REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs)

Size: px
Start display at page:

Download "REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs)"

Transcription

1 <. elastimoldo Thomaslaletts R&D Center 497 Schooley's Mountain Road Hackettstown, NJ Tel: Fax: TEST REPORT NUMBER: # DATE: REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs) Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual limits of commercial testing practices. Prepared by P.E. 17dL~ 7;~1 Approved.Project Dan Director Gardner Leader of Engineering, Title by This information is transmitted subject to the following understanding and agreement: By acceptance of this document you agree that all rights to the information contained herein, as well as the proprietary novel features of the subject matter are reserved by Thomas and Betts Corporation and that devices embodying such features or information derived from these disclosures will not be manufactured by or for you, or disclosed to others without our express written consent. This test report and other information are and remain the property of Thomas and Betts Corporation and are not to be copied, reproduced or disclosed to others without our express written consent.

2 ADMINISTRATIVE DATA 1.0 Purpose Type, Quantity Security Place(s) Manufacturer Disposition Drawing, Date(s) Part Test(s) Classification of or Specification or Items ofmodel Specimens Conducted Tested No. of or Items Exhibit Certification Thomas 3188C0110, Various Powertech N/A MVRx-xx-xx-xx EXTERNAL IEEE & refer Betts Labs, C , 3188C0111, of- the 2012 to- BC specific USE Elastimold I Lapem 3188C0112, IEC subsection Labs, 15/27/38kV C0113, MX I Molded 3188C0114, Vacuum Thomas&Betts Reclosers 3188C0115,3188C0116 R&D(MVRs) Center, NJ Page 2 of 10

3 SECTION 6.2 Insulation (dielectric) tests To demonstrate dry power frequency withstand capability, wet power frequency withstand capability, and lightning impulse withstand capability. Testing was conducted in accordance with IEEE C Section 6.2. Each dry power frequency withstand test was performed at 60Hz at 60kVrms for 1 minute on a 15/27kV MVR and at 70kVrms for 1 minute on a 38kV MVR. Each wet power frequency withstand test was performed at 60Hz at 50kVrms for 1Osec on a 15/27kV MVR and at 60kVrms for 1Osec on a 38kV MVR. Each lightning impulse withstand test was performed at 150kV pk on a 15/27kV MVR and at 170kV pk on a 38kV MVR. All testing was successful. voltage in all configurations Both the 15/27kV and the 38kV units withstood for all tests. The 15/27kV MVR meets the requirements of dry and wet power frequency withstand capability per IEEE C Section 6.2. The 38kV MVR meets the requirements of dry and wet power frequency withstand capability per IEEE C Section 6.2. The 15/27kV MVR exceeds the lightning impulse withstand requirement specified in IEEE C Section 6.2. capability The 38kV MVR exceeds the lightning impulse withstand capability requirement specified in IEEE C Section 6.2. Certified and approved by:4 Tests performed at ThomasBSetts R&D Center, Hackettstown, NJ Ref # Page 3 of 10

4 Switching, SECTIONS 6.3/6.4/6.5 Making Current Capability, and Rated Symmetrical Interrupting Current Tests To demonstrate duty tests. load switching, fault making current capability, and operating Testing was conducted in accordance with IEEE C Sections 6.3, 6.4, and 6.5. Each unit tested was installed in accordance a SEL 651 R control at Powertech Labs. with the standard and operated with The 15/27kV unit was tested as a single phase device at 29.3kV with a load switching rating of 800A and a maximum symmetrical fault interrupting rating of 12.5kA. The 38kV unit was tested as a three phase device at 38kV with a load switching rating of 800A and a maximum symmetrical fault interrupting rating of 12.5kA. The reclose sequence for all tests was O-CO-CO-CO using the fastest sequence settings allowed on the SEL 651 R with the first shot using the instantaneous trip "A" curve and the remaining operations on the delayed operation "c" curve. All testing was successful. according to the standard. Both the 15/27kV and the 38kV units passed all tests The 15/27kV testing is documented on Powertech Test Report # The 38kV testing is documented on Powertech Test Report # The 15/27kV MVR meets the requirements of a single phase recloser with a continuous current rating of 800A and a rated maximum symmetrical interrupting current of 12.5kA per IEEE C Sections 6.3,6.4, and 6.5. The 38kV MVR meets the requirements of a three phase recloser with a continuous current rating of 800A and a rated maximum symmetrical interrupting current of 12.5kA per IEEE C Sections 6.3, 6.4, and 6.5. Certified and approved by: ~I~ q Tests performed at Powertech Labs, Surrey, BC Ref # and # Page 4 of 10

5 SECTIONS 6.6 & 6.11 Minimum Tripping and Time-Current Tests To demonstrate the minimum tripping current and the time-current curve accuracy of the Elastimold MVR with the SEL controls. Testing was conducted in accordance with IEEE C Sections 6.6 and 6.11 using a SEL 351 RS-Kestrel control. Minimum tripping level on the SEL 351 R-Kestrel control was set to 50A. Current was injected into the recloser starting at 80% of the trip level and ramping slowly over a period greater than 1Osec and the trip level was recorded. Minimum tripping level was then changed to 500A and the delayed operation curve "C" was selected. This allowed verification of the tripping curve over the full range of currents. Time-current curve accuracy was tested at a variety of currents between 50A and 12.5kA by injecting current into the recloser and monitoring the tripping time. Minimum trip values recorded all fell within the +/-10% requirement standard. of the All time-current trip curve tests resulted in a trip initiation within +/-10% of the published SEL curve. The Elastimold MVR, when controlled by a SEL control, meets the rated minimum tripping current requirement and the time-current requirement per IEEE C Sections 6.6 and Certified and approved by:, /Z1M Tests performed at Thomas & Betts R&D Center, Hackettstown, NJ Ref # Page 5 of 10

6 SECTION 6.7 Partial Discharge (Corona) tests To demonstrate partial discharge test capability of the Elastimold MVR. Testing was conducted in accordance with IEEE C Section 6.7. Tests were performed in three configurations on a 15/27kV unit and a 38kV unit: 1. Contacts closed and energized with the housing grounded. 2. Contacts open with the side terminal energized and the top terminal and the housing grounded. 3. Contacts open with the top terminal energized and the side terminal and housing grounded. The maximum LN voltage was applied for at least 30sec (VLN MAX). Then each unit was stressed for at least 60 sec at an elevated voltage (VSTRESS).Then the voltage was dropped to 105% VLN MAX and the partial discharge value was recorded. For 15/27kV units: VLN MAX = 16.9kV, VSTRESS= 34kV, 115% VLN MAX = 17.8kV Observed pc values were less than 3pC in all configurations. For 38kV units: VLN MAX = 21.9kV, VSTRESS= 40kV, 115% VLN MAX = 23kV Observed pc values were less than 3pC in all configurations. Partial discharge results were deemed acceptable as all values observed at 105% VLN MAX were less than 60pC after stressing the units. N Tests Certified performed and approved at Thomas by: ~jtt & eus R&D Center, Hackettstown, NJ Ref # Page 6 of 10

7 SECTION 6.10 Temperature Rise tests To demonstrate current. that the Elastimold MVR is capable of carrying 800A continuous Testing was conducted in accordance with IEEE C Section Testing was performed using 1000kcmil bare copper conductor. Current was injected into a unit and component temperatures were allowed to reach steady state. Contact temperatures were measured at four locations: top contact of the vacuum bottle, bottom contact of the vacuum bottle, top terminal lug, side terminal lug. The ambient temperature was also measured. Ambient = 25C Top contact of vacuum bottle = 92.4C (67.4C rise) Bottom contact of vacuum bottle = 83.2C (58.2C rise) Top Terminal = 78.2C (53.2C rise) Side Terminal = 76.5C (51.5C rise) Terminal to terminal resistance was also recorded at the end of the test at J0hms. Max allowable temperature rise for the bottle contacts was 75C. Max allowable temperature rise for the terminals was 65C. All temperature readings and resistance readings were within limits showing that the Elastimold MVR is capable of carrying 800A continuously. Certified and approved by: '- /'14 Tests performed at Thomas & Betts R&D Center, Hackettstown, NJ Ref # Page 7 of 10

8 SECTION 6.12 Mechanical Duty tests To demonstrate the mechanical durability of the Elastimold MVR. Testing was conducted in accordance with IEEE C Section An Elastimold MVR was cycled using a SEL 351 RS-Kestrel control and a PLC based cycling circuit. The cycling circuit was set to initiate an operation every 10 sec. 10,000 close-open operations were performed. Resistance readings were taken before and after the cycling. Upon completion of the test, the recloser was examined for loosening or degradation of parts. The unit was also hi-potted for 60 sec. No loosening of parts or substantial degradation of components was observed during or after the test. Terminal to terminal resistance prior to the test was 93jJohms. After the test the resistance was 117jJohms. The unit also successfully passed hi-pot testing at 60kVrms for 60sec. The Elastimold MVR exceeds the requirements set in the standard for mechanical duty testing. Certified Tests performed and approved at Thomas by: ~ & etts R&D Center, JL( Hackettstown, NJ Ref # Page 8 of 10

9 SECTION 6.13 Surge Withstand Capability (SWC) tests To demonstrate the oscillatory and fast transient surge withstand capability and to demonstrate the simulated surge arrester operation withstand capability of the Elastimold MVR and the SEL 351 RS-Kestrel and SEL 651 R controls. Testing was conducted in accordance with IEEE C Section 6.13 at Powertech Labs. All units were tested as 38kV devices. Testing was performed on the Elastimold MVR with each type of control specified above per the standard. The Elastimold MVR and the SEL 351 RS-Kestrel operated normally after the testing. Detailed results can be found in detail in Powertech Test Report # The Elastimold MVR and the SEL 651 R operated normally after the testing. Detailed results can be found in detail in Powertech Test Report # The Elastimold MVR meets the requirements of the standard when used with the SEL 351 RS-Kestrel and the SEL 651 R controls. Certified and approved by: ~ M Tests performed at Powertech abs, Surrey, BC Ref # Page 9 of 10

10 OTHER UV/Weathering tests To evaluate the UV/weatherability of Elastimold's 370 silicone and 935 EPDM compounds in accelerated aging tests and to demonstrate their tracking resistance via salt fog testing. Samples of the 935 and 370 materials were prepared and exposed to varying amounts of UV radiation, heat, water spray, and humidity for varying time periods up to 1000 hours. Field aged samples were also placed and evaluated. Physical properties and/or electrical properties of these materials were tested before and after the aging cycles and the results compared. Salt fog testing was performed at Powertech per IEC on 38kV MVR modules. The sample was run for 1600hrs with the bottle contacts closed and energized at 22kV and the housing grounded. Weathering characteristics of both the 935 EPDM High Voltage insulation and the 370 Silicone High Voltage insulation compounds passed field and accelerated aging tests. Water submersion and UV testing showed no significant loss in dielectric strength for either material. Both of these materials have been used extensively in products placed in the field for many years, and experience in manufacturing products with these materials confirms that a long outdoor service life is expected from parts produced from these compounds. Both materials have superior performance versus a control EPDM sample. The unit that was salt fog tested successfully in Powertech Labs Test Report # passed 1,600hr testing as detailed The Elastimold MVR is suitable for extended outdoor use and shows good UV/weatherability characteristics when the side terminal, the top shed, and the bottom shed are made from Elastimold 370 and the main body is made of Elastimold 935 EPDM. The MVR also meets salt fog requirements for 1600hrs at 22kV as specified in IEC ~11f Certified and approved by:. Tests performed at Powerte tabs, Surrey, BC at the Thomas & Betts R&D Center Ref # and # Page 10 of 10

600 Amp Surge Arrester

600 Amp Surge Arrester R&D Center 497 Schooley s Mountain Road Hackettstown, NJ 07840-3906 Tele: 908-852-1122 Fax: 908-813-2091 TEST REPORT NUMBER: 379-17-12164 DATE: 4-3-2012 REPORT OF TEST ON 600 Amp Surge Arrester Statements

More information

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV The recloser you want, all in one package. Single- and Three-Phase, 15 38kV The need for automated reclosers has never been greater, but many of today s reclosers come with penalties. They weigh too much,

More information

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series 3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series Data Sheet 1. Product Description 3M Cold Shrink Termination Kit QT-III 7672-S-8 Series contains one silicone rubber termination

More information

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester

ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester ANSI DESIGN TEST REPORT Report No. EU 1512-HR-00.5 Type PDV 100 Optima Heavy Duty Distribution Class Surge Arrester This report records the results of the design tests made on Type PDV 100 Optima Distribution

More information

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number: 25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report Report Number: Date: RN-R7604 9/16/2013 Table of Contents I. OBJECTIVE... 2 II. SUMMARY... 2 III. CONCLUSION... 2 IV. CABLE DATA... 2 V.

More information

VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY

VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY VEIKI-VNL Ltd. VEIKI-VNL Electric Large Laboratories Ltd. is an independent accredited testing member laboratory of

More information

Solid Dielectric, Single Phase Recloser

Solid Dielectric, Single Phase Recloser Solid Dielectric, Single Phase Recloser Catalog O-vsp17 Viper-SP Viper-SP solid dielectric, single phase recloser combines the time-proven reliability of electronically controlled, vacuum fault interrupters

More information

Molded Current-Limiting Fuse

Molded Current-Limiting Fuse Molded Current-Limiting provide fullrange fault current protection using specially designed fuse elements, rated through 23kV line to ground and 50kA interrupting current. Construction is modular with

More information

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number: 15kV 200A Loadbreak Fuse Elbow Design Test Report Report Number: Date: RN-R2601 9/3/2015 Table of Contents 1. Partial Discharge Test Fuse Elbow... 2 2. AC Withstand Voltage Test - Fuse Elbow... 3 3. DC

More information

TEMPERATURE RISE TESTS

TEMPERATURE RISE TESTS CP No.: CP0511 Rev. 01 Page: 1 of 6 CERTIFIED TEST REPORT TEMPERATURE RISE TESTS Type CMU Power Fuses REV. 01 DATE: August 12, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems, Inc. CP No.:

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 120-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 120-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 120-0.3

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 60-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 60-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 60-0.3

More information

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12 16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting

More information

Solid Dielectric, Single Phase Reclosers

Solid Dielectric, Single Phase Reclosers Solid Dielectric, Single Phase Reclosers Providing electronic overcurrent protection for single phase operation on systems rated through 38kV, 800A continuous current,12.5ka symmetrical interrupting Reliable

More information

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C CP No.: CP1101 Rev. 00 Page: 1 of 9 CERTIFIED TEST REPORT 8.3, 9.9, 15.5, 17.2 and 23 Cooper ELSP Backup Fuses Testing per C37.41-2008 Rev. 00 DATE: May 3, 2011 ORIGINAL REPORT DATE: May 3, 2011 Cooper

More information

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com TGOOD produces over 5000 switchgear units annually for projects around the globe SOLUTION OVERVIEW For use in affordable air insulated

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

Edison modular fuse, vault application products

Edison modular fuse, vault application products Fusing Equipment Catalog Data CA132025EN Supersedes 240-92 October 2008 Edison modular fuse, vault application products COOPER POWER SERIES Description Eaton s Cooper Power series Edison modular fuses

More information

Eaton s Cooper Power Systems

Eaton s Cooper Power Systems Page: 1 of CERTIFIED TEST REPORT Eaton s Cooper Power Systems 600 Amp - 35 kv Class Deadbreak Bushing With Internal Ground Screen Design Qualification Tests December 17, 2013 Supersedes 10/20 2013 Eaton

More information

Product Description: Objective and Certification: Test Samples and Test Cable:

Product Description: Objective and Certification: Test Samples and Test Cable: Product Description: The CableMate 2LBE loadbreak elbow connector and 2LBI loadbreak bushing insert are fully-shielded, fully submersible, insulated plug-in terminations for connecting underground cables

More information

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv 3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv Data Sheet September 2014 Description 3M Cold Shrink QT-III Silicone Rubber Termination Kits, 7640-T

More information

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE H U B B ELL L ABO R ATO R I E S CAPABILITY GUIDE INTRODUCTION Hubbell Power Systems, Inc. manufactures a wide variety of products for the electric utility, telecommunications, civil construction, transportation,

More information

High Voltage Technology & Testing

High Voltage Technology & Testing The Power of Trust. The Future of Energy. HIGH VOLTAGE TESTING Qualification testing, condition assessment, and forensic analysis Manufacturers and utility users of high-voltage electrical equipment face

More information

your Green Power WIND POWER SOLUTIONS only Greener

your Green Power WIND POWER SOLUTIONS only Greener your Green Power WIND POWER SOLUTIONS only Greener WIND POWER SOLUTIONS Thomas & Betts is committed to being your partner in power delivery by leading the industry in innovative wind power solutions and

More information

Surge arrester POLIM-H..SD

Surge arrester POLIM-H..SD Data sheet Surge arrester POLIM-H..SD Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-B High current impulse I hc (4/10

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION Surge Arresters UltraSIL Housed VariSTAR Station Class Surge Arresters Electrical Apparatus 235-88 GENERAL Cooper Power Systems has set a new standard of excellence for polymerhoused station class surge

More information

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide 1ZSE 2750-112 EN, REV. 4 Wall bushings type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report File Ref: CA132015EN Effective Mar 2015 COOPER POWER CT132001EN SERIES 38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report CT132001EN Page: 3 of 9 Introduction Eaton designs its Cooper

More information

Wind Power Solutions. Make Energy Renewable and Reliable!

Wind Power Solutions. Make Energy Renewable and Reliable! Wind Power Solutions Make Energy Renewable and Reliable! Reliable Thomas & Betts Products for Clean, Green, Thomas & Betts makes all the products that connect and protect a wind farm and its power distribution

More information

Prüffeld der Schaltwerke

Prüffeld der Schaltwerke Report No.: 16-043-MS Sheet: 2 Notes 1. The testing station of the Siemens switchgear factory (Prüffeld der Schaltwerke),, Berlin, has been approved by the DAkkS (German accreditation body) for rendering

More information

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS

37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS

More information

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide 1ZSC563-AAA EN, REV. 7 Transformer bushings type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Product Group Brochure. PS Range Capacitor Vacuum Switches

Product Group Brochure. PS Range Capacitor Vacuum Switches Product Group Brochure PS Range Capacitor Vacuum Switches Introduction ABB introduces the latest range of PS capacitor vacuum switches. Building on the proven PS switch design, new single phase and three

More information

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM CP No.: CP9806 Page: 1 of 35 CERTIFIED TEST REPORT Cooper Power Systems 25 kv Class 200 Amp SEPARABLE CONNECTOR SYSTEM Includes Cooper POSI-BREAK Loadbreak Elbow and Insulated Protective Cap April 3, 1998

More information

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL Surge Arresters UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 Electrical Apparatus I235-93 GENERAL UltraSIL Polymer-Housed VariSTAR

More information

Faulted Circuit Interrupting Tests on Type CMU Power Fuses

Faulted Circuit Interrupting Tests on Type CMU Power Fuses CP No.: CP0508 Rev. 01 Page: 1 of 9 CERTIFIED TEST REPORT Faulted Circuit Interrupting Tests on Type CMU Power Fuses REV. 01 DATE: August 10, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems,

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features Surge s Electrical Apparatus 235-99 General Cooper Power Systems set the standard for design, manufacturing and delivery of polymeric distribution arresters with the UltraSIL polymerhoused arrester family.

More information

CERTIFIED TEST REPORT

CERTIFIED TEST REPORT CP No.: CP0316 Rev. 01 Page: 1 of 22 CERTIFIED TEST REPORT COOPER POWER SYSTEMS FOUR POSITION SECTIONALIZING LOADBREAK SWITCH 12.5 ka Momentary and Making Rating REV. 01 DATE: December 3, 2004 ORIGINAL

More information

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C Page:1 of 9 CERTIFIED TEST REPORT Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C37.41-2008 REV. 00 August 11, 2014 Original Report Date: August 11, 2014 Eaton s Cooper Power Systems

More information

HIGH VOLTAGE SURGE ARRESTER SPECIFICATION

HIGH VOLTAGE SURGE ARRESTER SPECIFICATION HIGH VOLTAGE SURGE ARRESTER SPECIFICATION Applications: (Polymer housed MOA for 110kv) (The polymer housed MOA for 10kv) (Porcelain housed MOA for 220kv) (35kv MOA without gaps for middle phase) (110kv

More information

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

solutions RUS accepted

solutions RUS accepted Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting

More information

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4)

VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC (99-4) CP9817 PAGE: 1 of 16 CERTIFIED TEST REPORT VariSTAR Type AZG2 Surge Arrester, 10,000 A, Line Discharge Class 2 IEC 60099-4 (99-4) 0711 Supersedes 0601 Cooper Industries. All Rights Reserved. CP9817 PAGE:

More information

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A 3M Cold Shrink QS-III Inline Splice Kits 15 kv Data Sheet June 2014! CAUTION Working around energized high-voltage systems may cause serious injury or death. Installation should be performed by personnel

More information

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv SF6 circuit breaker EDT with integrated current transformer ABB is a world leader in live tank circuit breaker

More information

Surge arrester POLIM-H.. ND

Surge arrester POLIM-H.. ND DATA SHEET Surge arrester POLIM-H.. ND Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-B High current impulse I hc (4/10

More information

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable 3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable Data Sheet September 2010 Description 3M Cold Shrink 3-Conductor

More information

Transformer bushings, type GOH. Technical guide

Transformer bushings, type GOH. Technical guide Transformer bushings, type GOH Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required

More information

Cobra-S. Catalog Cobra-S

Cobra-S. Catalog Cobra-S Cobra-S Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5/16kA symmetrical interrupting Control

More information

Faulted Circuit Interrupting Tests on Type CMU Power Fuses

Faulted Circuit Interrupting Tests on Type CMU Power Fuses CP No.: CP0509 Rev.01 Page: 1 of 9 CERTIFIED TEST REPORT Faulted Circuit Interrupting Tests on Type CMU Power Fuses REV. 01 DATE: August 10, 2005 ORIGINAL REPORT DATE: May 25, 2005 Cooper Power Systems,

More information

power cable accessories

power cable accessories power cable accessories kv up to 4 kv Completing the picture based on experience is the future nkt cables GmbH NKT was established in 89 as cable manufacturer. In 999 NKT A/S Denmark merged with Felten

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate

More information

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress.

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress. Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress. George Fofeldea Power Engineer, 3M Canada August 2018 Abstract 3M invented cold shrink

More information

GENERAL. CONSTRUCTION External

GENERAL. CONSTRUCTION External Surge Arresters VariSTAR Type AZG4 Surge Arresters for Systems through 400 kv IEC 20-kA; Line Discharge Class 4 Electrical Apparatus I235-84 GENERAL VariSTAR AZG4 Surge Arresters incorporate the latest

More information

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv

Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series kv Cold Shrink Silicone Rubber Termination Kit QT-III 7620-S, 7690-S and 7680-S Series 5-34.5 kv Data Sheet 1.0 Product Description 3M Cold Shrink Silicone Rubber Termination Kit QT- III 7620-S, 7690-S and

More information

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide 1ZSC000563-AAC en, Rev. 2 Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers,

More information

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

Solid Dielectric, Triple Option Reclosers Catalog O-vst14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting

More information

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide 1ZSE 2750-112 en, Rev. 3 Wall bushings, type GSA-AA Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications.

More information

Independent Testing Laboratory for High Voltage Equipment

Independent Testing Laboratory for High Voltage Equipment T E S T I N G L A B O R A T O R Y Independent Testing Laboratory for High Voltage Equipment 1 CHALLENGING ENVIRONMENT The primary concern for utilities is to ensure grid reliability, efficiency, and security.

More information

Loadbreak Apparatus Connectors

Loadbreak Apparatus Connectors Loadbreak Apparatus Connectors 200 A 25 kv Class POSI-BREAK Loadbreak Elbow Connector with Optional Integral Jacket Seal* Electrical Apparatus 500-29-7 general The POSI-BREAK Loadbreak Elbow Connector

More information

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide 1ZSC563-AAA en, Rev. 6 Resin impregnated paper bushing, oil to SF 6, type GSBK Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society Guideline No.: E-07(201501) E-07 TRANSFORMERS Issued date: October 20,2015 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation Elastimold solid dielectric switchgear agenda Compelling value Design principles Product overview Switchgear applications

More information

600 A 15 kv class T-OP II deadbreak connector

600 A 15 kv class T-OP II deadbreak connector Deadbreak Apparatus Connectors CA650017EN Supersedes 600-12 February 2010 COOPER POWER SERIES 600 A 15 kv class T-OP II deadbreak connector General Eaton terminates high-voltage underground cable to transformers,

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society Guideline No.: E-07(201610) E-07 TRANSFORMERS Issued date: October 28,2016 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection and

More information

25 kv Apparatus Bushings

25 kv Apparatus Bushings Page 1 2001 ELRIM Cycloaliphatic Epoxy Provides: Nontracking, self-scouring, nonweathering performance Superior dielectric strength, dielectric loss and power factor Choice of shapes allows design innovation

More information

Surge arrester POLIM-C.. HD

Surge arrester POLIM-C.. HD DATA SHEET Surge arrester POLIM-C.. HD Technical data Classification according to EN 50526-1 and IEC 62848-1 Nominal discharge current I n (8/20 µs) 10 ka peak Class DC-A High current impulse I hc (4/10

More information

OVR Three Phase Recloser 15 kv - 38 kv. Descriptive Bulletin

OVR Three Phase Recloser 15 kv - 38 kv. Descriptive Bulletin OVR Three Phase Recloser 15 kv - 38 kv Descriptive Bulletin Always a Generation Ahead ABB continually strives to bring customers the latest technological advances and superior performance. This is especially

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection

More information

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

Solid Dielectric, Three Phase Reclosers Catalog O-vs18 Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society Guideline No.: E-07(201712) E-07 TRANSFORMERS Issued date: December 26, 2017 China Classification Society Foreword: This Guide is a part of CCS Rules, which contains technical requirements, inspection

More information

IEC Separable Connectors 17.5 kv/24 kv, 630A

IEC Separable Connectors 17.5 kv/24 kv, 630A IEC Separable Connectors 17.5 kv/24 kv, 630A Front T-Body / Coupling (Rear) T-Body Connector Application The Chardon T-Body connectors are used to terminate polymeric cable to dead front apparatus such

More information

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV December, 1975 New nformation and Supersedes DB 38-131 Pages 1-4, dated May 1972, and 38-121 D WE A, Pages 1-4, dated April1974 E, D, C/1981/ DB Westinghouse Electric Corporation Distribution Apparatus

More information

600 A 25 kv class BT-TAP deadbreak connector

600 A 25 kv class BT-TAP deadbreak connector Deadbreak Connectors Catalog Data CA650001EN Supersedes January 2015 600 A 25 kv class BT-TAP deadbreak connector COOPER POWER SERIES General Eaton terminates high-voltage underground cable to transformers,

More information

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection 35 kv Separable Insulated Connector (elbow) Bus Bar or Other Component Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other

More information

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series 3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series Data Sheet March 2011 Description 3M Cold Shrink 1/C Transition Splice Kits QS-III, 5510A-1T-PILC Series (which includes 5513A-1T-PILC,

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable ELRIM Cycloaliphatic

More information

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC Characteristics time delay relay 2 functions - 0.02 s..300 h - 24..240 V AC - 2 OC Complementary Product front plate size Control type Housing material Main Range of product Product or component type Electrical

More information

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features: Issue Date: 07/17/2017 Page: 1 of 5 PSS- K656LR Elbow Connector (with Test ) Applications: The Elastimold K656LR (with test point) is designed to provide fully shielded, dead-front submersible cable connections

More information

MEDIUM VOLTAGE NETWORKS

MEDIUM VOLTAGE NETWORKS MEDIUM VOLTAGE NETWORKS LIGHTNING ARRESTERS & INSULATORS SICAME GROUP OUR EXPERIENCE With 25 years of experience in the field of over protection for medium lines, DERVASIL designs and manufactures zinc

More information

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description Quick Splice II 5461 (CN) Cable (JCN) Cable 35 kv Molded Rubber Inline Splicing Kit Data Sheet Accessory Splice Jacket 1. Product Description The 3M 5461 Quick Splice II is a 35 kv class inline splice

More information

ZX2 Gas-insulated medium voltage switchgear

ZX2 Gas-insulated medium voltage switchgear Gas-insulated medium voltage switchgear Double busbar 13 8 10 12 11 10 9 8 7 2 1 3 4 5 6 2 Versatile Partitioned single or double busbar system for all applications even with the most demanding parameters

More information

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses CP No.: CP9716 Rev. 02 Page: 1 of 9 CERTIFIED TEST REPORT Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses Rev. 02 DATE: June 3, 2010 ORIGINAL REPORT DATE: June 13, 1997 Cooper Power Systems,

More information

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp Page 1 2018 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 35 kv Separable Insulated Connector (elbow) Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other

More information

TABLE OF CONTENTS Page

TABLE OF CONTENTS Page TABLE OF CONTENTS Page Objective 3 Summary 3 Conclusion 3 Sample Preparation 4 Testing 4 Test Results 5 Summary of Test Results (Table 1) 6 Appendix I 7 Addendum 1 8 2 I. OBJECTIVE To evaluate the performance

More information

GROUP D. Switch & Protective device.

GROUP D. Switch & Protective device. GROUP D Switch & Protective device PYUNGIL Bldg., 147-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-0~3 FAX : 82-31-424-7300 www.pyungil.com Pole-mounted SF Insulated

More information

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn Surge arresters UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters electrical apparatus 235-75 General Cooper Power Systems has set a new standard of excellence for polymerhoused

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

Three-Phase Pole Mounted Recloser

Three-Phase Pole Mounted Recloser Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE

More information