Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv
|
|
- Jessie Whitehead
- 6 years ago
- Views:
Transcription
1 Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv
2 General Description The Protective link is an oil immersed, expulsion type, fuse assembly for use in the high voltage circuit of a distribution transformer. Used in coordination with the CSP circuit breaker, the protective link s function is to disconnect a defective transformer from the feeder circuit, and to limit the severity of the damage to the transformer in case of an internal fault. The link consists of a fuse wire element contained within a hard fiber tube. The wire is welded to a top electrode at one end and crimped to a bottom electrode or welded directly to the cable lead at the other end. Protective links are available in a wide variety of fuse sizes and kv classes for proper coordination with CSP circuit breakers. Application Information Fuse Curve Selection When designing a CSP protection scheme, the secondary CSP circuit breaker is selected first. After the secondary circuit breaker is selected, the protective link is chosen so that proper coordination between the primary side protective link and the secondary side circuit breaker is achieved. The simplest way to determine if proper coordination has been achieved is to compare the time versus current characteristics curves (TCC curves) of both devices. Coordination is acceptable when, Figure 1: Schematic Diagram of CSP Transformer Table 1: Interruption Rating 2 1 Interrupting Rating Application Voltage (rms symmetrical Amperes) 2,400 5,000 4,800 4,800 7,200 3,500 12,000 3,000 14,400 2,500 23,000 1,200 34,500 1,200 1 Application Voltage listed as: Single Phase: Line to Ground Three Phase: Line to Line 2 Interruption ratings are based on a well constructed round tank distribution transformer. Ratings will generally be greater for pad mounted distribution transformers because of the rectangular tank's ability to absorb a considerable ammount of energy during high current fault interruption. for all values of secondary fault current, the circuit breaker will clear the fault before the protective link melts. The protective links are produced in a wide range of fuse sizes which are described on curve drawing for minimum melt characteristics and curve drawing for average clearing characteristics. Circuit Connection The protective link is connected between the primary winding and high voltage bushing. In a transformer with a single high voltage bushing (where one end of the primary winding is connected to the ground), one protective link per transformer is used. In a transformer with two high voltage bushings, two protective links are used. A typical CSP transformer schematic diagram is shown in Figure 1. A jack bolt (style number 240A394H01 ordered separate) fits into the 0.25 x 28 thread in the top terminal of the protective link and may be used to make up the top connection to the link. In lieu of this bolt, any standard 0.25 diameter x 28 threads per inch x 0.38 thread length bolt will work. The lower connection to the protective link is made through the flexible cable lead. The flexible cable lead is specified on the dimension sheets as: number of wire strands - individual wire strand thickness (example = 259 strands of diameter wire). Mounting Information Protective links may be mounted in any orientation as long as the expulsion arc will be under oil during arc interruption. Standard mounting configuration is in a near vertical to vertical 2
3 position in round tank transformers and horizontal to vertical in pad mounted units. All energized parts of the protective link must be under oil and spaced away from all other energized or grounded parts with sufficient distance to withstand all operating and test voltages. The transformer tank design must be capable of absorbing the arc energy of the protective link through tank venting or other means. The interrupting rating of this device is a function of the tank design and the live part insulation. See the appropriate breaker application manual for coordination with CSP breakers. Mounting Accessories Three different methods may be used to mount Protective Links: a narrow groove flat clip bolted to an insulator, retaining rings and terminal block, or directly mounted to an insulating mounting block. The narrow groove flat clip (75D0426H01) is placed in the small groove around the protective link, the ends are closed together, the mounting bolt is run through the eye ends of the mounting clip, and is bolted to the insulating structure. The bolt holds the clip closed around the protective link, as well as securing the link to the insulating structure. The retaining rings (style number 9820A65H05) fit into two small grooves on the fiber tube body and secures the fuse in the terminal block (style number 584B903H01). This mounting arrangement is shown in Figure 3. The protective link may also be mounted using an insulating block. This mounting scheme is shown in Figure 4. Details Protective Link Figure 3: Block Mounting - 584B903H01 Mounting Hole - bolt to insulating member of transformer superstructure Retaining Clips (above & below) Terminal Block Cable Lead Flat Clip Groove Figure 2: Part Identification and dimensional information for this block may be found on Dimension Sheet Pg 13. Link Operation When the fuse wire melts due to a fault current, an arc is established within the fiber tube. The interaction of the arc on the fiber tube s interior wall generates gases, which (in combination with the expulsive action of the protective link) extinguishes the arc rapidly and clears the circuit. Features & Advantages Top Electrode Fiber Tube Cable Lead Multiple Ratings Protective links are manufactured in three voltage classes and up to thirteen different fuse curve variations. The three voltage classes are 15 kv, 23 kv, and 35 kv. These ratings apply to a single phase transformer s line to ground voltage, or a three phase transformer s line to line voltage. For example, a three phase transformer connected to an 11kV system would use the 15kV links and if connected to a 22kV system would use the 23kV links. The various fuse curves are shown on TCC curves and
4 Ordering Information Curve Number Current Rating < = 15kV < =23 kv <=35 kv B581G01 779C667G01 345B995G B581G02 779C667G02 345B995G29 3A 7 592B581G11 779C667G03 345B995G B581G06 779C667G08 345B995G B581G03 779C667G04 345B995G23 5A B581G12 779C667G09 345B995G B581G04 779C667G05 345B995G B581G05 779C667G06 345B995G25 7A B581G13 779C667G33 345B995G B581G07 779C667G07 345B995G B581G08 779C667G34 345B995G B581G09 Contact 345B995G B581G14 Contact 345B995G B581G31 Contact B581G32 Contact Contact Contact Printed in USA by Tennessee Industrial Printing Services, Inc. Figure 4: Block Mounted 35kV Protective Link Inc S. Cavalier Drive Alamo, TN 38001, USA Telephone: Fax: Design Tests The protective link assembly has passed a series of design tests which offer verification of the design reliability: 1. Interruption Tests 2. Minimum Melt Tests 3. Safe Transit Test Production Tests In addition to the initial design testing that was performed, the following tests are run on daily production units: 1. Dimension check to verify critical dimensions. 2. Visual inspection to verify assembly process. Warning The misapplication of the protective link constitutes a potential hazard to life & property. Accordingly, the user must exercise due care in utilizing this information to ensure that the protective link is properly applied. IZUA en Replaces TPL , February 2003
5
6
7
8
9
Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break
Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926 Technical Guide Load-break, General Description The Drywell Current Limiting Fuse Cannister is a removable fuse assembly for use in single and three
More informationDO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.
DO-III DO-III Fuse Holder TPL 44-835, May 2000, Page 1 of 4 General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder ABB Inc. General Description The ABB DO-III fuse holder is a draw
More informationLoad Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount
Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA 5321-100 Technical Guide Nut Mount Weld Mount General Description The ABB Type LBOR-II switch is a manually operated, two position, load make
More informationLV Bushing Oil to Air Dry Insulation PTAB-SLV832
LV Bushing Oil to Air Dry Insulation PTAB-SLV832 Technical Guide 600 V, 30 kv BIL, 600-2500 A 5/8" Integral Flange Bushing 1.0" Integral Flange Bushing 1.25" Bushing General Description The ABB low voltage
More informationCSP Circuit Breaker Three Phase
General Information : LR Breaker SQR Breaker LQR Breaker, HQR Breaker Wall-Mounting Type CSP Circuit Breaker Three Phase Three Phase CSP Circuit Breaker For Distribution Transformers General Information
More informationOVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)
1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165
More informationK-Limiter high ampere Companion II fuse
Fusing Equipment Catalog Data CA132059EN Supersedes February 2016 COOPER POWER SERIES K-Limiter high ampere Companion II fuse General Eaton designs its Cooper Power series K-Limiter fuse to be conveniently
More informationFusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element
Fusing Equipment Kearney Fuse Links Electrical Apparatus 327-40 general Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution
More informationFigure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating
Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection
More informationABB Power T&D Company Inc. General Information: DT-100 DT-150 DV-100 DV-150. De-energized Switches TPL , July 1999, Page 1 of 4
General Information: DT-100 DT-150 DV-100 DV-150 De-energized Switches TPL 44-816, July 1999, Page 1 of 4 Type DT-100 & DT - 150, Tap Changers; Type DV-100 & DV- 150, Dual Voltage Switches - General Information
More informationKearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013
Kearney fuse links Supersedes December 2013 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems
More informationK-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT
Fusing Equipment Kearney Fuse Links Electrical Apparatus K-SEC 030 GENERAL Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems and equipment.
More informationKearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009
Kearney fuse links Supersedes November 2009 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationPROTECTION AND CONTROL
B C Table 1 DIMENSIONAL Information for Trans-Guard OS Fuses Fuse Voltage Rating (kv) 1/4-20 threaded hole 1/2 deep (both ends) Current Rating (Amps) Fuse Catalog Number 35 HTDS232035 Overall Diameter
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationX-Limiter full-range current-limiting fuse
Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDesign Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C
Page:1 of 9 CERTIFIED TEST REPORT Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C37.41-2008 REV. 00 August 11, 2014 Original Report Date: August 11, 2014 Eaton s Cooper Power Systems
More informationProduct Selection Guide
Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility
More informationEE 741 Over-voltage and Overcurrent. Spring 2014
EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationDescriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications
Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter
More informationCompanion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses
CP No.: CP9716 Rev. 02 Page: 1 of 9 CERTIFIED TEST REPORT Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses Rev. 02 DATE: June 3, 2010 ORIGINAL REPORT DATE: June 13, 1997 Cooper Power Systems,
More informationwww. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV
December, 1975 New nformation and Supersedes DB 38-131 Pages 1-4, dated May 1972, and 38-121 D WE A, Pages 1-4, dated April1974 E, D, C/1981/ DB Westinghouse Electric Corporation Distribution Apparatus
More informationCMU medium voltage power fuses
Fusing Equipment Catalog Data C132038EN Supersedes 240-94 December 2013 COOPER POWER SERIES General Eaton s Cooper Power series CMU power fuse is a boric acid, expulsion-style fuse. Suitable for both indoor
More informationFusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION
Fusing Equipment Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly Electrical Apparatus 40-40 GENERAL Cooper Power Systems Bay-O-Net Fuse Assemblies are used to protect transformers and distribution
More information26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents.
.3 Power Breakers, Contactors and Fuses Fuses General Contents Description Fuses General Product Overview Power Fuse Eaton s roots in the medium voltage power fuse business began over 75 years ago under
More informationRecommended Procedures
Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationType DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003
Type DTU De-energized Tap Changer Application, Installation & Selection Guide IL 44-750-1A Page 1 September, 2003 Page 2 September, 2003 Scope This leaflet contains general information about ordering and
More informationFigure 1. Two and Three-phase MagneX.
Fusing Equipment Two- & Three-Phase MagneX Interrupter Electrical Apparatus 240-33 GENERAL The Cooper Power Systems MagneX Interrupter is an overcurrent protective device that protects distribution transformers
More informationNX indoor current-limiting fuses
Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground
More information3.5. Current Limiting Fuses. Contents. CLPT and NCLPT Type Fuses. CLPT and NCLPT Type Fuses
.5 Limiting Fuses (N)CLPT Fuses Contents escription Selection................ Product Selection....................... etails........................ Page V14-T-4 V14-T-4 V14-T-48 Product escription aton
More informationOutdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter
Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles
More informationS&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)
S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles
More information8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C
CP No.: CP1101 Rev. 00 Page: 1 of 9 CERTIFIED TEST REPORT 8.3, 9.9, 15.5, 17.2 and 23 Cooper ELSP Backup Fuses Testing per C37.41-2008 Rev. 00 DATE: May 3, 2011 ORIGINAL REPORT DATE: May 3, 2011 Cooper
More informationFX Full-Range Current-Limiting Fuse
Hi-Tech FX Full-Range Current-Limiting Fuses Trans-Guard FX Full-Range Current-Limiting Fuse Patented damage sensor significantly reduces the risk of fuse failure should the fuse be subjected to an element-damaging
More informationMolded Current-Limiting Fuse
Molded Current-Limiting provide fullrange fault current protection using specially designed fuse elements, rated through 23kV line to ground and 50kA interrupting current. Construction is modular with
More informationCOOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN
Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND
More informationFusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION
Fusing Equipment Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly Electrical Apparatus 240-40 GENERAL Cooper Power Systems Bay-O-Net Fuse Assemblies are used to protect transformers and distribution
More informationType SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.
Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings
More informationGeneral Purpose US Fuses
SMARTSPOT with Maximum circuit protection Amp-trap 2000 SmartSpot AJT fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product line the AJT fuse provides
More informationMica Element Support. Compacted Quartz Sand. Length B
Construction A Tin-Plated Brass Caps Dimensional Information for Trans-Guard s NOMINAL 5.5 Resin-Rich Filament Wound Glass/Epoxy Body 3 75 80 200 3 50 5 80 5 125 3 50 5 5 100 23.0 50 Low Current Interruption
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationSURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION
Fusing Equipment Tandem ELF Current-Limiting Dropout Fuse Electrical pparatus 240-67 GENERL The Cooper Power Systems Tandem ELF current-limiting fuse is designed for transformer protection. The Tandem
More informationS&C Manual PME Pad-Mounted Gear
S&C Manual PME Pad-Mounted Gear Outdoor Distribution,. kv and 5 kv S&C Manual PME Pad-Mounted Gear... Featuring Elbow-Connected Encased Components. S&C Manual PME Pad-Mounted Gear brings in-air insulation,
More informationSWITCHGEAR DIVISION PRODUCT PROFILES
SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,
More informationSecondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor
Reducing Arc Flash Energies on Transformer Secondaries arc flash note 6 By Mike Lang, principal field engineer and Dave Komm, Technical Services Supervisor 1. Introduction Arc flash incident energy calculations
More informationyour Green Power WIND POWER SOLUTIONS only Greener
your Green Power WIND POWER SOLUTIONS only Greener WIND POWER SOLUTIONS Thomas & Betts is committed to being your partner in power delivery by leading the industry in innovative wind power solutions and
More informationSubject: Trans-Guard EX Full-Range Current-Limiting Capacitor Fuses Date: 4/10/09 File: PCUP _EX
File: PCUP-09-002_EX Outdoor Use Indoor Use The Trans-Guard EX full-range current-limiting capacitor fuse provides both low and high current fault protection in a single, compact fuse body. As a full-range
More informationDIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.
DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them
More informationMedium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A
DISTRIBUTION SOLUTIONS Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A Continuous protection and reliable operation Proven design and compliance with newest fuses standards Compatibility with other ABB
More information2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)
.7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous
More informationPower Fuses. > Power Fuses > BPA & HPA kv AMPs
The equipment described in this bulletin performs in accordance with NEMA standards publication SG2-1954, paragraphs SG2-5, SG2-5.10, and SG2-5.11 TYPE BPA Power Fuses 7.2-161 kv 100-200-300 400 AMPs The
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationFigure 1. ELSG Current-Limiting fuses. TABLE 1 Maximum Interrupting Current (rms symmetrical) INSTALLATION
Fusing Equipment ELSG Full Range Current-Limiting Fuse Electrical pparatus 240-82 Contents General......................1 Installation...................1 Production Tests..............1 Electrical Characteristics.......3
More informationTable 1.-Elemsa code and characteristics of Type K fuse links (Fast).
FUSE CATALOG 2 Table 1.-Elemsa code and characteristics of Type K fuse links (Fast). TYPE DESCRIPTION CAT PAGE 15K-1 UNIVERSAL TYPE FUSE LINK 2066A1 38K-1 UNIVERSAL TYPE FUSE LINK 2070A1 15K-2 UNIVERSAL
More informationELF -LR current-limiting fuse
Fusing Equipment Catalog Data C132044EN Supersedes 240-71 ugust 2006 COOPER POWER SERIES ELF -LR current-limiting fuse General Eaton's Cooper Power series ELF -LR currentlimiting fuse is a full range current-limiting
More information5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application
The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1
More information3.2. Current Limiting Fuses. Contents
.2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse
More informationMedium Voltage Fuses
2,400-38,000 VAC General Information Current-limiting E and rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of the fuse. This provides
More information2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)
.7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous
More information38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report
File Ref: CA132015EN Effective Mar 2015 COOPER POWER CT132001EN SERIES 38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report CT132001EN Page: 3 of 9 Introduction Eaton designs its Cooper
More informationVisual comparison of Plain & Hazy PP Film
ECOVAR High Voltage Power Capacitors are manufactured at our Sinnar Plant in India which is an ISO 9001 accredited facility & houses a computer aided design manufacturing processing and testing infrastructure
More informationEdison modular fuse, vault application products
Fusing Equipment Catalog Data CA132025EN Supersedes 240-92 October 2008 Edison modular fuse, vault application products COOPER POWER SERIES Description Eaton s Cooper Power series Edison modular fuses
More informationRBA Catalog Numbers and Information
50 RBA s and Information Type RBA Expulsion Fuses for Use Indoors or in an Enclosure Ampere Rating Standard Speed (Fuse Refills) Curve Reference 36-635 Time-Lag (Fuse Refills) Curve Reference 36-635 Approx.
More information3.6. Current Limiting Fuses. Contents. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses. ACLS, BCLS, CLS, HCLS and NCLS Type Fuses
.6 Limiting Fuses Motor Start Fuses Product Description Eaton s CLS current limiting fuses are used in conjunction with medium voltage motor starters to provide shortcircuit protection for individual motor
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationEngineering Dependable Protection
Electrical Distribution System Engineering Dependable Protection Engineering Dependable Protection - Part II "Selective Coordination of Overcurrent Protective Devices" Table of Contents Page Basic Considerations
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationPower Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers
Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Main Service s INTRODUCTION by Robert E. Fuhr, P.E. The use of electronic equipment has dramatically increased
More informationwww. ElectricalPartManuals. com Engineering Dependable Protection
Electrical Distribution System Engineering Dependable Protection Engineering Dependable Protection - Part II "Selective Coordination of Overcurrent Protective Devices" Table of Contents Page Basic Considerations
More informationwww. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers
Instructions for Load Break Air Switch, Type LBF, for Power Centers The Westinghouse Type LB 1 F Switch is an air insulated, gang operated, three pole, two position link type load interrupter switch. The
More informationShippensburg University
Shippensburg University 1871 Old Main Drive Shippensburg, PA 17257 SUPPLEMENT 1 Electrical Coordination Study Professional: Entech Engineering, Inc. 4 South Fourth Street P.O. Box 32 Reading, PA 19603
More informationExpulsion Fuses. 2.2 Fuse Selection. 2.3 Application. 2.4 BA Type Fuses. 2.5 DBA Type Fuses. 2.6 DBU Type Fuses. 2.7 RBA and RDB Type Fuses
Expulsion Fuses Eaton Expulsion Fuses.1 Product Overview Product Description....................................... Accessories............................................. Catalog Numbers.........................................
More informationTechnical Specification for Pole Mounted Capacitor Rack
Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to
More informationBoric Acid Fuse Links
Boric Acid Fuse Links BBU Fuse Link Mount Construction Bird proof design insulator provides insulation characteristics higher than ANSI distribution cut-out standards and equal in most cases to ANSI switch
More informationBUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352
8.3kV E-Rated Description: E-Rated, current-limiting, medium voltage fuses for feeder circuit, switchgear and transformer protection. Supersedes pril 2015 USSMNN SERIES Medium voltage fuses for feeder
More informationSelection Guide. HHD-BPT, DIN Style, Current-Limiting, Back-Up, Potential Transformer Protection
HHD-BPT Selection Guide HHD-BPT, DIN Style, Current-imiting,, Potential Transformer Protection Current ratings [A]; 0.5, 1, 2, 2.5, 3.15, 4, 5 E=192mm Page E=292mm Page E=367mm Page E=442mm Page E=537mm
More informationPRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT
PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT COS 38kV 100A 8kA asym. Type PGC Parallel groove terminal bronze with tin plated NEMA Bracket type B Upper contact copper with silver plated Cap - Cast bronze
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction
SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor
More informationElastimold & Hi-Tech Fuse Products
In this section... Elastimold & Hi-Tech Fuse Products Elastimold & Hi-Tech Fuse Products Overview...H-62 Elastimold Fused Loadbreak Elbows (FLE)... H-63 H-67 Elastimold Molded Current-Limiting Fuses (MCLF)...
More informationSpecifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)
S&C Power Fuses Types SM- 4, SM-5, SMD-0, and SMD-40 Outdoor Distribution (4.16 kv through kv) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: The seller s standard
More informationCL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES
SERIES E-RATED / MEDIUM VOLTAGE FUSES 5kV AND 15kV CLIP-LOCK MOUNTED FUSES Amp-trap E-rated 5kV and 15kV fuses have 3" diameter barrels and mount in unique cam-locking clips, for superior connections as
More informationwww. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003
Types SM-4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through kv) Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet apply, except as modified under
More informationEquipment Protection. Transformers 600V or Less
Equipment s or Less The requirements of 450.3 cover only transformer protection. In practice, other components must be considered in applying circuit overcurrent protection. For circuits with transformers,
More informationAppendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies
Engineering Studies Coordination Study Every 5 years and in conjunction with electrical system modifications. Short Circuit Study NETA MTS 6.2 Every 5 years and in conjunction with electrical system modifications.
More informationCPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards
Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1
More informationFEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation
FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation Elastimold solid dielectric switchgear agenda Compelling value Design principles Product overview Switchgear applications
More informationSelection Guide S&C ELECTRIC COMPANY. For Transformer-Primary Fuses in Medium- and High-Voltage
S&C Power FusesTypes SMD-1A, SMD-2B, SMD-2C, SMD-3, and SMD-50 Selection Guide For Transformer-Primary Fuses in Medium- and High-Voltage monsterfuses.com Utility and Industrial Substations Factory Authorized
More information25 kv class fused loadbreak elbow connector
Loadbreak Connectors Catalog Data CA650070EN Supersedes 500-111 July 2012 COOPER POWER SERIES 25 kv class fused loadbreak elbow connector General Eaton combines a fully-shielded and insulated plug-in termination
More informationSpecifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)
Outdoor Distribution (4.4 kv through 46 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 50 apply, except as modified under WARRANTY QUALIFICATIONS
More informationOil Circuit Breakers
ČESKÉ VYSOKÉ UČENÍ TECHNICKÉ V PRAZE Fakulta elektrotechnická Katedra elektrických pohonů a trakce K13114 BE1M 14 ESP Electrical apparatuses and machines Oil Circuit Breakers BE1M14 SSP Electrical apparatuses
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin
SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive
More informationFUSES. Safety through quality
Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced
More informationFuse Link Designation
Westinghouse The fundamental use of distribution fuse links is in fuse cutouts to provide protection for electrical equipment against faults and overloads, and increased system service continuity through
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Type VFI, Vacuum Fault Interrupter Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear
More information