Thermal Imaging Infrared Survey. Report. Report. Thermography Inspection at ABC Company.
|
|
- Matthew Thomas
- 5 years ago
- Views:
Transcription
1 Thermal Imaging Infrared Survey Report. Thermal Imaging Infrared Survey Report. Thermography Inspection at ABC Company. Vancouver,BC May 25, Rick Turdubay, Certified Infrared Investigator.
2 AiturGroup Ltd Thermal Imaging /Infrared Survey Report Sample. Thermography Inspection at (ABC Company). Address:.. By Rick Turdubay, Certified Infrared Investigator. May 25,2012 WEB: E:mail: Phone: Relationship to Standards Section National Master Specification (NMS) Thermographic Assessment Electrical Systems. Canadian General Standards Board, Document 149-GP-2MP, Manual for Thermographic Analysis of Building Enclosures.
3 How Infrared Thermography Works Infrared imagers see the heat radiated from your equipment in real time, just like a video camera sees visible light. In black/white thermograms (pictures of heat), white is hot and black is cold unless stated otherwise. When thermograms are in color, colors in the scene are matched to the reference bar. Colors appearing closer to the top or right of the reference bar indicate higher temperatures. Colors appearing closer to the bottom or left of the reference bar indicate lower temperatures. Inspection Site Information Customer Address Contact person Phone number address Thermographer Rick Turdubay, Flir Certificate # CON Information: Limited Liability, Errors& Omission. All conclusions and recommendations are based on the data taken at the time of the inspection and no guarantee regarding additional issues of any anomalies found as a result of any other source present or not present at the time of the investigation are made. It is client's responsibility to have the recommended 60% or more of a rated electrical load during the 3-4 hours before inspection. No one can predict when a failure will occur. As a result, we suggest that you use the Subjective Repair Priority Ratings as a guide but that you investigate and take appropriate corrective actions as soon as possible. Repair Priority Ratings Each thermogram is given a Subjective Repair Priority Rating which is based upon your qualified assistant s opinion of how critical the subject item is to the safe and profitable operation of your overall system. The Inspection Summary section of this report explains how to use this Subjective Repair Priority Rating to help you determine how quickly you need to investigate and correct the potential problem. Overheating can cause premature deterioration and costly, unplanned failure of your equipment. Overheating connectors, conductors and components will never get better. In fact, the temperature and rate of deterioration will increase with time. Overview of Fault Rating: 0: Normal Temp rise 0-5 C No action 1: Low grade Temp rise 5-10 C To be monitored Plan new inspection 2: Medium grade Temp rise C Repair at scheduled shut down 3: Severe Temp rise >35 C Repair immediately Doc # Page 2 of 13 May 25,2012
4 Summary of Inspection Fault Recommendation Page Number (Where) (What) ( ) () ABC Company, Pacific Centre 1., Panel A Incoming lugs: 120/208V 0 No action 4 2., Panel A Upper circuit breakers 2 Repair at scheduled shut down 5 3., Panel A Lower circuit breakers 2 Repair at scheduled shut down 6 4., Panel B Circuit breakers 0 No action 7 5., Panel B1 Circuit breakers 0 No action 8 6., Panel C Circuit breakers 0 No action 9 7., Panel D Circuit breakers 0 No action 10 8., Panel DP-6A 3 Phase breakers 0 No action 11 9., Panel Main Disconnect 3 Phase breaker 0 No action , Panel DP-2A 3 Phase breaker 2 Repair at scheduled shut down 13 Note: Most units electrical loads under 60% of rated load. Doc # Page 3 of 13 May 25,2012
5 Actual Load Fault Panel A,120/208V, 225A Incoming lugs:120/208v 225A Phases somewhat unbalanced at Phase: A=118A, Load %=52; B=101A, Load %=45; C=78A, Load %=35. Fault Rating: 0: Normal, Max. Temp =33.1, Min=29, 4; Tem. rise 0-5 C Emissivity= 0.95; Distance=1m Phases somewhat unbalanced at A=118A, Load %=52; B=101A, Load %=45; C=78A, Load %=35; Tem. rise=0-5 C This is considered a level 0: Normal; however, unbalanced phase loads should be monitored. Ideally, phase loads should be balanced. Inspected By: (Rick Turdubay) Signature: (25/05/2012) Doc # Page 4 of 13 May 25,2012
6 Panel A,120/208V, 225A Upper circuit breakers 20 A Actual Load CB # 4, Load= 16 A; Load %= 80 CB # 16, Load= 16, 6 A; Load %= 83. Fault Fault Rating: 2: Max. Temp =35.2, Min=32.7; Tem. rise 0-5 C, Emissivity= 0.95; Distance=1m CB# 4, Sp 1-2, Load= 16 A; Load %= 80; CB # 16, Sp.3-4 Load= 16, 6 A; Load %= 83. This might be considered a level 2, Repair at scheduled shut down. Since loads =80% and over contact your service company to plan a preventive action. Inspected By: (Rick Turdubay) Signature: (25/05/2012) Doc # Page 5 of 13 May 25,2012
7 Panel A,120/208V, 225A Lower circuit breakers 20 A Actual Load CB # 44,Load= 18 A; Load %= 90 CB# 46, Load= 16 A; Load %= 80 CB# 48, Load= 16 A; Load %= 80 Fault Fault Rating: 2: Max. Temp =41.7, Min=35; Tem. rise 6.7 C, Emissivity= 0.95; Distance=1m CB#44, Sp1-2, Load = 90%, Tem. Rise= 5; CB# 46, Sp3-4, Load %= 80. It seems the CB clip loosed, Tem. Rise =6.7 This might be considered a level 2, Repair at scheduled shut down. Since loads =90%; 80% and the CB#46 clip could be loosed contact your service company to plan a preventive action. Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 6 of 13 May 25,2012
8 Actual Load Fault Panel B,120/208V, Rated:200A Incoming lugs loads: A=114A, Load %=57 B=115A, Load %=57.5 C=125A, Load %=62.5 Circuit breakers 20 A Max. load on the Double-Pole Circuit Breaker CB #1 Load Pole 1= 8 A; Load %= 40 Load Pole 2= 13.6 A; Load %= 68 Fault Rating: 0: Normal Max. Temp =42.5, Min=38.6; Tem. rise 0-5 C, Emissivity= 0.95; Distance=1m Double pole CB#1, Sp1 Temp =42.5, Pole 2 Load = 68%, Tem. Rise= 3.9; Sp2, Load %= 40. It seems no action required. Fault Rating: 0: Normal Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 7 of 13 May 25,2012
9 Panel B1,120/208V, 200A Actual Load Circuit breakers 20 A Max. load on the CB #1,Load= 12.3A; Load %=61.5 Double-Pole Circuit Breaker #7 Load Pole 1= 9.6 A; Load %= 48 Load Pole 2= 10A; Load %= 50 Three Pole Circuit Breaker CB #24 Load Pole 1= 11.8 A; Load %= 58 Load Pole 2= 9.2 A; Load %= 46 Load Pole 3= 3.3 A; Load %= 17 Fault Fault Rating: 0: Max. Temp =42.5, Min=38, 6; Tem. rise 3.9 C, Emissivity= 0.95; Distance=1m Max. Load on the CB #1, Load= 12.3A; Load %=61.5. Fault Rating: 0: Normal Incoming lugs phases loads somewhat unbalanced at A=103A, Load %=51.5; B=73A, Load %=36.5; C=53A, Load %=26.5 Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 8 of 13 May 25,2012
10 Actual Load Panel C,120/208V, 200A Circuit breakers 20 A Max. load on the Double-Pole Circuit Breaker #30 Load Pole 1= 5.8 A; Load %= 29 Load Pole 2= 9.8A; Load %= 49 Fault Fault Rating: 0: Max. Temp =29.8, Min=27. 6; Tem. rise 0-5 C, Emissivity= 0.95; Distance=1m Max. load on the Double-Pole Circuit Breaker #30; Load Pole 1= 5.8 A; Load %= 29; Load Pole 2= 9.8A; Load %= 49 Incoming lugs phases loads: A=31A, Load %=15.5; B=39A, Load %=19.5; C=39A, Load %=19.5 Fault Rating: 0: Normal Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 9 of 13 May 25,2012
11 Actual Load Panel D,120/208V, 125A Circuit breakers 20 A Max. load on breakers up to 3A Load %= about 15 Fault Fault Rating: 0: Emissivity= 0.95; Distance=1m Max. load on breakers up to 3A; Load %= about 15 Incoming lugs phases loads: A=14A, Load %=11.2; B=4.7A, Load %=3.7; C=3.3A, Load %=2.6 Fault Rating: 0: Normal Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 10 of 13 May 25,2012
12 Panel DP-6A,600V, 400A 3 Phase breakers 225 A Actual Load Max. load on the breaker - 225KVA transformer. Phases somewhat unbalanced at Phase: A=105A, Load %=46.6; B=121A, Load %=53.7; C=112A, Load %=49.7. Fault Fault Rating: 0: Max. Temp =42.5, Min=41; Tem. rise 0-5 C, Emissivity= 0.95; Distance=1.6m Max. load on the breaker - 225KVA transformer. Phases somewhat unbalanced at phase: A=105A, Load %=46.6; B=121A, Load %=53.7; C=112A, Load %=49.7. Max. Temp =42.5 on the phase B since the load %=53.7 Fault Rating: 0: Normal Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 11 of 13 May 25,2012
13 Main Disconnect,600V, 400A Actual Load 3 Phase breakers 400 A Phases loads almost balanced at Phase: A=130A, Load %=32.5 B=142A, Load %=35.5 C=135A, Load %=33.7 Fault Fault Rating: 0: Max. Temp Phase B =37.2 Min=35.2; Tem. rise 0-5 C, Emissivity= 0.95; Distance=1.6m Phases loads almost balanced Phase: A=130A, Load %=32.5; B=142A, Load %=35.5 ; C=135A, Load %=33.7 Max. Temp Phase B =37.2 since the load %=35.5; Min Tem Phase B= 35.2; Tem. rise 0-5 C, Fault Rating: 0: Normal Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 12 of 13 May 25,2012
14 Panel DP-2A Actual Load 3 Phase breakers 200 A Max.load on the breaker Panel C Phases somewhat unbalanced at Phase: A=17A, Load %=8.5 B=9.5A, Load %=4.5 C=5.5A, Load %=2.5 Fault Fault Rating: 2: Max. Temp on the ph. A =39.8, Min=30.6; Tem. rise 9,2 C, Emissivity= 0.95; Distance=2m Max.load on the breaker which feeds the Panel C. Phases somewhat unbalanced at Phase: A=17A, Load %=8.5; B=9.5A, Load %=4.5; C=5.5A, Load %=2.5. Max. Temp on the phase A =39.8, Min=30.6; Tem. Rise= 9, 2 C, Load is too small to analyze. It seems the connection of the breaker Panel C, phase A is loosed. Tem. Rise=9, 2 C. This might be considered a level 2, Repair at scheduled shut down. Contact your service company to plan a preventive action. Inspected By: (Rick Turdubay) Signature: ((25/05/2012) Doc # Page 13 of 13 May 25,2012
INFRARED INSPECTION REPORT
REPORT February 13, 2015 Companies Unlimited 1401 Brand St. Los Angeles, CA 90028 Contact: Ron McKinney An Introduction to Infrared Inspection When installed correctly and operated within their ratings,
More informationSYSCO INDIANAPOLIS INDIANAPOLIS, INDINA
SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA November, 2017 Infrared Inspection Report Sysco Indianapolis LLC. 4000 West 62nd Street Indianapolis, Indiana, 46268 Company Contact: Trevor Gray Project: 05161117
More informationThermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:
Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: 27-10-2006 Reference Number: 2710061 Thermographer: John Crawford Thermal Imaging
More informationSIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS
SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS July, 2015 Infrared Inspection Report Sidewinder Drilling Company Contact Tommy Green Project: 02170715 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE:
More informationSYSCO OKLAHOMA LLC NORMAN, OKLAHOMA
SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA August, 2018 Infrared Inspection Report SYSCO Oklahoma LLC 1350 West Tecumseh Road Norman, Oklahoma, 73069 Company Contact Chris Hill Project: 03210818 2605 CHARTER
More informationBUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE
BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE July, 2015 Infrared Inspection Report Buzzi Unicem Terminal Company Contact Randy Miguez Project: 06220715 2605 CHARTER OAK DRIVE, LITTLE
More informationSIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS
SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS November, 2017 Infrared Inspection Report Sidewinder Drilling Rig 127 Pecan Acres 23 PSA 3-3H(WB) Company Contact Colton Chesney Project: 02201117 2605 CHARTER
More informationThermographic Inspection at SMALLVILLE DPW 123 ANY WAY SMALLVILLE, CA PETER PLEIN
191 BOULEVARD GLEN ROCK, NJ 07452 201-444 444-3620 Thermographic Inspection 123 ANY WAY SMALLVILLE, CA 01234 2006-04-25 By PETER PLEIN SAMPLE 1 (10) April 25, 2006 De: This is the in initial inspection
More informationTHERMOGRAPHY REPORT ELECTRICAL
LAMBERT CONDITION MONITORING LTD. CERTIFIED THERMOGRAPHER A.I.R. #12-01-243 THERMOGRAPHY REPORT ELECTRICAL Thermographic inspection at: Sample site Inspected by: David Lambert date: 20170701 Customer Sample
More informationSubstation inspection guidelines Mark B. Goff, P.E.
Substation inspection guidelines Mark B. Goff, P.E. Tennessee Valley Authority, Chattanooga, Tennessee ABSTRACT We need to better understand what our infrared camera is really showing us. Without guidelines,
More informationSYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA
SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA July, 2018 Infrared Inspection Report Sysco Central California 136 South Mariposa Road Modesto, California, 95393 Company Contact: Steve Handel Project: 04110718
More informationThermal Patterns Associated with Infrared Inspection of Electrical Systems
Thermal Patterns Associated with Infrared Inspection of Electrical Systems James Brady Level III Certified Infrared Thermographer Brady Infrared Inspections, Inc. 935 Pine Castle Court Stuart, FL 34996
More informationINFRARED THERMOGRAPHY:
INFRARED THERMOGRAPHY: X-treme Electrical can now also assist with infrared thermography of various electrical installations. Please take the time to review the following presentation for comprehensive
More informationSubstation Equipment (Bushings)
Substation Equipment (Bushings) Mark B. Goff, P.E. Tennessee Valley Authority ABSTRACT Bushings provide a point of interface such that electrical current can pass to and from an electrical apparatus. Much
More informationSYSCO RDC SOUTH ALACHUA, FLORIDA
SYSCO RDC SOUTH ALACHUA, FLORIDA July, 2018 Infrared Inspection Report Sysco RDC South 12421 NW 173rd Street Alachua, Florida, 32615 Company Contact: Natha Hall Project: 05110818 2605 CHARTER OAK DRIVE,
More informationFault Summary The following table is a summary of faults or items featured for your information
This document is an annotated sample of a report you receive. following our visit to your premises... We pride ourselves on the quality of the report and submit. this sample for your evaluation.. Report
More informationTransformer Protection
Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com
More information50 years experience in offering tailor made solutions to suit every customer s need.
Digital Brochure 50 years experience in offering tailor made solutions to suit every customer s need. Mages Group was established in 1960 by Mr William Mages and has since grown to become one of the South
More information750 kva Transformer V Delta Primary Voltage - 480Y/277 Wye-N Voltage Secondary - NEMA 3R
750 kva Transformer - 12470V Delta Primary Voltage - 480Y/277 Wye-N Voltage Secondary - NEMA 3R Part #: MT-PMD-3P-12470D-750KVA-480Y.277-N3R Page: 1 The MT-PMD-3P-12470D-750KVA-480Y.277-N3R 12470D 3 Phase
More information2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9
8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection
More informationPractical Thermography for Mechanical Applications Pub ITC 110 H Infrared Training Center
Practical Thermography for Mechanical Applications 2010-05-27 Pub ITC 110 H - 2010 Infrared Training Center 1 2010-05-27 Pub ITC 110 H - 2010 Infrared Training Center 2 Lesson Objectives Learn basics of
More informationUtilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications
G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...
More informationSolution Overview. Asset Condition Monitoring. Extend operational life and reduce downtime
Solution Overview Asset Condition Monitoring Extend operational life and reduce downtime QUALITROL Integrated Monitoring Server : Data Integration Diagram SMARTSUB Substation Condition Monitoring: Transformer
More information112.5 kva Transformer Delta Primary - 240/120V Secondary - 60 Hz - 3 Phase - NEMA 3R
112.5 kva Transformer 480 Delta Primary 240/120V Secondary 60 Hz 3 Phase NEMA 3R Part #: MT112.5KVA480240.1203P Page: 1 The MT112.5KVA480240.1203P 480D 3 Phase Energy Efficient isolation transformer from
More informationElectrical Existing Conditions and Building Load Summary Report
Electrical Existing Conditions and Building Load Summary Report Executive Summary: This Electrical Existing Conditions and Building Load Summary Report will describe the general and specific characteristics
More informationData Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?
Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0
More informationControl Circuit Protection
Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC
More informationC E R T I F I C A T E O F C O M P L I A N C E
Issued to: SIEMENS AG I IA CE CP R&D-VI 4 WERNER-VON-SIEMENS-STRASSE 48 92220 AMBERG, GERMANY This is to certify that representative samples of CIRCUIT BREAKERS, MOLDED-CASE AND CIRCUIT BREAKER ENCLOSURES
More informationAvid Electrical Services
Avid Electrical Services Thermal Imaging Report To: Mr A. Customer Your Business Australia Pty Ltd Fault Summary The following table is a summary of faults or items featured for your information Grading
More informationPega 345 Queen with 04PC Control Layout Drawings
Amada America Inc. 7025 Firestone Blvd. Buena Park CA. 90621 Phone: (714) 739 2111 Fax: (714) 739 4099 Email info@amada.com Print Date 03/01/2001 Revision 4.0 This document available on the World Wide
More informationIntersel Dowding and Mills FZCO Company Profile - Aug 2015
Intersel Dowding and Mills FZCO Company Profile - Aug 2015 About Intersel Dowding & Mills Established in 1986, Intersel Dowding and Mills has grown into the leading repair specialist in the Gulf Region
More informationATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A
Transfer switches The solution for > Genset < 90 kva > Heating systems > Climate control > Ventilation systems > Telecommunications atys-s_018_a Strong points Function products are 4 pole remotely operated
More informationFuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.
Fuseology Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression Optima Fuse Holders & Overcurrent Protection Modules Compact, full-featured modules that deliver Type 2 coordinated protection,
More informationB BASIC HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationProtection Equipment. 5/2 Introduction
Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1
More informationAGN Single Phase Loading for Re- Connectable 3-Phase Windings
Application Guidance Notes: Technical Information from Cummins Alternator Technologies AGN 154 - Single Phase Loading for Re- Connectable 3-Phase Windings TECHNICAL OVERVIEW It must be accepted; when reconnecting
More informationFile E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised:
File E47705 Vol. 7 Sec. 9 Page 1 Issued: 1997-08-29 and Report Revised: 2005-06-30 DESCRIPTION PRODUCT COVERED: USL, CNL - Type Nos. 3RV1021, 3RV1121, 3RV1321 or 3RV1421, followed by combination of 0,
More informationFlue Gas Analyzer IMR 1100F
Flue Gas Analyzer IMR Environmental Equipment. Inc. 3634 Central Ave. St. Petersburg Florida 33711 Tel: 727-328-2818 Fax 727-328-2826 info@imrusa.com www.imrusa.com User Manual INTRODUCTION 3 SAFETY INSTRUCTIONS
More informationP80074 (150 amp connectors) P80071 (300 amp connectors)
Overview: The Restore-Lite Temporary Power Restoration System is a compact mobile transformer unit that contains a single-phase, floating-tap transformer designed to restore power to customers who have
More information1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled
1500 kva Pad Mount Transformer - 24940GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled Part #: MT-PMO-3P-24940GRDY.14400-1500KVA-208Y.120-N3R Page: 1 The MT-PMO-3P-24940GRDY.14400-1500KVA-208Y.120-N3R
More informationOriginal Manual 2CCC444010M0201 Rev. 1.0, Date of Release: 02/2016. Remote Power Panel Assembly instructions
Original Manual 2CCC444010M0201 Rev. 1.0, Date of Release: 02/2016 Remote Power Panel Assembly instructions Table of contents Unpacking and checking the cabinet Visual control of the packaging 3 Unpacking
More informationApplication Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80
Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Motor settings using the SIPROTEC Compact motor protection relay 7SK80 is explained below. Information is given on how to
More informationV. Design, Application, Maintenance & Operation Technical Requirements
V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented
More informationDSPS DSPS. Wide DC input. Switching Power Supply. Models: ESA-DS160 ESA-DS200. ESA-DS Ver.1.01 PAGE: 1 OF 7
Wide DC input Switching Power Supply Models: ESA-DS160 ESA-DS200 ESA-DS Ver.1.01 PAGE: 1 OF 7 TABLE OF CONTENTS 1. INPUT... 3 1.1. DC INPUT... 3 2. DC OUTPUT - RATED (MAX)... 3 2.1. REGULATION... 3 2.2.
More informationSelective Coordination
Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings
More informationSwitch Base Replacement Instructions 3-Pole, 60 AMP, Fusible, w Neutral, Visible-Blade, Heavy Duty Safety Switches
Step Switch Base Replacement Instructions 3-Pole, 60 AMP, Fusible, w Neutral, Visible-Blade, Heavy Duty Safety Switches Work Description All work should be performed in accordance with NFPA 70E. Tools
More informationMagnetism Magnets: Types and Uses
Non-fiction: Magnetism Magnets: Types and Uses Magnetism Magnets: Types and Uses Magnets come in a wide variety with an equally wide variety of uses. The most common are bars or disks. Because they stick
More informationIndustrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw
Industrial Generator Set Accessories Line Circuit Breakers 15-2500 kw Standard Features Single Circuit Breaker Kit with Neutral Bus Bar 15-300 kw Model Shown The line circuit breaker interrupts the generator
More information3 - Protection components Motor circuit-breakers
Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page
More informationANZI Transfer Switch and Generator Wiring Installation Addendum
ANZI Transfer Switch and Generator Wiring Installation Addendum Reference all appropriate documentation. NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS. THIS PRODUCT CAN BE INSTALLED BY THE
More informationPOWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012
POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORT WEST TASMANIA ON 6 APRIL 2012 PREPARED BY: Systems Capability DATE: 28 September 2012 FINAL IN NORT WEST TASMANIA ON 6 APRIL 2012
More informationOrder No. of the options EMC filter Class A
Ordering Data for Variant Dependent Options The options listed here (filters, chokes, brake resistors, gland plates, fuses and circuit breakers) are inverter specific. The inverter and the associated options
More informationCalculation of the Cross-sectional Areas of Circuit Live Conductors
Calculation of the Cross-sectional Areas of Circuit Live Conductors MOTOR CIRCUITS SUBJECT TO FREQUENT STOPPING AND STARTING Regulations requires that where a motor is intended for intermittent duty and
More informationHigh Voltage Electrical Maintenance Training
High Voltage Electrical Maintenance Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq High Voltage Electrical
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More informationTrellex Conveyor Belt Guiding System. Conveyor Components
Trellex Conveyor Belt Guiding System Conveyor Components www.metsominerals.com Trellex Belt Conductor provides automated supervision of conveyor belt centring thus relieving the staff of much of the time-consuming
More informationELECTRIC BENDING IRON
ELECTRIC BENDING IRON This is intended as a short pictorial essay on the construction of an electrical side bending iron. As the items used may vary from the ones shown here, only limited dimensions are
More informationV 2.0 DC TO AC POWER INVERTER PWRINV500012W PWRINV500024W PWRINV500036W PWRINV500048W. Instruction Manual
DC TO AC POWER INVERTER PWRINV500012W PWRINV500024W PWRINV500036W PWRINV500048W Instruction Manual Introduction The AIMS Power 5000 Watt series inverters are the most advanced line of mobile DC to AC power
More informationRE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW
Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient
More information- 4 amp (100VA). - 4 amp (100VA). - Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
ALTV248 Series CCTV Power Supplies Installation Guide Models Include: ALTV248 ALTV248CB - @ 4 amp (100VA). - @ 4 amp (100VA). or @ 3.5 amp. or @ 3.5 amp. - Eight (8) Fuse Protected s. - Eight (8) PTC Protected
More information75 kva Transformer - 208V Delta Primary Voltage - 480V Delta Secondary Voltage - NEMA 3R
75 kva Transformer 208V Delta Primary Voltage 480V Delta Secondary Voltage NEMA 3R Part #: MTATX3P208D75KVA480DN3R Page: 1 The MTATX3P208D75KVA480DN3R 208D 3 Phase Energy Efficient Transformer from Larson
More informationUnit Protection System for Pumped-Storage Power Stations
Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve
More informationARCO Electric Products Ph. (317) Bulletin MI0703 8/1/2013
ARCO Electric Products Ph. (317) 398-9713 www.arco-electric.com Bulletin MI0703 8/1/2013 INSPECTION Upon receiving the Roto-Phase, inspect for damage or missing parts and report such losses to the carriers
More information30kVA Transformer - 3 Phase Delta Primary - 380Y/220 or 400Y/230 Secondary - NEMA 3R
30kVA Transformer 3 Phase 480 Delta Primary 380Y/220 or 400Y/230 Secondary NEMA 3R Part #: MT480D30KVA380.400V Page: 1 The MT480D30KVA380.400V 480V 3 Phase Energy Efficient transformer from Larson Electronics
More informationContinuing Education Course #206 Introduction to Designing Machine Control Systems Part 2
1 of 5 Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1. Continuing to answer the following questions indicates that you understands that the presented material
More informationH. J. Arnett Industries, LLC SW Avery Court Tualatin, OR 97062
H. J. Arnett Industries, LLC 20460 SW Avery Court Tualatin, OR 97062 Phone: 503-692-4600 Fax: 503-692-4661 Toll free: 800-684-9844 Web address: www.arnettindustries.com USE OF THE MEGA BEAST SERVICE CONDUCTOR
More informationInverter / Charger Accessory for Steca Solarix PLI Phase / Parallel Kit. Installation and operating instructions Z01 17.
Inverter / Charger Accessory for Steca Solarix PLI 5000-48 3-Phase / Parallel Kit Installation and operating instructions GB Z01 17.31 Table of Contents About this Manual... 2 Purpose... 2 Scope... 2 Keywords
More information- 4 amp (100VA). - 4 amp (100VA). - Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
ALTV248 Series CCTV Power Supplies Installation Guide Models Include: ALTV248 ALTV248CB - @ 4 amp (100VA). - @ 4 amp (100VA). ALTV248175 ALTV248175CB - @ 7.25 amp (175VA). - @ 7.25 amp (175VA). or @ 6.25
More informationFile E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany
File E47705 Project 97ME18400 August 21, 1997 REPORT on MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany Copyright 1997 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above
More informationATyS t M - ATyS g M Automatic Transfer Switching Equipment from 40 to 160 A
TyS t M - TyS g M utomatic Transfer Switching Equipment Transfer switches new The solution for > High Rise uildings > Data centre > Healthcare buildings TyS g M I-0-II P atys-mg_001_b_1_cat Function TyS
More informationINTELLIGENT MEDIUM POWERBAR
INTELLIGENT MEDIUM POWERBAR POWERBAR INTRODUCTION TECHNICAL FEATURES Intelligent Medium Powerbar is a patented range of busbar trunking that is utilized within Data Centers and various industrial applications
More information- 4 amp. - 4 amp. - Sixteen (16) Fuse Protected - Sixteen (16) PTC Protected
Rack Mount Series CCTV Power Supplies Installation Guide Models Include: R615DC416 R615DC416CB - 6-15VDC @ 4 amp. - 6-15VDC @ 4 amp. R615DC616 R615DC616CB - 6-15VDC @ 6 amp. - 6-15VDC @ 6 amp. R615DC1016
More informationNew Demag DR-Bas rope hoist. Now up to. 50t. The right choice. High quality and excellent value
New Demag DR-Bas rope hoist Now up to 50t The right choice High quality and excellent value Demag DR-Bas rope hoist Are you looking for a reliable, high-performing and compact rope hoist with a lifting
More informationATyS. 63 to 3200 A. Functions. Conformity to standards. General characteristics. Changeover switches. Functions
to 00 A Accessories Enclosed Characteristics M e atysm_007_a cat M s atysm_0_a cat products are and 4pole switches remotely controlled by volt free contacts ( ) or automatic transfer switches ( ). They
More informationOil Palm Ripeness Detector (OPRID) and Non-Destructive Thermal Method of Palm Oil Quality Estimation
Oil Palm Ripeness Detector (OPRID) and Non-Destructive Thermal Method of Palm Oil Quality Estimation Abdul Rashid Mohamed Shariff, Shahrzad Zolfagharnassab, Alhadi Aiad H. Ben Dayaf, Goh Jia Quan, Adel
More informationBattery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.
More informationThe Shocking Truth About Electrical Safety Teacher s Guide
The Shocking Truth About Electrical Safety Teacher s Guide FOUR SIMPLE CONCEPTS ABOUT ELECTRICAL SAFETY 1. Electricity travels in a closed loop called a circuit. 2. Electricity flows easily through conductors,
More informationMonicon Instruments Co., Ltd. CHR-1285/2485 CHR-1285/2485 BATTERY CHARGER
CHR-1285/2485 BATTERY CHARGER TEL:886-4-2238-0698 FAX:886-4-2238-0891 Web Site:http://www.monicon.com.tw E-mail:sales@monicon.com.tw Copyright 2007 Monicon Instruments Co., Ltd. All right reserved. Contents
More informationMiniature Circuit Breaker
Introduction - Miniature Circuit Breaker (MCB) SALIENT FEATURES SALIENT FEATURES Standards MCBs conform to the latest standard IS 8828: 1996/IEC: 898 1995 Mid-Trip Position The Mid trip position of the
More informationTWO TECHNOLOGIES, ONE SOLUTION
TWO TECHNOLOGIES, ONE SOLUTION two technologies, one solution The smart transformer has arrived, combining two proven technologies in one revolutionary package. To save you more. The Bowers Intellivolt
More informationJoseph Lookup Senior Thesis 2005 Wegmans Fairfax. Section 2.0. Electrical Depth
Section 2.0 Electrical Depth 2.0 Electrical Depth 2.1 Introduction The electrical distribution system was analyzed to determine if any improvements could be made, to analyze its capabilities, to verify
More informationMobile Power Distribution Center - Input 240D/120V 200A - Output (8) 120v GFCI & (2) 240V Outlets
Mobile Power Distribution Center - Input 240D/120V 200A - Output (8) 120v GFCI & (2) 240V Outlets Part #: MDC-240-200MB-8X120-2X240 Made in the USA The Larson Electronics MDC-240-200MB-8X120-2X240 Mobile
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More information112.5 kva Isolation Transformer - 440V Delta Primary - 110V Delta Secondary - NEMA 3R
112.5 kva Isolation Transformer 440V Delta Primary 110V Delta Secondary NEMA 3R Part #: MTISX3P440D112.5KVA110DN3R Page: 1 The MTISX3P440D112.5KVA110DN3R 440 V Delta 3 Phase Energy Efficient Distribution
More informationDOC / SQUARE D BREAKER BOX HINGES DOWNLOAD
13 June, 2018 DOC / SQUARE D BREAKER BOX HINGES DOWNLOAD Document Filetype: PDF 224.03 KB 0 DOC / SQUARE D BREAKER BOX HINGES DOWNLOAD New in box Square D Thermal Magnetic Circuit Breaker FAL34020 Series.
More informationUL Listed CCTV Power Supplies. - 4 amp. - 4 amp. - Eight (8) Fuse Protected - Eight (8) PTC Protected
Rack Mount Series UL Listed CCTV Power Supplies Installation Guide Models Include: R615DC8UL R615DC8ULCB - 6-15VDC @ 4 amp. - 6-15VDC @ 4 amp. - Eight (8) Fuse Protected - Eight (8) PTC Protected R615DC416UL
More informationMAINTENANCE TESTING SPECIFICATIONS
MTS-2001 Appendix B Frequency of Maintenance Tests MAINTENANCE SPECIFICATIONS FOR POWER DISTRIBUTION EQUIPMENT AND SYSTEMS InterNational Electrical Testing Association Inc. Quality Since 1972 Copyright
More informationLenze Gearmotor Product Warning (Verification of Ground Connectivity)
Issued by Responsible Phone / Email Date DCUS/ETC-MT Paul Zielbauer 269-697-5300 12/19/11 paul.zielbauer@boschrexroth-us.com Material and information flow technology Lenze Gearmotor Product Warning (Verification
More informationHI-LOW-HI MOTOR STARTING AN APPROACH FOR STARTING DEEP WELL SUBMERSIBLE PUMPS
ABSTRACT HI-LOW-HI MOTOR STARTING AN APPROACH FOR STARTING DEEP WELL SUBMERSIBLE PUMPS Scott Honeyfield, P.E. Marcelino N. Trujillo, P.E. Parkhill, Smith & Cooper Inc. 501 W. San Antonio El Paso, Texas
More informationCamouflaging Vehicles Using Field Expedient Materials, Commercial Hardware Store Materials, Camouflage Nets, and Rubber Conveyer Belt Material
Hardware Store Materials, Camouflage Nets, and Rubber Conveyer Belt Material Joseph W. Papa, George A. Fahlsing US Army Research Development and Engineering Command CERDEC NVESD Fort Belvoir, Virginia
More informationCondition Monitoring in Low Voltage Circuit Breaker Technology
Condition Monitoring in Low Voltage Circuit Breaker Technology Tom Craig B.Eng (Hons) MIET Terasaki Electric (Europe) Ltd., UK 80 Beardmore Way, Clydebank Industrial Estate, Glasgow G81 4HT, SCOTLAND tom.craig@terasaki.co.uk
More informationC E R T I F I C A T E O F C O M P L I A N C E
1512 E47705 Report Reference E4770519970821 15OCTOBER12 Issued to: SIEMENS AG DF CP R&D V 3 WERNERVONSIEMENSSTRASSE 48 9 AMBERG GERMANY This is to certify that representative samples of MOTOR CONTROLLERS,
More informationABB Services for Low Voltage equipment Your choice, your future
ABB Services for Low Voltage equipment Your choice, your future You choose, we respond. Globally. The future of your equipment depends on the service you choose Whatever you choose, it should be a well-informed
More informationAttention: NEON. **Read on... Installers - Designers - Assemblers
Attention: NEON Installers - Designers - Assemblers How to improve installation reliablity of UL 2161 transformers and reduce installation problems **Read on... 3490 Venture Drive, San Angelo, TX 76905
More informationALLMAC Electrical Eng. 61 (0) Advanced Infrared +61 (0) BES (Aust) Pty Ltd AUSTPTA
page 1a ABB Australia 1800 222 435 Advanced Infrared +61 (0)425 758 820 ALLMAC Electrical Eng. 61 (0)419 819 756 Ampcontrol 1300 267 373 AUSTPTA www.austpta.asn.au BES (Aust) Pty Ltd 61 2 9686 4811 Products/
More informationATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A
ATyS d M Remotely operated Transfer Switching Equipment Transfer switches new The solution for > Applications with an external ATS/AMF controller > Building Management Systems (BMS) atys-md_002_b_1_cat
More informationOptimizing Emergency Power Systems for Health Care Applications
2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan
More informationUltra Fast Earthing Switch UFES retrofit Overview
Gordon van der Linde ABB PTMV - Service Ultra Fast Earthing Switch UFES retrofit Overview May 20, 2013 UFES Slide 1 Ultra Fast Earthing Switch UFES retrofit Content 1. Effects of an internal arc 2. The
More informationArt. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2
SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2 DESCRIPTION AND FEATURES... 3 CHARGING STAGES... 4 Art. No. EC-315 Art. No. EC-330 Art. No. EC-340 PROTECTIONS... 5 INSTALLATION...
More informationPOWER SYSTEM OPERATING INCIDENT REPORT TRIPS OF YALLOURN W POWER STATION UNITS W1 AND W3 ON 14 NOVEMBER 2012
POWER SYSTEM OPERATING INCIDENT REPORT TRIPS OF YALLOURN W POWER STATION UNITS W1 AND W3 ON 14 NOVEMBER 2012 PREPARED BY: System Performance and Commercial DATE: 7 March 2013 FINAL Disclaimer Purpose This
More information