ADDENDUM NUMBER 2 (DATED May 7, 2012) TO THE CONTRACT DOCUMENTS AND CONSTRUCTION SPECIFICATIONS FOR WINDSOR CRUDE OIL TERMINAL

Size: px
Start display at page:

Download "ADDENDUM NUMBER 2 (DATED May 7, 2012) TO THE CONTRACT DOCUMENTS AND CONSTRUCTION SPECIFICATIONS FOR WINDSOR CRUDE OIL TERMINAL"

Transcription

1 ADDENDUM NUMBER 2 (DATED May 7, 2012) TO THE CONTRACT DOCUMENTS AND CONSTRUCTION SPECIFICATIONS FOR WINDSOR CRUDE OIL TERMINAL From: Michael Brake, JR Engineering To: All Plan holders and/or Prospective Bidders. The following revisions, additions and/or deletions are hereby made a part of the Contract Documents and plans for the above referenced project as fully and completely as if the same were fully set forth therein: BIDDING REQUIREMENTS Bidders are required to acknowledge receipt of this Addendum by replying to the notification . RESPONSES TO BIDDER QUESTIONS 1. Information from SafeRack says there will be (5) safety showers installed at ground level, however they are not shown on the drawings. Do we include pricing for the installation and connections? Do we use the water lines from above to make the connections? Include pricing for installation and connection of five (5) showers per the SafeRack drawings. Use the potable water service line under the rack to make the connections. 2. DWG 45 of 47 shows vapor connections on top of 4 strainer on details A&B. What sizes are these lines, how do we connect to the vapor lines? The detail is revised to show the connections. 3. DWG 45 of 47 in reference to the 4 flex product hoses. Detail says qty of 24 however there are only 12 shown on drawings 40 & 41 and the bid schedule only calls for 12. Where do the other 12 go? Are they spares? The Crude and Condensate lines each have 12 product hose assemblies. 4. DWG 45 of 47, Where do the 2 flex recovery hoses get installed? The 2 flex recovery hoses connect to the return line under the rack. 5. What supports are required for the vapor line VP-04 None are shown on DWG S-11. Detail 4/S16 may be used for support of vapor line VP-04, modified with a 3-0 concrete pier depth. 6. Please furnish vapor line drop detail at truck unloading area. A Detail has been provided on sheet Connections to the existing tanks. Are the connections on the tank existing? If not, are we installing the nozzles on the tanks and are the tanks cleaned and ready? Connections are existing and are cleaned and ready. 8. DWG 45 of 47 No meter prover connections shown. Meter Provers are on main meter. Page 1

2 9. DWG 45 of 47 No pressure gauges shown. There are no pressure gauges on connecting lines, only on pump skids. 10. Do we figure garlock or flexitalic gaskets? Garlock Gylon Style 3500 or equivalent are acceptable. 11. DWG 17 of 47 Please confirm the track pans all connect to each other and have one drain at the end of the run. Who provides and installs the track pans? We have experienced numerous issues with these pans due to them having multiple connections which fail over time. Is the owner open to alternates in lieu of the Ultra track pans? Alternate manufacturers of the rail car spill containment pans will be considered on a case-by-case basis provided the proposed pans meet SPCC regulations. The general concept of spill containment will remain the same. The track pans will need to be connected and drain to a common discharge point and go to the containment tank. 12. S12 and S13 of 16 Vapor line supports. The 4 vapor line is shown to be supported by supports up to 49 tall and made from pipe sizes 8 up to 20. Is the owner willing to drop the vapor line down to ground level and use a blower system? No, the elevated vapor line will be used. 13. Are catwalks for LACT tanks furnished by the owner with the owner furnished tanks? If not please provide drawings for the catwalk structure. The catwalk structure is provided by the owner and is supported from the L.A.C.T. tanks. Details will be provided by the owner. Provide a concrete pad at the bottom of the stairs as indicated for the SafeRack stairs (detail shown on sheet S3). All parts are bolted connections. Kicker plates are bolted to the tanks. The manufacturer will forward the required ½ bolts and nuts for assembly in the field. A materials list for assembly will be provided as soon as it is available. 14. What foundations are required for the LACT tank catwalk? See response to Question Reference bid schedule # 72 Concrete column stubs : 76 are at the Saferack foundation cap beams. Where are the other 12 located? The count on Concrete Column Stubs and SafeRack Base Plates should be Do the vapor line foundations get screw piles as well? The screw piles are being utilized at the SafeRack foundation to control settlement. The vapor line structure can tolerate more settlement, therefore screw piles are not required at the vapor line support structure. 17. Who is supplying the flare and the knockout pots? Owner 18. Who furnishes the propane tank for the flare gas assist? Owner 19. Does the propane tank get a heater for winter operations? Not at this time 20. Does any of the piping and valves need to be furnished per cold weather specifications? Yes. All materials need to be rated to -30 F. Page 2

3 21. Can you please provide cut sheets for the crude loading skids and the LACT skids? Sheets for the crude loading skid is not yet available. Sheets for the LACT Skids are attached. CLARIFICATIONS Electronic Specifications File An electronic version of the material specifications are provided for your use on the FTP site. Instructions for accessing the FTP site are as follows: Directions For Using The FTP Site 1. Go to: ftp://ftp.westrian.com in Internet Explorer 2. Input login information: User Name: jrguest Password: jrengineering 3. Go to the folder named Windsor Crude Oil Terminal. LACT Tanks Catwalk Shop Drawings for the LACT Tank catwalk will be provided as soon as they are available. END OF ADDENDUM NUMBER 2 Page 3

4 Know what's

5 Windsor Crude Oil Terminal Musket Corporation ITEM NO. DESCRIPTION MFR / PART No. Light Fixture, (Overhead) [2 per pole] McGraw-Edison Light Fixture, (Flood Lights) Cooper Lighting 1" PVC C900 Service Line JM Eagle 3" Steel Tee 3" Welded Steel Pipe [Casing Pipe] PermaPipe 1"x3/4" Reducer 16"x8" Reducer (M.J.) 20"x16" Tee (M.J.) 8" PVC C900 Water Main JM Eagle 6" DIP [Fire Hydrant Lateral] US Pipe 4" PVC C900 [Casing Pipe] JM Eagle 6" Gate Valve (M.J.) Mueller 2360 Series Resilient Wedge Ductile Iron 8" 90 Bend (M.J.) 8" Gate Valve (M.J.) Mueller 2360 Series Resilient Wedge Ductile Iron 8" Tapping Saddle Romac Industries 304 Series 8"x6" Reducer (M.J.) 8"x6" Tee (M.J.) Pipe Hangers (3") Piping Technology and Products Adjustable Band Hanger Pipe Hangers (4") Piping Technology and Products Adjustable Band Hanger Pipe Hangers (8") Piping Technology and Products Adjustable Band Hanger Unloading Area Slop Line Assembly (1" Welded Steel Pipe, Gate Valves, 500 Gal Slop Tank, and Pump) 1" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 1" Elbow 1" Welded Steel Pipe Sch 40 PermaPipe Tank WE-MAC Tanks Ko-101 Pump with motor Red Jacket P75 SI 4" Welded Steel Pipe (A53B ERW Type E) [Vapor Line] PermaPipe 4" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 4" Welded Steel Pipe (A53B ERW Type E) [Recovery and Return Piping] PermaPipe 8" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 10" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 12" Welded Steel Pipe (A53B ERW Type E) [Carrier Pipe] PermaPipe 12" Welded Steel Pipe [Casing Pipe] PermaPipe 18" Welded Steel Pipe [Casing Pipe] PermaPipe 20" Welded Steel Pipe [Casing Pipe] PermaPipe 4" 22.5 Bend (A53 Grade B) 4" 45 Bend (A53 Grade B) 4" 90 Bend (A53 Grade B) 8" 45 Bend (A53 Grade B) 8" 90 Bend (A53 Grade B) 10" 45 Bend (A53 Grade B) 10" 90 Bend (A53 Grade B) 12" 22.5 Bend (A53 Grade B) 12" 45 Bend (A53 Grade B) 12" 90 Bend (A53 Grade B) 4" Tee (A53 Grade B) 4" Wye (A53 Grade B) 4" Cross (A53 Grade B) 4"x8" Tee (A53 Grade B) 8" Tee (A53 Grade B) 8" Cross (A53 Grade B) 8"x10" Tee (A53 Grade B) 10" Tee (A53 Grade B) 10"x12" Tee (A53 Grade B) 12" Tee (A53 Grade B) 4" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 4" Check Valve Cla-Val Series 581

6 8" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 10" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 12" Gate Valve Mueller 2360 Series Resilient Wedge Ductile Iron 10"x8" Reducer 12"x10" Reducer 8"x4" Reducer 4" Expansion Coupling with Limit Rods Romac EJ400 Series 8" Expansion Coupling with Limit Rods Romac EJ400 Series Offloading Drop Assembly [Drum, Fittings, Valves, Strainer, Adapter, and all appurtenances] Containment Drum, HDPE, 40 gal min. - 3"x4" Tee 3" Elbow 3" Basket Strainer w/air Eliminator, 150#, RF, Carbon Steel Liquid Controls 3" Isolation Adapter 3" Plug Valve ValMatic 5800 Series 3" Hose Connector Dixon Primer for all pipes Sherwin-Williams Epoxy Zinc Primer Paint, for All Above Ground Product and Product Casing Pipes Sherwin-Williams Acrolon 218 -Y Paint, for All Vapor and Vapor Casing Pipes Sherwin-Williams Acrolon 218 -O Railroad Track Spill Containment Pans Leading Innovative Products and Solutions Concrete Vault, 12'x6'x6' [South Recovery Vault] Vaughn Concrete Concrete Vault, 6'x6'x6' [SafeRack and Railroad Containment] Vaughn Concrete Steel Tank, Single Wall (1,000 Gal) Eaton Sales and Service Pump (SafeRack and Railroad Containment Tank) and all Appurtenances Red Jacket P75 SI Pumps (SafeRack South Recovery Tank) and all Appurtenances Red Jacket P75 SI Knockout Tank (500 Gal) WE-MAC Tanks Ko-101 Knockout Tank Pumps Red Jacket P75 SI Crude Loading Arm Assembly [Meter provided by owner] Sight Glass, 4", 150#, RF Ball Valve, 4", 150#, RF, Carbon Steel, Full Port Check Valve, 4", 150#, RF, Carbon Steel, Removeable Seat Temperature Probe and Transducer Solenoid Control Valve, 4", 150#, RF Flow Control Valve, 4", 150#, RF, Carbon Steel, Solenoid Basket Strainer w/air Eliminator, 4", 150#, RF, Carbon Steel Condensate Loading Arm Assembly Sight Glass, 4", 150#, RF Ball Valve, 4", 150#, RF, Carbon Steel, Full Port Solenoid Control Valve, 4", 150#, RF Check Valve, 4", 150#, RF, Carbon Steel, Removeable Seat Temperature Probe and Transducer Flow Control Valve, 4", 150#, RF, Carbon Steel, Solenoid Basket Strainer w/air Eliminator, 4", 150#, RF, Carbon Steel Dixon 5200-SFI-4" Kuka CBA15-4" Wheatley 9D * Trerice Cla-Val Series FMC Technologies 455 series Liquid Controls Dixon 5200-SFI-4" Kuka CBA15-4" Cla-Val Series Wheatley 9D * Trerice FMC Technologies 455 series Liquid Controls Vapor Loading Arm Assembly Flame Arrestor, 4", 150#, RF, Carbon Steel Varec " Adapter Dixon 200-AL-AL 4"x2" Reducer 2" 90 Elbow 4" Product Hose Assembly 4" Flex Hose Parker Industrial 7307 Series 4" Butterfly Valve ABZ Series 402 4" Swing Check Valve Cla-Val Series 580 4" Valve Coupler Dixon 400 DL-DL 4" Sight Glass Dixon 5200-SFI-4" 4" Butterfly Valve (Wet/Dri) Betts WD401 AL V 4" Swivel Tank Car Connection Dixon RTCA40 4" Flanged Combo Nipple Dixon FST40 4" Male Adapter Dixon 400-AL-AL 4" Recovery Loading Arm Assembly 4" Flex Hose Parker Industrial 7307 Series 4" Valve Coupler Dixon 400 DL-DL 4" Sight Glass Dixon 5200-SFI-4" 4" Butterfly Valve (Wet/Dri) Betts WD401 AL V 4" Swivel Tank Car Connection Dixon RTCA40 4" Male Adapter Dixon 400-AL-AL 1" Air Fitting Dixon 2" Vapor Hose Assembly 2" Flex Hose Parker Industrial 7208 Series 2" Valve Coupler Dixon 200-C-AL

7

8

ATTACHMENT I BID SCHEDULE IFB NO , CHURCH FARMS EAST STORAGE TANK AND BOOSTER PUMP STATION

ATTACHMENT I BID SCHEDULE IFB NO , CHURCH FARMS EAST STORAGE TANK AND BOOSTER PUMP STATION ATTACHMENT I BID SCHEDULE IFB NO. 19-021, CHURCH FARMS EAST STORAGE TANK AND BOOSTER PUMP STATION Item No. Description Qty Unit Unit Cost Amount Pump Station Site Work 1 Site Demolition / Removals / Haul

More information

APPROVED MATERIALS LIST SERVICE MATERIALS July 2017 **REVISED 12/6/17**

APPROVED MATERIALS LIST SERVICE MATERIALS July 2017 **REVISED 12/6/17** APPROVED MATERIALS LIST SERVICE MATERIALS July 2017 **REVISED 12/6/17** SIZE DESCRIPTION MANUFACTURER & MODEL NUMBER CORPORATION STOPS 1" MIP x GRIP Comp ball corp stop Ford: FB 1100-4Q McDonald: 74704-BQ

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems.

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION. A. Pipe, fittings, valves, and connections for sprinkler systems. SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, valves, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS A. Section 099000

More information

$69, $63, $63, $62, Schedule B - PIP & C905 Pipe

$69, $63, $63, $62, Schedule B - PIP & C905 Pipe Supplier Bid Bond Signed Proposal Form Signed Addendum #1 Subtotal (Items 1-5) Subtotal (Items 1-5) Sales tax @ 8.3% Subtotal (Items 1-56) Subtotal (Items 1-3) Subtotal (Items 1-41) 2015-2016 ELIPS Pipe

More information

CITY OF SAN DIEGO PUBLIC UTILITIES DEPARTMENT APPROVED MATERIALS LIST TABLE OF CONTENTS

CITY OF SAN DIEGO PUBLIC UTILITIES DEPARTMENT APPROVED MATERIALS LIST TABLE OF CONTENTS CITY OF SAN DIEGO PUBLIC UTILITIES DEPARTMENT TABLE OF CONTENTS SYSTEM Page A. Bronze Water Service Fittings.... 3 Corporation Stop, Curb Stop, Property Valve, Coupling, Compression Fittings, Adaptors,

More information

VALVES, FIRE HYDRANTS, AND APPURTENANCES

VALVES, FIRE HYDRANTS, AND APPURTENANCES VALVES, FIRE HYDRANTS, AND APPURTENANCES PART 1 - GENERAL 1.01 SECTION INCLUDES A. Butterfly Valves B. Gate Valves C. Tapping Valve Assemblies D. Fire Hydrant Assemblies E. Flushing Devices (Blowoffs)

More information

Winning Bid US Petroleum Equipment Walts Petroleum Northwest Petroleum Petro-Chemical Systems Kimberly Green Bay Wausau Fond Du Lac

Winning Bid US Petroleum Equipment Walts Petroleum Northwest Petroleum Petro-Chemical Systems Kimberly Green Bay Wausau Fond Du Lac Minimum Specifications/Questionnaire Bid Results for One (1) New Fuel Dispensing System-Larrabee Shop Winning Bid PERMIT FEES, FORMS, PLANS and NOTIFICATIONS Secure all necessary state and local permits

More information

ABS-0918 SUPERSEDES ABS-0318 ASTM D2661 R/SEPT ABS DWV FITTINGS.

ABS-0918 SUPERSEDES ABS-0318 ASTM D2661 R/SEPT ABS DWV FITTINGS. ABS-0918 SUPERSEDES ABS-0318 ASTM D2661 R/SEPT. 2018 ABS DWV FITTINGS www.bow-group.com COUPLING 1 1/4" 601112 125 9,000 5.63 1 1/2" 601120 125 9,000 3.48 2" 601138 100 4,800 4.65 3" 601146 45 1,440 13.07

More information

ABS DWV FITTINGS ABS-1116 NOVEMBER 2016 SUPERCEDES ABS-1215 ASTM D2661

ABS DWV FITTINGS ABS-1116 NOVEMBER 2016 SUPERCEDES ABS-1215 ASTM D2661 ABS DWV FITTINGS ABS-1116 NOVEMBER 2016 SUPERCEDES ABS-1215 ASTM D2661 COUPLING 1 1/4" 601112 125 9,000 3.36 1 1/2" 601120 125 9,000 2.25 2" 601138 100 4,800 3.03 3" 601146 45 1,440 8.49 4" 601153 25 800

More information

Harlingen Water Works System Approved Products List For Subdivisions. January 11, 2005

Harlingen Water Works System Approved Products List For Subdivisions. January 11, 2005 Harlingen Water Works System Approved Products List For Subdivisions January 11, 2005 Revised March 24, 2016 Harlingen Water Works System Approved Products List for Subdivisions Table of Contents: 1. Valves

More information

CAST IRON FITTINGS STANDARD

CAST IRON FITTINGS STANDARD 060-1 CAST IRON FITTINGS STANDARD ITEM 1/4" 3/8" 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 90 ELL 11.03 15.95 6.99 7.29 8.62 12.24 16.93 26.45 90 REDUCING ELL * 22.20 14.69 12.27 15.44 31.19 41.74 45 ELL 13.59 14.60

More information

MATERIAL SPECIFICATIONS AND BID PROPOSAL SHEET

MATERIAL SPECIFICATIONS AND BID PROPOSAL SHEET CATEGORY 1: STEEL COUPLINGS 0 ¾" Steel Couplings (Smith-Blair #411-0501-003) 20 1" Steel Couplings (Smith-Blair #411-013201-003) 20 1¼" Steel Couplings (Smith-Blair #411-016601-003) 20 2" Steel Couplings

More information

Electrical Applications. Metal Framing & Cable Tray Superstrut Metal Framing System. Column A. Design Data: Materials: Column B

Electrical Applications. Metal Framing & Cable Tray Superstrut Metal Framing System. Column A. Design Data: Materials: Column B Electrical Raceway Series 800 Surface Raceway and Lighting Systems Superstrut channel together with snap-in closure strip is listed by Underwriters Laboratories as a surface metal raceway. Other accessories

More information

ELIPS Pipe Materials Bid Summary August 29, :00am Bid Opening

ELIPS Pipe Materials Bid Summary August 29, :00am Bid Opening 2013-2014 ELIPS Pipe Materials Bid Summary August 29, 2013 11:00am Bid Opening Supplier Bid Bond Signed Proposal Form Addendum No. 1 Subtotal (Items 1-5) Sales tax @ 7.9% Total Bid Amount Subtotal (Items

More information

PUBLIC UTILITIES DEPARTMENT CITY OF SAN DIEGO APPROVED MATERIALS LIST FOR WATER STAN MEDINA DEPUTY DIRECTOR WATER OPERATIONS. u f! ASSISTANT DIRECTOR

PUBLIC UTILITIES DEPARTMENT CITY OF SAN DIEGO APPROVED MATERIALS LIST FOR WATER STAN MEDINA DEPUTY DIRECTOR WATER OPERATIONS. u f! ASSISTANT DIRECTOR PUBLIC UTILITIES DEPARTMENT CITY OF SAN DIEGO FOR WATER STAN MEDINA DEPUTY DIRECTOR WATER OPERATIONS DEPUTY DIRECTOR ENGINEERING & PROGRAM MANAGEMENT u f! u~~~ 7 STAN GRIFFITH ASSISTANT DIRECTOR DISTRIBUTION

More information

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate requirements that are optional depending

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS

San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS 834.1 DESCRIPTION: This item shall consist of fire hydrant installations using joint restraints in accordance

More information

PB18 Series Portable Pump Assembly Service Parts List

PB18 Series Portable Pump Assembly Service Parts List Document Number Issue Date 09/20/94 Rev. Date 02/02/12 PB18 Series Portable Pump Assembly Service Parts List Index: Component Pump Model (Located on Pump Serial Plate) See Page PB18-2515, PB18-2515B 2,

More information

WILKINSBURG-PENN JOINT WATER AUTHORITY DUCTILE IRON PIPE AND ACCESSORIES BID TABULATIONS CONTRACT NO

WILKINSBURG-PENN JOINT WATER AUTHORITY DUCTILE IRON PIPE AND ACCESSORIES BID TABULATIONS CONTRACT NO WILKINSBURG-PENN JOINT AUTHORITY UNIT # 1- PIPE AND MJ FITTINGS & TAYLOR 1A 6 RON PIPE, CLASS 52 no bid no bid 11.98 12.61 14.23 no bid no bid 13.40 14.93 1B 8 RON PIPE, CLASS 52 16.94 17.83 20.12 17.83

More information

2. Compartments 2 compartments with gallons front to rear with double bulkheads

2. Compartments 2 compartments with gallons front to rear with double bulkheads January 10, 2016 STE # 11602 & 11605 (Ref. QT 3098/STE#10741-10744) ST&E SPECIFICATIONS FOR 4,000 US GALLON DOT-407 DOUBLE CONICAL STAINLESS STEEL INSULATED TWO COMPARTMENT TANDEM TRANSPORT TANK PREPARED

More information

ORDERING: Specify size, figure number, description, nominal pipe size or special O.D. and C-to-C dimension. C - C LOAD lb.

ORDERING: Specify size, figure number, description, nominal pipe size or special O.D. and C-to-C dimension. C - C LOAD lb. Fig. 2110 www.pipingtech.com/fig2110 Sway Strut with 4 of Adjustment Engineered spring supports option 1 option 2 ORDERING: Specify size, figure number, description, nominal pipe size or special O.D. and

More information

PIPE OUTSIDE DIAMETER GUIDE

PIPE OUTSIDE DIAMETER GUIDE June 7, 2018-1 PIPE OUTSIDE DIAMETER GUIDE PIPE OUTSIDE DIAMETER GUIDE - SMALL DIAMETER PIPE SIZES NOMINAL PIPE SIZES 1 /2" 3 /4" 1" 1 1 /4" 1 1 /2" 2" 2 1 /2" THIS O.D. GUIDE IS FOR YOUR CONVENIENCE &

More information

***************************************************************************************************************

*************************************************************************************************************** 15515 VALVES, HANGERS, AND SPECIALTIES *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number:23 21 16 ***************************************************************************************************************

More information

LATEST ARRIVALS CATALOGUE STOCK

LATEST ARRIVALS CATALOGUE STOCK LATEST ARRIVALS CATALOGUE STOCK PIPES VALVES FLANGES & FITTINGS IN CARBON STEEL STAINLESS STEEL LATEST ARRIVALS!!!!!! VALVE PRODUCTS CAST IRON WAFER TYPE BUTTERFLY VALVE, PINLESS SHAFT, DUCTILE NICKEL

More information

2150 F&I 4" PVC pipe LF 100 $ F&I 6" PVC pipe LF 100 $ F&I 8" PVC pipe LF 100 $ 90.00

2150 F&I 4 PVC pipe LF 100 $ F&I 6 PVC pipe LF 100 $ F&I 8 PVC pipe LF 100 $ 90.00 1 of 5 2100 F&I 4" ductile iron pipe LF 200 $ 143.00 $28,600.00 2102 F&I 6" ductile iron pipe LF 200 $ 135.00 $27,000.00 2104 F&I 8" ductile iron pipe LF 200 $ 141.00 $28,200.00 2105 F&I 10" ductile iron

More information

ABS-C0717 JULY 2017 SUPERSEDES ABS-C0217 CSA B181.1 ABS DWV FITTINGS.

ABS-C0717 JULY 2017 SUPERSEDES ABS-C0217 CSA B181.1 ABS DWV FITTINGS. ABS-C0717 JULY 2017 SUPERSEDES ABS-C0217 CSA B181.1 ABS DWV FITTINGS www.bow-group.com dimension item Ctn Skid list price dimension item Ctn Skid list price SANITARY TEE (Hub x Hub x Hub) 1 1/4" 600007

More information

Approved Branded Traceable Fire Protection & Waterworks Valves

Approved Branded Traceable Fire Protection & Waterworks Valves Approved Branded Traceable Fire Protection & Waterworks Valves (800) 766-0076 www.smithcooper.com Los Angeles, CA Atlanta, GA Vancouver, WA Chicago, IL AWWA C515 Compliant CONSIDER Your Options Tamper

More information

ADDENDUM No. 1 Prospective Bidders

ADDENDUM No. 1 Prospective Bidders Page 1 of 1 Attachment to Addendum # 1 Revised Itemized Bid ADDENDUM No. 1 TO: Prospective Bidders FROM: Gregory Tate, Construction Contracts Administrator DATE: January 24, 2019 PROJECT: Traffic Signal

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS

San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS San Antonio Water System Standard Specifications for Construction ITEM NO. 834 FIRE HYDRANTS 834.1 DESCRIPTION: This item shall consist of fire hydrant installations using joint restraints in accordance

More information

PEI/RP Recommended Practices for Installation of Bulk Storage Plants

PEI/RP Recommended Practices for Installation of Bulk Storage Plants PEI/RP800-08 Recommended Practices for Installation of Bulk Storage Plants Recommended Practices for Installation of Bulk Storage Plants CONTENTS Foreword...iii. SECTIONS 1. Introduction Page 1.1 Background...1

More information

PVC Couplings. Brass Couplings BRASS COMPRESSION COUPLING 3 -LENGTH PVC COMPRESSION COUPLING BRASS COMPRESSION COUPLING 5 -LENGTH

PVC Couplings. Brass Couplings BRASS COMPRESSION COUPLING 3 -LENGTH PVC COMPRESSION COUPLING BRASS COMPRESSION COUPLING 5 -LENGTH & FITT Brass Couplings BRASS COMPRESSION COUPL 3 -LENGTH 46331 3/8 1/2 12 120 5.80 46332 1/2 3/4 12 120 7.38 46333 3/4 1 6 72 10.52 46334 1 1 1/4 6 60 13.44 46335 1 1/4 1 1/2 4 48 18.00 46336 1 1/2 4 36

More information

January 2007 Approval Guide Fixed Extinguishing Systems 5-57

January 2007 Approval Guide Fixed Extinguishing Systems 5-57 Fixed Extinguishing Systems 5-57 CHEMETRON Fire Systems, 4801 Southwick Dr, 3rd Floor, Matteson IL 60443 High Pressure System Equipment. Automatic Actuator. 1-026-02, -0250. Alarm. 1-003-0033, -0070, -0071,

More information

1. All piping shall have flow arrows indicating direction of flow.

1. All piping shall have flow arrows indicating direction of flow. PART 1: GENERAL 1.01 Scope of Standards A. This design guidelines contained herein includes the requirements for systems, materials, fittings and valves utilized for piping systems at Texas State University.

More information

SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION WATER DISTRIBUTION VALVES

SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION WATER DISTRIBUTION VALVES SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION 33 12 16 WATER DISTRIBUTION VALVES PART 1 GENERAL... 2 1.1 Description... 2 1.2 Reference Specifications, Codes, and

More information

Specification Sheet Form Rev

Specification Sheet Form Rev Sales Administration Use Only Customer Quote Number Quote Revision Shop Order Number Serial Number(s) Date : Customer Name Salesperson Model : Salesperson Name : 8400 DDC S1 Part / Drawing Number : 730-8400

More information

See our expanding selection of products on Product Portfolio

See our expanding selection of products on  Product Portfolio See our expanding selection of products on www.fnw.com Product Portfolio Table of Contents Low Lead Products- Page 3 Ball Valves, Check Valves, Strainers, Water Hammer Arrestors Ball Valves, Brass - Page

More information

ABS-C0219 FEB SUPERSEDES ABS-C0717R CSA B181.1 ABS DWV FITTINGS.

ABS-C0219 FEB SUPERSEDES ABS-C0717R CSA B181.1 ABS DWV FITTINGS. ABS-C0219 FEB. 2019 SUPERSEDES ABS-C0717R CSA B181.1 ABS DWV FITTINGS www.bow-group.com DIMENSION ITEM CTN SKID LIST PRICE DIMENSION ITEM CTN SKID LIST PRICE SANITARY TEE (Hub x Hub x Hub) 1 1/4" 600007

More information

this equipment. Does Not

this equipment. Does Not SPECIFICATIONS FOR THE SUPER SEALCOATER 550 TRAILER MOUNTED SEALCOAT APPLICATOR 420 N. Roosevelt Ave. Chandler AZ 85226 +1 800 528 8242 +1 602 276 0406 FAX +1 480 961 0513 www.crafco.com MARCH 2014 The

More information

CATALOG OF REPLACEMENT PARTS C24GA6 & C24GA10 GAS CONVECTION STEAMERS PRIOR MLS COVERED IN THIS MANUAL

CATALOG OF REPLACEMENT PARTS C24GA6 & C24GA10 GAS CONVECTION STEAMERS PRIOR MLS COVERED IN THIS MANUAL CATALOG OF REPLACEMENT PARTS C24GA6 & C24GA10 GAS CONVECTION STEAMERS C24GA6 C24GA10 ML-136056 ML-136057 PRIOR MLS COVERED IN THIS MANUAL C24GA6 C24GA10 ML-136021 ML-136022 For additional information on

More information

CATALOG OF REPLACEMENT PARTS

CATALOG OF REPLACEMENT PARTS CATALOG OF REPLACEMENT PARTS C24GA6 & C24GA10 Gas Convection Steamers C24GA6 ML-136056 C24GA10 ML-136057 C24GA6 ML-136021 C24GA10 ML-136022 VULCAN-HART DIVISION OF ITW FOOD EQUIPMENT GROUP, LLC 3600 NORTH

More information

DIAMOND CONCRETE SAW PARTS LIST MODEL CC8000 P R O D U C T S. (Revised )

DIAMOND CONCRETE SAW PARTS LIST MODEL CC8000 P R O D U C T S. (Revised ) DIAMOND P R O D U C T S CONCRETE SAW PARTS LIST MODEL CC8000 (Revised 10-15-2002) Table of Contents Page Saw Controls Legend. 3 Drawing 1. Frame Group. 4-5 Drawing 2. Arm Assembly... 6-7 Drawing 3. Hydraulics

More information

Specification Sheet Form Rev

Specification Sheet Form Rev 10000 CDC S1 Sales Administration Use Only Quote Number Quote Revision Shop Order Number Serial Number(s) Date CUSTOMER SALESPERSON MODEL : Customer Name : Salesperson Name : 10000 CDC S1 PART NO./DRAWING

More information

SUPERSEDES ABS-C0811/AUG.

SUPERSEDES ABS-C0811/AUG. ABS-C0612/R JUNE 2012 SUPERSEDES ABS-C0811/AUG. 2011 SANITARY TEE REDUCING TEE TEE - Left Side Inlet 600007 1 1/4" 0 62852 60000 5 50 4,800 15.41 600015 1 1/2" 0 62852 60001 2 90 2,880 8.27 600023 2"

More information

See our expanding selection of products on Product Portfolio

See our expanding selection of products on  Product Portfolio See our expanding selection of products on www.fnw.com Product Portfolio Table of Contents Low Lead Products- Page 3 Ball Valves, Check Valves, Strainers, Water Hammer Arrestors Ball Valves, Brass - Page

More information

BUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3

BUREAU OF STANDARDS. Effective Date: 8/19/2016 Section No. 4. Version: 1.2 Procedure No. 3 BUREAU OF STANDARDS Effective Date: 8/19/2016 Section No. 4 Version: 1.2 Procedure No. 3 TITLE: LP Gas Bulk Plant Final Inspection PURPOSE: This document details the procedures used to conduct a Final

More information

JUST PIPING, JUST FITTING. A Comprehensive Integrated Solution For Piping Systems

JUST PIPING, JUST FITTING. A Comprehensive Integrated Solution For Piping Systems JUST PIPING, JUST FITTING A Comprehensive Integrated Solution For Piping Systems SF 01 DUCTILE IRON PIPE FITTINGS FD1011 FD1021 FD1022 FD1031 FD1102 FD1103 FD1111 FD1121 Double Flanged Piece Flanged spigot

More information

SECTION FIRE HYDRANTS WITH HYDRANT LOCKS

SECTION FIRE HYDRANTS WITH HYDRANT LOCKS SECTION 33 12 19 FIRE HYDRANTS WITH HYDRANT LOCKS PART 1: GENERAL 1.01 SCOPE A. Fire hydrants. B. Adjustment of fire hydrants and gate valves. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33

More information

2014 HEIL DOT407AL 9240GL, DOUBLE CONICAL, TANDEM AXLE, CRUDE OIL TRANSPORT WITH PUMP & CENTRIFUGE NV1309 VIN: 5HTDL4527D7H45530

2014 HEIL DOT407AL 9240GL, DOUBLE CONICAL, TANDEM AXLE, CRUDE OIL TRANSPORT WITH PUMP & CENTRIFUGE NV1309 VIN: 5HTDL4527D7H45530 2014 HEIL DOT407AL 9240GL, DOUBLE CONICAL, TANDEM AXLE, CRUDE OIL TRANSPORT WITH PUMP & CENTRIFUGE NV1309 VIN: 5HTDL4527D7H45530 VESSEL 1) Design Two piece barrel, 5454-H32 aluminum alloy for shell. 5454-0

More information

A GUIDE TO PIPE SIZES

A GUIDE TO PIPE SIZES A GUIDE TO PIPE SIZES Pipe Strengths To identify the dimensions and strengths of different pipe, it is common to use schedule terminology taken from the ANSI pipe schedule chart. The pipe schedule chart

More information

6. Butterfly Valves & Accessories

6. Butterfly Valves & Accessories 1. Plastic Pipes 2. Steel Pipes 3. Penetration Tubes 4. Piping Accessories 5. Needle Valves 6. Butterfly Valves & Accessories 7. Miscellaneous Valves 7 1. PLASTIC PIPES TYPES OF PLASTIC PIPES ADAPTATOR

More information

Sentinel 250 Fire Hydrant. Solid design and features to meet any municipal requirement.

Sentinel 250 Fire Hydrant. Solid design and features to meet any municipal requirement. Sentinel 250 Fire Hydrant Solid design and features to meet any municipal requirement. Product Features That meet any municipal requirement. 1 Operating Nut Shields the hold down nut from tampering and

More information

SECTION GENERAL-DUTY VALVES FOR HVAC. A. Section includes valves for building services piping.

SECTION GENERAL-DUTY VALVES FOR HVAC. A. Section includes valves for building services piping. SECTION 23 05 23 GENERAL-DUTY VALVES FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section includes valves for building services piping. 1.2 REFERENCES A. AGA Z21.22 (American Gas Association) - Relief Valves

More information

SECTION VALVES AND OPERATORS

SECTION VALVES AND OPERATORS SECTION 15200 VALVES AND OPERATORS PART 1 - GENERAL 1.1 SUBMITTALS A. Shop Drawings: 1. Product data sheets for make and model. 2. Complete catalog information, descriptive literature, specifications,

More information

List of Materials and Approved Manufacturers

List of Materials and Approved Manufacturers List of Materials and Approved Manufacturers Revised April 2017 300 West Plant Street, Winter Garden, FL 34787 (407) 656-4111 www.wintergarden-fl.gov Water Distribution Please indicate your selection by

More information

SECTION GENERAL-DUTY VALVES FOR HVAC PIPING. A. Contents of Division 23, HVAC and Division 01, General Requirements apply to this Section.

SECTION GENERAL-DUTY VALVES FOR HVAC PIPING. A. Contents of Division 23, HVAC and Division 01, General Requirements apply to this Section. SECTION 23 05 23 PART 1 - GENERAL 1.1 SUMMARY A. Work Included: 1. Gate Valves 2. Balancing Valves 3. Ball Valves 4. Butterfly Valves 5. Swing Check Valves 1.2 RELATED SECTIONS A. Contents of Division

More information

Contents Project: Model: Chk d: Date:

Contents Project: Model: Chk d: Date: Contents Model DSHU6. DSHU6.7 DSHU6. DSU6. DSHU6. DSU6.7 DSHU6.7 8DSU6. 8DSHU6. 8DSU6.7 8DSHU6.7 DSU6. DSU67. Section Page Specifications -7, 8 Selection Chart -7., 8. Performance Curves -6 Outline Drawings

More information

516509_tabs 11/16/10 4:55 AM Page 1 FIRE HYDRANTS

516509_tabs 11/16/10 4:55 AM Page 1 FIRE HYDRANTS Date Printed: November 2010 FIRE HYDRANTS or Tyton (6"),6, or 8" A EDDY FIRE HYDRANTS PARTS LIST WORKING PRESSURE: 150 PSI Note: Discontinued For Reference Only 350 PSI Working Pressure

More information

Clay & Bailey Mfg. Co.

Clay & Bailey Mfg. Co. Clay & Bailey Mfg. Co. OIL EQUIPMENT PRICE LIST 2018 Effective: June 1, 2018 Applicable for Aboveground Storage Tank Equipment Underground Storage Tank Equipment Service Station Equipment D. O. T. Manholes

More information

Valves for building. Y-strainers... page 272 PVC valves Ball valves... page 272 Butterfly valves... page 272 Ball check valves...

Valves for building. Y-strainers... page 272 PVC valves Ball valves... page 272 Butterfly valves... page 272 Ball check valves... Valves for building Ball valves PN25/20... page 262 PN30/20...pages 262 to 263 PN40/30 - Lead-free brass... page 264 Valve for gas... page 265 Stem extension valves... page 265 3 way valves... page 265

More information

Dos Rios Chlorine Contact Basin Scum Well Rehabilitation Project Solicitation Number: CO Job No.:

Dos Rios Chlorine Contact Basin Scum Well Rehabilitation Project Solicitation Number: CO Job No.: Dos Rios Chlorine Contact Basin Scum Well Rehabilitation Project Solicitation Number: CO-00031 Job No.: 15-6504 To Respondent of Record: ADDENDUM I November 20, 2015 This addendum, applicable to work referenced

More information

Eclipse Encapsulated Air Compressor Service Parts List (Models ECL-100 and ECL-300)

Eclipse Encapsulated Air Compressor Service Parts List (Models ECL-100 and ECL-300) Eclipse Encapsulated Air Compressor Service Parts List (Models ECL-100 and ECL-300) Document Number Issue Date 03/13/14 Rev. Date 11/8/18 Compressor Air Circuit Tubing Oil Cooler and Oil Filter Electrical

More information

Engineering & Design Data

Engineering & Design Data PVC & CPVC Corrosion Resistant Industrial Pressure Pipe Engineering & Design Data Engineering & Design Data Hydraulic Shock Hydraulic shock is the term used to describe the momentary pressure rise in a

More information

PREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843

PREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843 BID ADDENDUM NO. 1 PROJECT: PREPACKAGED AVIATION FUEL TANKS AND EQUIPMENT CITY OF HORNELL, NEW YORK 82 MAIN STREET HORNELL, NEW YORK 14843 LABELLA PROJECT NO: 2160128 DATE: FEBRUARY 11, 2016 FROM: LaBella

More information

THOMAS. Fabricated Steel Pipe Specials. Pipe Fittings PIPE PRODUCTS. Standard & Socketed Pipe Fittings for All Rigid Pipe Materials

THOMAS. Fabricated Steel Pipe Specials. Pipe Fittings PIPE PRODUCTS. Standard & Socketed Pipe Fittings for All Rigid Pipe Materials THOMAS PIPE PRODUCTS Pipe Fittings Fabricated Steel Pipe Specials Standard & Socketed Pipe Fittings for All Rigid Pipe Materials B1 PIPE FITTINGS LEPHALALE - Limpopo - South Africa PROJECT Medupe Power

More information

List of Materials and Approved Manufacturers

List of Materials and Approved Manufacturers List of Materials and Approved Manufacturers Revised April 2017 300 West Plant Street, Winter Garden, FL 34787 (407) 656-4111 www.wintergarden-fl.gov Water Distribution Please indicate your selection by

More information

Cast Iron Valves. Product Information. It s all at Albion

Cast Iron Valves. Product Information. It s all at Albion Cast Iron Valves Product Information It s all at Albion ART 77-78 Cast Iron Ball Valve Flanged Ends Flange Mounting PN16 Only ISO 5211 Direct Mount (Not 200mm) Art 77/78 Plated Brass/Stainless Ball BS

More information

PUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES

PUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES PUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES 3rd EDITION - 01/2006 Foreword This publication, together with the

More information

AWWA SWING CHECK VALVES. Engineering Creative Solutions for Fluid Systems Since 1901

AWWA SWING CHECK VALVES. Engineering Creative Solutions for Fluid Systems Since 1901 AWWA SWING CHECK VALVES Engineering Creative Solutions for Fluid Systems Since 1901 TABLE OF CONTENTS AWWA SWING CHECK VALVE Series 8001 Lever & Weight or Spring...1 Series 9001 Lever & Weight or Spring...2

More information

FILTERS, STRAINERS AND VALVES PRODUCT GUIDE

FILTERS, STRAINERS AND VALVES PRODUCT GUIDE FILTERS, STRAINERS AND VALVES PRODUCT GUIDE TEE FILTERS INLINE FILTERS BRASS FILTERS SPIN ON FILTERS OFF-LINE FILTRATION Y STRAINERS BASKET STRAINERS DUPLEX STRAINERS STRAINING ELEMENTS FRP STRAINERS DUAL

More information

Yellow Shading Depicts Recommended Vendor ACT PIPE & SUPPLY AGUAWORKS PIPE & SUPPLY, LLC EMMSA CO FERGUSON WATERWORKS

Yellow Shading Depicts Recommended Vendor ACT PIPE & SUPPLY AGUAWORKS PIPE & SUPPLY, LLC EMMSA CO FERGUSON WATERWORKS Yellow Shading Depicts Recommended Vendor Bid Opening Date: February 05, 2015 at 4:00 p.m. Location: Conference Room 1B (1st floor) McAllen City Hall Project: 02-15-SP04-176 SUPPLY CONTRACT FOR THE PURCHASE

More information

PRESSURE GAUGES DIAL THERMOMETERS PRESSURE & TEMP. SWITCHES PRESSURE & TEMP. TRANSMITTERS PIPES, PIPE FITTINGS & FLANGES

PRESSURE GAUGES DIAL THERMOMETERS PRESSURE & TEMP. SWITCHES PRESSURE & TEMP. TRANSMITTERS PIPES, PIPE FITTINGS & FLANGES WATER METERS VALVES & COCKS PRESSURE GAUGES DIAL THERMOMETERS PRESSURE & TEMP. SWITCHES PRESSURE & TEMP. TRANSMITTERS PIPES, PIPE FITTINGS & FLANGES FILTER, REGULATOR & LUBRICATORS W IKA V I INSTRUMENTS

More information

SECTION 8. PARTS INFORMATION

SECTION 8. PARTS INFORMATION SECTION 8. PARTS INFORMATION 8-1. INTRODUCTION This section lists the replaceable parts of the Henny Penny Model LVG fryer. 8-2. GENUINE PARTS Use only genuine Henny Penny parts in your fryer. Using a

More information

MIDDLESEX COUNTY COLLEGE EDISON, NJ LOCAL SUPPLIER BLANKET ORDER SPECIFICATIONS

MIDDLESEX COUNTY COLLEGE EDISON, NJ LOCAL SUPPLIER BLANKET ORDER SPECIFICATIONS MIDDLESEX COUNTY COLLEGE EDISON, NJ 08818 LOCAL SUPPLIER BLANKET ORDER SPECIFICATIONS The College is soliciting bids to award a Local Supplier Blanket Order agreement for the purchase of supplies for the

More information

STREET IMPROVEMENTS PROPOSAL BID ITEMS

STREET IMPROVEMENTS PROPOSAL BID ITEMS STREET IMPROVEMENTS 1 Excavation 3,525 CY $ $ 2 A.C. Planing (2" to 4" Depth) 20,586 SY $ $ 3 Furnish & Install Asphalt Concrete 4,270 TON $ $ 4 Furnish & Install Aggregate Base 2,955 TON $ $ 5 Remove

More information

Section One. Steel Underground. PVC Accessories Bolt-on Dresser Fittings Solvent PVC Pipe Fittings Gasketed PVC Pipe Fittings

Section One. Steel Underground. PVC Accessories Bolt-on Dresser Fittings Solvent PVC Pipe Fittings Gasketed PVC Pipe Fittings Page Steel Underground Section One Powder Coated Steel Fittings Galvanized Steel Fittings PVC Fittings Riser Valves Clampon Saddles, Couplers, Male Ends Repair Couplers PVC Accessories Bolton Dresser Fittings

More information

SECTION VIII. (Sub-section 430) Wastewater Valves and Appurtenances. 1. General thru Gate Valves thru 430-3

SECTION VIII. (Sub-section 430) Wastewater Valves and Appurtenances. 1. General thru Gate Valves thru 430-3 SECTION VIII (Sub-section 430) Wastewater Valves and Appurtenances Article Page 1. General 430-1 thru 430-2 2. Gate Valves 430-2 thru 430-3 3. Plug Valves 430-3 thru 430-4 4. Check Valves 430-4 5. Tapping

More information

Systems to be regarded as the # 1 Sanitizing System available on the market. Sage TM

Systems to be regarded as the # 1 Sanitizing System available on the market. Sage TM Welcome For over 40 years Sage TM Systems have been leading the world in the manufacture of High Pressure Sanitizing Systems. A commitment to continual product development to reflect the everchanging needs

More information

SECTION 1019 VALVES AND APPURTENANCES GENERAL: Valves shall have manufacturer's name and pressure rating cast in raised letters.

SECTION 1019 VALVES AND APPURTENANCES GENERAL: Valves shall have manufacturer's name and pressure rating cast in raised letters. SECTION 1019 VALVES AND APPURTENANCES Delete this Section in its entirety and replace with the following: SECTION 1019 VALVES AND APPURTENANCES 1019-1 GENERAL: Valves shall have manufacturer's name and

More information

Founded in 1941 The World s Largest Manufacturer and Supplier of Piping Components for the Pneumatic Conveying Industry.

Founded in 1941 The World s Largest Manufacturer and Supplier of Piping Components for the Pneumatic Conveying Industry. Founded in 1941 The World s Largest Manufacturer and Supplier of Piping Components for the Pneumatic Conveying Industry. COUPLING PRODUCTS Compression Couplings Side-Band Couplings Quickon II Couplers

More information

2-1. Power Unit. Power Unit Installation. Rev: 06/2018 B Page 1 of

2-1. Power Unit. Power Unit Installation. Rev: 06/2018 B Page 1 of 2- Installation Rev: 0/208 B Page of Installation Item Part No. Qty Description Item Part No. Qty Description Installation * 58. Assembly 2 5. Vibration Dampener 3 YC-22. Capscrew 583 0. Washer 5 R38 5.

More information

Clay & Bailey Mfg. Co.

Clay & Bailey Mfg. Co. Clay & Bailey Mfg. Co. OIL EQUIPMENT PRICE LIST 2015 Effective: February 9, 2015 Applicable for Aboveground Storage Tank Equipment Underground Storage Tank Equipment Service Station Equipment D. O. T.

More information

Valves for building. Y-strainers... page 204 PVC valves Ball valves... page 204 Butterfly valve... page 204 Ball check valve...

Valves for building. Y-strainers... page 204 PVC valves Ball valves... page 204 Butterfly valve... page 204 Ball check valve... Valves for building Ball valves PN25/20... page 194 PN30/20... page 195 PN40/30 - Lead-free brass... page 196 Valve for gas... page 197 Stem extension valves... page 197 3 way valves... page 197 Mini valves...

More information

Retriever 360G/P. 5/92 revised 2/01 FORM NUMBER

Retriever 360G/P. 5/92 revised 2/01 FORM NUMBER Retriever 360G/P PARTS LIST Advance MODELS 56468470, 56468480 This parts list is for machines after serial number 505073 All models covered in this manual are OBSOLETE 5/92 revised 2/01 FORM NUMBER 56042267

More information

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems.

A. American National Standards Institute: 1. ANSI Z Relief Valves for Hot Water Supply Systems. SECTION 220523 - PLUMBING VALVES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Ball valves. 2. Butterfly valves. 3. Swing check valves. 4. Spring loaded check valves. 5. Water pressure reducing

More information

GENERAL-SERVICE COMPRESSED-AIR PIPING SECTION GENERAL-SERVICE COMPRESSED-AIR PIPING PART 1 - GENERAL

GENERAL-SERVICE COMPRESSED-AIR PIPING SECTION GENERAL-SERVICE COMPRESSED-AIR PIPING PART 1 - GENERAL 13686.00 GENERAL-SERVICE COMPRESSED-AIR PIPING 221513-1 SECTION 22 1513 - GENERAL-SERVICE COMPRESSED-AIR PIPING 1.1 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of the Contract,

More information

PROJECT: : Maysak New House Construction_Weno, Chuuk State DATE : 27 June 2016 ORDER : 23 SETS (Complete with Electrical) of the below Items

PROJECT: : Maysak New House Construction_Weno, Chuuk State DATE : 27 June 2016 ORDER : 23 SETS (Complete with Electrical) of the below Items PROJECT: : Maysak New House Construction_Weno, Chuuk State DATE : 27 June 2016 ORDER : 23 SETS (Complete with Electrical) of the below Items ITEM # QUANTITY UNIT DESCRIPTION A. LUMBER - all wood to be

More information

SECTION ELECTRONIC ACTUATED PRESSURE REDUCING VALVES AND ACCESSORIES

SECTION ELECTRONIC ACTUATED PRESSURE REDUCING VALVES AND ACCESSORIES SECTION 33 12 16.05 REDUCING VALVES AND ACCESSORIES PART 1 - GENERAL 1.1 THE REQUIREMENT A. The Electronic Actuated Pressure Reducing Valve (PRV) shall maintain a constant downstream pressure regardless

More information

ADDENDUM NO REFERENCE: FORM OF AGREEMENT, Schedule 2 List of Contract Drawings C C C C

ADDENDUM NO REFERENCE: FORM OF AGREEMENT, Schedule 2 List of Contract Drawings C C C C ADDENDUM NO. 1 PROJECT: Olalla Water System Upgrades Phase 2; RDOS-17-PW-3 The Contract Documents for this work are revised as noted herein. All such revisions become a part of the work and shall be included

More information

UNLV Animal Care Facility. University of Nevada Las Vegas CAM 1513/PC ADDENDUM A August 5, 2016

UNLV Animal Care Facility. University of Nevada Las Vegas CAM 1513/PC ADDENDUM A August 5, 2016 UNLV Animal Care Facility University of Nevada Las Vegas ADDENDUM A August 5, 2016 Owner: Architect: To: University of Nevada Las Vegas 4505 S. Maryland Parkway Las Vegas, Nevada 89154 Tate Snyder Kimsey

More information

MLS Meter Leveling Saddle. Parts List

MLS Meter Leveling Saddle. Parts List Meter Leveling Saddles Meter Level Saddle is an accepted means to support chart recorders on meter runs or as an economical means to support pipe runs. Rugged Ductile Iron Construction Standard " Meter

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 2123 - PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

INSERTA VALVE SLEEVE INSERTA VALVE ASSEMBLY. Valve insertion, simplified MATERIAL SPECIFICATIONS MATERIAL SPECIFICATIONS.

INSERTA VALVE SLEEVE INSERTA VALVE ASSEMBLY. Valve insertion, simplified MATERIAL SPECIFICATIONS MATERIAL SPECIFICATIONS. MADE IN U.S.A. Valve insertion, simplified 10-12 installations in cast iron, ductile iron, A/C, PVC C-900 and steel pipe No Loss of Pressure Minimal Water Loss Completion time is less than 2 hours Much

More information

PB18-G Series Portable Pump Service Parts List

PB18-G Series Portable Pump Service Parts List Document Number Issue Date 01/24/07 Rev. Date 7/28/16 PB18-G Series Portable Pump Service Parts List Component Pump Pump Model (Located on Serial Plate) PB18-G2015B PB18-G2015F Exploded View See Page Cross

More information

Litter Spreader. Models SP400, SP450, SP500, SP550. Illustrated Parts Breakdown

Litter Spreader. Models SP400, SP450, SP500, SP550. Illustrated Parts Breakdown Litter Spreader Models SP00, SP0, SP00, SP0 Illustrated Parts Breakdown Page Front End Page Hydraulic System (w/ Side Mounted Reservoir) Page Hydraulic System (w/ Front Mounted Reservoir) Page Hydraulic

More information

HDPE FUSIBLE VALVES EXPECT INNOVATION

HDPE FUSIBLE VALVES EXPECT INNOVATION AVK HDPE FUSIBLE VALVES HDPE FUSIBLE VALVES EXPECT INNOVATION AVK HDPE VALVES SERIES 89 FUSIBLE BUTTERFLY VALVE Series 89 fusible butterfly valves are designed for quick, direct heat butt-fusion or electrofusion

More information

CITY OF TAMPA ADDENDUM 2. July 13, Contract 17-C-00030; David L. Tippin Water Treatment Facility Lime Slaker Replacement

CITY OF TAMPA ADDENDUM 2. July 13, Contract 17-C-00030; David L. Tippin Water Treatment Facility Lime Slaker Replacement CITY OF TAMPA Bob Buckhorn, Mayor CONTRACT ADMINISTRATION DEPARTMENT Michael W. Chucran, Director ADDENDUM 2 July 13, 2017 Contract 17-C-00030; David L. Tippin Water Treatment Facility Lime Slaker Replacement

More information

ADDENDUM No. 1. BID No /15 Chevrolet Silverado Work Trucks

ADDENDUM No. 1. BID No /15 Chevrolet Silverado Work Trucks Purchasing Department 530 Water Street Oakland, CA 94607 Date: November 17, 2017 ADDENDUM No. 1 BID No. 17-18/15 Chevrolet Silverado Work Trucks This Addendum modifies the original BID Documents for the

More information

Bid Summary Still Creek Wastewater Improvements Phase III City Job No. 411-D November 21, 2013

Bid Summary Still Creek Wastewater Improvements Phase III City Job No. 411-D November 21, 2013 Bid Summary Still Creek Wastewater Improvements Phase III City Job No. 411-D4-1102 November 21, 2013 Doughtie Construction Co., Elliott Construction Dudley Construction Ltd. SUBTOTAL GENERAL ITEMS : $191,713.00

More information

ALBEMARLE COUNTY SERVICE AUTHORITY WATER APPROVED PRODUCTS LIST Effective Date: February 9, 2017

ALBEMARLE COUNTY SERVICE AUTHORITY WATER APPROVED PRODUCTS LIST Effective Date: February 9, 2017 ALBEMARLE COUNTY SERVICE AUTHORITY WATER APPROVED PRODUCTS LIST Effective Date: February 9, 2017 I. Water Pipe, Fittings & Appurtenances A. Ductile Iron Pipe & C.I. or D.I. Fittings 1. Griffin Pipe Products,

More information

AUTOMATION ACCESSORIES IN-PLANT VALVE PRODUCTS EXTENSION STEMS FLOORBOX STEM GUIDES FLOORSTANDS COMMITTED TO ENVIRONMENTAL RESPONSIBILITY FLAP VALVES

AUTOMATION ACCESSORIES IN-PLANT VALVE PRODUCTS EXTENSION STEMS FLOORBOX STEM GUIDES FLOORSTANDS COMMITTED TO ENVIRONMENTAL RESPONSIBILITY FLAP VALVES INCREASING SWING CHECK VALVES FLAP VALVES SWING CHECK VALVES AUTOMATION ACTUATION CLOW VALVE has furnished valves with many assorted types of motorized to operate our valves. The gate valves use multi-turn,

More information