SECTION DUST COLLECTOR

Size: px
Start display at page:

Download "SECTION DUST COLLECTOR"

Transcription

1 PART1-GENERAL 1.1 DESCRI PTION A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract Drawings. 1.2 SUBMITTALS A. Submit shop drawings and curves on air flow external static pressure, sound data for the entire dust collector silencer combination. Fan curves alone are not acceptable. And also provide documentation on accessories, Operations maintenance and instruction manuals and any other data to describe the unit. 1.3 GENERAL REQUIREMENTS A. Capacity, size and arrangement, static pressure, brake horsepower, component parts and accessories as called for and lor as necessary to obtain required results and allow for proper maintenance. Ratings based on tests made in accordance with AMCA Standard 210. Each size fan to be supplied shall be tested in the manufacturers laboratory under simulated installation conditions. Guaranteed full capacity delivery through duct systems finally installed and under conditions listed. Guaranteed sound-power level ratings not exceeding those of design equipment, or as scheduled. Equipment statically and dynamically balanced to acceptable tolerance with weights permanently fastened. B. Motors: Furnished with fan. Horsepower and type as called for. C. Drive: 1. Direct drive as called for. PART 2- PRODUCTS 2.1 GENERAL A. Furnish and install, were shown on the plans, a high efficiency filter type dust collector with integral blower sized for design air flow of 4800 WG EXT.SP. B. Dust collector shall be self-cleaning fabric type complete with cotton filters, backward C. Inclined blower, motorized shaker, factory wired controller and external discharge silencer. Manufacturer's literature shall state that dust collector and selected filter Spacing is designed for the collection of wood dust. D. Dust collector shall be airtight, all steel construction with sealed seams and gasketed quick opening doors with "V4 turn knobs. Housing shall be minimum of 14- gao mild steel

2 E. Unit shall consist of a filter section, with sloped roof to shed rain and a funnel bottom section without slide gates or doors to allow down flow of dust directly into (2) 55-gallon drum assemblies furnished by manufacturer. When the 55 gallon drums are furnished the inlet shall be centered between the drums so that wood waste is deposited in both drums. Designs where the inlet is located above one of the drums is not acceptable. Include an explosion relief vent, in the dirty section of the filter housing, per NFPA #68 and #644. F. Interior and exterior carbon steel surfaces shall be primed with two part epoxy and exterior finished urethane enamel paint. 2.2 FILTER SECTION A. Unit to include multi-pocket filter modules, each of which is sewn from one (1) piece of 8-1/4 ounce cotton sateen fabric designed to deliver in excess of 99.5% efficiency by weight on industrial dusts. The filter modules shall have rigid insert separators to prevent collapse of filters and loss of the effective filter area. Flat shaker fingers located at the bottom of the filter modules, shall prevent adjoining pockets from touching one another and blanking off. The filter pocket spacing shall be of the wide spacing type (1-1/2 in.) to permit the collected dust to be shaken off the outside of the filters freely and recommended by the manufacturer for the collection of sawdust. Paper cartridges (any derivative), fabric media, or with narrow spacing or filter that collect the dust on the inside of the filter pockets will not be accepted. B. Each filter module shall be secured in place by two lever, operated over-center, Locking mechanisms to assure a positive seal and allow for easy removal of filters from outside of unit, without tools. Designs, which require entry into unit (confined space), for filter maintenance, are not acceptable. C. Filter Cleaning: 1. Filters will be cleaned automatically after a fifteen second delay following the Shut down of the blower, by the oscillating actions delivered by the motorized Eccentric driven shaker assembly, which imparts a vibratory force throughout the entire surface of each individual filter pocket to dislodge the dust. Shaker motor shall be 1/3 HP. D. If dust collector is recirculating air back to building, the system should include an after filter section with less than % of 1 % by pass or leakage or air around the housing and include a MERV 11 section and a Hepa Filter section or the dust collector shall include an after filter housing built into the collector with Hepa Filter rated for 99.97%@.3 microns

3 2.3 BLOWER SECTION A. The integral non-sparking AMCA direct drive blower shall be located on the clean air side of the filters top mounted at the factory and be backward inclined design with a dynamically balanced impeller. It shall be driven by a 15 HP, 208V,3, PH,3450 RPM TEFC motor. The blower shall be licensed to bear the AMCA seal and be tested in accordance with AMCA Standard 210 and comply with the requirements of the AMCA Certified Air Performance Ratings Program. A factory-supplied cover shall protect the motor cooling fan from ice. B. An external field supported duct silencer fabricated with 4.75Ib. density inorganic mineral or glass fiber shall attenuate discharge noise from the blower. This media shall be protected from erosion by the airflow through the use of galvanized perforated metal with aerodynamic leading and trailing edges to insure maximum acoustical insertion loss at minimum static pressure drop. Lining of the fan scroll, instead of an external silencer, shall not be accepted. Include factory installed bird screen on discharge of silencer if air is not recirculated. 2.4 CONTROL A. Operation of the automatic shaker shall be controlled by a solid state, dual mode timer with adjustable shaker cycle range from seconds. Magnetic starters with overload relays for the blower and shaker motor and control transformer shall be factory wired in NEMA 4 control panel mounted on the unit for a single point wiring. Also included shall be a push button station for remote mounting. Unit supplied with factory wired and mounted NEMA 3R fused disconnect. Unit rated at 208 Volt- 3 Phase. B. The control pane wiring shall be either UL or ETL labeled for compliance with 508A. A certified UL or ETL representative, prior to placing equipment in operation, shall label control panels not labeled by dust collector manufacturer, in field. C. Pressing start button activates blower. Pressuring stop button deactivates blower. After a delay of 15 seconds (to allow blower to coast to a stop) the automatic shaker is activated and remains on until timer of shaker motor runs out. D. Factory mounted disconnect E. If Air flow of the system is greater than 5000 cfm and air is recirculated back to the building: 1. The return duct shall include an abort gate damper controlled by the spark detection system controller

4 2.5 SPARK DETECTION AND EXTINGUISHING SYSTEM A. Control Panel shall be the FLAMEX FLE 3000 Single Zone Console, Incoming Power requirement shall be 120/60/1. The panel shall include One (1)-12V 2.5H Battery to provide emergency back-up power for a minimum of 24 Hours to the panel in the event of loss of incoming power. The Panel shall be housed in an I P-54 Enclosure and must be installed in a dry heated area. B. Provide Two (2) Infrared Spark Detectors capable of detecting IR in.78 to 1.2 micron range. Sensors must be housed in a metallp 65 enclosure and come complete with Stainless Steel mounting hardware. Sensors must be easily removable from the duct for maintenance inspections. Detector Lens must be removable and replaceable if damaged as well as horn and strobe. C. Provide One (1) Extinguishing Assembly complete with 12 VDC Solenoid Valve, Brass Y Strainer with Stainless Steel Screen, and Ball Valve with Locking Strap, Lock and Key. The Solenoid Valve shall be the slow closing type to eliminate water hammer. A Stainless Steel Directional Spray Nozzle shall be provided as part of this Assembly, which will produce a 180-degree Fan Shaped Spray Pattern, Stainless Steel mounting hardware of Nozzle shall also be provided. The Extinguishing Assembly must be capable of flowing a minimum of 17 GPM at 44 PSI flowing pressure at the Solenoid Valve during discharge. D. If the air flow is greater than 5000 cfm and air is recirculated back to the Building: 1. The return air duct shall include a fast acting abort gate controlled by the spark detection system controller E. The spark detection System shall be Factory Mutual Approved, and installed consistent with the Manufactures recommendations. F. Provide dust switch interlock on all wood working devises so that energizing any of the wood wording machines energizes the dust collector. This dust switch shall then allow the collector to run for a full 30 sec -3 min after the wood working equipment has been de-energized to clear the system or debris 2.6 DESIGN MAKE A. Dust collector shall be Sternvent Vibraclean Mode DKPD or approval equal. Makes, Sternvent, Torit, AAF

5 PART 3- EXECUTION 3.1 I NST ALLA TION A. Provide equipment in accordance with manufacturer's instructions and compatible with intent of the respective system performance requirements. B. Provide all associated ductwork, final connections and duct supports as required. C. Test collector and dust system for operation. 1. Provide balance and test reports. D. A provision shall be made for all low voltage wiring for the complete operation of the system from control panel of spark suppression system to optical eyes and to spray solenoid. HVAC contractor shall provide all interconnecting wiring required for operation of the Flamex system. Refer to manufacturers wiring diagrams for wiring required. Refer to for further detail of wiring and routing. 120 V power to the control panel shall be by the Electrical contractor. E. Contractor will coordinate with plumbing trades to have a water line installed to feed spray nozzle of extinguish system. Water line should not be connected to fire protection sprinkler system. END OF SECTION

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Direct Gas-Fired Heating

Direct Gas-Fired Heating Direct Gas-Fired Heating Model DG 800 to 15,000 cfm Up to 1,600,000 BTU/hr Optional Evaporative Cooling January 2005 PRODUCT FEATURES Model DG Direct Gas-Fired Make-Up Air Unit The Greenheck model DG is

More information

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating.

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating. Issued 2005/06/01 Section 15831 Commercial Fans Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01355 Waste Management and Disposal..2 Section 15053 Motors, Drives and Guards..3 Section 15072

More information

Climas y Proyectos Leyco, S.A. de C.V.

Climas y Proyectos Leyco, S.A. de C.V. GENERAL DESCRIPTION : FURNISH AND INSTALL MULTI COMPONENT ROOF MOUNTED LEYCO, MODEL CAH CUSTOM AIR HANDLER MADE SELF-CONTAINED, WEATHER RESISTANT, AIR HANDLING UNITS PER MODEL NUMBER, AND PERFORMANCE DATA

More information

NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG C-PREP

NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG C-PREP Item :A Prep Room NON PRESSURIZED, GALVANIZED PREP ROOM Model #ENCG-200830-C-PREP Booth Working Dimensions: 20'0 Wide x 8'0 High x 30'0 Working Depth Approx. Booth Overall Dimensions: 20'4 Wide x 8'10

More information

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System V-Series (rev. 08/17/10) Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System Note: Optional items and/or items requiring a choice, are shown between brackets and/or parentheses

More information

SECTION HVAC POWER VENTILATORS

SECTION HVAC POWER VENTILATORS SECTION 233423 HVAC POWER VENTILATORS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive Centrifugal Inline s Models SQ-M and BSQ-M Direct and Belt Drive July 2010 Centrifugal Inline Duct s Greenheck's model SQ-M and BSQ-M centrifugal square inline fans feature a unique combination of installation

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 23 30 00 - HVAC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00, "Mechanical

More information

University of Delaware

University of Delaware SECTION 23 36 00 _ SUMMARY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Constant/Variable volume supply terminal units. 2. Fan powered terminal units. 3. Exhaust valves B. Related Sections: Section

More information

Centrifugal Filtered Supply Roof Blowers

Centrifugal Filtered Supply Roof Blowers CFS Centrifugal Filtered Supply Roof Blowers Page Introduction...................................... 2 Specifications and Dimension Data................... 3 Typical Installation................................

More information

AIR ZONE INTERNATIONAL MIXED-FLOW AIR COLUMN UNIT

AIR ZONE INTERNATIONAL MIXED-FLOW AIR COLUMN UNIT ZONE INTERNATIONAL MIXED- COLUMN UNIT 5220 TED ST. HOUSTON, TEXAS 77040 (713) 460-4040 FAX (713) 460-4050 WWW.ZONEINC.COM ZONE INTERNATIONAL MIXED- COLUMN UNIT T DUCT COLLAR INLET (A x B) PRIMARY RETURN

More information

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499] BC--1.0 03-01-1 Belt Drive Blower Coil Unit, Basic Unit Discharge ARGT. 1 4. See page 1 for filter rack details. 5. Base rail is optional on he base unit. See page 13. Base rails must be used with mixing

More information

ENVIRO UNIT CES SERIES

ENVIRO UNIT CES SERIES ENVIRO UNIT CES SERIES ENVIRO UNIT FILTER BOX Commercial Kitchen Exhaust CES-ISH 1,000 to 40,000 CFM Operation The grease laden air rises from the cooking equipment into the NFPA- 96 commercial kitchen

More information

DESIGN GUIDELINES FANS PAGE 1 of 7

DESIGN GUIDELINES FANS PAGE 1 of 7 DESIGN GUIDELINES FANS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the

More information

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MEL TXD Model Features Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

LEDGELESS VERTICAL CARTRIDGE DUST COLLECTOR

LEDGELESS VERTICAL CARTRIDGE DUST COLLECTOR RIES Platinum Cartridge Dust Collectors LEDGELESS VERTICAL CARTRIDGE DUST COLLECTOR 7 to 10 Gauge Construction 1'' Goyen Valves Goyen Solenoid lock Kit Service Ladder and Platform (optional) Manual Cam

More information

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SO TOUGH, WE GUARANTEE IT. SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL SBH SBV www.superiorrex.com SO TOUGH, WE GUARANTEE IT! www.superiorrex.com SBH / SBV Series: CONSTRUCTION FEATURES

More information

forward curved inline duct blowers

forward curved inline duct blowers Defining Innovation. forward curved inline duct blowers TYPE DBS (Single) DBT (Twin) BULLETIN 4220 January 2011 Duct Blowers General Information Twin City Fan s belt driven DBS (single) and DBT (twin)

More information

The reference in sandblasting. DCM\DCM 3000 a DCM to series.

The reference in sandblasting. DCM\DCM 3000 a DCM to series. P:\@ISTblast\1-RÉSUMÉS\Depoussiereurs \ 3000 a 50000 dust collectors 3 000 to 50 000 series general brochure Overview THE SERIES IS A POWERFUL AND ROBust UNIT FOR YOUR INDUSTRIAL DUST COLLECTION NEEDS.

More information

PACKAGED DOWNFLO EVOLUTION DUST COLLECTORS. The Complete Plug-and-Play Solution

PACKAGED DOWNFLO EVOLUTION DUST COLLECTORS. The Complete Plug-and-Play Solution PACKAGED DOWNFLO EVOLUTION DUST COLLECTORS The Complete Plug-and-Play Solution WE KNOW FILTRATION Donaldson is a global provider of filtration solutions for manufacturing industries. Our advanced technology,

More information

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile November 204 BCF Centrifugal Cabinet Contents Standard Construction Features... 3 Options and Accessories... 4 Filter and Mixing Box Data... 5 Typical Installations...

More information

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MEL TXD MEL FEATURES Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT TERMINAL UNITS www.igcaire.com SINGLE DUCT TERMINAL UNITS Direct Digital Control, Pressure Independent FEATURES 22 Gauge Galvanized Steel Casing Construction with a 20 Gauge Casing Option that Provides Strength and Product

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

The Industrial Choice. Model SCDD Direct Drive. Model SCBD Belt Driven SQUARE INLINE FANS. Direct Drive & Belt Driven Model SCDD / SCBD

The Industrial Choice. Model SCDD Direct Drive. Model SCBD Belt Driven SQUARE INLINE FANS. Direct Drive & Belt Driven Model SCDD / SCBD The Industrial Choice. Model SCDD Direct Drive Model SCBD Belt Driven SQUARE INLINE FANS Direct Drive & Belt Driven Model SCDD / SCBD BULLETIN 40 January 007 Square Inline Centrifugal Fans General Information

More information

SQUARE INLINE CENTRIFUGAL FANS

SQUARE INLINE CENTRIFUGAL FANS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS SQUARE INLINE CENTRIFUGAL FANS DSI BSI CATALOG 40 FEBRUARY 07 SQUARE INLINE CENTRIFUGAL FANS Overview DSI BSI Twin City Fan & Blower

More information

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans.

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans. SECTION 23 34 43 LABORATORY HIGH PLUME EXHAUST FANS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Tubular Centrifugal Fans

Tubular Centrifugal Fans Tubular Centrifugal Fans Model TCB Inline - Horizontal or Vertical Roof Upblast and Roof Supply March 2007 Tubular Centrifugal Fans The TCB series of inline centrifugal fans is designed for ducted inline,

More information

Filtered Kitchen Supply Packaged Ventilator

Filtered Kitchen Supply Packaged Ventilator Filtered Kitchen Supply Packaged Ventilator Page Introduction........................................... 2 Information............................................ 3 Specifications and Dimension Data KD................................................

More information

SECTION HVAC AIR CLEANING DEVICES

SECTION HVAC AIR CLEANING DEVICES SECTION 23 40 00 HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes activated carbon filters, automatic renewable media filters, disposable, extended area panel filters, disposable

More information

Downflo Systems. Containment. With Triple-Sealed Bag-In/Bag-Out for filters and hopper discharge

Downflo Systems. Containment. With Triple-Sealed Bag-In/Bag-Out for filters and hopper discharge Systems Containment With Triple-Sealed Bag-In/Bag-Out for filters and hopper discharge Setting High Standards qüé=çéã~åçë=ã~çé=çå=ñáäíê~íáçå=éèìáéãéåí=~êé=åçåíáåì~ääó=êáëáåök=`äé~åéê=~áê=~åç ïçêâéê=éñéçëìêé=~êé=ã~àçê=åçååéêåëk=qüé=açå~äçëçå

More information

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile May 2007 BCF Belt Drive Cabinet s Greenheck belt drive low-profile cabinet fans, BCF, are designed for efficiency and reliability in supply, exhaust or

More information

BELT DRIVEN CENTRIFUGAL ROOFTOP FILTERED SUPPLY FAN

BELT DRIVEN CENTRIFUGAL ROOFTOP FILTERED SUPPLY FAN Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS BELT DRIVEN CENTRIFUGAL ROOFTOP FILTERED SUPPLY FAN MODEL BCRFS CATALOG 4310 JUNE 2012 FILTERED SUPPLY VENTILATORS Model BCRFS Twin City

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MODEL RED MODEL FEATURES Exhaust air up to 3,000 CFM in high static pressure applications up to 1 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan Centrifugal Cabinet s BDF Belt Drive Duct July 007 BDF Belt Drive Duct s Greenheck s Belt Drive Duct s, BDF, provide the industry s best performance and durability. BDF is carefully engineered for efficiency

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Quiet-Duct Conic-Flow Silencers Section Specifications

Quiet-Duct Conic-Flow Silencers Section Specifications Quiet-Duct Conic-Flow Silencers Section 15000 Specifications 1.01 General A. Furnish and install Conic-Flow (tubular) silencers of the types and sizes shown on the plans and/or listed in the schedule.

More information

SPUN ALUMINUM POWER ROOF AND WALL VENTILATORS

SPUN ALUMINUM POWER ROOF AND WALL VENTILATORS BULLETIN 0 January 007 SPUN ALUMINUM POWER ROOF AND WALL VENTILATORS TYPE ACX / ACXD TYPE ATD / ATDR / ATDW / ATDWR TYPE ATB / ATBR / AWX / AWXR Model ACX Model ATB Model ACXD Model ATDR Model AWX Centrifugal

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

WAC Air Curtains Technical Guide

WAC Air Curtains Technical Guide TGWAC-2 WAC Air Curtains Technical Guide FOR WIND STOPPING, INSECT CONTROL, AND ENVIRONMENTAL SEPARATION IN COMMERCIAL AND INDUSTRIAL APPLICATIONS TABLE OF CONTENTS Introduction......................................................................2

More information

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges Phone: 800-348-1097 www.aeipaintbooths.com Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges Thank you for the opportunity to work with you on your paint booth project. Below

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS

MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS Model FF Model FFC Model ff Features Exhaust air up to 1500 CFM Forward curve centrifugal wheel for high static pressure capabilities to 1 w.g. Resilient mount, low RPM motor for quiet operation (except

More information

I Fan Powered Terminal Unit

I Fan Powered Terminal Unit I Fan Powered Terminal Unit VARIABLE VOLUME PARALLEL FLOW Fan Powered Terminal Unit Variable volume parallel flow Product Overview Variable Volume/Parallel Flow Fan Powered Terminal Units Honeywell parallel

More information

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODELS & e DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODEL DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 4,780 CFM in high static pressure applications up to 1-1/2 w.g. Attractive

More information

TURBO PRESSURE BLOWERS

TURBO PRESSURE BLOWERS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS TURBO PRESSURE BLOWERS TBA TBR CATALOG 10 APRIL 13 TURBO PRESSURE BLOWERS Models TBA TBR TBR Arrangement 8 Model TBA and TBR fans from

More information

AMCA Seal Assures rating of Sound and Air performance. 2 year fan housing warranty, 1 year motor warranty

AMCA Seal Assures rating of Sound and Air performance. 2 year fan housing warranty, 1 year motor warranty MODEL FEATURES Exhaust air up to 2,800 CFM in high static pressure applications up to 1 w.g. Direct drive units have low sound levels and quiet operation Ideal for applications where space is limited Non-overloading

More information

CH5000 Heat Recovery Ventilator

CH5000 Heat Recovery Ventilator ADVANCED COMMERCIAL Heat Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 3500-5500 CFM CASING Double-wall cabinet White exterior paint, 22-gauge galvanized steel -gauge

More information

TORIT POWERCORE DUST COLLECTORS TG SERIES. Silver Award

TORIT POWERCORE DUST COLLECTORS TG SERIES. Silver Award TORIT POWERCORE DUST COLLECTORS TG SERIES 010 Silver Award SMARTER, SMALLER COLLECTORS The Torit PowerCore TG Series designed for thermally generated dust is reshaping the future of dust and fume collection

More information

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS Air Zoë Centrifugal Inline Duct fans have been developed to efficiently handle the

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MODELS & e DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS MODEL - DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES Exhaust air up to 4,980 CFM in high static pressure applications up to 1-1/2

More information

Installation & Service Manual for Horizontal Cartridge Filtration Systems

Installation & Service Manual for Horizontal Cartridge Filtration Systems Installation and Service Manual for Installation & Service Manual for Horizontal Cartridge Filtration Systems MODELS HCF-3000 HCF-3030 HCF-3050 February 10, 2003 Installation and Service Manual for TABLE

More information

DUST COLLECTORS. Stronger. Better. CLEANER.

DUST COLLECTORS. Stronger. Better. CLEANER. DUST COLLECTORS Stronger. Better. CLEANER. Stronger. Better. CLEANER. Micro Air FORCE Dust Collectors The Next Generation Of CLEAN Air Systems Unrivaled Cleaning Technology FORCE Dust Collectors are designed

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

Issue 4 (Record Only) Job #: Innovent Submittal Date: October 30, 2012 Project: Location: Columbus, OH Innovent Job #: Submittal Issue: 4 (Record Only) Engineer: Contractor: Tag Innovent Model # AHU-BG-01

More information

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS

SECTION HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS SECTION 08350 HYDRAULIC FOUR FOLD DOORS MODEL 48 LOUVERS PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1

More information

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume PennBarry Fan Guide Specification Laboratory Exhaust System: Model vplume This document 2018 PennBarry vplume is a commercial lab exhaust fan that ensures a greater margin of safety by effectively dispersing

More information

Industry best 5 year fan housing warranty, 1 year motor warranty

Industry best 5 year fan housing warranty, 1 year motor warranty MEL FEATURES Exhaust air up to 28,000 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Belt drives permit easy performance adjustments when needed Non-overloading

More information

MODULAR BAGHOUSE DUST COLLECTORS POWERED BY

MODULAR BAGHOUSE DUST COLLECTORS POWERED BY POWERED BY COMPACT, MODULAR DESIGN The enhanced Donaldson Torit Modular Baghouse (MB) delivers reliable, efficient, continuous-duty, pulse-jet operation. The MB advantage is found in the breakthrough technology

More information

MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN

MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN MODEL FEATURES Rated up to 20,000 CFM in static pressure applications up to 2-1/2 w.g. Motor drives are located outside of the airstream Ideal for applications where space is limited Belt drives permit

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL HP COMBINATION GAS/OIL BURNERS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone 316-421-0480, Fax 316-421-0948

More information

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc. ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT 15 Metal Industries, Inc. BENEFITS: Fan powered terminals are typically used for heating and cooling of perimeter zones.

More information

DOWNFLO II DUST COLLECTORS

DOWNFLO II DUST COLLECTORS DOWNFLO II Engineered for Reliable Performance The long-standing, most influential cartridge collector in industrial air filtration history, the Donaldson Torit Downflo II (DFT), delivers optimum performance

More information

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES FAN TERMINAL UNIT SPECIFIABLE FEATURES Galvanized steel casing, mechanically sealed for low leakage construction NEMA TYPE 1 rated hinged control enclosure with standoff to prevent penetration of casing

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Defining Innovation. turbo pressure blowers. Twin City Catalog 1200

Defining Innovation. turbo pressure blowers. Twin City Catalog 1200 Defining Innovation. turbo pressure blowers MODEL TBA TBR 1 Twin City Catalog CATALOG -A May 11 Model TBA/TBR Turbo Pressure Blowers Model TBA and TBR fans from Twin City Fan & Blower are constant pressure,

More information

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section SECTION 15910 DUCT ACCESSORIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division-1 Specification Sections,

More information

TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST PROPELLER ROOF VENTILATORS. LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat)

TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST PROPELLER ROOF VENTILATORS. LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat) TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST ROOF VENTILATORS LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat) CATALOG 4870 April 17 ROOF VENTILATORS Overview Propeller Roof

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the industry s best performance and durability

More information

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

PROJ. NO SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Centrifugal Spun Aluminum Products

Centrifugal Spun Aluminum Products Centrifugal Spun Aluminum Products SDB SDBD STXB STXD Downblast & Upblast Centrifugal Roof Wall Exhausters Designed with Efficiency in Mind CSAP_0415 April 2015 Centrifugal Spun Aluminum Line Overview

More information

ceiling & inline/cabinet ventilators

ceiling & inline/cabinet ventilators Air Moving Solutions. ceiling & inline/cabinet ventilators T-Series ( T TL ) CATALOG 4600 March 2012 Ceiling&InlineVentilators T-Series T TL Twin City Fan & Blower s T Series Ceiling and TL Series Inline/Cabinet

More information

APPENDIX A. 15 DUAL WELD STATION FUME EXTRACTION with 30 WELDING BOOTHS

APPENDIX A. 15 DUAL WELD STATION FUME EXTRACTION with 30 WELDING BOOTHS APPENDIX A 15 DUAL WELD STATION FUME EXTRACTION with 30 WELDING BOOTHS The Technology Center of DuPage is seeking bids for fifteen (15) dual weld stations (total of 30 individual welding booths) with fume

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved B U I L D I N G V A L U E I N A I R. April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the

More information

MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER

MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER MODEL CWD MODEL FEATURES Exhaust air up to 3,360 CFM in high static pressure applications up to 1 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL 13686.00 MECHANICAL AND ELECTRICAL COORDINATION 230002-1 SECTION 230002 MECHANICAL AND ELECTRICAL COORDINATION 1.1 WORK INCLUDED PART 1 - GENERAL A. Work Included in This Section: Materials, equipment,

More information

MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS

MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS Model FF Model FFC MODEL FF FEATURES Exhaust air up to 1500 CFM Forward curve centrifugal wheel for high static pressure capabilities to 1 w.g. Resilient mount, low RPM motor for quiet operation Speed

More information

Tubular Centrifugal Inline Fans Page Introduction... 2 Construction Features... 3 Specification and Dimension Data TCN-D (Inline Fan- Direct

Tubular Centrifugal Inline Fans Page Introduction... 2 Construction Features... 3 Specification and Dimension Data TCN-D (Inline Fan- Direct Tubular Centrifugal Inline Fans Page Introduction........................................... 2 Construction Features.................................. 3 Specification and Dimension Data TCN-D (Inline Fan-

More information

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS SECTION 22 1123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Torit powercore. tg series. Silver Award

Torit powercore. tg series. Silver Award Torit powercore dust collectors tg series 2010 Silver Award Smarter, smaller collectors The Torit PowerCore TG Series designed for thermally generated dust is reshaping the future of dust and fume collection

More information

SINGLE DUCT AIR TERMINAL UNITS

SINGLE DUCT AIR TERMINAL UNITS AIR terminal units AIR TERMINAL UNITS MODEL NUMBER LEGEND XXXXX XXX -XXXX Model TH TL THECO Inlet Size (04, 05, 06, etc.) Generation 5, 6, 7 The METALAIRE single duct terminal units are at the core of

More information

Tamper Proof Downblast Centrifugal Exhaust Ventilators Page

Tamper Proof Downblast Centrifugal Exhaust Ventilators Page SRSH Tamper Proof Downblast Centrifugal Exhaust Ventilators Page Introduction....................................... 2 SRSH-D Specifications and Dimension Data............. 3 SRSH-B Specifications and

More information

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS

Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS Horizontal and Vertical BELT DRIVE AIR HANDLING UNITS TABLE OF CONTENTS H & V Features and Benefits...4 Coil and Filter Data, Static Pressure Data...7 Electric Resistance Heat Section...8 Coil Information

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Direct and Belt Driven Models VUDK and VUBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

PULSE JET CARTRIDGE DUST COLLECTOR FEATURES ADVANTAGE

PULSE JET CARTRIDGE DUST COLLECTOR FEATURES ADVANTAGE PULSE JET CARTRIDGE DUST COLLECTOR PAGE 07 APZEM Pulse jet bag filter is one type of baghouse dust collector using large array of filter bags for air filtering and high velocity pulsed air passed in reverse

More information

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL

NSGV PT-1000 PORTABLE WELDING STATION I, O & M MANUAL APPLICATION OF DUST CONTROL EQUIPMENT: CAUTION - Warning Improper operation of dust control system may contribute to conditions in the work area or facility that could result in severe personal injury

More information

Air Boss CA3000C & CA6000C. Installation Operation Maintenance Manual. Cartridge Air Cleaners

Air Boss CA3000C & CA6000C. Installation Operation Maintenance Manual. Cartridge Air Cleaners Installation Operation Maintenance Manual Due to the nature and wide variety of dusts, it is impossible to list all of the potential hazards associated with dust control equipment or systems. Therefore,

More information

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR

HBC SERIES-PSC MOTOR HBCX SERIES-ECM MOTOR PRODUCT SPECIFICATIONS *HBC(X) *PHBC(X) *RHBC(X) *CHBC(X) Chilled Water/Hot Water 2-pipe/4-Pipe HBC SERIES- HBCX SERIES-ECM MOTOR Ceiling Concealed Horizontal -1 CFM Ceiling Concealed Ceiling Recessed

More information

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA PH SERIES SINGLE DUCT ATU PERFORMAE DATA The Performance Aire PH Series is the simplest and most widely used VAV terminal unit. Its basic components are an insulated sheet metal box, round inlet damper,

More information

CEILING & INLINE/CABINET VENTILATORS

CEILING & INLINE/CABINET VENTILATORS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS CEILING & INLINE/CABINET VENTILATORS T-Series TL-Series CATALOG 4600 MARCH 2018 CEILING & INLINE VENTILATORS OVERVIEW T I TL T-Series

More information

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK CENTRIFUGAL WALL EXHAUSTERS Direct and Belt Driven Models VWDK and VWBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company centrifugal wall

More information

PROPOSAL. Fume-A-Vent 4 Drop Source Capture Diesel Fume Extraction System for Firehouse/EMS

PROPOSAL. Fume-A-Vent 4 Drop Source Capture Diesel Fume Extraction System for Firehouse/EMS PROPOSAL Page 1 of 2 826 HORAN DRIVE FENTON, MO 63026 Phone: (636) 349-4400 Fax: (636) 349-0556 http://www.aircleaningspecialists.com Order Number: Order Date: Salesperson: Customer Number: 0084040 9/20/2017

More information

SECTION MOTOR REQUIREMENTS for HVAC

SECTION MOTOR REQUIREMENTS for HVAC PART 1 GENERAL 1.1 SECTION INCLUDES A. Single-phase electric motors B. Three-phase electric motors 1.2 REFERENCES SECTION 23 05 13 MOTOR REQUIREMENTS for HVAC A. ABMA 9 - Load Ratings and Fatigue Life

More information

UPBLAST ROOF, WALL & KITCHEN EXHAUSTERS

UPBLAST ROOF, WALL & KITCHEN EXHAUSTERS Twin City Fan INDUSTRIAL PROCESS AND COMMERCIAL VENTILATION SYSTEMS UPBLAST ROOF, WALL & KITCHEN EXHAUSTERS DCRU DCRUR DCRW DCRWR BCRU BCRUR BCRW BCRWR BCRUSH CATALOG 405 APRIL 08 ROOF & WALL EXHAUSTERS

More information

The Anatomy of a Drum Filter

The Anatomy of a Drum Filter The Anatomy of a Drum Filter Theory of Operation Dirty air is introduced into the Drum Filter Enclosure The Main System Fan pulls the air across the filter media The dirty particles are vacuumed off the

More information

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators Version: Dec. 01, 2004 RERV & RERVX Rotary Energy Recovery Ventilators Indoor and Outdoor Installations 250 20,000 CFM Capacities RERVLP Low Profile Indoor Rotary Energy Recovery Ventilators Ideal for

More information

A Fläkt Woods Company. Model PFB Panel Exhaust Fans 24" 72" Diameter Bulletin PF-1410 July 2003

A Fläkt Woods Company. Model PFB Panel Exhaust Fans 24 72 Diameter Bulletin PF-1410 July 2003 A Fläkt Woods Company PFB Panel Exhaust Fans 24" 72" Diameter Bulletin PF-1410 July 2003 Fläkt Woods Group Creative Air Fläkt Woods was created by bringing together several of the worlds leading players

More information