5000 A Type 8DQ1. siemens.com/energy. Answers for energy. Gas-insulated switchgear up to 420 kv, 63 ka, 5000 A Type 8DQ1 siemens.com/energy Answers for energy. Gaining from experience Our switchgear ensures extraordinarily high availability at a low operating

More information

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders Applications HV HRC (high-voltage high rupturing capacity) fuses are used for short circuit protection in high-voltage switchgear for the 50 to 60 Hz frequency range Distribution transformers up to 2000

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses CP No.: CP9716 Rev. 02 Page: 1 of 9 CERTIFIED TEST REPORT Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses Rev. 02 DATE: June 3, 2010 ORIGINAL REPORT DATE: June 13, 1997 Cooper Power Systems,

More information

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The

More information

HIGH VOLTAGE SURGE ARRESTER SPECIFICATION

HIGH VOLTAGE SURGE ARRESTER SPECIFICATION HIGH VOLTAGE SURGE ARRESTER SPECIFICATION Applications: (Polymer housed MOA for 110kv) (The polymer housed MOA for 10kv) (Porcelain housed MOA for 220kv) (35kv MOA without gaps for middle phase) (110kv

More information

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement. INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side

More information

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System Raju Pandey, A. K. Kori Abstract FACTS devices can be added to power transmission and distribution systems at appropriate

More information

Presented to the IAPMO Standards Review Committee on December 9, 2013

Presented to the IAPMO Standards Review Committee on December 9, 2013 Summary of Substantive Changes between the 2010 edition including Updates No. 1 and No. 2 dated September 2010 and August 2011 and the 2013 edition of CSA C22.2 No. 14 Industrial control equipment Presented

More information

Benefits of HVDC and FACTS Devices Applied in Power Systems

Benefits of HVDC and FACTS Devices Applied in Power Systems Benefits of HVDC and FACTS Devices Applied in Power Systems 1 P. SURESH KUMAR, 2 G. RAVI KUMAR 1 M.Tech Research Scholar, Priyadarshini Institute of Technology & Management 2 Associate Professor, Priyadarshini

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Outdoor vacuum breaker for railway applications - FSK II

Outdoor vacuum breaker for railway applications - FSK II Outdoor vacuum breaker for railway applications - FSK II Single or two-pole outdoor vacuum breaker with magnetic actuator 27.5 kv - 250 kv BIL - 1250 A. 2000 A - 25.0 ka - 50/60 Hz 27.5 kv - 200 kv BIL

More information

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Mining The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Reprint Authors: Kurt Tischler Siemens AG, Mining Technologies, Erlangen, Germany Reprint: WORKSHOP SAG

More information

A New Synthetic Test Circuit For the Operational Tests of HVDC Thyristor Modules

A New Synthetic Test Circuit For the Operational Tests of HVDC Thyristor Modules Paper presented at IEEE PELS APEC Conference on March -8,, at Anaheim, USA. Conf. Proceedings pp.-6 A New Synthetic Test Circuit For the Operational Tests of HVDC Thyristor Modules B.L. Sheng E. Jansson

More information

Implementation of FC-TCR for Reactive Power Control

Implementation of FC-TCR for Reactive Power Control IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 5, Issue 5 (May. - Jun. 2013), PP 01-05 Implementation of FC-TCR for Reactive Power Control

More information

Advanced Protective Relay Training

Advanced Protective Relay Training Advanced Protective Relay Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq A properly designed protection

More information

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 1 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 2 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC

More information