Methods of Testing Heavy Duty Dampers for Rating

Size: px
Start display at page:

Download "Methods of Testing Heavy Duty Dampers for Rating"

Transcription

1 Methods of Testing Heavy Duty Dampers for Rating AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL INC. The International Authority on Air System Components

2 AMCA Publications Authority AMCA International Standard 510 was approved by the membership of the Air Movement and Control Association International Inc. on July 26, It was approved as an American National Standard by the American National Standards Institute (ANSI) and became effective on October 9, As of 2015, this document no longer undergoes routine maintenance and has been withdrawn due to a lack of use. Since the document is no longer regularly reviewed by engineers as part of AMCA's document review cycle, it is to be used as a historic reference. It is not a current American National Standard. Copyright 2009 by Air Movement and Control Association International Inc. All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and 108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for permission or further information should be addressed to the Executive Director, Air Movement and Control Association International, Inc. at 30 West University Drive, Arlington Heights, IL U.S.A. Objections Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding its standards, certification programs, or interpretations thereof. For information on procedures for submitting and handling complaints, write to: Air Movement and Control Association International 30 West University Drive Arlington Heights, IL U.S.A. AMCA International, Incorporated c/o Federation of Environmental Trade Associations 2 Waltham Court, Milley Lane, Hare Hatch Reading, Berkshire, United Kingdom RG10 9TH Disclaimer AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of available information and accepted industry practices. However, AMCA does not guarantee, certify or assure the safety or performance of any products, components or systems tested, designed, installed or operated in accordance with AMCA standards or that any tests conducted under its standards will be nonhazardous or free from risk.

3 Review Committee John Hughey, Chair Per Olesen Shane Glidewell Johnny Johnson Dave Forney Jack Neiser Pete Connor Scott Hall John Powell Joseph Brooks Tim Orris Clarage Air Clean Damper Co. Barron Industries Barron Industries Effox, Inc. Effox, Inc. Ron-Noc Industries, Inc. Wahlco Metroflex Wahlco Metroflex AMCA International, Inc. AMCA International, Inc.

4 Related AMCA Documents Related Publications AMCA Publication 502 AMCA Publication 503 Damper Application Manual for Heating/ Ventilating, and Air Conditioning Fire, Ceiling (Radiation), Smoke and Fire/Smoke Damper Application Manual Related Standards ANSI/AMCA Standard 210 ANSI/AMCA Standard 500-D Laboratory Methods of Testing Fans for Certified Aerodynamic Performance Labortory Methods of Testing Dampers for Rating

5 Contents 1. Purpose and Scope Normative References Definitions / Units of Measure / Symbols Definitions Units of measure Instruments / Methods of Measurements Observations / Conduct of Tests Leakage test Cycle test Obstruction test Deflection test Seal gap test Seal air consumption test Stall test Drive redundancy test Calculations Annex A Flow Measurement (Normative) Annex B Test Report Form (Informative)

6

7 Methods of Testing Heavy Duty Dampers for Rating 1. Purpose and Scope The purpose of this standard is to establish testing methods to be used in measuring the performance of dampers used in the utility and heavy industry. The scope of the products covered in this standard shall include dampers, which are used to control flow of a gas (be it a specific gas, a mixture of gas and air, or air alone) or to isolate one section of a duct system from another section of the system. The scope narrows to those dampers generally described as custom design, heavy duty, or severe service, because such dampers are normally used in applications where elevated temperature, erosion and/or corrosion conditions exist. 2. Normative References ANSI/AMCA Laboratory Methods of Testing Fans for Aerodynamic Performance Rating, Air Movement and Control Association International, Inc., 30 W. University Drive, Arlington Heights, IL U.S.A., Definitions / Units of Measure / Symbols 3.1 Definitions Heavy duty damper A device used to control, isolate or divert a gas in a process, industrial or power generation application in accordance with customer requirements Performance variables Shop conditions Ambient temperature and atmospheric pressure in the manufacturing test facility at the time of the damper test System conditions The design temperature and pressure conditions under which the damper will operate, as specified by the purchaser Pressure drop Pressure drop is a measure of the resistance to airflow across a device. It is expressed as the difference in static pressure across an air control device for a specific rate of airflow Closure pressure Pressure drop across a closed damper Leakage Leakage is the amount of gas passing though a device when it is in the closed position at a specific pressure differential and density. It is expressed as the volumetric rate or percentage of specified flow Gland leakage A gland is a device, such as the outer sleeve of a stuffing box, designed to prevent a fluid from leaking past a moving machine part. In this context, gland leakage refers to leakage thru any moving part sealing device intended to prevent or limit the amount of gas from leaking from inside the damper to the atmosphere or vice versa Miscellaneous Shall and should The word shall is to be understood as mandatory, the word should as advisory. 3.2 Units of Measure System of units SI units (The International System of Units, Le Systéme International d'unités) [1] are the primary units employed in this standard, with I-P units (Inch-Pound) given as the secondary reference. SI units are based on the fundamental values of the International Bureau of Weights and Measures [1], and I-P values are based on the values of the National Institute of Standards and Technology, which are in turn based on the values of the International Bureau Basic units The unit of length is the meter(m), or the millimeter (mm); I- P units are the foot (ft) or the inch (in). The unit of mass is the kilogram (kg); the I-P unit is the pound mass (lbm). The unit of time is either the minute (min), or the second (s). The unit of temperature is either the degree Celsius ( C), or the degree Kelvin ( K). I-P units are either the degree Fahrenheit ( F), or the degree Rankine ( R). The unit of force is the newton (N); the I-P unit is the pound force(lbf) Flow rate and velocity Flow rate The unit of volumetric flow rate is the cubic meter per second (m 3 /s); the I-P unit is the cubic foot per minute (cfm) Velocity The unit of velocity is the meter per second (m/s); the I-P unit is the foot per minute (fpm). ANSI/AMCA

8 3.2.4 Pressure The unit of pressure is the pascal (Pa) or the millimeter of mercury (mm Hg); the I-P unit is either the inch water gauge (in. wg), or the inch mercury (in. Hg). Values in mm Hg or in in. Hg shall be used only for barometric pressure measurements Torque The unit of torque is the newton-meter (N-m); the I-P unit is the foot-pound (ft-lbf) Gas properties The unit of density is the kilogram per cubic meter (kg/m 3 ); the I-P unit is the pound mass per cubic foot (lbm/ft 3 ). The unit of viscosity is the Pascal-second, (Pa-s); the I-P unit is the pound mass per foot-second (lbm/ft-s). The SI unit of gas constant is the joule per kilogram-kelvin (J/kg-K); the I- P unit is the foot-pound force per pound mass-degree Rankine, (ft-lbf/lbm- R) Dimensionless groups Various dimensionless quantities appear in the text. Any consistent system of units may be employed to evaluate these quantities unless a numerical factor is included, in which case units must be as specified. 4. Instruments / Methods of Measurements The requirements of ANSI/AMCA 210, Section 5, shall apply where required. 5. Observations / Conduct of Tests 5.1 Leakage test Purpose The purpose of this test is to determine the amount of leakage past the closed damper at a specified operating pressure Test setup A test apparatus is to be used that allows pressure to be applied against the closed damper. The amount of gas that flows past the damper can be determined using a calibrated orifice plate or pitot tube (see Annex A). The customer is to specify if testing is to be done at system conditions otherwise the testing will be done at shop conditions and adjusting for actual conditions by the ratio of specified and tested gas density. Dampers shall be oriented in the installed position for testing when specified Test equipment Calibrated orifice plate or pitot tube A manometer of the liquid column type using inclined or vertical legs or other instruments which provide a maximum uncertainty of 1% of the maximum observed test reading during the test or 1 Pa (0.005 in. wg) whichever is larger A thermometer capable of temperature accuracies within 5 C (9 F) and with a temperature range that covers the specified operating temperature during the test Method of determining the applied force or torque required during the test to compare to predicted actuator requirements. This may consist of a pressure gauge, catalog actuator output data, a spring scale and torque arm, or other device Measurements to be taken during the test Temperature of air used to pressurize damper Pressure applied to damper Flow measurements as required for instrument Applied torque or force required to maintain the measured leakage Test methods Leakage testing shop condition With the duct pressurized to the specified condition, and maintained for a period of ten minutes, record temperature, pressure at the damper, applied torque (or force), and flow measurement Leakage testing system condition Partially open damper blade(s) allowing enough flow for heating. Heat damper until temperature reaches the test temperature and maintain for ten minutes. Close the damper blade(s) fully, and adjust upstream pressure to test pressure, record temperature, pressure at the damper, applied torque (or force), and flow measurement data Test evaluation The calculations require having the test data adjusted for temperature, altitude or other operating conditions different from any test conditions. Pass/fail criteria: If the damper exceeds the manufacturers quoted leakage rate or if the applied torque required to achieve acceptable leakage rates exceeds specifications, 2 ANSI/AMCA

9 Duct Pressure Measurement PLANE 1 Flow Measurement (Pitot or Orifice) Flow Control T1 Heating Element Pressurizing Fan Leakage to Atmosphere Test Damper Fully Closed in Position of Installation Figure 5.1 Leakage Test Setup ANSI/AMCA

10 the damper fails this test. Observations shall be recorded on the Test Report Form (see Annex B) Gland leakage The leakage tests measure the total leakage of the damper. When measurement of the gland leakage is required by the customer, a blanking plate shall be placed over the downstream side of the damper and the test procedure repeated. 5.2 Cycle test Purpose The purpose of this test is to demonstrate the successful operation of a damper through its entire range of movement Test setup The damper is to be placed in the positioning which it is to be installed, unless otherwise agreed to by the customers. If the damper is to be tested at conditions other than ambient conditions, the purchaser must specify the temperature and/or pressure that is to be applied to the damper during the cycle test Test equipment: A timer An amp meter A thermometer A manometer or pressure gauge A pressure gauge for measuring the fluid pressure applied to the damper actuator Measurements to be taken during the test: Time of operation from energizing of actuator to completion of stroke in seconds Maximum power required during stroke, in amps or fluid pressure applied to damper actuator Temperature of gas used to pressurize damper Test method If the damper is to be tested at other than ambient conditions, the specified temperature and pressure shall be applied to the damper and time allowed for equilibrium to be reached. Minimum settling time at specified temperature shall be no less than 10 minutes. The damper shall be cycled from full open to full close three times. The following observations shall be recorded on the Test Report Form (see Annex B): Time required for damper to move from actuator energization to end of stroke in each direction Maximum amperage or fluid pressure during stroke in each direction Temperature, and pressure Test evaluation No calculations are required for this test. Pass/fail criteria: If the damper manifests any of the following symptoms during the cycle test, it will be considered to have failed the test: Failure to operate Requiring any assistance to facilitate movement Any evidence of permanent distortion or damage after the test is complete Overload of motor 5.3 Obstruction test Purpose The purpose of this test is to demonstrate operation of the damper in simulated field conditions with the damper partially obstructed Test setup The damper shall be placed in the position in which it is to be installed. The purchaser shall specify the type, amount, and condition of material that is to be placed in the path of damper operation (Example: twelve inches of dry cement dust) Test equipment No test equipment is required for this test Measurements to be taken during the test No measurements are required for this test Test method The damper shall be cycled through the obstruction as specified. 4 ANSI/AMCA

11 The damper can be placed horizontally,vertically, or in the position in which it is to be installed. When specified, damper will be tested at operational temperature and pressure Damper Drive AMP Meter Duct Pressure Duct Pressure Control Flow Control T1 Heating Element Pressurizing Fan Figure 5.2 Damper Cycle Test Setup ANSI/AMCA

12 Figure 5.3 Obstruction Test Setup 6 ANSI/AMCA

13 5.3.6 Test evaluation No calculations are required for this test. Pass/fail criteria: Any permanent distortion or damage, stopping without completing the stroke, or requiring any assistance to continue operating will indicate that the damper has failed the test. Observations shall be recorded on Test Report Form (see Annex B). 5.4 Deflection test Purpose The purpose of this test is to determine blade deflection Test setup The damper shall be tested in the installed position and temperature, and pressurized on the side of the blade(s) corresponding with the customer s system once the damper is fully closed. A bar or other support will be placed across the downstream damper flanges at the point of maximum blade deflection. If this point is not readily apparent, a series of measurements across the blade will be made to determine this. If the damper consists of multiple blades having varying cross sections, measurements of each blade type will be made Test equipment A dial indicator is required Measurements to be taken during the test The blade deflection shall be measured Test method With the damper pressurized to the specified conditions, the dial indicator will read directly. If a seal air system is required, the seal air blower should be operating. The damper shall be maintained at a near constant temperature throughout the test Test evaluation No calculations are required for this test. Pass/fail criteria: Deflection at the blade(s) point of maximum deflection will be measured and recorded on the Test Report Form (see Annex B). Data will be compared to the specification to demonstrate conformance. The test temperature and pressure shall also be recorded. 5.5 Seal gap test Purpose The purpose of this test is to determine the total amount of gap present between sealing surfaces of a damper. This test is intended to compare the conformance of the manufactured part to specifications. It is not normally performed under conditions of pressure and temperature unless otherwise specified Test setup The damper should be placed in the position in which it is to be installed with the specified closing force applied Test equipment Standard sets of feeler gauges are required Measurements to be taken during the test Gap dimensions shall be measured Test method The damper shall be placed in the fully closed position. Measurements shall be taken at the gap between the blade(s) and the mating seal at 12" intervals, but no fewer than three measurements per side. The gap will be measured by the largest feeler gauge that can be inserted between the two mating surfaces without forcing them apart. The gap measurements shall be recorded for each location Test evaluation Calculations to be made: Average gap = sum of all gap measurements/number of measurement points Total gap area = average gap sealed perimeter Pass/fail criteria: If the average gap or the total gap area is more than specified, the damper has failed the test. Observations shall be recorded on the Test Report Form (see Annex B). 5.6 Seal air consumption test Purpose The purpose of this test is to determine the seal air fan consumption Test setup The damper should be tested in the installed orientation and pressurized on the side of the blade(s) corresponding with the customer s system Test equipment The seal airflow will be measured using either a pitot traverse or a calibrated orifice. ANSI/AMCA

14 Figure 5.4 Seal Air Consumption Test Setup 8 ANSI/AMCA

15 A static pressure tap shall be installed in the damper seal air chamber to record the chamber pressure Measurements to be taken during the test: Chamber pressure Seal air fan flow Test method With the damper pressurized to the specified conditions, the seal air valve shall be opened and the seal air fan started. Measure and record damper seal airflow, duct static pressure, seal air chamber pressure and temperature on the Test Report Form (see Annex B) Test evaluation No calculations are required for this test. Pass/fail criteria: If the measured seal air fan flow exceeds the specified flow, the damper has failed. If the chamber pressure is below the specified value, the damper has failed. 5.7 Stall test Purpose The purpose of this test is to demonstrate the structural integrity of the damper under the maximum actuator output Test setup The damper should be placed horizontally, vertically or in the position in which it is to be installed. A solid blockage capable of stopping the operation of the damper shall be inserted into the path of damper movement. The blockage shall be installed in such a way as to prevent movement on either opening or closing. The purchaser may specify that the location of the blockage be selected to produce the maximum amount of loading eccentricity. For electrically actuated dampers, the circuit protection should reasonably approximate the type of protection that will be used in final installation. The purchaser and manufacturer shall agree upon type and size of circuit protection that will be used during the test. For dampers that are actuated pneumatically or hydraulically, the pressure of the motive fluid shall be regulated as specified Test equipment No test equipment is required for this test Measurements to be taken during the test No measurements are required to be taken during this test Test method The damper will be either opened or closed until it contacts the blockage and stalls. The obstruction shall be removed and the damper shall be subjected to a Damper Cycle Test as described in Section Test evaluation No calculations are required for this test. Pass/fail criteria: Any visible sign of damage or permanent distortion or failure to pass the Damper Cycle Test will be an indication that the damper has failed the test. Observations shall be recorded on the Test Report Form (see Annex B). 5.8 Drive redundancy test Purpose The purpose of this test is to demonstrate the successful operation of a guillotine damper with only one half of a dualconnected drive system operating. Due to the complexities of maintaining operating conditions of temperature and flow, this test is normally performed under shop conditions unless otherwise specified Test setup The damper shall be placed in the position in which it is to be installed. One side of the drive system will be disconnected from the blade assembly. Any parts that might jam or interfere with damper operation are permitted to be removed prior to damper operation. It is allowable for the damper manufacturer to completely remove one side of the drive system prior to positioning the damper Test equipment No test equipment is required for this test Measurements to be taken during the test No measurements are required for this test Test method The damper shall be operated through one complete cycle (from full open to closed and back to full open or from full closed to open and back to full closed) Test evaluation No calculations are required for this test. Pass/fail criteria: The damper will be considered to have failed the test if it stops at any point during the cycle or requires any form of assistance to continue its movement. Observations shall be recorded on the Test Report Form (see Annex B). 6. Calculations If the tests are conducted at other than operating conditions, they shall be corrected to operating conditions. ANSI/AMCA

16 Annex A Flow Measurement (Normative) Flow measurement and test setups shall conform to ANSI/AMCA 210, Figures 1, 2A, 2B, 3, 4A, 7 and ANSI/AMCA

17 Annex B Test Report Form (Informative) Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION AND CONTROL INTERNATIONAL MEMBER 5.1 Leakage Test Purpose: The purpose of this test is to determine the amount of leakage past the closed Damper at a specified operating pressure. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper Installed Orientation: Tested Orientation: Operating Conditions: Test Conditions: Adjusted Conditions: Gas Temperature: Gas Temperature: Gas Temperature: Gas Pressure: Gas Pressure: Gas Pressure: Gas Density: Gas Density: Gas Density: Allowable Leakage: Measured Leakage: Adjusted Leakage: Damper has Passed/Failed Test: Comments: Approved By: Date: ANSI/AMCA

18 Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION MEMBER AND CONTROL INTERNATIONAL 5.2 Damper Cycle Test Purpose: The purpose of this test is to demonstrate the successful operation of a damper through its entire range of movement. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper: Installed Orientation: Tested Orientation: First Cycle Operating Conditions: Test Conditions Open Cycle Test Conditions Closed Cycle Gas Temperature: Gas Temperature: Gas Temperature: Gas Pressure: Gas Pressure: Gas Pressure: Allowable Time: Measured Time: Measured Time: Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure Second Cycle: Gas Temperature: Gas Temperature: Gas Temperature: Gas Pressure: Gas Pressure: Gas Pressure: Allowable Time: Measured Time: Measured Time: Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure: Third Cycle: Gas Temperature: Gas Temperature: Gas Temperature: Gas Pressure: Gas Pressure: Gas Pressure: Allowable Time: Measured Time: Measured Time: Allowable Amps/Pressure: Measured Amps/Pressure: Measured Amps/Pressure Damper has Passed/Failed Test: Comments: Approved By: Date: 12 ANSI/AMCA

19 Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION MEMBER AND CONTROL INTERNATIONAL 5.3 Obstruction Test Purpose: The purpose of this test is to demonstrate operation of the damper in simulated field conditions with the damper partially obstructed. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper: Installed Orientation: Description of Obstruction: Tested Orientation: Pass/Fail Criteria: Any permanent distortion or damage, stopping without completing the stroke, or requiring any assistance to continue operating will indicate the damper has failed the test. Observations: Approved by: Date: ANSI/AMCA

20 Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION MEMBER AND CONTROL INTERNATIONAL 5.4 Deflection Test Purpose: The purpose of this test is to determine blade deflection. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper: Installed Orientation: Tested Orientation: Pass/Fail Criteria: If the deflection of the center of the blade exceeds the specified amount, the damper has failed the test. Specified Conditions Measured Conditions Temperature: Temperature: Pressure: Pressure: Maximum Deflection: Maximum Deflection: Based on comparison of specified to measured blade deflection, the damper has Passed/Failed this test: Comments: Approved By: Date: 14 ANSI/AMCA

21 Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION AND CONTROL INTERNATIONAL MEMBER 5.5 Seal Gap Test Purpose: The purpose of this test is to determine the total amount of gap present between sealing surfaces of a damper. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper: Specified Total Gap Area: Specified Average Gap: Pass/Fail Criteria: If the average or total gap is greater than the specified gap, or if the total gap area is more than specified, then the damper has failed the test. Side 1 Gap Measurement Side 2 Gap Measurement Side 3 Gap Measurement Side 4 Gap Measurement Average Gap = Sum of Gaps/No. Gaps = Total Gap Area = Average Gap/Sealed Perimeter = Based on comparison of specified to measured blade deflection, the damper has Passed/Failed this test: Comments: Approved by: Date: ANSI/AMCA

22 Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION MEMBER AND CONTROL INTERNATIONAL 5.6 Seal Air Consumption Test Purpose: The purpose of this test is to determine the seal air consumption. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper: Installed Orientation: Tested Orientation: Pass/Fail Criteria: If the measured seal airflow exceeds the specified flow, the damper has failed the test. Specified Conditions Measured Conditions Seal air pressure: Seal air pressure: Duct static pressure: Duct static pressure: Specified flow: Specified flow: Based on comparison of specified to measured seal airflow the damper has Passed/Failed this test: Comments: Approved By: Date: 16 ANSI/AMCA

23 Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION AND CONTROL INTERNATIONAL MEMBER 5.7 Stall Test Purpose: The purpose of this test is to demonstrate the structural integrity of the damper under the maximum actuator output. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper: Installed Orientation: Description and Location of Obstruction: Tested Orientation: Observations: Pass/Fail Criteria: Any visible sign of damage or permanent distortion, or failure to pass the damper cycle test will cause the damper to fail the test. Based on observations and passing the Approved: Damper Cycle Test 5.2 (see attached Test Report) the damper has Passed/Failed Date: this Test: ANSI/AMCA

24 Insert your Logo here AMCA 510 Heavy Damper Method of Test AIR MOVEMENT ASSOCIATION AND CONTROL INTERNATIONAL MEMBER 5.8 Drive Redundancy Test Purpose: The purpose of this test is to demonstrate the successful operation of a guillotine damper with only one half of a dual-connected drive system operating. Date: Test Personnel: Witnesses: Reference No: Customer/User Information: Description of Damper: Installed Orientation: Description of drive type and how disconnected: Tested Orientation: Observations: Pass/Fail Criteria: The damper will be considered to have failed the test if it stops at any point during the cycle or requires any form of assistance to continue movement. Based on observations and successfully Approved: completing a complete cycle, the damper Passed/Failed this test: Date: 18 ANSI/AMCA

25 AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL INC. 30 West University Drive Arlington Heights, IL U.S.A. Tel: (847) Fax: (847) info@amca.org Web: The Air Movement and Control Association International Inc. is a not-for-profit international association of the world s manufacturers of related air system equipment, primarily but limited to fans, louvers, dampers, air curtains, airflow measurement stations, acoustic attenuators and other air system components for the industrial, commercial and residential markets.

Laboratory Methods for Testing Actuators

Laboratory Methods for Testing Actuators Laboratory Methods for Testing Actuators AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL INC. The International Authority on Air System Components AMCA Publications Authority AMCA International Standard

More information

AMCA Publication

AMCA Publication AMCA Publication 311-05 (Rev. 10/10) Certified Ratings Program - Product Rating Manual for Fan Sound Performance AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on

More information

AMCA Publication (R2010)

AMCA Publication (R2010) AMCA Publication 212-07 (R2010) Certified Ratings Program Product Rating Manual for Smoke Management Fan Performance Air Movement and Control Association International 30 W. University Drive Arlington

More information

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AMCA International Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International

More information

AMCA Publication

AMCA Publication AMCA Publication 511-13 Certified Ratings Program Product Rating Manual for Air Control Devices AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air System Components

More information

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken frame and blade to eliminate the transfer of heat or cold penetration and

More information

Central Station Air-Handling Units

Central Station Air-Handling Units 2008 STANDARD FOR Standard 430 Central Station Air-Handling Units ISHRAE ( INDIAN SOCIETY OF HEATING, REFRIGERATING & AIR CONDITIONING ENGINEERS 4100 N. FAIRFAX DR., STE. 200 ARLINGTON, VIRGINIA 22203

More information

ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on 27 October 2011 IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify

More information

Thermal Isolation. Break

Thermal Isolation. Break Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken frame and blade will minimize the transfer of thermal energy and reduces condensation.it

More information

Product Development and Testing An AMCA Registered Laboratory LJ Airflow: Static Pressure: Temperature: To 80,000 CFM To 50" wg To 600 F Bradner Ohio Test Facility Floor Plan I Approved to conduct performance

More information

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in. R Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken frame and blade to eliminate the transfer of heat or cold penetration and

More information

ANSI/AHRI Standard 881 (SI) with Addendum Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 881 (SI) with Addendum Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 881 (SI) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:

More information

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA

More information

Thermal Isolation Break. Frame Type Channel Quick Connect Single or Reverse Flange Blade Action Parallel Opposed Parallel Opposed Parallel Opposed

Thermal Isolation Break. Frame Type Channel Quick Connect Single or Reverse Flange Blade Action Parallel Opposed Parallel Opposed Parallel Opposed Application The is a low leakage thermally insulated damper with extruded airfoil blades. features broken blade which minimized the transfer of thermal energy and reduce condensation. It s also IECC (International

More information

CLASSIFICATION NOTES. Type Testing Procedure for. Crankcase Explosion Relief Valves

CLASSIFICATION NOTES. Type Testing Procedure for. Crankcase Explosion Relief Valves CLASSIFICATION NOTES Type Testing Procedure for Crankcase Explosion Relief Valves Contents 1. Scope, Application 2. Recognized Standards 3. Purpose 4. Test Facilities 5. Explosion Test Process 6. Testing

More information

TED50XT EXTREME TEMPERATURE THERMALLY EFFICIENT, INSULATED BLADE DAMPER

TED50XT EXTREME TEMPERATURE THERMALLY EFFICIENT, INSULATED BLADE DAMPER 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 APPLICATION Ruskin model TED50XT is a low leak, thermally efficient damper with insulated extruded aluminum blades specially

More information

EXPERIMENT PITOT TUBE

EXPERIMENT PITOT TUBE Read the following BEFORE getting started: EXPERIMENT PITOT TUBE Objectives, Pitot tube: a) Understand dynamic pressure, static pressure, and total pressure, and how they can be used to find air velocity.

More information

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc. ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT 15 Metal Industries, Inc. BENEFITS: Fan powered terminals are typically used for heating and cooling of perimeter zones.

More information

RM-1200 Slim Round Control Damper

RM-1200 Slim Round Control Damper RM-1200 Slim Round Control Damper Product Bulletin Code No. LIT-12011358 Issued June 16, 2008 Since 1905, Johnson Controls has developed and refined air control products by providing the highest quality

More information

VANEAXIAL FANS. DUCT FANS Capacities to 60,000 CFM Static pressures to 2 WG. TUBEAXIAL FANS Capacities to 86,000 CFM Static pressures to 3 WG

VANEAXIAL FANS. DUCT FANS Capacities to 60,000 CFM Static pressures to 2 WG. TUBEAXIAL FANS Capacities to 86,000 CFM Static pressures to 3 WG BULLETIN 671 AUGUST, 2016 VANEAXIAL FANS DUCT FANS Capacities to 60,000 Static pressures to 2 WG TUBEAXIAL FANS Capacities to 86,000 Static pressures to 3 WG Capacities to 0,000 Static pressures to 5 WG

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

Performance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment

Performance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2011 Standard for Performance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does

More information

Air Measuring Products. AMS Thermal Dispersion Pressure Differential

Air Measuring Products. AMS Thermal Dispersion Pressure Differential Air Measuring Products AMS Thermal Dispersion Pressure Differential August 2014 1 Airflow Measuring Technologies Greenheck airflow measuring products are available with either differential pressure based

More information

PC-125x Counter-Balanced Backdraft Damper

PC-125x Counter-Balanced Backdraft Damper PC-15x Counter-Balanced Backdraft Damper Product Bulletin Code No. LIT-101180 Issued April 7, 015 Refer to the QuickLIT Web site for the most up-to-date version of this document. Since 1885, Johnson Controls

More information

SP Standard Profile. In Duct or Flanged to Duct Install Types OPPOSED ACTION PARALLEL ACTION. Extended Rear Flange Install Type

SP Standard Profile. In Duct or Flanged to Duct Install Types OPPOSED ACTION PARALLEL ACTION. Extended Rear Flange Install Type 1 SUBMITTAL DATA Series 1000 Air-Foil Control Damper SP Standard Profile 2" 50.8 mm In Duct or Flanged to Duct Install Types 4" 101.6 mm 6.4" 162.6 mm blades fully open 1" 25.4 mm Extended Rear Flange

More information

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101) 500-YH SINGLE DUCT AIR TERMINAL UNIT FORM 130.12-EG1 (1101) Table of Contents General Description.......................................................................3 500-YH Features........................................................................4-5

More information

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options Application and Design The series is a general purpose, low leakage control damper intended for application in low pressure and velocity systems. atings Pressure: 2 in. wg (.5 kpa) - pressure differential.

More information

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178)

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178) Application and Design The is an extremely low leakage damper designed to meet the highest standards established for commercial control dampers. The is intended for application in medium to high pressure

More information

SD-1250 and SD-1600 Series Smoke Dampers

SD-1250 and SD-1600 Series Smoke Dampers SD-1250 and SD-1600 Series Smoke Dampers Product Bulletin Code No. LIT-1201592 Issued January 30, 2014 Supersedes October 14, 2013 Johnson Controls provides a leakage-rated damper for life safety smoke

More information

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES FAN TERMINAL UNIT SPECIFIABLE FEATURES Galvanized steel casing, mechanically sealed for low leakage construction NEMA TYPE 1 rated hinged control enclosure with standoff to prevent penetration of casing

More information

Fluid Sealing Association

Fluid Sealing Association Fluid Sealing Association STANDARD FSA-HIPD-803-10 HEAVY INDUSTRY PROCESS DAMPERS TERMS AND DEFINITIONS 994 Old Eagle School Road, Suite 1019 Wayne, Pennsylvania 19087-1866 Phone: (610) 971-4850 Fax: (610)

More information

Performance Rating of Central Station Air-handling Unit Supply Fans

Performance Rating of Central Station Air-handling Unit Supply Fans AHRI Standard 430 (I-P) With Addendum 1 2014 Standard for Performance Rating of Central Station Air-handling Unit Supply Fans AHRI STANDARD 430 (I-P)-2014 WITH ADDENDUM 1, PERFORMANCE RATING OF CENTRAL

More information

VCD-23. Flange Options. Size Limitations

VCD-23. Flange Options. Size Limitations Application and Design The series is a ruggedly built low leakage control damper intended for application in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators

More information

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178)

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178) R Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken blade to eliminate the transfer of heat or cold penetration and reduced

More information

Defining Innovation. backward curved FANs

Defining Innovation. backward curved FANs Defining Innovation. high efficiency industrial backward curved FANs TYPE HIB BULLETIN 00-B May 20 HIB High-Efficiency Industrial Backward-Curved Fans Model HIB fans from Twin City Fan & Blower employ

More information

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404) 500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT Table of Contents Introduction...3 500-YVI Features...4-5 Dimensional Data...6-7 ARI Rating Points...8 Statement of Standard Test Conformity...8 Motor Amperage

More information

AMD-33 Air Measuring Station with VCD-33 Control Damper

AMD-33 Air Measuring Station with VCD-33 Control Damper Application and Design Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) Frame Type 5 in. x 1 in. hat channel - Blade Material Galvanized

More information

VCD-23 Low Leakage CONTROL DAMPER

VCD-23 Low Leakage CONTROL DAMPER Application and Design The series is a ruggedly built low leakage control damper intended for application in low to medium pressure and velocity systems. A wide range of electric actuators are available.

More information

VERANTIS. FRP Fans: CMHB Series Performance and Technical Information. Environmental Solutions Group

VERANTIS. FRP Fans: CMHB Series Performance and Technical Information. Environmental Solutions Group VERANTIS Environmental Solutions Group FRP Fans: CMHB Series 6-8-10 Performance and Technical Information Bulletin 11-6 Rev May 2013 VERANTIS Environmental Solutions Group Verantis Environmental Solutions

More information

VCD-23. Low Leakage CONTROL DAMPER

VCD-23. Low Leakage CONTROL DAMPER Application and Design The series is a ruggedly built low leakage control damper intended for application in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators

More information

Turning Air Into Solutions. PLUG FANS TYPE BCPL

Turning Air Into Solutions. PLUG FANS TYPE BCPL Turning Air Into Solutions. PLUG FANS TYPE BCPL CATALOG 350 December 2009 BCPL Plug Fans BCPL plug fans from Twin City Fan & Blower are compact and versatile. Their versatility allows them to be used for

More information

HCD-230 Industrial Control Damper

HCD-230 Industrial Control Damper Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options.

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options. Model Application The is a low leakage high performance control damper with extruded aluminum airfoil blades. Blades are completely contained within the frame allowing the damper to be directly mounted

More information

WD-200 Series. Model WD-220 Flange Opposite Motor. Model WD-210 Flange on Motor Side. Model WD-200 No Flange. Motorized Backdraft Damper.

WD-200 Series. Model WD-220 Flange Opposite Motor. Model WD-210 Flange on Motor Side. Model WD-200 No Flange. Motorized Backdraft Damper. Application The WD200 series are electrically motorized backdraft dampers that open when energized and spring return close when deenergized. The WD200 series are for horizontal or vertical mounting. Primary

More information

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction. Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404)

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404) 500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT Table of Contents General Information...3 500-YCI Features...4-5 Dimensional Data...6-7 ARI Rating Points...8 Statement of Standard Test Conformity...8 Motor

More information

VANEAXIAL & TUBEAXIAL FANS

VANEAXIAL & TUBEAXIAL FANS BULLETIN 482 July 2008 VANEAXIAL & TUBEAXIAL FANS Type "S" Belt Driven Featuring Welded Steel Propellers Models VSBD & TSBD Model TSBD Belt Driven Tubeaxial Type "S" Vaneaxial & Tubeaxial Fans For applications

More information

Product Information. Applications. Warranty. Lab Calibrated. Residential, Commercial, OEM. ABV Sizes Available Airflow Range THE USA PROUDLY MADE IN

Product Information. Applications. Warranty. Lab Calibrated. Residential, Commercial, OEM. ABV Sizes Available Airflow Range THE USA PROUDLY MADE IN PROUDLY MADE IN R38089 THE USA Classified by UL to UL 2043 for heat release rate and smoke optical density. ABV-4 ABV-5 ABV-6 Product Information The ABV Automatic Balancing Valves maintain a constant

More information

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options Application The series is a general purpose control damper for applications as an automatic control or manual balancing damper with low to medium pressure and velocity systems. A wide range of electric

More information

Laboratory Exhaust Air Terminal

Laboratory Exhaust Air Terminal Laboratory Exhaust Air Terminal Page 1 of 11 Figure 1. Laboratory Exhaust Air Terminal. The APOGEE Automation Laboratory Room Exhaust Air Terminal is an industrial grade, easy-to-install, prepackaged airflow

More information

Fire Dampers Catalogue

Fire Dampers Catalogue Fire s Catalogue DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) CRFD - Type A, B, CR & CO Rectangular, Round & Flat Oval UL 555 Classified 2013 For Use in Static & Dynamic Systems 3 Hour Rating Made in

More information

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options Application and Design The combines the functionality of an accurate airflow measuring station and a low leakage control damper into one compact assembly that both measures and regulates airflow volumes

More information

EVALUATION REPORT 347

EVALUATION REPORT 347 Printed: March 1984 Tested at: Lethbridge ISSN 0383-3445 Group 5i EVALUATION REPORT 347 Koenders Model KV20 Ventilation Fan A Co-operative Program Between ALBERTA FARM MACHINERY RESEARCH CENTRE PRAIRIE

More information

Weather Louvre Test. Report 57668/1. Carried out for Seng Yoon Seng Holdings SDN. BHD. By Andrew Freeth. 14 January 2014

Weather Louvre Test. Report 57668/1. Carried out for Seng Yoon Seng Holdings SDN. BHD. By Andrew Freeth. 14 January 2014 Weather Louvre Test Report 57668/1 Carried out for Seng Yoon Seng Holdings SDN. BHD By Andrew Freeth 14 January 2014 Weather Louvre Test Carried out for: Seng Yoon Seng Holdings SDN. BHD No. 46, Jalan

More information

PIM Pressure Independence Module

PIM Pressure Independence Module PIM Pressure Independence Module PIM : Product Overview BENEFITS AT A GLANCE QUIET VAV DIFFUSER OPERATION The PIM Pressure Independence Module is a modulating static pressure controller/actuator that allows

More information

COMMERCIAL DUTY PLENUM FANS

COMMERCIAL DUTY PLENUM FANS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS COMMERCIAL DUTY PLENUM FANS EPLFN EPLQN CATALOG 455 JUNE 2014 PLENUM FANS Overview EPLFN I EPLQN Plenum fans are unhoused fans designed

More information

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD R CONTENTS MODEL: KYODO / KYODO-R... 1 INTRODUCTION... 1 APPLICATION... 1 VARIABLE AIR VOLUME SYSTEM... 1 FEATURES... 2 MATERIALS... 3 AIR VOLUME CONTROL

More information

AD-1251 Probe with Differential Pressure Transducer

AD-1251 Probe with Differential Pressure Transducer AD-1251 Probe with Differential Pressure Transducer Product Bulletin Code No. LIT-12011473 Issued October 31, 2011 Supersedes September 6, 2011 The AD-1251 Probe with Differential Pressure Transducer (DPT)

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1 X X testregistrierung CAV controllers Type Adjustment scale ATEX-Zertifizierung For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) Circular, mechanical self-powered

More information

TURNING AIR INTO SOLUTIONS. COMMERCIAL DUTY PLENUM FANS EPLFN EPLQN

TURNING AIR INTO SOLUTIONS. COMMERCIAL DUTY PLENUM FANS EPLFN EPLQN TURNING AIR INTO SOLUTIONS. COMMERCIAL DUTY PLENUM FANS EPLFN EPLQN CATALOG 455 June 2014 PLENUM FANS Overview EPLFN I EPLQN Plenum fans are unhoused fans designed to operate inside of field-fabricated

More information

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section SECTION 15910 DUCT ACCESSORIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division-1 Specification Sections,

More information

Performance Rating of Air Terminals

Performance Rating of Air Terminals AHRI Standard 881 (SI) 2017 Standard for Performance Rating of Air Terminals IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products,

More information

FRP Fans: CLUB Series Performance and Technical Information

FRP Fans: CLUB Series Performance and Technical Information FRP Fans: CLUB Series 1500-7300 Performance and Technical Information Verantis Environmental Solutions Group provides solutions for most common and complex situations including repair, rebuilding, field

More information

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options Application Thermal Dispersion Air Measuring Station with VCD-23 Control Damper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage control

More information

Model VCD-43 Extruded Airfoil Blade Control Damper

Model VCD-43 Extruded Airfoil Blade Control Damper Application and Design The is an extremely low leakage damper designed to meet the highest standards established for commercial control dampers. The is intended for application in medium to high pressure

More information

I Fan Powered Terminal Unit

I Fan Powered Terminal Unit I Fan Powered Terminal Unit VARIABLE VOLUME PARALLEL FLOW Fan Powered Terminal Unit Variable volume parallel flow Product Overview Variable Volume/Parallel Flow Fan Powered Terminal Units Honeywell parallel

More information

PIM Pressure Independent Module

PIM Pressure Independent Module PIM Pressure Independent Module PIM : Product Overview BENEFITS AT A GLANCE QUIET VAV DIFFUSER OPERATION The PIM Pressure Independent Module is a modulating static pressure controller/actuator that allows

More information

DASMA DASMA

DASMA DASMA DASMA 108-2017 Standard Method For Testing Sectional Garage Doors And Rolling Doors: Determination Of Structural Performance Under Uniform Static Air Pressure Difference DASMA 108-2017 Door & Access Systems

More information

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume PennBarry Fan Guide Specification Laboratory Exhaust System: Model vplume This document 2018 PennBarry vplume is a commercial lab exhaust fan that ensures a greater margin of safety by effectively dispersing

More information

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) X X testregistrierung CAV controllers Type Adjustment scale For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) Rectangular, mechanical self-powered

More information

WD-300 Series. Backdraft Damper Vertical Mount - Horizontal Airflow. Application and Design. Ratings. Frame Styles. Size Limitations.

WD-300 Series. Backdraft Damper Vertical Mount - Horizontal Airflow. Application and Design. Ratings. Frame Styles. Size Limitations. Application and Design The WD300 series dampers are designed to prevent reverse airflow in horizontal exhaust applications. The WD300 features a pressure sensitive blade design that opens and remains open

More information

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available:

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available: Model ABV Tag: Project: Location: Date: Engineer: Contractor: Architect: Submitted by: Application: The ABV Automatic maintains a constant airflow volume in HVAC applications. The highly engineered damper

More information

Model SEVCD-33. Low Leakage Airfoil Control Damper. Application and Design. Ratings (See page 3 for specific limitations) Blade Operation

Model SEVCD-33. Low Leakage Airfoil Control Damper. Application and Design. Ratings (See page 3 for specific limitations) Blade Operation Application and Design The is a severe environment 316SS ultra low leakage control damper with rugged stainless steel airfoil blades designed to meet the highest standards established for commercial control

More information

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations.

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations. Application and Design The is a vertical style face and bypass low leakage damper. This model is intended for application in medium to high pressure and velocity systems. Smooth profile extruded aluminum

More information

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems

More information

Series HCD Airfoil Control Damper

Series HCD Airfoil Control Damper Series HCD Airfoil Control Damper Model: HCD-1 The Holyoake HCD-1 is a precisely made volume and pressure control device with extremely low leakage when closed, (in the range of 0.003m 3 /s at 100 Pa).

More information

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I Application and Design Model is a combination fire smoke damper that is UL classified to protect corridor ceiling penetrations as required by the Uniform Building Code. This model s operational ratings

More information

UK Weighing Federation Technical Articles

UK Weighing Federation Technical Articles 3.4 WEIGHTS Introduction It normally starts with a phone call from a potential customer, I need some weights. As with any enquiry for any piece of weighing equipment, the first and most important point

More information

Fan Powered Terminal Units FPV, FDV Series Variable Volume Parallel Flow

Fan Powered Terminal Units FPV, FDV Series Variable Volume Parallel Flow Recommended Air Volume Ranges CP 101 Unit Size L/s Min.* L/s Max. cfm Min.* cfm Max. 6 31 212 66 450 8 62 378 132 800 10 104 637 221 1350 12 146 991 310 2100 14 207 1416 439 3000 16 268 1888 568 4000 CP

More information

CURTAIN TYPE FIRE DAMPER

CURTAIN TYPE FIRE DAMPER MODEL: IBD-2 / IBD-2H STANDARD CONSTRUCTION FIRE RATING UL 555 1-1/2 hours UL classification damper SS: 4 hours rating classification damper NOTES Damper s dimension is usually about 10 mm smaller than

More information

Air Measuring Products AMD AMS IAQ

Air Measuring Products AMD AMS IAQ Air Measuring Products AMD AMS IAQ January 1 2012 Air Measuring Products Why is outside air measurement important? There are many significant benefits to monitoring outside air volumes. By measuring the

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

VCD-43V. Vertical Airfoil Blade Control Damper. Application and Design. Ratings. Size Limitations. Features and Options: Pressure:

VCD-43V. Vertical Airfoil Blade Control Damper. Application and Design. Ratings. Size Limitations. Features and Options: Pressure: Application and Design is a low leakage damper with vertical blade orientation designed to meet the highest standards established for commercial control dampers. The is intended for application in medium

More information

NEBB STANDARDS SECTION-6, PART 2 PROCEDURES

NEBB STANDARDS SECTION-6, PART 2 PROCEDURES NEBB STANDARDS SECTION-6, PART 2 PROCEDURES SECTION 6 BASIC TAB MEASUREMENTS 6.1 INTRODUCTION The purpose of this Section is to describe the procedures used in making basic TAB measurements. These recommended

More information

A Complete Line of Quality Products for Marine Applications

A Complete Line of Quality Products for Marine Applications american warming and ventilating A Mestek Company A Complete Line of Quality Products for Marine Applications 1 About AWV Marine Dampers At American Warming and Ventilating, we are committed to design

More information

MOTORIZED VOLUME DAMPER

MOTORIZED VOLUME DAMPER MOTORIZED VOLUME DAMPER 1 a perfect partner in performance... Our Product Ranges Dampers 1 Fire Dampers 2 Fire / Smoke Dampers 3 Volume Control Dampers 4 Motorized Control Dampers 5 Pressure Relief Dampers

More information

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations. Application Model is a leakage rated modulating smoke damper with 3V style blades. The has been qualified to 2,000 fpm (10.2 m/s) and 6 in. wg (1.5 kpa) for operational closure in emergency smoke control

More information

Model VCD-34. Low Leakage Insulated Airfoil CONTROL DAMPER. Ratings (See page 3 for specific limitations) Flange Options.

Model VCD-34. Low Leakage Insulated Airfoil CONTROL DAMPER. Ratings (See page 3 for specific limitations) Flange Options. Application and Design The Series is a ruggedly built low leakage control damper with thermally insulated blades. The is intended for application in medium pressure and velocity systems. This model also

More information

Centrifugal Inline Fans Models SQ and BSQ Direct and Belt Drive

Centrifugal Inline Fans Models SQ and BSQ Direct and Belt Drive Centrifugal Inline s Models SQ and BSQ Direct and Belt Drive May 21 Models SQ and BSQ Centrifugal Square Inline Duct s Table of Contents Standard Construction Features...4-5 Vari-Green Motor & Control

More information

High Performance Axial Fans

High Performance Axial Fans High Performance Axial Fans Model RA Standard and High Temperature High Efficiencies Low Sound January 2014 High Performance Axial Fans Greenheck s model RA, high performance, direct-driven axial fans,

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -HS, Vektor -MS and Vektor -CS with Variable Geometry Nozzle September 017 Vektor -HS, Vektor -MS and Vektor -CS Greenheck s Variable Geometry Nozzle exhaust systems allow

More information

Model VCD-20V. 3V Vertical Control Damper. Application and Design. Ratings (See page 4 for specific limitations) Flange Options.

Model VCD-20V. 3V Vertical Control Damper. Application and Design. Ratings (See page 4 for specific limitations) Flange Options. Application and Design The series is a vertical blade general purpose damper for application as an automatic control or manual balancing damper. This model is intended for application in low to medium

More information

Performance of VAV Fan-Powered Terminal Units: Experimental Setup and Methodology

Performance of VAV Fan-Powered Terminal Units: Experimental Setup and Methodology NY-08-012 (RP-1292) Performance of VAV Fan-Powered Terminal Units: Experimental Setup and Methodology James C. Furr Dennis L. O Neal, PhD, PE Michael A. Davis Fellow ASHRAE John A. Bryant, PhD, PE Andrew

More information

RD-2000 Round Control Dampers

RD-2000 Round Control Dampers RD-000 Round Control Dampers Product Bulletin Code No. LIT-8105 Issued February 5, 010 Supersedes July, 009 Johnson Controls provides top-quality, low-leakage RD-000 Round Control Dampers for use in Heating,

More information

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS

ZEPHYR CABINET. Single & Twin Unit Cabinet Fans. Moving Your Way BULLETIN ZC15 TABLE OF CONTENTS ZEPHYR CABINET Single & Twin Unit Cabinet Fans Moving Your Way TABLE OF CONTENTS Introduction, Certifications & Listings, Features & Benefits 3 Options & Accessories 4 Typical Applications & Belt Drive

More information

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm Product Data 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems 40 to 3700 cfm The 35J retrofit terminal units offer: Unit casing of 22-gage galvanized steel construction (optional

More information

DRAFT TANZANIA STANDARD MEDC9(5278)P3 - INLET AIR CLEANING EQUIPMENT FOR INTERNAL COMBUSTION ENGINES AND COMPRESSORS (Rev TZS 1959:2017

DRAFT TANZANIA STANDARD MEDC9(5278)P3 - INLET AIR CLEANING EQUIPMENT FOR INTERNAL COMBUSTION ENGINES AND COMPRESSORS (Rev TZS 1959:2017 DRAFT TANZANIA STANDARD MEDC9(5278)P3 - INLET AIR CLEANING EQUIPMENT FOR INTERNAL COMBUSTION ENGINES AND COMPRESSORS (Rev TZS 1959:2017 TBS 2017 Second Edition 1 INLET AIR CLEANING EQUIPMENT FOR INTERNAL

More information

SECTION DUST COLLECTOR

SECTION DUST COLLECTOR PART1-GENERAL 1.1 DESCRI PTION A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract Drawings. 1.2 SUBMITTALS

More information