1 Guidance for Low Voltage Electrical Synopsis This document provides information in support of GI/RT7007 Low Voltage Electrical. Signatures removed from electronic version Submitted by Anne E Blakeney Standards Project Manager Authorised by Brian Alston Controller, Railway Group Standards This document is the property of Railway Safety. It shall not be reproduced in whole or in part without the written permission of the Controller, Railway Group Standards, Railway Safety. Published by: Railway Safety Evergreen House 160 Euston Road London NW1 2DX Copyright 2002 Railway Safety

2 This page has been left blank intentionally

3 Page 1 of 15 Contents Section Description Page Part A A1 Issue record 2 A2 Implementation of this document 2 A3 Responsibilities 2 A4 Health and safety responsibilities 2 A5 Technical content 2 A6 Supply 3 Part B B1 Purpose 5 B2 Application of this document 5 B3 Definitions 5 B4 General requirments 6 B5 Protection and switiching 6 B6 General earthing requirments 7 B7 Earthing requirements for LV electrical installations in AC electrified lines areas 8 B8 Earthing requirements for LV electrical installations in DC electrified lines areas 10 B9 Temporary low voltage electrical installations 12 Appendices A B References LV electrical equipment within the LV electrical installations directly bonded to the AC traction return circuit 13 LV electrical equipment within the LV electrical installations indirectly bonded to the AC traction return circuit RAILWAY SAFETY 1

4 Page 2 of 15 Document Withdrawn as of April 2009 A1 Issue record Part A Issue Date Comments One June 2002 Original Document This document will be updated when necessary by distribution of a complete replacement. A2 Implementation of this document The publication date of this document is 1 June This document supersedes the following s, either in whole or in part as indicated: Railway Group Guidance Note Issue No. Title GN sections superseded by this document Date(s) as of which sections are superseded GM/RC Code of Practice for Low Voltage Electrical on Railway Network Premises All 3 August 2002 (document withdrawn as of this date) A3 Responsibilities s are non-mandatory documents providing helpful information relating to the control of hazards and often set out a suggested approach, which may be appropriate for Railway Group* members to follow. * The Railway Group comprises Railtrack PLC, Railway Safety, and the train and station operators who hold Railway Safety Cases for operation on or related to infrastructure controlled by Railtrack PLC. Railtrack PLC is known as Railtrack. A4 Health and safety responsibilities A5 Technical content In issuing this document, Railway Safety makes no warranties, express or implied, that compliance with all or any document published by Railway Safety is sufficient on its own to ensure safe systems of work or operation. Each user is reminded of its own responsibilities to ensure health and safety at work and its individual duties under health and safety legislation. The technical content of this document has been approved by: P Williment, Principal Electrification Engineer, Railway Safety H Peers, Principal Plant Engineer, Railway Safety J Allan, Principal Signalling and Telecoms Engineer, Railway Safety Enquires to be directed to Railway Safety Tel: RAILWAY SAFETY

5 Page 3 of 15 A6 Supply Controlled and uncontrolled copies of this document may be obtained from the Industry Safety Liaison Dept, Railway Safety, Evergreen House, 160 Euston Road, London NW1 2DX. RAILWAY SAFETY 3

6 Page 4 of 15 Document Withdrawn as of April 2009 This page has been left blank intentionally 4 RAILWAY SAFETY

7 Page 5 of 15 B1 Purpose B2 Application of this document Part B This document provides information in support of GI/RT7007 Low Voltage Electrical. B2.1 To whom the guidance applies This document contains guidance that is applicable to the duty holders of the following categories of Railway Safety Case: a) infrastructure controller b) station operator. B3 Definitions Circuit protective conductor (BS 7671) Circuit protective conductor (cpc) is a protective conductor connecting exposedconductive-parts of equipment to the main earth terminal. Electrical installation (BS 7671) An assembly of associated electrical equipment supplied from a common origin to fulfil a specific purpose and having certain co-ordinated characteristics. High voltage High voltage (HV) is normally exceeding low voltage. Low voltage Normally not exceeding 1000 V AC or 1500 V DC between conductors, or 600 V AC or 900 V DC between conductors and earth. Nominal voltage (BS EN ) Voltage by which an installation or part of an installation is designated. Temporary installation An installation that is not intended to become a fixed installation, regardless of the length of time. Touch voltage (BS EN ) Voltage under fault conditions between parts when touched simultaneously. Traction equipment The term traction equipment is used to mean the electrical equipment and conductors necessary to power the trains on an electrified railway. It includes the incoming supply feeders, switchgear and transformers which control and provide the electrical current at the traction system s line voltage, the distribution network and catenary or conductor rail system including the traction return circuit. Traction return circuit (GL/RT1254) The path by which the traction current returns from the traction unit to the feeder station, or substation, incorporating the traction return rails, bonding connections, return conductors and booster transformers as appropriate. RAILWAY SAFETY 5

8 Page 6 of 15 Document Withdrawn as of April 2009 B4 General requirements B4.1 B4.1 General requirements for LV electrical installations The general requirements for LV electrical installations given in BS 7671, as applicable to the rail industry, shall be followed. B4.2 B4.2 Cables to LV electrical equipment on or near to the running rail Except as follows, cables that cross the track and that are energised at a nominal voltage of more than 110 V shall not be routed on the surface. It is permissible to route cables energised at a nominal voltage of 110 V or less, or any cables connected to equipment attached to a running rail, on the surface across the track formation rather than in under track crossings. B4.2.1 The preferred methods of routing cables on the surface across the track formation are by the use of notched sleepers/bearers or ducted or hollow sleepers/bearers. B5 Protection and switching B5.1 B5.1 Residual current devices providing additional protection against direct contact in DC electrified lines areas When selecting a residual current device (RCD) to provide additional protection against direct contact in DC electrified lines areas, consideration shall be given to the effects of the level of DC leakage that may affect the operation of the RCD. The infrastructure controller shall produce and maintain a list of approved suppliers of RCDs that are immune up to declared levels of DC leakage and shall make this list available to other Railway Group members on request. B5.1.1 The level of DC leakage will be dependent upon the location and the traction return bonding arrangements. B5.2 B5.2 Fuses Rewirable fuses shall not be used for short circuit or overcurrent protection. B5.2.1 Suitable cartridge fuses are those compliant with BS 88 or BS 1361 as appropriate. B5.3 B5.3 Interlocking Interlocking shall be provided where it is necessary to prevent paralleling of independent LV electrical power sources. B5.4 B5.4 Miniature circuit breakers Miniature circuit breakers shall not be installed where they may be used as a switch, for example as a light switch. B5.4.1 Miniature circuit breakers (MCB), complying with BS EN 60898, may be used to protect final circuits. The selection of the correct type and rating of MCB to 6 RAILWAY SAFETY

9 Page 7 of 15 match the circuit duty will depend on the methods used by manufacturers to determine device ratings. B5.4.2 MCBs have a relatively low maximum fault current rating and back-up fuse protection may be necessary. B5.4.3 The careful selection of location of MCBs during the installation design process can inhibit the use of the MCBs as switches. B6 General earthing requirements B6.1 B6.1 Segregated HV and LV earth systems Where HV and LV earth systems are segregated, Railway Group members shall co-operate to design, install and maintain the LV electrical installation such that the values of touch voltages specified in BS EN are not exceeded. B6.2 B6.2 Circuit protective conductor Metallic conduit, trunking and cable trays shall not be used as a cpc where high currents associated with other electrical systems would affect the integrity of the cpc. B6.3 B6.3 Earth monitoring or earth proving device Where appliances are used in hazardous situations the use of an earth monitoring device, in addition to an RCD, shall be considered as part of the risk assessment required by the Management of Health and Safety Regulations. B6.3.1 Currents flowing through the body under fault conditions will produce a momentary electric shock. Where appliances are used in hazardous situations, for example, where there is an increased risk of falling as a result of an electric shock or where there is an increased risk due to using water, then the use of an earth monitoring device in addition to an RCD should be considered. B6.3.2 An earth monitoring system provides a pilot conductor to the device, usually in the form of a cable braid, which forms a loop with the cpc. The continuity of the earth path is proven by passing a small electrical current through the loop. If the earth path is not continuous, or if it has a resistance higher or lower than set values, the power supply will not be energised. B6.3.3 Guidance on methods of protection for areas where high pressure water jets are used is given in HSE Guidance Note PM29 Electrical hazards from steam/water pressure cleaners etc. RAILWAY SAFETY 7

10 Page 8 of 15 Document Withdrawn as of April 2009 B6.4 B6.4 Touch potentials Where it is possible for a person simultaneously to touch exposed conductive parts that are connected to the equipotential bonding system of the LV electrical installation and the exposed conductive parts of the equipotential bonding system of a rail mounted vehicle, touch voltage values shall not exceed those specified in BS EN B6.4.1 Even though rolling stock is excluded from the scope of the Railway Group Standard this important interface needs to be considered. B6.5 B6.5 LV electrical equipment on or near to the running rail Except where agreed by the infrastructure controller, all electrical equipment attached to a running rail shall be energised from an earth-free, isolated power supply, operated at a nominal voltage less than or equal to 110 V. B6.5.1 Many existing train detection systems are not designed to withstand nominal voltages greater than 110 V. B7 Earthing requirements for LV electrical installations in AC electrified lines areas B7.1 B7.1 Earthing and bonding The requirements for AC electrified lines traction bonding are contained in GL/RT1254. B7.1.1 The overhead contact wire is energised at a nominal voltage of V. Electric trains draw power from the overhead wire with current returning to the feeder station via the running rails, return conductors or aerial earth wire depending upon the specific location design. Each overhead line equipment (OLE) support mast is bonded to the traction return circuit and provides an earth path through the mast foundation. B7.1.2 Where there is a risk of exposed metalwork becoming electrically connected to live OLE (by flashover, breakage of conductors, etc) conductive structures and services are bonded to the traction return circuit to ensure rapid disconnection of the traction power supply in the event of a traction fault. B7.1.3 Additionally, equipotential bonding is required where it is possible simultaneously to touch exposed metalwork and the running rails, trains or other conductive objects connected to the traction return circuit. This is necessary to limit touch voltage to values not exceeding those specified in BS EN B7.1.4 The final choice of whether to bond directly or indirectly will depend on the cost of providing a reinforced cpc compared to direct bonding and the practicality of segregating the earth systems at the LV electrical equipment or elsewhere. 8 RAILWAY SAFETY

11 Page 9 of 15 B7.2 B7.2 LV electrical equipment within the LV electrical installations directly bonded to the traction return circuit The LV electrical equipment cpc shall not be connected to the LV electrical equipment when the LV electrical equipment is either: a) directly bonded to the traction return circuit or b) is in contact with a conductive structure having a direct bond to the traction return circuit. B7.2.1 Parallel paths for traction current will be avoided by not connecting the LV electrical installation supply cpc to the LV electrical equipment (see Appendix A for a typical arrangement) when the LV electrical equipment is either directly bonded to the traction return circuit, or is in contact with a conductive structure having a direct bond to the traction return circuit. B7.2.2 Separation is achieved by gapping the supply cable armouring by: a) the use of an insulated gland or b) cutting back the cable armouring to a maximum distance of 300 mm from the equipment entry point and c) applying heavy duty heat shrink sleeving to cover the gland or the cut back section and 150 mm of the cable outer sheath and d) terminating any additional cpc before it reaches the equipment. B7.2.3 A suitable permanent warning label (securely attached to the cable) identifies that the incoming service cable earth has been gapped and should not be bridged. B7.2.4 An equipotential bond may be required between the traction return circuit and the LV electrical installation supply main earth to provide earth fault protection for the equipment and minimise touch voltages. This equipotential bond between the traction return circuit and the LV electrical installation should not be fitted at feeder stations. The type and rating of this bond should be agreed between the infrastructure controller and the regional electricity company (REC). B7.2.5 Gapped circuits should have RCD protection. RAILWAY SAFETY 9

12 Page 10 of 15 Document Withdrawn as of April 2009 B7.3 B7.3 LV electrical equipment within the LV electrical installations indirectly bonded to the traction return circuit In each of the following circumstances the LV electrical equipment cpc shall be connected to the LV electrical equipment and be rated to carry the prospective traction fault current when the LV electrical equipment requires to be bonded and either: a) the LV electrical equipment is not in contact with any metalwork which itself is connected to the traction return circuit or b) a direct bond as in section B7.2 is not selected. Where indirect bonding is used the fault path shall be completed by an equipotential bond between the LV electrical installation supply main earth and the traction return circuit. B7.3.1 When the LV electrical equipment requires to be bonded to ensure safety during traction fault conditions, but is not in contact with any metalwork which itself is connected to the traction return circuit, an alternative to direct bonding of the equipment is required (see Appendix B for a typical arrangement). B7.3.2 The LV electrical equipment cpc provides a fault path which is completed by an equipotential bond between the LV electrical installation supply main earth and the traction return circuit. B7.3.3 A suitable permanent warning label should be securely attached to the equipotential bond identifying that the traction return circuit is connected to the LV supply main earth and that care needs to be taken when disconnection is required. B7.4 B7.4 Telecommunications equipment within the LV electrical installations that is not allowed to be bonded to the traction return circuit Where the LV electrical installation feeds active telecommunications equipment which requires a noise free earth to operate reliably, the LV electrical installation cpc shall not be bonded to the traction return circuit, either directly or indirectly. Where the structure of the building that houses the telecommunications equipment room is metallic so that section B7.1 would apply, the telecommunications equipment room must be segregated from the remainder of the building and provided with an isolated electrical supply, which shall be independently earthed and bonded to equipment within the segregated room. 8 Earthing requirements for LV electrical installations in DC electrified lines areas B8.1 B8.1 General The requirements for DC electrified lines traction bonding are contained in GL/RT RAILWAY SAFETY

13 Page 11 of 15 B8.1.1 The conductor rail is energised at a nominal voltage of 750 V DC. Electric trains draw power from the conductor rail with current returning to the substation via the running rails. The running rails are not deliberately earthed but allowed to float electrically about true earth. B8.1.2 As a result of the high traction current levels and corresponding volt-drop, the running rails may rise to 30 V above true earth. Also, because the running rails are not electrically insulated from the ground, the track ballast, surrounding area and the conductive framework of buildings nearby will take up a DC voltage between true earth and the running rail potential. B8.1.3 DC will flow when an earthed electrical appliance makes contact with a running rail or conductive object at running rail potential. In the case of an electrical appliance, this current will flow in the earth lead. An arc may be produced when contact between the electrical appliance and the running rail or conductive object at running rail potential occurs. Overheating is possible in the earth lead and possibly the cpc of the electrical distribution system. Also, uncontrolled DC can cause corrosion in adjacent metalwork. B8.2 B8.2 Non-electrified sidings in an electrified area Non-electrified sidings in an electrified area shall be treated as electrified lines unless fitted with insulated block joints. B8.3 B8.3 Protection against DC leakage The LV electrical installation shall prevent the adverse effects of DC leakage in the earth wire of any socket outlet, which may provide power to an electrical appliance that will be used on or near an object in contact with the running rail or other exposed conductive parts of the traction return circuit. B8.3.1 Special precautions are required where any socket outlet, within 30 m of a running rail at traction potential, may provide power to an electrical appliance to be used on or about an object in contact with the running rail. B8.4 B8.4 Protection against DC leakage entering the neutral conductor The LV electrical installation shall also prevent adverse effects from DC leakage which may enter the neutral of any other equipment or electrical distribution system because of earth faults. B8.4.1 Special precautions are required as the neutral conductor is earthed at the supply point and neutral to earth faults can remain undetected. B8.4.2 For a supply with a nominal voltage of 400 V 3 phase there should be no neutral connection at the socket outlet. Any neutral necessary for control circuits should be derived from an isolating transformer mounted on the appliance. B8.4.3 For a supply with a nominal voltage of 110 V or 230 V, the supply should be derived from a BS 3535 isolating transformer, centre tapped to earth. RAILWAY SAFETY 11

14 Page 12 of 15 Document Withdrawn as of April 2009 B8.5 B8.5 Earth monitoring or earth proving devices The detection system of earth monitoring or earth proving devices shall be protected against the effects of DC leakage. B9 Temporary low voltage electrical installations B9.1 B9.1 Temporary LV electrical installations All temporary LV electrical installations, including construction and non construction sites, shall comply with clause 604 of BS 7671 and with HSG 141. B9.2 B9.2 Temporary supply Where an LV electrical installation is to provide a temporary supply to a rail mounted vehicle the Railway Group members shall co-operate to ensure compliance with this standard. 12 RAILWAY SAFETY

15 Page 13 of 15 Appendix A LV electrical equipment within the LV electrical installations directly bonded to the AC traction return circuit LV electrical installation LV electrical equipment E (cpc) LV supply LV supply main earth Section B7.2 b) - in contact with traction return circuit N L Metallic overhead line structure Section B7.2 a) - directly bonded to traction return circuit Section B possible bond by agreement with REC Traction supply Traction supply main earth Traction return circuit Note: E (cpc) is not rated for traction fault current RAILWAY SAFETY 13

16 Page 14 of 15 Document Withdrawn as of April 2009 Appendix B LV electrical equipment within the LV electrical installations indirectly bonded to the AC traction return circuit LV electrical installation LV electrical equipment E (cpc) LV supply LV supply main earth Section B7.3 - not directly bonded to, nor in contact with, traction return circuit N L Metallic overhead line structure Traction supply Traction supply main earth Traction return circuit Note: E (cpc) is rated for traction fault current 14 RAILWAY SAFETY

17 Page 15 of 15 GL/RT1254 GI/RT7007 References Railway Group Standards and other Railway Group Documents Electrified Lines Traction Bonding Low Voltage Electrical The Catalogue of Railway Group Standards and the Railway Group Standards CD-ROM give the current issue number and status of documents published by Railway Safety. BS 88 BS 1361 BS 3535 BS 6701 BS 7671 BS EN BS EN BS EN Other References Management of Health and Safety Regulations Cartridge fuses for voltages up to and including 1000V A.C. and 1500V D.C. Specification for cartridge fuses for A.C. circuits in domestic and similar premises Isolating transformers and safety isolating transformers Code of practice for installation of apparatus intended for connection to certain telecommunication systems Requirements for Electrical Railway applications Fixed installations Part 1. Protective provisions relating to electrical safety and earthing Plugs and sockets for industrial purposes Specification for circuit breakers for overcurrent protection for household and similar installations PM29 HSG 141 HSE Guidance Notes: Electrical Hazards from Steam/Water Pressure Cleaners, etc Electrical Safety on Construction Sites RAILWAY SAFETY 15

Low Voltage Power Supplies in Electrified Areas

Low Voltage Power Supplies in Electrified Areas Low Voltage Power Supplies in Electrified Areas Synopsis This document mandates requirements for control of return and stray currents and the management of earthing for low voltage power supplies in electrified

More information

Equipotential Bonding of Rail Vehicles to Running Rail Potential

Equipotential Bonding of Rail Vehicles to Running Rail Potential Railway Group Standard Equipotential Bonding of Rail Vehicles to Running Rail Potential Synopsis This standard mandates the requirements for equipotenial bonding of rail vehicles to comply with the Electricity

More information

Compatibility Between Electric Trains and Electrification Systems

Compatibility Between Electric Trains and Electrification Systems Compatibility Between Electric Trains and Electrification Systems Synopsis Process for managing change that affects the compatibility between electric trains and electrification systems Submitted by Signatures

More information

Train Safety Systems. Railway Group Standard GM/RT2185 Issue Two Date December 2001

Train Safety Systems. Railway Group Standard GM/RT2185 Issue Two Date December 2001 Train Safety Systems Synopsis This document defines the requirements for train safety systems to enable safe operation of trains on Railtrack controlled infrastructure. Signatures removed from electronic

More information

Mechanical Trainstop Systems

Mechanical Trainstop Systems Mechanical Trainstop Systems Synopsis This document defines the functional requirements for mechanical trainstop systems and the requirements relating to their use on both track and trains. Signatures

More information

Controlling the Speed of Tilting Trains Through Curves

Controlling the Speed of Tilting Trains Through Curves Controlling the Speed of Tilting Trains Through Curves Synopsis This document mandates the means by which Tilting Trains may be operated at higher speeds than nontilting trains around curves. Signatures

More information

Interface between Rail Vehicle Weights and Underline Bridges

Interface between Rail Vehicle Weights and Underline Bridges Interface between Rail Vehicle Weights and Synopsis This document sets out the requirements for managing the risk of overloading of underline bridges by rail vehicles Submitted by Signatures removed from

More information

Rapid Response. Lineside Signal Spacing. Railway Group Standard GK/RT0034 Issue Three Date September 1998

Rapid Response. Lineside Signal Spacing. Railway Group Standard GK/RT0034 Issue Three Date September 1998 Rapid Response Railway Group Standard Lineside Signal Spacing Synopsis This Standard specifies the minimum distance that must be provided between the first signal displaying a cautionary aspect and the

More information

Code of Practice for Low Voltage Electrical Installations on Railway Network Premises

Code of Practice for Low Voltage Electrical Installations on Railway Network Premises for Low Voltage Electrical Installations on Railway Network Submitted by... K J Thompson Nominated Responsible Manager Approved by... B J Wojtas Standards Manager Authorised by... J R Mitchell Chairman,

More information

Risk Management of Rail Vehicle Axle Bearings

Risk Management of Rail Vehicle Axle Bearings Railway Group Standard Risk Management of Rail Vehicle Axle Bearings Synopsis This Railway Group Standard mandates that there shall be riskbased processes to minimise and detect failures of rail vehicle

More information

Track Circuit Assister Configuration for Rail Vehicles

Track Circuit Assister Configuration for Rail Vehicles Track Circuit Assister Configuration for Rail Synopsis This Standard mandates where TCAs shall be fitted onto a vehicle and how they shall be set up. It also contains the requirements for testing a TCA.

More information

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001 CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines.

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines. 1 PAPER 4 Sample Questions - C&G 2382 17th Edition full paper D 1 o/c 1 - A recommendation for the interval to the first periodic inspection shall be made by: a the installation electrician. b the main

More information

Signing of Permissible Speeds and Speed Restrictions

Signing of Permissible Speeds and Speed Restrictions Document to be withdrawn as of 04/06/11 Railway Group Standard published on 05/03/11 Date December 00 Signing of Permissible Speeds and Speed Restrictions Synopsis This document defines the principles

More information

GT/TDINT100 Issue: 1 Date: SEP 1993 Page 1 of 11

GT/TDINT100 Issue: 1 Date: SEP 1993 Page 1 of 11 British Railways Board Group Standard Page 1 of 11 Part A Synopsis This Directive gives the general requirements of telecommunications earthing systems, and encompasses the requirements for the earthing

More information

Title High Voltage and 1500 System Earthing References and Definitions. Reference Number PDS 02 (RIC Standard: EP SP)

Title High Voltage and 1500 System Earthing References and Definitions. Reference Number PDS 02 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title High Voltage and 1500 System Earthing References and Definitions Reference Number PDS 02 (RIC Standard: EP 12 00 00 01 SP) Document Control

More information

Company Directive STANDARD TECHNIQUE: SD4O/1. Standard HV Connection Arrangements

Company Directive STANDARD TECHNIQUE: SD4O/1. Standard HV Connection Arrangements Company Directive STANDARD TECHNIQUE: SD4O/1 Standard HV Connection Arrangements Policy Summary This document specifies the standard arrangements for HV metered connections. NOTE: The current version of

More information

RSC-G-004-B Guidelines For The Design Of Section 3 3 ELECTRIC TRACTION SYSTEMS 2

RSC-G-004-B Guidelines For The Design Of Section 3 3 ELECTRIC TRACTION SYSTEMS 2 3 ELECTRIC TRACTION SYSTEMS 2 3.1. SAFE FOR PEOPLE 2 3.1.1. Electric Traction System 2 3.1.2. Protection against unwanted access 2 3.1.3. Fencing 2 3.1.4. On bridges and other structures 2 3.1.5. At level

More information

Acceptance of Trams and Light Rail or Metro Vehicles for Shared Running on Railtrack Controlled Infrastructure

Acceptance of Trams and Light Rail or Metro Vehicles for Shared Running on Railtrack Controlled Infrastructure Acceptance of Trams and Light Rail or Metro Vehicles for Shared Running on Railtrack Controlled Infrastructure Synopsis This Standard defines the mandatory requirements for trams, light rail or metro vehicles

More information

Branding of Wheels,Tyres and Axles

Branding of Wheels,Tyres and Axles Branding of Wheels,Tyres and Axles Signatures removed from electronic version Submitted by G A Clayton Nominated Responsible Manager Synopsis This standard details the branding requirements for all wheels,

More information

ECS CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS

ECS CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS Network(s): Summary: ENGINEERING CONSTRUCTION STANDARD ECS 03-0054 CONNECTION OF LARGE LV SERVICES TO SECONDARY DISTRIBUTION SUBSTATIONS EPN, LPN, SPN This standard details the procedures to be undertaken

More information

GM/RC2532. Recommendations for Rail Vehicle Emergency and Safety Equipment. Uncontrolled When Printed. Railway Group Recommendations for GM/RT2130

GM/RC2532. Recommendations for Rail Vehicle Emergency and Safety Equipment. Uncontrolled When Printed. Railway Group Recommendations for GM/RT2130 RC Published by Rail Safety and Standards Board Evergreen House 160 Euston Road London NW1 2DX Copyright 2008 Rail Safety and Standards Board Limited GM/RC2532 Issue One: June 2008 Railway Group Recommendations

More information

Research Brief. Impact of higher 25kV fault currents. T873 - October Background. Aims

Research Brief. Impact of higher 25kV fault currents. T873 - October Background. Aims Research Brief Impact of higher 25kV fault currents Background Increasing the maximum fault levels at traction feeder stations has the potential to reduce the costs of electrification schemes. The potential

More information

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS 717.1 Scope The particular requirements of this section apply to a.c. and d.c. installations for mobile or transportable

More information

Title Low Voltage Distribution and Installations Earthing References and Definitions. Reference Number PDS 03 (ARTC Standard: EP SP)

Title Low Voltage Distribution and Installations Earthing References and Definitions. Reference Number PDS 03 (ARTC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Low Voltage Distribution and Installations Earthing References and Definitions Reference Number PDS 03 (ARTC Standard: EP 12 00 00 02 SP) Document

More information

Wilkins Safety Group

Wilkins Safety Group H & S Guidance - Electricity INTRODUCTION Each year there are almost 1000 reportable accidents at work due to contact with electricity including a significant number of fatalities (about 20 a year). Even

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

Structural Requirements For Drawgear And Buffers On Railway Vehicles

Structural Requirements For Drawgear And Buffers On Railway Vehicles Structural Requirements For Drawgear And Buffers On Railway Vehicles Submitted by D. Boocock Nominated Responsible Manager Synopsis This standard prescribes the strength requirements for drawgear and buffers

More information

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification

More information

Rolling Stock Subsystem and Interfaces to AC Energy Subsystem

Rolling Stock Subsystem and Interfaces to AC Energy Subsystem Rolling Stock and Interfaces to AC Energy Synopsis This document defines the interface requirements to the AC energy system for all rolling stock operating over the AC electrified railway. Copyright in

More information

Procedure PR D Definitions and Conventions for Electrical Safety. Engineering Procedure Electrical Distribution Unit. Version 1.

Procedure PR D Definitions and Conventions for Electrical Safety. Engineering Procedure Electrical Distribution Unit. Version 1. Engineering Procedure Electrical Distribution Unit PR D 78100 Definitions and Conventions for Electrical Safety Version 1.0 Date in Force: 26 February 2016 Procedure UNCONTROLLED COPY WHEN PRINTED Approved

More information

On-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011)

On-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) Author: IET Publications (edited by Mark Coles) Book details Author: IET Publications (edited by Mark Coles) Year: 2011 Format: Paperback,

More information

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT Date of publication: 1 November 2016Not yet published Issued by: Mark Wogan, Manager Energy Safety WorkSafe New ZealandNot yet issued Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

More information

WIRING MATTERS SEPTEMBER 2018

WIRING MATTERS SEPTEMBER 2018 WIRING MATTERS SEPTEMBER 2018 The 18 th Edition (BS 7671:2018) launch - revisited This is the second of two articles on the launch of the 18 th Edition (BS 7671:2018). The first article covered electric

More information

Control, Safe Use and Operation of Excavators, Loaders and Earth Moving Equipment

Control, Safe Use and Operation of Excavators, Loaders and Earth Moving Equipment Control, Safe Use and Operation of Excavators, Loaders and Earth Moving Equipment Page 1 of 14 Part A Synopsis A standard detailing the requirements for the control, safe use and operation of excavators,

More information

Control, Safe Use and Operation of Road-Rail Plant

Control, Safe Use and Operation of Road-Rail Plant Control, Safe Use and Operation of Page 1 of 13 Part A Synopsis A Standard detailing the requirements for the control, safe use and operation of road-rail plant in the railway environment. Approval and

More information

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and HIGH VOLTAGE METAL CLAD SWITCHGEAR WITH SPOUTS Copyright National Grid plc 2014, all rights reserved. No part of this publication

More information

The Impact of the 18 th edition (BS 7671:2018)

The Impact of the 18 th edition (BS 7671:2018) The Impact of the 18 th edition (BS 7671:2018) In this article, Geoff Cronshaw looks at some of the proposed changes in the DPC (draft for public comment) for electrical installations, focusing on Section

More information

Renewable sources of electricity a brief overview

Renewable sources of electricity a brief overview Micro generation 11 Renewable sources of electricity a brief overview THE SCOPE of the 17th Edition is wider and contains many new requirements, including additional requirements to ensure the safe connection

More information

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show.

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show. 1 PAPER 7 Sample Questions - C&G 2382 17th Edition paper C 1 o/c 1 - BS 7671 relates to permanent and temporary installations for equipment on: a marinas. b ships. c equipment on aircraft. d railway traction

More information

Key elements of the AS3000 Wiring standards and some of the recent changes.

Key elements of the AS3000 Wiring standards and some of the recent changes. Key elements of the AS3000 Wiring standards and some of the recent changes. Dean of Engineering Steve Mackay Worked for 30 years in Industrial Automation 30 years experience in mining, oil and gas, electrical

More information

WORKING NEAR OR ADJACENT TO A DC CONDUCTOR RAIL (DCCR)

WORKING NEAR OR ADJACENT TO A DC CONDUCTOR RAIL (DCCR) KEYPOINTS WORKING NEAR OR ADJACENT TO A DC CONDUCTOR RAIL (DCCR) Issue two valid from July 2017 CERTIFICATION REQUIRED: CURRENT SENTINEL CARD ENDORSED WITH PTS COMPETENCY Sentinel Cards and Track Visitor

More information

SUBSTATION INTERLOCKING SCHEMES

SUBSTATION INTERLOCKING SCHEMES SUBSTATION INTERLOCKING SCHEMES This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any losses

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links

NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links Version:- 7.0 Date of Issue:- July 2017 Page 1 of 19 NPS/001/017 Technical Specification for Low Voltage and High Voltage Current Limiting Fuse Links 1. Purpose The purpose of this document is to detail

More information

SELECT MEMBERSHIP NUMBER Full Installation 75% new and 25% alteration to exsisting

SELECT MEMBERSHIP NUMBER Full Installation 75% new and 25% alteration to exsisting The Electrical Contractors Association SELECT MEMBERSHIP NUMBER 15019 ELECTRICAL INSTALLATION CERTIFICATE (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IET WIRING REGULATIONS]) EI Copyright The

More information

EARTHING YOUR QUESTIONS ANSWERED

EARTHING YOUR QUESTIONS ANSWERED 18 EARTHING YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing

More information

The Management of Electrical Safety in Quarries, Associated Plant and Equipment

The Management of Electrical Safety in Quarries, Associated Plant and Equipment Quarries National Joint Advisory Committee (QNJAC) Plant Information Sheet 1 (Version 1, November 2015, review date: 2020) The Management of Electrical Safety in Quarries, Associated Plant and Equipment

More information

BS : C&G 2382 Outcomes 4

BS : C&G 2382 Outcomes 4 BS7671 2008: C&G 2382 Outcomes 4 Outcome 4 Protection for safety The candidate will be able to: 4.1 Identify the differences between basic and fault protection 4.2 State means of protection against electrical

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation 86 Customhouse Quay PO Box 165, Wellington 6140 New Zealand Date of publication: 1 November 2016 Issued by: Mark Wogan, Manager Energy Safety WorkSafe New Zealand Electric Vehicle Charging Safety Guidelines

More information

Permissible Track Forces for Railway Vehicles

Permissible Track Forces for Railway Vehicles British Railways Board Page 1 of 11 Part A Synopsis This document prescribes design and maintenance requirements for traction and rolling stock and for on track plant to ensure that interactive forces

More information

Procedure PR D Electrical Permits. Engineering Procedure Electrical Distribution Unit. Version 1.0. Date in Force: 4 November 2015

Procedure PR D Electrical Permits. Engineering Procedure Electrical Distribution Unit. Version 1.0. Date in Force: 4 November 2015 Engineering Procedure Electrical Distribution Unit PR D 78500 Electrical s Version 1.0 Date in Force: 4 November 2015 Procedure UNCONTROLLED COPY WHEN PRINTED Approved by: Sean Budge Manager Electrical

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3112:2011 AS/NZS 3112:2011 Australian/New Zealand Standard Approval and test specification Plugs and socket-outlets AS/NZS 3112:2011 This Joint Australian/New Zealand Standard was prepared by Joint

More information

NZQA unit standard version 8 Page 1 of 5. Apply and remove earths from conductors on electricity supply networks

NZQA unit standard version 8 Page 1 of 5. Apply and remove earths from conductors on electricity supply networks Page 1 of 5 Title Apply and remove earths from conductors on electricity supply networks Level 4 Credits 4 Purpose People credited with this unit standard are able to: demonstrate knowledge of earthing

More information

Guidelines for connection of generators:

Guidelines for connection of generators: Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

AS/NZS 3112:2004 AS/NZS

AS/NZS 3112:2004 AS/NZS AS/NZS 3112:2011 Incorporating Amendment No. 1, 2, and 3 Australian/New Zealand Standard Approval and test specification Plugs and socket-outlets Superseding AS/NZS 3112:2004 AS/NZS 3112:2011 AS/NZS 3112:2011

More information

Initial and Periodic Inspection and Testing of Electrical Installations ( ) Sample Test

Initial and Periodic Inspection and Testing of Electrical Installations ( ) Sample Test Initial and Periodic Inspection and Testing of Electrical Installations (2391-052) Sample Test Version 1.1 January 2018 Please note this is not a complete sample theory exam, this document consists of

More information

Steve Summers Region Sales Manager

Steve Summers Region Sales Manager Steve Summers Region Sales Manager Institute For Animal Healthcare LV Switchgear Package Package Subs LV Switchboards PDU s LV sub Distribution MCC s MV Switchgear Established in 1972 manufacturing control

More information

Control, Safe Use and Operation of Forklift Trucks and Sideloaders

Control, Safe Use and Operation of Forklift Trucks and Sideloaders Control, Safe Use and Operation of Forklift Trucks and Sideloaders British Railways Board Page 1 of 12 Part A Synopsis A standard detailing the requirements for control, safe use and operation of forklift

More information

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( )

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( ) Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 (2382-18) March 2018 Version 1.0 FAQs 1 18 th Edition IET Wiring Regulations 2018 FAQs When will the 18 th Edition of BS 7671

More information

Rail Industry Standard for 750 V and 1500 V DC Overhead Lines and corresponding Rolling Stock requirements

Rail Industry Standard for 750 V and 1500 V DC Overhead Lines and corresponding Rolling Stock requirements for 750 V and 1500 V DC Overhead Lines and corresponding Rolling Stock requirements Synopsis This document specifies requirements and associated rationale and guidance at the interface between energy subsystems

More information

Technical Specification 43-8 Issue Amendment

Technical Specification 43-8 Issue Amendment PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 43-8 Issue 4 2015 + Amendment 1 2016 Overhead line clearances www.energynetworks.org PUBLISHING AND COPYRIGHT

More information

EDS CUSTOMER LV INSTALLATION EARTHING DESIGN

EDS CUSTOMER LV INSTALLATION EARTHING DESIGN Document Number: EDS 06-0017 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 06-0017 CUSTOMER LV INSTALLATION EARTHING DESIGN EPN, LPN, SPN This standard provides guidance on the earthing of customer

More information

A guide for the connection of a low voltage installation to The Guernsey Electricity Network

A guide for the connection of a low voltage installation to The Guernsey Electricity Network A guide for the connection of a low voltage installation to The Guernsey Electricity Network Guernsey Electricity Limited (GEL) - January 2017 2 Contents Definitions 3 Introduction 5 Scope 6 Sections 1

More information

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED PART B-07 TITLE: SERVICE CONNECTIONS SPECIFICTION NO: B-07 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 3 YEAR PERIOD) AMENDMENTS / REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

Electrical safety and you

Electrical safety and you Electrical safety and you Electrical safety and you Introduction Electricity can kill. Each year about 1000 accidents at work involving electric shock or burns are reported to the Health and Safety (HSE).

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

ELECTRICIANS REGULATIONS EXAMINATION 30 June 2012 QUESTION AND ANSWER BOOKLET

ELECTRICIANS REGULATIONS EXAMINATION 30 June 2012 QUESTION AND ANSWER BOOKLET ER47 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 30 June 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Int Time Allowed: Three

More information

EDS SUBSTATION LVAC SUPPLIES

EDS SUBSTATION LVAC SUPPLIES Document Number: EDS 08-1112 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 08-1112 SUBSTATION LVAC SUPPLIES The standard details the requirements and options for the provision of LVAC

More information

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,

More information

Estimation of electrical losses in Network Rail Electrification Systems

Estimation of electrical losses in Network Rail Electrification Systems Estimation of electrical losses in Network Rail Electrification Systems Page 1 of 16 Contents 1. BACKGROUND...3 2. PURPOSE...3 3. SCOPE...3 4. DEFINITIONS & ABBREVIATIONS...4 5. NETWORK RAIL INFRASTRUCTURE

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3001:2008 (Incorporating Amendment No. 1) AS/NZS 3001:2008 Australian/New Zealand Standard Electrical installations Transportable structures and vehicles including their site supplies AS/NZS 3001:2008

More information

GM/RC2495. Recommendations for Railway Wheelset Manufacture and Assembly. Railway Group Recommendations for GM/RT2466.

GM/RC2495. Recommendations for Railway Wheelset Manufacture and Assembly. Railway Group Recommendations for GM/RT2466. RC Published by Rail Safety and Standards Board Evergreen House 160 Euston Road London NW1 2DX Copyright 2008 Rail Safety and Standards Board Limited GM/RC2495 Issue One: August 2008 Railway Group Recommendations

More information

Uncontrolled When Printed Supersedes GERT8000-DC Iss 2 on 01/03/2014. Module DC. GE/RT8000/DC Rule Book. DC electrified lines. Issue 3.

Uncontrolled When Printed Supersedes GERT8000-DC Iss 2 on 01/03/2014. Module DC. GE/RT8000/DC Rule Book. DC electrified lines. Issue 3. GE/RT8000/DC Rule Book Module DC DC electrified lines Issue 3 March 2014 Comes into force 07 June 2014 Conventions used in the Rule Book Example A black line in the margin indicates a change to that rule

More information

EDS CUSTOMER LV INSTALLATION EARTHING DESIGN

EDS CUSTOMER LV INSTALLATION EARTHING DESIGN Document Number: EDS 06-0017 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 06-0017 CUSTOMER LV INSTALLATION EARTHING DESIGN EPN, LPN, SPN This standard provides guidance on the earthing of customer

More information

BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012

BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012 BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012 3.1.2 re batteries secure against excessive movement in any direction? R Check by visual assessment the

More information

Major changes within the New 18 th Edition Wiring Regulations announced by The IET

Major changes within the New 18 th Edition Wiring Regulations announced by The IET Major changes within the New 18 th Edition Wiring Regulations announced by The IET BS 7671:2018 Requirements for Electrical Installations will be issued on 2 nd July 2018 and is intended to come into effect

More information

Effective discrimination of protective devices

Effective discrimination of protective devices Effective discrimination of protective devices In the event of a fault occurring on an electrical installation only the protective device nearest to the fault should operate,leaving other healthy circuits

More information

Electrical Awareness and Considerations

Electrical Awareness and Considerations Electrical Awareness and Considerations By David Taylor FIHE MIET IEng Objectives Awareness of specifications. Awareness of Distribution Network Operators (DNO) earthing arrangements. Awareness of basic

More information

Network Safeworking Rules and Procedures

Network Safeworking Rules and Procedures Network Safeworking Rules and Procedures Working around Electrical Rule Number: 2017 Version 1.0, 31 March 2016 Working around Electrical Rule Number: 2017 Document Control Identification Document title

More information

MCST LIGHTING AND POWER DESIGN AND CONSTRUCTION

MCST LIGHTING AND POWER DESIGN AND CONSTRUCTION Engineering Standard- Design Structures & Facilities MCST 000002-01 Version: 3 Issued: May 2016 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT MAY NOT BE UP-TO-DATE; REFER

More information

SOUTH AFRICAN NATIONAL STANDARD. Plug and socket-outlet systems for household and similar purposes for use in South Africa

SOUTH AFRICAN NATIONAL STANDARD. Plug and socket-outlet systems for household and similar purposes for use in South Africa ISBN 978-0-626-27016-2 SANS 164-1:2012 SOUTH AFRICAN NATIONAL STANDARD Plug and socket-outlet systems for household and similar purposes for use in South Africa Part 1: Conventional system, 16 A 250 V

More information

Books. Code of Practice for In-Service Inspection and Testing of Electrical Equipment (3rd edition) By IET Publication

Books. Code of Practice for In-Service Inspection and Testing of Electrical Equipment (3rd edition) By IET Publication Books Code of Practice for In-Service Inspection and Testing of Electrical Equipment (3rd edition) By IET Publication Available: 2008 Format: Paperback Product Code: PWR08630 ISBN: 978-0-86341-833-4 Pagination:

More information

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient

More information

The Project North West Electrification Programme

The Project North West Electrification Programme Assessment of Technical Specifications for Interoperability on Projects Background The European Union has mandated moving towards interoperable railways to lower boundaries for cross-eu running of trains.

More information

ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION

ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION 23 June 2018 Time Allowed: 2 Hours ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION Check the label on the back of this paper to ensure you have your paper. INSTRUCTIONS READ CAREFULLY You have

More information

Module M4. Floods and snow. GE/RT M4 Rule Book. Issue 1. June 2003

Module M4. Floods and snow. GE/RT M4 Rule Book. Issue 1. June 2003 GE/RT8000 - M4 Rule Book Module M4 Floods and snow Issue 1 June 2003 Comes into force 6 December 2003 Issue Date Comments Comes into force 1 June 2003 Initial issue 6 December 2003 Copyright 2003 Railway

More information

2 x 25 kv ac / 1 x 25 kv ac Grounding and Bonding

2 x 25 kv ac / 1 x 25 kv ac Grounding and Bonding 2 x 25 kv ac / 1 x 25 kv ac Grounding and Bonding By George Ardavanis, PhD Keywords: overhead catenary system (OCS), electric multiple unit (EMU), grounding and bonding (G&B), overhead contact line (OCL),

More information

ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010

ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010 Candidate Code No. Result Date Int For Board Use Only ER38 Version of AS/NZS 3000 used (tick ONE Box) 2000 2007 & Amend 1 ELECTRICIAN S REGULATIONS EXAMINATION 26 June 2010 QUESTION AND ANSWER BOOKLET

More information

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2 Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL

More information

STANDARD TECHNIQUE : SD5P/2

STANDARD TECHNIQUE : SD5P/2 Company Directive STANDARD TECHNIQUE : SD5P/2 Design of Un-metered Connections ST:SD5P/2 7 th December 2009-1 of 10 - 1.0 INTRODUCTION This document specifies the requirements for the design of un-metered

More information

Title Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP)

Title Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category General Title Reference Number PMP 01 (RIC Standard: EP 00 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards and

More information

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and Guidance WASHING HIGH VOLTAGE INSULATORS USING PORTABLE WASHING EQUIPMENT Copyright National Grid plc 2014, all rights reserved.

More information

AS/NZS 3131:2001 AS/NZS

AS/NZS 3131:2001 AS/NZS AS/NZS 3131:2015 Australian/New Zealand Standard Approval and test specification Plugs and socket-outlets for stationary appliances Superseding AS/NZS 3131:2001 AS/NZS 3131:2015 AS/NZS 3131:2015 This joint

More information

Reviewed: DD Month University Code of Practice for Electrical Safety. PART B - Design and Construction of Electrical Equipment within the University

Reviewed: DD Month University Code of Practice for Electrical Safety. PART B - Design and Construction of Electrical Equipment within the University Safety Office Reviewed: 17 July 2012 Reviewed: DD Month University Code of Practice for Electrical Safety PART B - Design and Construction of Electrical Equipment within the University The purpose of this

More information

Element C8.3 Installation, Use and Inspection of Electrical Systems

Element C8.3 Installation, Use and Inspection of Electrical Systems .3 Installation, Use and Inspection of Electrical Systems Duty Holders Electricity at Work Regs 1989 EWR Employers and Self Employed Comply with regs as far as they are under their control Managers of

More information

Rail Safety and Standards Board

Rail Safety and Standards Board Rail Safety and Standards Board Certificate of Derogation from a Railway Group Standard (under 8.3 of the Railway Group Standards Code) Derogation Number: Applicant: Subject Matter of Derogation: RGS Number:

More information