2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9

Size: px
Start display at page:

Download "2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9"

Transcription

1 8/139 Woolooware Rd Burraneer NSW 2230 T. (02) F. (02) E. W. Accredited Thermographers 2006 Thermographic Inspection Terrific Towers 1001 Sparks St Sydney NSW Vol. 9 Client ACME Electrical Pty Ltd Job No Address 1050 Sydney St Sydney NSW 200 Date 28/03/06 Tel. (02) Fax (02) :00 AM Contact Eddie the Electrician Vol. Nine (9) Location Terrific Towers 1001 Sparks St Sydney IR Camera Avio TVS 610 Serial No. 0342A1141AD Visual Camera Kodak DX3600 Serial No. KJCAJ Load Measurement Device Kyoritsu-2017 Serial No. KY B Thermographer Accreditation No. AINDT General Information An Infrared Thermal Scan of Listed Electrical Switchboards was conducted 28 th March The complex was drawing load from the Local Supply Authority at time of inspection. Internal switchgear components and associated wiring were inspected for abnormal operating temperatures effected by load or equipment condition. Wiring and terminations were inspected for high resistance connections and insulation condition. Load conditions were as experienced during periods of normal demand. All inspected switchboards and associated wiring within were thermally operating within load conditions. Internal wiring insulation and terminations appear to be sound with exceptions as listed within. 1

2 General Information Application Thermal Scanning The information listed below is to assist in the interpretation and discharge of appropriate remedial action of reported faults or potential areas of concern. Recommendations listed within this report are within the area of our expertise and recommend you discuss the implementation of service/repair with your maintenance service provider. Scope Infrared Thermal scan of electrical switchgear and associated conductors to detect the evidence of equipment operating near or above rated thermal temperatures. Where possible load readings are taken to ensure proper diagnosis of prospective faults. Australian and IEC Standards along with Copper & Brass Association publication No.22 are used as benchmarks for assessing permissible temperature limits. Method All accessible covers are removed from the switchboards with internal PVC shrouds removed when installed in a manner that facilitates safe removal. Switchboards assigned a segregation rating greater than two (2), in accordance with AS3439, or where fitted with internal busbar shrouds can be arranged to be scanned with the arrangement of at least two shutdowns to remove and reinstall covers. Internal metal covers will not be removed whilst the switchboard is on line. An infrared radiometer with its range initially set at 20 C and 40 C is passed over all switchgear, bus system and cable connections. Areas displaying abnormal temperature variations are further investigated by means of equipment application analysis, load measurement and pinpoint temperature readings. Faults and areas of concern have infrared thermal and digital images saved for report and condition monitoring tasks. Results A priority rating schedule along with suggested remedial action plans are included for prioritising rectification works. Where faults of a life or property threatening situation are detected, notification will be immediately made to the client s representative. Ultimately it is the owner or plant operator s responsibility to implement or gain further advice of the recommended repairs contained within this report. Each thermal image is uniquely identified to correspond with a label placed upon the affected equipment for ready identification by maintenance personnel. Priority Rating Recommended Action 0 No Fault. Re-scan within 12 months 1 Disconnect supply immediately 2 Arrange service /repair within 24 hours 3 Arrange service/repair at very next service opportunity 4 Arrange service/repair at next scheduled maintenance 5 Condition monitor Licensed electricians must perform all repairs and service. Services Available Annual preventative maintenance surveys. Design and repair advice. Procurement of services Property/asset reports Condition Monitoring Compliance Reports Insurance Audits 2

3 Table of Contents Section Equipment Priority Page Chiller 2 Compressor 3 DOL Starter 3 4 Located Roof Plant Room MSSB-2 SF3 AHU Located Catwalk C Phase Supply Fuse Main Switchboard Non Essential Main Switch 3 6 Located Carpark Main Switchroom Mechanical Services MCC-3 SF3 AHU-3 C Phase Fuse 2 7 Located Level 16 Plant Room S1 Dry Store C Phase Fuse Main Switchboard (Panel 7) Un-marked Fuse 2 8 Located Boiler Plant Room Summary of Inspection List of Reported Items 9 Fault Log of Inspected Assets 10 &11 Certification Details 12 3

4 Inspected Equipment Chiller 2 Located Roof Plant Room Operator: Malcolm Rhind Reference Image Equipment Equipment Type Additional Information Compressor 3 DOL Starter Interconnection Cable Date 25/04/2006 Working conditions: Loadings A Phase 86.2 Amperes B Phase 85.9 Amperes C Phase 86.1 Amperes 11:24 AM Plant mounted within a ventilated plant room Thermal Image C elsius IR Image Details Image No. Emissivity 0.95 Spot C Spot C Area 1 Max C Area 2 Max. <unknown> Background 30.0 C Max Thermoteknix TV S :24:08 A M 25/04/2006 e : 0.95 Bg : 30.0 C Description of Fault Priority Rating 3 Recommendation High resistance termination at circuit breaker terminal. Evidence of cable insulation deterioration. Replace interconnecting cable. As only 5 of 10 contactors were on line at time of inspection a complete re-tension of all connections is advisable. Previous Fault Description Date Image Vol. Code Page Remedial Action Taken Authorised 4

5 Inspected Equipment MSSB-2 Located Catwalk Operator: Malcolm Rhind Reference Image Thermal Image Equipment Equipment Type Additional Information SF3 AHU-3 C Phase Supply Fuse Alstom RS100 Date 24/06/2006 Working conditions: Loadings A Phase 36.7 Amperes B Phase 32.1 Amperes C Phase 33.6 Amperes 12:17 PM Located within a well ventilated area. IR Image Details C elsius Image No. Emissivity 0.95 Spot C Spot C Difference <unknown> Area 1 Max C 60.0 Area 2 Max. <unknown> Max Background 28.0 C Thermoteknix TV S :17:09 PM 24/06/2006 e : 0.95 Bg : 28.0 C Description of Fault Priority Rating 2 Recommendation Previous Fault Description Date Image Vol. Code Page Remedial Action Taken High resistance connection on C Phase load side fuse fitting. Ensure fuse cartridge is securely fixed to carrier and that carrier is making firm contact with base upon insertion. Ensure load side termination is tensioned. 5

6 Authorised Inspected Equipment Main Switchboard Located Carpark Main Switchroom Operator: Malcolm Rhind Reference Image Equipment Equipment Type Non Essential Main Switch Dumeco 1250A Additional Information Date 13/09/2004 Working conditions: 10:14 AM Floor mounted within an air conditioned switchroom Thermal Image Celsius Spot Spot Spot Spot Spot Spot IR Image Details Image No. Emissivity 0.95 Spot C Spot C Difference <unknown> Area 1 Max. <unknown> Area 2 Max. <unknown> Background 18.0 C Thermoteknix TVS :14:10 AM 13/09/2004 e : 0.95 Bg : 18.5 C Description of Fault Priority Rating 3 Recommendation High resistance connection A & B Phase load side busbars to main switch. Deterioration most probably caused by downstream short circuit Clean contact surfaces and re-tension. Ensure busbars are not supported by main switch as pressure on connecting tags can cause internal contact misalignment. Previous Fault Description Date Image Vol. Code Page Remedial Action Taken 6

7 Authorised Inspected Equipment Mechanical Services MCC-3 Located Level 16 Plant Room Operator: Malcolm Rhind Reference Image Equipment Equipment Type Additional Information Date 24/06/2005 Working conditions: SF3 AHU-3 C Phase Fuse S1 Dry Store C Phase Fuse Alstom RS100 Loadings Fuse Amperes Fuse Amperes 12:18 PM Located within a well ventilated area. Thermal Image C elsius Thermoteknix TV S :18:56 PM 24/06/1906 e : 0.95 Bg : 28.8 C Max Max IR Image Details Image No. Emissivity 0.95 Spot C Spot C Difference <unknown> Area 1 Max C Area 2 Max C Background 29.0 C Description of Fault Priority Rating 2 Recommendation Previous Fault Description Date Image Vol. Code Page Remedial Action Taken High resistance connection on load side of fuse fittings. Ensure fuse cartridges are securely fixed to carrier and that carriers are making firm contact with bases upon insertion. Ensure load side terminations are tensioned. 7

8 Authorised Reference Image Inspected Equipment Main Switchboard (Panel 7) Located Boiler Plant Room Operator: Malcolm Rhind Equipment Equipment Type Un-marked Fuse HRC Fuse Additional Loading 11.9 Amperes Information Date 8/03/2006 Working conditions: 09:53 AM Floor mounted within a non-ventilated plant room. Ambient temperature influenced by plant equipment. Thermal Image Celsius IR Image Details Image No. Emissivity 0.95 Spot C Spot 2 <unknown> Difference <unknown> Area 1 Max C Area 2 Max. <unknown> Background 32.0 C Max Thermoteknix TVS-600 9:53:27 AM 8/03/2006 e : 0.95 Bg : 32.3 C Description of Fault Priority Rating 2 Recommendation Previous Fault Description Date Image Vol. Code Page Remedial Action Taken High resistance connection load side of fuse fitting. Make good cable end and re-terminate. Ensure fuse is securely fixed to carrier and that the carrier is making firm contact with the fuse base. Authorised 8

9 List of Reported Items Switchboard Component Fault Priority Recommendations Chiller 2 Compressor 3 DOL Located Roof Plant Starter Room MSSB-2 Located Catwalk Main Switchboard Located Carpark Main Switchroom Mechanical Services MCC-3 Located Level 16 Plant Room Main Switchboard (Panel 7) Located Boiler Plant Room SF3 AHU-3 C Phase Supply Fuse Non Essential Main Switch SF3 AHU-3 C Phase Fuse S1 Dry Store C Phase Fuse Un-marked Fuse High resistance termination at circuit breaker terminal. Evidence of cable insulation deterioration. High resistance connection on C Phase load side fuse fitting. High resistance connection A & B Phase load side busbars to main switch. Deterioration most probably caused by downstream short circuit High resistance connection on load side of fuse fittings. High resistance connection load side of fuse fitting. 3 Replace interconnecting cable. As only 5 of 10 contactors were on line at time of inspection a complete retension of all connections is advisable. 2 Ensure fuse cartridge is securely fixed to carrier and that carrier is making firm contact with base upon insertion. Ensure load side termination is tensioned. 3 Clean contact surfaces and re-tension. Ensure busbars are not supported by main switch as pressure on connecting tags can cause internal contact misalignment 2 Ensure fuse cartridges are securely fixed to carrier and that carriers are making firm contact with bases upon insertion. Ensure load side terminations are tensioned. 2 Make good cable end and re-terminate. Ensure fuse is securely fixed to carrier and that the carrier is making firm contact with the fuse base 9

10 Fault Log of Inspected Assets Location Switchboard Basement Main Switchboard 1 F F F F Main Power Factor Switchroom Correction Unit NOL House DB-B Roof Plant Room Air Compressor 1 Control Panel Air Compressor 2 Control Panel NOL NOL Chiller 1 Controls F F Chiller 2 Controls F F F F MP1-04 Vacuum Pump Panel MCC-1 Services/CIP MCC-2 Services/CIP CWP VLT Cabinet NOL Catwalk MSSB-2 Level 16 Plant Room Level 15 Level 14 Level 13 Level 12 Level 11 Level 10 Level 9 Level 8 Level 7 Level 6 Mechanical Services F F MCC-3 Tenant DB-15 F House DB-H15 F F Tenant DB-14 House DB-H14 Tenant DB-13 F House DB-H13 Tenant DB-12 House DB-H12 Tenant DB-11 House DB-H11 Tenant DB-10 House DB-H10 Tenant DB-9 F F F House DB-H9 Tenant DB-8 House DB-H8 Tenant DB-7 House DB-H7 F Tenant DB-6 House DB-H6 10

11 Location Switchboard Level 5 Tenant DB-5 House DB-H5 Level 4 Level 3 Level 3 Level 2 Level 1 Ground Level East Service Cupboard Ground Level West Service Cupboard Tenant DB-4 House DB-H4 F Tenant DB-3 F House DB-H3 Tenant DB-3 House DB-3 F F Tenant DB-2 House DB-H2 Tenant DB-1 F House DB-H1 Retail Tenant DB-1E Retail Tenant DB-2E F F Retail Tenant DB-3E Retail Tenant DB-4E Retail Tenant DB-5E F F F Retail Tenant DB-6E Retail Tenant DB-1W Retail Tenant DB-2W Retail Tenant DB-3W Retail Tenant DB-4W F F Retail Tenant DB-5W Retail Tenant DB-6W F NOL = Fault = No Fault Detected = Not on Line 11

12 12

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection: Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: 27-10-2006 Reference Number: 2710061 Thermographer: John Crawford Thermal Imaging

More information

THERMOGRAPHY REPORT ELECTRICAL

THERMOGRAPHY REPORT ELECTRICAL LAMBERT CONDITION MONITORING LTD. CERTIFIED THERMOGRAPHER A.I.R. #12-01-243 THERMOGRAPHY REPORT ELECTRICAL Thermographic inspection at: Sample site Inspected by: David Lambert date: 20170701 Customer Sample

More information

SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA

SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA July, 2018 Infrared Inspection Report Sysco Central California 136 South Mariposa Road Modesto, California, 95393 Company Contact: Steve Handel Project: 04110718

More information

BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE

BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE July, 2015 Infrared Inspection Report Buzzi Unicem Terminal Company Contact Randy Miguez Project: 06220715 2605 CHARTER OAK DRIVE, LITTLE

More information

SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA

SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA November, 2017 Infrared Inspection Report Sysco Indianapolis LLC. 4000 West 62nd Street Indianapolis, Indiana, 46268 Company Contact: Trevor Gray Project: 05161117

More information

Avid Electrical Services

Avid Electrical Services Avid Electrical Services Thermal Imaging Report To: Mr A. Customer Your Business Australia Pty Ltd Fault Summary The following table is a summary of faults or items featured for your information Grading

More information

Fault Summary The following table is a summary of faults or items featured for your information

Fault Summary The following table is a summary of faults or items featured for your information This document is an annotated sample of a report you receive. following our visit to your premises... We pride ourselves on the quality of the report and submit. this sample for your evaluation.. Report

More information

SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS

SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS July, 2015 Infrared Inspection Report Sidewinder Drilling Company Contact Tommy Green Project: 02170715 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE:

More information

Low and medium voltage service. Power Care Customer Support Agreements

Low and medium voltage service. Power Care Customer Support Agreements Low and medium voltage service Power Care Customer Support Agreements Power Care Power Care is the best, most convenient and guaranteed way of ensuring electrification system availability and reliability.

More information

SYSCO RDC SOUTH ALACHUA, FLORIDA

SYSCO RDC SOUTH ALACHUA, FLORIDA SYSCO RDC SOUTH ALACHUA, FLORIDA July, 2018 Infrared Inspection Report Sysco RDC South 12421 NW 173rd Street Alachua, Florida, 32615 Company Contact: Natha Hall Project: 05110818 2605 CHARTER OAK DRIVE,

More information

SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS

SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS November, 2017 Infrared Inspection Report Sidewinder Drilling Rig 127 Pecan Acres 23 PSA 3-3H(WB) Company Contact Colton Chesney Project: 02201117 2605 CHARTER

More information

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA August, 2018 Infrared Inspection Report SYSCO Oklahoma LLC 1350 West Tecumseh Road Norman, Oklahoma, 73069 Company Contact Chris Hill Project: 03210818 2605 CHARTER

More information

Product Overview. Soft Starters Motor Protection Control and Measurement. Solcon Industries Ltd.

Product Overview. Soft Starters Motor Protection Control and Measurement. Solcon Industries Ltd. Product Overview Soft Starters Motor Protection Control and Measurement Solcon Industries Ltd. Medium Voltage Soft Starters HRVS-DN Medium Voltage Soft Starter, 50-2500A, 1500-15000V Incorporating microprocessor

More information

Safe Working on or near low voltage electrical installations & equipment

Safe Working on or near low voltage electrical installations & equipment Safe Working on or near low voltage electrical installations & equipment Guidance Notes Version 1.11 28 June 2017 Gippsland Water Document Details Business Owner Procedure Process Owner/s Document Title

More information

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3

TABLE OF CONTENTS FOREWORD... 2 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS... 3 TITLE SPECIFICATION FOR MEDIUM VOLTAGE DATE: FEBRUARY 2015 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD... 2 INTRODUCTION... 3 1 SCOPE... 3 2 NORMATIVE S... 3 3 DEFINITIONS AND ABBIATIONS... 3 4 REQUIREMENTS...

More information

High Voltage Electrician Training

High Voltage Electrician Training High Voltage Electrician Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our 2-Day High Voltage Electrician

More information

Appendix 11 RETURN TO APPENDICES LIST. High Voltage Power Supply Upgrade (Welcon Technologies Pty Ltd)

Appendix 11 RETURN TO APPENDICES LIST. High Voltage Power Supply Upgrade (Welcon Technologies Pty Ltd) Appendix 11 RETURN TO APPENDICES LIST High Voltage Power Supply Upgrade (Welcon Technologies Pty Ltd) GLADSTONE AREA WATERBOARD AWOONGA DAM HIGH VOLTAGE POWER SUPPLY UPGRADE Document: GJ543-RP-02B Submission

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

Steve Summers Region Sales Manager

Steve Summers Region Sales Manager Steve Summers Region Sales Manager Institute For Animal Healthcare LV Switchgear Package Package Subs LV Switchboards PDU s LV sub Distribution MCC s MV Switchgear Established in 1972 manufacturing control

More information

ype UP T Busplugs Low Voltage Switchboard Equipment

ype UP T Busplugs Low Voltage Switchboard Equipment Busplugs Type UP Low Voltage Switchboard Equipment Publication UP 2013 Since product improvement is a continuing policy, we reserve the right to change specifications without notice. Contents Descriptive

More information

FAQ s. Designing metering switchboards as per Victorian service installation rules

FAQ s. Designing metering switchboards as per Victorian service installation rules FAQ s Designing metering switchboards as per Victorian service installation rules Designing metering switchboards as per Victorian service installation rules Q: Who develops the Victorian service installation

More information

Thermal Imaging Infrared Survey. Report. Report. Thermography Inspection at ABC Company.

Thermal Imaging Infrared Survey. Report.  Report. Thermography Inspection at ABC Company. Thermal Imaging Infrared Survey Report. Thermal Imaging Infrared Survey Report. Thermography Inspection at ABC Company. Vancouver,BC May 25,2012 www.aiturgroup.com info@aiturgroup.com Rick Turdubay, Certified

More information

Exceeding the standards with MNS

Exceeding the standards with MNS Exceeding the standards with MNS Exceeding the standards with MNS 5 essentials of switchgear solutions Since ABB first introduced MNS the modular low voltage switchgear platform over forty years ago, MNS

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

ALLMAC Electrical Eng. 61 (0) Advanced Infrared +61 (0) BES (Aust) Pty Ltd AUSTPTA

ALLMAC Electrical Eng. 61 (0) Advanced Infrared +61 (0) BES (Aust) Pty Ltd AUSTPTA page 1a ABB Australia 1800 222 435 Advanced Infrared +61 (0)425 758 820 ALLMAC Electrical Eng. 61 (0)419 819 756 Ampcontrol 1300 267 373 AUSTPTA www.austpta.asn.au BES (Aust) Pty Ltd 61 2 9686 4811 Products/

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

High Voltage Electrical Maintenance Training

High Voltage Electrical Maintenance Training High Voltage Electrical Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq High Voltage Electrical

More information

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In

More information

INFRARED INSPECTION REPORT

INFRARED INSPECTION REPORT REPORT February 13, 2015 Companies Unlimited 1401 Brand St. Los Angeles, CA 90028 Contact: Ron McKinney An Introduction to Infrared Inspection When installed correctly and operated within their ratings,

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

PRACTICAL TROUBLESHOOTING OF ELECTRICAL EQUIPMENT & CONTROL SYSTEMS

PRACTICAL TROUBLESHOOTING OF ELECTRICAL EQUIPMENT & CONTROL SYSTEMS Training Title PRACTICAL TROUBLESHOOTING OF ELECTRICAL EQUIPMENT & CONTROL SYSTEMS Training Duration 5 days Training Venue and Dates Practical Troubleshooting Of Electrical Equipment & Control Systems

More information

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS Supersedes: 160.75-PW2 (508) Form 160.75-PW2 (311) FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS WIRING DIAGRAM CONTRACTOR ORDER NO. YORK CONTRACT NO.

More information

January 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit.

January 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit. 3018 Eastpoint Parkway Louisville, KY 40223 (502) 716-7073 January 30, 2006 Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT Re: NFPA 70E Hazard Assessment Date of Visit January 24, 2006

More information

GAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura

GAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura Modular-C\Standardized Motor Control Centres\ M600204.15 PT Guna Era Manufaktura Catalogue 2015 GAE MCC Modular-C Standardized Motor Control Centres General Definition Type-tested low-voltage switchgear

More information

A DIAGNOSTIC MAINTENANCE SYSTEM FOR COMMERICIAL AND NAVAL VESSELS JANE CULLUM

A DIAGNOSTIC MAINTENANCE SYSTEM FOR COMMERICIAL AND NAVAL VESSELS JANE CULLUM A DIAGNOSTIC MAINTENANCE SYSTEM FOR COMMERICIAL AND NAVAL VESSELS JANE CULLUM jane.cullum@utas.edu.au SUPERVISORS: Associate Professor Jonathan Binns, Professor Kiril Tenekedjiev, Dr. Rouzbeh Abbassi,

More information

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs [ MV Air-insulated Switchgear Range ] 1 PIX CUSTOMER BENEFITS Compact, versatile and highly reliable designs Choice of vacuum or SF6 switching technology Wide range of applications Enhanced operator safety

More information

Service and Rehabilitation Electrical Power Systems

Service and Rehabilitation Electrical Power Systems Service and Rehabilitation Electrical Power Systems From water to wire 3 ANDRITZ HYDRO Electrical Power System Modernization and rehabilitation International technology group ANDRITZ is a globally leading

More information

S H A D E S ELECTRICAL DB MANUFATURING

S H A D E S ELECTRICAL DB MANUFATURING CORPORATE BROCHURE S H A D E S ELECTRICAL DB MANUFATURING S H D E S ELECTRICAL DB MANUFACTURING L.L.C. www.shadesdb.com I N T R O D U C T I O N Welcome to SHADES, this portfolio has been designed to give

More information

Paramount HRC Cartridge

Paramount HRC Cartridge Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing

More information

Company Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI

Company Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI Company Name City, State Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI 54476-0740 April 9, 2012 (Customer Name & Address) Attn: Customer Enclosed is a report on the

More information

FAQ S. Main Switchboard Design Criteria. ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS

FAQ S. Main Switchboard Design Criteria.   ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS FAQ S Main Switchboard Design Criteria h ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS www.electricalswitchboards.com.au Main switchboard Design criteria Q: What is the Australian standard for main

More information

Modular medium-voltage switchgear. NorMax

Modular medium-voltage switchgear. NorMax Modular medium-voltage switchgear NorMax NorMax MODULAR MEDIUM-VOLTAGE SWITCHGEAR 2 NorMax Modular medium-voltage switchgear Contents Subject Page Table of contents 2 Introduction and main features 2 Technical

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information

Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition. Compliance Checklist.

Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition. Compliance Checklist. Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition Compliance Checklist Note: The requirements noted against the various sections in this checklist

More information

DESIGN AND RETROFITTING OF LOW VOLTAGE AIR CIRCUIT BREAKERS.

DESIGN AND RETROFITTING OF LOW VOLTAGE AIR CIRCUIT BREAKERS. DESIGN AND RETROFITTING OF LOW VOLTAGE AIR CIRCUIT BREAKERS. Terasaki Electric Europe Ltd, UK 80 Beardmore Way, Clydebank Industrial Estate, Glasgow G81 4HT By Peter Anderson Abstract Throughout the world

More information

onlinecomponents.com

onlinecomponents.com s ST Spring cage fuse terminal blocks from Phoenix Contact satisfy two important tasks of electrical connection systems. Firstly, they act as carriers for fuses and secondly, they assume the task of potential

More information

YOUR ELECTRICAL SYSTEM IS YOUR LIFELINE AMP-TRAP 2000 FUSES

YOUR ELECTRICAL SYSTEM IS YOUR LIFELINE AMP-TRAP 2000 FUSES YOUR ELECTRICAL SYSTEM IS YOUR LIFELINE AMP-TRAP 2000 FUSES AMP-TRAP 2000 FUSES IN SHORT, AMP-TRAP 2000 FUSES PROTECT YOUR ASSETS A lifeline that can be cut by an arc flash can disintegrate. Conductors

More information

ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION

ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION Chanmari, Fatullah, Narayanganj- 1400 GPS Coordinate:23.634239,90.496801 Inspected by Report Generated by : Noman Saber Khan & Shaik Muhammed Wasi

More information

SWITCHBOARDS (LV and MV)

SWITCHBOARDS (LV and MV) ELEC9713 Industrial and Commercial Power Systems SWITCHBOARDS (LV and MV) 1. Introduction Depending on the size of the building or factory site and whether the supply is high voltage or low voltage, there

More information

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY

MOTHER DAIRY A UNIT OF GUJARAT CO-OPERATIVE MILK MARKETING FEDERATION LIMITED PURCHASE ENQUIRY PURCHASE ENQUIRY Inquiry No : MDG/PUR/PKS/ENQ/Panels, Dated: Jan 30, 2015 Description Qty Specifications : Purchase Inquiry for Supply, installation and commissioning of Panels for PFP Expansion project.

More information

OWNER S MANUAL Please read this manual before operating your power supply

OWNER S MANUAL Please read this manual before operating your power supply AC-DC POWER SUPPLY Switch Mode AC-DC Power Supply Model No. PSU-1210 PSU-1223 PSU-1230 OWNER S MANUAL Please read this manual before operating your power supply Table of Contents Precautions 2 Description

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

PRIVATELYOWNED POWER POLES AND POWERLINES

PRIVATELYOWNED POWER POLES AND POWERLINES PRIVATELYOWNED POWER POLES AND POWERLINES Privately-owned power poles and powerlines Privately-owned power poles and overhead powerlines must be properly maintained to ensure that they do not pose a serious

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented

More information

Contents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers

Contents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers DISTRIBUTION CODE Contents 1 Introduction 2. Advisory and Information Systems 3. Supply 3.1 Quality of Electric Supply 3.2 Interference with other Customers 3.3 Application for the Supply of Electricity

More information

Artesis MCM Case Studies. March 2011

Artesis MCM Case Studies. March 2011 Artesis MCM Case Studies March 2011 Case 1 Automotive Company: Automobile Manufacturer A Equipment: Pump Stator Isolation Breakdown Decreasing current unbalance level Case 1 Automotive Company: Automobile

More information

PM/ECCM Course Description and Outline

PM/ECCM Course Description and Outline PM/ECCM Course Description and Outline Preventive Maintenance/Essential Care and Condition Monitoring is one of the cornerstones in a world-class reliability process. Condition monitoring will provide

More information

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION

REFERENCE REV CP_TSSPEC_016 1 TITLE SPECIFICATION FOR DATE: NOVEMBER 2010 LIGHTING TABLE OF CONTENTS Page FOREWORD INTRODUCTION TITLE SPECIFICATION FOR CONTACTORS FOR PUBLIC LIGHTING REFERENCE REV DATE: NOVEMBER 2010 PAGE: 1 OF 16 TABLE OF CONTENTS Page FOREWORD.. 2 INTRODUCTION 3 1 SCOPE...... 3 2 NORMATIVE REFERENCES...... 3

More information

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks

Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks by Georges Barbarin Executive summary Aging electrical switchgear infrastructure is a threat to the reliability of power

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING dv Sentry TM 208V 600V INSTALLATION GUIDE FORM: DVS-IG-E REL. January 2018 REV. 003 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation of this filter.

More information

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers 2 Introduction This discussion describes in detail retrofitting medium voltage circuit

More information

Solar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings

Solar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings TOOLKIT DOCUMENT #4 Your City logo here Solar Standard Plan Simplified Microinverter and M Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters

More information

Range : 20A, 32A, 63A & 100A in front connection, bus bar connection & rear connection versions.

Range : 20A, 32A, 63A & 100A in front connection, bus bar connection & rear connection versions. 164 Fuse Holder consisting of carrier and base for mounting fuse links have been in use for long. Keeping operators safety and ease / reliability of removal in mind, a complete range of unique CAM operated

More information

Installation Operation & Maintenance Manual. Oil-Free (Dry) Rotary Vane Vacuum Pump Systems

Installation Operation & Maintenance Manual. Oil-Free (Dry) Rotary Vane Vacuum Pump Systems Installation Operation & Maintenance Manual Oil-Free (Dry) Rotary Vane Vacuum Pump Systems Part No. 9983-0000-S07 / November 2018 OIL-FREE (DRY) ROTARY VANE VACUUM PUMP SYSTEMS TABLE OF CONTENTS CUSTOMER

More information

Research Brief. Impact of higher 25kV fault currents. T873 - October Background. Aims

Research Brief. Impact of higher 25kV fault currents. T873 - October Background. Aims Research Brief Impact of higher 25kV fault currents Background Increasing the maximum fault levels at traction feeder stations has the potential to reduce the costs of electrification schemes. The potential

More information

System Manual 02/2008

System Manual 02/2008 System Manual 02/2008 SIRIUS Infeed System for 3RA6 sirius COMPACT STARTER Introduction 1 Product-specific information 2 SIRIUS industrial switchgear Load feeders, motor and soft starters System Manual

More information

SAFETY FACT SHEETS. Electrical Hazards Safety Non Negotiable. G-HS-ST Electrical Hazards. G-HS-FS Version:1

SAFETY FACT SHEETS. Electrical Hazards Safety Non Negotiable. G-HS-ST Electrical Hazards. G-HS-FS Version:1 SAFETY FACT SHEETS Electrical Hazards Safety Non Negotiable G-HS-ST-00752 Electrical Hazards Safety Non-Negotiables (SNN) Zinfra Group is committed to providing a safe workplace in line with our number

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT ABSS HIGH TECH SWEATER LTD. Kalameshar, Board Bazar, Gazipur. Factory List: ABSS HIGH TECH SWEATER LTD. Inspected by Report Generated by : Hossain Shah Aarif : Mobassear

More information

INFO. SHEET: E1:1 INSPECTION & TESTING OF ELECTRICAL EQUIPMENT

INFO. SHEET: E1:1 INSPECTION & TESTING OF ELECTRICAL EQUIPMENT INFO. SHEET: E1:1 INSPECTION & TESTING OF ELECTRICAL EQUIPMENT This Information Sheet provides guidance on how to carry out User Checks, Formal Visual Inspections and combined Inspection and Tests on portable

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA

STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA CB-02 STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA POWER CENTER PC MOTOR CONTROL CENTER MCC32 MOTOR CONTROL CENTER MCCF Premises 10.000mq Offices 2.000mq Warehouse 1.200mq Open Area 15.000mq

More information

UniSec Maintenance solutions

UniSec Maintenance solutions DISTRIBUTION SOLUTIONS UniSec Maintenance solutions ABB supports you to improve the reliability, safety and efficiency of your electrical equipment UniSec Maintenance solutions Table of contents 004 00

More information

ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET

ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Candidate Code No. EIN15 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Low Voltage Industrial Type T Fuse Links

Low Voltage Industrial Type T Fuse Links Low Voltage Industrial Type T Fuse Links Type T HRC Fuse Links for Industrial and General Application Contents Introduction 2 Performance Data 3 List Numbers and Dimensions 4 Utilisation Categories 8 Application

More information

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Modular Standardized Electrical and Control Solutions for Fast Track Projects Modular Standardized Electrical and Control Solutions for Supporting fast track projects ABB is the leading supplier of electrical and control equipment for power plants. The company offers a comprehensive

More information

Low Voltage Systems. Service and Support Lifecycle. proactive value. innovative value. resourceful value. activate value.

Low Voltage Systems. Service and Support Lifecycle. proactive value. innovative value. resourceful value. activate value. Low Voltage Systems Service and Support Lifecycle proactive value innovative value resourceful value activate value adaptable value intelligent value communicative value Keeping important services running

More information

MODVAR Low voltage reactive power compensation modules Installation manual

MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Installation manual MODVAR Low voltage reactive power compensation modules Before installation, read this manual carefully and keep at the disposal

More information

AT EVO SERIES BATTERY CHARGER

AT EVO SERIES BATTERY CHARGER STANDARD FEATURES 5 YEAR WARRANTY EVO AT Series Battery Charger is HindlePower s next generation SCR-based utility battery charger. This evolutionary product is revolutionary in its design and operation

More information

INFRARED THERMOGRAPHY:

INFRARED THERMOGRAPHY: INFRARED THERMOGRAPHY: X-treme Electrical can now also assist with infrared thermography of various electrical installations. Please take the time to review the following presentation for comprehensive

More information

NZQA registered unit standard version 1 Page 1 of 5

NZQA registered unit standard version 1 Page 1 of 5 Page 1 of 5 Title Demonstrate and apply knowledge of theory and practice for registration of electrical workers (stage 3) Level 4 Credits 3 Purpose This unit standard is for people who are completing an

More information

Guidelines when working near TasNetworks electrical assets

Guidelines when working near TasNetworks electrical assets Guidelines when working near TasNetworks electrical assets About TasNetworks Tasmanian Networks Pty Ltd (ACN 167 357 299) ( TasNetworks ) is the owner and operator of the regulated electricity network

More information

Performance Service Centres. ABB Performance Services. Power and productivity for a better world TM

Performance Service Centres. ABB Performance Services. Power and productivity for a better world TM Performance Service Centres ABB Performance Services Power and productivity for a better world TM The ABB difference ABB, a global leader in power and automation technologies, has five Performance Service

More information

TRADE EXPERIENCE LOG BOOK CANADIAN PETROLEUM CONTRACTORS ASSOCIATION. Petroleum Mechanic Training & Certification

TRADE EXPERIENCE LOG BOOK CANADIAN PETROLEUM CONTRACTORS ASSOCIATION. Petroleum Mechanic Training & Certification CANADIAN PETROLEUM CONTRACTORS ASSOCIATION Petroleum Mechanic Training & Certification TRADE EXPERIENCE LOG BOOK PM1 - Service & Maintenance PM2 - Underground Installation PM3 - Aboveground Installation

More information

In any of the 5 star hotels. The exact venue will be informed once finalized.

In any of the 5 star hotels. The exact venue will be informed once finalized. Training Title ELECTRIC DISTRIBUTION SYSTEM EQUIPMENT: Transformers, Switchgears, Circuit Breakers, Relays, Capacitors, Surge Arresters, Cables & Meters: Operation, Inspection, Testing, Evaluation, Maintenance

More information

Eilat, 11/2017. Cost Effective switchgear Modernization solutions

Eilat, 11/2017. Cost Effective switchgear Modernization solutions Eilat, 11/2017 Cost Effective switchgear Modernization solutions Asset upgrade Today s situation Aging of install base. Demands for Health & Safety Standards. Demands for improve quality of supply. Lose

More information

PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE

PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE Page 1 of 6 1. SUMMARY... 3 1.1 USE OF PORTABLE ELECTRICAL EQUIPMENT... 3 1.2 FAULTY EQUIPMENT... 3 2. PURPOSE & SCOPE... 3 3. DEFINITIONS... 3 3.1

More information

ELECTRICAL TECHNOLOGY 3 March 2008

ELECTRICAL TECHNOLOGY 3 March 2008 I. Course Description ELECTRICAL TECHNOLOGY 3 March 2008 The purpose for this course is to instruct potential electricians in the skills necessary for entry into the job market. During this course, the

More information

CrownSAFE Procedure. Electrical Safety CS-P Objective. 2. Scope. 3. Definitions

CrownSAFE Procedure. Electrical Safety CS-P Objective. 2. Scope. 3. Definitions 1. Objective To minimise the risk of injury to all Crown employees, contractors and visitors who conduct work on and use electrical plant, equipment, furniture and fittings. 2. Scope This procedure applies

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

Installation and Construction Notes for EVSE4

Installation and Construction Notes for EVSE4 Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process

More information

ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET Candidate Code No. ET54 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours

More information

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System

More information

ZX2 Gas-insulated medium voltage switchgear

ZX2 Gas-insulated medium voltage switchgear Gas-insulated medium voltage switchgear Double busbar 13 8 10 12 11 10 9 8 7 2 1 3 4 5 6 2 Versatile Partitioned single or double busbar system for all applications even with the most demanding parameters

More information

FUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1

FUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1 THE SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS FUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1 OVERVIEW : 1. Introduction to Distribution, Transmission and Generation

More information

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages

More information

Two Recent Case Studies in the Mining Industry

Two Recent Case Studies in the Mining Industry Two Recent Case Studies in the Mining Industry Remote Isolation Arc Flash Remediation David B. Durocher Senior Member, IEEE Global Industry Manager, Mining Eaton Corporation 26850 SW Kinsman Rd Wilsonville,

More information

MCset kv Medium voltage equipment

MCset kv Medium voltage equipment Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide

More information