1. Unit selection (based on cooling load)
|
|
- Georgia Reynolds
- 5 years ago
- Views:
Transcription
1 . Outdoor unit 1. Unit selection (based on cooling load) 11. Indoor unit selection Select the indoor unit based upon cooling load and unit capacity. (The indoor unit capacity should larger than the load.) Indoor units can be of different capacities, however total capacity must be checked against the outdoor unit capacity table. 12. Outdoor unit selection Allowable combinations are described on the indoor unit combination total capacity index table. For a standard indoor unit and outdoor unit combination, select the nearest value of the total indoor unit capacity index that is less than a 100% outdoor unit combination capacity index. Indoor unit combination total capacity index outdoor unit 130% 120% indoor unit combination rate 110% 100% 90% % % 60% % RVMH060GBM RVMH100GAM RVMH100FAM (ISO) The system enables the connection of indoor units with a total capacity of between to 130% of that of the corresponding outdoor unit but where this capacity ratio exceeds 100% then the actual capacity of each indoor unit will fall a little short of its individual rated capacity when all the units are operated simultaneously. (Except Middle East models) Indoor unit capacity index Hz Unit size capacity index Hz Unit size capacity index
2 13. Real function data (1) Select the exact capacity according to outdoor unit model and combination rate using outdoor unit capacity table. According to given indoor and outdoor, find outdoor unit capacity and power input using the table. Each indoor unit capacity (power input) is calculated as follow. IUC=OUC x INX/TNX IUC: Each indoor unit capacity (power input) OUC: Outdoor unit capacity (power input) INX: Each indoor unit capacity index TNX: Total capacity index (2) If the capacity is smaller than the load, change unit to a larger capacity indoor unit and repeat the selection process. 3
3 . Outdoor unit 2. Specification Model Power supply Remark Performance Capacity (ISO) Power Others Size Function / Option Cooling 1) Heating 2) Capacity (SASO) Cooling 3) Sound Level (Front View) 4) Compressor Cooling Heating Model Type ø, V, Hz db db Fan output Running current (ISO) Power input (ISO) Running current (SASO) Power input (SASO) Design pressure Piston displacement Output Type Output Air flow rate Cooling Heating Cooling Heating Cooling Heating Cooling Heating cc/rev Watt CFM A A Watt Watt A A Watt Watt Mpa Refrigerant Refrigerant oil Connecting pipe Name Charge Control Name Charge Liquid Gas Drain lbs oz inch inch inch Net weight lbs Shipping weight lbs Net dimension (WxHxD) inch Shipping dimension(carton/case) (WxHxD) inch Temperature range (Outdoor) Cooling Heating F F Max. piping length ft Max. lift ft RVMC0CBM0 RVMC0FAM0 RVMC100FAM0 RVMH0CBM0 RVMH100FAM0 1, 208~230, 60 3, 208~230, 60 3, 208~230, 60 1, 208~230, 60 3, 208~230, 60 Set 000(00~000) 14.5(2.0~14.5) ZRD49KCPFV Digital scroll Propeller 128 x R EEV Sontex 200LT /8 3/ xx1 44.3x5x20 23 to Cooling only Set 76000(00~76000) 22.4(2.0~22.4) ZRD72KCTF5 Digital scroll Propeller 106 x R EEV Sontex 200LT / x69.5x x82.3x to Set 0(00~0) 28.0(2.0~28.0) ZRDU13MCTF5 Digital scroll + Fixed scroll Propeller (6.4~31.0) 11000(2300~11000) R EEV Sontex 200LT 66.5 x 2 1/2 1 1/ x69.5x x82.3x to Set 000(00~000) 14.5(2.0~14.5) 500(~500) 16.0(2.2~16.0) ZRD49KCPFV Digital scroll Propeller 128 x R22 22 EEV Sontex 200LT /8 3/ xx1 44.3x5x20 23 to to Heat pump Set 0(00~0) 28.0(2.0~28.0) 10(~10) 31.5(2.2~31.5) ZRDU13MCTF5 Digital scroll + Fixed scroll Propeller (6.4~31.0) 29.0(7.9~29.0) 11000(2300~11000) 100(20~100) R EEV Sontex 200LT 66.5 x 2 1/2 1 1/ x69.5x x82.3x to to ) Indoor : ºF DB, 67ºF WB / Outdoor : ºF DB, 75ºF WB / Piping length : 30ft, no lift 2) Indoor : ºF DB, 67ºF WB / Outdoor : 45ºF DB, 43ºF WB / Piping length : 30ft, no lift 3) Indoor : ºF DB, 67ºF WB / Outdoor : ºF DB, 75ºF WB / Piping length : 30ft, no lift 4) Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room. 4
4 3. Functional parts and safety devices Item Code Name RVMC0CBM0 RVMC0FAM0 RVMC100FAM0 Motor output Compressor open temp. Compressor safety OLP trip current CCH Crank case heater model Fan motor output Motor on Safety thermostat Safety off devices HPS High pressure switch Temperature Functional parts LPS Low pressure switch HPSO High pressure LPSO Low pressure DTS Thermistor (discharge) CMS Thermistor (condenser center) COS Thermistor (condenser outlet) OATS Thermistor (outdoor ) SUC.S Suction OIL.S Oil FDTS Thermistor (fixed discharge) Solenoid valve PWM (for compressor operation) Solenoid valve HGBV (for bypass of high gas) LBV Solenoid valve (liquid injection) VBV Solenoid valve (for exhaust air) BV1 Solenoid valve (for capacity control) BV2 Solenoid valve (for capacity control) 4W/V 4way valve C/V Check valve EEV Electronic expansion valve (for heating) ZRD49KCPFV 248 F 37A 90W 128W + 128W 275 F 194 F ZRD72KCTF5 347 F 110A 90W OSM1076SRC 106W + 106W 302 F 212 F ZRDU13MCTF F/320 F 110A/A 90W OSM48SRC 4W 302 F 212 F OFF : 425 Psig ON : 315 Psig OFF : 20 Psig ON : 30 Psig PS30A (NH4H) (0~425 Psig) PS30A (NH4L) (0~425 Psig) Model : , Rt=302 F, F=86Ω 103AT ( F=10kΩ) 103AT ( F=10kΩ) 103AT ( F=10kΩ) 204CTB (25 C=200kΩ) Coil : Copeland (Part # ) Body : EPV1530D Coil : Siginomiya Body : NEV603D Coil : Siginomiya Body : NEV202D 5
5 . Outdoor unit 3. Functional parts and safety devices Item Code Name RVMH0CBM0 RVMH100FAM0 Motor output ZRD49KCPFV ZRDU13MCTF Compressor Compressor safety OLP open temp. trip current 248 F 37A 311 F A CCH Crank case heater 90W 90W Safety devices Motor HPS model Fan motor output on Safety thermostat off High pressure switch 128W + 128W 275 F 194 F OFF : 425 Psig ON : 315 Psig OSME48SRC 4W 302 F 212 F LPS Low pressure switch Temperature Functional parts HPSO LPSO DTS CMS COS OATS SUC.S OIL.S FDTS PWM High pressure Low pressure Thermistor (discharge) Thermistor (condenser center) Thermistor (condenser outlet) Thermistor (outdoor ) Suction Oil Thermistor (fixed discharge) Solenoid valve (for compressor operation) Solenoid valve PS30A (NH4H) (0~425 Psig) PS30A (NH4L) (0~??? Psig) Model : , Rt=302 F, F=86Ω 103AT ( F=10kΩ) 103AT ( F=10kΩ) 103AT ( F=10kΩ) 103AT ( F=10kΩ) 204CTB ( F=200kΩ) Coil : Copeland (Part # ) Body : EPV1530D Coil : Siginomiya HGBV (for bypass of high gas) Body : NEV603D LBV VBV BV1 BV2 Solenoid valve (liquid injection) Solenoid valve (for exhaust air) Solenoid valve (for capacity control) Solenoid valve (for capacity control) Coil : Siginomiya Body : NEV202D 4W/V 4way valve Coil & Body : Saginomiya, CHV0401 Coil & Body : CHV0712 (Saginomiya) C/V Check valve Fujikoki (425 Psig) EEV Electronic expansion valve (for heating) EDM60YH (Fujikoki) EDMAOYH (Fujikoki) 6
6 4. Capacity table Combination, %(Capacity index) Outdoor (ºF, DB) Cooling (1) 0 Indoor (ºF, WB) : DB is ºF : Total capacity, : Power input 7
7 4. Capacity table 8. Outdoor unit Combination, %(Capacity index) Outdoor (ºF, DB) Indoor (ºF, WB) : DB is ºF : Total capacity, : Power input
8 (2) : Total capacity, : Power input Combination, %(Capacity index) Outdoor (ºF, DB) Indoor (ºF, WB) : DB is ºF
9 4. Capacity table 10. Outdoor unit : Total capacity, : Power input Combination, %(Capacity index) Outdoor (ºF, DB) Indoor (ºF, WB) : DB is ºF
10 (3) : Total capacity, : Power input Combination, %(Capacity index) Outdoor (ºF, DB) Indoor (ºF, WB) : DB is ºF
11 4. Capacity table 12. Outdoor unit : Total capacity, : Power input Combination, %(Capacity index) Outdoor (ºF, DB) Indoor (ºF, WB) : DB is ºF
12 13 Combination, %(Capacity index) Outdoor ºF, DB ºF, WB Heating (1) 0 Indoor (ºF, WB) : DB is ºF : Total capacity, : Power input
13 4. Capacity table 14. Outdoor unit (2) 100 : Total capacity, : Power input Combination, %(Capacity index) Outdoor ºF, DB ºF, WB Indoor (ºF, WB) : DB is ºF
14 Dimension 51. Upward (2FAN) Unit : mm/inch / 12/ 17/ Slot Anchor bolt hole 600/23 637/25 (Anchor bolt hole pitch) 3 920/36 16 (Anchor bolt hole pitch) / / / / / / / / / 9 69/ / / No. Name Description Discharge gas pipe connection hole Suction gas pipe connection hole Power wiring port Power wiring port ø12.7(1/2 ) Brazing connection ø25.4(1 ) Brazing connection 2ø22(3/4 ) ø42(1 5/8 ) 15
15 . Outdoor unit 5. Dimension 52. Onward Unit : mm/inch 0/ (pitch of foundation bolt hole) 3 1 4/ 12/ dia.hole / / 7 / / 15 8 (pitch of foundation bolt hole) Communication wire inlet Power wire inlet / / 29 2 / / 7 / 118/ / / / 7/ 1255/ 1269/ 11/ 416/ 41/ No. Name Description Gas pipe connection port Liquid pipe connection port Drain connection port ø19.05(3/4 ) Pipe ø9.52(3/8 ) Pipe ø20.0(13/16 ) Pipe 16
16 53. Upward (1FAN) Unit : mm/inch 0/ / 12/ 4 2 foundation bolt hole 11 6/25 16 (pitch of foundation bolt hole) (pitch of foundation bolt hole) 944/ / / / / / / / / / / / /416 30/ / / / / /2 16 No. Name Description Liquid pipe connection port Gas pipe connection port Foundation bolt hole Power cord & cable routing hole Power cord & cable routing hole Power cord & cable routing hole Power cord & cable routing hole Power cord & cable routing hole Power cord & cable routing hole ø12.7(1/2 ) Brazing pipe ø28.6(1 2/16 ) Brazing pipe 6ø12(8/16 ) Hole ø42(1 10/16 ) Knockout hole/side ø22(1 14/16 ) Knockout hole/side ø22(1 14/16 ) Knockout hole/side ø42(1 10/16 ) Knockout hole/inside ø22(1 14/16 ) Knockout hole/inside ø22(1 14/16 ) Knockout hole/inside 17
17 . Outdoor unit 6. Refrigerant system diagram. Cooling only (1) 0/0 fan fan solenoid valve (HGBV) super cooler motor motor capillary tube high pressure switch heat exchanger solenoid valve (PWM) digital scroll compressor CCH solenoid valve (VBV) solenoid valve (LBV) receiver capillary tube capillary tube accumulator low pressure switch flow direction of refrigerant bypass flow of protection actuated Note Supper cooler : For Middle East only 18
18 (2) 100 fan motor solenoid valve (HGBV) capillary tube high pressure switch high pressure heat exchanger Oil separator solenoid valve (PWM) cond out CCH fixed scroll compressor digital scroll compressor CCH solenoid valve (LBV) receiver solenoid valve (VBV) capillary tube capillary tube accumulator low pressure flow direction of refrigerant bypass flow of protection actuated 19
19 . Outdoor unit 6. Refrigerant system diagram (3) Main parts 1) Digital scroll compressor The variable capacity compressor shall control the unit capacity from 10% to 100%, utilizing 19 separate capacity steps. 2) Accumulator This shall prevent the return of liquid refrigerant to the compressor. 3) Liquid receiver This shall reduce the unit noise level, and also shall allow control of the flow of high pressure liquid refrigerant to the individual indoor units. 4) Solenoid valve (PWM) This valve shall be installed at the top of the digital scroll compressor and shall be used to provide capacity control of the compressor. When the valve is open the compressor is in its unloaded state. 5) Solenoid valve (HGBV) Should the suction pressure in the unit fall this valve shall open. The valve shall also be used to equalize system pressures upon shut down and assist the compressor in starting. 6) Solenoid valve (LBV) Should the compressor rise this valve shall open to cool the compressor and maintain reliable operation. 7) Solenoid valve (VBV) This valve shall also assist in equalizing the system pressure upon shut down, reducing the starting load on the compressor. 8) High pressure switch (HPS) Shall be used to stop the system operation in the event of a high pressure situation occurring. 9) Low pressure switch (LPS) Shall be used to prevent system operation should the system pressure fall below a preset limit (20 Psig) 10) Discharge (DTS) Shall be used to measure the of the discharge gas from the digital scroll compressor. 11) Condenser Mid point (CMS) Shall be used to measure condenser coil to provide control of the condenser fan motor and head pressure. 12) Condenser outlet (COS) Shall be used to measure the of the liquid refrigerant leaving the condenser coil. 13) Outdoor air (OATS) Shall be used to measure the outdoor air. 14) Fixed capacity scroll compressor Shall be used whenever the system load exceeds % in a two compressor unit. 15) Fixed discharge (FDTS) Shall be used to measure the of the discharge gas leaving the fixed capacity scroll compressor. 16) Low pressure (LPSO) By measuring the low pressure, any abnormal system status is determined and the lowpressure protection control is performed. 17) High pressure (HPSO) By measuring the high pressure, any abnormal system status is determined and the highpressure protection control is performed. 18) Oil separator This device recovers oils emitted from the compressor and returns it to the compressor again. 20
20 62. Heat pump (1) 0 fan fan motor motor solenoid valve (HGBV) capillary tube high pressure 4way valve (4W/V) high pressure switch heat exchanger electronic expansion valve(eev) filter digital scroll compressor CCH solenoid valve (PWM) check valve (C/V) cond out low pressure solenoid valve (VBV) solenoid valve (LBV) receiver suction oil accumulator capillary tube capillary tube flow direction of refrigerant(cooling) bypass flow of protection actuated 21
21 . Outdoor unit 6. Refrigerant system diagram (2) 100 fan motor solenoid valve (HGBV) high pressure capillary tube 4way valve (4W/V) oil separator high pressure switch heat exchanger electronic expansion valve(eev) filter CCH digital scroll compressor fixed scroll compressor CCH solenoid valve (PWM) check valve (C/V) cond out low pressure solenoid valve (VBV) oil solenoid valve (LBV) receiver suction accumulator capillary tube capillary tube flow direction of refrigerant(cooling) bypass flow of protection actuated 22
22 (3) Main parts 1) Digital scroll compressor The variable capacity compressor shall control the unit capacity from 10% to 100%, utilizing 19 separate capacity steps. 2) Accumulator This shall prevent the return of liquid refrigerant to the compressor. 3) Liquid receiver This shall reduce the unit noise level, and also shall allow control of the flow of high pressure liquid refrigerant to the individual indoor units. 4) Solenoid valve (PWM) This valve shall be installed at the top of the digital scroll compressor and shall be used to provide capacity control of the compressor. When the valve is open the compressor is in its unloaded state. 5) Solenoid valve (HGBV) Should the suction pressure in the unit fall this valve shall open. The valve shall also be used to equalize system pressures upon shut down and assist the compressor in starting. 6) Solenoid valve (LBV) Should the compressor rise this valve shall open to cool the compressor and maintain reliable operation. 7) Solenoid valve (VBV) This valve shall also assist in equalizing the system pressure upon shut down, reducing the starting load on the compressor. 8) High pressure switch (HPS) Shall be used to stop the system operation in the event of a high pressure situation occurring. 9) Low pressure switch (LPS) Shall be used to prevent system operation should the system pressure fall below a preset limit (20 Psig) 10) Condenser outlet (COS) Shall measure the of the liquid refrigerant leaving the condenser coil. In the heat pump mode this shall be used for defrost control. 11) Outdoor air (OATS) Shall be used to measure the outdoor air. 12) Fixed capacity scroll compressor Shall be used whenever the system load exceeds % in a two compressor unit. 23
23 . Outdoor unit 6. Refrigerant system diagram 13) 4 Way valve (4W/V) This shall control the direction of the refrigerant flow, allowing operation in both cooling and heat pump mode. 14) Electronic expansion valve (EEV) This shall control the flow of refrigerant in the heat pump mode. The valve shall sense the suction line and pressure and adjust accordingly for optimum performance. 15) Check valve (C/V) This valve shall be used to allow the bypass of refrigerant around the EEV when the unit is in the cooling mode. 16) Suction lint (SUCS) This shall measure the suction line and be used to control the Electronic Expansion Valve. 17) Oil (OILS) This shall measure the oil to prevent oil dilution by liquid refrigerant flooding back to the compressor. 18) Fixed discharge (FDTS) Shall be used to measure the of the discharge gas leaving the fixed capacity scroll compressor. 19) Low pressure (LPSO) By measuring the low pressure, any abnormal system status is determined and the lowpressure protection control is performed. 20) High pressure (HPSO) By measuring the high pressure, any abnormal system status is determined and the highpressure protection control is performed. 21) Oil separator This device recovers oils emitted from the compressor and returns it to the compressor again. 24
24 7. Electric circuit diagram 71. Cooling only (1) 0 NOT USED USED 25
25 . Outdoor unit 7. Electric circuit diagram (2) 0 26
26 (3)
27 . Outdoor unit 7. Electric circuit diagram 72. Heat pump (1) 0 28
28 (2)
29 . Outdoor unit 8. Considerations for outdoor unit selection 81. Capacity change dependant on refrigerant piping length (1) Cooling capacity change 1) 5 ~ 7 HP % 9% 9% 92.5%.0% 89.5%.0% 86.5% % 30 Height difference (ft.) 0 100% 100% 97.0% 9%.0%.0% 86.5% Piping length (ft.) 2) 8 ~ 10 HP Height difference (ft.) %.0% 89.5%.0% 86.5% 9% 9% 97.0% 98.5% 100% 100% 97.0% 9%.0%.0% 86.5% Piping length (ft.) Refrigerant piping length and performance range correction following the height difference should be extracted from the graph (minus height difference means that the outdoor unit is installed below the indoor unit). 30
30 (2) Heating capacity change 1) 5 ~ 7 HP Height difference (ft.) Piping length (ft.) 2) 8 ~ 10 HP Height difference (ft.) % 9% 9% 93.0% 92.0%.0% 97.0% 98.0%.0% 100% 100% 98.0% 96.0% 9% 92.0%.0% Piping length (ft.) Refrigerant piping length and performance range correction following the height difference should be extracted from the graph (minus height difference means that the outdoor unit is installed below the indoor unit). 31
31 . Outdoor unit 8. Considerations for outdoor unit selection 82. Operating restrictions (1) Cooling (2) Heating 129 Outdoor (DB) 109 Only for the Middle East Outdoor (WB) Operating Envelope Operating Envelope Indoor (WB) Coldoriented type Indoor (DB) The reliability of air conditioner is preserved till the outdoor drops below 5 O F even though the air conditioner is a coldoriented type, but wind chill heating performance may fall. (3) Heating capacity restrictions During heating operation, when snow accumulates upon thermo exchanger or the outdoor s are blow 23 O F ~ 45 O F, frost may form and the heating performance may be down. To remove the frost, air conditioner performs periodic (forty minutes to seventy minutes) frost removing operation, the heating operation is turned off and fan of indoor unit also stops during the frost removing operation, the heating operation is turned off and fan of indoor unit also stops during the frost removing state (five to ten minutes) (the heating capacity table of inner and outdoor units do not reflect the performance reduction part caused by the frost removing operation). 32
32 9. Noise level 0 Sound pressure level (db, ref.2xe5) Front of unit Back of unit NC65 NC60 NC55 NC NC45 NC40 NC35 NC30 NC25 NC20 NC15 Octave band center frequency(hz) 0 Sound pressure level (db, ref.2xe5) Front of unit Back of unit NC65 NC60 NC55 NC NC45 NC40 NC35 NC30 NC25 NC20 NC15 Octave band center frequency(hz) 33
33 . Outdoor unit 9. Noise level 100 Sound pressure level (db, ref.2xe5) Front of unit Back of unit NC65 NC60 NC55 NC NC45 NC40 NC35 NC30 NC25 NC20 NC15 Octave band center frequency(hz) 34
34 10. Options Unit type Capacity (HP) Discharge duct Interface module Optional Items Centralized controller Function controller Refnet joint 7.0 MDF45AU (2 FAN) MIMB00U MCMA200U MCMA100U MDF46AU (2 FAN) MIMB00U MXJ0906AU MXJ1206AU MCMA200U MCMA100U MXJ2212AU MXJ3112AU 10.0??? (1 FAN) MIMB00U MCMA200U MCMA100U Two fan units require two discharge ducts. 35
35 VInstallation 1. Product 11. Preparation for installation 12. Deciding on where to install the air conditioner 13. Space requirements for the air conditioner 14. Accessories 15. Installation Wiring 71. Overall system configuration 72. Cable sizing for outdoor unit. Interconnect wire sizing 74. Wiring diagram 75. Interconnect wiring diagram 76. Power wiring and communication wiring configuration. Communication cable connections Panel 21. 1way cassette type 22. 4way cassette type 23. Duct type (Builtin) 3. Connecting the indoor unit refrigerant pipe 4. Drain hose installation Piping and refnet joint selection 81. Examples of using only Refnet joint 82. Examples of using both Refnet joint and distributor kit 83. Limitation when piping is installed by using only Refnet joint. Requirement when piping is installed using simultaneously both refnet joint and contributor kit 85. Pipe selection 86. Refnet joint selection 87. Installation of piping filter Drain pump installation 51. Accessories 52. Installation 6. Electronic expansion valve kit. Builtin type 62. Distributor kit type Charge/recovery of refrigerant. Refrigerant charging 92. Additional refrigerant amount calculation method 93. Recovery of refrigerant 10. Testing operation Cautions for refrigerant leaks
1. Functional parts and safety devices
. Outdoor unit 1. Functional parts and safety devices RVMC060GAM0 Item Code Name RVMC050CBM0 RVMC060GDM0 RVMC060GAM1 Motor output Compressor open temp. Compressor safety OLP trip current Crank case heater
More informationVRF Technical Data Book
VRF Technical Data Book DVM S Eco for America (R410A, 60Hz, HR) Model : AM***NXMDCR/AA History Version Modification Date Remark Ver.1.0 Released DVM S Eco HR for North America TDB 18.02.28 Ver.1. Re 18.0
More informationtechnical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO
technical sales guide - 60Hz Taurus R Ducted Split Units UPTO HIGH AMBIENT OPERATION 52 O C Page CONTENTS Nomenclature.. 2 Description. 3 Features.. 3 Product Data. 4 Condensing Unit Cooling Performance
More informationVersion Modification Date Remark
Version Modification Date Remark Index 1 Nomenclature 2 Specifications 3 Capacity table 4 Dimensional drawing 5 Electrical wiring diagram 6 Sound pressure level 7 Temperature and air flow distribution
More informationVRF. Technical Data Book. Ceiling for America (R410A, 60Hz, HP) Model : AM***FNCDCH***
VRF Technical Data Book Ceiling for America (R410A, 60Hz, HP) Model : AM***FNCDCH*** History Version Modification Date Remark Ver.1.0 Release Ceiling for America (R410A, 60Hz, HP) 15.11.04 - 1 Nomenclature
More informationSPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE
SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASYA24LCC ASYA24LCC ASYA24LCC Outdoor unit AOYR24LCC AOYR24LCD AOYR24LCL CONTENTS SPECIFICATIONS..................1 DIMENSIONS.....................
More informationSINGLE. Technical Data Book. Big Duct for Europe (R410A, 50Hz, H/P) Model : AC180JNHPKH/EU AC180JXAPNH/EU AC200JNHPKH/EU AC200JXAPNH/EU
SINGLE Technical Data Book Big Duct for Europe (R410A, 50Hz, H/P) Model : AC180JNHPKH/EU AC180JXAPNH/EU AC200JNHPKH/EU AC200JXAPNH/EU History Version Modification Date Remark Ver.1.0 Release SINGLE Big
More informationSINGLE. Technical Data Book. 4Way Cassette S for Nordic (R410A, 50Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU)
SINGLE Technical Data Book 4Way Cassette S for Nordic (R4A, 5Hz) Model : AC***JN4CEH/EU (ODU: AC***JXSC*H/EU) History Version Modification Date Remark Ver.1. Released SINGLE for Nordic TDB 15.3.. Ver.1.1
More informationSPLIT TYPE AIR CONDITIONER. CASSETTE type. Models Indoor unit Outdoor unit MC24Y3E
SPLIT TYPE AIR CONDITIONER CASSETTE type Models Indoor unit Outdoor unit C24YE MC24Y3E MR24Y3E1 SPECIFICATIONS TYPE COOL & HEAT INDOOR UNIT MC24Y3E OUTDOOR UNIT MR24Y3E1 COOLING CAPACITY 23,500-22,500
More informationSINGLE. Technical Data Book. HSP Duct for America (R410A, 60Hz, H/P)
SINGLE Technical Data Book HSP Duct for America (R41A, 6Hz, H/P) Version Modification Date Remark Ver.1.4 Modified MCA 16.3.8 Ver.1.5 Modified Specifcation for MCA, Compressor oil type, Capacity Table,
More informationR22 TECHNICAL MANUAL. Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E. Cooling only & Heatpump [50Hz]
R22 TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FF-C, FHC-E, FFY-C, FHYC-E Cooling only & Heatpump [50Hz] Table of Contents Table of Contents Nomenclature...1 Indoor...1
More informationPerformance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW
R410a Refrigerant SHS1 Split Ducted Model INDOOR COIL ENTERING AIR TEMP DB WB 21 23 2 27 29 31 Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE 30 3 40 4 17 14.0 9.1 9.8 13.2 8.8 9.0 12. 8. 12.9
More informationR-22, 13 SEER 60 Hertz
TECHNICAL GUIDE R-22, 13 SEER 60 Hertz Description These UPG packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point
More informationR410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2
R410A TECHNICAL MANUAL Inverter Single Split Series Air Conditioner FTK-J, FTXN-J Series Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2 Table of Contents Table of Contents Nomenclature...1 Indoor...1 Outdoor...1
More informationPRK PREVIEW. System. OZONE FRIENDLY R-407C Series. Inverter Heat Pump Series Heat Recovery Series PLUS Series (Heat Pump)
PRK 00-04 PREVIEW System OZONE FRIENDLY R-407C Series Inverter Heat Pump Series Heat Recovery Series PLUS Series (Heat Pump) 3DUW#4 2XWGRRU#8QLWV 111111111111111111111111111111111111111111111111111111111111111111111
More informationD M S 760 C01 A A 1 1
CONTENTS Description Features Options Available Selection Method Product Data Cooling Performance Data (85 F Ambient Cooling Performance Data (95 F Ambient) Cooling Performance Data (105 F Ambient)..............................
More informationHEAT PUMPS UPKB- SERIES. Seven Models
FORM NO. P22-754 REV. 1 Supersedes Form No. P11-729 Rev. 8 HEAT PUMPS UPKB- SERIES Seven Models 10 SEER with efficiencies ranging up to 10.30 SEER in certain matched systems. Nominal Sizes 1 1 /2 to 5
More informationTECHNICAL GUIDE R-410A, 13 SEER LATITUDE SERIES 60 Hertz
TECHNICAL GUIDE R-410A, 13 SEER LATITUDE SERIES 60 Hertz Description These York Latitude packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections
More informationTECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:
036-21323-001-B-0202 GENERAL SPECIFICATIONS OUTDOOR UNIT: Two independent refrigerant circuits Inherently protected fan motors Two independent scroll compressors V-Coil Design Exterior service port connections
More informationSPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE
SPLIT TYPE ROOM AIR CONDITIONER FLOOR TYPE Indoor unit AGYF09LAC AGYFLAC AGYFLAC AGYFLAC Outdoor unit AOYV09LAC AOYVLAC AOYVLAC AOYVLAL CONTENTS SPECIFICATIONS..................... DIMENSIONS.........................
More informationFDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E
R407C TECHNICAL MANUAL Split Systems Air Conditioner Ducted Blower D & E Series FDMP-D, FDYMP-D, FDP-D, FGP-D, FDYP-E, FGYP-E series Cooling only & Heatpump [50Hz] Table of Contents Table of Contents
More information50 Hz AIR - COOLED SPLIT SYSTEM. Products That Perform...By People Who Care AIR CONDITIONERS WITH SCROLL COMPRESSORS
R FORM NO: MS0305F Products That Perform...By People Who Care AIR - COOLED SPLIT SYSTEM AIR CONDITIONERS WITH SCROLL COMPRESSORS 50 Hz COOLING CAPACITY- 60 MBH TO 1360 MBH ACCS SERIES HEB-D, EB-D SERIES
More informationAE R5 February 1997 Reformatted November 2010
AE21-1278 R5 February 1997 Reformatted November 2010 Moduload Capacity Control for 3D Compressors On refrigeration and air conditioning applications where the refrigeration load may vary over a wide range,
More informationT-SERIES COMMERCIAL SPLIT SYSTEMS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 232,000 Btuh AIR CONDITIONERS ELS
AIR CONDITIONERS ELS T-SERIES COMMERCIAL SPLIT SYSTEMS R-40A - 60 HZ Bulletin No. ELS-072-240 (2/208) P R O D U C T S P E C I F I C AT I O N S 072-090 Models 80-240 Models EER up to 2.0 6 to 20 Tons Cooling
More informationSINGLE. Technical Data Book. Big Ceiling for Europe (R410A, 50Hz, H/P)
SINGLE Technical Data Book Big Ceiling for Europe (R4A, Hz, H/P) Version Modification Date Remark Ver.1. Release SINGLE Big Ceiling for Europe (R4A, Hz, H/P) TDB 1.4.3 Ver.1.1 Modification for drain pipe
More informationPH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C
PH120 R410a Refrigerant Rooftop Packaged INDOOR COIL ENTERING AIR TEMP 0 c DB WB 21 23 25 27 29 31 PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C 30 35 40 45 Cap Cap Cap Cap 17 115.3 70.7 11.5
More informationSplit-Sky Air RMX-JZ Super Multi Plus
TECHNICAL DATA Split-Sky Air RMX-JZ Super Multi Plus Split Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment from the potential
More informationDVM. Technical Data Book
DVM Technical Data Book Outdoor Units I. Products 1 2 3 Outdoor units Indoor units Accessories 6 7 9 2 II. Outdoor units 1 2 3 4 5 6 Specifications Operation limit Electrical wiring diagram Sound level
More informationTechnical Service Manual
Technical Service Manual 60 Hz Low/Mid Pressure Duct Units 7 48 MBH Units 96 MBH Unit June 2009 VRF-SVM21A-EN Low and Mid Pressure Duct Units 1. Features......... 2 2. Specifications......... 3 3. Dimensions.........
More informationN2AE - 50 Hz PRODUCT SPECIFICATIONS
ISO 9001:2000 REGISTERED N2AE - 50 Hz PRODUCT SPECIFICATIONS 50 Hz AIR CONDITIONING CONDENSING UNIT 230 Volt, 1-phase, 50 Hz in 1½, 2, 2½, 3, 4 tons 400 Volt, 3-phase, 50 Hz in 3, 3½, 4, 5 tons REFRIGERATION
More informationELITE COMMERCIAL SPLIT SYSTEMS R-410A - 50 HZ. 21 to 70 kw Cooling Capacity to 58.9 kw Models AIR CONDITIONERS ELS EL S 120 S 4 S T 1 M
AIR CONDITIONERS ELS ELITE COMMERCIAL SPLIT SYSTEMS R-40A - 50 HZ Bulletin No. 49073 March 208 P R O D U C T S P E C I F I C AT I O N S Supersedes February 208 072-090 Models 80-240 Models 2 to 70 kw ing
More informationMODEL : 55A240IUBEM ROTARY COMPRESSOR SPECIFICATION SHEET 1. APPLICATION 2. COMPRESSOR DATA 3. MOTOR DATA 4. ELECTRICAL COMPONENTS
SPECIFICATION SHEET 1. APPLICATION H/P & Cooling Type Air conditioner Rated & Frequency... 208~230V 1Φ 60Hz Refrigerant.. R-22 2. COMPRESSOR DATA Pump Type Rolling Piston Type Displacement. 33.43cc/rev
More informationHigh Wall Type ( 2 Series )
Jan.05' Engineering Data High Wall Type ( 2 Series ) Indoor Unit MMK-AP0072H MMK-AP0092H MMK-AP0122H 1. Equipments 2. Technical Specifications 3. Dimensional Drawing 4. Wiring Diagram 5. Refrigerant Cycle
More informationBRIVIS DUCTED INVERTER SERVICE MANUAL DRCi
BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi 1 TABLE OF CONTENTS TABLE OF CONTENTS... 2 IMPORTANT NOTE... 3 FAULT FINDING AND DIAGNOSTICS... 3 ABBREVIATIONS... 3 PCB S... 4 OUTDOOR MAIN PCB... 4 INDOOR PCB...
More informationAir-Cooled Liquid Chiller with integrated hydraulic module
Air-Cooled Liquid Chiller with integrated hydraulic module Cooling only: CGAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800 - 900-925 Reversible: CXAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800
More informationAir Conditioning System
For continual product development, LG reserves the right to change specifications without notice. LG MULTI V Air Conditioning System 00 Air Conditioning System 00 Air Conditioning System Enjoy a clean
More informationOutdoor Units R-410A ARX-GV1B
Outdoor Units R-40A ARX-GVB t A i n y U k BS r o AV t o0g i d- lt4x pur- SRAO 2 Specifications Outdoor Units R-40A ARX-GVB 2- NOMINAL CAPACITY AND NOMINAL INPUT ARX20GVB ARX25GVB ARX5GVB For combination
More informationtechnical data air conditioning systems MXS-B Multi Application Split Sky Air
technical data MXS-B Multi Application air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health and the environment
More informationVRF. Technical Data Book. DVM Indoor Unit PAC for Global (INV, R410A, HP) Model : AM140JNPDKH/TK (50/60Hz) AM280JNPDKH/TK (50Hz)
VRF Technical Data Book DVM Indoor Unit PAC for Global (INV, R410A, HP) Model : AM140JNPDKH/TK (50/60Hz) AM280JNPDKH/TK (50Hz) History Version Modification Date Remark Ver.1.0 Release DVM Indoor PAC for
More informationProduct Data PH13NAZ. DUCTED HEAT PUMP Sizes 018 To To 5 Nominal Tons INDUSTRY LEADING FEATURES / BENEFITS
DUCTED HEAT PUMP Sizes 018 To 060 1.5 To 5 Nominal Tons Product Data A08379 INDUSTRY LEADING FEATURES / BENEFITS Energy Efficiency S Sound S Levels as low as 71 dba Design Features S New aesthetics S Small
More informationMODULOAD CAPACITY CONTROL FOR 3D COMPRESSORS
21-1278 Application Engineering Bulletin AE-1278-R5 Revised February, 1997 MODULOAD CAPACITY CONTROL FOR 3D COMPRESSORS On refrigeration and air conditioning applications where the refrigeration load may
More informationModel RAS-25YHA2 RAS-35YHA3 RAS-50YHA2 RAS-60YHA2 RAS-70YHA2 RAS-80YHA2
2-8 GENERAL DATA 2.3. INVERTER SERIES 2.3.1. INVERTER (RAS-25YHA2/35YHA3/50YHA2/60YHA2/70YHA2/80YHA2) Model RAS-25YHA2 RAS-35YHA3 RAS-50YHA2 RAS-60YHA2 RAS-70YHA2 RAS-80YHA2 Power Supply From Outdoor Unit
More informationHCH6. Product Specifications
HCH6 Product Specifications HIGH EFFICIENCY 16 SEER TWO- STAGE HEAT PUMP WITH OBSERVERt COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland
More informationDESCRIPTION FEATURES
SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H5CE150, H5CE180 AND H5CE240 12-1/2, 15 AND 20 NOMINAL TONS (World 50Hz) DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at
More informationAIR COOLED CHILLERS WATER COOLED CHILLERS
AIR COOLED CHILLERS WATER COOLED CHILLERS STANDARD UNIT SPECIFICATIONS OF COMMERCIAL AIR COOLED CHILLERS General Description & Assembly Air Cooled Chillers are commercial packaged systems complete with
More informationWALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models
SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASH9LSACW ASH12LSACW Outdoor unit AOH9LSAC AOH12LSAC CONTENTS SPECIFICATIONS...................... 1 DIMENSIONS..........................
More informationPRODUCT CODE MODEL NAME. No. DESCRIPTION DWG No. PART No. Qty Qty Qty Qty Qty Qty REMARKS
ERSATZTEILE RAS-4HNC1E, 3~ 400V 50Hz RAS-5HNC1E, 3~ 400V 50Hz RAS-6HNC1E, 3~ 400V 50Hz 1 Rear Cover Assy XEK24870 A E03946 1 1 1 1 1 1 Assembly 1-1 Pipe Cover B 17C86251 A P27003 1 1 1 1 1 1 1-2 Handle
More informationFFQN-C, FCRN-E, FFRN-C
R410A TECHNICAL MANUAL Split Unit Air Conditioner Ceiling Cassette C & E Series FCQN-E, FFQN-C, FCRN-E, FFRN-C Cooling only & Heatpump [50Hz] DAIKIN_FFRN.indb i 12/27/2012 9:28:06 AM DAIKIN_FFRN.indb ii
More informationDUCTED INDOOR UNIT ENGINEERING MANUAL
EM_MultiV_Ducted_IndoorUnits_4_16 DUCTED INDOOR UNIT ENGINEERING MANUAL High Static Ducted 7,500 to 95,900 Btu/h Low Static Ducted 7,500 to 24,000 Btu/h Low Static Built In Ducted 7,500 to 24,200 Btu/h
More informationTable of Contents. 1. Model Designation And Unit Models Guide Specifications Technical Data Performance Data 10
Table of Contents Page No. 1. Model Designation And Unit Models 1 2. Features 2 3. Guide Specifications 4 4. Standard Unit Components 5 5. Technical Data 6 6. Performance Data 10 7. Electrical Data 19
More informationV33B High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has motor-driven
More informationHigh Static Pressure Duct Fan Coil Unit
MCAC-KTSM-2012-03 High static pressure ducted FCU High Static Pressure Duct Fan Coil Unit 1. Introduction... 2 2. Nomenclature... 2 3. Product Schedule... 3 4. External Appearance... 3 5. Features... 4
More informationtechnical data air conditioning systems RXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air
technical data RXG-C Wall Mounted, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human
More informationVRF. Technical Data Book. DVM IDU_Vertical AHU for NA (R410A, 60Hz, HP) Model : AM***JNZDCH/AA
VRF Technical Data Book DVM IDU_ for NA (R4A, 6Hz, HP) Model : AM***JNZDCH/AA Version Modification Date Remark Ver.. Release DVM Indoor Unit_ TDB for America 5. 6.. Ver.. Modification for Heater kit (option)
More informationVWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ
PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ Bulletin No. 210712 March 2018 Low-sound, three-speed Wall Mount with LED display offers three
More informationHEAT PUMPS UPLB- SERIES. Seven Models
FORM NO. P22-755 Supersedes Form No. P11-732 Rev. 6 HEAT PUMPS UPLB- SERIES Seven Models 11 SEER with efficiencies ranging up to 12 SEER in certain matched systems. Nominal Sizes 1 1 /2 to 5 Tons [5.28
More informationPerformance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW
R410a Refrigerant SHS25 Split Ducted Model INDOOR COIL ENTERING AIR TEMP DB WB 21 2 25 27 29 1 Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE 0 5 40 45 17 2.4 1.8 11. 22.2 1.4 11.9 21.1 12.9 12.2
More informationEclipse 2000 Service Parts
This part list contains the service parts for the Eclipse 000 systems. The models that are covered include: CME08 CP08 ERC08 Eclipse 000 Service Parts Table of Contents CME08 Cabinet Page CME08 Interior
More informationRAC. Technical Data Book. RAC for North America (Inv, R410A, 60Hz, HP)
RAC Technical Data Book RAC for North America (Inv, R410A, 60Hz, HP) Model : AR09/12JSALBWKNCV AR09/12JSALBWKXCV AR09/12/18/24JSFLBWKNCV AR09/12/18/24JSFLBWKXCV History Version Modification Date Remark
More informationPerformance Data OUTDOOR COIL ENTERING AIR TEMPERATURE C 30 C 35 C 40 C 45 C LWB C. Sens Cap KW
R410a Refrigerant SHS35 Split Ducted Model INDOOR COIL ENTERING AIR TEMP DB WB 21 23 25 27 29 31 Performance Data OUTDOOR COIL ENTERING AIR TEMPERATURE 30 35 40 45 17 34.1 21.1 11.4 32.5 20.4 11.7 30.8
More informationSINGLE. Technical Data Book. PAC for Europe (R410A, 50Hz, HP) Model : AC***KNPDEH/EU AC***KXAD*H/EU
SINGLE Technical Data Book PAC for Europe (R410A, 50Hz, HP) Model : AC***KNPDEH/EU AC***KXAD*H/EU History Version Modification Date Remark Ver 1.0 Release SINGLE PAC for Europe (R410A, 50Hz) 16.07.15 -
More informationtechnical data air conditioning systems RKS-C RKS-B Pair Application, Inverter Controlled Unit Split Sky Air
technical data RKS-C RKS-B Pair Application, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help
More informationCAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE
COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE Single stage cooling capacity control on all 0 241 models Two stage cooling capacity control on
More information19,1 261,0 kw COOLING 23,7 333,0 kw HEATING
199 RE ER RS SO AIR COOLED HEAT PUMP LIQUID CHILLERS 19,1 261,0 kw COOLING 23,7 333,0 kw HEATING R410A PLATE RCGROUP SpA 19632013 fiftycoolyears 200 VERSIONS: (R410A) Cooling capacity 19,2 261,0 kw Heating
More informationEngineering Data Book
40VMA Outside Air Processing Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without
More informationSPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS
550.13-TG1Y(98) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS HCA300, 360, 80 & 600 5 THRU 50 NOMINAL TONS HCA80 DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece
More informationMSP Duct S Specifications
MSP Duct S Specifications Model Name AM022FNMDEH AM028FNMDEH AM036HNMPKH AM045HNMPKH AM056HNMPKH Capacity *2) 2.2 2.8 3.6 4.5 5.6 *3) 2.5 3.2 4.0 5.0 6.3 Perfomance (Total) *5) kw 1.8 2.3 2.9 3.7 4.6 VRF
More informationDUCT type. SPLIT TYPE AIR CONDITIONER (50Hz) Models Indoor unit Outdoor unit C O N T E N T S
SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit RD-90EB RO-90EPB C O N T E N T S SPECIFICATIONS... OUTLINE AND DIMENSIONS... CIRCUIT DIAGRAM...5 REFRIGERANT SYSTEM DIAGRAM...6
More informationHEAT PUMPS CLASSIC X HEAT PUMPS RPKA- SERIES. Nominal Sizes 1 1 /2 to 5 Tons [5.28 to kw]
FORM NO. P11-729 REV. 6 Supersedes Form No. P11-729 Rev. 5 HEAT PUMPS CLASSIC X HEAT PUMPS RPKA- SERIES Nominal Sizes 1 1 /2 to 5 Tons [5.28 to 17.58 kw] The Rheem RPKA- Heat Pump Outdoor units can provide
More informationACPSB-P Series 60Hz. Rooftop Units Cooling Capacity : 30 to 1360 MBH (9 to 398 kw) R22 R407C. Products that perform...
ACPSB-P Series Rooftop Units Cooling Capacity : 30 to 1360 MBH (9 to 398 kw) R R407C Products that perform...by people who care NOMENCLATURE 6 AC P S B 435 P - Q P 6-60 Hz Blank - 50Hz Blank P - R - R407C
More informationVRF. For Commercial and Light Commercial
118 VRF For Commercial and Light Commercial 119 SOLUTIONS SMALL OFFICES Fujitsu General provides perfect total air conditioning systems that take into account energy saving, low noise, comfortable airflow,
More informationConcealed Ducted Split Series R22
Concealed Ducted Split Series R22 24-60 MBH Ducted Split with Hermetic Compressor Tropical 50 Hz For more technical information please visit Table of Contents INTRODUCTION 2 NOMENCLATURE 2 UNIT RATING
More informationQ6SD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 13 SEER, 7.7 HSPF Three Phase, Packaged Heat Pump 3-5 Ton Units WARRANTY
TECHNICAL SPECIFICATIONS Q6SD Series 13 SEER, 7.7 HSPF Three Phase, Packaged Heat Pump 3-5 Ton Units The Q6SD Series packaged units are high efficiency self contained cooling and heating units that can
More informationIndoor Console. Slim Design This is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your décor.
Indoor Console Slim Design This is only 199mm thick, the slimmest on the market. Its slim design easily integrates the unit into your décor. Black Display Functional art, the touch screen display is elegant
More informationVMDA Concealed Medium Static Ducted Indoor Models - 60HZ
VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDA Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Slim, compact design for limited space requirements. Installs out of sight between the
More informationSERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI
SPLIT TYPE ROOM AIR CONDITIONER Compact Wall Mounted Wall Mounted / Floor Compact Cassette / Slim Duct INVERTER MULTI SERVICE INSTRUCTION Models Indoor unit Outdoor unit ASU7RLF ASU9RLF ASU2RLF ASU8RLF
More informationtechnical data Systems RSX(Y)P-K7W1 Inverter cooling only / heat pump series
technical data Systems RSX(Y)P-K7W1 Inverter cooling only / heat pump series Inverter cooling only / heat pump series RSX(Y)P5,8,10K7W1 RSX(Y)P-K7W1 1 Inverter cooling only / heat pump series 1 1 Specifications
More informationLow Profile Unit Coolers
Bulletin 306.0D August 2004 (Replaces 306.0C 3/04) Low Profile Unit Coolers Model ADT - Air Defrost Model LET/LLE - Electric Defrost Model HGT - Hot Gas Defrost Front access to refrigeration components.
More informationDriving and Connecting Globally. Fan Coil Unit. Model : PHW-K Size : 510CMH~2720CMH. Made in Taiwan
Driving and Connecting Globally Fan Coil Unit : PHW-K Size : 510CMH~2720CMH Made in Taiwan Features Superior low-height design. Stainless steel drain pan for condensate and corrosion protection. Flexibe-reverse
More informationR4H4. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationTechnical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.
Technical Support Division 2012.10 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram 8. Capacity tables 9. Electric characteristics
More informationV33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ
PRODUCT SPECIFICATIONS Low-sound, standard or high efficiency cassette, encased in galvanized steel offers 360 airflow for immediate, equal distribution of wide-range cooling and heating. Cassette has
More informationSPLIT-SYSTEM AIR-COOLED CONDENSING UNITS
(1100) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS H3CE180 & 240 15 AND 20 NOMINAL TONS DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at the factory to provide one-piece
More informationDESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS
DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS These completely assembled units include a well-insulated cabinet, a DX cooling coil
More information1. Features Specifications Dimensions Service Spaces Piping Diagrams Wiring Diagrams...
MCAC-VTSM-2013-08 1. Features... 264 2. Specifications... 265 3. Dimensions... 268 4. Service Spaces... 272 5. Piping Diagrams... 273 6. Wiring Diagrams... 274 7. Capacity Tables... 276 8. Electrical Characteristics...
More informationGQ6SD Series. Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS WARRANTY
TECHNICAL SPECIFICATIONS GQ6SD Series Single Packaged Heat Pump 13 SEER, R-410A 2-5 Ton Units The GQ6 Series single packaged units are high efficiency self contained cooling and heating units that can
More informationProduct Data. Features/Benefits. 38HDL Cooling Only Condensing Unit. 1 1 / 2 to 5 Nominal Tons
Product Data 38HDL018-060 Cooling Only Condensing Unit 1 1 / 2 to 5 Nominal Tons The 38HDL energy-efficient condensing unit incorporates innovative technology to provide reliable cooling performance. Built
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS Model PSH1BF Series M1200 Product Line Ultra High Efficiency Heat Pumps 16 SEER 2-5 Ton Capacity The PSH1BF Series of Maytag heat pumps offers exceptional performance as well as
More informationFault Codes. J control
J control Timer Temp Fault Codes 12 11 10 9 8 7 6 5 4 3 2 1 30 29 28 27 26 25 24 23 22 21 20 Enter unit inspection mode by pushing the UP and DOWN buttons simultaneously for two seconds. Ensure that the
More informationVMDB Concealed Medium Static Ducted Indoor Models - 60HZ
VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDB Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Bulletin No. 210711 March 2018 Slim, compact design for limited space requirements. Installs
More informationPERFORMANCE DATA TYPICAL FIELD WIRING CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS
50FP-1SB 50FP034, 038, 044, 048, 054, 064, 074 SINGLE-PACKAGE COOLING UNITS CONSTANT/VARIABLE VOLUME PRODUCT INTEGRATED CONTROLS CARRIER COMFORT NETWORK COMPATIBLE FACTORY-INSTALLED OPTIONAL ELECTRIC HEAT
More informationAFGP12B. Features. Efficiency: 12 SEER 80% AFUE. Warranty: 10-year limited compressor 10-year limited heat exchanger 5-year limited components
AFGP12B Gas/Electric Package Unit Features Shipped for horizontal applications; easily converted to downshot Side-by-side horizontal discharge Standard thermostatic expansion valve Crimp-Tite weld-free
More informationDF6SF Series Rev B TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS
TECHNICAL SPECIFICATIONS DF6SF Series Rev B Two-Stage Heat/Two-Stage Cool with Variable Speed Blower ihybrid Dual Fuel Package Units DF6SF 15 SEER, 81% AFUE, 8.0 HSPF 2 Ton thru 5 Ton Units These dual
More informationCAPACITY BTU/H FAN DATA MOTORS 240V AMPS
LP Series Cooler above 34 F AIR DEFROST CAPACITY BTU/H 10 FTD 15 FTD QTY CFM MOTORS R-404A CHARGE LPA-18-0380 3850 5775 1 940 2 0.72 32 LPA-18-0520 5200 7800 1 900 2 1.09 34 LPA-18-0610 6100 9150 1 860
More informationSUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS 50 AND 60 HZ DESCRIPTION FEATURES
(791) SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS 50 AND 60 HZ H1CE180 & 240 15 AND 20 NOMINAL TONS (60 HZ) 13 AND 17-1/2 NOMINAL TONS (50 HZ) SUNLINE 2000 DESCRIPTION These Sunline 2000 units are completely
More informationFSH1BG Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Ultra High Efficiency Heat Pump, Up to 19 SEER Residential System 2-5 Ton Capacities
TECHNICAL SPECIFICATIONS FSH1BG Series Ultra High Efficiency Heat Pump, Up to 19 SEER Residential System 2-5 Ton Capacities The iq Drive heat pump system features modulating compressor technology and variable
More informationCopeland Scroll Indoor Condensing Units for Refrigeration
Copeland Scroll Indoor Condensing Units for Refrigeration Copeland air-cooled condensing units for medium temperature and low temperature applications. Copeland Scroll condensing units are equipped with
More informationPACKAGED LIQUID CHILLER 6. HUMIDIFIER SECTIONS. C Member. Liquid Chiller. nowlc And noalc Series
6. HUMIDIFIER SECTIONS Liquid Chiller nowlc And noalc Series C Member 1 Features and Benefits OMRAN cold generator reciprocating Liquid chiller are designed and built to provide reliable,efficient performance
More informationHP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control
SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains
More informationCeiling Concealed Series FDMRN-AV1K. 50Hz. Preliminary
Ceiling Concealed Series FDMRN-AV1K 50Hz Nomenclature Main Benefits Engineering and Physical Data Electrical Data Capacity Tables Outline and Dimensions Electrical Connection Refrigerant Piping Nomenclature
More information