Fan Powered Terminal Units FPV, FDV Series Variable Volume Parallel Flow

Size: px
Start display at page:

Download "Fan Powered Terminal Units FPV, FDV Series Variable Volume Parallel Flow"

Transcription

1 Recommended Air Volume Ranges CP 101 Unit Size L/s Min.* L/s Max. cfm Min.* cfm Max CP 100 and CP 200 Controller Unit Size L/s Min.* L/s Max. cfm Min.* cfm Max Electronic or Digital Controls Unit Size L/s Min.* L/s Max. cfm Min.* cfm Max Notes: Factory calibrated controls must be selected within the above flow range limits. A minimum value of zero is also available. The maximum flow setting of the controller must be equal to or less than the selected capacity of the recirculating fan. On controls mounted by Price but supplied by others, the air volume ranges are guidelines only. * Selection of air flow limits below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supplied. Minimum air fl ow limit is based on min.02 in. w.g. differential pressure signal from air flow sensor (.04 in. w.g. for CP100 and CP200). Selection of air fl ow limits below the listed values is not recommended. Stability and accuracy may not be acceptable at lower than recommended air flow limits. The actual performance will vary depending on the terminal unit controls supplied. Maximum air flow limit is based on max 1.0 in. w.g. differential pressure signal from air flow sensor. F-449

2 Typical Selection Guide Cooling Cycle 100% Primary Discharge NC Ps Across Unit Radiated NC Ps Across Unit Unit Air Flow Min. Ps Min. Pt. 0.5 in. w.g. 1.0 in. w.g. 1.5 in. w.g. 0.5 in. w.g. 1.0 in. w.g. 1.5 in. w.g. Size cfm L/s in.w.g Pa in.w.g Pa 125Pa 250Pa 375Pa 125Pa 250Pa 375Pa NCs are derived from sound power levels, which are obtained in accordance with AHRI Standard and ASHRAE Standard NCs are derived from sound power levels which include duct end corrections per AHRI Standard Please refer to page F25 for more details. 3. Blank spaces (--) indicate NCs less than Air flow is given in L/s and cfm. 5. ΔPs is the difference in static pressure from inlet to discharge of the unit. 6. ΔPt is the difference in total pressure from inlet to discharge of the unit. 7. Min. ΔPs is the minimum static pressure required to achieve rated air flow. 8. Pressure is given in Pa and in. w.g. 9. Fan external static pressure is 63 Pa (0.25 in.w.g) in all cases. 10. NC values are calculated based on typical attenuation values outlined in Appendix E, AHRI Standard , A Procedure for Estimating Occupied Space Sound Levels in the Application of Air Terminals and Air Outlets. Typical Attenuation Values: Radiated Sound Total Deduction Octave Band Mid Frequency, Hz All Sizes Discharge Sound Total Deduction Octave Band Mid Frequency, Hz < 300 cfm cfm > 700 cfm F-450 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.

3 Typical Selection Guide Heating Cycle Fan Only Unit Air Flow Discharge Radiated Size L/s cfm NC NC NCs are derived from sound power levels, which are obtained in accordance with AHRI Standard and ASHRAE Standard NCs are derived from sound power levels which include duct end corrections per AHRI Standard Please refer to page F25 for more details. 3. Blank spaces (--) indicate NCs less than Fan external static pressure is 63 Pa (0.25 in.w.g) in all cases. 5. NC values are calculated based on typical attenuation values outlined in Appendix E, AHRI Standard , A Procedure for Estimating Occupied Space Sound Levels in the Application of Air Terminals and Air Outlets. Typical Attenuation Values: Radiated Sound Total Deduction Octave Band Mid Frequency, Hz All Sizes Discharge Sound Total Deduction Octave Band Mid Frequency, Hz < 300 cfm cfm > 700 cfm NC vs Sound Power Levels Compare Them Carefully Price represents the sound performance data for the FPV/FDV series of fan powered terminals in two manners. The laboratory attained discharge and radiated sound power levels for each unit at various flows and inlet static pressures is presented in the Acoustical Data tables. This data is derived in accordance with AHRI Standard 880 and shows the 'raw' sound power levels of the terminal in the second through seventh octave bands with NO attenuation allowances. This data includes AHRI standard ratings which are on record with the Air-Conditioning Refrigeration Institute. Price also offers this Typical Application and Selection Guide to assist you in selecting the proper size and configuration of terminal for your needs. The attenuation allowances listed are based on values suggested in AHRI Standard , Appendix E. The suggested attenuation allowances are intended to be representative of typical jobsite constructions. If your conditions differ significantly from these it is recommended you utilize the sound power level data in the catalog and the procedures outlined in AHRI Standard If the NC levels listed in the Price catalog are being compared to other manufacturers catalogued NC information, a careful review of the other manufacturers attenuation allowances must be made. If allowances other than recommended AHRI Standard , Appendix E are used, a fair comparison of NC levels cannot be performed. F-451

4 Discharge Sound Data Cooling Cycle 100% Primary Sound Power Levels Lw db re Watts 0.5 in. w.g. [125 Pa] 1.0 in. w.g. [250 Pa] 1.5 in. w.g. [375 Pa] Unit Air Flow Octave Band Octave Band Octave Band Size L/s cfm Test data obtained in accordance with AHRI Standard and ASHRAE Standard Sound power levels include duct end corrections per AHRI Standard Please refer to page F25 for more details. 3. Air flow given in L/s and cfm. 4. Pressure is given in Pa and in.w.g. 5. Fan external static pressure is 63 Pa (0.25 in.w.g.) in all cases. 6. AHRI certified data is highlighted in blue. All other data are application ratings. 7. Application ratings are outside the scope of the AHRI 880 Certification Program. F-456 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.

5 Radiated Sound Data Cooling Cycle 100% Primary Sound Power Levels Lw db re Watts 0.5 in. w.g. [125 Pa] 1.0 in. w.g. [250 Pa] 1.5 in. w.g. [375 Pa] Unit Air Flow Octave Band Octave Band Octave Band Size L/s cfm Test data obtained in accordance with AHRI Standard and ASHRAE Standard Sound power levels include duct end corrections per AHRI Standard Please refer to page F25 for more details. 3. Air flow given in L/s and cfm. 4. Pressure is given in Pa and in.w.g. 5. Fan external static pressure is 63 Pa (0.25 in.w.g.) in all cases. 6. AHRI certified data is highlighted in blue. All other data are application ratings. 7. Application ratings are outside the scope of the AHRI 880 Certification Program. F-457

6 Discharge and Radiated Sound Power Levels Heating Cycle - Fan Only Sound Power Levels, LW, db, re Watts Discharge Sound Data Radiated Sound Data Unit Air Flow Octave Band Octave Band Size L/s cfm Test data obtained in accordance with AHRI Standard and ASHRAE Standard Sound power levels include duct end corrections per AHRI Standard Please refer to page F25 for more details. 3. Air flow given in L/s and cfm. 4. Fan external static pressure is 63 Pa (0.25 in.w.g) in all cases. 5. AHRI certified data is highlighted in blue. All other data are application ratings. 6. Application ratings are outside the scope of the AHRI 880 Certification Program. F-458 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.

7 AHRI Certification Rating Points Discharge Sound Power Level, db (1) (2) (3) (4) (5) (6) Unit Size Primary Air Flow Fan Air Flow Power Input Minimum Operating Pressure Fan only 100% Primary Air Valve Flow at 1.5 in. w.g. [375 Pa] Octave Band Octave Band L/s cfm L/s cfm Watts Pa in. Water Radiated Sound Power Level, db (1) (2) (3) (4) (5) (6) Unit Size Primary Air Flow Fan Air Flow Power Input Minimum Operating Pressure Fan only 100% Primary Air Valve Flow at 1.5 in. w.g. [375 Pa] Octave Band Octave Band L/s cfm L/s cfm Watts Pa in. Water Primary cfm is the standard rated air volume for the inlet size listed. 2. Fan cfm is maximum rated fan volume at 0.25 in. downstream static pressure. 3. Input watts is the maximum electrical power input at the maximum rated fan volume. 4. Min. operating pressure Inlet is the minimum operating pressure requirement of the primary air valve at the rated primary cfm. 5. Fan only sound power levels are at the maximum rated fan volume % primary sound power levels at rated primary cfm with fan off. 7. Sound power levels include duct end corrections per AHRI Standard Please refer to page F25 for more details. F-459

8 1 and 2 Row Hot Water Coil Data IP Units Size 20 Standard Size Rows gpm Loss Row Multi Circuit Row Multi Circuit Size 20 High Capacity Rows gpm Loss Row Single Circuit Row Multi Circuit Size 30 Standard Size Rows gpm Loss Row Multi Circuit Row Multi Circuit Size 30 High Capacity Rows gpm Loss Row Single Circuit Row Multi Circuit Size 40 Standard Coil Rows gpm Loss Row Multi Circuit Row Multi Circuit Size 40 High Capacity Rows gpm Loss Row Single Circuit Row Multi Circuit F-460 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.

9 1 and 2 Row Hot Water Coil Data IP Units Size 50 Standard Coil Rows gpm Loss Row Multi Circuit Row Multi Circuit Size 50 High Capacity Rows gpm Loss Row Multi Circuit Row Multi Circuit Size 60 Standard Coil Rows gpm Loss Row Multi Circuit Row Multi Circuit Size 60 High Capacity Rows gpm Loss Row Multi Circuit Row Multi Circuit Correction Factors 1 and 2 Row Hot Water Coils Entering Water Temp, F Ent. Air Temp, F Tabulated values are in MBH (thousands of Btu per hour). 2. Tables are based on a temperature difference of 105 F (180 F entering water temperature and 75 F entering air temperature). For other temperature differences, multiply MBH values by factors as listed above. 3. Minimum air and water flow values are based on ASHRAE recommendations for coil selections. For selections below these tabulated air or water values, please consult your local Price representative. 4. Do not select coils for a leaving air temperature above 120 F. 5. HD (Head) loss is in ft of water. 6. Through the Coil Ps, is the pressure drop in in. of water across the coil. 7. Air temperature rise = ATR, ATR ( F) = 927 x MBH/cfm 8. Water temperature drop = WTD, WTD ( F) = 2.04 x MBH/gpm 9. Values in tables are listed for 0 ft of altitude and no glycol in the system. 10. For information outside the ranges used in the table, consult the current Price software or your Price representative for accurate coil information. 11. Heating coils used in this unit have performance rated and certified in accordance with the current edition of AHRI Standard Connections: Single Circuit 1/2 in. OD male solder Multi Circuit 7/8 in. OD male solder F-461

10 1 and 2 Row Hot Water Coil Data SI Units Size 20 Standard Size Coil HD Air Flow Rate (L/s) Rows L/s Loss Row Multi Circuit Row Multi Circuit Size 20 High Capacity Rows Coil L/s HD Loss Air Flow Rate (L/s) Row Single Circuit Row Multi Circuit Size 30 Standard Size Rows Coil L/s HD Loss Air Flow Rate (L/s) Row Multi Circuit Row Multi Circuit Size 30 High Capacity Rows Coil L/s HD Loss Air Flow Rate (L/s) Row Single Circuit Row Multi Circuit Size 40 Standard Coil Rows Coil L/s HD Loss Air Flow Rate (L/s) Row Multi Circuit Row Multi Circuit Size 40 High Capacity Rows Coil L/s HD Loss Air Flow Rate (L/s) Row Single Circuit Row Multi Circuit F-462 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.

11 1 and 2 Row Hot Water Coil Data SI Units Size 50 Standard Coil Coil HD Air Flow Rate (L/s) Rows L/s Loss Row Multi Circuit Row Multi Circuit Size 50 High Capacity Coil HD Air Flow Rate (L/s) Rows L/s Loss Row Multi Circuit Row Multi Circuit Size 60 Standard Coil Coil HD Air Flow Rate (L/s) Rows L/s Loss Row Multi Circuit Row Multi Circuit Size 60 High Capacity Coil HD Air Flow Rate (L/s) Rows L/s Loss Row Multi Circuit Row Multi Circuit Correction Factors 1 and 2 Row Hot Water Coils Entering Water Temp, C Ent. Air Temp, C Tabulated values are in kw (thousands of watts). 2. Tables are based on a temperature difference of 58 C (82 C entering water temperature and 24 C entering air temperature). For other temperature differences, multiply MBH values by factors as listed above. 3. Minimum air and water flow values are based on ASHRAE recommendations for coil selections. For selections below these tabulated air or water values, please consult your local Price representative. 4. Do not select coils for a leaving air temperature above 49 C. 5. HD (Head) loss is in kilopascals (kpa) of water. 6. Through the Coil Ps, is the pressure drop in Pascals (Pa) of water across the coil. 7. Air temperature rise = ATR, ATR ( C) = 829 x kw/l/s (Air flow) 8. Water temperature drop = WTD, WTD ( C) = x kw/l/s (Water Flow) 9. Values in tables are listed for 0 metres of altitude and no glycol in the system. 10. For information outside the ranges used in the table, consult the current Price software or your Price representative for accurate coil information. 11. Heating coils used in this unit have performance rated and certified in accordance with the current edition of AHRI Standard Connections: Single Circuit 13 mm OD male solder Multi Circuit 22 mm OD male solder F-463

FDCLP2 Constant Volume Series Flow, Low Profile

FDCLP2 Constant Volume Series Flow, Low Profile The Price low profile series fan powered terminal unit is an ideal product for use in typical series fan powered applications with limited ceiling space. The is designed for constant air volume applications,

More information

fan powered terminals

fan powered terminals PTFS-F, ATFS-F, DTFS-F / AIRFLOW VS. DOWSTREAM STATIC PRESSURE TFS-F Size B 650 600 550 450 350 250 200 1 1200 1100 600 TFS-F Size C 150 TFS-F Size D 2 TFS-F Size E 1 2600 1 1 1600 1 1 1 1200 1100 2 2

More information

High Performance Fan Coils FCHG Genesis Series Horizontal

High Performance Fan Coils FCHG Genesis Series Horizontal Dimensional Data 5 7 /8 (150) D 14 (356) 2 (51) Diverter - Slides Into Discharge Ductwork Optional: Second Drain Pan Connection E Coil Section X Dimensional Data - IP (in.) / SI [mm] Unit Fan Outlet Duct

More information

Dual Duct Terminal Units DPS, DDS Series, DPQ, DDQ Series, DPV, DDV Series, DPM, DDM Series, DPUQ, DDUQ Series

Dual Duct Terminal Units DPS, DDS Series, DPQ, DDQ Series, DPV, DDV Series, DPM, DDM Series, DPUQ, DDUQ Series DPS, DDS Series, DPQ, DDQ Series, DPV, DDV Series, DPM, DDM Series, DPUQ, DDUQ Series Product Key UQ Ultra Quiet Product Selection Checklist 1] Select Unit Inlet Size based on control and acoustic parameters.

More information

SINGLE DUCT AIR TERMINAL UNITS

SINGLE DUCT AIR TERMINAL UNITS AIR terminal units AIR TERMINAL UNITS MODEL NUMBER LEGEND XXXXX XXX -XXXX Model TH TL THECO Inlet Size (04, 05, 06, etc.) Generation 5, 6, 7 The METALAIRE single duct terminal units are at the core of

More information

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI Air Terminal Units Models MQTH, MQFCI and MQFVI Catalog 903-1 Model MQTH Model MQFCI Model MQFVI Table of Contents Single Duct Air Terminal Units.... 3 Introduction....3 MQTH-500 Single Duct Air Terminal

More information

single / dual duct terminals

single / dual duct terminals PERFORANCE DATA RECOENDED PRIARY AIR CF RANGES / ALL TERINALS Control Types: PESV / Pneumatic AESV / Analog Electronic DESV / Digital Electronic QUICK SELECTION PROCEDURE 1. Select unit inlet size based

More information

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES FAN TERMINAL UNIT SPECIFIABLE FEATURES Galvanized steel casing, mechanically sealed for low leakage construction NEMA TYPE 1 rated hinged control enclosure with standoff to prevent penetration of casing

More information

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA PH SERIES SINGLE DUCT ATU PERFORMAE DATA The Performance Aire PH Series is the simplest and most widely used VAV terminal unit. Its basic components are an insulated sheet metal box, round inlet damper,

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101) 500-YH SINGLE DUCT AIR TERMINAL UNIT FORM 130.12-EG1 (1101) Table of Contents General Description.......................................................................3 500-YH Features........................................................................4-5

More information

SINGLE DUCT AIR TERMINAL UNITS

SINGLE DUCT AIR TERMINAL UNITS SINGLE DUCT AIR terminal units SINGLE DUCT AIR TERMINAL UNITS MODEL NUMBER LEGEND XXXXX XXX -XXXX Model TH TL THECO Inlet Size (04, 05, 06, etc.) Generation 5, 6, 7 The METALAIRE single duct terminal units

More information

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404) 500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT Table of Contents Introduction...3 500-YVI Features...4-5 Dimensional Data...6-7 ARI Rating Points...8 Statement of Standard Test Conformity...8 Motor Amperage

More information

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404)

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404) 500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT Table of Contents General Information...3 500-YCI Features...4-5 Dimensional Data...6-7 ARI Rating Points...8 Statement of Standard Test Conformity...8 Motor

More information

PERFORMANCE DATA Intermittent Volume (Parallel Flow), Standard Design

PERFORMANCE DATA Intermittent Volume (Parallel Flow), Standard Design FAN CURVES vs FAN SIZE A AS 05, 06, 07 1/6 H.P. Motor FAN SIZE B AS 06, 07, 08 1/6 H.P. Motor NOTES: 1. External Static Pressure (ESP) consists of down stream ductwork, coils, flex, duct, etc. 2. Pressure

More information

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc. ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT 15 Metal Industries, Inc. BENEFITS: Fan powered terminals are typically used for heating and cooling of perimeter zones.

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS Benefits: Fan powered terminals are typically used for heating and cooling of perimeter zones. Operating cost savings can be achieved through the use of waste heat recovery from the ceiling plenum and

More information

RETROFIT TERMINAL UNITS

RETROFIT TERMINAL UNITS GENERAL PROUCT OVERVIEW Retrofit Terminal s Convert Constant Air Volume Systems to Variable Air Volume. Convert Constant Volume ual uct Systems to Variable Air Volume. Convert Multizone Systems to Variable

More information

FPV, FDV Series Variable Volume Parallel Flow

FPV, FDV Series Variable Volume Parallel Flow Product Overview Variable Volume/Parallel Flow Fan Powered Terminal s With the variable volume model, the conditioned primary air does not pass through the fan. The primary air section and the recirculating

More information

HORIZONTAL HIGH CAPACITY FAN COIL UNITS DUCTED

HORIZONTAL HIGH CAPACITY FAN COIL UNITS DUCTED Direct Drive, Draw-through Design Model Series 3FH Filter 1" (2) throwaway (standard) 2" (1) MERV 8 or MERV 13 pleated (optional) Multiple coil options: 3, 4,, 6 row cooling or heating coils 1 or 2 row

More information

SPV / SDV Series SINGLE DUCT TERMINAL UNITS

SPV / SDV Series SINGLE DUCT TERMINAL UNITS SPV / SDV Series SINGLE DUCT Price single duct terminal units are designed to control the airflow rate of conditioned air into an occupied space with minimal pressure drop and low noise levels. An extensive

More information

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm Product Data 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems 40 to 3700 cfm The 35J retrofit terminal units offer: Unit casing of 22-gage galvanized steel construction (optional

More information

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA

More information

Variable Air Volume (VAV) Pressure Independent Control

Variable Air Volume (VAV) Pressure Independent Control VAV Terminal Units Asli Variable Air Volume (Vav) Terminal Units are volume flow rate controller for supply air on variable air volume system. These units are designed to control the airflow rate of conditioned

More information

I Fan Powered Terminal Unit

I Fan Powered Terminal Unit I Fan Powered Terminal Unit VARIABLE VOLUME PARALLEL FLOW Fan Powered Terminal Unit Variable volume parallel flow Product Overview Variable Volume/Parallel Flow Fan Powered Terminal Units Honeywell parallel

More information

Fan-Powered Parallel

Fan-Powered Parallel Table of Contents Model Number Description 76 Selection Procedure 77-79 General Data Setting Guidelines 80 Performance Data Pressure Requirements 81 Performance Data Fan Curves 82-85 Performance Data Hot

More information

SPVQ / SDVQ Series QUIET SINGLE DUCT TERMINAL UNIT

SPVQ / SDVQ Series QUIET SINGLE DUCT TERMINAL UNIT Patented SPVQ / SDVQ Series QUIET SINGLE DUCT TERMINAL UNIT In an era of increasing IAQ and noise concerns, this innovative product is specifically designed to meet the challenges headon. Certified assemblies

More information

FCVC Series VERTICAL FAN COILS

FCVC Series VERTICAL FAN COILS VERTICAL FAN COILS The FCVC is designed for concealed, wall mounted installations with flexible heating/ cooling loads and minimal duct requirements. With a variety of options, such as fiber free insulation,

More information

Laboratory Room Single Duct Supply Air Terminal

Laboratory Room Single Duct Supply Air Terminal Technical Specification Sheet Document No. 149-319A June 24th, 2010 Laboratory Room Single Duct Supply Air Terminal Features Figure 1. Laboratory Room Single Duct Supply Air Terminal. The APOGEE Automation

More information

catalog SDL Single-Duct, Low-Height, VAV Terminals

catalog SDL Single-Duct, Low-Height, VAV Terminals catalog SDL Single-Duct, Low-Height, VAV Terminals TABLE OF CONTENTS Features and Benefits.... 2 Controls.... 3 Construction Features... 4 Standard and Optional Features.... 5 Dimensional and Weight Data....

More information

Product Data. Features/Benefits. 35E Single Duct Terminal Units for Variable Air Volume Systems. Nominal 45 to 7100 cfm

Product Data. Features/Benefits. 35E Single Duct Terminal Units for Variable Air Volume Systems. Nominal 45 to 7100 cfm Product Data 35E Single Duct Terminal Units for Variable Air Volume Systems Nominal 45 to 7100 cfm Single duct variable air volume (VAV) terminal units provide: 22-gage galvanized steel, unit casing lined

More information

ANSI/AHRI Standard 881 (SI) with Addendum Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 881 (SI) with Addendum Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 881 (SI) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:

More information

Fan-Powered Series. Table of Contents. Model Number Description FPS 2 3. Service Model Number Description FPS 4. Selection Procedure FPS 5 7

Fan-Powered Series. Table of Contents. Model Number Description FPS 2 3. Service Model Number Description FPS 4. Selection Procedure FPS 5 7 Table of Contents Model Number Description FPS 2 3 Service Model Number Description FPS 4 Selection Procedure FPS 5 7 General Data Valve/Controller Airflow Guidelines FPS 8 Performance Data Pressure Requirements

More information

VAV RETROFIT/BYPASS TERMINAL UNITS TABLE OF CONTENTS RETROFIT/BYPASS TERMINAL UNITS. E-2 Excellence in Air Distribution MODEL RVE MODEL KLB MODEL SVE

VAV RETROFIT/BYPASS TERMINAL UNITS TABLE OF CONTENTS RETROFIT/BYPASS TERMINAL UNITS. E-2 Excellence in Air Distribution MODEL RVE MODEL KLB MODEL SVE TALE OF CONTENTS RETROFIT/YPASS TERMINAL UNITS RVE This retrofi t terminal unit is designed to convert high pressure mechanical constant volume systems to low pressure variable volume systems and also

More information

Laboratory Room Single Duct Supply Air Terminal

Laboratory Room Single Duct Supply Air Terminal Technical Specification Sheet Document No. 149-319P25 July 28, 2017 Laboratory Room Single Duct Supply Air Terminal Features Figure 1. Laboratory Room Single Duct Supply Air Terminal. The Laboratory Room

More information

D2-2. Table of Contents RETROFIT/BYPASS TERMINAL UNITS

D2-2. Table of Contents RETROFIT/BYPASS TERMINAL UNITS D2 RETROFIT/YPASS TERMINA UNITS Table of Contents RETROFIT/YPASS TERMINA UNITS RVE This retrofit terminal unit is designed to convert high pressure mechanical constant volume systems to low pressure variable

More information

STR Circular VAV Terminal Units

STR Circular VAV Terminal Units STR Circular VAV ASLI Circular Variable Air Volume (STR) Terminal s are volume flow rate controller for supply air on variable air volume system. These units are designed to control the airflow rate of

More information

Product Data. FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 SLIM LINE DUCTED FAN COIL WITH PLENUM ON/OFF DISPLAY TEMP

Product Data. FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 SLIM LINE DUCTED FAN COIL WITH PLENUM ON/OFF DISPLAY TEMP FS3QX Slim Line Ducted Fan Coil With Plenum Sizes 018 thru 060 Product Data A114 SLIM LINE DUCTED FAN COIL WITH PLENUM Installation Ease S Factory installed 24 volt transformer and relay S High and low

More information

ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on 27 October 2011 IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify

More information

Fan-Powered Parallel

Fan-Powered Parallel Table of Contents Service Model Number Description FPP 2 Selection Procedure FPP 3 5 General Data Valve/Controller Guidelines FPP 6 Performance Data ir Pressure Requirements FPP 7 8 Performance Data Fan

More information

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design FAN TERAL UNITS Constant Volume (Series Flow), Standard Design Models ACF w/o Coil ACW w/hot Water Coil ACE w/electric Coil The Carnes constant volume fan terminal unit provides constant air volume to

More information

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD R CONTENTS MODEL: KYODO / KYODO-R... 1 INTRODUCTION... 1 APPLICATION... 1 VARIABLE AIR VOLUME SYSTEM... 1 FEATURES... 2 MATERIALS... 3 AIR VOLUME CONTROL

More information

Unit Report For CH-1 30RB070 Project: UNF Soccer Stadium 04/21/2017

Unit Report For CH-1 30RB070 Project: UNF Soccer Stadium 04/21/2017 Unit Report For CH-1 30RB070 Unit Information Tag Name: CH-1 30RB070 Model Number: 30RB070 Condenser Type: Air Cooled Compressor Type: Scroll Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing

More information

catalog SDL Single-Duct, Low-Height, VAV Terminals

catalog SDL Single-Duct, Low-Height, VAV Terminals catalog SDL Single-Duct, Low-Height, VAV Terminals Catalog: ET130.13-EG2 (708) TABLE OF CONTENTS Single-Duct, Low-Height VAV Terminals Features and Benefits....................... 2 Controls..................................

More information

UNDERFLOOR FAN POWERED TERMINAL UNITS

UNDERFLOOR FAN POWERED TERMINAL UNITS UNERFLOOR FAN POWERE TERMINAL UNITS 1 UNERFLOOR FAN POWERE TERMINAL UNITS Contents UNERFLOOR FAN POWERE TERMINAL UNITS Underfloor Fan Powered Terminal Units Model 38S, 38SE, 38SW Features, Options, Accessories

More information

Single-Duct. Table of Contents. Model Number Description SD 2 3. Service Model Number Description SD 4. Selection Procedure SD 5 6

Single-Duct. Table of Contents. Model Number Description SD 2 3. Service Model Number Description SD 4. Selection Procedure SD 5 6 Table of Contents Model Number Description SD 2 3 Service Model Number Description SD 4 Selection Procedure SD 5 6 General Data Valve/Controller Airflow Guidelines SD 7 Performance Data Pressure Requirements

More information

Unit Report For CH-1 Replacement Project: Marlboro County High School Chiller Replacement 10/22/2018

Unit Report For CH-1 Replacement Project: Marlboro County High School Chiller Replacement 10/22/2018 Unit Report For CH-1 Replacement Unit Information Tag Name: CH-1 Replacement Model Number: 30RAP050 Condenser Type: Air Cooled Compressor Type: Scroll Nameplate Voltage: 460-3-60 V-Ph-Hz Quantity: 1 Manufacturing

More information

IAQ. ROUND DUCT RETROFIT Model ARR

IAQ. ROUND DUCT RETROFIT Model ARR Non Fan Powered Units ROUND DUCT RETROFIT Model ARR IAQ External Insulation Standard The Carnes Model ARR offers low pressure drop, low sound levels, and valve characteristics which create stable control

More information

IAQ. Model AVC. SINGLE DUCT VAV Model AVC

IAQ. Model AVC. SINGLE DUCT VAV Model AVC NON FAN POWERED UNITS SINGLE DUCT VAV Model AVC Model AVC The Carnes Model AVC is available as a basic control unit with open end discharge, with an optional multi-discharge adapter module, or sound attenuator

More information

Laboratory Exhaust Air Terminal

Laboratory Exhaust Air Terminal Laboratory Exhaust Air Terminal Page 1 of 11 Figure 1. Laboratory Exhaust Air Terminal. The APOGEE Automation Laboratory Room Exhaust Air Terminal is an industrial grade, easy-to-install, prepackaged airflow

More information

Performance Rating of Air Terminals

Performance Rating of Air Terminals AHRI Standard 881 (SI) 2017 Standard for Performance Rating of Air Terminals IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products,

More information

catalog SDR Single-Duct VAV Terminals

catalog SDR Single-Duct VAV Terminals catalog SDR Single-Duct VAV Terminals TABLE OF CONTENTS Features And Benefits...2 Standard Construction...6 Optional Construction...7 Standard And Optional Features...8 Application And Selection...9 Airflow

More information

PACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE.

PACKAGE UNIT PCA340U TECHNICAL SELECTION DATA. -10 o C UNIT FEATURES SPECIFICATION SUMMARY UNIT OPTIONS CONTROL OPTIONS UNIT COMPLIANCE. TECHNICAL SELECTION DATA PACKAGE UNIT + o C -10 o C 3 THREE PHASE SCROLL TWO STAGE CENTRIFUGAL LOUVRE LIANT SCROLL RESSOR AXIAL UNIT FEATURES SPECIFICATION SUMMARY Scroll Compressor Multiple Speed Outdoor

More information

Vertical Hi-Rise Fan Coil Unit (Model FS)

Vertical Hi-Rise Fan Coil Unit (Model FS) Technical Bulletin Issue Date March 1, 2005 Vertical Hi-Rise Fan Coil Unit (Model FS) Model FS Vertical Hi-Rise fan coil units are designed to maximize flexibility of selection and installation. The units

More information

SINGLE DUCT TERMINAL UNITS 30X/HQX SERIES

SINGLE DUCT TERMINAL UNITS 30X/HQX SERIES 30X/HQX SERIES 30X SERIES EXHUST 30HQX SERIES EXHUST HOSPITL GRDE QUIET TYPE WITH DISSIPTIVE SILENCER PRODUCT OVERVIEW Nailor Single Duct Exhaust Terminal Units are used to modulate exhaust flow from an

More information

series RVV Variable flow rate controllers

series RVV Variable flow rate controllers series RVV Variable flow rate controllers www.koolair.com Series RVV 1 CONTENTS Variable flow rate controllers, type RVV Description 2 Dimensions and product code 3 Selection tables 4 Variable flow rate

More information

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm

Product Data. Features/Benefits. 42BH System Fan Coil. 800 to 4000 Cfm Product Data 42BH System Fan Coil 800 to 4000 Cfm Satisfy All Your Design Requirements with Carrier s Versatile 42BH Fan Coil Unit A selection of 6 sizes covers capacities from 800 to 4000 cfm Choice of

More information

Fan - Powered Terminal Unit Series Flow

Fan - Powered Terminal Unit Series Flow 5/22/M/1 Fan - Powered Terminal Unit Series Flow Type TFP Trox (Malaysia) Sdn Bhd 20 Persiaran Bunga Tanjung 1 Senawang Land Industrial Park 70400 Seremban Negeri Sembilan Darul Khusus Malaysia Telephone

More information

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDA Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Slim, compact design for limited space requirements. Installs out of sight between the

More information

VMDB Concealed Medium Static Ducted Indoor Models - 60HZ

VMDB Concealed Medium Static Ducted Indoor Models - 60HZ VARIABLE REFRIGERANT FLOW SYSTEMS VRF VMDB Concealed Medium Static Ducted Indoor Models - 60HZ PRODUCT ECIFICATIONS Bulletin No. 210711 March 2018 Slim, compact design for limited space requirements. Installs

More information

CFM (L/s) Dimensions. Filter Size in. Ship Wt. H x W x D in. (mm) 1800A 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

CFM (L/s) Dimensions. Filter Size in. Ship Wt. H x W x D in. (mm) 1800A 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15 ENVIRONMENTALLY SOUND REFRIGERANT FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits available

More information

IAQ. Model AVW. SINGLE DUCT w/hot WATER HEAT Model AVW

IAQ. Model AVW. SINGLE DUCT w/hot WATER HEAT Model AVW SINGLE DUCT w/hot WATER HEAT Model AVW Model AVW The Carnes Model AVW is available as a basic control unit with hot water reheat and open end discharge, with an optional sound attenuator module, and optional

More information

Residential Packaged Geothermal Heat Pump

Residential Packaged Geothermal Heat Pump ENGIneering Design Guide Residential Packaged Geothermal Heat Pump HP Series 1 1 /2 to 5 Tons Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com Engineering

More information

Product Data. AXIS 45X, 45U, 42K, 35BF Access Floor Terminal Units for Variable Air Volume Systems

Product Data. AXIS 45X, 45U, 42K, 35BF Access Floor Terminal Units for Variable Air Volume Systems Product Data AXIS 45X, 45U, 42K, 35BF Access Floor Terminal Units for Variable Air Volume Systems 45UC 35BF-R 42KC 45XC 35BF-D Features/Benefits Access Floor Systems can provide flexibility and economic

More information

CFM (L/s) Min Max 450 (212) 600 (283) 750 (354) Dimensions H x W x D in. (mm) 675 (319) 36 1/2 x 20 1/2 x (425)

CFM (L/s) Min Max 450 (212) 600 (283) 750 (354) Dimensions H x W x D in. (mm) 675 (319) 36 1/2 x 20 1/2 x (425) ENVIRONMENTALLY SOUND REFRIGERANT FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2.5, and 3 Tons Upflow application only For use with R 410A refrigerant or R 22 with accessory TXV

More information

Product Data. Features/Benefits. 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

Product Data. Features/Benefits. 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm Product Data 36CBAC,AE,AF,AN, PB,PD,PS Series Active and Passive Chilled Beams 11 to 190 cfm 36CBAC Chilled beam units offer: An increase in total airflow Sensible cooling and heating options Induction

More information

Product Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

Product Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15 Product Data FMA4X, FMA4P APARTMENT FAN COIL UNIT 1 1/2 TONS THROUGH 3 TONS APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits

More information

FMU4X, FMC4X FMU4Z, FMC4Z

FMU4X, FMC4X FMU4Z, FMC4Z HORIZONTAL FAN COILS FMU4Z and FMC4Z 1 1/2, 2, 2 1/2, and 3 Tons FMU4X and FMC4X 1 1/2, 2, 2 1/2, and 3 Tons Horizontal application only Accessory field installed electric heat kits available in 3, 5,

More information

Large Belt Drive (HBH/V) Series HBH HBV

Large Belt Drive (HBH/V) Series HBH HBV Design Guide Large Belt Drive (HBH/V) Series HBH 072-120 HBV 072-300 60Hz - HFC-410A 517.787.2100 www.marsdelivers.com www.heatcontroller.com Table of Contents *Page Number Unit Features.... 2 Selection

More information

PIM Pressure Independent Module

PIM Pressure Independent Module PIM Pressure Independent Module PIM : Product Overview BENEFITS AT A GLANCE QUIET VAV DIFFUSER OPERATION The PIM Pressure Independent Module is a modulating static pressure controller/actuator that allows

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

Kirby WRC Remote Condenser. With HyBlade EC Fans and AxiTop Diffuser

Kirby WRC Remote Condenser. With HyBlade EC Fans and AxiTop Diffuser Kirby WRC Remote Condenser With HyBlade EC Fans and AxiTop Diffuser 114kW 651kW Product Overview The Kirby WRC Remote Condenser is a market leading and energy efficient remote condenser specifically designed

More information

VHIA High-Static Ducted Indoor Units - 60HZ

VHIA High-Static Ducted Indoor Units - 60HZ PRODUCT SPECIFICATIONS Compact design for limited space requirements. Installs out of sight between the drop ceiling and ceiling slab with ducted distribution to the indoor space. All models have three-stage

More information

Product Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil

Product Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil A13303 Fig. 1 - FPM(A,B)NU Uncased Horizontal Fan Coil (FPMANU model shown) Fig. 2 - FPM(A,B)NC Cased Horizontal Fan Coil

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS GENERAL PRODUT OVERVIE Leading The Industry Providing products that incorporate the desires and requirements of the industry we serve has traditionally been a primary focus at Nailor. e listened in-depth

More information

R410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2

R410A TECHNICAL MANUAL. Inverter Single Split Series Air Conditioner. FTK-J, FTXN-J Series. Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2 R410A TECHNICAL MANUAL Inverter Single Split Series Air Conditioner FTK-J, FTXN-J Series Cooling only & Heatpump [50Hz] TM-5WMY-J-ST-A2 Table of Contents Table of Contents Nomenclature...1 Indoor...1 Outdoor...1

More information

VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ

VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ PRODUCT SPECIFICATIONS VARIABLE REFRIGERANT FLOW SYSTEMS VRF VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ Bulletin No. 210712 March 2018 Low-sound, three-speed Wall Mount with LED display offers three

More information

BAC / BHC Product Specifications

BAC / BHC Product Specifications COMMERCIAL AIR HANDLERS (3 PHASE) 6 to 20 TON / Product Specifications REFRIGERATION CIRCUIT Standard factory-installed thermostatic expansion valves (TXVs) on units; units include TXVs and check valves

More information

D1-2. Table of Contents MODULAR CORE DIFFUSERS. 1240, Introduction & Product Description... D1-3. Dimensional Information...

D1-2. Table of Contents MODULAR CORE DIFFUSERS. 1240, Introduction & Product Description... D1-3. Dimensional Information... D Table of Contents, These supply, ceiling diffusers feature four handremovable modular cores. Available in steel or aluminum construction. P, P These supply, ceiling diffusers feature four handremovable

More information

catalog VFR Parallel Flow, Fan-Powered, 50/60 Hz VAV Terminals

catalog VFR Parallel Flow, Fan-Powered, 50/60 Hz VAV Terminals catalog VFR Parallel Flow, FanPowered, 50/60 Hz VAV Terminals TABLE OF CONTENTS Features and Benefits...2 Controls...4 Construction Features...5 Standard and Optional Features...7 Application and Selection....8

More information

LOW STATIC FAN COIL UNITS District Cooling Chilled Water Application

LOW STATIC FAN COIL UNITS District Cooling Chilled Water Application STATIC FAN COIL UNITS District Cooling Chilled Water Application CLASSIFIED INSULATION & FILTER MEDIA GFC LD Series Cooling Capacity Range 9,690 yo 46,064 BTU/HR (4 ROWS ) GFC-LD-TC-10-13 3 General Specifications

More information

Submittal. Holder Construction Company. Reviewed. Reviewed as Noted. Rejected. 1. Updates per Bulletin #4

Submittal. Holder Construction Company. Reviewed. Reviewed as Noted. Rejected. 1. Updates per Bulletin #4 Holder Construction Company 230 Peachtree Street NW, Suite 1250 Atlanta, GA 30303 Submittal Project Telephone #404.688.6233 Project Name: Submittal Number: Submittal Description: Submittal Review Date:

More information

Vertical Floor Fan Coil Unit (Model FW)

Vertical Floor Fan Coil Unit (Model FW) Technical Bulletin Issue Date March 24, 2005 Vertical Floor Fan Coil Unit (Model FW) Figure 1: Model FWX Vertical Exposed Model FW Vertical Floor fan coil units are designed to maximize flexibility of

More information

Resolair 64 and 68. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 3,900 23,100 m³/h

Resolair 64 and 68. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 3,900 23,100 m³/h Comfort air conditioning unit with highly efficient regenerative heat storage packages 68 10 01 - simplified illustration Automatically selects the most economical operating mode! 64 and 68 AIR OLUME FLOW:

More information

catalog CFRQ, Extra Quiet Series Flow, Constant Volume Fan Powered VAV Terminals

catalog CFRQ, Extra Quiet Series Flow, Constant Volume Fan Powered VAV Terminals catalog CFRQ, Extra Quiet Series Flow, Constant Volume Fan Powered VAV Terminals TABLE OF CONTENTS Features And Benefits... 2 Construction Features... 4 Standard & Optional Features... 6 Application And

More information

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS

DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS SUPPLY AIR PLENUMS DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS KBBU060, KDBC090, KCBC120 & KCBC180 5 THRU 15 NOMINAL TONS These completely assembled units include a well-insulated cabinet, a DX cooling coil

More information

FAN POWERED TERMINAL UNITS

FAN POWERED TERMINAL UNITS GENERAL PRODUT OVERVIEW Leading The Industry Providing products that incorporate the desires and requirements of the industry we serve has traditionally been a primary focus at Nailor. We listened in-depth

More information

CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15 ENVIRONMENTALLY SOUND REFRIGERANT FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1 1/2, 2, 2 1/2, and 3 Tons Upflow application only Accessory field installed electric heat kits available

More information

catalog VFR Parallel Flow, Fan-Powered, VAV Terminals

catalog VFR Parallel Flow, Fan-Powered, VAV Terminals catalog VFR Parallel Flow, FanPowered, VAV Terminals TABLE OF CONTENTS Features and Benefits... 2 Controls... 4 Construction Features... 5 Standard and Optional Features... 7 Application and Selection....

More information

Specification Manual Ground Source Heat Pumps Northern Geo LLC 75 West Veum Appleton, MN

Specification Manual Ground Source Heat Pumps Northern Geo LLC 75 West Veum Appleton, MN Specification Manual Ground Source Heat s www.northernheatpump.com Northern Geo LLC 75 West Veum Appleton, MN 56208 320-297-9100 info@northerngeo.com 07/30/2015 NL003 NorthStar Series Features & Benefits

More information

HCH6. Product Specifications

HCH6. Product Specifications HCH6 Product Specifications HIGH EFFICIENCY 16 SEER TWO- STAGE HEAT PUMP WITH OBSERVERt COMMUNICATING CONTROL SYSTEM 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Copeland

More information

SUBMITTAL. Palm Beach Gardens Fire Station. Fausto Frias

SUBMITTAL. Palm Beach Gardens Fire Station. Fausto Frias SUBMITTAL Project Palm Beach Gardens Fire Station Date February 5, 2018 Fausto Frias Prepared For TLC Attention- Steve Job Name Palm Beach Gardens Fire Station Mark for AHU-1 Date February 5, 2018 Unit

More information

catalog VFL Parallel Fan-Powered, Low-Height, VAV Terminals

catalog VFL Parallel Fan-Powered, Low-Height, VAV Terminals catalog VFL Parallel FanPowered, LowHeight, VAV Terminals TABLE OF CONTENTS Features And Benefits...2 Construction Features...4 Standard And Optional Features...6 Application And Selection...7 Application

More information

YEAR-ROUND AIR CONDITIONING Our Deluxe-Aire units are ideally suited to provide heating, cooling and air filtration for areas where it is not

YEAR-ROUND AIR CONDITIONING Our Deluxe-Aire units are ideally suited to provide heating, cooling and air filtration for areas where it is not YEAR-ROUND AIR CONDITIONING Our Deluxe-Aire units are ideally suited to provide heating, cooling and air filtration for areas where it is not feasible to provide a large central system and run duct work

More information

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES FFMA Base Series Fan Coil Sizes 018 thru 037 Product Data A13417 FEATURES The FFMA Series Fan Coil unit is primarily designed for apartment applications as an upflow only indoor fan coil for split -system

More information

CFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381)

CFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381) FMA4X, FMA4P Product Specifications APARTMENT FAN COILS ALL MODELS 1-1/2, 2, 2-1/2, and 3 Tons Upflow application only Accessory field- installed electric heat kits available in, 7., or 10 kw 208/230-1-

More information

Modular Air Handling. Up to 3,500 Litres / sec. Low profile & Plant room application. Draft. Version. Second Edition A-. AirDesign 2015 AirDesign 2016

Modular Air Handling. Up to 3,500 Litres / sec. Low profile & Plant room application. Draft. Version. Second Edition A-. AirDesign 2015 AirDesign 2016 Modular Air Handling U n i t R a n g e Up to 3,500 Litres / sec Low profile & Plant room application AirDesign 2015 AirDesign 2016 Second Edition Draft Version A-. Air Design is a proud Australian based

More information

Submittal PESVD

Submittal PESVD PESV Single Duct erminal Unit Pneumatic Control, Pressure Dependent Submittal PESVD-1.0 5-1-01 W Pneumatic Actuator L H D D 4 1/2" Slip & Drive Cleat Connection Right hand unit shown. All dimensions are

More information

catalog VFR Parallel Flow, Fan-Powered, 50/60 Hz VAV Terminals

catalog VFR Parallel Flow, Fan-Powered, 50/60 Hz VAV Terminals catalog VFR Parallel Flow, Fan-Powered, 50/60 Hz VAV Terminals TABLE OF CONTENTS Features and Benefits.... 2 Controls.... 4 Construction Features... 5 Standard and Optional Features.... 7 Application and

More information