SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION

Size: px
Start display at page:

Download "SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION"

Transcription

1 Fusing Equipment Tandem ELF Current-Limiting Dropout Fuse Electrical pparatus GENERL The Cooper Power Systems Tandem ELF current-limiting fuse is designed for transformer protection. The Tandem ELF fuse can be applied for fusing single-phase transformers and for fusing three-phase transformers (or three-phase banks of single-phase transformers). This fuse combines the features of a series fuse link and a backup current-limiting fuse in one convenient package. The Tandem ELF fuse (refer to Figure 1) includes a unique design for fast replacement of the backup current-limiting fuse after a high fault current operation. The fuse link holder is accessible for replacement of the fuse link after a low fault current operation or excessive transformer overload current. The fuse link holder of the Tandem ELF is specifically designed to accommodate standard Cooper Power Systems Type D (D-Link) and Kearney Type X (X-Link) high surge current fuse links. These fuse links make it possible to protect the transformer from damage due to overload, and at the same time gain increased surge current withstand capability over conventional fuse links to help eliminate nuisance fuse blowings. The Tandem ELF fuse uses the Cooper Power Systems Companion II (25K rated) backup current-limiting fuse (reference for more detailed information) to interrupt high magnitude fault currents. The backup currentlimiting fuse also limits the amount of energy let-through to the transformer, which prevents the possibility of a catastrophic tank rupture. TRNSFORMER OVERLOD PROTECTION The Tandem ELF fuse offers the ability to protect the transformer from damaging overload currents. The availability of a wide range of ampere rated Type D and Type X fuse links allows for the selection of a fuse link that has a melting characteristic that closely matches the NSI safe loading curve for the respective transformer. This allows for proper transformer protection, even for smaller kv rated transformers. Figure 1. Tandem ELF Current-Limiting Dropout Fuse (left: Tandem ELF in Type L cutout). SURGE DURILITY ND IMPROVED TRNSFORMER PROTECTION The Tandem ELF fuse is a surge durable transformer fuse particularly well suited for applications in high isokeraunic areas where there is a high probability of lightning surges. When it is used with the Surge Durable Cooper Power Systems D-Link or Kearney X-Link, the unit can withstand high surge currents that might be discharged through a surge arrester. Therefore, the surge arrester can be connected on the load side of the fuse and closer to the transformer. This shortens the lead length to the arrester and provides the best overvoltage protection. In this configuration, the Tandem ELF fuse is actually protecting the arrester as well as the transformer. This would not be possible with similar ampere ratings of conventional type links because of the high probability of damage due to the lightning surge current passing through the link. The benefits of high surge current withstand capability of the D-Link and X-Link are achieved without sacrificing the ability of the fuse links to provide overload protection for the transformer. ENHNCED POWER QULITY ND IMPROVED SERVICE CONTINUITY The Tandem ELF current-limiting fuse will enhance power quality of the system and improve the service continuity during high magnitude faults due to operation of the backup current-limiting fuse. The duration of the voltage dip associated with system short circuits will be limited to the short melt time of the current-limiting section of the Tandem ELF fuse. Immediately after melting, the arc voltage generated by the current-limiting fuse will support system voltage until the fault is interrupted by the fuse. For high fault currents, the duration of the voltage dip associated with the melt time of the current-limiting fuse will be well within the allowable limits for sensitive electronic equipment as defined by CEM curves. MINIMIZES EQUIPMENT DMGE The Tandem ELF s backup currentlimiting fuse will interrupt high magnitude fault currents while also limiting the amount of current and energy let-through to the transformer. The backup current-limiting fuse will limit the let-through current to minimize the October 1998 New Issue Printed in U.S.. 1

2 Tandem ELF Current-Limiting Dropout Fuse SILVER-PLTED UPPER CONTCT C UPPER PULL RING CONNECTOR llows for the use of a loadbreak tool to open and hookstick to close the fuse into the upper contact of an interchangeable cutout. PULL RING HIGH PURITY SILIC SND FILLER Specific particle size, purity and compaction gives the heat-absorbing and arc-quenching properties necessary for consistent clearing and low energy let-through levels. URETHNE COTED FIERGLSS REINFORCED EPOXY HOUSING Provides strength and maintains integrity of the fuse during any interruption. FUSE CP MIC SPIDER Provides stable winding support without generating gas and pressure buildup during fuse operation. HIGH-CURRENT CLERING SECTION The pure silver element remains stable under current cycling and thermal stress, providing consistent melt characteristics. The element effectively controls and limits both current and energy (I 2 t) let-through levels during interruption. CKUP CURRENT-LIMITING FUSE NMEPLTE Includes easy-to-read fuse voltage, current, interrupting ratings and catalog number. CKUP CURRENT-LIMITING FUSE The 25K Companion II fuse provides energy-limiting capability during a high magnitude fault operation up to 50 k. LIFTING EYE llows for the use of a hookstick to install the Tandem ELF fuse into the lower contact of an interchangeable cutout. FUSE LINK HOLDER llows the standard NSI/IEEE fuse links to be installed for operation during a low magnitude fault or overload current. TNDEM ELF FUSE NMEPLTE Includes easy-to-read fuse voltage ratings. It also includes the voltage rating of the compatible interchangeable cutout mounting. FUSE LINK Specifically designed to use the high surge current Type D and Type X fuse links to protect the transformer from overloads and provide increased surge current withstand capability. Figure 2. Line illustration of Tandem ELF fuse with dimensions. (Refer to Table 2.) 2

3 TLE 1 Tandem ELF Fuse - Electrical Characteristics Voltage Three-Phase Single-Phase Minimum Maximum Maximum Class Voltage Rating Voltage Rating Melt I 2 t Clear I 2 t Interrupting Current (kv) (kv) (kv) (k 2 sec) (k 2 sec) (k rms Symmetrical) TLE 2 Tandem ELF Fuse Dimensional Data (Refer to Figure 2) in Inches (mm) Cutout Rating Tandem ELF Voltage/IL Rating Voltage Class (kv) (kv) C 15/95 & (328) (289) 7.47 (190) 27/125 & (417) (378) 7.47 (190) 27/125 & (417) (378) 7.47 (190) possibility of transformer tank rupture from high magnitude internal faults or to minimize damage to the tank or bushing that might result from bushing flashovers. INSTLLTION The Tandem ELF fuse is designed to be mounted in 15 kv rated 95 kv and 110 kv IL or 27 kv rated 125 kv and 150 kv IL interchangeable open distribution cutouts. The applicable interchangeable cutouts include Cooper Power Systems Type L, S&C Type XS,.. Chance Type C, and Type ICX. The Tandem ELF fuse is easily single hotstick installed due to its small size. Refer to Service Literature Section S for more information on the installation and refusing instructions. PRODUCTION TESTS Tests are conducted on 100% of production TNDEM ELF fuses in accordance with Cooper Power Systems requirements. Physical Inspection I 2 t Testing of Companion II ackup Current-limiting fuses Resistance Testing of Companion II ackup Current-limiting fuses Helium Mass Spectrometer Leak Testing of Companion II ackup Current-limiting fuses TLE 3 Tandem ELF Fuse Voltage pplication System Voltage (kv) Recommended Tandem ELF Voltage Class Rating (kv) Nominal Maximum Wye Delta / / / / / / / / / / / / / / / / * 13.2/ / * * 14.4/ / * * * For single phase applications on delta systems, one Tandem ELF fuse of this rating is required in each phase. PPLICTION Voltage Rating Selection The Tandem ELF fuse has voltage ratings compatible with most common distribution voltages. The most common distribution voltages for different transformer connections are shown in Table 3. For system voltages other than those listed, consult your Cooper Power Systems representative. Current Rating Selection The current rating for the Tandem ELF fuse is dependent on the selected fuse link. Table 4 shows the recommendations for the selection of the Type D and Type X fuse link in single-phase and three-phase applications. The backup current-limiting fuse of the Tandem ELF fuse has a fuse rating of 25K, which means it can be used in series with a maximum of a 25 Type K fuse link. The continuous current capacity of this backup current-limiting fuse is 50. 3

4 Tandem ELF Current-Limiting Dropout Fuse Delta-Connected Primary Wye-Connected Primary N N N C C FIGURE FIGURE FIGURE C FIGURE D FIGURE E FIGURE F Figure 3. Schematic of primary voltage system connections. TLE 4 Type D and Type X Fuse Link* Recommendations for Distribution Transformers in Single-Phase and Three-Phase pplications (Refer to Figure 3 for primary voltage connections) /4160Y /8320Y Transformer Figs. and Fig. C Figs. D, E and F Figs. and Fig. C Figs. D, E and F Size per phase Rated Link Rated Link Rated Link Rated Link Rated Link Rated Link (kv) mps Rating mps Rating mps Rating mps Rating mps Rating mps Rating /12470Y 7620/13200Y 7970/13800Y Transformer Figs. and Fig. C Figs. D, E and F Figs. D, E and F Figs. D, E and F Figs. and Fig. C Size per phase Rated Link Rated Link Rated Link Rated Link Rated Link Rated Link Rated Link (kv) mps Rating mps Rating mps Rating mps Rating mps Rating mps Rating mps Rating /20800Y /24940Y Transformer Figs. D, E and F Figs. and Fig. C Figs. and Fig. C Figs. D, E and F Size per phase Rated Link Rated Link Rated Link Rated Link Rated Link Rated Link (kv) mps Rating mps Rating mps Rating mps Rating mps Rating mps Rating NOTE: Table shows recommended fuse ratings based on the use of Cooper Power Systems Tandem ELF fuse time current characteristics defined in R , June Recommendations provide overload protection (fusing ratio) between 200% and 300% rated load. Fusing Ratio = Fuse Min. Melt 300 sec. x 100 Transformer Full Load Current *Kearney Type X fuse links for 1/3 through 2 ratings and Cooper Power Systems Type D fuse links for 3 through 20 ratings. 4

5 ORDERING INFORMTION Selecting a Catalog Number To select a catalog number, determine the Tandem ELF fuse voltage and current rating from the PPLICTION SECTION on page 3. For Tandem ELF fuse ordering (including fuse link), choose the base catalog number from Table 5 and complete the number by selecting the appropriate fuse link code from Table 6. Example: T425KD To select a 15 kv Class Tandem ELF fuse with a 5 fuse link for a 95 kv or 110 kv IL interchangeable cutout. TLE 5 Tandem ELF Fuse Catalog Numbers (Includes all parts shown in Figure 4) Tandem ELF fuse Catalog Number Cutout Rating Voltage/IL Rating Tandem ELF Voltage Class Voltage Rating (kv) Interrupting Rating ase Fuse Link Code Weight lbs (kg) (kv) (kv) Three-Phase Single-Phase (k Sym.) Catalog Number Digits 6 and 7 15/95 & T425 Refer to Table (1.62) 27/125 & T4C25 Refer to Table (1.65) 27/125 & T9C25 Refer to Table (2.35) Notes: To order a Tandem ELF fuse without a Type D or Type X fuse link, leave digits 6 and 7 blank and order the base catalog number in Table 5. TLE 6 Tandem ELF Fuse- Fuse Link Current Rating Selection Current Fuse Fuse Link Rating Link Catalog () Code Number ONLY.33 X X CX DX EX FX GX HD FL3D3 4 JD FL3D4 5 KD FL3D5 7 LD FL3D7 10 MD FL3D10 15 ND FL3D15 20 PD FL3D20 dd the fuse link code to the end of the base catalog number in Table 5. FUSE CP (included with fuse link holder) TYPE D OR TYPE X FUSE LINK HRDWRE (included in hardware kit) UPPER PULL RING CONNECTOR (included in hardware kit) CKUP CURRENT-LIMITING FUSE HRDWRE (included in hardware kit) FUSE LINK HOLDER Figure 4. Tandem ELF fuse parts. TLE 7 Tandem ELF Fuse Replacement Parts Only Cutout Rating Tandem ELF Voltage/IL Rating Voltage Class Fuse Link Holder ackup Current-Limiting Hardware Kit* (kv) (kv) Catalog Number Fuse Catalog Number Catalog Number 15/95 & T400 FH8KV25K THWKIT 27/125 & T4C00 FH8KV25K THWKIT 27/125 & T9C00 FH17KV25K THWKIT * Hardware kit includes one upper pull ring connector, two bolts and two lock washers for installing the backup current-limiting fuse. 5

6 Tandem ELF Current-Limiting Dropout Fuse New Installations lncludes Type L Cutout Mounting and Tandem ELF Fuse To order Tandem ELF fuse and mounting: (1) Select base catalog number in accordance with desired cutout and Tandem ELF Fuse ratings using Table 8. (2) Complete the number by selecting the appropriate fuse link code from Table 9, and add it to the end of the chosen catalog number in Table 8. Example: To select a 27 kv Class Tandem ELF in a 27 kv, 125 kv IL Type L cutout with a 20 fuse link, (1) Select base catalog number L9CTP15 from Table 8 and (2) Select the fuse link code P from Table 9. Therefore order catalog number L9CTP15P. TLE 8 Tandem ELF Fuse Catalog Numbers New Installations* Type L Cutout Tandem ELF Voltage Ratings (kv) Voltage/IL Voltage Class Interrupting Rating ase Fuse Link Rating (kv) (kv) Three-Phase Single-Phase (k Sym) Catalog Number** Code 15/ L4TP12 Refer to Table 9 15/ L4TP12 Refer to Table 9 27/ L9CTP L9CTP15 Refer to Table 9 27/ L9DTP L9DTP15 Refer to Table 9 Notes: * Refer to Catalog Section for more detailed information on the Type L interchangeable cutout. lncludes mounting, Tandem ELF fuse and fuse link (if appropriate fuse link code added to catalog number). ** Standard unit includes tin-plated bronze parallel-groove connector and NEM Type crossarm mounting bracket. Refer to Table 10 Type L Cutout Connector/racket Options for optional connectors and brackets. Refer to Table 9 for fuse link current rating selection and add the fuse link code (digit 9) to the end of the catalog number in Table 8. If no fuse link desired, add 0 in digit 9 of the base catalog number. TLE 9 Type L Cutout With Tandem ELF Fuse Fuse Link Current Ratings Selection Digit 9 Fuse Link Code NONE C D E F G H J K L M N P Notes: 0 in digit 9 defines no fuse link supplied with the Tandem ELF fuse. Type L Cutout Connectors/rackets CONNECTORS For new installations, the Tandem ELF fuse is mounted in a Type L open distribution cutout. The Type L cutout includes, as a standard, a tin plated bronze parallel-groove connector. The parallel groove connector fits a conductor range of #8 solid to 250 MCM. Tin plated bronze eyebolt and large eyebolt connectors are also available. The eyebolt connector fits a conductor range of #8 solid to 2/0 stranded and the large eyebolt connector fits a conductor range of #6 solid to 250 MCM. Refer to Table 10 for the different connector catalog code options. RCKETS The Type L cutout is shipped with a NEM Type mounting bracket as a standard. Refer to Table 10 for the mounting bracket catalog numbering codes. TLE 10 Type L Cutout Connector/racket Options Catalog Number* 5 th Digit 6 th Digit Type L Cutout Connector/racket Description P 0 Includes parallel groove connector; deletes crossarm mounting bracket P 1 Includes parallel groove connector and NEM Type crossarm mounting bracket P 3 Includes parallel groove connector and extended crossarm mounting bracket E 0 Includes eyebolt connector; deletes crossarm mounting bracket E 1 Includes eyebolt connector and NEM Type crossarm mounting bracket E 3 Includes eyebolt connector and extended crossarm mounting bracket L 0 Includes large eyebolt connector; deletes crossarm mounting bracket L 1 Includes large eyebolt connector and NEM Type crossarm mounting bracket L 3 Includes large eyebolt connector and extended crossarm mounting bracket *Refer to Catalog Number in Table 8. 6

7 DDITIONL INFORMTION Refer to the following reference literature for application recommendations: S Tandem ELF Fuse Installation Instruction R Tandem ELF Fuse Time Current Characteristic Curves Companion II ackup Current-Limiting Fuse Catalog Section R Recommended D-Link Primary Fusing for Distribution Transformers Type L Open Distribution Cutout Catalog Section 7

8 ISO 9001:2000-Certified Quality Management System 1998 Cooper Power Systems, Inc. ELF and Kearney are trademarks of Cooper Industries, Inc. Companion is a registered trademark of Cooper Industries, Inc. P.O. ox 1640 Waukesha, WI Printed on Recycled Paper MI 10/98

Figure 1. ELSG Current-Limiting fuses. TABLE 1 Maximum Interrupting Current (rms symmetrical) INSTALLATION

Figure 1. ELSG Current-Limiting fuses. TABLE 1 Maximum Interrupting Current (rms symmetrical) INSTALLATION Fusing Equipment ELSG Full Range Current-Limiting Fuse Electrical pparatus 240-82 Contents General......................1 Installation...................1 Production Tests..............1 Electrical Characteristics.......3

More information

K-Limiter high ampere Companion II fuse

K-Limiter high ampere Companion II fuse Fusing Equipment Catalog Data CA132059EN Supersedes February 2016 COOPER POWER SERIES K-Limiter high ampere Companion II fuse General Eaton designs its Cooper Power series K-Limiter fuse to be conveniently

More information

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description Type L Cutouts UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout Electrical Apparatus 327-30 Description Cooper Power Systems has set a new standard of excellence for polymer distribution

More information

ELF -LR current-limiting fuse

ELF -LR current-limiting fuse Fusing Equipment Catalog Data C132044EN Supersedes 240-71 ugust 2006 COOPER POWER SERIES ELF -LR current-limiting fuse General Eaton's Cooper Power series ELF -LR currentlimiting fuse is a full range current-limiting

More information

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection

More information

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Fusing Equipment Catalog Data CA132035EN Supersedes November 2015 COOPER POWER SERIES UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Description Eaton has set a standard

More information

Disconnect & ByPass Switches

Disconnect & ByPass Switches Disconnect & ByPass Switches Disconnect & Oil Circuit Recloser Bypass Switches; Regulator & Current Transformer Bypass Switches Electrical Apparatus K-SEC 060 & 090 Contents Type D-73 Distribution Class

More information

Figure 1. HX cutout fuseholders.

Figure 1. HX cutout fuseholders. Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus K-SEC 010 GENERAL Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted

More information

Product Selection Guide

Product Selection Guide Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility

More information

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

Figure 1. HX cutout fuseholders. Positive Interruption

Figure 1. HX cutout fuseholders. Positive Interruption Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus 327-10 general Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted to

More information

distribution transformers. Single-Phase Overhead GENERAL. Cooper Power Systems manufactures a complete line of single-phase overhead-type

distribution transformers. Single-Phase Overhead GENERAL. Cooper Power Systems manufactures a complete line of single-phase overhead-type Distribution Transformers Single-Phase Overhead Electrical pparatus 0-0 GENERL ooper Power Systems manufactures a complete line of single-phase overhead-type distribution transformers. Single-phase transformers

More information

NX indoor current-limiting fuses

NX indoor current-limiting fuses Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element Fusing Equipment Kearney Fuse Links Electrical Apparatus 327-40 general Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution

More information

X-Limiter full-range current-limiting fuse

X-Limiter full-range current-limiting fuse Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting

More information

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT Fusing Equipment Kearney Fuse Links Electrical Apparatus K-SEC 030 GENERAL Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems and equipment.

More information

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION Surge Arresters UltraSIL Housed VariSTAR Station Class Surge Arresters Electrical Apparatus 235-88 GENERAL Cooper Power Systems has set a new standard of excellence for polymerhoused station class surge

More information

Surge Arresters. Surge Arrester/Type L Fuse Cutout Combination. Description. Construction. Connectors/Brackets

Surge Arresters. Surge Arrester/Type L Fuse Cutout Combination. Description. Construction. Connectors/Brackets Surge Arresters Surge Arrester/Type L use ombination Electrical Apparatus 235-26 escription ooper Power Systems surge arrester/type L interchangeable fuse cutout combinations are available in a wide variety

More information

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013 Kearney fuse links Supersedes December 2013 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009 Kearney fuse links Supersedes November 2009 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX

Subject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX File: PCUP-09-002_EX Outdoor Use Indoor Use The Trans-Guard EX full-range current-limiting capacitor fuse provides both low and high current fault protection in a single, compact fuse body. As a full-range

More information

INSTALLATION PRODUCTION TESTS

INSTALLATION PRODUCTION TESTS Deadbreak Apparatus Connectors 600 A 15/25 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-10 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class Bol-T Deadbreak Connector is used to terminate

More information

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses CP No.: CP9716 Rev. 02 Page: 1 of 9 CERTIFIED TEST REPORT Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses Rev. 02 DATE: June 3, 2010 ORIGINAL REPORT DATE: June 13, 1997 Cooper Power Systems,

More information

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV. DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them

More information

M-Force three-phase switch

M-Force three-phase switch Supersedes K-SEC 926 December 2012 M-Force three-phase switch Description The M-Force switch from Eaton's Cooper Power Systems is a distribution-class, gangoperated, factory unitized three-phase overhead

More information

FX Full-Range Current-Limiting Fuse

FX Full-Range Current-Limiting Fuse Hi-Tech FX Full-Range Current-Limiting Fuses Trans-Guard FX Full-Range Current-Limiting Fuse Patented damage sensor significantly reduces the risk of fuse failure should the fuse be subjected to an element-damaging

More information

CATALOG. Hi-Tech Fuse Products

CATALOG. Hi-Tech Fuse Products CATALOG Hi-Tech Fuse Products Thomas & Betts is now ABB Installation Products, but our long legacy of quality products and innovation remains the same. From connectors that help wire buildings on Earth

More information

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN Surge Arresters MN235004EN Effective December 2015 Supersedes S235-26-1 August 2012 COOPER POWER SERIES Surge arrester interchangeable fuse cutout combination installation instructions DISCLAIMER OF WARRANTIES

More information

Figure 1. Two and Three-phase MagneX.

Figure 1. Two and Three-phase MagneX. Fusing Equipment Two- & Three-Phase MagneX Interrupter Electrical Apparatus 240-33 GENERAL The Cooper Power Systems MagneX Interrupter is an overcurrent protective device that protects distribution transformers

More information

PROTECTION AND CONTROL

PROTECTION AND CONTROL B C Table 1 DIMENSIONAL Information for Trans-Guard OS Fuses Fuse Voltage Rating (kv) 1/4-20 threaded hole 1/2 deep (both ends) Current Rating (Amps) Fuse Catalog Number 35 HTDS232035 Overall Diameter

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015 10A Type C PORCELAIN Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10A Page 1 Type C Cutouts LINKBREAK cutout, pages 8-10 LOADBREAK cutout with Arc-Chute interrupter,

More information

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION Fusing Equipment Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly Electrical Apparatus 240-40 GENERAL Cooper Power Systems Bay-O-Net Fuse Assemblies are used to protect transformers and distribution

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv) Outdoor Distribution (4.16 through 25 ) Specifications Conditions of Sale STANDAD: Seller s standard conditions of sale set forth in Price Sheet 153 apply, except as modified under WAANTY QUALIFICATIONS

More information

Elastimold & Hi-Tech Fuse Products

Elastimold & Hi-Tech Fuse Products In this section... Elastimold & Hi-Tech Fuse Products Elastimold & Hi-Tech Fuse Products Overview...H-62 Elastimold Fused Loadbreak Elbows (FLE)... H-63 H-67 Elastimold Molded Current-Limiting Fuses (MCLF)...

More information

M-Force three-phase switch

M-Force three-phase switch Switches and Disconnects CA008004EN Supersedes May 2015 COOPER POWER SERIES M-Force three-phase switch Description Eaton's Cooper Power series M-Force switch is a distribution-class, gang-operated, factory

More information

Electronic Resettable Sectionalizer

Electronic Resettable Sectionalizer POWER SYSTEMS, INC. Protected by U.S. Patents No. 5,612,661; 4,935,715; DES. 278,331 and other patents pending Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable

More information

Direct-connected capacitor fuse

Direct-connected capacitor fuse Fusing Equipment Catalog Data CA132037EN Supersedes 240-63 December 2013 COOPER POWER SERIES General The use of Eaton's Cooper Power series X-Limiter fuse (Catalog Section 240-56) as a direct-connected

More information

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn Surge arresters UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters electrical apparatus 235-75 General Cooper Power Systems has set a new standard of excellence for polymerhoused

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT COS 38kV 100A 8kA asym. Type PGC Parallel groove terminal bronze with tin plated NEMA Bracket type B Upper contact copper with silver plated Cap - Cast bronze

More information

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products Hi-Tech SX Full-Range Current-Limiting Fuses Provides both overload and fault current protection for distribution equipment in a single fuse body. Trans-Guard SX Full-Range Current-Limiting Fuse As a full-range

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014 10A Type C PORCELAIN Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10A Page 1 Type C Cutouts LINKBREAK cutout, pages 8-10 LOADBREAK cutout with Arc-Chute interrupter,

More information

3.6. Current Limiting Fuses. Contents. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses

3.6. Current Limiting Fuses. Contents. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses .6 Limiting Fuses Motor Start Fuses Product Description Eaton s CLS current limiting fuses are used in conjunction with medium voltage motor starters to provide shortcircuit protection for individual motor

More information

Westinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401

Westinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401 February 26, 1976 Supersedes PL 38-640 dated October 15,1974 Pages 1-8 Prices effective April 29, 1974 Subject to change without notice Selling Policy 38-000 Mailed to E, D, C/1991, 2430/ PL Standard Bill

More information

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL Deadbreak Apparatus Connectors 600 A 15/25 kv Class BOL-T Deadbreak Connector Electrical Apparatus 600-30 GENERAL The Cooper Power Systems 600 A, 15/25 kv Class BOL-T Deadbreak Connector is used to terminate

More information

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C Page:1 of 9 CERTIFIED TEST REPORT Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C37.41-2008 REV. 00 August 11, 2014 Original Report Date: August 11, 2014 Eaton s Cooper Power Systems

More information

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50 Deadbreak Apparatus Connectors 600 A 35 kv Class Bol-T Deadbreak Connector Electrical Apparatus 600-50 General The Cooper Power Systems 600 A, 35 kv Class Bol-T Deadbreak Connector is used to terminate

More information

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv) Outdoor Distribution (4.4 kv through 46 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 50 apply, except as modified under WARRANTY QUALIFICATIONS

More information

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C CP No.: CP1101 Rev. 00 Page: 1 of 9 CERTIFIED TEST REPORT 8.3, 9.9, 15.5, 17.2 and 23 Cooper ELSP Backup Fuses Testing per C37.41-2008 Rev. 00 DATE: May 3, 2011 ORIGINAL REPORT DATE: May 3, 2011 Cooper

More information

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

OVERALL LENGTH (B)  ( mm)  ( mm)  ( mm)  ( mm) 1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165

More information

3.5. Current Limiting Fuses. Contents. CLPT and NCLPT Type Fuses. CLPT and NCLPT Type Fuses

3.5. Current Limiting Fuses. Contents. CLPT and NCLPT Type Fuses. CLPT and NCLPT Type Fuses .5 Limiting Fuses (N)CLPT Fuses Contents escription Selection................ Product Selection....................... etails........................ Page V14-T-4 V14-T-4 V14-T-48 Product escription aton

More information

CMU medium voltage power fuses

CMU medium voltage power fuses Fusing Equipment Catalog Data C132038EN Supersedes 240-94 December 2013 COOPER POWER SERIES General Eaton s Cooper Power series CMU power fuse is a boric acid, expulsion-style fuse. Suitable for both indoor

More information

10DD 10DD-1. Section CAUTION:

10DD 10DD-1. Section CAUTION: POLYMER Electronic Resettable Sectionalizer Protected by U.S. Patents No. 6,593,842; 5,854,582; 5,612,661; 4,935,715; 4,795,996; and other patents pending Section 10DD-1 10DD Warranty - Material Hubbell

More information

Loadbreak Apparatus Connectors

Loadbreak Apparatus Connectors Loadbreak Apparatus Connectors 200 A 25 kv Class POSI-BREAK Loadbreak Elbow Connector with Optional Integral Jacket Seal* Electrical Apparatus 500-29-7 general The POSI-BREAK Loadbreak Elbow Connector

More information

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified Surge s Catalog Data CA235022EN Supersedes TD235009EN September 2014 COOPER POWER SERIES VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified General Eaton s Cooper

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

D-73P disconnect and bypass switches

D-73P disconnect and bypass switches Switches atalog Data 008005EN Supersedes pril 2016 OOPER POWER SERIES D-73P disconnect and bypass switches ontents Description Page D-73P disconnect switch....2 D-73P3 bypass switch....5 D-73P-D cutout

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013 10AA Type C-Polymer Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10AA Page 10AA-1 Quality Construction Efficient Current Transfer The Type C-Polymer cutout has an all

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA August 2015

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA August 2015 10AA Type C-POLYMER Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10AA Page 10AA-1 Quality Construction Efficient Current Transfer The Type C-Polymer cutout has an all

More information

600 A 35 kv class BT-TAP deadbreak connector

600 A 35 kv class BT-TAP deadbreak connector Supersedes 600-55 July 2014 600 A 35 kv class BT-TAP deadbreak connector General Eaton's Cooper Power Systems 600 A 35 kv Class BT-TAP deadbreak connector is used to terminate high-voltage underground

More information

Fuse Link Designation

Fuse Link Designation Westinghouse The fundamental use of distribution fuse links is in fuse cutouts to provide protection for electrical equipment against faults and overloads, and increased system service continuity through

More information

GENERAL. CONSTRUCTION External

GENERAL. CONSTRUCTION External Surge Arresters VariSTAR Type AZG4 Surge Arresters for Systems through 400 kv IEC 20-kA; Line Discharge Class 4 Electrical Apparatus I235-84 GENERAL VariSTAR AZG4 Surge Arresters incorporate the latest

More information

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features Surge s Electrical Apparatus 235-99 General Cooper Power Systems set the standard for design, manufacturing and delivery of polymeric distribution arresters with the UltraSIL polymerhoused arrester family.

More information

600 A 15 kv class Cleer loadbreak connector system

600 A 15 kv class Cleer loadbreak connector system Loadbreak/Deadbreak Connectors CA650010EN Supersedes 600-100 April 2013 COOPER POWER SERIES 600 A 15 kv class Cleer loadbreak connector system General Eaton's Cooper Power series Cleer loadbreak connector

More information

600 A 28 kv class Cleer loadbreak connector system

600 A 28 kv class Cleer loadbreak connector system Loadbreak/Deadbreak Connectors CA650012EN Supersedes 600-102 April 2013 COOPER POWER SERIES 600 A 28 kv class Cleer loadbreak connector system General Eaton's Cooper Power series Cleer loadbreak connector

More information

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv) S&C Loadbuster Disconnect Switches Outdoor Distribution ( kv through 34.5 kv) S&C s Loadbuster Disconnect Switches, when used with S&C s Loadbuster tool, provide the ultimate in distribution live-switching

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal Loadbreak Connectors Catalog Data CA650062EN Supersedes June 2015 COOPER POWER SERIES 200 A 15 kv class loadbreak elbow connector with optional integral jacket seal General Eaton s Cooper Power series

More information

600 A 15 and 25 kv class Cleer grounding elbow

600 A 15 and 25 kv class Cleer grounding elbow Loadbreak/Deadbreak Connectors CA650013EN Supersedes March 2015 COOPER POWER SERIES 600 A 15 and 25 kv class Cleer grounding elbow General Eaton provides a visible ground on its Cooper Power series 600

More information

600 A 15 kv class T-OP II deadbreak connector

600 A 15 kv class T-OP II deadbreak connector Deadbreak Apparatus Connectors CA650017EN Supersedes 600-12 February 2010 COOPER POWER SERIES 600 A 15 kv class T-OP II deadbreak connector General Eaton terminates high-voltage underground cable to transformers,

More information

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA 5670-100 Technical Guide 15 kv, 23 kv, & 35 kv General Description The Protective link is an oil immersed, expulsion type, fuse

More information

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary 14B-2 Type M3 Hookstick Disconnect Switches Up to 38kV 0 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch. It is for manual switching

More information

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003 Types SM-4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through kv) Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet apply, except as modified under

More information

Edison modular fuse, vault application products

Edison modular fuse, vault application products Fusing Equipment Catalog Data CA132025EN Supersedes 240-92 October 2008 Edison modular fuse, vault application products COOPER POWER SERIES Description Eaton s Cooper Power series Edison modular fuses

More information

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. CUTOUTS (Standard, Linkbreak & Loadbreak) and CUTOUT-ARRESTER COMBINATIONS Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined in

More information

A240R/A480R/A072F/A072B MED. VOLTAGE FUSES / R-RATED

A240R/A480R/A072F/A072B MED. VOLTAGE FUSES / R-RATED A240R/A480R/A072F/A072B MED. VOTAGE FUSES / R-RATED R-RATED MOTOR STARTER FUSES Amp-trap R-rated fuses are current-limiting, high interrupting rating fuses intended for the short-circuit protection of

More information

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv) S&C Power Fuses Types SM- 4, SM-5, SMD-0, and SMD-40 Outdoor Distribution (4.16 kv through kv) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: The seller s standard

More information

Section 1 Introduction to the Presentation

Section 1 Introduction to the Presentation 2007 Thomas & Betts Section 1 Introduction to the Presentation Introduction of T&B Hi-Tech Fuses and our products Expulsion fuses vs. Current-Limiting fuses Hi-Tech s fuse construction & design features

More information

Catalog 14A January 2013

Catalog 14A January 2013 Catalog 14A January 2013 Page 1 January 2013 Type AR (Automation-Ready) Switch 14.4kV, 25kV or 34.5kV 900 Amperes Continuous/Interrupt Description The Hubbell unitized Type AR switch is a distribution-level,

More information

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL Loadbreak Apparatus Connectors 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal Electrical Apparatus 500-10-7 GENERAL The Cooper Power Systems Loadbreak Elbow Connector is

More information

Application of Primary Fuses

Application of Primary Fuses Application of Primary Fuses Introduction The wide variety of fuse links offered by the A.B. Chance Company is instrumental in reducing the many problems facing today s coordination engineers. Besides

More information

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage 1500 kva Padmount Transformer 12470 delta Primary Voltage 208Y/120 Secondary Voltage Cooper Power Systems Proposal Number: BED1096719 Date: January 4, 2010 Revision 00 Item Number: 00001 Item Details Customer

More information

UltraSIL polymer-housed VariSTAR station-class surge arresters

UltraSIL polymer-housed VariSTAR station-class surge arresters Surge s Catalog Data CA235013EN Supersedes August 2015 COOPER POWER SERIES UltraSIL polymer-housed VariSTAR station-class surge arresters General Eaton has set a new standard of excellence for polymer-housed

More information

RBA Catalog Numbers and Information

RBA Catalog Numbers and Information 50 RBA s and Information Type RBA Expulsion Fuses for Use Indoors or in an Enclosure Ampere Rating Standard Speed (Fuse Refills) Curve Reference 36-635 Time-Lag (Fuse Refills) Curve Reference 36-635 Approx.

More information

S&C Loadbuster Disconnects

S&C Loadbuster Disconnects S&C Loadbuster Disconnects Outdoor Distribution ( kv through 34.5 kv) With these outstanding features... Up to -ampere continuous ratings, 40,000-ampere RMS asymmetrical momentary ratings Designed for

More information

25 kv class fused loadbreak elbow connector

25 kv class fused loadbreak elbow connector Loadbreak Connectors Catalog Data CA650070EN Supersedes 500-111 July 2012 COOPER POWER SERIES 25 kv class fused loadbreak elbow connector General Eaton combines a fully-shielded and insulated plug-in termination

More information

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Catalog 14B January 2015 HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch.

More information

Type NR oil switch installation and operation instructions

Type NR oil switch installation and operation instructions Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

Pole-mounted capacitor racks with single-phase capacitor units

Pole-mounted capacitor racks with single-phase capacitor units Power Capacitors Catalog Data CA230001EN Supersedes October 2014 COOPER POWER SERIES Pole-mounted capacitor racks with single-phase capacitor units General Eaton s Cooper Power series products offer a

More information

Mica Element Support. Compacted Quartz Sand. Length B

Mica Element Support. Compacted Quartz Sand. Length B Construction A Tin-Plated Brass Caps Dimensional Information for Trans-Guard s NOMINAL 5.5 Resin-Rich Filament Wound Glass/Epoxy Body 3 75 80 200 3 50 5 80 5 125 3 50 5 5 100 23.0 50 Low Current Interruption

More information

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34. S&C Power Fuses s SM and SMLa Indoor Distribution (4.16 through 34. ) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set

More information

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka)

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka) Surge s UltraSIL Polymer-Housed VariSTAR Surge s: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka) Electrical Apparatus 235-35 General Cooper Power Systems has set the standard

More information

Cutouts (Standard, Linkbreak & Loadbreak) and Cutout-Arrester Combinations U.S. Patent 4,546,341; 6,392,526

Cutouts (Standard, Linkbreak & Loadbreak) and Cutout-Arrester Combinations U.S. Patent 4,546,341; 6,392,526 Cutouts (Standard, Linkbreak & Loadbreak) and Cutout-Arrester Combinations U.S. Patent 4,546,341; 6,392,526 Section 10A 10A-1 Warranty - Material Hubbell Power Systems, Inc. warrants all products sold

More information

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL

I Surge Arresters. UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 GENERAL Surge Arresters UltraSIL Polymer-Housed VariSTAR Type U3 Surge Arrester for Systems through 275 kv IEC 10 ka; Line Discharge Class 3 Electrical Apparatus I235-93 GENERAL UltraSIL Polymer-Housed VariSTAR

More information

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV Cutler Hammer SECTION PB-1A-110 PAGE 1 Replaces April, 1996 TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV The PSI/II Padmount is the second generation of switchgear in the PSI switchgear family. The PSI/II

More information