ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION

Size: px
Start display at page:

Download "ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION"

Transcription

1 ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION Chanmari, Fatullah, Narayanganj GPS Coordinate: , Inspected by Report Generated by : Noman Saber Khan & Shaik Muhammed Wasi : Noman Saber Khan & Shaik Muhammed Wasi Inspected on: December 4, 2016

2 SUMMARY The Factory was surveyed for electrical safety by Stichting Bangladesh Accord Foundation. The purpose of the survey was to identify significant electrical safety issues and to provide recommendations for remediation based on applicable standards specified by the Accord. Electrical Safety Audit is a methodical approach to evaluate potential electrical hazards and to recommend suggestions for improvement. The scope of this initial electrical safety inspection was limited to the review and identification of major electrical safety issues. The inspection did not include identification of minor deficiencies, which would be further dealt with as part of follow-up inspections. The findings and recommendations in this report are not intended to imply, guarantee, ensure or warrant compliance with any government regulations. Additionally, the results do not imply in any way that compliance with the findings or recommendations as stated in this report will eliminate all risks or exposures not referred to in this report do not exist. Compliance with the findings and recommendations stated in this report does not relieve the factory owner from obligation to comply with specific project requirements, industry standards, or the provisions of any local government regulations. Warn Knit Fashion factory is established in its 6 storied (G +5) building and a separate utility shed. The building is rented by Factory Management for 2 years and owned as personal property as reported by building management. Right now, 3 rd and 4 th is used as Warn Knit Fashion. 5 th Floor is used by difference factory named ARS Printing. Ground, 1 st and 2 nd floor is occupied by another factory named as Sun Knitwear. The building was constructed in 2004 as personal properties and the production began in November During the time of the Inspection, the factory accommodated a total of approx. 100 (Regular shift) workers working on regular basis. 1. FINDINGS AND RECOMMENDATIONS The table below summarizes the major electrical hazards identified during the walk-through inspection. Recommendations have been provided to each finding. The implementation schedule shall be developed by the factory to remediate each of the findings. The specific timing of improvements, including any requested extensions due to design / installation constraints, shall be submitted to the Accord for an approval. Page 2 of 12

3 FINDING E - 1 DOCUMENTATION Electrical Single Line Diagram (SLD) is unavailable in the factory As built Electrical SLD must be prepared; it must have factory's whole electrical installation information. FINDING E - 2 TESTING & PERIODIC MAINTENANCE Insulation resistance test of electrical power cables is not performed Insulation resistant test of all the cables must be performed once every 2-year cycle and recorded (this must require a complete power shut off) FINDING E - 3 TESTING & PERIODIC MAINTENANCE Thermography survey record is unavailable. Hot spots have been observed at some points. Thermography survey must be done and recorded at least twice in a year. Hot spots must be removed. Page 3 of 12

4 FINDING E - 4 TESTING & PERIODIC MAINTENANCE Earth Pit resistance record is unavailable. Number of earth pits must be increased; and all those shall be identifiable. And all earthing systems shall be tested for resistance on any dry day not less than once in every two years. A record of every earth test made and the result shall be kept for not less than two years and shall be available to the Inspector when required. FINDING E - 5 DOCUMENTATION Electric safety training program is not initiated/ conducted. Electrical safety training and awareness program for the electrical personnel must be initiated. It is a periodic task which factory has to continue to improve overall electrical safety situation for the staffs. FINDING E - 6 LIGHTNING PROTECTION SYSTEM Lightning Protection System (LPS) installation is not done. Factory has to design Lightning Protection System (LPS) for the whole factory (where the Risk index is more than 40). Once a LPS is designed properly, installation must be done accordingly asap. Page 4 of 12

5 FINDING E - 7 SUBSTATION ROOM Lead acid battery terminals are filled with rust and left open. Lead acid battery terminals must be covered/capped and rust must be cleaned. P3 FINDING E - 8 SUBSTATION ROOM Wooden cable channel/ducts are used for power cable distribution. Metal type cable tray (perforated one is preferred) shall be used for distributing power cables P3 FINDING E - 9 Cable channels are filled with fluffs (Lint/ dust). Cable channels must be kept neat and clean; these must be sealed properly thus no scope of ingression of fluffs. Page 5 of 12

6 FINDING E - 10 Power Cables are hanging without proper support. Power cables must be supported by cable tray (ladder- where needed). Outdoor arrangement must be covered. FINDING E - 11 Service cables from Grid network has inadequate support (or excessively sagged) Power service cables must be draw using cable tray/ladder (in case of overhead drawing); covering is required for LT cables. FINDING E - 12 Cables in service are joined (splicing) between terminations. Splicing in the power cables shall be avoided; in unavoidable cases splicing, must be made following proper guidance. Page 6 of 12

7 FINDING E - 13 Power cables entering or exiting from Distribution board/ panel are not properly fixed. Power cables entering or exiting from distribution board/panel must be fixed through Panel base/top plate using proper sized cable glands (metal/ PVC). P3 FINDING E - 14 Generator output cables (laid on floor) are not protected and supported Service cables from generator must be supported at its own breaker's terminal and with cable tray. FINDING E - 15 Magnetic ballast found inside the cable channel. Magnetic ballast shall not be kept inside of cable channel. Page 7 of 12

8 FINDING E - 16 MCCBs are not adjusted per load demand. All the MCCBs must be adjusted per cable current ampacity/load current; if adjustment is not possible, replacement will be the only way. FINDING E - 17 Panel doors are not connected with earth. All metal installation which are part of electrical system must be connected to earth to avoid electrical shock or electrocution. FINDING E - 18 Phase barrier/separators are missing in MCCBs Phases must be separated by insulator (a rubber type no-flammable materials shall be used for it) Page 8 of 12

9 FINDING E - 19 Distribution Board's top/bottom are not properly sealed (typical issue) Each electrical distribution board/panel must be properly sealed to avoid ingression of fluffs; but an adequate ventilation system must also be ensured. FINDING E - 20 Multiple cables (came from different electrical consumers) terminated at MCCB terminals Each electrical circuit must be terminated at single MCB/MCCB terminals. FINDING E - 21 No/ Inadequate rubber (insulation) mat at the working area of distribution board/panel. Electrical insulation (not less than 3 mm thick in case of rubber mat) at the working area of each electrical installation (LT panel / MDB / DB / SDB/ other manual operated machineries) must be ensured. Page 9 of 12

10 FINDING E - 22 Loop connection has been used powering multiple circuits through MCB/ MCCBs. Loop Connections shall be removed from entire electrical system. FINDING E - 23 Multiple cables connected in the MCCB terminal bus bar through single lugs. Each cable must be connected in the MCCB terminal / bus bar through single lugs. FINDING E - 24 Instruction for CPR (Cardiopulmonary Resuscitation) or Electrical shock restoration is not present CPR instruction shall be hanged near all electrical installations (LT panel, MDB, FDB, DB, SDB) at visible location Page 10 of 12

11 FINDING E - 25 Distribution boards have no clear identification markings. All distribution boards, switchboards, sub main boards and switches shall be marked clearly for proper identification. FINDING E - 26 EARTHING SYSTEM Manually operated machines (may have chance to be touched by operator/user) have no earth connection. Each manually operated machine (may have chance to be touched by user/operator) must have earth connection. Cable selection shall be made per CB response and circuit's power demand. FINDING E - 27 EARTHING SYSTEM Earth lead cable/earth Continuity Conductor size is inadequate/undersize Earth lead cable/ Earth Continuity Conductor (ECC) must be resized by half of the phase cable. Cable size shall be selected depending on the CB's response time and phase cables' size. Page 11 of 12

12 FINDING E - 28 BOILER & COMPRESSOR Flexible PVC pipe is used to cover power and signal cable for boiler Power and signal cable for boilers shall be distributed using proper type insulator to avoid damage of cables. FINDING NO: E - 29 BOILER & COMPRESSOR Electric boiler. motor has inadequate /no earthing connection Each electrical installation must have proper earth connection. REMEDIATION TIME FRAME: 1 MONTH FINDING NO: E - 30 GENERATOR ROOM Generator Body and neutral has no earth connection. Adequate earthing connection for generator/ transformer body and generator neutral (consult with your generator supplier) shall be ensured. Page 12 of 12

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT APPLE KNITWEAR LTD. House 1, Road 1, Horinchala, Konabari, Gazipur GPS Coordinate:24.010091, 90.319184 Factory List: Apple knitwear Ltd. Inspected by Report Generated

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT ABSS HIGH TECH SWEATER LTD. Kalameshar, Board Bazar, Gazipur. Factory List: ABSS HIGH TECH SWEATER LTD. Inspected by Report Generated by : Hossain Shah Aarif : Mobassear

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,

More information

33kV Connection up to 90MVA

33kV Connection up to 90MVA Electricity Specification 217 Issue 2 December 2007 33kV Connection up to 90MVA Contents 1 Scope 2 General 3 Connection Arrangements 4 Equipment Records 5 Documentation 6 Documents Referenced 7 Keywords

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Construction and Wiring Guidelines for Ergon Energy Substation Panels

Construction and Wiring Guidelines for Ergon Energy Substation Panels Construction and Wiring Guidelines for Ergon Energy Substation Panels Table of Contents Purpose and Scope... 1 Responsibilities... 1 Definitions, Abbreviations and Acronyms... 1 References... 1 Panel Wiring...

More information

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

56-SDMS-07 REV. 01 SPECIFICATIONS FOR 56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

SUBSTATION DESIGN TRAINING

SUBSTATION DESIGN TRAINING 2017 SUBSTATION DESIGN TRAINING ADVANCE ELECTRICAL DESIGN & ENGINEERING INSITUTE (Registered under MSME& An ISO 9001:2008 CERTIFIED) Training Centre: Advance Group of Institutions C-1, Second Floor Near

More information

SCHEDULE OF QUANTITY

SCHEDULE OF QUANTITY SCHEDULE OF QUANTITY ELECTRICAL WORKS PM PALEM BRANCH, VISAKHAPATNAM SL NO. DESCRIPTION OF ITEM / WORK UNIT Qty RATE AMOUNT PART - A : ELECTRICAL WORKS 1 Energy Meter Cubicle : 2 Emergency Off Box (Red

More information

Surface Regulations and Policies

Surface Regulations and Policies Surface Regulations and Policies COAL FATALITIES 1970-2002 350 300 250 200 150 100 50 0 1970 1973 1976 1979 1982 1985 1988 1991 1994 1997 2000 From January 1, 1970 through today, a total of 240 coal miners

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii)

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii) IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The

More information

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program. Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative

More information

Guidance for Low Voltage Electrical Installations

Guidance for Low Voltage Electrical Installations Guidance for Low Voltage Electrical Synopsis This document provides information in support of GI/RT7007 Low Voltage Electrical. Signatures removed from electronic version Submitted by Anne E Blakeney Standards

More information

Siemens Com www.alfazalengineering.com Company Introduction Al-Fazal Engineering is Authorized Dealer of Siemens Components supply and Services also we are electrical construction material manufacturing

More information

36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS

36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS 36-27-1. General. 1.1. Scope. -- Rules and Regulations Governing Surface Areas. 1.2.

More information

GC108: EU Code: Emergency & Restoration: Black start testing requirement

GC108: EU Code: Emergency & Restoration: Black start testing requirement Stage 01: Modification Proposal Grid Code GC108: EU Code: Emergency & Restoration: Black start testing requirement Purpose of Modification: This modification seeks to align the GB Grid Code with the European

More information

GC108: EU Code: Emergency & Restoration: Black start testing requirement

GC108: EU Code: Emergency & Restoration: Black start testing requirement Stage 01: Modification Proposal Grid Code GC108: EU Code: Emergency & Restoration: Black start testing requirement Purpose of Modification: This modification seeks to align the GB Grid Code with the European

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax

More information

NEC REQUIREMENTS FOR GENERATORS

NEC REQUIREMENTS FOR GENERATORS PROFESSIONAL DEVELOPMENT SEMINAR SERIES NEC REQUIREMENTS FOR GENERATORS (Based on NEC 2005 with limited 2008 commentary) AIA certified Continuing Education Units (CEU) Available GPS-140 National Electric

More information

The Management of Electrical Safety in Quarries, Associated Plant and Equipment

The Management of Electrical Safety in Quarries, Associated Plant and Equipment Quarries National Joint Advisory Committee (QNJAC) Plant Information Sheet 1 (Version 1, November 2015, review date: 2020) The Management of Electrical Safety in Quarries, Associated Plant and Equipment

More information

STATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2012

STATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2012 Safety Services 16 th floor, Commerce Place Tel: 1-866-421-6929 10155 102 nd Street Fax: 780-427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS ELECTRICAL INCIDENTS IN ALBERTA January 1 to December 31,

More information

Electric & Gas Service Requirements (Greenbook) Overview

Electric & Gas Service Requirements (Greenbook) Overview INTRODUCTION The Greenbook contents and standard documents are updated regularly to provide users with the most current information possible. In conjunction with this effort, the 2016 Greenbook was reviewed

More information

EXTENSIVELY READ THE MANUALS AND HAVE SOME TRAINING. THIS TYPE OF CONNECTION IS NOT EVEN LISTED IN THE TM

EXTENSIVELY READ THE MANUALS AND HAVE SOME TRAINING. THIS TYPE OF CONNECTION IS NOT EVEN LISTED IN THE TM IN THIS SLIDE, THE INDIVIDUAL / S WHO MADE THIS CONNECTION NEEDs TO EXTENSIVELY READ THE MANUALS AND HAVE SOME TRAINING. THIS TYPE OF CONNECTION IS NOT EVEN LISTED IN THE TM s AND THE CECOM GROUNDING BOOK.

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9 8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection

More information

Electrical Testing Company Pty Ltd / download at electricaltestingcompany.com.au / AS/NZS 3003:2011 Cardiac (Rev C)

Electrical Testing Company Pty Ltd / download at electricaltestingcompany.com.au / AS/NZS 3003:2011 Cardiac (Rev C) AS/NZS 3003:2011 Cardiac Protected Electrical Areas (shall comply with Section 2 and Section 4 of the standard) The following is a guide for electricians involved with electrical installations for patient

More information

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

Tender Schedule. Sl. No. Particulars Quantity Unit Rate `

Tender Schedule. Sl. No. Particulars Quantity Unit Rate ` Tender Schedule Estimate for Electrical Works at Savalyapuram Branch(18901) Guntur(District). Sl. No. Particulars Quantity Unit Rate ` 1 Wiring for light point/ fan point/ exhaust fan point/ call bell

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

Powered Industrial Trucks

Powered Industrial Trucks INDIANA UNIVERSITY-PURDUE UNIVERSITY at INDIANAPOLIS IUPUI Department of Environmental Health and Safety 620 Union Drive, Room 043, Indianapolis, Indiana 46202 Powered Industrial Trucks Purpose and Background

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011 Page 1 of 6 STANDARD SPECIFICATION FOR LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs Rev No. Issue Date Pages Rev Description Prepared By Checked By Approved By 0 15.07.2008 6 Issued for FEED MSJ VDV VDV

More information

Guidelines for Filming in The City of Vernon. General Requirements

Guidelines for Filming in The City of Vernon. General Requirements Guidelines for Filming in The City of Vernon The City of Vernon, a primarily industrial city, provides a wide range of services to the Entertainment Industry as a means of maintaining and expanding the

More information

Underground Distribution Construction Manual

Underground Distribution Construction Manual Underground Distribution Construction Manual Section E7 Earthing Approved by: A Smith de Perez Energex Limited 2014 ABN 40 078 849 055 MANUAL 00305 1. INSTALLATION Detailed earthing information may be

More information

MAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT CS-OHS-32

MAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT CS-OHS-32 CS ENERGY OPERATIONS PROCEDURE FOR MAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL CS-OHS-32 Responsible Officer: Electrical Services Engineering Manager Error! Bookmark

More information

PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE

PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE Page 1 of 6 1. SUMMARY... 3 1.1 USE OF PORTABLE ELECTRICAL EQUIPMENT... 3 1.2 FAULTY EQUIPMENT... 3 2. PURPOSE & SCOPE... 3 3. DEFINITIONS... 3 3.1

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA TENDER FOR

GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA TENDER FOR GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA - 390 007 TENDER FOR Design,Engineering, manufacturing, supply, erection, testing & commissioning of 66

More information

LIST OF EDD DESCRIPTION/ SPECIFICATION AS 19 TH OCTOBER 2016

LIST OF EDD DESCRIPTION/ SPECIFICATION AS 19 TH OCTOBER 2016 No Description/ Specification Amendment 1 EDD 1 :2008 11/0.415 kv Distribution Transformer, Oil Filled - 2 ED 2 :1987 The Galvanization of Iron and Steel, Articles Other Than Steel Wire - 3 ED 3 :1979

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

VP, Facilities and Construction Management

VP, Facilities and Construction Management Title: Effective Date: November 2005 Revision Date: January 12, 2017 Issuing Authority: Responsible Officer: VP, Facilities and Construction Management Director Environmental Health and Safety PURPOSE

More information

Electrical Safety. Presented By- C S Chakraverty. L&T Construction ( MMH ) Head- E&I Operation

Electrical Safety. Presented By- C S Chakraverty. L&T Construction ( MMH ) Head- E&I Operation Electrical Safety Presented By- C S Chakraverty Head- E&I Operation L&T Construction ( MMH ) Objective of the session Create an awareness about importance of electrical safety in our day today activities,

More information

BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012

BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012 BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012 3.1.2 re batteries secure against excessive movement in any direction? R Check by visual assessment the

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

Contents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers

Contents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers DISTRIBUTION CODE Contents 1 Introduction 2. Advisory and Information Systems 3. Supply 3.1 Quality of Electric Supply 3.2 Interference with other Customers 3.3 Application for the Supply of Electricity

More information

Portable Ladder Safety

Portable Ladder Safety Portable Ladder Safety Disclaimer This training material presents very important information. Your organization must do an evaluation of all exposures, applicable codes and regulations, and establish proper

More information

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented

More information

Estimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount

Estimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount Estimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount 1 2 Writing for light point/ fan point/ exhaust fan point /call bell point with 1.5 sq.mm FR PVC insulated

More information

PRIVATELYOWNED POWER POLES AND POWERLINES

PRIVATELYOWNED POWER POLES AND POWERLINES PRIVATELYOWNED POWER POLES AND POWERLINES Privately-owned power poles and powerlines Privately-owned power poles and overhead powerlines must be properly maintained to ensure that they do not pose a serious

More information

34-SDMS-01 SPECIFICATIONS FOR

34-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES

More information

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

Louisville Gas and Electric Company

Louisville Gas and Electric Company P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

HOLY SPIRIT RCSRD NO.4 BUS DRIVER S GUIDE

HOLY SPIRIT RCSRD NO.4 BUS DRIVER S GUIDE HOLY SPIRIT RCSRD NO.4 BUS DRIVER S GUIDE Updated May 2017 Holy Spirit RCSRD No.4 Bus Driver s Guide TABLE OF CONTENTS INTRODUCTION... 3 CARRIER PROFILE... 4 BUS DRIVERS... 5 Authorized Driver... 5 Un-authorized

More information

NETWORK ELECTRICAL TECHNOLOGY LLC

NETWORK ELECTRICAL TECHNOLOGY LLC 2016 NETWORK ELECTRICAL TECHNOLOGY LLC Sameh Al-Sinani Network Electrical Technology 12/1/2016 Network Electrical Technology established in 2010 as Electrical Services Company. In 2014 NET registered in

More information

Position Paper. Telehandler Use: Lifting Suspended Loads

Position Paper. Telehandler Use: Lifting Suspended Loads Position Paper Telehandler Use: Lifting Suspended Loads The following paper reflects the considered opinion on the Crane Association of New Zealand (Inc.) This document has been prepared by the Technical

More information

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum. FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared

More information

RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS CHAPTERS APPROACH

RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS CHAPTERS APPROACH PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS TITLE 47 SUPPLY VESSELS SECTION 6 PIPING CHAPTERS A B C D E F G H T APPROACH MATERIALS AND MANUFACTURE - See

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

Electrical Workplace Safety

Electrical Workplace Safety Electrical Workplace Safety Alan Kelly 23 rd September 2015 Objectives To provide an understanding of Electrical terms and the concepts of electricity To introduce Electrical Protective Devices and provide

More information

Wind and Temperature Tip Over Hazard Do not add notice boards or similar

Wind and Temperature Tip Over Hazard Do not add notice boards or similar Lift & Work Platform Safety Information Safety Information: Boom Lifts Safety Information: Scissor Lifts Safety Information: Boom Lifts Power Lines Electrocution Hazard Maintain safe clearance from Electrical

More information

INDIAN INSTITUTE OF TECHNOLOGY KANPUR

INDIAN INSTITUTE OF TECHNOLOGY KANPUR INDIAN INSTITUTE OF TECHNOLOGY KANPUR Tender Notice No. 40/Elect./2018 SCHEDULE OF QUANTITY Name of Work: Electrical work for the Clean Room at NCFlexE IIT Kanpur. Name of the Contractor S. No Description

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

DEVELOPMENT OF DRAFT GUIDELINES FOR CONSISTENT IMPLEMENTATION OF REGULATION OF MARPOL ANNEX VI

DEVELOPMENT OF DRAFT GUIDELINES FOR CONSISTENT IMPLEMENTATION OF REGULATION OF MARPOL ANNEX VI E INTERSESSIONAL MEETING ON CONSISTENT IMPLEMENTATION OF REGULATION 14.1.3 OF MARPOL ANNEX VI Agenda item 2 25 May 2018 ENGLISH ONLY DEVELOPMENT OF DRAFT GUIDELINES FOR CONSISTENT IMPLEMENTATION OF REGULATION

More information

Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act ZEK

Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act ZEK -GB-2017-01: Defining the requirements for a GS mark approval Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act about

More information

CONVEYOR REGULATIONS. AA COUTINHO Director Mine Safety

CONVEYOR REGULATIONS. AA COUTINHO Director Mine Safety CONVEYOR REGULATIONS AA COUTINHO Director Mine Safety CONTENTS 1. Accident» Fatalities» Injuries 2. Conveyor regulations 3. Way forward INJURIES-Fatalities 12 10 8 6 4 2 0 2002 2003 2004 2005 2006 2007

More information

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 REDUNDANT PROPULSION JANUARY 2003 This booklet includes the relevant amendments and corrections

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

LIGHTING JUNCTION BOX

LIGHTING JUNCTION BOX Channels Max. No. of Terminals Cat No. Max. Max. 4 10 16 35 50 70 95 Size Length No. mm 2 mm 2 mm 2 mm 2 mm 2 mm 2 mm 2 DB 6006 260 x 160 L 245 1 30 20 16 B 145 2 32 22 18 6 DB 6024 300 x 225 L 285 2 72

More information

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL

More information

Installation and Construction Notes for EVSE4

Installation and Construction Notes for EVSE4 Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process

More information

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:

Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection: Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: 27-10-2006 Reference Number: 2710061 Thermographer: John Crawford Thermal Imaging

More information

PRODUCT DATA. Parking Automat P kg 1

PRODUCT DATA. Parking Automat P kg 1 - Car KLAUS Multiparking Systems Pvt. Ltd. /, Prashant Apartments, Erandwane, Pune INDIA Phone +9-- 78 / 866 Fax +9-- 66 E-mail info@klausmultiparking.in Website www.klausindia.com PRODUCT DATA Parking

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001 CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS

More information

Powered Industrial Vehicle Policy

Powered Industrial Vehicle Policy Powered Industrial Vehicle Policy Policy The Flight Department is committed to protecting employees from the hazards involved in the operation of powered industrial vehicles. This Policy is established

More information

Solar PV General Introduction Guide for Electricians

Solar PV General Introduction Guide for Electricians Solar PV General Introduction Guide for Electricians Important Note: This guide was written to provide a broad guidance for electricians that would like to expand their product knowledge and skills for

More information

EU TOY DIRECTIVE 2009/48/EC: OVERVIEW - REGULATORY CONTEXT AND MAJOR CHANGES

EU TOY DIRECTIVE 2009/48/EC: OVERVIEW - REGULATORY CONTEXT AND MAJOR CHANGES EU TOY DIRECTIVE 2009/48/EC: OVERVIEW - REGULATORY CONTEXT AND MAJOR The EU Toy Directive was revised in order to take into account the new technological developments and increasing child safety requirements.

More information

STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA to

STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA to Safety Services th 16 floor, Commerce Place Tel 1-866/421-6929 10155 102 nd Street Fax 780/427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA 01 01 to 12 31 Regulations

More information

CHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations

CHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations Only the Danish version is authentic Notice D II-1 D 1 October 2002 Technical regulation on the construction and equipment, etc. of passenger ships on domestic voyages CHAPTER II-1 D Construction subdivision

More information

Tender Schedule for Electrical Works at Varagani Branch. Sl. No. Particulars Quantity Unit Rate Amount

Tender Schedule for Electrical Works at Varagani Branch. Sl. No. Particulars Quantity Unit Rate Amount Tender Schedule for Electrical Works at Varagani Branch Sl. No. 1 Particulars Quantity Unit Rate Amount SITC of following rated Indoor operated wall/floor mounted, cubicle type MV cum APFC Panel suitable

More information

Task Force on Electro-magnetic Compatibility (TF EMC) Status report of TF to GRE-75 Friday, 8 April 2016

Task Force on Electro-magnetic Compatibility (TF EMC) Status report of TF to GRE-75 Friday, 8 April 2016 Submitted by TF EMC Informal document GRE-75-18 (75 th GRE, 5-8 April 2016, agenda item 7(c)) Task Force on Electro-magnetic Compatibility (TF EMC) Status report of TF to GRE-75 Friday, 8 April 2016 TF

More information

GENERAL HOUSEKEEPING. 1. Are all aisles, passageways, stairways and stairwells kept clear of tools, hoses, and trash?

GENERAL HOUSEKEEPING. 1. Are all aisles, passageways, stairways and stairwells kept clear of tools, hoses, and trash? Inspection Checklist GENERAL HOUSEKEEPING 1. Are all aisles, passageways, stairways and stairwells kept clear of tools, hoses, and trash? 2. Is oil, grease, or other liquids, when spilled on the floor

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

MICROCARE 3 PHASE INVERTER MANUAL

MICROCARE 3 PHASE INVERTER MANUAL 3 PHASE INVERTER MANUAL 1 Contents 1. INTRODUCTI... 3 2. SAFETY INSTRUCTI... 4 3. SYSTEM DESCRIPTI... 6 4. WIRING DIAGRAM... 9 5. INVERTER OPERATI... 10 6. INVERTER CLUSTER PROGRAMMING... 13 7. CLUSTER

More information

FAQ s. Designing metering switchboards as per Victorian service installation rules

FAQ s. Designing metering switchboards as per Victorian service installation rules FAQ s Designing metering switchboards as per Victorian service installation rules Designing metering switchboards as per Victorian service installation rules Q: Who develops the Victorian service installation

More information

Prepared for: BP-Husky Refining LLC 4001 Cedar Point Road Oregon, Ohio Prepared by:

Prepared for: BP-Husky Refining LLC 4001 Cedar Point Road Oregon, Ohio Prepared by: BP-HUSKY REFINING LLC REVISION TO FCCU WET GAS COMPRESSOR RECONSTRUCTION PERMIT TO INSTALL (04-01482) TO INCORPORATE FINAL FCCU NO X EMISSIONS LIMITS Prepared for: BP-Husky Refining LLC 4001 Cedar Point

More information

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS... TITLE SPECIFICATION FOR PORTABLE DATE: JULY 2006 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD...3 INTRODUCTION...4 1 SCOPE...4 2 NORMATIVE S...4 3 DEFINITIONS AND ABBIATIONS...4 4 REQUIREMENTS...5 4.1

More information

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation 86 Customhouse Quay PO Box 165, Wellington 6140 New Zealand Date of publication: 1 November 2016 Issued by: Mark Wogan, Manager Energy Safety WorkSafe New Zealand Electric Vehicle Charging Safety Guidelines

More information

CONTENT 1 PICTURE GENERAL... 3

CONTENT 1 PICTURE GENERAL... 3 IP67 CONTENT 1 PICTURE... 3 1.1 GENERAL... 3 2 DIMENSIONS... 4 2.1 SYMBOLS... 5 2.2 PROTECTION FROM ELECTRIC SHOCK... 6 2.3 PROTECTIONS FROM FIRE AND BURNS... 6 2.4 PROTECTION FROM INJURY... 7 2.5 DISPOSING

More information

CAL/OSHA ELECTRICAL LOW VOLTAGE

CAL/OSHA ELECTRICAL LOW VOLTAGE Preparation: Safety Mgr Authority: CEO Issuing Dept: Safety Page: Page 1 of 7 Purpose The purpose of this program is to prevent injuries due to electrical exposure to low voltage (less than or equal to

More information

Substation Lightning Protection. Document Number: 1-11-FR-11

Substation Lightning Protection. Document Number: 1-11-FR-11 Substation Lightning Protection Document Number: 1-11-FR-11 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-11 Substation Lightning Protection Asset

More information