1 SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA November, 2017 Infrared Inspection Report Sysco Indianapolis LLC West 62nd Street Indianapolis, Indiana, Company Contact: Trevor Gray Project: CHARTER OAK DRIVE, LITTLE ROCK, AR PHONE: & FAX:

2 ORDER OF REPORT CONTENTS 1: Data To Facilitate Understanding & Utilizing Scan Report 2: Scan Results Overview & Action Taken Form 3: Identified Faulting Conditions, Information & Photographs 4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found DISCLAIMER This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not intended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility s condition, maintenance practices or correction of conditions indicated herein. By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, concerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.

3 Utilizing Report Contents Included in this report are Photographs and Thermographs of problem areas found during our recent Infrared Inspection of your facility. Each problem area picture is accompanied by: Date Location Information Temperature Calculations Color-coded Temperature Intensity and/or Condition Significance Data A Brief Comment Relating The Item In The Photograph To Its Corresponding Thermograph Suggested Corrective Recommendations. In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity. Thermal intensity is indicated by use of a color-coded data inserts that locate a fault s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows: INSERT Red Orange Yellow Green Temperature Range 70ºC/126ºF and higher above Ambient Operating Temp. 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp. 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp. *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp. ( * See page 4)

4 Determining Cost Effective Responses Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate. Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports. STANDARD ELECTRICAL FAULT FAILURE CURVE (Does Not Include Area In Blue) MINOR INTERMEDIATE SERIOUS CRITICAL DEVICE TEMP IS AMBIENT, BUT DEVICE IS EITHER FAULTY OR UNSAFE. 10ºC * 18ºF 25ºC 45ºF 40 C 72ºF 70 C 126ºF AMBIENT TEMP YEARS MONTHS MONTHS TO WEEKS WEEKS TO NOW FAULTY EQUIP Built In Trend Monitoring When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings. If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.

5 Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use Total Temperature: Total Temperature = Ambient Operating Temperature + Fault temperature Allows you, the customer, to evaluate possible damage to equipment. Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating. Contacts start to fail around 130ºC/266ºF Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes: Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet. If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault. Allows you, the customer, to determine if device will operate at intended amperage. Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine) If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip. 1. An intermittent high load. 2. A minor (Green) or intermediate (Yellow) fault. Report pages with photographs: PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph *AOT stands for Ambient Operating Temperature Both black & white and color infrared thermographs are presented to better depict the fault condition.

6 In addition to the corrective response time frame suggested below and the failure curve located on the previous page, you may want to consider using the military standard responses presented below. Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment: Temperatures rise above Ambient Operating Temperature: *10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label) 25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label) 40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected. (Orange Label) 70ºC/126ºF and above component failure imminent. Immediately inform the person responsible for continued operation of equipment. (Red Label) Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions. * Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind. Fault Correction Recommendation When Our Source Assessment Is Inaccurate: When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist. The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located. Example: If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp. in the lead holder lug.

7 SCAN RESULTS OVERVIEW PROMPT ATTENTION ITEMS: Because of: 1. The intensity or heat level indicated at the time of the scan. 2. Deterioration caused by excessive temperature not present at the time of the scan. 3. Physical condition irregularities observed at the time of the scan. We recommend that the following faults be given prompt attention: Faults: #1* Items With Asterisks Have High Total or Ambient Operating Temperatures. United Spectrographics November, 2017

8 SUMMARY OF FINDINGS FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO. MINOR 0 0 INTERMEDIATE 0 0 SERIOUS 0 0 CRITICAL 1 1/25 SERIOUS 0 0 Number of items located at facility: 125 Number of faults: 1

9 ACTION TAKEN Sysco Indianapolis LLC. Indianapolis, Indiana November, 2017 Fault # Item # Category Repaired Monitor Date Name Serious

10 PROJECT: CUST REP: SCAN REP: Trevor Trey Dent DATE: November 16th, 2017 LOCATION: Warehouse 36 Volt Battery Charger Area Battery Labeled: Battery Connector PH # 1 > ITEM: SOURCE: TEMP: Connector Plug Negative Lead Lead connection crimp. Temp. of connection and crimp is: 98ºC / 208ºF Total Temp - 21ºC / 70ºF AOT = 77ºC / 138ºF above AOT. TH # 1 > COMMENTS TH # 1 > Abnormal heat is being generated in battery connector connection. See red arrows in PH#1 and TH#1. Loose and/or corroded contact areas. Clean, inspect and re-secure serviceable components. TEMPERATURE ABOVE AOT 77 C / 138 F

11 AREA/EQUIPMENT LIST Following is a list of the electrical equipment located at the Sysco Indianapolis LLC., Indianapolis, Indiana, facility and data relating to its operating condition at the time the scan was performed. NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection. No. Equipment Operating Visually Inspected EQUIPMENT LIST BUILDING A WAREHOUSE MAINTENANCE MAIN POWER AREA Fault # 1 C-14 Fuse Disconnect X 2 Panel CR Volt Distribution Panel X 3 HDR Fuse Disconnect X 4 DP Fuse Disconnect X 5 Switchgear X 6 Transformer Fuse Disconnect X 7 D-1 Fuse Disconnect X 8 D-2 Fuse Disconnect X 9 Panel E 208/120 Volt Distribution Panel X 10 Transformer Fuse Disconnect X 11 Office / Showroom 240 Volt Distribution Panel X 12 Panel B1 208/120 Volt Distribution Panel X 13 Transformer Hevi Duty 3ø 50KVA X WAREHOUSE 14 Panel-L 480 Volt Distribution Panel X 15 Panel-M 480/277 Volt Distribution Panel X 16 Transformer 3ø 45KVA X 17 KT ACME Transformer 3ø 75KVA X 18 Transformer Fuse Disconnect X 19 Battery Charger Panel 208/120 Volt Dist. Panel X 20 Unlabeled Fuse Disconnect X 21 Battery Charger Fuse Disconnect X

12 No. Equipment Operating Visually Inspected 22 Transformer Federal Pacific 3ø 75KVA X Fault # 23 KT-1 208/120 Volt Distribution Panel X 24 KT-2 208/120 Volt Distribution Panel X Volt Battery Charger Area X Volt Battery Charger Area X WAREHOUSE CAGE AREA 27 Panel-Z 208/120 Volt Distribution Panel X 28 Unlabeled Fuse Disconnect for Panel Z X WAREHOUSE ROOF ACCESS AREA 29 Panel-R 208/120 Volt Distribution Panel X 30 Hevi Duty Transformer 3ø 75KVA X 31 Panel-R Fuse Disconnect X 32 Refrigerator Fuse Disconnect X 33 A / Warehouse Ceiling Lights 240 Volt Dist. Panel X 34 Warehouse Lights Fuse Disconnect X 35 Panel-A 208/120 Volt Distribution Panel X Volt Fuse Disconnect X 37 Panel A1 Sub-panel 208/120 Volt Distribution Panel X 38 UPS 208/120 Volt Distribution Panel X FIRE PUMP ROOM 39 Fire Panel Control Cabinet X 40 Unlabeled 480/277 Volt Distribution Panel X DRY SIDE WAREHOUSE 41 XLS Fuse Disconnect X 42 Panel G 208/120 Volt Distribution Panel X 43 Panel M 208/120 Volt Distribution Panel X 44 Panel L 208/120 Volt Distribution Panel X 45 Transformer Riser Panel Fuse Disconnect X 46 Riser Panel I 208/120 Volt Distribution Panel X

13 No. Equipment Operating Visually Inspected 47 Transformer 3ø 75KVA X WILL CALL DOCK 48 Transformer X-9 X 49 Panel WC11 208/120 Volt Distribution Panel X 50 Panel WC12 208/120 Volt Distribution Panel X DRY SIDE LOADING DOCK 51 XLS Dock Panel 208/120 Volt Distribution Panel X 52 Sub Panel XLS 208/120 Volt Distribution Panel X 53 XLS2 Transformer X 54 Disconnect R25-27 X 55 P-1 208/120 Volt Distribution Panel X 56 Sub Panel P-1 208/120 Volt Distribution Panel X 57 UPS 208/120 Volt Distribution Panel X 58 P-1 Transformer X BREAK ROOM 59 Panel P1-A 208/120 Volt Distribution Panel X OFFICE BUILDING UPSTAIRS STORAGE 60 Office Panel A 208/120 Volt Distribution Panel X COMPUTER ROOM 61 Right Unlabeled 208/120 Volt Distribution Panel X 62 Left Unlabeled 208/120 Volt Distribution Panel X UTILITY CLOSET 63 Transformer Federal Pacific Singleø 25KVA X 64 CR-1 208/120 Volt Distribution Panel X 65 CR-2 208/120 Volt Distribution Panel X 66 Transformer Hevi Duty Singleø 37.5KVA X 67 Panel C 208/120 Volt Distribution Panel X 68 Panel A 208/120 Volt Distribution Panel X 69 Panel B 208/120 Volt Distribution Panel X Fault #

14 No. Equipment Operating Visually Inspected ELECTRICAL ROOM DOWN STAIRS Fault # 70 T-1 Transformer GE 3ø 75KVA X 71 P1A 208/120 Volt Distribution Panel X 72 P1B 208/120 Volt Distribution Panel X 73 L1 480/277 Volt Distribution Panel X 74 L2 Main Disconnect X 75 H2 Main Disconnect X 76 H1 480/277 Volt Distribution Panel X ELECTRICAL ROOM UPSTAIRS 77 UPS Panel 208/120 Volt Distribution Panel X 78 Sub-Panel P2A 208/120 Volt Distribution Panel X 79 P2A 208/120 Volt Distribution Panel X 80 L2 480/277 Volt Distribution Panel X 81 H2 480/277 Volt Distribution Panel X UPSTAIRS KITCHEN AREA 82 Unlabeled 208/120 Volt Distribution Panel X 83 Unlabeled 208/120 Volt Dist. Panel (under sink) X TELEPHONE ROOM 84 Unlabeled 208/120 Volt Distribution Panel X ELEVATOR CONTROL ROOM 85 Elevator Control Cabinet X 86 Elevator Fuse Disconnect X 87 Cab-Lights Fuse Disconnect X BARN 88 Panel N 208/120 Volt Distribution Panel X TRUCK SHOP 89 HVWB 480/277 Volt Distribution Panel X 90 TWB Transformer X 91 LVWB 208/120 Volt Distribution Panel X

15 No. Equipment Operating Visually Inspected BUILDING B FREEZER BUILDING MAIN ELECTRICAL ROOM Fault # 92 Switchgear #1 Sections 1-5 X 93 Switchgear #2 Sections 1-3 X 94 MCC 1 X 95 P2 480/277 Volt Distribution Panel X 96 P1 480/277 Volt Distribution Panel X 97 P3 208/120 Volt Distribution Panel X 98 P3-A 208/120 Volt Distribution Panel X 99 T1 Transformer GE 3ø 45KVA X 100 Transformer Federal Pacific 3ø 45KVA X COMPRESSOR ROOM 101 North Video Cameras Control Cabinet X 102 C1 Compressor Control Cabinet X 103 D2 Compressor Control Cabinet X Compressor Control Cabinet X Compressor Control Cabinet X 106 B4 Ammonia Pump Control Cabinet X 107 A5 Ammonia Pump Control Cabinet X BATTERY CHARGER AREA 108 PP4 480/277 Volt Distribution Panel X 109 Battery Chargers X FREEZER DOCK 110 HV2 480/277 Volt Distribution Panel X 111 LV2 208/120 Volt Distribution Panel X 112 HV1 480/277 Volt Distribution Panel X 113 LV1 208/120 Volt Distribution Panel X 114 HV3 480/277 Volt Distribution Panel X

16 No. Equipment Operating Visually Inspected COOLER RISER ROOM Fault # 115 Air Compressor Control Cabinet X 116 Air Compressor Fuse Disconnect X FREEZER AIR COMPRESSOR ROOM 117 Air Compressor Control Cabinet X 118 Air Compressor Fuse Disconnect X OUTSIDE 119 ATS 1 X 120 ATS 2 X 121 Utility Transformer 1 (Fins Only) X 122 Utility Transformer 2 (Fins Only) X 123 Mobile Generator Tap Box X 124 Transfer Switch X 125 Building A Emergency Panel X

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA August, 2018 Infrared Inspection Report SYSCO Oklahoma LLC 1350 West Tecumseh Road Norman, Oklahoma, 73069 Company Contact Chris Hill Project: 03210818 2605 CHARTER

More information

SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA

SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA July, 2018 Infrared Inspection Report Sysco Central California 136 South Mariposa Road Modesto, California, 95393 Company Contact: Steve Handel Project: 04110718

More information

SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS

SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS July, 2015 Infrared Inspection Report Sidewinder Drilling Company Contact Tommy Green Project: 02170715 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE:

More information

BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE

BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE July, 2015 Infrared Inspection Report Buzzi Unicem Terminal Company Contact Randy Miguez Project: 06220715 2605 CHARTER OAK DRIVE, LITTLE

More information

SYSCO RDC SOUTH ALACHUA, FLORIDA

SYSCO RDC SOUTH ALACHUA, FLORIDA SYSCO RDC SOUTH ALACHUA, FLORIDA July, 2018 Infrared Inspection Report Sysco RDC South 12421 NW 173rd Street Alachua, Florida, 32615 Company Contact: Natha Hall Project: 05110818 2605 CHARTER OAK DRIVE,

More information

SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS

SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS November, 2017 Infrared Inspection Report Sidewinder Drilling Rig 127 Pecan Acres 23 PSA 3-3H(WB) Company Contact Colton Chesney Project: 02201117 2605 CHARTER

More information

Thermal Imaging Infrared Survey. Report. Report. Thermography Inspection at ABC Company.

Thermal Imaging Infrared Survey. Report.  Report. Thermography Inspection at ABC Company. Thermal Imaging Infrared Survey Report. Thermal Imaging Infrared Survey Report. Thermography Inspection at ABC Company. Vancouver,BC May 25,2012 www.aiturgroup.com info@aiturgroup.com Rick Turdubay, Certified

More information

Fault Summary The following table is a summary of faults or items featured for your information

Fault Summary The following table is a summary of faults or items featured for your information This document is an annotated sample of a report you receive. following our visit to your premises... We pride ourselves on the quality of the report and submit. this sample for your evaluation.. Report

More information

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9 8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection

More information

Company Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI

Company Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI Company Name City, State Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI 54476-0740 April 9, 2012 (Customer Name & Address) Attn: Customer Enclosed is a report on the

More information

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection: Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: 27-10-2006 Reference Number: 2710061 Thermographer: John Crawford Thermal Imaging

More information

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION MODEL: PS600 HZ: 60 A model ps600 installation and service manual for federal model ps600 FEDERAL SIGNAL CORPORATION POWER SUPPLY VOLTS: SERIES: 120VAC FEDERAL SIGNAL CORPORATION UNIVERSITY PARK, IL. U.S.A.

More information

Substation inspection guidelines Mark B. Goff, P.E.

Substation inspection guidelines Mark B. Goff, P.E. Substation inspection guidelines Mark B. Goff, P.E. Tennessee Valley Authority, Chattanooga, Tennessee ABSTRACT We need to better understand what our infrared camera is really showing us. Without guidelines,

More information

SOLAR DASH CHARGING SYSTEM USER GUIDE

SOLAR DASH CHARGING SYSTEM USER GUIDE SOLAR DASH CHARGING SYSTEM Doc 1.01 INST049 INSTALLATION STEP 1 Place 20 watt solar panel in the dash of the vehicle facing up. Note: For ideal results position the vehicle in a manner in which the solar

More information

A2P Single Phase Automatic Industrial Battery Charger

A2P Single Phase Automatic Industrial Battery Charger A2P Single Phase Automatic Industrial Battery Charger Featuring 205B Konrad Cres., Markham, ON, L3R 8T9 www.chargers.ca Building Canada s toughest battery chargers for over a century. Congratulations on

More information

INFRARED INSPECTION REPORT

INFRARED INSPECTION REPORT REPORT February 13, 2015 Companies Unlimited 1401 Brand St. Los Angeles, CA 90028 Contact: Ron McKinney An Introduction to Infrared Inspection When installed correctly and operated within their ratings,

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

Reliable Temperature Compensation is Critical to CNG Vehicle Safety

Reliable Temperature Compensation is Critical to CNG Vehicle Safety Reliable Temperature Compensation is Critical to CNG Vehicle Safety August 18, 2014 This Technical Bulletin addresses the potential hazards created by failure of compressed natural gas (CNG) dispensers

More information

Integrated Inverter/Battery Monitoring System (IBMS)

Integrated Inverter/Battery Monitoring System (IBMS) Integrated Inverter/Battery Monitoring System (IBMS) Battery monitoring at its finest Maintenance Bypass Switch Input AC to DC Converter DC to AC Inverter Static Bypass Switch Output Operations: Normal

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Avid Electrical Services

Avid Electrical Services Avid Electrical Services Thermal Imaging Report To: Mr A. Customer Your Business Australia Pty Ltd Fault Summary The following table is a summary of faults or items featured for your information Grading

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

TRAILER AUXILIARY POWER SYSTEM (TAPS) INSTALLATION GUIDE V1.10

TRAILER AUXILIARY POWER SYSTEM (TAPS) INSTALLATION GUIDE V1.10 TRAILER AUXILIARY POWER SYSTEM (TAPS) INSTALLATION GUIDE V1.10 TAPS INSTALLATION GUIDE V1.10 1 TRAILER AUXILIARY POWER SYSTEM CONTENTS General Information and System Logic... 2 Diagrams... 3 System Diagram

More information

Thermographic Inspection at SMALLVILLE DPW 123 ANY WAY SMALLVILLE, CA PETER PLEIN

Thermographic Inspection at SMALLVILLE DPW 123 ANY WAY SMALLVILLE, CA PETER PLEIN 191 BOULEVARD GLEN ROCK, NJ 07452 201-444 444-3620 Thermographic Inspection 123 ANY WAY SMALLVILLE, CA 01234 2006-04-25 By PETER PLEIN SAMPLE 1 (10) April 25, 2006 De: This is the in initial inspection

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

Substation Equipment (Bushings)

Substation Equipment (Bushings) Substation Equipment (Bushings) Mark B. Goff, P.E. Tennessee Valley Authority ABSTRACT Bushings provide a point of interface such that electrical current can pass to and from an electrical apparatus. Much

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication serves as a guide that represents the consensus of NEMA member companies and is not intended to override the recommendations

More information

ATLAS Wheel Balancer Electrical Flow Chart

ATLAS Wheel Balancer Electrical Flow Chart ATLAS Wheel Balancer Electrical Flow Chart WARNING: Leave all work to trained and licensed electricians. Attempting repairs yourself is extremely dangerous, with the potential for serious injury and even

More information

Electrical Existing Conditions and Building Load Summary Report

Electrical Existing Conditions and Building Load Summary Report Electrical Existing Conditions and Building Load Summary Report Executive Summary: This Electrical Existing Conditions and Building Load Summary Report will describe the general and specific characteristics

More information

PMC-MC-X2-Chassis PMC-MC-X4-Chassis

PMC-MC-X2-Chassis PMC-MC-X4-Chassis DYNAMIC ENGINEERING 150 DuBois St Suite 3, Santa Cruz Ca 95060 831-457-8891 Fax 831-457-4793 http://www.dyneng.com sales@dyneng.com Est. 1988 User Manual Four Slot Carrier Two Slot Carrier PMC-MC-X2-Chassis

More information

LG Alert TM Helping Drivers Operate Safely. LG Alert Lateral Acceleration Indicator User / Installation Manual

LG Alert TM Helping Drivers Operate Safely. LG Alert Lateral Acceleration Indicator User / Installation Manual INTRODUCTION US Pat. No. 6,130,608 The is intended for use as an early alert system to assist drivers in recognizing when they are exceeding set maximum maneuvering limits of the vehicle. The device monitors

More information

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE Duty B: Power Distribution (600V and below) B-03: Troubleshoot 480V System Issued 06/01/98 Task Preview Troubleshoot 480V System The 480V distribution

More information

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...

More information

SMC BATTERY CHARGER USER S MANUAL SMC USER S MANUAL

SMC BATTERY CHARGER USER S MANUAL SMC USER S MANUAL SMC BATTERY CHARGER SMC 1 INDEX 1 INDEX... 1 2 INTRODUCTION... 2 2.1 INTRODUCTION AND REFERENCES... 2 2.2 GLOSSARY... 2 2.3 DATA LABEL... 2 2.4 HOW TO USE THE USER'S MANUAL... 2 2.5 RESPONSIBILITY DISCLAIMER...

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented

More information

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls P-269-89-0408 Installation Installation & Operating Instructions Contents Introduction........................... 2 Specifications.........................

More information

RCL-7A. User s Guide. Battery Charging Station. Technology in Depth

RCL-7A. User s Guide. Battery Charging Station. Technology in Depth RCL-7A Battery Charging Station User s Guide Technology in Depth - NOTICE - This manual and the information contained herein are provided for use as a maintenance and operation guide. No license or rights

More information

OBE, OBEXU, ON BOARD Battery Chargers

OBE, OBEXU, ON BOARD Battery Chargers C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S OBE, OBEXU, ON BOARD Battery Chargers INTRODUCTION: These chargers are designed for the permanent installation on battery powered vehicles

More information

IB PowlVac ITE-HK Remote Racking Device

IB PowlVac ITE-HK Remote Racking Device IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking

More information

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies Engineering Studies Coordination Study Every 5 years and in conjunction with electrical system modifications. Short Circuit Study NETA MTS 6.2 Every 5 years and in conjunction with electrical system modifications.

More information

THERMOGRAPHY REPORT ELECTRICAL

THERMOGRAPHY REPORT ELECTRICAL LAMBERT CONDITION MONITORING LTD. CERTIFIED THERMOGRAPHER A.I.R. #12-01-243 THERMOGRAPHY REPORT ELECTRICAL Thermographic inspection at: Sample site Inspected by: David Lambert date: 20170701 Customer Sample

More information

INFRARED THERMOGRAPHY:

INFRARED THERMOGRAPHY: INFRARED THERMOGRAPHY: X-treme Electrical can now also assist with infrared thermography of various electrical installations. Please take the time to review the following presentation for comprehensive

More information

EasyStart 364 (ASY-364-X20-IP) Installation Instructions for the Coleman / Airxcel Air Conditioners

EasyStart 364 (ASY-364-X20-IP) Installation Instructions for the Coleman / Airxcel Air Conditioners EasyStart 364 (ASY-364-X20-IP) Installation Instructions for the Coleman / Airxcel Air Conditioners using Installation Kit KIT-364-CM1 Contents Introduction... 2 Safety first... 2 Making a good crimp...

More information

RU SERIES UPGRADE TempAssure Compatible

RU SERIES UPGRADE TempAssure Compatible RU SERIES UPGRADE TempAssure Compatible This converter section has been designed as a converter section replacement in the following MagneTek or Parallax Power Supply series products and models with DC

More information

EasyStart Installation Instructions for Dometic Family RV A/Cs

EasyStart Installation Instructions for Dometic Family RV A/Cs EasyStart Installation Instructions for Dometic Family RV A/Cs DuoTherm Brisk Brisk II Penguin Penguin II Contents Introduction... 4 Safety first... 4 Making a good crimp... 4 Identifying Dometic AC Units...

More information

Louisville Gas and Electric Company

Louisville Gas and Electric Company P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer

More information

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker IL 33-LGH-1 Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE

More information

VI Chip BCM Bus Converter Thermal Management

VI Chip BCM Bus Converter Thermal Management APPLICATION NOTE AN: VI Chip BCM Bus Converter Thermal Management Joe Aguilar Product Line Engineer, VI Chip & Paul Yeaman Principal Product Line Engineer, VI Chip Strategic Accounts Contents Page Introduction

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation M T E C o r p o r a t i o n dv/dt Filter Series A 440-600 VAC USER MANUAL PART NO. INSTR - 019 REL. 041119 2004 MTE Corporation IMPORTANT USER INFORMATION NOTICE The MTE Corporation dv/dt Filter is designed

More information

Key features. DESIGNS: - Conservator type - Hermetically sealed

Key features. DESIGNS: - Conservator type - Hermetically sealed Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the

More information

ProFlo FatBoy

ProFlo FatBoy The Standard For Professional Grade Diaphragm Pumps. ProFlo 3300 5500 FatBoy Operational and Installation Guidelines, Repair & Parts Contents 3300 5500 Fatboy Operational and Installation Guidelines...2

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Pump Installation and Service Manual HRS Hydromatic Retractable System

Pump Installation and Service Manual HRS Hydromatic Retractable System Pump Installation and Service Manual HRS Hydromatic Retractable System NOTE! To the installer: Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party

More information

Thermal Patterns Associated with Infrared Inspection of Electrical Systems

Thermal Patterns Associated with Infrared Inspection of Electrical Systems Thermal Patterns Associated with Infrared Inspection of Electrical Systems James Brady Level III Certified Infrared Thermographer Brady Infrared Inspections, Inc. 935 Pine Castle Court Stuart, FL 34996

More information

DTC P0A04 - Open Wiring Fault

DTC P0A04 - Open Wiring Fault DTC P0A04 - Open Wiring Fault Orion Product Orion BMS [Original] (24-180 Cell) Orion BMS 2 (24-180 Cell) Orion JR (16 Cell) Fault Supported YES YES YES FAULT DESCRIPTION This fault is a serious code that

More information

Generator/Loadbank Quick Connection Tap Box

Generator/Loadbank Quick Connection Tap Box / Generator/Loadbank Quick Connection Tap Box WM2-Series Generator/Loadbank Quick Connection Solutions Brochure www.apt-power.com 433 N. 36 th Street Lafayette, IN 47905 (765) 446-2343 ALN: 517 Rev. 01

More information

PRIVATELYOWNED POWER POLES AND POWERLINES

PRIVATELYOWNED POWER POLES AND POWERLINES PRIVATELYOWNED POWER POLES AND POWERLINES Privately-owned power poles and powerlines Privately-owned power poles and overhead powerlines must be properly maintained to ensure that they do not pose a serious

More information

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER KEW6201A CONTENTS 1. Safe testing 1 2. Procedure of removing cover. 3 2.1 Method of removing the cover. 3 2.2 Method of storing the cover. 3 3. Product summary

More information

Reach ins, Freeezers & Refrigerators Installation & Operation Manual

Reach ins, Freeezers & Refrigerators Installation & Operation Manual Reach ins, Freeezers & Refrigerators Installation & Operation Manual BSR23 BSF23 BSR49 BSF49 BSR72 BSF72 IMPORTANT SAFETY INSTRUCTIONS (SAVE THESE INSTRUCTIONS) Visit us on the web at www.blueairinc.com

More information

Parkit360 Force. Owner s Manual V2.6.2

Parkit360 Force. Owner s Manual V2.6.2 Parkit360 Force Owner s Manual V2.6.2 2 Introduction We know you re busy, and need to get that trailer moved. Now. So with that in mind, we ve kept these instructions as brief as possible, but they are

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

KIT # MC-2911, MC-2923 FOR ALL YEAR SUZUKI M-109R SERIES

KIT # MC-2911, MC-2923 FOR ALL YEAR SUZUKI M-109R SERIES Congratulations on your purchase of an Arnott Motorcycle Air Suspension system. This system provides you with the ability to maintain your bike at a constant level regardless of load, resulting in enhanced

More information

Series 1000 and Figure NOTE: The top terminals are showing normally closed at rest and the middle terminals are normally

Series 1000 and Figure NOTE: The top terminals are showing normally closed at rest and the middle terminals are normally 38.18.The red wire on the OCR plug carries battery voltage. Behavior: D.C. battery voltage should show-up on a volt meter when the red probe is touched to this terminal and the black probe is grounded,

More information

Tundra Racing LOWERING KIT INSTALLATION MANUAL Toyota Tundra 2wd & 4x4 Part #TR-2040 & TR-2050 Reg Cab, Double Cab & Crewmax

Tundra Racing LOWERING KIT INSTALLATION MANUAL Toyota Tundra 2wd & 4x4 Part #TR-2040 & TR-2050 Reg Cab, Double Cab & Crewmax Page 12 Front Coil Spring Perch, Sleeve and Bump Stops Leaf Spring Shackle and Hardware PARTS INCLUDED IN KIT Tundra Racing LOWERING KIT INSTALLATION MANUAL Axle Perches Top & Bottom Plates U-Bolts and

More information

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission

More information

Inspection and Assessment of Track Geometry

Inspection and Assessment of Track Geometry Purpose This document defines requirements for inspection and assessment of track geometry. This document applies to all infrastructure on the Victorian Regional Infrastructure Lease managed by V/Line

More information

PHYSICS 6 EXTENDED PHYSICS

PHYSICS 6 EXTENDED PHYSICS PHYSICS 6 EXTENDED PHYSICS GRADE 11 TERM 3 PORTFOLIO TASKS 2013-2014 STS\G11\Portfolio\Extended Physics Assessment Booklet\CDAU\ADVETIVersion 1.0 2014 1 31 Unit/Topic Performance Criteria Assess Event

More information

SELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02

SELECT DIAGNOSTIC GUIDE. INST028 Doc 3.02 SELECT DIAGNOSTIC GUIDE INST028 Doc 3.02 CONTENTS General Information...2 Select Call-Outs...3 Wire Diagram and Legend...4 Diagnostics...6 Excessive Voltage Drop Diagnostics...6 Static Diagnostics...7

More information

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient

More information

LG Alert TM Helping Drivers Operate Safely. LG Alert Oshkosh Truck Corporation User / Installation Manual

LG Alert TM Helping Drivers Operate Safely. LG Alert Oshkosh Truck Corporation User / Installation Manual INTRODUCTION US Pat. No. 6,130,608 The LG Alert Lateral Acceleration Indicator is intended for use as an early alert system to assist drivers in recognizing when they are exceeding set maximum maneuvering

More information

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries RS-2046 Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries FOLLOW MANUFACTURER S PUBLISHED INSTRUCTIONS WHEN INSTALLING, CHARGING AND SERVICING BATTERIES.

More information

ITS-50R TRANSFER SWITCH OWNER S MANUAL

ITS-50R TRANSFER SWITCH OWNER S MANUAL ITS-50R OWNER S MANUAL IOTA Engineering Transfer Switches provide automatic power switching between two or three separate 120/240 volt AC input sources, including powercords, onboard generators, onboard

More information

OBAE, OBAEXU, ON BOARD Battery Chargers

OBAE, OBAEXU, ON BOARD Battery Chargers C O R P O R A T IO N O P E R A T I N G I N S T R U C T I O N S OBAE, OBAEXU, ON BOARD Battery Chargers INTRODUCTION: The OBAE line of chargers are designed for the permanent installation on battery powered

More information

B BASIC HEAT TREATMENT CONSOLE

B BASIC HEAT TREATMENT CONSOLE Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL

More information

OutdoorXUPS-600AHV-8364

OutdoorXUPS-600AHV-8364 OutdoorXUPS-600AHV-8364 TSi Power s OutdoorXUPS-600AHV-8364 provides secure and uninterrupted 230 vac power to critical loads. 1) Weather-tight metal cabinet (IP44 or NEMA 3R rated) 2) 2A and 2B are wide

More information

INVERTER HARNESS INSTALLATION FOR FREIGHTLINER CASCADIA

INVERTER HARNESS INSTALLATION FOR FREIGHTLINER CASCADIA FOR FREIGHTLINER CASCADIA Part #: P808 1004FC 08/05/2014 Doc 1.04 INST065 Page 1 Step 1: Unpack the plate assembly and both positive and negative cables. INSTALLATION INSTRUCTIONS Step 2: Insert the negative

More information

8300 Series Installation Guidelines

8300 Series Installation Guidelines 1-800-443-4859 8300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER

More information

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Instruction Leaflet IL 33-FH6-2 Supersedes IL 33-FH6-1 Dated 11/99 Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers Contents Description Page Introduction..............................

More information

Switchgear and Distribution Systems for Engineers and Technicians

Switchgear and Distribution Systems for Engineers and Technicians Switchgear and Distribution Systems for Engineers and Technicians WHAT YOU WILL LEARN: How to identify typical characteristics of an industrial distribution system Become familiar with the main components

More information

Compressed Natural Gas Vehicle Fuel System Inspection Guidance

Compressed Natural Gas Vehicle Fuel System Inspection Guidance Prepared by NGVAmerica Technology & Development Committee Fuel System Inspection Working Group Compressed Natural Gas Vehicle Fuel System Inspection Guidance Disclaimer LEGAL NOTICE: NGVAmerica makes great

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for

More information

CELL PREPARATION AND INSTALLATION INSTRUCTIONS

CELL PREPARATION AND INSTALLATION INSTRUCTIONS HYDRO~STICK Water Fuel Cell CELL PREPARATION AND INSTALLATION INSTRUCTIONS DISCLAIMER: This Product is designed and constructed based on the current best practices and state of the art concepts of the

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Installation and Operation Instructions Safety Director Arrow

Installation and Operation Instructions Safety Director Arrow Installation and Operation Instructions Safety Director Arrow! WARNING! Failure to install or use this product according to manufacturers recommendations may result in property damage, serious bodily/personal

More information

MANUAL Model: PT 12/24-60 Solar Converters Inc. - Rev. F

MANUAL Model: PT 12/24-60 Solar Converters Inc. - Rev. F 1.0 Specification MANUAL Model: PT 12/24-60 Solar Converters Inc. - Rev. F Note: This unit is a Multi - Voltage unit with adjustable input panel and output battery adjustment. Please review the section

More information

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,

More information

UL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity.

UL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity. INSTALLATION, OPERATION and MAINTENANCE MANUAL MODEL SCPF1 15, 25, 40 & 65 AMP SCR POWER CONTROLS UL/cUL FILE NUMBER E151547 CE See last page of manual for CE Declaration of Conformity. AMETEK HDR POWER

More information

Report Turbine inspection WTG 15035, Groettocht 7

Report Turbine inspection WTG 15035, Groettocht 7 Report Turbine inspection WTG 15035, Groettocht 7 Report No. V662015067 17-11-2015 Contents 1 Purpose... 3 2 Abbreviations... 3 3 General information... 4 4 Wind turbine main components... 4 5 Documents...

More information

AUTO CHARGE 11HO PIM AUTOMATIC BATTERY CHARGER

AUTO CHARGE 11HO PIM AUTOMATIC BATTERY CHARGER BOOK# 091-11HO-PIM-1 INSTRUCTION MANUAL AUTO CHARGE 11HO PIM AUTOMATIC CHARGER MODEL #091-11HO-PIM NOTE : This charger is designed for vehicles with dual batteries and negative ground. INPUT :115 volts,

More information

CAPACITOR ACTUATED PORTABLE STARTER CAPS USER GUIDE. INST048 Doc 3.01

CAPACITOR ACTUATED PORTABLE STARTER CAPS USER GUIDE. INST048 Doc 3.01 CAPACITOR ACTUATED PORTABLE STARTER CAPS USER GUIDE INST048 Doc 3.01 CONTENTS General Information...2 Charts...3 Before First Use...4 Safety Requirements...5 What to Expect from the CAPS...5 CAPS Diagram...6

More information

CBC-160-1N and CBC-160-2N Clutch/Brake Controls

CBC-160-1N and CBC-160-2N Clutch/Brake Controls P-239-36 819-04 CBC-160-1N and Clutch/Brake Controls Installation Instructions An Altra Industrial Motion Company Contents Introduction...2 Specifications........................... 2 Installation...3

More information

8" - 12" Hydraulic Steel Squeeze Off Tool

8 - 12 Hydraulic Steel Squeeze Off Tool 8" - 12" Hydraulic Steel Squeeze Off Tool ECN 19130 C812S Hydraulic Steel Squeeze Off Tool for Steel Pipe Page 1 of 8 This Footage Tools C812S Steel Squeeze Off Tool is sold with one pump configuration

More information

Bulletins - SI/MI - ( ) Battery maintenance program

Bulletins - SI/MI - ( ) Battery maintenance program SERVICE INFORMATION Bulletin Nbr: 311-2009 Date:...DECEMBER 1998 Market: NOT SE Battery maintenance program Cars affected 9-3, 9-3CV and 9-5 from M1999 inclusive. Background This SI replaces SI 311-1773,

More information

High Frequency SineWave Guardian TM

High Frequency SineWave Guardian TM High Frequency SineWave Guardian TM 380V 480V INSTALLATION GUIDE FORM: SHF-IG-E REL. January 2018 REV. 002 2018 MTE Corporation High Voltage! Only a qualified electrician can carry out the electrical installation

More information

Selective Coordination

Selective Coordination Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings

More information

Low and medium voltage service. Power Care Customer Support Agreements

Low and medium voltage service. Power Care Customer Support Agreements Low and medium voltage service Power Care Customer Support Agreements Power Care Power Care is the best, most convenient and guaranteed way of ensuring electrification system availability and reliability.

More information

Plus SABRE LIGHTBARS

Plus SABRE LIGHTBARS INSTALLATION AND INSTRUCTION MANUAL Plus SABRE LIGHTBARS Models 5364LED, 5462LED, 5464LED and 5564LED PLIT445 REV. D 2/2/18 Keep any radio frequency sensitive equipment at least 20 from the bar and power

More information