ADDENDUM NUMBER 2 (DATED May 7, 2012) TO THE CONTRACT DOCUMENTS AND CONSTRUCTION SPECIFICATIONS FOR WINDSOR CRUDE OIL TERMINAL
|
|
- Shanna Burke
- 5 years ago
- Views:
Transcription
1 ADDENDUM NUMBER 2 (DATED May 7, 2012) TO THE CONTRACT DOCUMENTS AND CONSTRUCTION SPECIFICATIONS FOR WINDSOR CRUDE OIL TERMINAL From: Michael Brake, JR Engineering To: All Plan holders and/or Prospective Bidders. The following revisions, additions and/or deletions are hereby made a part of the Contract Documents and plans for the above referenced project as fully and completely as if the same were fully set forth therein: BIDDING REQUIREMENTS Bidders are required to acknowledge receipt of this Addendum by replying to the notification . RESPONSES TO BIDDER QUESTIONS 1. Information from SafeRack says there will be (5) safety showers installed at ground level, however they are not shown on the drawings. Do we include pricing for the installation and connections? Do we use the water lines from above to make the connections? Include pricing for installation and connection of five (5) showers per the SafeRack drawings. Use the potable water service line under the rack to make the connections. 2. DWG 45 of 47 shows vapor connections on top of 4 strainer on details A&B. What sizes are these lines, how do we connect to the vapor lines? The detail is revised to show the connections. 3. DWG 45 of 47 in reference to the 4 flex product hoses. Detail says qty of 24 however there are only 12 shown on drawings 40 & 41 and the bid schedule only calls for 12. Where do the other 12 go? Are they spares? The Crude and Condensate lines each have 12 product hose assemblies. 4. DWG 45 of 47, Where do the 2 flex recovery hoses get installed? The 2 flex recovery hoses connect to the return line under the rack. 5. What supports are required for the vapor line VP-04 None are shown on DWG S-11. Detail 4/S16 may be used for support of vapor line VP-04, modified with a 3-0 concrete pier depth. 6. Please furnish vapor line drop detail at truck unloading area. A Detail has been provided on sheet Connections to the existing tanks. Are the connections on the tank existing? If not, are we installing the nozzles on the tanks and are the tanks cleaned and ready? Connections are existing and are cleaned and ready. 8. DWG 45 of 47 No meter prover connections shown. Meter Provers are on main meter. Page 1
2 9. DWG 45 of 47 No pressure gauges shown. There are no pressure gauges on connecting lines, only on pump skids. 10. Do we figure garlock or flexitalic gaskets? Garlock Gylon Style 3500 or equivalent are acceptable. 11. DWG 17 of 47 Please confirm the track pans all connect to each other and have one drain at the end of the run. Who provides and installs the track pans? We have experienced numerous issues with these pans due to them having multiple connections which fail over time. Is the owner open to alternates in lieu of the Ultra track pans? Alternate manufacturers of the rail car spill containment pans will be considered on a case-by-case basis provided the proposed pans meet SPCC regulations. The general concept of spill containment will remain the same. The track pans will need to be connected and drain to a common discharge point and go to the containment tank. 12. S12 and S13 of 16 Vapor line supports. The 4 vapor line is shown to be supported by supports up to 49 tall and made from pipe sizes 8 up to 20. Is the owner willing to drop the vapor line down to ground level and use a blower system? No, the elevated vapor line will be used. 13. Are catwalks for LACT tanks furnished by the owner with the owner furnished tanks? If not please provide drawings for the catwalk structure. The catwalk structure is provided by the owner and is supported from the L.A.C.T. tanks. Details will be provided by the owner. Provide a concrete pad at the bottom of the stairs as indicated for the SafeRack stairs (detail shown on sheet S3). All parts are bolted connections. Kicker plates are bolted to the tanks. The manufacturer will forward the required ½ bolts and nuts for assembly in the field. A materials list for assembly will be provided as soon as it is available. 14. What foundations are required for the LACT tank catwalk? See response to Question Reference bid schedule # 72 Concrete column stubs : 76 are at the Saferack foundation cap beams. Where are the other 12 located? The count on Concrete Column Stubs and SafeRack Base Plates should be Do the vapor line foundations get screw piles as well? The screw piles are being utilized at the SafeRack foundation to control settlement. The vapor line structure can tolerate more settlement, therefore screw piles are not required at the vapor line support structure. 17. Who is supplying the flare and the knockout pots? Owner 18. Who furnishes the propane tank for the flare gas assist? Owner 19. Does the propane tank get a heater for winter operations? Not at this time 20. Does any of the piping and valves need to be furnished per cold weather specifications? Yes. All materials need to be rated to -30 F. Page 2
3 21. Can you please provide cut sheets for the crude loading skids and the LACT skids? Sheets for the crude loading skid is not yet available. Sheets for the LACT Skids are attached. CLARIFICATIONS Electronic Specifications File An electronic version of the material specifications are provided for your use on the FTP site. Instructions for accessing the FTP site are as follows: Directions For Using The FTP Site 1. Go to: ftp://ftp.westrian.com in Internet Explorer 2. Input login information: User Name: jrguest Password: jrengineering 3. Go to the folder named Windsor Crude Oil Terminal. LACT Tanks Catwalk Shop Drawings for the LACT Tank catwalk will be provided as soon as they are available. END OF ADDENDUM NUMBER 2 Page 3
4 Know what's
5 Windsor Crude Oil Terminal Musket Corporation ITEM NO. DESCRIPTION MFR / PART No. Light Fixture, (Overhead) [2 per pole] McGraw-Edison Light Fixture, (Flood Lights) Cooper Lighting 1" PVC C900 Service Line JM Eagle 3" Steel Tee 3" Welded Steel Pipe [Casing Pipe] PermaPipe 1"x3/4" Reducer 16"x8" Reducer (M.J.) 20"x16" Tee (M.J.) 8" PVC C900 Water Main JM Eagle 6" DIP [Fire Hydrant Lateral] US Pipe 4" PVC C900 [Casing Pipe] JM Eagle 6" Gate Valve (M.J.) Mueller 2360 Series Resilient Wedge Ductile Iron 8" 90 Bend (M.J.) 8" Gate Valve (M.J.) Mueller 2360 Series Resilient Wedge Ductile Iron 8" Tapping Saddle Romac Industries 304 Series 8"x6" Reducer (M.J.) 8"x6" Tee (M.J.) Pipe Hangers (3") Piping Technology and Products Adjustable Band Hanger Pipe Hangers (4") Piping Technology and Products Adjustable Band Hanger Pipe Hangers (8") Piping Technology and Products Adjustable Band Hanger Unloading Area Slop Line Assembly (1" Welded Steel Pipe, Gate Valves, 500 Gal Slop Tank, and Pump) 1" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 1" Elbow 1" Welded Steel Pipe Sch 40 PermaPipe Tank WE-MAC Tanks Ko-101 Pump with motor Red Jacket P75 SI 4" Welded Steel Pipe (A53B ERW Type E) [Vapor Line] PermaPipe 4" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 4" Welded Steel Pipe (A53B ERW Type E) [Recovery and Return Piping] PermaPipe 8" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 10" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 12" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 12" Welded Steel Pipe [Casing Pipe] PermaPipe 18" Welded Steel Pipe [Casing Pipe] PermaPipe 20" Welded Steel Pipe [Casing Pipe] PermaPipe 4" 22.5 Bend (A53 Grade B) 4" 45 Bend (A53 Grade B) 4" 90 Bend (A53 Grade B) 8" 45 Bend (A53 Grade B) 8" 90 Bend (A53 Grade B) 10" 45 Bend (A53 Grade B) 10" 90 Bend (A53 Grade B) 12" 22.5 Bend (A53 Grade B) 12" 45 Bend (A53 Grade B) 12" 90 Bend (A53 Grade B) 4" Tee (A53 Grade B) 4" Wye (A53 Grade B) 4" Cross (A53 Grade B) 4"x8" Tee (A53 Grade B) 8" Tee (A53 Grade B) 8" Cross (A53 Grade B) 8"x10" Tee (A53 Grade B) 10" Tee (A53 Grade B) 10"x12" Tee (A53 Grade B) 12" Tee (A53 Grade B) 4" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 4" Check Valve Cla-Val Series 581
6 8" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 10" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 12" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 10"x8" Reducer 12"x10" Reducer 8"x4" Reducer 4" Expansion Coupling with Limit Rods Romac EJ400 Series 8" Expansion Coupling with Limit Rods Romac EJ400 Series Offloading Drop Assembly [Drum, Fittings, Valves, Strainer, Adapter, and all appurtenances] Containment Drum, HDPE, 40 gal min. - 3"x4" Tee 3" Elbow 3" Basket Strainer w/air Eliminator, 150#, RF, Carbon Steel Liquid Controls 3" Isolation Adapter 3" Plug Valve ValMatic 5800 Series 3" Hose Connector Dixon Primer for all pipes Sherwin-Williams Epoxy Zinc Primer Paint, for All Above Ground Product and Product Casing Pipes Sherwin-Williams Acrolon 218 -Y Paint, for All Vapor and Vapor Casing Pipes Sherwin-Williams Acrolon 218 -O Railroad Track Spill Containment Pans Leading Innovative Products and Solutions Concrete Vault, 12'x6'x6' [South Recovery Vault] Vaughn Concrete Concrete Vault, 6'x6'x6' [SafeRack and Railroad Containment] Vaughn Concrete Steel Tank, Single Wall (1,000 Gal) Eaton Sales and Service Pump (SafeRack and Railroad Containment Tank) and all Appurtenances Red Jacket P75 SI Pumps (SafeRack South Recovery Tank) and all Appurtenances Red Jacket P75 SI Knockout Tank (500 Gal) WE-MAC Tanks Ko-101 Knockout Tank Pumps Red Jacket P75 SI Crude Loading Arm Assembly [Meter provided by owner] Sight Glass, 4", 150#, RF Ball Valve, 4", 150#, RF, Carbon Steel, Full Port Check Valve, 4", 150#, RF, Carbon Steel, Removeable Seat Temperature Probe and Transducer Solenoid Control Valve, 4", 150#, RF Flow Control Valve, 4", 150#, RF, Carbon Steel, Solenoid Basket Strainer w/air Eliminator, 4", 150#, RF, Carbon Steel Condensate Loading Arm Assembly Sight Glass, 4", 150#, RF Ball Valve, 4", 150#, RF, Carbon Steel, Full Port Solenoid Control Valve, 4", 150#, RF Check Valve, 4", 150#, RF, Carbon Steel, Removeable Seat Temperature Probe and Transducer Flow Control Valve, 4", 150#, RF, Carbon Steel, Solenoid Basket Strainer w/air Eliminator, 4", 150#, RF, Carbon Steel Dixon 5200-SFI-4" Kuka CBA15-4" Wheatley 9D * Trerice Cla-Val Series FMC Technologies 455 series Liquid Controls Dixon 5200-SFI-4" Kuka CBA15-4" Cla-Val Series Wheatley 9D * Trerice FMC Technologies 455 series Liquid Controls Vapor Loading Arm Assembly Flame Arrestor, 4", 150#, RF, Carbon Steel Varec " Adapter Dixon 200-AL-AL 4"x2" Reducer 2" 90 Elbow 4" Product Hose Assembly 4" Flex Hose Parker Industrial 7307 Series 4" Butterfly Valve ABZ Series 402 4" Swing Check Valve Cla-Val Series 580 4" Valve Coupler Dixon 400 DL-DL 4" Sight Glass Dixon 5200-SFI-4" 4" Butterfly Valve (Wet/Dri) Betts WD401 AL V 4" Swivel Tank Car Connection Dixon RTCA40 4" Flanged Combo Nipple Dixon FST40 4" Male Adapter Dixon 400-AL-AL 4" Recovery Loading Arm Assembly 4" Flex Hose Parker Industrial 7307 Series 4" Valve Coupler Dixon 400 DL-DL 4" Sight Glass Dixon 5200-SFI-4" 4" Butterfly Valve (Wet/Dri) Betts WD401 AL V 4" Swivel Tank Car Connection Dixon RTCA40 4" Male Adapter Dixon 400-AL-AL 1" Air Fitting Dixon 2" Vapor Hose Assembly 2" Flex Hose Parker Industrial 7208 Series 2" Valve Coupler Dixon 200-C-AL
7
8
ATTACHMENT I BID SCHEDULE IFB NO , CHURCH FARMS EAST STORAGE TANK AND BOOSTER PUMP STATION
ATTACHMENT I BID SCHEDULE IFB NO. 19-021, CHURCH FARMS EAST STORAGE TANK AND BOOSTER PUMP STATION Item No. Description Qty Unit Unit Cost Amount Pump Station Site Work 1 Site Demolition / Removals / Haul
More informationAPPROVED MATERIALS LIST SERVICE MATERIALS July 2017 **REVISED 12/6/17**
APPROVED MATERIALS LIST SERVICE MATERIALS July 2017 **REVISED 12/6/17** SIZE DESCRIPTION MANUFACTURER & MODEL NUMBER CORPORATION STOPS 1" MIP x GRIP Comp ball corp stop Ford: FB 1100-4Q McDonald: 74704-BQ
More informationSECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems.
SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS A. Section 099000
More information$69, $63, $63, $62, Schedule B - PIP & C905 Pipe
Supplier Bid Bond Signed Proposal Form Signed Addendum #1 Subtotal (Items 1-5) Subtotal (Items 1-5) Sales tax @ 8.3% Subtotal (Items 1-56) Subtotal (Items 1-3) Subtotal (Items 1-41) 2015-2016 ELIPS Pipe
More informationCITY OF SAN DIEGO PUBLIC UTILITIES DEPARTMENT APPROVED MATERIALS LIST TABLE OF CONTENTS
CITY OF SAN DIEGO PUBLIC UTILITIES DEPARTMENT TABLE OF CONTENTS SYSTEM Page A. Bronze Water Service Fittings.... 3 Corporation Stop, Curb Stop, Property Valve, Coupling, Compression Fittings, Adaptors,
More informationVALVES, FIRE HYDRANTS, AND APPURTENANCES
VALVES, FIRE HYDRANTS, AND APPURTENANCES PART 1 - GENERAL 1.01 SECTION INCLUDES A. Butterfly Valves B. Gate Valves C. Tapping Valve Assemblies D. Fire Hydrant Assemblies E. Flushing Devices (Blowoffs)
More informationWinning Bid US Petroleum Equipment Walts Petroleum Northwest Petroleum Petro-Chemical Systems Kimberly Green Bay Wausau Fond Du Lac
Minimum Specifications/Questionnaire Bid Results for One (1) New Fuel Dispensing System-Larrabee Shop Winning Bid PERMIT FEES, FORMS, PLANS and NOTIFICATIONS Secure all necessary state and local permits
More informationABS-0918 SUPERSEDES ABS-0318 ASTM D2661 R/SEPT ABS DWV FITTINGS.
ABS-0918 SUPERSEDES ABS-0318 ASTM D2661 R/SEPT. 2018 ABS DWV FITTINGS www.bow-group.com COUPLING 1 1/4" 601112 125 9,000 5.63 1 1/2" 601120 125 9,000 3.48 2" 601138 100 4,800 4.65 3" 601146 45 1,440 13.07
More informationABS DWV FITTINGS ABS-1116 NOVEMBER 2016 SUPERCEDES ABS-1215 ASTM D2661
ABS DWV FITTINGS ABS-1116 NOVEMBER 2016 SUPERCEDES ABS-1215 ASTM D2661 COUPLING 1 1/4" 601112 125 9,000 3.36 1 1/2" 601120 125 9,000 2.25 2" 601138 100 4,800 3.03 3" 601146 45 1,440 8.49 4" 601153 25 800
More informationHarlingen Water Works System Approved Products List For Subdivisions. January 11, 2005
Harlingen Water Works System Approved Products List For Subdivisions January 11, 2005 Revised March 24, 2016 Harlingen Water Works System Approved Products List for Subdivisions Table of Contents: 1. Valves
More informationCAST IRON FITTINGS STANDARD
060-1 CAST IRON FITTINGS STANDARD ITEM 1/4" 3/8" 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 90 ELL 11.03 15.95 6.99 7.29 8.62 12.24 16.93 26.45 90 REDUCING ELL * 22.20 14.69 12.27 15.44 31.19 41.74 45 ELL 13.59 14.60
More informationMATERIAL SPECIFICATIONS AND BID PROPOSAL SHEET
CATEGORY 1: STEEL COUPLINGS 0 ¾" Steel Couplings (Smith-Blair #411-0501-003) 20 1" Steel Couplings (Smith-Blair #411-013201-003) 20 1¼" Steel Couplings (Smith-Blair #411-016601-003) 20 2" Steel Couplings
More informationElectrical Applications. Metal Framing & Cable Tray Superstrut Metal Framing System. Column A. Design Data: Materials: Column B
Electrical Raceway Series 800 Surface Raceway and Lighting Systems Superstrut channel together with snap-in closure strip is listed by Underwriters Laboratories as a surface metal raceway. Other accessories
More informationELIPS Pipe Materials Bid Summary August 29, :00am Bid Opening
2013-2014 ELIPS Pipe Materials Bid Summary August 29, 2013 11:00am Bid Opening Supplier Bid Bond Signed Proposal Form Addendum No. 1 Subtotal (Items 1-5) Sales tax @ 7.9% Total Bid Amount Subtotal (Items
More informationPUBLIC UTILITIES DEPARTMENT CITY OF SAN DIEGO APPROVED MATERIALS LIST FOR WATER STAN MEDINA DEPUTY DIRECTOR WATER OPERATIONS. u f! ASSISTANT DIRECTOR
PUBLIC UTILITIES DEPARTMENT CITY OF SAN DIEGO FOR WATER STAN MEDINA DEPUTY DIRECTOR WATER OPERATIONS DEPUTY DIRECTOR ENGINEERING & PROGRAM MANAGEMENT u f! u~~~ 7 STAN GRIFFITH ASSISTANT DIRECTOR DISTRIBUTION
More informationPROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA
The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS
San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS 834.1 DESCRIPTION: This item shall consist of fire hydrant installations using joint restraints in accordance
More informationPB18 Series Portable Pump Assembly Service Parts List
Document Number Issue Date 09/20/94 Rev. Date 02/02/12 PB18 Series Portable Pump Assembly Service Parts List Index: Component Pump Model (Located on Pump Serial Plate) See Page PB18-2515, PB18-2515B 2,
More informationWILKINSBURG-PENN JOINT WATER AUTHORITY DUCTILE IRON PIPE AND ACCESSORIES BID TABULATIONS CONTRACT NO
WILKINSBURG-PENN JOINT AUTHORITY UNIT # 1- PIPE AND MJ FITTINGS & TAYLOR 1A 6 RON PIPE, CLASS 52 no bid no bid 11.98 12.61 14.23 no bid no bid 13.40 14.93 1B 8 RON PIPE, CLASS 52 16.94 17.83 20.12 17.83
More information2. Compartments 2 compartments with gallons front to rear with double bulkheads
January 10, 2016 STE # 11602 & 11605 (Ref. QT 3098/STE#10741-10744) ST&E SPECIFICATIONS FOR 4,000 US GALLON DOT-407 DOUBLE CONICAL STAINLESS STEEL INSULATED TWO COMPARTMENT TANDEM TRANSPORT TANK PREPARED
More informationORDERING: Specify size, figure number, description, nominal pipe size or special O.D. and C-to-C dimension. C - C LOAD lb.
Fig. 2110 www.pipingtech.com/fig2110 Sway Strut with 4 of Adjustment Engineered spring supports option 1 option 2 ORDERING: Specify size, figure number, description, nominal pipe size or special O.D. and
More informationPIPE OUTSIDE DIAMETER GUIDE
June 7, 2018-1 PIPE OUTSIDE DIAMETER GUIDE PIPE OUTSIDE DIAMETER GUIDE - SMALL DIAMETER PIPE SIZES NOMINAL PIPE SIZES 1 /2" 3 /4" 1" 1 1 /4" 1 1 /2" 2" 2 1 /2" THIS O.D. GUIDE IS FOR YOUR CONVENIENCE &
More information***************************************************************************************************************
15515 VALVES, HANGERS, AND SPECIALTIES *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number:23 21 16 ***************************************************************************************************************
More informationLATEST ARRIVALS CATALOGUE STOCK
LATEST ARRIVALS CATALOGUE STOCK PIPES VALVES FLANGES & FITTINGS IN CARBON STEEL STAINLESS STEEL LATEST ARRIVALS!!!!!! VALVE PRODUCTS CAST IRON WAFER TYPE BUTTERFLY VALVE, PINLESS SHAFT, DUCTILE NICKEL
More information2150 F&I 4" PVC pipe LF 100 $ F&I 6" PVC pipe LF 100 $ F&I 8" PVC pipe LF 100 $ 90.00
1 of 5 2100 F&I 4" ductile iron pipe LF 200 $ 143.00 $28,600.00 2102 F&I 6" ductile iron pipe LF 200 $ 135.00 $27,000.00 2104 F&I 8" ductile iron pipe LF 200 $ 141.00 $28,200.00 2105 F&I 10" ductile iron
More informationABS-C0717 JULY 2017 SUPERSEDES ABS-C0217 CSA B181.1 ABS DWV FITTINGS.
ABS-C0717 JULY 2017 SUPERSEDES ABS-C0217 CSA B181.1 ABS DWV FITTINGS www.bow-group.com dimension item Ctn Skid list price dimension item Ctn Skid list price SANITARY TEE (Hub x Hub x Hub) 1 1/4" 600007
More informationApproved Branded Traceable Fire Protection & Waterworks Valves
Approved Branded Traceable Fire Protection & Waterworks Valves (800) 766-0076 www.smithcooper.com Los Angeles, CA Atlanta, GA Vancouver, WA Chicago, IL AWWA C515 Compliant CONSIDER Your Options Tamper
More informationADDENDUM No. 1 Prospective Bidders
Page 1 of 1 Attachment to Addendum # 1 Revised Itemized Bid ADDENDUM No. 1 TO: Prospective Bidders FROM: Gregory Tate, Construction Contracts Administrator DATE: January 24, 2019 PROJECT: Traffic Signal
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS
San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS 834.1 DESCRIPTION: This item shall consist of fire hydrant installations using joint restraints in accordance
More informationPEI/RP Recommended Practices for Installation of Bulk Storage Plants
PEI/RP800-08 Recommended Practices for Installation of Bulk Storage Plants Recommended Practices for Installation of Bulk Storage Plants CONTENTS Foreword...iii. SECTIONS 1. Introduction Page 1.1 Background...1
More informationPVC Couplings. Brass Couplings BRASS COMPRESSION COUPLING 3 -LENGTH PVC COMPRESSION COUPLING BRASS COMPRESSION COUPLING 5 -LENGTH
& FITT Brass Couplings BRASS COMPRESSION COUPL 3 -LENGTH 46331 3/8 1/2 12 120 5.80 46332 1/2 3/4 12 120 7.38 46333 3/4 1 6 72 10.52 46334 1 1 1/4 6 60 13.44 46335 1 1/4 1 1/2 4 48 18.00 46336 1 1/2 4 36
More informationJanuary 2007 Approval Guide Fixed Extinguishing Systems 5-57
Fixed Extinguishing Systems 5-57 CHEMETRON Fire Systems, 4801 Southwick Dr, 3rd Floor, Matteson IL 60443 High Pressure System Equipment. Automatic Actuator. 1-026-02, -0250. Alarm. 1-003-0033, -0070, -0071,
More information1. All piping shall have flow arrows indicating direction of flow.
PART 1: GENERAL 1.01 Scope of Standards A. This design guidelines contained herein includes the requirements for systems, materials, fittings and valves utilized for piping systems at Texas State University.
More informationSUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION WATER DISTRIBUTION VALVES
SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION 33 12 16 WATER DISTRIBUTION VALVES PART 1 GENERAL... 2 1.1 Description... 2 1.2 Reference Specifications, Codes, and
More informationSpecification Sheet Form Rev
Sales Administration Use Only Customer Quote Number Quote Revision Shop Order Number Serial Number(s) Date : Customer Name Salesperson Model : Salesperson Name : 8400 DDC S1 Part / Drawing Number : 730-8400
More informationSee our expanding selection of products on Product Portfolio
See our expanding selection of products on www.fnw.com Product Portfolio Table of Contents Low Lead Products- Page 3 Ball Valves, Check Valves, Strainers, Water Hammer Arrestors Ball Valves, Brass - Page
More informationABS-C0219 FEB SUPERSEDES ABS-C0717R CSA B181.1 ABS DWV FITTINGS.
ABS-C0219 FEB. 2019 SUPERSEDES ABS-C0717R CSA B181.1 ABS DWV FITTINGS www.bow-group.com DIMENSION ITEM CTN SKID LIST PRICE DIMENSION ITEM CTN SKID LIST PRICE SANITARY TEE (Hub x Hub x Hub) 1 1/4" 600007
More informationthis equipment. Does Not
SPECIFICATIONS FOR THE SUPER SEALCOATER 550 TRAILER MOUNTED SEALCOAT APPLICATOR 420 N. Roosevelt Ave. Chandler AZ 85226 +1 800 528 8242 +1 602 276 0406 FAX +1 480 961 0513 www.crafco.com MARCH 2014 The
More informationCATALOG OF REPLACEMENT PARTS C24GA6 & C24GA10 GAS CONVECTION STEAMERS PRIOR MLS COVERED IN THIS MANUAL
CATALOG OF REPLACEMENT PARTS C24GA6 & C24GA10 GAS CONVECTION STEAMERS C24GA6 C24GA10 ML-136056 ML-136057 PRIOR MLS COVERED IN THIS MANUAL C24GA6 C24GA10 ML-136021 ML-136022 For additional information on
More informationCATALOG OF REPLACEMENT PARTS
CATALOG OF REPLACEMENT PARTS C24GA6 & C24GA10 Gas Convection Steamers C24GA6 ML-136056 C24GA10 ML-136057 C24GA6 ML-136021 C24GA10 ML-136022 VULCAN-HART DIVISION OF ITW FOOD EQUIPMENT GROUP, LLC 3600 NORTH
More informationDIAMOND CONCRETE SAW PARTS LIST MODEL CC8000 P R O D U C T S. (Revised )
DIAMOND P R O D U C T S CONCRETE SAW PARTS LIST MODEL CC8000 (Revised 10-15-2002) Table of Contents Page Saw Controls Legend. 3 Drawing 1. Frame Group. 4-5 Drawing 2. Arm Assembly... 6-7 Drawing 3. Hydraulics
More informationSpecification Sheet Form Rev
10000 CDC S1 Sales Administration Use Only Quote Number Quote Revision Shop Order Number Serial Number(s) Date CUSTOMER SALESPERSON MODEL : Customer Name : Salesperson Name : 10000 CDC S1 PART NO./DRAWING
More informationSUPERSEDES ABS-C0811/AUG.
ABS-C0612/R JUNE 2012 SUPERSEDES ABS-C0811/AUG. 2011 SANITARY TEE REDUCING TEE TEE - Left Side Inlet 600007 1 1/4" 0 62852 60000 5 50 4,800 15.41 600015 1 1/2" 0 62852 60001 2 90 2,880 8.27 600023 2"
More informationSee our expanding selection of products on Product Portfolio
See our expanding selection of products on www.fnw.com Product Portfolio Table of Contents Low Lead Products- Page 3 Ball Valves, Check Valves, Strainers, Water Hammer Arrestors Ball Valves, Brass - Page
More informationBUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3
BUREAU OF STANDARDS Effective Date: 8/19/2016 Section No. 4 Version: 1.2 Procedure No. 3 TITLE: LP Gas Bulk Plant Final Inspection PURPOSE: This document details the procedures used to conduct a Final
More informationJUST PIPING, JUST FITTING. A Comprehensive Integrated Solution For Piping Systems
JUST PIPING, JUST FITTING A Comprehensive Integrated Solution For Piping Systems SF 01 DUCTILE IRON PIPE FITTINGS FD1011 FD1021 FD1022 FD1031 FD1102 FD1103 FD1111 FD1121 Double Flanged Piece Flanged spigot
More informationSECTION FIRE HYDRANTS WITH HYDRANT LOCKS
SECTION 33 12 19 FIRE HYDRANTS WITH HYDRANT LOCKS PART 1: GENERAL 1.01 SCOPE A. Fire hydrants. B. Adjustment of fire hydrants and gate valves. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33
More information2014 HEIL DOT407AL 9240GL, DOUBLE CONICAL, TANDEM AXLE, CRUDE OIL TRANSPORT WITH PUMP & CENTRIFUGE NV1309 VIN: 5HTDL4527D7H45530
2014 HEIL DOT407AL 9240GL, DOUBLE CONICAL, TANDEM AXLE, CRUDE OIL TRANSPORT WITH PUMP & CENTRIFUGE NV1309 VIN: 5HTDL4527D7H45530 VESSEL 1) Design Two piece barrel, 5454-H32 aluminum alloy for shell. 5454-0
More informationA GUIDE TO PIPE SIZES
A GUIDE TO PIPE SIZES Pipe Strengths To identify the dimensions and strengths of different pipe, it is common to use schedule terminology taken from the ANSI pipe schedule chart. The pipe schedule chart
More information6. Butterfly Valves & Accessories
1. Plastic Pipes 2. Steel Pipes 3. Penetration Tubes 4. Piping Accessories 5. Needle Valves 6. Butterfly Valves & Accessories 7. Miscellaneous Valves 7 1. PLASTIC PIPES TYPES OF PLASTIC PIPES ADAPTATOR
More informationSentinel 250 Fire Hydrant. Solid design and features to meet any municipal requirement.
Sentinel 250 Fire Hydrant Solid design and features to meet any municipal requirement. Product Features That meet any municipal requirement. 1 Operating Nut Shields the hold down nut from tampering and
More informationSECTION GENERAL-DUTY VALVES FOR HVAC. A. Section includes valves for building services piping.
SECTION 23 05 23 GENERAL-DUTY VALVES FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section includes valves for building services piping. 1.2 REFERENCES A. AGA Z21.22 (American Gas Association) - Relief Valves
More informationSECTION VALVES AND OPERATORS
SECTION 15200 VALVES AND OPERATORS PART 1 - GENERAL 1.1 SUBMITTALS A. Shop Drawings: 1. Product data sheets for make and model. 2. Complete catalog information, descriptive literature, specifications,
More informationList of Materials and Approved Manufacturers
List of Materials and Approved Manufacturers Revised April 2017 300 West Plant Street, Winter Garden, FL 34787 (407) 656-4111 www.wintergarden-fl.gov Water Distribution Please indicate your selection by
More informationSECTION GENERAL-DUTY VALVES FOR HVAC PIPING. A. Contents of Division 23, HVAC and Division 01, General Requirements apply to this Section.
SECTION 23 05 23 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Gate Valves 2. Balancing Valves 3. Ball Valves 4. Butterfly Valves 5. Swing Check Valves 1.2 RELATED SECTIONS A. Contents of Division
More informationContents Project: Model: Chk d: Date:
Contents Model DSHU6. DSHU6.7 DSHU6. DSU6. DSHU6. DSU6.7 DSHU6.7 8DSU6. 8DSHU6. 8DSU6.7 8DSHU6.7 DSU6. DSU67. Section Page Specifications -7, 8 Selection Chart -7., 8. Performance Curves -6 Outline Drawings
More information516509_tabs 11/16/10 4:55 AM Page 1 FIRE HYDRANTS
Date Printed: November 2010 FIRE HYDRANTS or Tyton (6"),6, or 8" A EDDY FIRE HYDRANTS PARTS LIST WORKING PRESSURE: 150 PSI Note: Discontinued For Reference Only 350 PSI Working Pressure
More informationClay & Bailey Mfg. Co.
Clay & Bailey Mfg. Co. OIL EQUIPMENT PRICE LIST 2018 Effective: June 1, 2018 Applicable for Aboveground Storage Tank Equipment Underground Storage Tank Equipment Service Station Equipment D. O. T. Manholes
More informationValves for building. Y-strainers... page 272 PVC valves Ball valves... page 272 Butterfly valves... page 272 Ball check valves...
Valves for building Ball valves PN25/20... page 262 PN30/20...pages 262 to 263 PN40/30 - Lead-free brass... page 264 Valve for gas... page 265 Stem extension valves... page 265 3 way valves... page 265
More informationDos Rios Chlorine Contact Basin Scum Well Rehabilitation Project Solicitation Number: CO Job No.:
Dos Rios Chlorine Contact Basin Scum Well Rehabilitation Project Solicitation Number: CO-00031 Job No.: 15-6504 To Respondent of Record: ADDENDUM I November 20, 2015 This addendum, applicable to work referenced
More informationEclipse Encapsulated Air Compressor Service Parts List (Models ECL-100 and ECL-300)
Eclipse Encapsulated Air Compressor Service Parts List (Models ECL-100 and ECL-300) Document Number Issue Date 03/13/14 Rev. Date 11/8/18 Compressor Air Circuit Tubing Oil Cooler and Oil Filter Electrical
More informationEngineering & Design Data
PVC & CPVC Corrosion Resistant Industrial Pressure Pipe Engineering & Design Data Engineering & Design Data Hydraulic Shock Hydraulic shock is the term used to describe the momentary pressure rise in a
More informationPREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843
BID ADDENDUM NO. 1 PROJECT: PREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843 LABELLA PROJECT NO: 2160128 DATE: FEBRUARY 11, 2016 FROM: LaBella
More informationTHOMAS. Fabricated Steel Pipe Specials. Pipe Fittings PIPE PRODUCTS. Standard & Socketed Pipe Fittings for All Rigid Pipe Materials
THOMAS PIPE PRODUCTS Pipe Fittings Fabricated Steel Pipe Specials Standard & Socketed Pipe Fittings for All Rigid Pipe Materials B1 PIPE FITTINGS LEPHALALE - Limpopo - South Africa PROJECT Medupe Power
More informationList of Materials and Approved Manufacturers
List of Materials and Approved Manufacturers Revised April 2017 300 West Plant Street, Winter Garden, FL 34787 (407) 656-4111 www.wintergarden-fl.gov Water Distribution Please indicate your selection by
More informationCast Iron Valves. Product Information. It s all at Albion
Cast Iron Valves Product Information It s all at Albion ART 77-78 Cast Iron Ball Valve Flanged Ends Flange Mounting PN16 Only ISO 5211 Direct Mount (Not 200mm) Art 77/78 Plated Brass/Stainless Ball BS
More informationPUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES
PUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES 3rd EDITION - 01/2006 Foreword This publication, together with the
More informationAWWA SWING CHECK VALVES. Engineering Creative Solutions for Fluid Systems Since 1901
AWWA SWING CHECK VALVES Engineering Creative Solutions for Fluid Systems Since 1901 TABLE OF CONTENTS AWWA SWING CHECK VALVE Series 8001 Lever & Weight or Spring...1 Series 9001 Lever & Weight or Spring...2
More informationFILTERS, STRAINERS AND VALVES PRODUCT GUIDE
FILTERS, STRAINERS AND VALVES PRODUCT GUIDE TEE FILTERS INLINE FILTERS BRASS FILTERS SPIN ON FILTERS OFF-LINE FILTRATION Y STRAINERS BASKET STRAINERS DUPLEX STRAINERS STRAINING ELEMENTS FRP STRAINERS DUAL
More informationYellow Shading Depicts Recommended Vendor ACT PIPE & SUPPLY AGUAWORKS PIPE & SUPPLY, LLC EMMSA CO FERGUSON WATERWORKS
Yellow Shading Depicts Recommended Vendor Bid Opening Date: February 05, 2015 at 4:00 p.m. Location: Conference Room 1B (1st floor) McAllen City Hall Project: 02-15-SP04-176 SUPPLY CONTRACT FOR THE PURCHASE
More informationPRESSURE GAUGES DIAL THERMOMETERS PRESSURE & TEMP. SWITCHES PRESSURE & TEMP. TRANSMITTERS PIPES, PIPE FITTINGS & FLANGES
WATER METERS VALVES & COCKS PRESSURE GAUGES DIAL THERMOMETERS PRESSURE & TEMP. SWITCHES PRESSURE & TEMP. TRANSMITTERS PIPES, PIPE FITTINGS & FLANGES FILTER, REGULATOR & LUBRICATORS W IKA V I INSTRUMENTS
More informationSECTION 8. PARTS INFORMATION
SECTION 8. PARTS INFORMATION 8-1. INTRODUCTION This section lists the replaceable parts of the Henny Penny Model LVG fryer. 8-2. GENUINE PARTS Use only genuine Henny Penny parts in your fryer. Using a
More informationMIDDLESEX COUNTY COLLEGE EDISON, NJ LOCAL SUPPLIER BLANKET ORDER SPECIFICATIONS
MIDDLESEX COUNTY COLLEGE EDISON, NJ 08818 LOCAL SUPPLIER BLANKET ORDER SPECIFICATIONS The College is soliciting bids to award a Local Supplier Blanket Order agreement for the purchase of supplies for the
More informationSTREET IMPROVEMENTS PROPOSAL BID ITEMS
STREET IMPROVEMENTS 1 Excavation 3,525 CY $ $ 2 A.C. Planing (2" to 4" Depth) 20,586 SY $ $ 3 Furnish & Install Asphalt Concrete 4,270 TON $ $ 4 Furnish & Install Aggregate Base 2,955 TON $ $ 5 Remove
More informationSection One. Steel Underground. PVC Accessories Bolt-on Dresser Fittings Solvent PVC Pipe Fittings Gasketed PVC Pipe Fittings
Page Steel Underground Section One Powder Coated Steel Fittings Galvanized Steel Fittings PVC Fittings Riser Valves Clampon Saddles, Couplers, Male Ends Repair Couplers PVC Accessories Bolton Dresser Fittings
More informationSECTION VIII. (Sub-section 430) Wastewater Valves and Appurtenances. 1. General thru Gate Valves thru 430-3
SECTION VIII (Sub-section 430) Wastewater Valves and Appurtenances Article Page 1. General 430-1 thru 430-2 2. Gate Valves 430-2 thru 430-3 3. Plug Valves 430-3 thru 430-4 4. Check Valves 430-4 5. Tapping
More informationSystems to be regarded as the # 1 Sanitizing System available on the market. Sage TM
Welcome For over 40 years Sage TM Systems have been leading the world in the manufacture of High Pressure Sanitizing Systems. A commitment to continual product development to reflect the everchanging needs
More informationSECTION 1019 VALVES AND APPURTENANCES GENERAL: Valves shall have manufacturer's name and pressure rating cast in raised letters.
SECTION 1019 VALVES AND APPURTENANCES Delete this Section in its entirety and replace with the following: SECTION 1019 VALVES AND APPURTENANCES 1019-1 GENERAL: Valves shall have manufacturer's name and
More informationFounded in 1941 The World s Largest Manufacturer and Supplier of Piping Components for the Pneumatic Conveying Industry.
Founded in 1941 The World s Largest Manufacturer and Supplier of Piping Components for the Pneumatic Conveying Industry. COUPLING PRODUCTS Compression Couplings Side-Band Couplings Quickon II Couplers
More information2-1. Power Unit. Power Unit Installation. Rev: 06/2018 B Page 1 of
2- Installation Rev: 0/208 B Page of Installation Item Part No. Qty Description Item Part No. Qty Description Installation * 58. Assembly 2 5. Vibration Dampener 3 YC-22. Capscrew 583 0. Washer 5 R38 5.
More informationClay & Bailey Mfg. Co.
Clay & Bailey Mfg. Co. OIL EQUIPMENT PRICE LIST 2015 Effective: February 9, 2015 Applicable for Aboveground Storage Tank Equipment Underground Storage Tank Equipment Service Station Equipment D. O. T.
More informationValves for building. Y-strainers... page 204 PVC valves Ball valves... page 204 Butterfly valve... page 204 Ball check valve...
Valves for building Ball valves PN25/20... page 194 PN30/20... page 195 PN40/30 - Lead-free brass... page 196 Valve for gas... page 197 Stem extension valves... page 197 3 way valves... page 197 Mini valves...
More informationRetriever 360G/P. 5/92 revised 2/01 FORM NUMBER
Retriever 360G/P PARTS LIST Advance MODELS 56468470, 56468480 This parts list is for machines after serial number 505073 All models covered in this manual are OBSOLETE 5/92 revised 2/01 FORM NUMBER 56042267
More informationA. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems.
SECTION 220523 - PLUMBING VALVES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball valves. 2. Butterfly valves. 3. Swing check valves. 4. Spring loaded check valves. 5. Water pressure reducing
More informationGENERAL-SERVICE COMPRESSED-AIR PIPING SECTION GENERAL-SERVICE COMPRESSED-AIR PIPING PART 1 - GENERAL
13686.00 GENERAL-SERVICE COMPRESSED-AIR PIPING 221513-1 SECTION 22 1513 - GENERAL-SERVICE COMPRESSED-AIR PIPING 1.1 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of the Contract,
More informationPROJECT: : Maysak New House Construction_Weno, Chuuk State DATE : 27 June 2016 ORDER : 23 SETS (Complete with Electrical) of the below Items
PROJECT: : Maysak New House Construction_Weno, Chuuk State DATE : 27 June 2016 ORDER : 23 SETS (Complete with Electrical) of the below Items ITEM # QUANTITY UNIT DESCRIPTION A. LUMBER - all wood to be
More informationSECTION ELECTRONIC ACTUATED PRESSURE REDUCING VALVES AND ACCESSORIES
SECTION 33 12 16.05 REDUCING VALVES AND ACCESSORIES PART 1 - GENERAL 1.1 THE REQUIREMENT A. The Electronic Actuated Pressure Reducing Valve (PRV) shall maintain a constant downstream pressure regardless
More informationADDENDUM NO REFERENCE: FORM OF AGREEMENT, Schedule 2 List of Contract Drawings C C C C
ADDENDUM NO. 1 PROJECT: Olalla Water System Upgrades Phase 2; RDOS-17-PW-3 The Contract Documents for this work are revised as noted herein. All such revisions become a part of the work and shall be included
More informationUNLV Animal Care Facility. University of Nevada Las Vegas CAM 1513/PC ADDENDUM A August 5, 2016
UNLV Animal Care Facility University of Nevada Las Vegas ADDENDUM A August 5, 2016 Owner: Architect: To: University of Nevada Las Vegas 4505 S. Maryland Parkway Las Vegas, Nevada 89154 Tate Snyder Kimsey
More informationMLS Meter Leveling Saddle. Parts List
Meter Leveling Saddles Meter Level Saddle is an accepted means to support chart recorders on meter runs or as an economical means to support pipe runs. Rugged Ductile Iron Construction Standard " Meter
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 23 2123 - PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationINSERTA VALVE SLEEVE INSERTA VALVE ASSEMBLY. Valve insertion, simplified MATERIAL SPECIFICATIONS MATERIAL SPECIFICATIONS.
MADE IN U.S.A. Valve insertion, simplified 10-12 installations in cast iron, ductile iron, A/C, PVC C-900 and steel pipe No Loss of Pressure Minimal Water Loss Completion time is less than 2 hours Much
More informationPB18-G Series Portable Pump Service Parts List
Document Number Issue Date 01/24/07 Rev. Date 7/28/16 PB18-G Series Portable Pump Service Parts List Component Pump Pump Model (Located on Serial Plate) PB18-G2015B PB18-G2015F Exploded View See Page Cross
More informationLitter Spreader. Models SP400, SP450, SP500, SP550. Illustrated Parts Breakdown
Litter Spreader Models SP00, SP0, SP00, SP0 Illustrated Parts Breakdown Page Front End Page Hydraulic System (w/ Side Mounted Reservoir) Page Hydraulic System (w/ Front Mounted Reservoir) Page Hydraulic
More informationHDPE FUSIBLE VALVES EXPECT INNOVATION
AVK HDPE FUSIBLE VALVES HDPE FUSIBLE VALVES EXPECT INNOVATION AVK HDPE VALVES SERIES 89 FUSIBLE BUTTERFLY VALVE Series 89 fusible butterfly valves are designed for quick, direct heat butt-fusion or electrofusion
More informationCITY OF TAMPA ADDENDUM 2. July 13, Contract 17-C-00030; David L. Tippin Water Treatment Facility Lime Slaker Replacement
CITY OF TAMPA Bob Buckhorn, Mayor CONTRACT ADMINISTRATION DEPARTMENT Michael W. Chucran, Director ADDENDUM 2 July 13, 2017 Contract 17-C-00030; David L. Tippin Water Treatment Facility Lime Slaker Replacement
More informationADDENDUM No. 1. BID No /15 Chevrolet Silverado Work Trucks
Purchasing Department 530 Water Street Oakland, CA 94607 Date: November 17, 2017 ADDENDUM No. 1 BID No. 17-18/15 Chevrolet Silverado Work Trucks This Addendum modifies the original BID Documents for the
More informationBid Summary Still Creek Wastewater Improvements Phase III City Job No. 411-D November 21, 2013
Bid Summary Still Creek Wastewater Improvements Phase III City Job No. 411-D4-1102 November 21, 2013 Doughtie Construction Co., Elliott Construction Dudley Construction Ltd. SUBTOTAL GENERAL ITEMS : $191,713.00
More informationALBEMARLE COUNTY SERVICE AUTHORITY WATER APPROVED PRODUCTS LIST Effective Date: February 9, 2017
ALBEMARLE COUNTY SERVICE AUTHORITY WATER APPROVED PRODUCTS LIST Effective Date: February 9, 2017 I. Water Pipe, Fittings & Appurtenances A. Ductile Iron Pipe & C.I. or D.I. Fittings 1. Griffin Pipe Products,
More informationAUTOMATION ACCESSORIES IN-PLANT VALVE PRODUCTS EXTENSION STEMS FLOORBOX STEM GUIDES FLOORSTANDS COMMITTED TO ENVIRONMENTAL RESPONSIBILITY FLAP VALVES
INCREASING SWING CHECK VALVES FLAP VALVES SWING CHECK VALVES AUTOMATION ACTUATION CLOW VALVE has furnished valves with many assorted types of motorized to operate our valves. The gate valves use multi-turn,
More information