BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE
|
|
- Shannon Hines
- 5 years ago
- Views:
Transcription
1 BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE July, 2015 Infrared Inspection Report Buzzi Unicem Terminal Company Contact Randy Miguez Project: CHARTER OAK DRIVE, LITTLE ROCK, AR PHONE: & FAX: Logistics@usscanman.com
2 ORDER OF REPORT CONTENTS 1: Data To Facilitate Understanding & Utilizing Scan Report 2: Scan Results Overview & Action Taken Form 3: Identified Faulting Conditions, Information & Photographs 4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found DISCLAIMER This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not intended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility s condition, maintenance practices or correction of conditions indicated herein. By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, concerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.
3 Utilizing Report Contents Included in this report are Photographs and Thermographs of problem areas found during our recent Infrared Inspection of your facility. Each problem area picture is accompanied by: Date Location Information Temperature Calculations Color-coded Temperature Intensity and/or Condition Significance Data A Brief Comment Relating The Item In The Photograph To Its Corresponding Thermograph Suggested Corrective Recommendations. In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity. Thermal intensity is indicated by use of a color-coded data inserts that locate a fault s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows: INSERT Red Orange Yellow Green Temperature Range 70ºC/126ºF and higher above Ambient Operating Temp. 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp. 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp. *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp. ( * See page 4)
4 Determining Cost Effective Responses Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate. Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports. STANDARD ELECTRICAL FAULT FAILURE CURVE (Does Not Include Area In Blue) MINOR INTERMEDIATE SERIOUS CRITICAL DEVICE TEMP IS AMBIENT, BUT DEVICE IS EITHER FAULTY OR UNSAFE. 10ºC * 18ºF 25ºC 45ºF 40 C 72ºF 70 C 126ºF AMBIENT TEMP YEARS MONTHS MONTHS TO WEEKS WEEKS TO NOW FAULTY EQUIP Built In Trend Monitoring When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings. If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.
5 Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use Total Temperature: Total Temperature = Ambient Operating Temperature + Fault temperature Allows you, the customer, to evaluate possible damage to equipment. Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating. Contacts start to fail around 130ºC/266ºF Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes: Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet. If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault. Allows you, the customer, to determine if device will operate at intended amperage. Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine) If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip. 1. An intermittent high load. 2. A minor (Green) or intermediate (Yellow) fault. Report pages with photographs: PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph * AOT stands for Ambient Operating Temperature Both black & white and color infrared thermographs are presented to better depict the fault condition.
6 In addition to the corrective response time frame suggested below and the failure curve located on the previous page, you may want to consider using the military standard responses presented below. Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment: Temperatures rise above Ambient Operating Temperature: *10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label) 25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label) 40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected. (Orange Label) 70ºC/126ºF and above component failure imminent. Immediately inform the person responsi ble for continued operation of equipment. (Red Label) Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions. * Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind. Fault Correction Recommendation When Our Source Assessment Is Inaccurate: When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist. The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located. Example: If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp. in the lead holder lug.
7 SCAN RESULTS OVERVIEW PROMPT ATTENTION ITEMS: Because of: 1. The intensity or heat level indicated at the time of the scan. 2. Deterioration caused by excessive temperature not present at the time of the scan. 3. Physical condition irregularities observed at the time of the scan. We recommend that the following faults be given prompt attention: Faults: #1 Items With Asterisks Have High Total or Ambient Operating Temperatures. United Spectrographics July, 2015
8 SUMMARY OF FINDINGS FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO. MINOR 0 0 INTERMEDIATE 3 2/91, 3/40, 4/39 SERIOUS 1 1/92 CRITICAL 0 0 SERIOUS 0 0 Number of items located at facility: 92 Number of faults: 4
9 ACTION TAKEN Buzzi Unicem Terminal Memphis, Tennessee July, 2015 Fault # Item # Category Repaired Monitor Date Name 1 92 Serious 2 91 Intermediate 3 40 Intermediate 4 39 Intermediate
10 PROJECT: CUST REP: Al Williams SCAN REP: Brett Harris DATE: July 22, 2015 LOCATION: 1509 Barge Box Labeled: Bow / Aft Manual Transfer Switch Disconnect Labeled: Aft (Bottom Disconnect) PH # 1 > ITEM: SOURCE: TEMP: Bø of Disconnect Line and load side disconnect blade contact area. Temp. of contact areas range to: 109ºC / 228ºF Total Temp - 41ºC / 106ºF AOT = 68ºC / 122ºF above AOT. TH # 1 > COMMENTS TH # 1 > Abnormal heat is being generated in disconnect components. See orange arrows in PH#1 and TH#1. Loose and/or corroded contact areas. Clean, inspect and re-secure serviceable components. TEMPERATURE ABOVE AOT 68 C / 122 F
11 PROJECT: CUST REP: SCAN REP: Al Williams Brett Harris DATE: July 22, 2015 LOCATION: 1509 Barge Box For: 15 kva Transformer Left Transformer Coil < PH # 2 ITEM: SOURCE: TEMP: Coil Top Tap Jumper Connection Lead connection lug. Temp. of connection and lug is: 65ºC / 149ºF Total Temp. - 40ºC / 104ºF AOT = 25ºC / 45ºF above AOT. < TH # 2 < TH # 2 COMMENTS Abnormal heat is being generated in transformer connection. See yellow arrows in PH#2 and TH#2. Loose and/or corroded contact area. Clean, inspect and re-secure. TEMPERATURE ABOVE AOT 25 C / 45 F
12 PROJECT: CUST REP: Al Williams SCAN REP: Brett Harris DATE: July 22, 2015 LOCATION: Compressor House Control Cabinet Labeled: Cooling System #1 / #2 (Right Side Of Cabinet) 3ø Fused Circuit For: Water Pump 1 PH # 3 > ITEM: SOURCE: TEMP: Aø Fuse Block Load side fuse clip. Temp. of fuse clip is: 64ºC / 147ºF Total Temp. - 39ºC / 102ºF AOT = 25ºC / 47ºF above AOT. TH # 3 > COMMENTS Abnormal heat is being generated in fuse block component See yellow arrows in PH#3 and TH#3. TH # 3 > Loose and/or corroded contact area. Clean, inspect and re-secure. TEMPERATURE ABOVE AOT 25 C / 47 F
13 PROJECT: CUST REP: SCAN REP: Al Williams Brett Harris DATE: July 22, 2015 LOCATION: Compressor House Box Labeled: Exhaust Fan Disconnect Combination Starter < PH # 4 ITEM: SOURCE: TEMP: Aø of Molded Case Breaker Line side lead connection lug. Temp. of connection and lug is: 65ºC / 149ºF Total Temp. - 36ºC / 102ºF AOT = 29ºC / 47ºF above AOT. < TH # 4 < TH # 4 COMMENTS Abnormal heat is being generated in case breaker connection. See yellow arrows in PH#4 and TH#4. Loose and/or corroded contact area. Clean, inspect and re-secure. TEMPERATURE ABOVE AOT 29 C / 47 F
14 AREA/EQUIPMENT LIST Following is a list of the electrical equipment located at the Buzzi Unicem USA, President s Island Terminal, Memphis, TN, facility and data relating to its operating condition at the time the scan was performed. NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection. No. Equipment Oper. Visually Inspected SILOS AREA Fault # MCC ROOM 1 A Panel 208/120 Volt Distribution Panel X 2 Receiving Lights Breaker Panel X 3 Lighting Contactor X 4 Pit Heaters 480 Volt Distribution Panel X 5 45 KVA Westinghouse 3ø Transformer (Overhead) X 6 MCC X OUTSIDE 7 Distribution Panel 480 Volt Distribution Panel X 8 Pad Mounted Transformer X TRUCK LOADING AREA 9 Leroi Air Compressor Control Cabinet X 10 Leroi Air Compressor Fuse Disconnect X 11 Air Dryer Fuse Disconnect X 12 No. 5 Blower Disconnect X BLOWER ROOM 13 Blower #1 Disconnect X 14 Blower #2 Disconnect X 15 Blower #3 Disconnect X 16 Blower #4 Disconnect X UNDER SILO #5 17 North Air Compressor Control Cabinet X 18 South Air Compressor Control Cabinet X 19 North & South Air Compressor Transfer Switch Cannot Open Under Load
15 No. Equipment Oper. Visually Inspected 2 ND FLOOR ABOVE TRUCK SCALES Fault # 20 Rail Dust Collector Disconnect X 21 Rail Spout / Dust Collector Control Cabinet X ROOF OF SILOS 22 East Dust Collector Disconnect X 23 West Dust Collector Disconnect X 24 Unlabeled 120 Volt Distribution Panel X WAREHOUSE WEST WALL 25 LTP Amp Molded Case Breaker X 26 LTP No /120 Volt Distribution Panel X 27 LTP No Volt Distribution Panel X 28 LTP No. 47 Breaker Panel X 29 Overhead Westinghouse 3ø Transformer X BREAK ROOM 30 LTP No Volt Distribution Panel X SUBSTATION 31 Pad Mounted Transformer X 32 Riser Pole w/ (3) Fuse Disconnects X COMPRESSOR HOUSE EXTERIOR 33 #2 Radiator Disconnect X 34 #2 Water Pump Disconnect X 35 #1 Water Pump Disconnect X 36 #1 Radiator Disconnect X INTERIOR 37 Compressor Control Cabinet X 38 East Exhaust Fan Motor Control X 39 Exhaust Fan LTP No. 61 Combination Starter X 4
16 No. Equipment Oper. Visually Inspected 40 Cooling System Control Cabinet X 3 41 LTP No Volt Distribution Panel X 42 LTP No /120 Volt Distribution Panel X 43 Receptacle Fuse Disconnect X 44 Cooling Fan #2 Motor Control X 45 Cooling Fan #1 Motor Control X Switchgear Cannot Open Under Load 47 Exhaust Fan Disconnect (Left) X 48 Exhaust Fan Disconnect (Right) X 49 Compressor #1 Motor Leads X 50 Compressor #2 Motor Leads X CAPTIVE BARGE MCC AREA 51 Panel LP03 208/120 Volt Distribution Panel X kva Transformer X 53 Air Compressor Control Cabinet X MCC 54 Main Breaker Captive Barge MCC 2 X 55 AC02 High Pressure Air Compressor X 56 West Capstan X 57 DF Barge Dust Collector Fan X 58 LP03 Captive Barge X 59 SP Utility Power X 60 East Capstan X 61 BL05 Captive Barge Air Slide Blower X Fuseblock Fed By SP1 X 63 PU Barge Cement Pump X 64 BF Barge Unloading X 65 Weld Receptacle Captive Barge X 66 HT04 Captive Barge ER Heater X Fault #
17 No. Equipment Oper. Visually Inspected 67 HT05 Captive Barge Comp. Room Heater X Fault # 68 West Crane Locked Out 69 East Crane Locked Out 70 Coastal Crane X 71 Spare X 72 Spare X 73 Spare X 74 Spare X 75 Spare X VACUUM SIDE 76 #3829 Pad Mounted 750 KVA Transformer X 77 T1 Fuse Disconnect X 78 Air Compressor Fuse Disconnect X 79 T1 208/120 Volt Distribution Panel X 80 T2 Fuse Disconnect X 81 Air Compressor Control Cabinet X 82 Vacuum Pump Motor Leads X 83 Hydraulic Pump Motor Leads X 84 Cement Pump Motor Leads X 85 Hydraulic Crane Combination Starter X 86 T-2 480/277 Volt Distribution Panel X CONTROL BUILDING 87 Breaker Box 208/120 Volt Distribution Panel X 88 Nozzle Hydraulic Unit Disconnect Locked Out KVA Hevi-Duty 3ø Transformer X 1509 BARGE Volt Distribution Panel X kva Transformer X 2 92 Bow / Aft Manual Transfer Switch X 1
SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS
SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS July, 2015 Infrared Inspection Report Sidewinder Drilling Company Contact Tommy Green Project: 02170715 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE:
More informationSYSCO INDIANAPOLIS INDIANAPOLIS, INDINA
SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA November, 2017 Infrared Inspection Report Sysco Indianapolis LLC. 4000 West 62nd Street Indianapolis, Indiana, 46268 Company Contact: Trevor Gray Project: 05161117
More informationSYSCO OKLAHOMA LLC NORMAN, OKLAHOMA
SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA August, 2018 Infrared Inspection Report SYSCO Oklahoma LLC 1350 West Tecumseh Road Norman, Oklahoma, 73069 Company Contact Chris Hill Project: 03210818 2605 CHARTER
More informationSYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA
SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA July, 2018 Infrared Inspection Report Sysco Central California 136 South Mariposa Road Modesto, California, 95393 Company Contact: Steve Handel Project: 04110718
More informationSIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS
SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS November, 2017 Infrared Inspection Report Sidewinder Drilling Rig 127 Pecan Acres 23 PSA 3-3H(WB) Company Contact Colton Chesney Project: 02201117 2605 CHARTER
More informationSYSCO RDC SOUTH ALACHUA, FLORIDA
SYSCO RDC SOUTH ALACHUA, FLORIDA July, 2018 Infrared Inspection Report Sysco RDC South 12421 NW 173rd Street Alachua, Florida, 32615 Company Contact: Natha Hall Project: 05110818 2605 CHARTER OAK DRIVE,
More informationFault Summary The following table is a summary of faults or items featured for your information
This document is an annotated sample of a report you receive. following our visit to your premises... We pride ourselves on the quality of the report and submit. this sample for your evaluation.. Report
More informationCompany Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI
Company Name City, State Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI 54476-0740 April 9, 2012 (Customer Name & Address) Attn: Customer Enclosed is a report on the
More informationThermal Imaging Infrared Survey. Report. Report. Thermography Inspection at ABC Company.
Thermal Imaging Infrared Survey Report. Thermal Imaging Infrared Survey Report. Thermography Inspection at ABC Company. Vancouver,BC May 25,2012 www.aiturgroup.com info@aiturgroup.com Rick Turdubay, Certified
More informationB BASIC HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More information2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9
8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection
More informationThermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:
Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: 27-10-2006 Reference Number: 2710061 Thermographer: John Crawford Thermal Imaging
More informationSubstation inspection guidelines Mark B. Goff, P.E.
Substation inspection guidelines Mark B. Goff, P.E. Tennessee Valley Authority, Chattanooga, Tennessee ABSTRACT We need to better understand what our infrared camera is really showing us. Without guidelines,
More informationSM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety
SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com
More informationThermographic Inspection at SMALLVILLE DPW 123 ANY WAY SMALLVILLE, CA PETER PLEIN
191 BOULEVARD GLEN ROCK, NJ 07452 201-444 444-3620 Thermographic Inspection 123 ANY WAY SMALLVILLE, CA 01234 2006-04-25 By PETER PLEIN SAMPLE 1 (10) April 25, 2006 De: This is the in initial inspection
More informationTHERMOGRAPHY REPORT ELECTRICAL
LAMBERT CONDITION MONITORING LTD. CERTIFIED THERMOGRAPHER A.I.R. #12-01-243 THERMOGRAPHY REPORT ELECTRICAL Thermographic inspection at: Sample site Inspected by: David Lambert date: 20170701 Customer Sample
More informationmodel ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION
MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.
More informationINSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS
INSTALLATION INSTRUCTIONS FOR EGA AND EGH SERIES ELECTRIC HEATERS IN V OR H SERIES UNITS NOTE TO INSTALLER The words SHALL and MUST indicate a requirement which is essential to satisfactory and safe product
More informationB-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE
B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE Duty B: Power Distribution (600V and below) B-03: Troubleshoot 480V System Issued 06/01/98 Task Preview Troubleshoot 480V System The 480V distribution
More informationPARTS CATALOG MODEL FBD352 DISPENSER
FBD Partnership, LP P.O. BOX 897 SAN ANTONIO, TX 788 USA 0-67-800 FAX 0-67-8 www.fbdfrozen.com FBD TECHNICAL SUPPORT -866--777 TECHNICAL SUPPORT FAX -0-67-8 PARTS CATALOG ------------------------------
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationATLAS Wheel Balancer Electrical Flow Chart
ATLAS Wheel Balancer Electrical Flow Chart WARNING: Leave all work to trained and licensed electricians. Attempting repairs yourself is extremely dangerous, with the potential for serious injury and even
More informationAUTOMATIC 12 WAY HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationAvid Electrical Services
Avid Electrical Services Thermal Imaging Report To: Mr A. Customer Your Business Australia Pty Ltd Fault Summary The following table is a summary of faults or items featured for your information Grading
More informationAGM. I-Lux MR 16 Style 2 & 5, Coil & Shunt. 108 Fairgrounds Drive Suite 8 Manlius, NY Phone: Fax:
AGM I-Lux MR 16 Style 2 & 5, Coil & Shunt Revision 7.5 Pg 2 I-Lux Catalog / Item Numbers Catalog Code XXX.XXF Sign Size 1 ~ Size 1 2 ~ Size 2 3 ~ Size 3 5 ~ Size 5 Sign Style 2 ~ Style 2 (3 step 4.8A -
More informationINFRARED THERMOGRAPHY:
INFRARED THERMOGRAPHY: X-treme Electrical can now also assist with infrared thermography of various electrical installations. Please take the time to review the following presentation for comprehensive
More informationIB PowlVac ITE-HK Remote Racking Device
IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking
More informationALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks.
ALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks. 1. Check log book for incomplete compliance for further operation. 2.
More informationPump Installation and Service Manual HRS Hydromatic Retractable System
Pump Installation and Service Manual HRS Hydromatic Retractable System NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party
More informationDigitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers
Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationThermal Patterns Associated with Infrared Inspection of Electrical Systems
Thermal Patterns Associated with Infrared Inspection of Electrical Systems James Brady Level III Certified Infrared Thermographer Brady Infrared Inspections, Inc. 935 Pine Castle Court Stuart, FL 34996
More informationSOLAR DASH CHARGING SYSTEM USER GUIDE
SOLAR DASH CHARGING SYSTEM Doc 1.01 INST049 INSTALLATION STEP 1 Place 20 watt solar panel in the dash of the vehicle facing up. Note: For ideal results position the vehicle in a manner in which the solar
More informationProCS and ProC Series Heat Trace Panelboards
ProCS and ProC Series Heat Trace Panelboards Introduction Contents Introduction... 2 System Overview... 3 Certifications... 4 Heat Trace Panel Images... 4-5 AMC Heat Trace Panel (HTP) Selection Guide...
More informationPOWER PINNER HAND WELDER 7200 OPERATOR S MANUAL
POWER PINNER HAND WELDER 7200 OPERATOR S MANUAL Copyright: January 5, 2009 Revised: November 24, 2014 Serial No. 0901189 - Gripnail Corporation An Employee Owned Company 97 Dexter Road East Providence,
More informationUNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK
UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission
More informationHenny Penny Rotisserie Display Model SCD-6/8 TECHNICAL MANUAL
Henny Penny Rotisserie Display Model SCD-6/8 TECHNICAL MANUAL TABLE OF CONTENTS Section Page Section 1. TROUBLESHOOTING... 1-1 1-1. Introduction... 1-1 1-2. Safety... 1-1 1-3. Troubleshooting... 1-1 1-4.
More informationSubstation Equipment (Bushings)
Substation Equipment (Bushings) Mark B. Goff, P.E. Tennessee Valley Authority ABSTRACT Bushings provide a point of interface such that electrical current can pass to and from an electrical apparatus. Much
More informationPUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4
PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In
More informationINGECON SUN PowerMax B SERIES. A new generation of central photovoltaic inverters
INGECON SUN PowerMax B SERIES A new generation of central photovoltaic inverters INGECON SUN PowerMax - B Series Main features of Ingeteam s central PV inverters The greatest power density on the market:
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationOBE, OBEXU, ON BOARD Battery Chargers
C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S OBE, OBEXU, ON BOARD Battery Chargers INTRODUCTION: These chargers are designed for the permanent installation on battery powered vehicles
More informationSELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02
SELECT DIAGNOSTIC GUIDE INST028 Doc 3.02 CONTENTS General Information...2 Select Call-Outs...3 Wire Diagram and Legend...4 Diagnostics...6 Excessive Voltage Drop Diagnostics...6 Static Diagnostics...7
More informationV. Design, Application, Maintenance & Operation Technical Requirements
V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationELECTRICAL SYSTEM RP-7
ELECTRICAL SYSTEM RP-7 This section of the manual does not include integral electrical components of the engine. Refer to section Engine RP-1 for details. This section of the manual is divided into three
More informationA2P Single Phase Automatic Industrial Battery Charger
A2P Single Phase Automatic Industrial Battery Charger Featuring 205B Konrad Cres., Markham, ON, L3R 8T9 www.chargers.ca Building Canada s toughest battery chargers for over a century. Congratulations on
More informationElectrical Existing Conditions and Building Load Summary Report
Electrical Existing Conditions and Building Load Summary Report Executive Summary: This Electrical Existing Conditions and Building Load Summary Report will describe the general and specific characteristics
More informationJoslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers
Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers 2 Introduction This discussion describes in detail retrofitting medium voltage circuit
More informationEasy Start. 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter. Installation Manual
Easy Start 364 (3 ton) Soft Starter 368 (6 ton) Soft Starter Installation Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526. www.microair.net Allentown NJ 08501 Fax (609) 259-6601 Retrofit
More informationMODEL 7100 PORTABLE PIN WELDER OPERATOR S MANUAL
Model 7100 Portable Pin Welder MODEL 7100 PORTABLE PIN WELDER OPERATOR S MANUAL Copyright: March 22, 2005 Revised: December 20, 2016 Gripnail Corporation An Employee Owned Company 97 Dexter Road East Providence,
More informationPMC-MC-X2-Chassis PMC-MC-X4-Chassis
DYNAMIC ENGINEERING 150 DuBois St Suite 3, Santa Cruz Ca 95060 831-457-8891 Fax 831-457-4793 http://www.dyneng.com sales@dyneng.com Est. 1988 User Manual Four Slot Carrier Two Slot Carrier PMC-MC-X2-Chassis
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationNSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL
APPLICATION OF DUST CONTROL EQUIPMENT: CAUTION - Warning Improper operation of dust control system may contribute to conditions in the work area or facility that could result in severe personal injury
More informationManufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN
Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180 ST Series Service Tester Phase Identifier Operating Instructions ST500PGN REV. ED. 101229 CONTENTS Limitation of Warranty and Liability
More informationSUPERIOR PERFORMANCE
REVERSE PULSE DUST COLLECTORS OPERATION & MAINTENANCE MANUAL M600-2C, M900-2C & M1200-2C SUPERIOR PERFORMANCE And Quality In Blast Cleaning Equipment! WARNING Read Manual Failure to read, understand &
More informationManual Transfer Switch
Manual Transfer Switch Instruction Manual 30 1200 Amp 2, 3 & 4 Pole Page 1 WARNING Before Installation READ THIS MANUAL carefully to learn how to properly install, operate and maintain this unit. Personal
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationINFRARED INSPECTION REPORT
REPORT February 13, 2015 Companies Unlimited 1401 Brand St. Los Angeles, CA 90028 Contact: Ron McKinney An Introduction to Infrared Inspection When installed correctly and operated within their ratings,
More informationReport Turbine inspection WTG 15035, Groettocht 7
Report Turbine inspection WTG 15035, Groettocht 7 Report No. V662015067 17-11-2015 Contents 1 Purpose... 3 2 Abbreviations... 3 3 General information... 4 4 Wind turbine main components... 4 5 Documents...
More informationCode Compliance. Perspectives on PV. Back to the Grid, Designing PV Systems for
Perspectives on PV A series of articles on photovoltaic (PV) power systems and the National Electrical Code by John Wiles Back to the Grid, Designing PV Systems for Code Compliance 20 IAEI NEWS January.February
More informationEasyStart Installation Instructions for Dometic Family RV A/Cs
EasyStart Installation Instructions for Dometic Family RV A/Cs DuoTherm Brisk Brisk II Penguin Penguin II Contents Introduction... 4 Safety first... 4 Making a good crimp... 4 Identifying Dometic AC Units...
More informationINOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual
INOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual Complete Installation and Operating Manual for the MEP 002/003 Auto / Remote Starter for the following MEP Power Generators: MEP 002A/003A/011A/802A/803A/811A
More informationCBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls
CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls P-269-89-0408 Installation Installation & Operating Instructions Contents Introduction........................... 2 Specifications.........................
More informationQSSE, QSSEX INDUSTRIAL Battery Chargers
C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S QSSE, QSSEX INDUSTRIAL Battery Chargers INTRODUCTION The QSE line are electronically controlled float chargers. The batteries are brought
More informationACC Series Power Conditioner OPERATION & INSTALLATION MANUAL
ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide
More informationOBAE, OBAEXU, ON BOARD Battery Chargers
C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S OBAE, OBAEXU, ON BOARD Battery Chargers INTRODUCTION: The OBAE line of chargers are designed for the permanent installation on battery powered
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationINSTRUCTIONS FOR REMOVAL OF GROUND FAULT PROTECTION DEVICE FROM HOBART GENERATOR SETS SPECIFICATION NUMBER
TO-161 073085 INSTRUCTIONS FOR REMOVAL OF GROUND FAULT PROTECTION DEVICE FROM HOBART GENERATOR SETS SPECIFICATION NUMBER 6184-3..-.-.._. HOBART BROTHERS COMPANY Power Systems Division Troy, Ohio 45373
More informationThis parts list is current as of the above revision date. See for the current revision.
Parts List This parts list is current as of the above revision date. See http://www.rheempartslists.net/92-800-.pdf for the current revision. Condensing Units Table of Contents Model Explanation...................................................................................................................
More information2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.
0 EDITION AIM MANUAL SUBMERSIBLE MORS APPLICATION INSTALLATION 60 Hz, Single-Phase and Three-Phase Motors franklinwater.com All Motors System Troubleshooting Motor Does Not Start A. No power or incorrect
More informationReliable Temperature Compensation is Critical to CNG Vehicle Safety
Reliable Temperature Compensation is Critical to CNG Vehicle Safety August 18, 2014 This Technical Bulletin addresses the potential hazards created by failure of compressed natural gas (CNG) dispensers
More informationMotor Protection. Voltage Unbalance & Single-Phasing
For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants
More informationMatrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL
Matrix APAX 380V-415V 50Hz TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference ❶ Performance Data Pages
More informationBattery Control Center - Diesel
Service Manual CAUTION: All servicing of the Battery Control Center should be done only by a qualified Service Technician. Inadvertent shorts inside the Battery Control Center could result in severe damage
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationTechnical Service Bulletin IOX/DCX Transmitter Maintenance Schedule
Technical Service Bulletin 140610 IOX/DCX Transmitter Maintenance Schedule Service Bulletin 140610 applies to Comark IOX, DCX and Paragon transmitters. This bulletin contains important maintenance schedule
More informationINSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION 0 F LOW AMBIENT ACCESSORY MODELS 2LA04703425, 3546 & 3658 (208, 230, 460 & 575 VOLT APPLICATIONS) Supersedes: 530.18-N5.6V (1091) 530.18-N5.6V (1193) FOR 15, 20 & 25 TON COOLING
More informationService and Parts Manual. NO LONGER IN PRODUCTION Some service parts may not be available for this product. Otolaryngology Chair.
thru 391-001 -002 Otolaryngology Chair Serial Number Prefixes: EN, PD & V Service and Parts Manual NO LONGER IN PRODUCTION Some service parts may not be available for this product. 391-001 thru -002 NOTE:
More information10 Commercial, Industrial, Agricultural Services
10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three
More informationDispenser & Warmer RIC-1909 RIC-1909EXP
Dispenser & Warmer RIC-1909 RIC-1909EXP Safety Precautions CAUTION This equipment is designed and sold for commercial use only. This equipment is not to be used by the consumer in home use. Do not allow
More informationA. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.
16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationApplication Engineering Europe
Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for
More informationINSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY MODELS 2NH THRU 2NH045025, 2NP THRU 2NP045025, 2ND , AND 2NX GENERAL
INSTALLATION INSTRUCTION ELECTRIC HEATER ACCESSORY S NH0005 THRU NH005, NP000 THRU NP005, ND006, AND NX006 Supersedes: 0-65-003-D-05 0-65-003-E-0705 GENERAL This instruction covers the installation of
More informationTechnical Information and Diagnostic Guide
Technical Information and Diagnostic Guide This guide will assist you in becoming more familiar with the working components of the NITE System and the proper steps and procedures to completely diagnose
More informationGE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System
GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationSelective Coordination
Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationCylindrical Silencers
Cylindrical Silencers A200 Series and 300 Series Installation and Operation Manual Rev. B (c) Copyright 2012, GT Exhaust, Inc. All Rights Reserved Published: April 30, 2012 NOTICE The instructions herein
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationP80074 (150 amp connectors) P80071 (300 amp connectors)
Overview: The Restore-Lite Temporary Power Restoration System is a compact mobile transformer unit that contains a single-phase, floating-tap transformer designed to restore power to customers who have
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationInstallation Instructions For Motor Control Center (MCC) Units
s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground
More information