1 .3 Power Breakers, Contactors and Fuses Fuses General Contents Description Fuses General Product Overview Power Fuse Eaton s roots in the medium voltage power fuse business began over 75 years ago under Westinghouse Electric. In 1935, Westinghouse introduced the medium voltage boric acid expulsion fuse followed by the medium voltage current limiting fuse. Even today, medium voltage fuses continue to use that core technology. Eaton continues to build on the technology legacy by engineering higher performance, cost-effective power fuse products. Eaton s medium voltage fuses are manufactured and tested to the requirements of the C37-4X series of standards, which are maintained and updated regularly to maintain currency with industry practices. These standards are: IEEE Std. C37.40 IEEE Standard Service Conditions and Definitions for High Voltage Fuses, Distribution Enclosed Single- Pole Air Switches, Fuse Disconnecting Switches, and Accessories (ANSI). IEEE Std. C37.41 IEEE Standard Design Tests for High-Voltage (>1000V) Fuses, Fuse and Disconnecting Cutouts, Distribution Enclosed Single- Pole Air Switches, Fuse Disconnecting Switches, and Fuse Links and Accessories used with These Devices (ANSI). ANSI C37.42 IEEE Standard Specifications for High-Voltage (>1000V) Expulsion-Type Distribution- Class Fuses, Fuse and Disconnecting Cutouts, Fuse Disconnecting Switches, and Fuse Links, and Accessories used with These Devices (ANSI). ANSI C37.46 American National Standard for High Voltage Expulsion and Current Limiting Type Power Class Fuses and Fuse Disconnecting Switches. ANSI C37.47 American National Standard for High Voltage Current Limiting Type Distribution Class Fuses and Fuse Disconnecting Switches. The following IEEE standards are also applicable to the fuse products covered in this publication: IEEE Std. C37.48 IEEE Guide for the Application, Operation, and Maintenance of High Voltage Fuses, Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories (ANSI). IEEE Std. C IEEE Guide for the Classification, Application, and Coordination of Current- Limiting Fuses with Rated Voltages 1 38 kv. A better understanding of some fuse terminology will help you understand and select the correct fuse. The following is a brief overview of those terms. Power vs. Distribution The differentiation is intended to indicate the test conditions and where fuses are normally applied on an electrical system, based on specific requirements for generating sources, substations and distribution lines. Each class has its own unique set of voltage, current and construction requirements (see C37.42,.46 and.47). Low vs. Medium vs. High Voltage While fuses are defined in the ANSI standards as either low or high voltage, Eaton has elected to name their fuses to correspond with the equipment in which they are installed. Therefore, per ANSI C84, our fuses are named as follows: Low voltage 1000V and below Medium voltage greater than 1000 to 69,000V High voltage greater than 69,000V V4-T-630 Volume 4 Circuit Protection CA E April For Immediate Delivery or Tech Support call KMParts.com at (866)

2 Power Breakers, Contactors and Fuses Fuses General.3 Expulsion vs. Current Limiting (Definitions per ANSI C ) An expulsion fuse is a vented Backup Fuses fuse in which the expulsion A fuse capable of interrupting effect of the gases produced all currents from the by internal arcing, either maximum rated interrupting alone or aided by other current down to the rated mechanisms, results in minimum interrupting current. current interruption. An expulsion fuse is not current limiting and as a result limits the duration of a fault on the electrical system, not the magnitude. A current limiting fuse is a fuse that, when its current responsive element is melted by a current within the fuse s specified current limiting range, abruptly introduces a high resistance to reduce current magnitude and duration, resulting in subsequent current interruption. Refer to Fuse Types Protection Range figure on Page V4-T-632 for a features comparison. Fuse Types There are three current limiting fuse types: Backup, General Purpose and Full Range. It is important that the user have an understanding of these definitions to ensure proper application of the fuse (see Fuse Types Protection Range figure on Page V4-T-632). Backup fuses are always used in a series with another interrupting device capable of interrupting currents below the fuse s minimum interrupting current. General Purpose Fuses A fuse capable of interrupting all currents from the rated interrupting current down to the current that causes melting of the fusible element in no less than one hour. General Purpose fuses are typically used to protect feeders and components such as transformers. Full Range Fuses A fuse capable of interrupting all currents from the rated interrupting current down to the minimum continuous current that causes melting of the fusible element, with the fuse applied at the maximum ambient temperature specified by the manufacturer. General Fuse Component Terms Fuse Refill Unit (of an Expulsion Fuse) A fuse refill unit is a replaceable assembly containing the calibrated current-responsive fuse element and certain other items that facilitate current interruption. On its own, the refill unit has no interrupting ability. A refill unit must be mounted in a fuseholder with a spring assembly to form a refillable fuse unit. The refill unit is the section of the fuse that must be replaced after a fuse operation. Fuseholder (of an Expulsion Fuse) A fuseholder is a reusable holder that when equipped with a fuse refill unit forms a fuse unit, capable of interrupting an overload or fault current. A fuseholder is supplied with a spring and shunt assembly, necessary to complete the internal interrupting assembly. The spring and shunt assembly is supplied with the fuseholder but is also available as a replacement part, as it may need replacement after several of heavy operations. Fuse Unit A fuse unit is a replaceable unit or assembly that is able, on its own, to perform current interruption. In the case of a refillable fuse unit, the refill unit must be replaced after a fuse operation. Where a complete fuse unit is supplied from the factory, the complete fuse unit must be replaced after a fuse operation. All currentlimiting fuses are fuse units. Exhaust Control Device When expulsion fuses are used in enclosures, exhaust control devices (filters, condensers or mufflers) are used to control the sound of the fuse operation, and to de-ionize and absorb the fuse exhaust products. These devices are normally supplied separately, because of different characteristics and ratings. They are reusable but may need replacement after several heavy operations. Mounting A mounting provides all the necessary parts to safely mount a fuse in its intended piece of equipment. The base is the metal support to which all other pieces attach. Insulators attach to the base and insulate the live fuse unit from the base and everything beyond the base. Live parts are the parts of the mounting that are energized once electricity is flowing. The live parts provide the means to hold the fuse unit in place, electrical contact, and a place to make line and load connections. Non-Disconnect Mounting A non-disconnect mounting does not provide a means for removing the fuse unit until the circuit is dead and the fuse unit can be removed manually. The fuse unit is held in place by friction through the use of fuse clips or by a cross bar. Volume 4 Circuit Protection CA E April V4-T-631 For Immediate Delivery or Tech Support call KMParts.com at (866)

3 .3 Power Breakers, Contactors and Fuses Fuses General Disconnect Mounting The disconnect mounting allows the fuse unit to be removed (off load) using an insulated hook stick. The hookstick grabs a pull ring and disconnects the fuse unit, which may then be lifted out of its mounting. Dropout Mounting Dropout mountings are used in outdoor applications. The fuse unit is equipped with a mechanical trigger that unlatches the upper contact, allowing the fuse unit to drop out, increasing the dielectric separation, and providing visible indication of a blown fuse. Live Parts Live parts were briefly discussed as part of the Mounting definition. Everything above the insulators on the mounting excluding the fuse unit, fuse holder, and the fuse end fittings (if required) are considered the live parts. Fuse end fittings are discussed next and are not required with non-disconnect live parts, but are required and included with disconnect live parts. Live parts may be sold separately as replacement parts or for new OEM applications. End Fittings End fittings are metal parts that attach to each end of a fuse unit s ferrules (end caps). As previously mentioned, they are used solely with disconnect fuse applications or when converting a nondisconnect to a disconnect fuse configuration. When end fittings are ordered, a fitting for each end of the fuse is included. Keep in mind that end fittings can become damaged in use and, therefore, are sold separately from the live parts when necessary. It is not necessary to purchase an entire set of live parts when only the end fittings are required. General High Voltage Fuse Comparison Expulsion Vented Electromechanical Interrupts at current zero Generally higher voltage and current application capabilities Different time/current characteristics Fuse Types Protection Range Current Limiting Type Interrupting Current Current Limiting Sealed Static Limits fault current Generally higher interrupting ratings Different time/current characteristics BACKUP GENERAL PURPOSE FULLL RANGE i i hr. i min. i max. V4-T-632 Volume 4 Circuit Protection CA E April For Immediate Delivery or Tech Support call KMParts.com at (866)

4 A ability, 2 able, 2 above, 3 abruptly, 2 absorb, 2 Accessories, 1 acid, 1 after, 2 ago, 1 aided, 2 Air, 1 All, 2 all, 2 allowing, 3 allows, 3 alone, 2 also, 1-2 always, 2 ambient, 2 American, 1 An, 2 an, 1-3 and, 1-3 another, 2 ANSI, 1-2 applicable, 1 Application, 1 application, 2-3 applications, 3 applied, 1-2 April, 1-3 arcing, 2 are, 1-3 As, 3 as, 1-3 assembly, 2 at, 1-3 attach, 2-3 available, 2 B BACKUP, 3 Backup, 2 bar, 2 base, 2 based, 1 be, 2-3 because, 2 become, 3 began, 1 below, 1-2 better, 1 beyond, 2 blown, 3 boric, 1 Breakers, 1-3 brief, 1 briefly, 3 build, 1

5 business, 1 but, 2-3 by, 1-2 C CA, 1-3 calibrated, 2 call, 1-3 can, 2-3 capabilitieslifted, 3 capable, 2 caps, 3 case, 2 causes, 2 certain, 2 characteristics, 2-3 Circuit, 1-3 circuit, 2 Class, 1 class, 1 Classification, 1 clips, 2 com, 1-3 comparison, 2 ComparisonThe, 3 complete, 2 Component, 2 components, 2 condensers, 2 Conditions, 1 conditions, 1 configuration, 3 connections, 2 considered, 3 construction, 1 contact, 2-3 Contactors, 1-3 containing, 2 Contents, 1 continue, 1 continues, 1 continuous, 2 Control, 2 control, 2 converting, 3 Coordination, 1 core, 1 correct, 1 correspond, 1 cost, 1 covered, 1 cross, 2 currency, 1 Current, 1-3 current, 1-3 Currentfittings, 3 currents, 2 Cutouts, 1 D damaged, 3 de, 2 dead, 2 defined, 1 definition, 3 Definitions, 1-2 definitions, 2 Delivery, 1-3 Description, 1 Design, 1 Device, 2 device, 2 Devices, 1 devices, 2 dielectric, 3 Different, 3 different, 2 differentiation, 1 Disconnect, 2-3 disconnect, 2-3 Disconnecting, 1 disconnects, 3 discussed, 3 Distribution, 1 distribution, 1 does, 2 down, 2 drop, 3 Dropout, 3 duration, 2

6 E Each, 1 each, 3 Eaton, 1 eaton, 1-3 effect, 2 effective, 1 either, 1-2 elected, 1 Electric, 1 electrical, 1-2 electricity, 2 Electromechanical, 3 element, 2 Enclosed, 1 enclosures, 2 End, 3 end, 3 energized, 2 ensure, 2 entire, 3 equipment, 1-2 equipped, 2-3 Even, 1 Everything, 3 everything, 2 excluding, 3 Exhaust, 2 exhaust, 2 Expulsion, 1-3 expulsion, 1-2 F facilitate, 2 factory, 2 fault, 2-3 features, 2 feeders, 2 ferrules, 3 figure, 2 filters, 2 fitting, 3 Fittings, 3 fittings, 3 flowing, 2 followed, 1 following, 1 follows, 1 For, 1-3 for, 1-3 form, 2 forms, 2 friction, 2 from, 2-3 FULL, 3 Full, 2 Fuse, 1-3 fuse, 1-3 Fuseholder, 2 fuseholder, 2 Fuses, 1-3 fuses, 1-2 fusible, 2 G gases, 2 GENERAL, 3 General, 1-3 Generally, 3 generating, 1 grabs, 3 greater, 1 Guide, 1 H has, 1-2 have, 2 heavy, 2 held, 2 help, 1 High, 1, 3 high, 1-2 higher, 1, 3 hold, 2 holder, 2-3 hook, 3

7 hookstick, 3 hour, 2 hr, 3 I IEEE, 1 if, 3 Immediate, 1-3 important, 2 In, 1-2 in, 1-3 included, 3 increasing, 3 indicate, 1 indication, 3 industry, 1 installed, 1 insulate, 2 insulated, 3 Insulators, 2 insulators, 3 intended, 1-2 internal, 2 Interrupting, 3 interrupting, 2-3 interruption, 2 Interrupts, 3 introduced, 1 introduces, 2 ionize, 2 is, 1-3 It, 2-3 it, 2 items, 2 its, 1-3 K Keep, 3 KMParts, 1-3 kv, 1 L legacy, 1 less, 2 Limiting, 1-3 limiting, 1-2 Limits, 3 limits, 2 line, 2 lines, 1 Links, 1 Live, 2-3 live, 2-3 load, 2-3 Low, 1 low, 1 M magnitude, 2 maintain, 1 maintained, 1 Maintenance, 1 make, 2 manually, 2 manufactured, 1 manufacturer, 2 max, 3 maximum, 2 may, 2-3 means, 2 mechanical, 3 mechanisms, 2 Medium, 1 medium, 1 melted, 2 melting, 2 mentioned, 3 metal, 2-3 min, 3 mind, 3 minimum, 2 mount, 2 mounted, 2 Mounting, 2-3 mounting, 2-3

8 mountings, 3 mufflers, 2 must, 2 N name, 1 named, 1 National, 1 necessary, 2-3 need, 2 new, 3 next, 3 no, 2 Non, 2 non, 2-3 normally, 1-2 not, 2-3 O OEM, 3 of, 1-3 off, 3 On, 2 on, 1-3 once, 2 one, 2 only, 3 Operation, 1 operation, 2 operations, 2 or, 1-3 ordered, 3 other, 2 our, 1 out, 3 outdoor, 3 over, 1 overload, 2 Overview, 1 overview, 1 own, 1-2 P Page, 2 part, 2-3 Parts, 3 parts, 2-3 per, 1-2 perform, 2 performance, 1 piece, 2 pieces, 2 place, 2 Pole, 1 Power, 1-3 power, 1 practices, 1 previously, 3 produced, 2 Product, 1 products, 1-2 proper, 2 protect, 2 Protection, 1-3 provide, 2 provides, 2 providing, 3 publication, 1 pull, 3 purchase, 3 Purpose, 2 PURPOSELive, 3 R RANGE, 3 Range, 2 range, 2 Rangeused, 3 Rated, 1 rated, 2 ratings, 2 ratingsunit, 3 reduce, 2 Refer, 2 Refill, 2 refill, 2

9 refillable, 2 regularly, 1 removed, 2-3 removing, 2 replaceable, 2 replaced, 2 replacement, 2-3 required, 3 requirements, 1 resistance, 2 responsive, 2 result, 2 resulting, 2 results, 2 reusable, 2 ring, 3 roots, 1 S safely, 2 Sealed, 3 section, 2 see, 1-2 select, 1 separately, 2-3 separation, 3 series, 1-2 Service, 1 set, 1, 3 several, 2 shunt, 2 Single, 1 sold, 3 solely, 3 some, 1 sound, 2 sources, 1 specific, 1 Specifications, 1 specified, 2 spring, 2 Standard, 1 standards, 1 Static, 3 Std, 1 stick, 3 subsequent, 2 substations, 1 such, 2 supplied, 2 Support, 1-3 support, 2 Switches, 1 system, 1-2 T Tech, 1-3 technology, 1 temperature, 2 terminology, 1 Terms, 2 terms, 1 test, 1 tested, 1 Tests, 1 than, 1-2 that, 1-3 The, 1-3 the, 1-3 their, 1 then, 3 There, 2 Therefore, 1 therefore, 3 These, 1-2 these, 2 They, 2 they, 1, 3 this, 1 those, 1 three, 2 through, 2 time, 3 to, 1-3 today, 1 transformers, 2 trigger, 3 Type, 1, 3 Types, 2-3 types, 2 typically, 2

10 U under, 1 understand, 1 understanding, 1-2 unique, 1 Unit, 2 unit, 2-3 units, 2 unlatches, 3 until, 2 updated, 1 upper, 3 use, 1-3 used, 1-3 user, 2 using, 3 with, 1-3 within, 2 www, 1-3 Y years, 1 you, 1 Z zero, 3 V Vented, 3 vented, 2 visible, 3 Voltage, 1, 3 voltage, 1, 3 Voltageengineering, 1 Voltages, 1 Volume, 1-3 vs, 1-2 W were, 3 Westinghouse, 1 When, 2-3 when, 2-3 Where, 2 where, 1 which, 1-3 While, 1 will, 1

Electrical Sector Solutions Volume 14: Fuses

Electrical Sector Solutions Volume 14: Fuses Electrical Sector Solutions Volume Electrical 14: Sector FusesSolutions Volume 14: Fuses Volume 14 Fuses Tab 1 Fuses General....................................... V14-T1-1 Tab Expulsion Fuses.....................................

More information

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses) .7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous

More information

RBA Catalog Numbers and Information

RBA Catalog Numbers and Information 50 RBA s and Information Type RBA Expulsion Fuses for Use Indoors or in an Enclosure Ampere Rating Standard Speed (Fuse Refills) Curve Reference 36-635 Time-Lag (Fuse Refills) Curve Reference 36-635 Approx.

More information

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses)

2.7. Expulsion Fuses. Contents. RBA/RDB Type Fuses (Including Superseded BA Fuses) RBA/RDB Type Fuses (Including Superseded BA Fuses) .7 Expulsion Fuses RBA Fuses Product Description BA Fuses Westinghouse Electric Company introduced the BA range of DE-ION boric acid refillable fuses in the 1930s, and BA refill units have been in continuous

More information

3.2. Current Limiting Fuses. Contents

3.2. Current Limiting Fuses. Contents .2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse

More information

Expulsion Fuses. 2.2 Fuse Selection. 2.3 Application. 2.4 BA Type Fuses. 2.5 DBA Type Fuses. 2.6 DBU Type Fuses. 2.7 RBA and RDB Type Fuses

Expulsion Fuses. 2.2 Fuse Selection. 2.3 Application. 2.4 BA Type Fuses. 2.5 DBA Type Fuses. 2.6 DBU Type Fuses. 2.7 RBA and RDB Type Fuses Expulsion Fuses Eaton Expulsion Fuses.1 Product Overview Product Description....................................... Accessories............................................. Catalog Numbers.........................................

More information

CMU medium voltage power fuses

CMU medium voltage power fuses Fusing Equipment Catalog Data C132038EN Supersedes 240-94 December 2013 COOPER POWER SERIES General Eaton s Cooper Power series CMU power fuse is a boric acid, expulsion-style fuse. Suitable for both indoor

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

Boric Acid Fuse Links

Boric Acid Fuse Links Boric Acid Fuse Links BBU Fuse Link Mount Construction Bird proof design insulator provides insulation characteristics higher than ANSI distribution cut-out standards and equal in most cases to ANSI switch

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Product Selection Guide

Product Selection Guide Oil-Submersible Backup Fuses Full-Range CL Fuses External Backup Fuses Molded Fuse Products Product Selection Guide Introduction Electric distribution systems demand high levels of reliability, and flexibility

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection

More information

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866) .4 Miniature Circuit Breakers and Supplementary Protectors SPHM Supplementary Protector SPHM Supplementary Protector Product Description The SPHM Supplementary Protector is a dual rated product for both

More information

Contents. General Electric Sangamo Astra CTB JCT-10 R6B TAB, TA CSF JCM-0 R6BA TCB, AA CMF JCW-0 R6M AB

Contents. General Electric Sangamo Astra CTB JCT-10 R6B TAB, TA CSF JCM-0 R6BA TCB, AA CMF JCW-0 R6M AB Panelboards and Lighting Control Metering Service Sections.7 Metering Service Section Contents Description Metering Service Sections Page Catalog Number Selection........................ 482 Product Selection..............................

More information

BUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352

BUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352 8.3kV E-Rated Description: E-Rated, current-limiting, medium voltage fuses for feeder circuit, switchgear and transformer protection. Supersedes pril 2015 USSMNN SERIES Medium voltage fuses for feeder

More information

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

IEC Standard Back-Up Fuse-Links

IEC Standard Back-Up Fuse-Links 3 / 7.2 kv 6 / 12 kv 10 / 17.5 kv 10 / 24 kv 20 / 36 kv Ferrule German DIN Standard Beyond our line of ANSI / IEEE current-limiting fuses, Mersen offers a full line of medium voltage fuse links according

More information

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses CP No.: CP9716 Rev. 02 Page: 1 of 9 CERTIFIED TEST REPORT Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses Rev. 02 DATE: June 3, 2010 ORIGINAL REPORT DATE: June 13, 1997 Cooper Power Systems,

More information

Section 1 Introduction to the Presentation

Section 1 Introduction to the Presentation 2007 Thomas & Betts Section 1 Introduction to the Presentation Introduction of T&B Hi-Tech Fuses and our products Expulsion fuses vs. Current-Limiting fuses Hi-Tech s fuse construction & design features

More information

K-Limiter high ampere Companion II fuse

K-Limiter high ampere Companion II fuse Fusing Equipment Catalog Data CA132059EN Supersedes February 2016 COOPER POWER SERIES K-Limiter high ampere Companion II fuse General Eaton designs its Cooper Power series K-Limiter fuse to be conveniently

More information

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013 Kearney fuse links Supersedes December 2013 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009 Kearney fuse links Supersedes November 2009 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

C1000 Series Automatic Cap Bank

C1000 Series Automatic Cap Bank C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,

More information

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA 5670-100 Technical Guide 15 kv, 23 kv, & 35 kv General Description The Protective link is an oil immersed, expulsion type, fuse

More information

FX Full-Range Current-Limiting Fuse

FX Full-Range Current-Limiting Fuse Hi-Tech FX Full-Range Current-Limiting Fuses Trans-Guard FX Full-Range Current-Limiting Fuse Patented damage sensor significantly reduces the risk of fuse failure should the fuse be subjected to an element-damaging

More information

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C CP No.: CP1101 Rev. 00 Page: 1 of 9 CERTIFIED TEST REPORT 8.3, 9.9, 15.5, 17.2 and 23 Cooper ELSP Backup Fuses Testing per C37.41-2008 Rev. 00 DATE: May 3, 2011 ORIGINAL REPORT DATE: May 3, 2011 Cooper

More information

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification For Outdoor Substation Harmonic Filter Banks Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field

More information

Electrical Safety and Overcurrent Protection

Electrical Safety and Overcurrent Protection Electrical Safety and Overcurrent Protection Dave Vallier DSE Bussmann division Contact info: Phone: 586-201-1348 Email: Davemvallier@eaton.com Agenda 1. Electrical hazards overview 2. The role of the

More information

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD

More information

Medium Voltage Fuses. Industry s most comprehensive medium voltage circuit protection

Medium Voltage Fuses. Industry s most comprehensive medium voltage circuit protection Medium Voltage Fuses Industry s most comprehensive medium voltage circuit protection We have your solution For over 100 years, Bussmann fuses have provided superior circuit protection, enhanced safety

More information

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element Fusing Equipment Kearney Fuse Links Electrical Apparatus 327-40 general Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution

More information

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT Fusing Equipment Kearney Fuse Links Electrical Apparatus K-SEC 030 GENERAL Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems and equipment.

More information

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017

HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION. March 2017 HV DIN FUSE-LINKS FOR TRANSFORMER PROTECTION March 2017 HV FUSE-LINKS IN THE WORLD UL STANDARD E OR R RATED: AMERICAN STANDARD DIN STANDARD: GERMAN STANDARD FR STANDARD: FRENCH STANDARD BS STANDARD: BRITISH

More information

F1-1 ACCESSORIES AND SPARE PARTS FOR DRIWISA EQUIPMENTS INDOOR SERVICE OVERVIEW DRIESCHER Y WITTJOHANN, S.A.

F1-1 ACCESSORIES AND SPARE PARTS FOR DRIWISA EQUIPMENTS INDOOR SERVICE OVERVIEW DRIESCHER Y WITTJOHANN, S.A. ACCESSORIES AND SPARE PARTS FOR DRIWISA EQUIPMENTS OVERVIEW has always been concerned with keeping a service policy for its products by means of a wide range of DRIWISA spare parts', original parts' and

More information

34-SDMS-02 SPECIFICATIONS FOR

34-SDMS-02 SPECIFICATIONS FOR SPECIFICATIONS FOR M V & L V FUSE LINKS This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Circuit Protection Solutions. Medium Voltage Boric Acid Fuses

Circuit Protection Solutions. Medium Voltage Boric Acid Fuses Circuit Protection Solutions Medium Voltage Boric Acid Fuses WORLD-WIDE CIRCUIT PROTECTION SOLUTIONS Cooper Bussmann are one of the world s leading suppliers of fuses and fusible protection systems. Provider

More information

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report File Ref: CA132015EN Effective Mar 2015 COOPER POWER CT132001EN SERIES 38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report CT132001EN Page: 3 of 9 Introduction Eaton designs its Cooper

More information

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

OVERALL LENGTH (B)  ( mm)  ( mm)  ( mm)  ( mm) 1 4-20 threaded hole 1 2" deep (both ends) Dimensional Information NOMINAL CURRENT CAT. NO. 40 HTSS232040 50 HTSS232050 65 HTSS232065 80 HTSS232080 100 HTSS232100 125 HTSS232125 150 HTSS232150 165 HTSS232165

More information

Design Standards NEMA

Design Standards NEMA Design Standards Although several organizations are involved in establishing standards for the design, construction, and application of motor control centers, the primary standards are established by UL,

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

Ampgard The name motor applications rely on

Ampgard The name motor applications rely on Medium-voltage motor control Ampgard The name motor applications rely on Oil and gas Mining Water/wastewater Pulp and paper Utility Ampgard medium-voltage control solutions Eaton has been an industry leader

More information

Power Fuses. > Power Fuses > BPA & HPA kv AMPs

Power Fuses. > Power Fuses > BPA & HPA kv AMPs The equipment described in this bulletin performs in accordance with NEMA standards publication SG2-1954, paragraphs SG2-5, SG2-5.10, and SG2-5.11 TYPE BPA Power Fuses 7.2-161 kv 100-200-300 400 AMPs The

More information

CS-3 SERIES E-RATED/MEDIUM VOLTAGE FUSES

CS-3 SERIES E-RATED/MEDIUM VOLTAGE FUSES SERIES E-RATED/MEDIUM VOLTAGE FUSES 5kV, 8kV and 15.5kV FERRULE MOUNTED FUSES Amp-trap E-rated 5kV 8kV and 15kV fuses have 2 or 3 inch diameter barrels with ferrules and are mounted in spring reinforced

More information

42.4. Terminal Blocks, Fuse Blocks and Fuse Holders. For Immediate Delivery or Tech Support call KMParts.com at (866)

42.4. Terminal Blocks, Fuse Blocks and Fuse Holders. For Immediate Delivery or Tech Support call KMParts.com at (866) .4 Terminal Blocks, Contents Description C383 Series Disconnect Fuse Holders...... C350 Series Fuse Blocks and W Series Fuse Holders.................. Page V7-T-129 V7-T-131 Overview Product Description

More information

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S ) Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The

More information

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C Page:1 of 9 CERTIFIED TEST REPORT Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C37.41-2008 REV. 00 August 11, 2014 Original Report Date: August 11, 2014 Eaton s Cooper Power Systems

More information

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES

CL-14 SERIES E-RATED / MEDIUM VOLTAGE FUSES SERIES E-RATED / MEDIUM VOLTAGE FUSES 5kV AND 15kV CLIP-LOCK MOUNTED FUSES Amp-trap E-rated 5kV and 15kV fuses have 3" diameter barrels and mount in unique cam-locking clips, for superior connections as

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

PROTECTION AND CONTROL

PROTECTION AND CONTROL B C Table 1 DIMENSIONAL Information for Trans-Guard OS Fuses Fuse Voltage Rating (kv) 1/4-20 threaded hole 1/2 deep (both ends) Current Rating (Amps) Fuse Catalog Number 35 HTDS232035 Overall Diameter

More information

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast). FUSE CATALOG 2 Table 1.-Elemsa code and characteristics of Type K fuse links (Fast). TYPE DESCRIPTION CAT PAGE 15K-1 UNIVERSAL TYPE FUSE LINK 2066A1 38K-1 UNIVERSAL TYPE FUSE LINK 2070A1 15K-2 UNIVERSAL

More information

Tolerance-Based Time-Current Coordination

Tolerance-Based Time-Current Coordination S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Tolerance-Based Time-Current Coordination Table of Contents Section Page Section Page Overview Background....

More information

Medium voltage fuses Medium voltage fuses

Medium voltage fuses Medium voltage fuses European Fuses DIN Fuses 7.2kV - 36kV IBD 7.2 UP TO 36 KV HIGH-VOLTAGE FUSES DESIGNED FOR POWER TRANSFORMER PROTECTION INTERIOR/EXTERIOR USE CERAMIC HOUSING MEDIUM CLASS TRIP-INDICATOR COMBINED WITH A

More information

PT Medium voltage fuses for potential and small power transformers

PT Medium voltage fuses for potential and small power transformers Technical Data 6002 BUSSMANN Supersedes December 2017 SERIES PT Medium voltage fuses for potential and Description: Bussmann series Indicating and nonindicating E-Rated, current-limiting, medium voltage

More information

Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses

Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses WHITE PAPER Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses The Trans-Guard EXT and Trans-Guard OS Shorty fuses, designed and manufactured by ABB under its Hi-Tech brand, are backup current-limiting

More information

FUSE TECHNOLOGY Ambient temperature

FUSE TECHNOLOGY Ambient temperature This fuse technology guide will discuss basic fuse operating, application, and selection criteria concepts. The intended purpose of this section is to aid designers with the operation and characteristics

More information

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN Surge Arresters MN235004EN Effective December 2015 Supersedes S235-26-1 August 2012 COOPER POWER SERIES Surge arrester interchangeable fuse cutout combination installation instructions DISCLAIMER OF WARRANTIES

More information

Medium Voltage Fuses

Medium Voltage Fuses 2,400-38,000 VAC General Information Current-limiting E and rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of the fuse. This provides

More information

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer Achieving Higher Short Circuit Current Ratings for Industrial Control Panels Standards & codes note 1 By Steve Hansen Sr. Field Engineer Introduction Articles 9.1 and. in the National Electrical Code require

More information

X-Limiter full-range current-limiting fuse

X-Limiter full-range current-limiting fuse Fusing Equipment Catalog Data CA132050EN Supersedes 240-56 June 2012 COOPER POWER SERIES X-Limiter full-range current-limiting fuse General Eaton's Cooper Power series X-Limiter full-range current-limiting

More information

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com DE-ION CURRENT-LIMITING POWER FUSE-TYPE BAL prevents short circuit s from reaching their maximum value and thereby provides greater protective capacity for both the connected apparatus and the feeder system.

More information

Industry s most comprehensive medium voltage circuit protection

Industry s most comprehensive medium voltage circuit protection Medium voltage fuses BUSSMANN SERIES Industry s most comprehensive medium voltage circuit protection We have your solution For over 100 years, Bussmann TM series fuses have provided superior circuit protection,

More information

Type ICX Interchangeable Cutout kv Outdoor Distribution Cutout Product Bulletin 1VAG DB

Type ICX Interchangeable Cutout kv Outdoor Distribution Cutout Product Bulletin 1VAG DB Type ICX Interchangeable Cutout 15-38 kv Outdoor Distribution Cutout Product Bulletin 1VAG271201-DB Product Features 15, 27, or 38 kv 110, 125, 150, 180, or 200 kv BIL 100 A, 200 A Fused 300 A Disconnect

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Figure 1. HX cutout fuseholders.

Figure 1. HX cutout fuseholders. Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus K-SEC 010 GENERAL Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted

More information

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required! DB 750-205 January 2007 Supercedes: December 2006 Now available with Vacuum Interrupter Monitor VBT Switch 15kV - 69kV VBU-T Switch 69kV - 230kV Longest Life Product for Electric Furnace Applications!

More information

Figure 1. HX cutout fuseholders. Positive Interruption

Figure 1. HX cutout fuseholders. Positive Interruption Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus 327-10 general Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted to

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

GE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?

GE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault? By Mark Clapper GE Specification Engineer Introduction To address the increasing concerns and standards around arcing faults, GE challenged our Global Research Center to develop a new, active method of

More information

Connect - Contact - Control. Fuses for high-voltage switchgear F-HS, F-VS Series Ø 60. F 185.en

Connect - Contact - Control. Fuses for high-voltage switchgear F-HS, F-VS Series Ø 60. F 185.en Connect - Contact - Control Fuses for high-voltage switchgear, F-VS 10 10 +0.3 60 7.5 0 F 185.en Fuses for high-voltage switchgear, and F-VS For the protection of high-voltage switchgear Schaltbau offers

More information

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection

More information

Metal-enclosed medium-voltage power factor correction system

Metal-enclosed medium-voltage power factor correction system Technical Data TD02607011E Supersedes June 2011 Metal-enclosed medium-voltage power factor correction system Contents Description Page Medium-voltage power factor correction... 1 Product description...

More information

AutoLink Frequently Asked Questions

AutoLink Frequently Asked Questions Rev. 3 October 2013 Page 1 of 8 AutoLink Frequently Asked Questions October 2013 1 Rev. 3 October 2013 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the AutoLink Single Phase Electronic Sectionalizer?...

More information

4-Day Power System Analysis, Coordination, System Studies

4-Day Power System Analysis, Coordination, System Studies 4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our

More information

FUSE: SAFE & RELIABLE

FUSE: SAFE & RELIABLE FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced

More information

Fuses still the best form of overload protection

Fuses still the best form of overload protection Fuses still the best form of overload protection 2001 George Moraitis (Fuseco Pty. Ltd.) Often when I visit people to talk about circuit protection I hear the comments fuses are a thing of the past and

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

ZX2 Gas-insulated medium voltage switchgear

ZX2 Gas-insulated medium voltage switchgear Gas-insulated medium voltage switchgear Double busbar 13 8 10 12 11 10 9 8 7 2 1 3 4 5 6 2 Versatile Partitioned single or double busbar system for all applications even with the most demanding parameters

More information

NX indoor current-limiting fuses

NX indoor current-limiting fuses Fusing Equipment Catalog Data CA132049EN Supersedes 240-60 September 2009 COOPER POWER SERIES NX indoor current-limiting fuses General Eaton provides overload protection for all indoor and underground

More information

Figure 1. Kearney Type HX cutout.

Figure 1. Kearney Type HX cutout. Fusing Equipment Kearney Open Distribution Cutouts Type HX Installation Instructions Service Information KS010-01-1 CONTENTS Product Information...........................1 Safety Information............................2

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

SIEMENS. Current-Limiting Fuses. DESCRIPTION ceo '1 I. 2.4 and 4.8 Kv for Motor Starting Application. Type FM. Page 1 EFFECTIVE FEB..

SIEMENS. Current-Limiting Fuses. DESCRIPTION ceo '1 I. 2.4 and 4.8 Kv for Motor Starting Application. Type FM. Page 1 EFFECTIVE FEB.. j SEMENS DESCRPTON CurrentLimiting Fuses 2.4 and 4.8 Kv for Motor Starting Application The fuse (Fig. ) is a totallyenclosed currentlimiting fuse, designed for motorstarting applications. t is available

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Substation Committee K2 TF1 of the GIS Subcommittee GIS/GIL/SF 6 -Tutorials

Substation Committee K2 TF1 of the GIS Subcommittee GIS/GIL/SF 6 -Tutorials IEEE/PES Substation Committee - Subcommittee IEEE Substation Committee K2 TF1 of the Subcommittee /GIL/SF 6 -Tutorials -1- IEEE/PES Substation Committee - Subcommittee IEEE Gas Insulated Switchgear ()

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#:

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#: Single phase pole mounted Distribution Transformers 11kV Prepared by: ARY SAIDAHMED SHEKSAEED Electrical Engineer KEU ID#: 4252 Email: ary.sayd@hotmail.com 1 S # Contents Page # 1 Introduction 3 2 Type

More information

S&C SMD -20 Power Fuses

S&C SMD -20 Power Fuses S&C SMD -20 Power Fuses Outdoor Distribution (14.4 kv through 34.5 kv) SMD-20 Power Fuses offer full-fault-spectrum protection. They detect and interrupt all faults large, medium, and small even down to

More information

CATALOG. Hi-Tech Fuse Products

CATALOG. Hi-Tech Fuse Products CATALOG Hi-Tech Fuse Products Thomas & Betts is now ABB Installation Products, but our long legacy of quality products and innovation remains the same. From connectors that help wire buildings on Earth

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH HH DRIESCHER - High-voltage high breaking capacity fuses from 1 kv up to 36 kv HH HH ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-866 MOOSBURG TEL. +9 87 61 6 81-0 FAX +9 87 61 68 11 37 http://www.driescher.com

More information

High-voltage high-breaking capacity VV fuse-links

High-voltage high-breaking capacity VV fuse-links High- high- VV fuse-links imum cold resistance power dissipation pre-arcing I t value total I t value [kv] (mm) I n [A] (ka) [mω] [W] [A s] [A s] 1 580,1 57 A 0 370 9 17,3 1 A 5 00 10 3 30 10 A 55 7 11

More information

EUROPEAN HIGH VOLTAGE FUSES

EUROPEAN HIGH VOLTAGE FUSES EUROPEAN HIGH VOLTAGE FUSES AS PER IEC 60282 EDUPACK TRAINING MODULE 2012 HH DIN NF MEDIUM OR HIGH VOLTAGE FUSE? High Voltage is the official definition provided by the standard. High Voltage starts just

More information