Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Size: px
Start display at page:

Download "Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses"

Transcription

1 CP No.: CP9716 Rev. 02 Page: 1 of 9 CERTIFIED TEST REPORT Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses Rev. 02 DATE: June 3, 2010 ORIGINAL REPORT DATE: June 13, 1997 Cooper Power Systems, Inc.

2 CP No.: CP9716 Rev. 02 Page: 2 of 9 Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses CERTIFICATION Statements made and data shown, to the best of our knowledge and belief, are correct and within the usual limits of commercial testing practice.

3 CP No.: CP9716 Rev. 02 Page: 3 of 9 Overview The Cooper Power Systems Companion II 12K through 40K fuses are designed to be applied as backup current limiting fuses. In this application, the Companion II fuse provides protection against high current faults and limits the peak current and the amount of let-through energy to the protected equipment. The CPS Companion II fuse is typically applied in series with an expulsion fuse. When applied in series with an expulsion or other type of low current interrupting device, the combination provides full range protection. Certification Tests as required by IEEE Std C Interruption Tests at Line-to-Neutral Rated Voltage Series 1 Rated Maximum Interrupting Current Series 2 Critical Current Series 3 Rated Minimum Interrupting Current 2. Temperature Rise Tests 3. Time Current Characteristic Tests 4. RIV Tests

4 CP No.: CP9716 Rev. 02 Page: 4 of 9 Requirements INTERRUPTION TESTS Back-up current-limiting fuses are required to operate on high available fault currents and limit the fault current magnitude and energy. They must interrupt these fault currents so that the other pieces of connected equipment are isolated from the electrical distribution system. Objective The objective of these tests is to verify the interrupting performance of the Companion II fuse for applications at the respective voltage rating by testing according to the requirements specified in ANSI/IEEE C , clause 6.6 and C Procedures These tests were run on production fuses which were assembled using standard methods and procedures. The testing was conducted at ambient temperature. Test Results The Companion II 12K 40K fuses successfully interrupted each respective test current. The performance parameters are detailed in Table 1: Table 1: Interruption test results Test current Test Voltage close angle Melt I²t Total I²t Total Energy Melt time Clear time Withstand Part number A kv deg X/R ka²sec ka²sec kj msec msec (min) 8.3kV 12K kV 12K kV 12K kV 12K kV 12K kV 12K kV 12K kV 12K kV 40K kV 40K kV 40K kV 40K kV 40K kV 40K kV 40K kV 40K kV 12K kV 12K

5 CP No.: CP9716 Rev. 02 Page: 5 of kV 12K kV 12K kV 12K kV 12K kV 12K kV 12K kV 40K kV 40K kV 40K kV 40K kV 40K kV 40K kV 40K kV 40K kV 12K kV 12K kV 12K kV 12K kV 12K kV 12K kV 12K kV 12K kV 25K kV 25K kV 25K kV 25K kV 25K kV 25K kV 25K kV 25K

6 CP No.: CP9716 Rev. 02 Page: 6 of 9 Requirements TEMPERATURE RISE TESTS Backup current limiting fuses are required to carry all normal system steady state currents without incurring temperature rises that would be detrimental to any of the fuse parts. Objective The objective of this test is to verify that the temperature rise does not exceed the values specified in ANSI C37.47 and ANSI C Procedures Production fuses were tested per requirements specified in ANSI/IEEE C37.41 (Clause, 10). Current was supplied by a regulated current source. Temperature levels of the various current carrying parts were recorded throughout the duration of the test. Note that the fuse itself does not have a continuous current rating there is an implied rating that the fuse must carry about 1.5 times the rating of the cutout link it is used in series with i.e. 60 A for the 40K fuse. Test Results Temperature rises were below maximum temperature rise levels allowed by standard IEEE C Table 1. Conclusion The Companion II 12K 40K fuses met the temperature rise requirements of Table 2 in ANSI/IEEE C37.40.

7 CP No.: CP9716 Rev. 02 Page: 7 of 9 Requirements TIME CURRENT CHARACTERISTICS TESTS Time current characteristic curves are primarily for application selections and system coordination studies. These curves, minimum melt and maximum clear, detail the performance data of a particular fuse design. Objective Establish time current characteristic curves for the 12K 40K Companion II fuses per ANSI/IEEE C (R-1992) requirements. Procedure Testing was performed on production fuses which were assembled using established methods and procedures. Minimum melt and maximum clear time current characteristic curves were developed using ANSI/IEEE C , Clause, 12 requirements as a guideline. The curves reflect the typical industry tolerances ± 10% of the average melting current. An allowance for arcing time is also added to the total clearing curve to determine the fuse s total clearing characteristics. Testing was performed at ambient temperatures. Results and Conclusions The minimum melt and maximum clear TCC curves for the 12 40K Companion II backup current limiting fuses were developed using the procedure described above and are detailed in R

8 CP No.: CP9716 Rev. 02 Page: 8 of 9 Requirements RIV Testing RIV performance data for the Companion II fuse family is necessary in order to ensure proper performance of the fuse for the manner in which it is mounted in the field. Objective Determine RIV performance levels of the highest voltage and K-rated Companion II fuses; 17.2kV 40K, 23kV 12K and 23kV 25K. The highest rated fuses were chosen to represent the worst case condition; therefore this would represent successful performance of the entire Companion II fuse family. Procedure Testing was performed as detailed in ANSI C , Clause 8. Testing was conducted by mounting the fuse on top of a 27kV Type L cutout and was performed at 1 MHz. The fuses were secured to the cutout connector in the same manner as is typical field practice. An Electro-Metric meter, model EM-7535 S/N 144, was used to record the data. Results and Conclusions Applied rms Voltage (kv) Corrected Reading (µvolts) Fuse Part number Meter Reading (µvolts) FAH17KV40K 15.8 <10 <10 FAH23KV12K 15.8 <10 <10 FAH23KV25K 15.8 <10 <10 Barometer = mmhg Dry Bulb = 23.5 C Wet Bulb = 16.5 C All fuses were less than the permissible maximum value, 250 µvolts, specified by standards. A 10 µvolt reading is considered RIV inception.

9 CP No.: CP9716 Rev. 02 Page: 9 of 9 Revision no. Date of addition/change REVISION HISTORY Addition/Change made to report 02 6/3/10 Updated report with new interruption data and RIV results Quality from Cooper Industries P.O. Box 1640, Waukesha, WI 53187

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C CP No.: CP1101 Rev. 00 Page: 1 of 9 CERTIFIED TEST REPORT 8.3, 9.9, 15.5, 17.2 and 23 Cooper ELSP Backup Fuses Testing per C37.41-2008 Rev. 00 DATE: May 3, 2011 ORIGINAL REPORT DATE: May 3, 2011 Cooper

More information

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C Page:1 of 9 CERTIFIED TEST REPORT Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C37.41-2008 REV. 00 August 11, 2014 Original Report Date: August 11, 2014 Eaton s Cooper Power Systems

More information

Faulted Circuit Interrupting Tests on Type CMU Power Fuses

Faulted Circuit Interrupting Tests on Type CMU Power Fuses CP No.: CP0509 Rev.01 Page: 1 of 9 CERTIFIED TEST REPORT Faulted Circuit Interrupting Tests on Type CMU Power Fuses REV. 01 DATE: August 10, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems,

More information

TEMPERATURE RISE TESTS

TEMPERATURE RISE TESTS CP No.: CP0511 Rev. 01 Page: 1 of 6 CERTIFIED TEST REPORT TEMPERATURE RISE TESTS Type CMU Power Fuses REV. 01 DATE: August 12, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems, Inc. CP No.:

More information

Faulted Circuit Interrupting Tests on Type CMU Power Fuses

Faulted Circuit Interrupting Tests on Type CMU Power Fuses CP No.: CP0508 Rev. 01 Page: 1 of 9 CERTIFIED TEST REPORT Faulted Circuit Interrupting Tests on Type CMU Power Fuses REV. 01 DATE: August 10, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems,

More information

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report File Ref: CA132015EN Effective Mar 2015 COOPER POWER CT132001EN SERIES 38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report CT132001EN Page: 3 of 9 Introduction Eaton designs its Cooper

More information

K-Limiter high ampere Companion II fuse

K-Limiter high ampere Companion II fuse Fusing Equipment Catalog Data CA132059EN Supersedes February 2016 COOPER POWER SERIES K-Limiter high ampere Companion II fuse General Eaton designs its Cooper Power series K-Limiter fuse to be conveniently

More information

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

Edison modular fuse, vault application products

Edison modular fuse, vault application products Fusing Equipment Catalog Data CA132025EN Supersedes 240-92 October 2008 Edison modular fuse, vault application products COOPER POWER SERIES Description Eaton s Cooper Power series Edison modular fuses

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents HHM High Voltage Fuses Motor Circuit Protection DIN and British Standard SIBA Motor Rated Fuses are available in - German DIN Standard and - British Standard Design The large variety in body sizes / mounting

More information

Product Selection Guide

Product Selection Guide Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility

More information

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number: 15kV 200A Loadbreak Fuse Elbow Design Test Report Report Number: Date: RN-R2601 9/3/2015 Table of Contents 1. Partial Discharge Test Fuse Elbow... 2 2. AC Withstand Voltage Test - Fuse Elbow... 3 3. DC

More information

Figure 1. Two and Three-phase MagneX.

Figure 1. Two and Three-phase MagneX. Fusing Equipment Two- & Three-Phase MagneX Interrupter Electrical Apparatus 240-33 GENERAL The Cooper Power Systems MagneX Interrupter is an overcurrent protective device that protects distribution transformers

More information

CERTIFIED TEST REPORT

CERTIFIED TEST REPORT CP No.: CP0316 Rev. 01 Page: 1 of 22 CERTIFIED TEST REPORT COOPER POWER SYSTEMS FOUR POSITION SECTIONALIZING LOADBREAK SWITCH 12.5 ka Momentary and Making Rating REV. 01 DATE: December 3, 2004 ORIGINAL

More information

AutoLink Frequently Asked Questions

AutoLink Frequently Asked Questions Rev. 3 October 2013 Page 1 of 8 AutoLink Frequently Asked Questions October 2013 1 Rev. 3 October 2013 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the AutoLink Single Phase Electronic Sectionalizer?...

More information

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast). FUSE CATALOG 2 Table 1.-Elemsa code and characteristics of Type K fuse links (Fast). TYPE DESCRIPTION CAT PAGE 15K-1 UNIVERSAL TYPE FUSE LINK 2066A1 38K-1 UNIVERSAL TYPE FUSE LINK 2070A1 15K-2 UNIVERSAL

More information

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013 Kearney fuse links Supersedes December 2013 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links imum cold resistance power dissipation pre-arcing I t value total I t value [kv] (mm) I n [A] (ka) [mω] [W] [A s] [A s] 1 580,1 57 A 0 370 9 17,3 1 A 5 00 10 3 30 10 A 55 7 11

More information

How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults.

How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults. How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults. This is the second in a series of articles describing how Coordinaide The S&C Protection and Coordination Assistant

More information

PROTECTION AND CONTROL

PROTECTION AND CONTROL B C Table 1 DIMENSIONAL Information for Trans-Guard OS Fuses Fuse Voltage Rating (kv) 1/4-20 threaded hole 1/2 deep (both ends) Current Rating (Amps) Fuse Catalog Number 35 HTDS232035 Overall Diameter

More information

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009 Kearney fuse links Supersedes November 2009 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

X-Limiter full-range current-limiting fuse

X-Limiter full-range current-limiting fuse Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting

More information

Section 1 Introduction to the Presentation

Section 1 Introduction to the Presentation 2007 Thomas & Betts Section 1 Introduction to the Presentation Introduction of T&B Hi-Tech Fuses and our products Expulsion fuses vs. Current-Limiting fuses Hi-Tech s fuse construction & design features

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links [A] (ka) [mω] [W] [A 2 s] [A 2 s] 12 580 4 6,1 57 4 A 20 370 9 17,3 164 6 A 25 260 10 36 340 10 A 46 55 7 161 1 530 16 A 60 37 13 250 2 270 20 A 80 30 15 430 3 750 25 A 105 25

More information

SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION

SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION Fusing Equipment Tandem ELF Current-Limiting Dropout Fuse Electrical pparatus 240-67 GENERL The Cooper Power Systems Tandem ELF current-limiting fuse is designed for transformer protection. The Tandem

More information

Figure 1. ELSG Current-Limiting fuses. TABLE 1 Maximum Interrupting Current (rms symmetrical) INSTALLATION

Figure 1. ELSG Current-Limiting fuses. TABLE 1 Maximum Interrupting Current (rms symmetrical) INSTALLATION Fusing Equipment ELSG Full Range Current-Limiting Fuse Electrical pparatus 240-82 Contents General......................1 Installation...................1 Production Tests..............1 Electrical Characteristics.......3

More information

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc. DO-III DO-III Fuse Holder TPL 44-835, May 2000, Page 1 of 4 General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder ABB Inc. General Description The ABB DO-III fuse holder is a draw

More information

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description Type L Cutouts UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout Electrical Apparatus 327-30 Description Cooper Power Systems has set a new standard of excellence for polymer distribution

More information

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number: 25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.

More information

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION Surge Arresters UltraSIL Housed VariSTAR Station Class Surge Arresters Electrical Apparatus 235-88 GENERAL Cooper Power Systems has set a new standard of excellence for polymerhoused station class surge

More information

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

OVERALL LENGTH (B)  ( mm)  ( mm)  ( mm)  ( mm) 1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165

More information

CMU medium voltage power fuses

CMU medium voltage power fuses Fusing Equipment Catalog Data C132038EN Supersedes 240-94 December 2013 COOPER POWER SERIES General Eaton s Cooper Power series CMU power fuse is a boric acid, expulsion-style fuse. Suitable for both indoor

More information

ECET Distribution System Protection. Overcurrent Protection

ECET Distribution System Protection. Overcurrent Protection ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.

More information

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents.

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents. .3 Power Breakers, Contactors and Fuses Fuses General Contents Description Fuses General Product Overview Power Fuse Eaton s roots in the medium voltage power fuse business began over 75 years ago under

More information

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element Fusing Equipment Kearney Fuse Links Electrical Apparatus 327-40 general Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution

More information

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM CP No.: CP9806 Page: 1 of 35 CERTIFIED TEST REPORT Cooper Power Systems 25 kv Class 200 Amp SEPARABLE CONNECTOR SYSTEM Includes Cooper POSI-BREAK Loadbreak Elbow and Insulated Protective Cap April 3, 1998

More information

Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses

Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses WHITE PAPER Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses The Trans-Guard EXT and Trans-Guard OS Shorty fuses, designed and manufactured by ABB under its Hi-Tech brand, are backup current-limiting

More information

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA 5670-100 Technical Guide 15 kv, 23 kv, & 35 kv General Description The Protective link is an oil immersed, expulsion type, fuse

More information

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E. MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E

More information

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4)

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4) CP9817 PAGE: 1 of 16 CERTIFIED TEST REPORT VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC 60099-4 (99-4) 0711 Supersedes 0601 Cooper Industries. All Rights Reserved. CP9817 PAGE:

More information

NX indoor current-limiting fuses

NX indoor current-limiting fuses Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground

More information

Molded Current-Limiting Fuse

Molded Current-Limiting Fuse Molded Current-Limiting provide fullrange fault current protection using specially designed fuse elements, rated through 23kV line to ground and 50kA interrupting current. Construction is modular with

More information

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features Surge s Electrical Apparatus 235-99 General Cooper Power Systems set the standard for design, manufacturing and delivery of polymeric distribution arresters with the UltraSIL polymerhoused arrester family.

More information

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester This report records the results of the design tests made on Type PDV 100 Optima Distribution

More information

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn Surge arresters UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters electrical apparatus 235-75 General Cooper Power Systems has set a new standard of excellence for polymerhoused

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

ELF -LR current-limiting fuse

ELF -LR current-limiting fuse Fusing Equipment Catalog Data C132044EN Supersedes 240-71 ugust 2006 COOPER POWER SERIES ELF -LR current-limiting fuse General Eaton's Cooper Power series ELF -LR currentlimiting fuse is a full range current-limiting

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

FUSE TECHNOLOGY Ambient temperature

FUSE TECHNOLOGY Ambient temperature This fuse technology guide will discuss basic fuse operating, application, and selection criteria concepts. The intended purpose of this section is to aid designers with the operation and characteristics

More information

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection

More information

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Fusing Equipment Catalog Data CA132035EN Supersedes November 2015 COOPER POWER SERIES UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Description Eaton has set a standard

More information

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer Reducing Arc Energies with Current Limiting Fuses arc flash note 2 By mike lang, Principal field engineer Why Use Current Limiting Fuses Current limiting fuses can reduce both the magnitude and duration

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

High voltage high-breaking capacity VV fuse-links

High voltage high-breaking capacity VV fuse-links High fuse-links High fuse-links High high-breaking capacity VV fuse-links VV General information ET fuse-links named VV THERMO are designed to protect devices in switch-gears and other equipment (distribution

More information

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT Fusing Equipment Kearney Fuse Links Electrical Apparatus K-SEC 030 GENERAL Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems and equipment.

More information

n For use in telecommunication circuit applications requiring low current protection with high surge tolerance

n For use in telecommunication circuit applications requiring low current protection with high surge tolerance *RoHS COMPLIANT & **HALOGEN FREE 0.5 SinglFuse SF-3812TM-T Series Features n Replacement for Bourns Telefuse models B0500T, B1250T and B2000T n For use in telecommunication circuit applications requiring

More information

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers Medium-voltage vacuum circuit breakers Catalog information Medium-voltage vacuum circuit breakers catalog Technical Data Effective

More information

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite

More information

COOPER POWER CA280012EN

COOPER POWER CA280012EN Reclosers Catalog Data CA280012EN Supersedes May 2014 (290-25) COOPER POWER SERIES Type VSA20B air-insulated, vacuum, electronically Description The Type VSA20B electronically controlled, vacuum circuit

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

Expulsion Fuses. 2.2 Fuse Selection. 2.3 Application. 2.4 BA Type Fuses. 2.5 DBA Type Fuses. 2.6 DBU Type Fuses. 2.7 RBA and RDB Type Fuses

Expulsion Fuses. 2.2 Fuse Selection. 2.3 Application. 2.4 BA Type Fuses. 2.5 DBA Type Fuses. 2.6 DBU Type Fuses. 2.7 RBA and RDB Type Fuses Expulsion Fuses Eaton Expulsion Fuses.1 Product Overview Product Description....................................... Accessories............................................. Catalog Numbers.........................................

More information

Recommended Procedures

Recommended Procedures Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that

More information

POLYFUSE Resettable PTCs Surface Mount > 2920L Series

POLYFUSE Resettable PTCs Surface Mount > 2920L Series Surface Mount > Description The device provides surface mount overcurrent protection for medium voltage ( 60V) applications where resettable protection is desired. Features Agency Approvals AGENCY AGENCY

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

Selection Guide. HHD-BPT, DIN Style, Current-Limiting, Back-Up, Potential Transformer Protection

Selection Guide. HHD-BPT, DIN Style, Current-Limiting, Back-Up, Potential Transformer Protection HHD-BPT Selection Guide HHD-BPT, DIN Style, Current-imiting,, Potential Transformer Protection Current ratings [A]; 0.5, 1, 2, 2.5, 3.15, 4, 5 E=192mm Page E=292mm Page E=367mm Page E=442mm Page E=537mm

More information

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka)

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka) Surge s UltraSIL Polymer-Housed VariSTAR Surge s: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka) Electrical Apparatus 235-35 General Cooper Power Systems has set the standard

More information

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX File: PCUP-09-002_EX Outdoor Use Indoor Use The Trans-Guard EX full-range current-limiting capacitor fuse provides both low and high current fault protection in a single, compact fuse body. As a full-range

More information

A 1.2 kv class externally removable secondary bushing

A 1.2 kv class externally removable secondary bushing OEM Equipment Catalog Data CA800018EN Supersedes July 2015 COOPER POWER SERIES 3010-4515 A 1.2 kv class externally removable secondary bushing General Eaton s Cooper Power series 3010-4515 A externally

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Protective Device Coordination ETAP Star

Protective Device Coordination ETAP Star Protective Device Coordination ETAP Star Agenda Concepts & Applications Star Overview Features & Capabilities Protective Device Type TCC Curves STAR Short-circuit PD Sequence of Operation Normalized TCC

More information

M-Force three-phase switch

M-Force three-phase switch Supersedes K-SEC 926 December 2012 M-Force three-phase switch Description The M-Force switch from Eaton's Cooper Power Systems is a distribution-class, gangoperated, factory unitized three-phase overhead

More information

Low-Peak 600V Class RK1

Low-Peak 600V Class RK1 LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:

More information

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products Hi-Tech SX Full-Range Current-Limiting Fuses Provides both overload and fault current protection for distribution equipment in a single fuse body. Trans-Guard SX Full-Range Current-Limiting Fuse As a full-range

More information

Application of Primary Fuses

Application of Primary Fuses Application of Primary Fuses Introduction The wide variety of fuse links offered by the A.B. Chance Company is instrumental in reducing the many problems facing today s coordination engineers. Besides

More information

Eaton s Cooper Power Systems

Eaton s Cooper Power Systems Page: 1 of CERTIFIED TEST REPORT Eaton s Cooper Power Systems 600 Amp - 35 kv Class Deadbreak Bushing With Internal Ground Screen Design Qualification Tests December 17, 2013 Supersedes 10/20 2013 Eaton

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse LPSRK100SP 600V TD Dual Elem Class RK1 Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK100SP 600V Class RK1 Low Peak Dual Element, Time Delay Fuse 0.4100 (lbs/each)

More information

Tolerance-Based Time-Current Coordination

Tolerance-Based Time-Current Coordination S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Tolerance-Based Time-Current Coordination Table of Contents Section Page Section Page Overview Background....

More information

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are

More information

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB

More information

Using Fuses to Provide Fault Protection of Windfarm Transformers

Using Fuses to Provide Fault Protection of Windfarm Transformers Using Fuses to Provide Fault Protection of Windfarm Transformers Dan Gardner R&D Manager, Hi-Tech Fuses, Thomas & Betts John G. Leach Consultant, Hi-Tech Fuses Abstract A rising concern among utilities

More information

Semiconductor Fuses European Fuses

Semiconductor Fuses European Fuses 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection - rated current (or ) I N - pre-arcing I²t (I²t p ) at ms - total ope I²t (I²tt) at 66 V, cos

More information

onlinecomponents.com

onlinecomponents.com 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection Rated current Pre-arcing I²t Total I²t at 66VAC I N (A) I²t p (A²s) I²t (A²s) - rated current

More information

WATT MBH SERIES DC/DC CONVERTERS

WATT MBH SERIES DC/DC CONVERTERS Features Delivers up to 2100 Watts Efficiency up to 97 Groundbreaking low profile compact 9.0 L x 6.5 W x 1.25 H package Only 3.3 lbs No minimum load required Fixed frequency operation at 400 khz Fully

More information

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT COS 38kV 100A 8kA asym. Type PGC Parallel groove terminal bronze with tin plated NEMA Bracket type B Upper contact copper with silver plated Cap - Cast bronze

More information

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

43-SDMS-04 REV. 00 SPECIFICATIONS FOR 43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser Reclosers Catalog Data CA280008EN Supersedes 280-45 July 2014 COOPER POWER SERIES Types VSA12, VSA12B, VSA16, VSA20, and ; three-phase; air-insulated; electronically controlled recloser VSA16 recloser

More information

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE.

RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE. RESPONSE OF A MEDIUM VOLTAGE CURRENT LIMITING FUSE OF SMALL SIZE TESTED AS GENERAL PURPOSE AND FULL- RANGE TYPE. Alfonso Avila Ramírez. Corporativo Arian, S.A. de C.V., Hidalgo 6 Santa Ana Tlacotenco,

More information

Prüffeld der Schaltwerke

Prüffeld der Schaltwerke Report No.: 16-043-MS Sheet: 2 Notes 1. The testing station of the Siemens switchgear factory (Prüffeld der Schaltwerke),, Berlin, has been approved by the DAkkS (German accreditation body) for rendering

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES SERIES E-RATED / MEDIUM VOLTAGE FUSES 5kV AND 15kV CLIP-LOCK MOUNTED FUSES Amp-trap E-rated 5kV and 15kV fuses have 3" diameter barrels and mount in unique cam-locking clips, for superior connections as

More information