SYSCO RDC SOUTH ALACHUA, FLORIDA

Size: px
Start display at page:

Download "SYSCO RDC SOUTH ALACHUA, FLORIDA"

Transcription

1 SYSCO RDC SOUTH ALACHUA, FLORIDA July, 2018 Infrared Inspection Report Sysco RDC South NW 173rd Street Alachua, Florida, Company Contact: Natha Hall Project: CHARTER OAK DRIVE, LITTLE ROCK, AR PHONE: & FA:

2 ORDER OF REPORT CONTENTS 1: Data To Facilitate Understanding & Utilizing Scan Report 2: Scan Results Overview & Action Taken Form 3: Identified Faulting Conditions, Information & Photographs 4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found DISCLAIMER This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not intended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility s condition, maintenance practices or correction of conditions indicated herein. By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, concerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.

3 Utilizing Report Contents Included in this report are Photographs and Thermographs of problem areas found during our recent Infrared Inspection of your facility. Each problem area picture is accompanied by: Date Location Information Temperature Calculations Color-coded Temperature Intensity and/or Condition Significance Data A Brief Comment Relating The Item In The Photograph To Its Corresponding Thermograph Suggested Corrective Recommendations. In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity. Thermal intensity is indicated by use of a color-coded data inserts that locate a fault s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows: INSERT Red Orange Yellow Green Temperature Range 70ºC/126ºF and higher above Ambient Operating Temp. 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp. 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp. *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp. ( * See page 4)

4 Determining Cost Effective Responses Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate. Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports. STANDARD ELECTRICAL FAULT FAILURE CURVE (Does Not Include Area In Blue) MINOR INTERMEDIATE SERIOUS CRITICAL DEVICE TEMP IS AMBIENT, BUT DEVICE IS EITHER FAULTY OR UNSAFE. 10ºC * 18ºF 25ºC 45ºF 40 C 72ºF 70 C 126ºF AMBIENT TEMP YEARS MONTHS MONTHS TO WEEKS WEEKS TO NOW FAULTY EQUIP Built In Trend Monitoring When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings. If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.

5 Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use Total Temperature: Total Temperature = Ambient Operating Temperature + Fault temperature Allows you, the customer, to evaluate possible damage to equipment. Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating. Contacts start to fail around 130ºC/266ºF Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes: Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet. If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault. Allows you, the customer, to determine if device will operate at intended amperage. Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine) If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip. 1. An intermittent high load. 2. A minor (Green) or intermediate (Yellow) fault. Report pages with photographs: PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph *AOT stands for Ambient Operating Temperature Both black & white and color infrared thermographs are presented to better depict the fault condition.

6 In addition to the corrective response time frame suggested below and the failure curve located on the previous page, you may want to consider using the military standard responses presented below. Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment: Temperatures rise above Ambient Operating Temperature: *10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label) 25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label) 40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected. (Orange Label) 70ºC/126ºF and above component failure imminent. Immediately inform the person responsible for continued operation of equipment. (Red Label) Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions. * Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind. Fault Correction Recommendation When Our Source Assessment Is Inaccurate: When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist. The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located. Example: If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp. in the lead holder lug.

7 SCAN RESULTS OVERVIEW PROMPT ATTENTION ITEMS: Because of: 1. The intensity or heat level indicated at the time of the scan. 2. Deterioration caused by excessive temperature not present at the time of the scan. 3. Physical condition irregularities observed at the time of the scan. We recommend that the following faults be given prompt attention: Faults: #2 Items With Asterisks Have High Total or Ambient Operating Temperatures. United Spectrographics July, 2018

8 SUMMARY OF FINDINGS FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO. MINOR 0 0 INTERMEDIATE 1 1/203 SERIOUS 1 2/224 CRITICAL 0 0 SERIOUS 0 0 Number of items located at facility: 234 Number of faults: 2

9 ACTION TAKEN Sysco RDC South Alachua, Florida July, 2018 Fault # Item # Category Repaired Monitor Date Name Intermediate Serious

10 PROJECT: CUST REP: SCAN REP: Mark Trey Dent DATE: July 11th, 2018 LOCATION: Roof Office Area Box Labeled: RTU-A2-S Fuse Disconnect PH # 1 > ITEM: SOURCE: TEMP: Bø Fuse Block Load side fuse clip Temp. of fuse clip is: 73ºC / 163ºF Total Temp - 37ºC / 99ºF AOT = 36ºC / 64ºF above AOT. TH # 1 > COMMENTS Abnormal heat is being generated in fuse block component. See yellow arrows in PH#1 and TH#1. Loose and/or corroded contact area. Clean, inspect and re-secure. TH # 1 > TEMPERATURE ABOVE AOT 36 C / 64 F

11 PROJECT: CUST REP: SCAN REP: Mark Trey Dent DATE: July 11th, 2018 LOCATION: Roof-Warehouse Area Penthouse #5 Box Labeled: AHU-18 Combination Starter < PH # 2 ITEM: SOURCE: TEMP: Cø of Disconnect Load side lead connection lug Temp. of connection and lug is: 31ºC / 88ºF Total Temp. -(12ºC) / 10ºF AOT = 43ºC / 78ºF above AOT. < TH # 2 < TH # 2 COMMENTS Abnormal heat is being generated in disconnect connection. See orange arrows in PH#2 and TH#2. Loose and/or corroded contact area. Clean, inspect and re-secure serviceable components. TEMPERATURE ABOVE AOT 43 C / 78 F

12 AREA/EQUIPMENT LIST Following is a list of the electrical equipment located at the Sysco RDC South, Alachua, Florida, facility and data relating to its operating condition at the time the scan was performed. NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection. No. Equipment Operating Visually Inspected MAIN BUILDING Fault # MAIN ELECTRICAL ROOM 1 Switchboard MDP2 Section 1 Terminals 2 Switchboard MDP2 Section 2 480/277 Volt Distribution Panel 3 Switchboard MDP1 Section 1 Terminals 4 Switchboard MDP1 Section 2 480/277 Volt Distribution Panel 5 Switchboard MSBE-1 / MSBE-2 Section 1 Terminals 6 Switchboard MSBE-1 / MSBE-2 Section 2 480/277 Volt Distribution Panel 7 Switchboard MSBE-1 / MSBE-2 Section 3 NATS-2 Circuit Breaker 8 Switchboard MSBE-1 / MSBE-2 Section 4 ATS-2 Circuit Breaker 9 Switchboard MSBE-1 / MSBE-2 Section 5 Terminals 10 Switchboard MSBE-1 / MSBE-2 Section 6 Tie Breaker 11 Switchboard MSBE-1 / MSBE-2 Section 7 Terminals 12 Switchboard MSBE-1 / MSBE-2 Section 8 ATS-1 Circuit Breaker 13 Switchboard MSBE-1 / MSBE-2 Section 9 NATS-1 Circuit Breaker 14 Switchboard MSBE-1 / MSBE-2 Section /277 Volt Distribution Panel 15 Switchboard MSBE-1 / MSBE-2 Section 11 Terminals 16 ATS-1 17 ATS-2

13 No. Equipment Operating Visually Inspected 18 NATS-1 Fault # 19 NATS-2 20 ATS-3 21 ATS-4 22 Switchboard MSB-1 Section 1 Main Breaker 23 Switchboard MSB-1 Section 2 480/277 Volt Distribution Panel 24 Switchboard MSB-1 Section 3 ATS-1 25 Switchboard MSB-1 Section 4 NATS-1 26 Switchboard MSB-2 Section 1 Main Breaker 27 Switchboard MSB-2 Section 2 480/277 Volt Distribution Panel 28 Switchboard MSB-2 Section 3 ATS-2 29 Switchboard MSB-2 Section 4 NATS-2 VFD ROOM 30 Power Distribution Panel #2 31 VFD 01 AU VFD 02 AU VFD 03 AU VFD 04 AU VFD 05 AU VFD 06 AU22-23 Cond EC1 Fan VFD 07 Cond EC1 Fan Refrigeration Section 1 Control Panel 39 Refrigeration Section 2 I/O Panel 40 Refrigeration Section 3 Distribution Panel 41 Refrigeration Section 4 Starter Panel COMPRESSOR ELECTRICAL ROOM 42 PPB-1 480/277 Volt Distribution Panel 43 PPB-2 480/277 Volt Distribution Panel

14 No. Equipment Operating Visually Inspected 44 LP1E 480/277 Volt Distribution Panel 45 LPA 480/277 Volt Distribution Panel 46 RP /120 Volt Distribution Panel 47 RP /120 Volt Distribution Panel 48 FMR TR1 45 KVA Siemens 3ø Transformer 49 LP /277 Volt Distribution Panel 50 LP /277 Volt Distribution Panel 51 Switchboard MDP3 Section 1 Terminals 52 Switchboard MDP3 Section 2 480/277 Volt Distribution Panel 53 Switchboard MDP4 Section 1 Terminals 54 Switchboard MDP4 Section 2 480/277 Volt Distribution Panel AMMONIA COMPRESSOR ROOM 55 C-1 Compressor Control Cabinet 56 C-2 Compressor Control Cabinet 57 C-3 Compressor Control Cabinet 58 C-4 Compressor Control Cabinet 59 C-5 Compressor Control Cabinet 60 C-6 Compressor Control Cabinet 61 RP-1 Disconnect 62 RP-2 Disconnect 63 RP-3 Disconnect 64 RP-4 Disconnect AMMONIA COMPRESSOR MEZZANINE 65 SF-RF12 Combination Starter 66 SF-RF11 Combination Starter 67 EF-REF13 Combination Starter 68 EF-REF12 Combination Starter 69 EF-REF11 Combination Starter 70 SF-RF13 Combination Starter Fault #

15 No. Equipment Operating Visually Inspected MAINTENANCE SHOP AREA Fault # 71 (Left) Main Battery Charger Switch 72 (Right) Main Battery Charger Switch 73 EF-BC1 Combination Starter 74 EF-BM1 Combination Starter 75 SF-BM1 Combination Starter 76 SF-BC1 Combination Starter MAINTENANCE SHOP MEZZANINE 77 LPBE 480/277 Volt Distribution Panel 78 UPS-2 208/120 Volt Distribution Panel 79 Heat Trace Control Panel HTCP-1 80 RP3 208/120 Volt Distribution Panel 81 FMR TR3 45 KVA Siemens 3ø Transformer 82 LP3 480/277 Volt Distribution Panel 83 LPB-3 480/277 Volt Distribution Panel 84 LPB-1 480/277 Volt Distribution Panel 85 LPB-2 480/277 Volt Distribution Panel 86 RP /120 Volt Distribution Panel 87 RP /120 Volt Distribution Panel 88 FMR TR2 45 KVA Siemens 3ø Transformer 89 LP /277 Volt Distribution Panel 90 LP /277 Volt Distribution Panel 91 LP /277 Volt Distribution Panel AIR COMPRESSOR ROOM 92 Air Compressor #A Control Cabinet 93 Air Compressor #A Disconnect 94 Air Compressor #B Control Cabinet 95 Air Compressor #B Disconnect 96 Air Dryer Disconnect

16 No. Equipment Operating Visually Inspected 97 EF-DW5 Combination Starter 98 SF-DW2 Combination Starter 99 EF-DW6 Combination Starter 100 SF-DW1 Combination Starter 101 EF-DW4 Combination Starter 102 SF-DW3 Combination Starter 103 EF-DW3 Combination Starter 104 SF-DW4 Combination Starter 105 EF-DW2 Combination Starter 106 SF-DW5 Combination Starter 107 EF-DW1 Combination Starter 108 SF-DW6 Combination Starter Not In Service 109 SF-DW6 Drive Cabinet Not In Service 110 EF-ACP1 Combination Starter RAIL DOCK 111 EF-RC1 Combination Starter 112 SF-RD22 Combination Starter 113 SF-RD12 Combination Starter 114 SF-RD32 Combination Starter 115 SF-RC1 Combination Starter 116 SF-RD31 Combination Starter 117 EF-RD3 Combination Starter 118 SF-RD21 Combination Starter 119 EF-RD2 Combination Starter 120 SF-RD11 Combination Starter 121 EF-RD1 Combination Starter 122 LP /277 Volt Distribution Panel 123 LP /277 Volt Distribution Panel 124 LP /277 Volt Distribution Panel Fault #

17 No. Equipment Operating Visually Inspected RAIL DOCK MEZZANINE Fault # 125 LP7 480/277 Volt Distribution Panel 126 RP7 208/120 Volt Distribution Panel 127 FMR TR7 30 KVA Siemens 3ø Transformer 128 Heat Trace Control Panel HCTP LP8 480/277 Volt Distribution Panel 130 FMR TR8 30 KVA Siemens 3ø Transformer 131 RP8 208/120 Volt Distribution Panel 132 LP8E 480/277 Volt Distribution Panel OFFICE AREA ROOM 205 ELEVATOR MECHANICAL ROOM 133 Elevator Control Cabinet 134 Elevator Disconnect 135 Elevator Cab Lights Disconnect ROOM 227 ELECTRICAL ROOM 136 LPC 480/277 Volt Distribution Panel 137 LPCE 480/277 Volt Distribution Panel 138 FMR TR6 150 KVA Siemens 3ø Transformer 139 RP /120 Volt Distribution Panel 140 RP /120 Volt Distribution Panel 141 LP /277 Volt Distribution Panel 142 LP /277 Volt Distribution Panel 143 Main Switch KVA Siemens 3ø Transformer 145 RP /120 Volt Distribution Panel 146 RP /120 Volt Distribution Panel

18 No. Equipment Operating Visually Inspected ROOM 509 KITCHEN 147 KP1 208/120 Volt Distribution Panel Fault # ROOM 521 ELECTRICAL ROOM 148 RP /120 Volt Distribution Panel 149 RP /120 Volt Distribution Panel 150 Main Switch 151 PP /277 Volt Distribution Panel 152 PP /277 Volt Distribution Panel 153 RP /120 Volt Distribution Panel 154 RP /120 Volt Distribution Panel 155 FMR TR KVA Siemens 3ø Transformer ROOM 523 COMPUTER ROOM 156 UPS Control Cabinet TRUCK SHOP OUTSIDE 157 ATS Switchboard MDP5 480/277 Volt Distribution Panel 159 Switchboard MDP5E 480/277 Volt Distribution Panel KVA Siemens 3ø Transformer GARAGE FLOOR 161 FMR TM1 75 KVA Siemens 3ø Transformer 162 FMR TM4 30 KVA Siemens 3ø Transformer 163 FMR TM5 45 KVA Siemens 3ø Transformer 164 EF-2 Combination Starter 165 EF-13 Combination Starter 166 EF-14 Combination Starter 167 EF-19 Combination Starter ELECTRICAL ROOM

19 No. Equipment Operating Visually Inspected 168 MS1-N 208/120 Volt Distribution Panel Fault # 169 MS2 208/120 Volt Distribution Panel 170 MS /120 Volt Distribution Panel 171 MS /120 Volt Distribution Panel 172 LPG /277 Volt Distribution Panel 173 LPG /277 Volt Distribution Panel 174 LPG1E-1 480/277 Volt Distribution Panel 175 LPG1E-2 480/277 Volt Distribution Panel 176 LPG2 480/277 Volt Distribution Panel 177 ATS-2 TRUCK WASH BAY 178 EF-20 Combination Starter 179 EF-25 Combination Starter TRUCK WASH ELECTRICAL ROOM 180 Unlabeled 480/277 Volt Distribution Panel 181 Main Switch 182 EF-7 Combination Starter OIL ROOM 183 EF-1 Combination Starter 184 Air Compressor Control Cabinet 185 Air Compressor Disconnect 186 Air Dryer Disconnect GUARD SHACK 187 LPG3 208/120 Volt Distribution Panel 188 FMR TM KVA Siemens 1ø Transformer 189 GS1 208/120 Volt Distribution Panel PUMP HOUSE DIESEL ROOM

20 No. Equipment Operating Visually Inspected 190 Fire Pump Controller Control Cabinet Fault # 191 Jockey Pump Control Cabinet ELECTRICAL ROOM 192 Fire Pump Controller Control Cabinet 193 Fire Pump Controller Disconnect 194 Jockey Pump Control Cabinet 195 Jockey Pump Disconnect 196 PS1 208/120 Volt Distribution Panel 197 Transformer Disconnect 198 Pad Mounted Transformer (Fins Only) (Outside) ROOF-OFFICE AREA 199 RTU-A2-N Fuse Disconnect 200 RTU-A12 Fuse Disconnect 201 RTU-A11 Fuse Disconnect 202 RTU-A13 Fuse Disconnect 203 RTU-A2-S Fuse Disconnect 1 REFRIGERATION PENTHOUSE 204 AHU-14 Combination Starter 205 AHU-12 Combination Starter 206 AHU-10 Combination Starter 207 AHU-9 Combination Starter 208 AHU-11 Combination Starter 209 AHU-13 Combination Starter 210 AHU-15 Combination Starter 211 AHU-16 Combination Starter ROOF-WAREHOUSE COOLING TOWER AREA 212 EC 1 Fan 1 Disconnect

21 No. Equipment Operating Visually Inspected 213 EC 1 Fan 2 Disconnect Fault # 214 EC 1 Fan 3 Disconnect 215 EC 1 Pump 1 Disconnect 216 EC 2 Pump 2 Disconnect 217 EC 2 Fan 1 Disconnect 218 EC 2 Fan 2 Disconnect 219 EC 2 Fan 3 Disconnect PENTHOUSE #3 220 AHU #8 Combination Starter 221 AHU #7 Combination Starter 222 AHU #6 Combination Starter PENTHOUSE #5 223 AHU #17 Combination Starter 224 AHU #18 Combination Starter AHU #19 Combination Starter 226 AHU #20 Combination Starter 227 AHU #21 Combination Starter PENTHOUSE #4 228 AHU #22 Disconnect 229 AHU #23 Disconnect PENTHOUSE #2 230 AHU #4 Combination Starter 231 AHU #5 Combination Starter PENTHOUSE #1 232 AHU #3 Combination Starter 233 AHU #2 Combination Starter 234 AHU #1 Combination Starter

SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA

SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA November, 2017 Infrared Inspection Report Sysco Indianapolis LLC. 4000 West 62nd Street Indianapolis, Indiana, 46268 Company Contact: Trevor Gray Project: 05161117

More information

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA August, 2018 Infrared Inspection Report SYSCO Oklahoma LLC 1350 West Tecumseh Road Norman, Oklahoma, 73069 Company Contact Chris Hill Project: 03210818 2605 CHARTER

More information

SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA

SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA July, 2018 Infrared Inspection Report Sysco Central California 136 South Mariposa Road Modesto, California, 95393 Company Contact: Steve Handel Project: 04110718

More information

BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE

BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE July, 2015 Infrared Inspection Report Buzzi Unicem Terminal Company Contact Randy Miguez Project: 06220715 2605 CHARTER OAK DRIVE, LITTLE

More information

SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS

SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS July, 2015 Infrared Inspection Report Sidewinder Drilling Company Contact Tommy Green Project: 02170715 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE:

More information

SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS

SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS November, 2017 Infrared Inspection Report Sidewinder Drilling Rig 127 Pecan Acres 23 PSA 3-3H(WB) Company Contact Colton Chesney Project: 02201117 2605 CHARTER

More information

Fault Summary The following table is a summary of faults or items featured for your information

Fault Summary The following table is a summary of faults or items featured for your information This document is an annotated sample of a report you receive. following our visit to your premises... We pride ourselves on the quality of the report and submit. this sample for your evaluation.. Report

More information

Company Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI

Company Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI Company Name City, State Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI 54476-0740 April 9, 2012 (Customer Name & Address) Attn: Customer Enclosed is a report on the

More information

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9 8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection

More information

Thermal Imaging Infrared Survey. Report. Report. Thermography Inspection at ABC Company.

Thermal Imaging Infrared Survey. Report.  Report. Thermography Inspection at ABC Company. Thermal Imaging Infrared Survey Report. Thermal Imaging Infrared Survey Report. Thermography Inspection at ABC Company. Vancouver,BC May 25,2012 www.aiturgroup.com info@aiturgroup.com Rick Turdubay, Certified

More information

Electrical Existing Conditions and Building Load Summary Report

Electrical Existing Conditions and Building Load Summary Report Electrical Existing Conditions and Building Load Summary Report Executive Summary: This Electrical Existing Conditions and Building Load Summary Report will describe the general and specific characteristics

More information

THERMOGRAPHY REPORT ELECTRICAL

THERMOGRAPHY REPORT ELECTRICAL LAMBERT CONDITION MONITORING LTD. CERTIFIED THERMOGRAPHER A.I.R. #12-01-243 THERMOGRAPHY REPORT ELECTRICAL Thermographic inspection at: Sample site Inspected by: David Lambert date: 20170701 Customer Sample

More information

Thermographic Inspection at SMALLVILLE DPW 123 ANY WAY SMALLVILLE, CA PETER PLEIN

Thermographic Inspection at SMALLVILLE DPW 123 ANY WAY SMALLVILLE, CA PETER PLEIN 191 BOULEVARD GLEN ROCK, NJ 07452 201-444 444-3620 Thermographic Inspection 123 ANY WAY SMALLVILLE, CA 01234 2006-04-25 By PETER PLEIN SAMPLE 1 (10) April 25, 2006 De: This is the in initial inspection

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

Electrical Depth. Josh Kreutzberger Lighting/Electrical

Electrical Depth. Josh Kreutzberger Lighting/Electrical Electrical Depth Electrical Introduction The current power distribution system provides the building with power; however, an alternative design solution was analyzed. This analysis was done in order to

More information

Avid Electrical Services

Avid Electrical Services Avid Electrical Services Thermal Imaging Report To: Mr A. Customer Your Business Australia Pty Ltd Fault Summary The following table is a summary of faults or items featured for your information Grading

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Substation inspection guidelines Mark B. Goff, P.E.

Substation inspection guidelines Mark B. Goff, P.E. Substation inspection guidelines Mark B. Goff, P.E. Tennessee Valley Authority, Chattanooga, Tennessee ABSTRACT We need to better understand what our infrared camera is really showing us. Without guidelines,

More information

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection: Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: 27-10-2006 Reference Number: 2710061 Thermographer: John Crawford Thermal Imaging

More information

B BASIC HEAT TREATMENT CONSOLE

B BASIC HEAT TREATMENT CONSOLE Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL

More information

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE Duty B: Power Distribution (600V and below) B-03: Troubleshoot 480V System Issued 06/01/98 Task Preview Troubleshoot 480V System The 480V distribution

More information

Reliable Temperature Compensation is Critical to CNG Vehicle Safety

Reliable Temperature Compensation is Critical to CNG Vehicle Safety Reliable Temperature Compensation is Critical to CNG Vehicle Safety August 18, 2014 This Technical Bulletin addresses the potential hazards created by failure of compressed natural gas (CNG) dispensers

More information

SOLAR DASH CHARGING SYSTEM USER GUIDE

SOLAR DASH CHARGING SYSTEM USER GUIDE SOLAR DASH CHARGING SYSTEM Doc 1.01 INST049 INSTALLATION STEP 1 Place 20 watt solar panel in the dash of the vehicle facing up. Note: For ideal results position the vehicle in a manner in which the solar

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

AGM. I-Lux MR 16 Style 2 & 5, Coil & Shunt. 108 Fairgrounds Drive Suite 8 Manlius, NY Phone: Fax:

AGM. I-Lux MR 16 Style 2 & 5, Coil & Shunt. 108 Fairgrounds Drive Suite 8 Manlius, NY Phone: Fax: AGM I-Lux MR 16 Style 2 & 5, Coil & Shunt Revision 7.5 Pg 2 I-Lux Catalog / Item Numbers Catalog Code XXX.XXF Sign Size 1 ~ Size 1 2 ~ Size 2 3 ~ Size 3 5 ~ Size 5 Sign Style 2 ~ Style 2 (3 step 4.8A -

More information

INFRARED INSPECTION REPORT

INFRARED INSPECTION REPORT REPORT February 13, 2015 Companies Unlimited 1401 Brand St. Los Angeles, CA 90028 Contact: Ron McKinney An Introduction to Infrared Inspection When installed correctly and operated within their ratings,

More information

ATLAS Wheel Balancer Electrical Flow Chart

ATLAS Wheel Balancer Electrical Flow Chart ATLAS Wheel Balancer Electrical Flow Chart WARNING: Leave all work to trained and licensed electricians. Attempting repairs yourself is extremely dangerous, with the potential for serious injury and even

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Integrated Inverter/Battery Monitoring System (IBMS)

Integrated Inverter/Battery Monitoring System (IBMS) Integrated Inverter/Battery Monitoring System (IBMS) Battery monitoring at its finest Maintenance Bypass Switch Input AC to DC Converter DC to AC Inverter Static Bypass Switch Output Operations: Normal

More information

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies Engineering Studies Coordination Study Every 5 years and in conjunction with electrical system modifications. Short Circuit Study NETA MTS 6.2 Every 5 years and in conjunction with electrical system modifications.

More information

LG Alert TM Helping Drivers Operate Safely. LG Alert Lateral Acceleration Indicator User / Installation Manual

LG Alert TM Helping Drivers Operate Safely. LG Alert Lateral Acceleration Indicator User / Installation Manual INTRODUCTION US Pat. No. 6,130,608 The is intended for use as an early alert system to assist drivers in recognizing when they are exceeding set maximum maneuvering limits of the vehicle. The device monitors

More information

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein. 16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional

More information

Thermal-cutoff, Fuse and Fuseholder Incorporated into a Simple Compact Device

Thermal-cutoff, Fuse and Fuseholder Incorporated into a Simple Compact Device Thermal-cutoff, Fuse and Fuseholder Incorporated into a Simple Compact Device It is generally known to employ a fuse for overcurrent protection and a thermal fuse or a thermostat for overheat protection

More information

SELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02

SELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02 SELECT DIAGNOSTIC GUIDE INST028 Doc 3.02 CONTENTS General Information...2 Select Call-Outs...3 Wire Diagram and Legend...4 Diagnostics...6 Excessive Voltage Drop Diagnostics...6 Static Diagnostics...7

More information

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER KEW6201A CONTENTS 1. Safe testing 1 2. Procedure of removing cover. 3 2.1 Method of removing the cover. 3 2.2 Method of storing the cover. 3 3. Product summary

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication serves as a guide that represents the consensus of NEMA member companies and is not intended to override the recommendations

More information

Arc flash hazard mitigation

Arc flash hazard mitigation Low Voltage Products Arc flash hazard mitigation Each year more than 2,000 people are treated in burn centers with severe arc flash injuries. ABB designs and manufactures products and solutions to provide

More information

Motors Automation Energy Transmission & Distribution Coatings. UMBW UL489 and UL1077 Thermal-Magnetic MCB

Motors Automation Energy Transmission & Distribution Coatings. UMBW UL489 and UL1077 Thermal-Magnetic MCB Motors Automation Energy Transmission & Distribution Coatings UMBW UL489 and UL1077 Thermal-Magnetic MCB UL489 AND UL1077 Circuit Protection Overview: Single pole and multi-pole thermal-magnetic minature

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

LG Alert TM Helping Drivers Operate Safely. LG Alert Oshkosh Truck Corporation User / Installation Manual

LG Alert TM Helping Drivers Operate Safely. LG Alert Oshkosh Truck Corporation User / Installation Manual INTRODUCTION US Pat. No. 6,130,608 The LG Alert Lateral Acceleration Indicator is intended for use as an early alert system to assist drivers in recognizing when they are exceeding set maximum maneuvering

More information

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers 2 Introduction This discussion describes in detail retrofitting medium voltage circuit

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

Grounding Of Standby & Emergency Power Systems

Grounding Of Standby & Emergency Power Systems July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due

More information

EasyStart 364 (ASY-364-X20-IP) Installation Instructions for the Coleman / Airxcel Air Conditioners

EasyStart 364 (ASY-364-X20-IP) Installation Instructions for the Coleman / Airxcel Air Conditioners EasyStart 364 (ASY-364-X20-IP) Installation Instructions for the Coleman / Airxcel Air Conditioners using Installation Kit KIT-364-CM1 Contents Introduction... 2 Safety first... 2 Making a good crimp...

More information

Application Engineering Europe

Application Engineering Europe Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for

More information

PARTS CATALOG MODEL FBD352 DISPENSER

PARTS CATALOG MODEL FBD352 DISPENSER FBD Partnership, LP P.O. BOX 897 SAN ANTONIO, TX 788 USA 0-67-800 FAX 0-67-8 www.fbdfrozen.com FBD TECHNICAL SUPPORT -866--777 TECHNICAL SUPPORT FAX -0-67-8 PARTS CATALOG ------------------------------

More information

EasyStart Installation Instructions for Dometic Family RV A/Cs

EasyStart Installation Instructions for Dometic Family RV A/Cs EasyStart Installation Instructions for Dometic Family RV A/Cs DuoTherm Brisk Brisk II Penguin Penguin II Contents Introduction... 4 Safety first... 4 Making a good crimp... 4 Identifying Dometic AC Units...

More information

CONTRACT DOCUMENTS FOR WAYNE STATE UNIVERSITY

CONTRACT DOCUMENTS FOR WAYNE STATE UNIVERSITY CONTRACT DOCUMENTS FOR 2700 W. Argyle Street WSU ELECTRICAL RELIAILITY UPGRADES - ID PACKAGE No. 6 OWNER Facilities Planning & Management Design & Construction Services 5454 Cass Avenue Detroit Mi 48202

More information

Motor Protection. Voltage Unbalance & Single-Phasing

Motor Protection. Voltage Unbalance & Single-Phasing For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants

More information

PMC-MC-X2-Chassis PMC-MC-X4-Chassis

PMC-MC-X2-Chassis PMC-MC-X4-Chassis DYNAMIC ENGINEERING 150 DuBois St Suite 3, Santa Cruz Ca 95060 831-457-8891 Fax 831-457-4793 http://www.dyneng.com sales@dyneng.com Est. 1988 User Manual Four Slot Carrier Two Slot Carrier PMC-MC-X2-Chassis

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO technical sales guide - 60Hz Taurus R Ducted Split Units UPTO HIGH AMBIENT OPERATION 52 O C Page CONTENTS Nomenclature.. 2 Description. 3 Features.. 3 Product Data. 4 Condensing Unit Cooling Performance

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Pump Installation and Service Manual HRS Hydromatic Retractable System

Pump Installation and Service Manual HRS Hydromatic Retractable System Pump Installation and Service Manual HRS Hydromatic Retractable System NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party

More information

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission

More information

A2P Single Phase Automatic Industrial Battery Charger

A2P Single Phase Automatic Industrial Battery Charger A2P Single Phase Automatic Industrial Battery Charger Featuring 205B Konrad Cres., Markham, ON, L3R 8T9 www.chargers.ca Building Canada s toughest battery chargers for over a century. Congratulations on

More information

SSZ14 PRODUCT SPECIFICATIONS 14 SEER HIGH-EFFICIENCY, R-410A SPLIT SYSTEM HEAT PUMP 1½ TO 5 TON

SSZ14 PRODUCT SPECIFICATIONS 14 SEER HIGH-EFFICIENCY, R-410A SPLIT SYSTEM HEAT PUMP 1½ TO 5 TON HIGH-EFFICIENCY, R-410A SPLIT SYSTEM HEAT PUMP The Goodman uses the environmentally friendly refrigerant R-410A and features operating sound levels that are among the best in the heating and cooling industry.

More information

OBE, OBEXU, ON BOARD Battery Chargers

OBE, OBEXU, ON BOARD Battery Chargers C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S OBE, OBEXU, ON BOARD Battery Chargers INTRODUCTION: These chargers are designed for the permanent installation on battery powered vehicles

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

OPERATING MANUAL. centrifugal fan SAFETY PRACTICES

OPERATING MANUAL. centrifugal fan SAFETY PRACTICES 2237 MARSHALLTOWN BLVD. MARSHALLTOWN, IOWA 50158 PHONE: (641) 753-5601 TOLL FREE: 1-800-383-5601 FAX: (641) 752-9748 WWW.SPREAD-ALLMFG.NET OPERATING MANUAL centrifugal fan SAFETY PRACTICES 1. Have a qualified

More information

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE MODEL A96 SERIES 130Vdc Switchmode Utility Rectifier / Battery Charger Used with LaMarche Power Cage CPN112138 ECN/DATE ISSUE DATE: ECN 17010-12/05 106 BRADROCK DRIVE DES PLAINES, IL. 60018-1967 (847)

More information

INFRARED THERMOGRAPHY:

INFRARED THERMOGRAPHY: INFRARED THERMOGRAPHY: X-treme Electrical can now also assist with infrared thermography of various electrical installations. Please take the time to review the following presentation for comprehensive

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW Page 1 of 5 RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & Features: Benefits: 0-10Vdc or 0-5Vdc control input Over temperature protection with auto reset Din-rail mounting Efficient electronic switching No

More information

PRIVATELYOWNED POWER POLES AND POWERLINES

PRIVATELYOWNED POWER POLES AND POWERLINES PRIVATELYOWNED POWER POLES AND POWERLINES Privately-owned power poles and powerlines Privately-owned power poles and overhead powerlines must be properly maintained to ensure that they do not pose a serious

More information

RCL-7A. User s Guide. Battery Charging Station. Technology in Depth

RCL-7A. User s Guide. Battery Charging Station. Technology in Depth RCL-7A Battery Charging Station User s Guide Technology in Depth - NOTICE - This manual and the information contained herein are provided for use as a maintenance and operation guide. No license or rights

More information

ELECTRICAL SYSTEM RP-7

ELECTRICAL SYSTEM RP-7 ELECTRICAL SYSTEM RP-7 This section of the manual does not include integral electrical components of the engine. Refer to section Engine RP-1 for details. This section of the manual is divided into three

More information

INGECON SUN PowerMax B SERIES. A new generation of central photovoltaic inverters

INGECON SUN PowerMax B SERIES. A new generation of central photovoltaic inverters INGECON SUN PowerMax B SERIES A new generation of central photovoltaic inverters INGECON SUN PowerMax - B Series Main features of Ingeteam s central PV inverters The greatest power density on the market:

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

Selective Coordination

Selective Coordination Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings

More information

IB PowlVac ITE-HK Remote Racking Device

IB PowlVac ITE-HK Remote Racking Device IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking

More information

Pneumatic Cylinder 14 Bore X 21 Stroke Part No. P Replaces Part No. P

Pneumatic Cylinder 14 Bore X 21 Stroke Part No. P Replaces Part No. P Pneumatic Cylinder 14 Bore X 21 Stroke Part No. P -322908-00000 Replaces Part No. P-191067-00000 Service Information WARNING: INSTALLATION AND MOUNTING The user of these devices must conform to all applicable

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

Diane Emert Senior Thesis 2005 Broadway Plaza, Rochester, MN. Electrical Appendix

Diane Emert Senior Thesis 2005 Broadway Plaza, Rochester, MN. Electrical Appendix Electrical Appendix 121 Panel Switchgear/Panelboard Calculations Future Load (VA) Growth (125%) (VA) FLA (A) Corrected Amps Wire Size Breaker Size (A) 01LNA 38776 48470 134.54 168.17 2/0 175 02LNA 13134

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

MOULDED CASE CIRCUIT BREAKERS BH630N, BH630S

MOULDED CASE CIRCUIT BREAKERS BH630N, BH630S MOULDED CASE CIRCUIT BREAKERS BH6N, BH6S F BH6N, BH6S COMMERCIAL INFORMATION Switching units, withdrawable device, plug-in device...f4 Switch-disconnector unit...f6 Connecting sets...f7 Mounting sets...f9

More information

GSZ14. High-Efficiency, R-410A 1½ to 5 Tons. up to 14 SEER

GSZ14. High-Efficiency, R-410A 1½ to 5 Tons. up to 14 SEER High-Efficiency, R-410A 1½ to 5 Tons Cooling Capacity: 18,000 to 57,600 BTU/h Split System Heat Pump up to 14 SEER Heating Capacity: 18,000 to 59,000 BTU/h Standard Features R-410A chlorine-free refrigerant

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

Fault Codes. J control

Fault Codes. J control J control Timer Temp Fault Codes 12 11 10 9 8 7 6 5 4 3 2 1 30 29 28 27 26 25 24 23 22 21 20 Enter unit inspection mode by pushing the UP and DOWN buttons simultaneously for two seconds. Ensure that the

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

BLAZER 9000 LUBE LIFT OPERATOR AND PARTS MANUAL

BLAZER 9000 LUBE LIFT OPERATOR AND PARTS MANUAL BLAZER 9000 LUBE LIFT OPERATOR AND PARTS MANUAL Blazer 9000 Lube Lift Operator s Manual Note: Instructions must be read thoroughly before installing, operating, or maintaining the lift. Devon Lube Center

More information

Series 1000 and Figure NOTE: The top terminals are showing normally closed at rest and the middle terminals are normally

Series 1000 and Figure NOTE: The top terminals are showing normally closed at rest and the middle terminals are normally 38.18.The red wire on the OCR plug carries battery voltage. Behavior: D.C. battery voltage should show-up on a volt meter when the red probe is touched to this terminal and the black probe is grounded,

More information

QOF-20/22/30. Parts Manual. Direct Drive Oil-free scroll compressors. Manual No November 2014 Edition

QOF-20/22/30. Parts Manual. Direct Drive Oil-free scroll compressors. Manual No November 2014 Edition QOF-20/22/30 Direct Drive Oil-free scroll compressors Parts Manual This manual contains important safety information and should be made available to all personnel who operate and/or maintain this product.

More information

Thermal Patterns Associated with Infrared Inspection of Electrical Systems

Thermal Patterns Associated with Infrared Inspection of Electrical Systems Thermal Patterns Associated with Infrared Inspection of Electrical Systems James Brady Level III Certified Infrared Thermographer Brady Infrared Inspections, Inc. 935 Pine Castle Court Stuart, FL 34996

More information

MANUAL Model: PT 12/24-60 Solar Converters Inc. - Rev. F

MANUAL Model: PT 12/24-60 Solar Converters Inc. - Rev. F 1.0 Specification MANUAL Model: PT 12/24-60 Solar Converters Inc. - Rev. F Note: This unit is a Multi - Voltage unit with adjustable input panel and output battery adjustment. Please review the section

More information

Frequency of Maintenance Tests These specifications have been developed by the InterNational Electrical Testing Association for use by electrical power distribution system engineers. Copyright 2001 InterNational

More information

MOULDED CASE CIRCUIT BREAKERS BC160N

MOULDED CASE CIRCUIT BREAKERS BC160N D MOULDED CASE CIRCUIT BREAKERS BC160N D BC160N COMMERCIAL INFORMATION Circuit breakers...d4 Switch-disconnectors...D5 Connecting sets......d6 Mounting sets......d6 Switches...D7 Shunt trips...d7 Undervoltage

More information

3 Phase Voltage Imbalance

3 Phase Voltage Imbalance 3 Phase Voltage Imbalance Keep in mind when reading ANY article about electrical theory or application is that it only scratches the surface of the topic. You can dedicate years of your life to understanding

More information

VI Chip BCM Bus Converter Thermal Management

VI Chip BCM Bus Converter Thermal Management APPLICATION NOTE AN: VI Chip BCM Bus Converter Thermal Management Joe Aguilar Product Line Engineer, VI Chip & Paul Yeaman Principal Product Line Engineer, VI Chip Strategic Accounts Contents Page Introduction

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TECHNICAL INSTRUCTIONS 76-50213-00 Solar Charger Kit This kit provides the necessary parts and instructions to install an optional Battery Solar Charger Kit. The solar panel charging system will help maintain

More information

SSX14 PRODUCT SPECIFICATIONS 14 SEER / R-410A HIGH-EFFICIENCY SPLIT SYSTEM AIR CONDITIONER 1½- TO 5-TON COOLING CAPACITY 18,000 TO 56,800 BTU/H

SSX14 PRODUCT SPECIFICATIONS 14 SEER / R-410A HIGH-EFFICIENCY SPLIT SYSTEM AIR CONDITIONER 1½- TO 5-TON COOLING CAPACITY 18,000 TO 56,800 BTU/H PRODUCT SPECIFICATIONS 14 SEER / R-410A 1½- TO 5-TON COOLING CAPACITY 18,000 TO 56,800 BTU/H HIGH-EFFICIENCY SPLIT SYSTEM AIR CONDITIONER The Goodman Air Conditioner uses the environmentally friendly refrigerant

More information

Easy Start. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual

Easy Start. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual Easy Start 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter Installation Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526. www.microair.net Allentown NJ 08501 Fax (609) 259-6601 Retrofit

More information

Tundra Racing LOWERING KIT INSTALLATION MANUAL Toyota Tundra 2wd & 4x4 Part #TR-2040 & TR-2050 Reg Cab, Double Cab & Crewmax

Tundra Racing LOWERING KIT INSTALLATION MANUAL Toyota Tundra 2wd & 4x4 Part #TR-2040 & TR-2050 Reg Cab, Double Cab & Crewmax Page 12 Front Coil Spring Perch, Sleeve and Bump Stops Leaf Spring Shackle and Hardware PARTS INCLUDED IN KIT Tundra Racing LOWERING KIT INSTALLATION MANUAL Axle Perches Top & Bottom Plates U-Bolts and

More information

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi 1 TABLE OF CONTENTS TABLE OF CONTENTS... 2 IMPORTANT NOTE... 3 FAULT FINDING AND DIAGNOSTICS... 3 ABBREVIATIONS... 3 PCB S... 4 OUTDOOR MAIN PCB... 4 INDOOR PCB...

More information

PHYSICS 6 EXTENDED PHYSICS

PHYSICS 6 EXTENDED PHYSICS PHYSICS 6 EXTENDED PHYSICS GRADE 11 TERM 3 PORTFOLIO TASKS 2013-2014 STS\G11\Portfolio\Extended Physics Assessment Booklet\CDAU\ADVETIVersion 1.0 2014 1 31 Unit/Topic Performance Criteria Assess Event

More information

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules. Fuseology Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression Optima Fuse Holders & Overcurrent Protection Modules Compact, full-featured modules that deliver Type 2 coordinated protection,

More information