Excitation systems for high power synchronous generators with redundant configurations
|
|
- Christopher Cole
- 6 years ago
- Views:
Transcription
1 Excitation systems for high power synchronous generators with redundant configurations Zvonimir Jurin, Blaženka Brkljač, Marin Kolić KONČAR Elektronika i informatika Fallerovo šetalište 22, Zagreb, Croatia uzbude@koncar-inem.hr tel Mladen Kajari, Vinko Ćesić, KONČAR Institut za elektrotehniku Fallerovo šetalište 22, Zagreb, Croatia mkajari@koncar-institut.hr tel Abstract In the article the solutions of synchronous generator excitation system with thyristor converter, digital voltage regulator and field discharge equipment are presented with attention paid to achieve increased reliability and availability by applying redundant configurations. The excitation system with thyristor converter in three-phase fully controllable bridge connection and 1+1 configuration, twin channel digital voltage regulator and field discharge equipment for big and important generators in parallel operation are shown. Field results verify the project-foreseen characteristics and qualities of presented solution. I. INTRODUCTION To achieve high availability of synchronous generators for electric energy production, attention has to be paid to the increase of availability of all generator subsystems and among them of the synchronous generator excitation system during a very long-term service. Requirements on availability of excitation system, beside its technical functions, have been always high and improvements are still being implemented. The excitation system consists of exciter (the excitation power source) and voltage regulator. In the article, the solutions of thyristor rectifier exciter and digital voltage regulator are discussed with the aim of achieving reliable and redundant configurations with increased availability in synchronous generators operation. The actual solution of an excitation system consists of a big number of electrical, electronic and mechanical components and software products, working together under heavy technical conditions. The basic technical environmental requirements are extreme working and storage temperatures, their deviations and rate of change, combined with humidity, dust and oil vapour, vibrations and shock strains and electromagnetic interference. The requirements on excitation power source depend on machine characteristics and its role in power system. There are potential-source and controlled rectifier exciter (static excitation system), alternator supplied rectifier excitation system (brushless excitation system) that use mechanical power on generator shaft and auxiliary constant voltage shaft generator and static thyristor rectifier. The compound-source controlled-rectifier exciter that utilizes the potential and the current of synchronous generators, as an excitation power source, together with thyristorcontrolled rectifier is also used for special purposes. The actual and world most common solutions of high power synchronous generator excitation system, is potential source thyristor rectifier exciters with digital voltage regulator. The basic approach to achieve high reliability and availability is application the proper ratings for components and usage of high quality components. To avoid production failures comprehensive during and after production tests and commissioning have to be carried out. Beside that it is not possible to guarantee that no failure can occur. Fig. 1: Block diagram of a static excitation system with thyristor converter in 1+1 configuration, the twin channel digital voltage regulator and discharge equipment A1-55
2 To minimize risks of failure of synchronous generators excitation system and outage of production of the generator the hardware and software redundancy is applied: significant disturbance of generator operation. Converters have redundant cooling fans. 1. Thyristor converter configuration n-1 and 1+1, 2. Twin channel digital voltage regulator 3. Field discharge equipment and field overvoltage protection The block diagram of a static excitation system with thyristor converter in 1+1 configuration, the twin channel digital voltage regulator and discharge equipment is in Fig 1. II. THYRISTOR CONVERTER CONFIGURATIONS N-1 AND 1+1 The standard solution of excitation system thyristor converter is a three-phase bridge converter with 1 thyristor in series and n thyristor in parallel per bridge arm. Fast fuse is in series with each thyristor, Fig 2. The number of parallel thyristors per arm is n>3, to maintain selectivity of fuse protection. Current ratings of thyristor are so that n-1 thyristor per arm are capable to withstand all static and transient ratings and one additional thyristor per arm is for security reasons. The converter has redundant fans. Fig. 3. Thyristor converter in 1+1 configuration Behaviour of generator and excitation voltage after simulated failure on one thyristor in the operating thyristor bridge is shown in Fig. 4. Transfer to the second bridge is carried out in app. 50 ms. Fig. 2. Thyristor converter in n-1 configuration The nowadays-applied configuration of thyristor converter is 1+1 Fig. 3, because high rating thyristors are now available. This configuration consists of two equal three-phase bridge converters with 1 thyristor in series and 1 thyristor in parallel per bridge arm. Fast fuse is in series with each thyristor. Each bridge is rated to withstand all static and transient generator excitation ratings. One bridge converter is in operation while the other is hot stand-by. AC current of bridges are monitored and in case of a thyristor failure the changeover is taking place using free wheeling thyristor without any Fig. 4. Transfer of excitation Converter Bridge 1 to Bridge 2 in the 1+1 configuration with the generator in parallel operation to the grid A1-56
3 III. TWIN CHANNEL DIGITAL VOLTAGE REGULATOR The single channel digital voltage regulator in comparison to the analogue voltage regulator offers a lot of benefits such as: Performing of sophisticated control, protection, supervision and logical and sequential control functions, Short response time, Long term stability, Self monitoring functions, Reduced diversity of hardware modules, Digital standardized communication to the superimposed control system. Twin channel digital voltage regulator is a solution with two identical digital voltage regulators working in parallel in hot stand-by configuration. Each of two channels has the same input signals and is executing the same application program. Each channel has a complete structure with automatic and manual voltage control, reactive power regulation, limiters protecting the generator of going-out the generator capability diagram, compound function, V/Hz limiter and power system stabilizer (PSS) functions. Every channel controls both thyristor bridges Comprehensive monitoring program monitors the function of both regulators and in case of detection of an irregularity or exception the changeover is performed to the healthy channel without interfering normal generator operation. Fig. 5. Changeover of Channel 1 to Channel 2 with generator in parallel operation to the grid The changeover between channels of two-channel digital voltage regulator after simulated disturbance in operating channel is shown in Figure 5. IV. FIELD DISCHARGE EQUIPMENT AND FIELD OVERVOLTAGE PROTECTION There are two basic solutions of generator field discharge equipment, one, which include DC field circuit breaker with discharge contact, non-linear discharge resistor and separate circuit for overvoltage protection and second which includes AC circuit breaker with common circuit for discharge and overvoltage protection. Besides, there is normal operative procedure for generator deexcitation, the transfer of thyristor exciter to inverter operation mode. In classic solutions of discharge equipment the thyristor converter is connected to synchronous machine field winding via de- excitation D.C. breaker with a discharge contact and a discharge resistor, Fig. 6. When instantaneous electrical fault arises in the synchronous machine or in outside facilities, the short-circuit current will appear and the field should be suppressed as quickly as possible in order to limit fault current damage. It is also necessary to ensure safe de-excitation in event of a fault in the exciter control circuit causing severe over-excitation. The voltage dependent or linear discharge resistor is used to achieve rapid field suppression with regard to the highest permissible voltage across the field winding and the field breaker. The purpose of the rotor overvoltage protection is to prevent the machine field and thyristor converter from being exposed to an excessive overvoltages induced in the machine field with rectifier excitation, which could arise during certain transient condition such as improper synchronizing, loss of synchronism and asynchronous operation. The main overvoltage protection circuit comprises the antiparalell connected thyristor (crow bar) and resistor in series. The thyristors are controlled by the over-voltage sensing triggering unit with BOD elements. When the voltage exceeds the preset protection level the thyristor switch-on and conduct the current caused by over voltage. The series resistor is intended to limit the current in the protection circuits. On the other hand, the resistor must be so designed that the voltage drop caused by the highest induced field current flowing through the resistor does not exceed the protection level. The overcurrent relay supervises of the protection and gives a tripping impulse when the protection operates. When thyristor converter is applied in configuration 1+1, freewheeling thyristor is used to short-circuit field winding during emergency change over between bridges under high currents. A1-57
4 Fig. 6 Discharge equipment with DC field circuit breaker and separate circuit for rotor over voltage protection In the Fig. 6 the usual and most adequate solution for the field circuit breaker and over voltage protection is shown. The merits of this solution are the completely independent over voltage protection circuit and field circuit breaker that separates generator excitation on both poles from thyristor rectifier. In case of failure on field circuit breaker or non-linear deexcitation resistor, the rotor over voltage protection could act as back-up deexcitation. Usually DC field circuit breaker has two coils for switching-off, which, together with monitoring of switching-off circuits, realize very reliable solution. The alternative solution of discharge equipment is implementation thyristors from thyristors over-voltage protection (crow bar) and AC circuit breaker at primary of thytistor rectifier Fig. 7. Deexcitation is performed by switching-off of the AC circuit breaker what causes the over voltage on the generator excitation winding. This over-voltage will activate over-voltage protection (crow bar), reduce the overvoltage and deexcite the generator. In this case the same resistor is used for the de-excitation and for the field circuit over voltage protection, and in a case of its failure, there is no redundant deexcitation circuit to prevent damage of rotor winding. Fig. 7 Discharge equipment with AC field circuit breaker and common discharge resistor wit rotor over voltage protection Fig. 8 Discharging of generator by DC field circuit breaker and nonlinear discharge resistor Site tests are carried out on excitation system type SEM 11E, delivered and putted into operation for two units on Hydro Power Plant Varaždin. Generator and excitation system data are given in Table 1. It is Potential source thyristor rectifier exciter (static excitation system) supplied from the generator terminals. It is controlled by twin (two) channel digital voltage controller with separate hardware for each channel. Each channel of digital voltage regulator comprises Generator voltage regulator (AVR), Excitation current regulator (SR), Trigger pulse system and Follow-up control between main and stand-by controller, and between AVR and SR mode for each channel. Excitation power is derived by: three-phase fully-controlled (6-pulse), air forced cooled, thyristor converter in configuration 1+1, with one thyristor per branch and two converter bridges in parallel. One thyristor bridge is in stand-by and blocked. TABLE I GENERATOR AND EXCITATION SYSTEM DATA Unit A Unit B Rated power S n MVA Nominal voltage U n KV Power factor cosϕ n Speed n n min Frequency f n Hz Nominal current In A Nominal excitation current I fn A Nominal excitation voltage U fn V Nominal exciter current I EN A Ceiling current I p A A1-58
5 V. CONCLUSION The presented excitation system with redundant configuration with a thyristor converter in consisting 1+1 three phase thyristor bridges, classic discharge equipment with field circuit breaker and separate circuit for over-voltage protection, and microprocessor based twin-channel voltage regulator is suitable for big and important synchronous machines in parallel operation. The excitation system is characterized by increased safety, reliability and availability because of build-in redundancy. Field results have verified characteristics in exploitation and qualities of presented strategy. REFERENCE [1] Z. Jurin, M. Kolić, M. Kajari, V. Ćesić: Redundant configuration in synchronous generator excitation system Hydro conference, Dubrovnik [2] S. Marijan, M. Kajari, N. Perić: Microprocessorbased Control System for Electrical Machines, Proceedings of the 8th International Conference on Electrical Drives and Power Electronics, EDPE 94, Pula, Croatia, pp , September [3] Mladen Kajari, Siniša Marijan, Vinko Ćesić, Nedjeljko Perić: Digital Control of a Synchronous Generator Excitation System, Proceedings of the 8th International Conference on Electrical Drives and Power Electronics, EDPE 94, Pula, Croatia, pp , September [4] N. Perić, S. Marijan, M. Kajari: Microprocessorbased control system for the control of electrical machines and processes. 6th European Conference on Power Electronics and Applications, EPE 95, Sevilla, pp ( ) [5] S. Marijan, M. Kajari, N. Perić: Microprocessorbased control system for electrical machines, Automatic 1-2/1995, Zagreb, pp (19-26). [6] V. Ćesić, M. Kajari, S. Marijan, Z. Jurin, M. Kolić: Excitation system with microprocessor based twin-channel voltage regulator for synchronous machines, EPE-PEMC Dubrovnik & Cavtat, A1-59
6 A1-60
RT2DB Excitation and voltage regulation system for synchronous generators
s RT2DB Excitation and voltage regulation system for synchronous generators Fully digital. Parameter settings done by software. Self monitoring routines. Maintenance free. High reliability. Excellent dynamic
More informationELECTRIC TRACTION.
ELECTRIC TRACTION www.koncar.hr MODERNISATION ELECTRIC TRACTION VEHICLES Company KON AR - ELECTRIC VEHICLES Inc. upgrades electric locomotives, electric multiple unit and electric tramcars. Upgrading proceedings
More informationUnit Protection System for Pumped-Storage Power Stations
Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve
More informationDouble earth fault in a PSP during back to back launching sequence
Double earth fault in a PSP during back to back launching sequence Jean-Louis DROMMI EDF Hydro Engineering Center, France Pump Storage Scheme, back to back launching Electricité de France Hydro Department
More informationproduction program 1
production program 1 Končar Group Founded in 1921, KON AR nowadays consists of 19 companies and one subsidiary company, employing more than 4,000 people. Annual sales account for EUR 350 million, with
More informationResearch and Reviews: Journal of Engineering and Technology
Research and Reviews: Journal of Engineering and Technology Brushless Excitation System of Turbo Generator Komala Koila* Department of Electrical and Electronics, Khammam Institute of Technology and Sciences,
More informationUNITROL 6800 excitation systems Proven performance solutions
UNITROL 6800 excitation systems Proven performance solutions Setting the standard ABB is the world leading volume supplier of UNITROL automatic voltage regulators (AVR) and static excitation systems (SES)
More informationMEDIUM VOLTAGE DISCONNECTOR SWITCHES for indoor installation
KON^AR KONCAR MEDIUM VOLTAGE APPARATUS, Inc. MEDIUM VOLTAGE DISCONNECTOR SWITCHES for indoor installation Series RSN General Information Disconnector switches are part of traditional medium voltage assortment.
More informationEXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR
EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR Velimir Nedic Thomas A. Lipo Wisconsin Power Electronic Research Center University of Wisconsin Madison
More informationINTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)
INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This
More informationAsynchronous Generators with Dynamic Slip Control
Transactions on Electrical Engineering, Vol. 1 (2012), No. 2 43 Asynchronous Generators with Dynamic Slip Control KALAMEN Lukáš, RAFAJDUS Pavol, SEKERÁK Peter, HRABOVCOVÁ Valéria University of Žilina,
More informationWind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment
2012 2nd International Conference on Power and Energy Systems (ICPES 2012) IPCSIT vol. 56 (2012) (2012) IACSIT Press, Singapore DOI: 10.7763/IPCSIT.2012.V56.2 Wind Power Plants with VSC Based STATCOM in
More informationFunctions provided by measuring relays in railway equipment
Functions provided by measuring relays in railway equipment 1-Current relays -Minimum current relays (During normal operation, if the current is present these relays are in operating position and switch
More informationModular Standardized Electrical and Control Solutions for Fast Track Projects
Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive
More informationINTER PLANT STANDARD - STEEL INDUSTRY THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS. Corresponding IS does not exist
INTER PLANT STANDARD - STEEL INDUSTRY IPSS THYRISTOR CONVERTORS FOR ARMATURE AND FIELD OF MAIN DRIVE MOTORS Corresponding IS does not exist IPSS: 1-10-038-08 0 FOREWORD 0.1 This Inter Plant Standard has
More informationElectrical Power Systems 2014/15
www.hft-education.com 2014/15 Electrical Power Engineering is fundamental to maintaining and protecting global electricity supply and preventing catastrophic power failures. With the current investment
More informationKONČAR Group. Research and Development
production program 2 KONČAR Group KONČAR Group consists of 20 companies and has around 4000 employees. Annual sales account for more than 300 million euros, with almost half the amount in exports. KONČAR
More informationPower Systems Trainer
Electrical Power Systems PSS A self-contained unit that simulates all parts of electrical power systems and their protection, from generation to utilisation Key Features Simulates generation, transmission,
More informationFAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE
FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE Yunqi WANG, B.T. PHUNG, Jayashri RAVISHANKAR School of Electrical Engineering and Telecommunications The
More informationSafety technique. Emergency Stop Module BH 5928, BI 5928
Safety technique Emergency Stop Module BH 5928, BI 5928 with time delay safemaster 0226419 Function diagram According to EU directive for machines 98/37/EG According to IEC/E 60 204, E 954-1 Safety category
More informationSINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options
/2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /1 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions
More informationBRUSHLESS EXCITERS FOR TURBINE GENERATORS
BRUSHLESS EXCITERS FOR TURBINE GENERATORS Economical, Manpower Saving Exciters Based on State-of-the-Art Technology. Mitsubishi Electrical manufactures brushless exciters for all types of turbine generator,
More informationModeling of 25 kv Electric Railway System for Power Quality Studies
Modeling of 25 kv Electric Railway System for Power Quality Studies Alan Župan 1, Ana Tomasović Teklić 2, Božidar Filipović-Grčić 3 1 HEP-Transmission System Operator Kupska 4, Zagreb, Croatia alan.zupan@hep.hr
More informationEPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION
EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy*** *Swiss Federal Institute of Technology, Electrical
More informationJ.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***
EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy*** *Swiss Federal Institute of Technology, Electrical
More informationDate Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More information9.1.4 Troubleshooting of Faults in LCD Screen
User Manual 9 and Maintenance 9.1.2 Arc Detection Self-test An auto-test circuit is included in the module design of the inverter s AFDI function. If a DC arc fault is detected, the corresponding fault
More informationNO-BREAK KS. Dynamic UPS system PRESENTATION
NO-BREAK KS Dynamic UPS system PRESENTATION Contents Chapter 1: Description of No-Break KS System...3 Chapter 2: Operation when mains power is available...4 Chapter 3: Operation when mains supply is disrupted...6
More informationProtective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON
21, rue d Artois, F-75008 PARIS B4-70 CIGRE 2016 http : //www.cigre.org Protective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON VILES Consulting
More informationReverse power relay and protection assemblies
Reverse power relay and protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE980053) (SE980054) Features Micro-processor based time directionalcurrent relay/protection
More informationUsing energy storage for modeling a stand-alone wind turbine system
INTERNATIONAL JOURNAL OF ENERGY and ENVIRONMENT Volume, 27 Using energy storage for modeling a stand-alone wind turbine system Cornel Bit Abstract This paper presents the modeling in Matlab-Simulink of
More informationResearch on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC
Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More informationT5S4P3 Synchronous Condensers Application. Mr. Marco Schenone Mr. Sandro Tuscano Mr. Alessandro Oldrati
Mr. Marco Schenone Mr. Sandro Tuscano Mr. Alessandro Oldrati 1 Introduction Ansaldo Energia has recently completed the manufacture, installation and commissioning of two synchronous condenser sets for
More informationThe behavior of the cycloconverter fed gearless drive under abnormal electrical conditions
Mining The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Reprint Authors: Kurt Tischler Siemens AG, Mining Technologies, Erlangen, Germany Reprint: WORKSHOP SAG
More informationTURBO GENERATORS BEST QUALITY FOR THERMAL POWER PLANTS
TURBO GENERATORS BEST QUALITY FOR THERMAL POWER PLANTS 1 2 Turbo generators with top modern standards International technology group ANDRITZ is a globally leading supplier of plants, equipment, and services
More informationWind protection. Low-voltage switching and protection strategies in wind turbines
Wind protection Low-voltage switching and protection strategies in wind turbines ANTONIO FIDIGATTI, PAOLO BARONCELLI, MARCO CARMINATI, ENRICO RAGAINI Wind turbines come in different designs, each with
More informationFuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators
Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators Abstract: G. Thrisandhya M.Tech Student, (Electrical Power systems), Electrical and Electronics Department,
More informationEnhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor
> 57 < 1 Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor Masaki Yagami, Non Member, IEEE, Junji Tamura, Senior Member, IEEE Abstract This paper
More informationWorld Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants
World Class Power Solutions Rectifiers For Stationary Battery Systems in Nuclear Power Plants General 2 1.1 Application Electronically controlled rectifier assemblies are used in conjunction with suitable
More informationTechnical Data Accessories MCBs Ex9B.
Auxiliary and signal contact units AX31, A31, AX31 General parameters With one circuit breaker Ex9B., it can be used up to three contact units with single CO contact or up to two contact units with 2 CO
More informationTECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008
NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationPower Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device
Australian Journal of Basic and Applied Sciences, 5(9): 1180-1187, 2011 ISSN 1991-8178 Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device
More informationTOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS
INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...
More informationCopyright 2003 Advanced Power Technologies, Inc.
Overview of the Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547 and it s potential impact on operation of the Distributed Generation (DG) systems and on the design
More informationSecond Edition. Power Electronics. Devices and Circuits. V. Jagannathan
Second Edition Power Electronics Devices and Circuits V. Jagannathan Power Electronics Devices and Circuits SECOND EDITION V. Jagannathan Professor and Head Department of Electrical and Electronics Engineering
More informationSola/Hevi-Duty S3K Series Mini-Tower UPS
Sola/Hevi-Duty S3K Series Mini-Tower UPS GUIDE SPECIFICATIONS 700VA to 1600VA 120V models Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical
More informationA novel synthetic test system for thyristor level in the converter valve of HVDC power transmission
A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission Longchen Liu 1, Ke Yue 2, Lei Pang 2, Xinghai Zhang 1, Yawei Li 1 and Qiaogen Zhang 2 1 State Grid Sichuan
More informationINTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS
INTER PLANT STANDARD STEEL INDUSTRY SOFT STARTER FOR VOLTAGE UP TO 690 V AC IPSS: 1-10-040-15 IPSS NO CORRESPONDING IS 0. FOREWORD 0.1 This interplant standard has been prepared by the Standard Committee
More informationSINAMICS GM150 IGCT version
/2 Overview /2 Benefits /2 Design /6 Function /8 Selection and ordering data /8 Options Technical data /14 General technical data /15 Control properties /15 Ambient conditions /16 Installation conditions
More information(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)
Technical Paper: Low voltage ride-through testing of wind turbine converters at ABB helps wind turbines meet the requirements of IEC 61400-21 more quickly (by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka
More informationPOWER TRANSMISSION OF LOW FREQUENCY WIND FIRMS
Available Online at www.ijcsmc.com International Journal of Computer Science and Mobile Computing A Monthly Journal of Computer Science and Information Technology IJCSMC, Vol. 3, Issue. 10, October 2014,
More informationModeling and Simulation of Firing Circuit using Cosine Control System
e t International Journal on Emerging Technologies 7(1): 96-100(2016) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Modeling and Simulation of Firing Circuit using Cosine Control System Abhimanyu
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements
Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner
More informationDESIGN AND IMPLEMENTATION OF THREE PHASES AUTOMATIC CHANGE OVER SWITCH
435 DESIGN AND IMPLEMENTATION OF THREE PHASES AUTOMATIC CHANGE OVER SWITCH I,. I.,.. I i i, i i y A i, i,, ABSTRACT: Many industries whose machines are three phases depends on three single change over
More informationCOMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES
Maszyny Elektryczne Zeszyty Problemowe Nr 3/2015 (107) 89 Stefan Schmuelling, Christian Kreischer TU Dortmund University, Chair of Energy Conversion Marek Gołȩbiowski Rzeszow University of Technology,
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE
Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 023 AVR Features ALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE AVRs On STAMFORD alternators, analogue AVR
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationPower Electronics. Motor brake relay GA 9031 ministop
Power Electronics Motor brake relay GA 90 ministop 0 Thyristor electronic brake relay for motors up to kw Adjustable braking current up to 0 A Adjustable braking time Automatic standstill monitoring (optional)
More informationUnit 32 Three-Phase Alternators
Unit 32 Three-Phase Alternators Objectives: Discuss the operation of a three-phase alternator. Explain the effect of rotation speed on frequency. Explain the effect of field excitation on output voltage.
More informationCHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM
61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this
More informationT-Line Generator Control, Protection and Monitoring
T-Line Generator Control, Protection and Monitoring» Control. Monitor. Protect. SELCO T-Line The SELCO T-line offers a complete range of system components for generator control, protection and power monitoring.
More informationTechnical information No. 01. IT systems. The basis for reliable power supply
IT systems The basis for reliable power supply FA01en/01.2004 IT systems The basis for reliable power supply in critical areas The advantages of sophisticated industrial systems can only be of use, if
More informationSTUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM
STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM Ms. Dipali A. Umak 1, Ms. Trupti S. Thakare 2, Prof. R. K. Kirpane 3 1 Student (BE), Dept. of EE, DES s COET, Maharashtra,
More informationFull-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA
Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA Philippe Maibach, Alexander Faulstich, Markus Eichler, Stephen Dewar ABB Switzerland Ltd CH-5300 Turgi, Switzerland Phone: +41
More informationCHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM
106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,
More informationComparison of different 600 kw designs of a new permanent magnet generator for wind power applications
Comparison of different 600 kw designs of a new permanent magnet generator for wind power applications E. Peeters, Vito, Boeretang 200, 2400 Mol, Belgium, eefje.peeters@vito.be, tel +32 14 33 59 23, fax
More informationELECTRIC MACHINES EUROLAB 0.3 kw
index SINGLE-PHASE MOTORS SPLIT-PHASE MOTOR DL 30130 CAPACITOR MOTOR DL 30140 UNIVERSAL MOTOR DL 30150 REPULSION MOTOR DL 30170 THREE PHASE ASYNCHRONOUS MOTORS SQUIRREL CAGE THREE PHASE ASYNCHRONOUS MOTOR
More informationModel ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase
Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible
More informationStatic frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids
Static frequency converter couples US paper mill s 2-Hz and 0-Hz electricity grids Before 0 Hz was adopted as the standard frequency for electricity distribution in the USA, power companies across the
More informationHardware Design of Brushless DC Motor System Based on DSP28335
Hardware Design of Brushless DC Motor System Based on DSP28335 Abstract Huibin Fu a, Wenbei Liu b and Xiangmei Du c School of Shandong University of Science and Technology, Shandong 266000, China. a imasmallfish@163.com,
More informationTechnical Explanation for Inverters
CSM_Inverter_TG_E_1_2 Introduction What Is an Inverter? An inverter controls the frequency of power supplied to an AC motor to control the rotation speed of the motor. Without an inverter, the AC motor
More informationExcitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR.
Turbo - Generator Type: QF Series 1. General The generator is a two pole, cylindrical rotor type synchronous machine, directly coupled with steam turbine. It has a closed-circuit cooling system to cool
More informationFortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state
More informationBHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2
BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR 1.00.00 GENERAL 1.01.00 Make : Jinan Power Equipment Factory 1.02.00 Type : WX21Z-073LLT 1.03.00 Reference Standard : GB/T7064-2002
More informationTECHNICAL DESCRIPTION
DC Circuit Breaker TECHNICAL DESCRIPTION TRK5650523200 Ed.1 of 23/07/13 CONTENTS 1. INTRODUCTION... 2 2. DESCRIPTION... 2 2.1 Description of circuit breaker... 2 2.2 Operating mode... 2 2.3 Variants and
More informationStudies regarding the modeling of a wind turbine with energy storage
Studies regarding the modeling of a wind turbine with energy storage GIRDU CONSTANTIN CRISTINEL School Inspectorate of County Gorj, Tg.Jiu, Meteor Street, nr. ROMANIA girdu23@yahoo.com Abstract: This paper
More informationProtection of Power Electronic Multi Converter Systems in AC and DC Applications
Protection of Power Electronic Multi Converter Systems in AC and DC Applications Prof. Norbert Grass Technische Hochschule Nürnberg, Institute for Power Electronic Systems, Nuremberg, Germany, Norbert.Grass@th-nuernberg.de
More informationTECHNICAL DATA SHEET KVA UPS Systemss
Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800
More informationAdvance Electronic Load Controller for Micro Hydro Power Plant
Journal of Energy and Power Engineering 8 (2014) 1802-1810 D DAVID PUBLISHING Advance Electronic Load Controller for Micro Hydro Power Plant Dipesh Shrestha, Ankit Babu Rajbanshi, Kushal Shrestha and Indraman
More informationPower Lynx 3 Uninterruptible Power System (UPS) Technical Specifications
Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible
More informationShort Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand L33-2
Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand ( July 14-18, 2007) Lecture on L33-2 By S.N.Singh Senior Scientific officer ALTERNATE HYDRO
More informationHVDC. TMT&D provides the best and most economical HVDC system.
HVDC TMT&D HVDC TMT&D provides the best and most economical HVDC system. In 1955, TMT&D started the development of HVDC and is the leading HVDC supplier in Japan. TMT&D has continued to develop HVDC technology
More informationBasics of Paralleling
Basics of Paralleling Revised: February 1, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Discuss basic paralleling control functions to gain a better understanding
More informationQUESTION BANK SPECIAL ELECTRICAL MACHINES
SEVENTH SEMESTER EEE QUESTION BANK SPECIAL ELECTRICAL MACHINES TWO MARK QUESTIONS 1. What is a synchronous reluctance 2. What are the types of rotor in synchronous reluctance 3. Mention some applications
More informationComparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. II (May June 2017), PP 124-129 www.iosrjournals.org Comparative Analysis
More informationAdvanced Active And Reactive Power Control For Mini Grids
RIO 9 - World Climate & Energy Event, 17-19 March 2009, Rio de Janeiro, Brazil Advanced Active And Reactive Power Control For Mini Grids Stratis Tapanlis and Michael Wollny SMA Solar Technology AG Sonnenallee
More informationAmerican Traction Systems
2000HP Locomotive Diesel Electric Propulsion System April 2010 10030 Amberwood Road Fort Myers, Florida 33913 Voice: +1 (239) 768 0757 http://www.americantraction.com Description of System Main components
More informationType DTH 31, 32 DTTM 11, 12 High Speed Biased Differential Relays
Type DTH 31, 32 DTTM 11, 12 High Speed Biased Differential Relays Type DTH 31, 32 DTTM 11, 12 High Speed Biased Differential Relays DTH relay withdrawn from case Features l High speed. l Low burden. l
More informationElectronic Ballast EVG 2000-T
Electronic Ballast EVG 2000-T Operating Manual Table of contents 1 Description 1.1 Advantages of this ballast... 3 1.2 Functional principle... 3 1.3 Energization... 4 1.4 Visualization... 5 1.5 Indications
More informationPower System Solutions (PSS)
About Power System Solutions mission The Power System Solutions Mission Statement To achieve customer satisfaction by providing innovative solutions to improve upon power quality, energy efficiency, and
More informationAsynchronous slip-ring motor synchronized with permanent magnets
ARCHIVES OF ELECTRICAL ENGINEERING VOL. 66(1), pp. 199-206 (2017) DOI 10.1515/aee-2017-0015 Asynchronous slip-ring motor synchronized with permanent magnets TADEUSZ GLINKA, JAKUB BERNATT Institute of Electrical
More informationPower Electronics. POWERSWITCH Semiconductor Relay / - Contactor With Load Circuit Monitoring PH 9270
Power Electronics POWERSWITCH Semiconductor Relay / - Contactor With Load Circuit Monitoring PH 9270 0255163 Semiconductor relay PH 9270.91 Semiconductor contactor PH 9270.91/000/02 AC semiconductor relay
More informationPerformance Analysis of Transient Stability on a Power System Network
Performance Analysis of Transient Stability on a Power System Network Ramesh B Epili 1, Dr.K.Vadirajacharya 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere
More informationThe 1,400-MW Kii-Channel HVDC System
The 1,4-MW Kii-Channel HVDC System The 1,4-MW Kii-Channel HVDC System 114 Hiroyuki Nakao Masahiro Hirose Takehisa Sakai Naoki Kawamura Hiroaki Miyata Makoto Kadowaki Takahiro Oomori Akihiko Watanabe OVERVIEW:
More informationA Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor
A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor 1 Chaudhari Krunal R, 2 Prof. Rajesh Prasad 1 PG Student, 2 Assistant Professor, Electrical Engineering
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SitePro 150 200 250 300 kva 400 VAC CE Series 6 Manufactured by: GE Digital Energy General Electric
More informationConstruction of a Hybrid Electrical Racing Kart as a Student Project
Construction of a Hybrid Electrical Racing Kart as a Student Project Tobias Knoke, Tobias Schneider, Joachim Böcker Paderborn University Institute of Power Electronics and Electrical Drives 33095 Paderborn,
More information