Laboratory Methods for Testing Actuators

Size: px
Start display at page:

Download "Laboratory Methods for Testing Actuators"

Transcription

1 Laboratory Methods for Testing Actuators AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL INC. The International Authority on Air System Components

2 AMCA Publications Authority AMCA International Standard 520 was approved by the membership of the Air Movement and Control Association International Inc. on July 26, It was approved as an American National Standard by the American National Standards Institute (ANSI) and became effective on December 2, As of 2014, this document no longer undergoes routine maintenance and has been withdrawn due to the removal of actuators from AMCA's scope. Since the document is no longer regularly reviewed by engineers as part of AMCA's document review cycle, it is to be used as a historic reference. It is not a current American National Standard. Copyright 2004 by Air Movement and Control Association International Inc. All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and 108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for permission or further information should be addressed to the executive director, Air Movement and Control Association International Inc. at 30 West University Drive, Arlington Heights, IL U.S.A. Objections Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding its standards, certification programs, or interpretations thereof. For information on procedures for submitting and handling complaints, write to: Air Movement and Control Association International 30 West University Drive Arlington Heights, IL U.S.A. AMCA International, Incorporated c/o Federation of Environmental Trade Associations 2 Waltham Court, Milley Lane, Hare Hatch Reading, Berkshire, United Kingdom RG10 9TH Disclaimer AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of available information and accepted industry practices. However, AMCA does not guarantee, certify or assure the safety or performance of any products, components or systems tested, designed, installed or operated in accordance with AMCA standards or that any tests conducted under its standards will be nonhazardous or free from risk.

3 Related AMCA Documents Related Publications ANSI/AMCA Standard 500-D ANSI/AMCA Standard 500-L Laboratory Methods for Testing Dampers for Rating Laboratory Methods for Testing Louvers for Rating

4 Contents 1. Purpose Scope Definitions / Units of Measure / Symbols Definitions Units of measure Symbols and subscripts Instruments and Methods of Measurement Instrumentation Accuracy Torque Meters Chronometers Temperature Air pressure Force Linear measurement Angular measurement Equipment and Setups Objective, Observations and Conduct of Test Long term holding tests Operational life tests Ambient and elevated temperature performance testing Periodic maintenance testing Production tests Sound level testing Annex A References Annex B Rated Load Annex C Rated Stall Load

5 ANSI/AMCA Laboratory Methods of Testing Actuators 1. Purpose To establish an industry standard for minimum rating and testing of actuators used on fire/smoke dampers. 2. Scope The testing requirements will cover torque or force rating, long term holding, operational life, elevated temperature performance, periodic maintenance, production, and sound testing for both pneumatic and electric operators. 3. Definitions / Units of Measure / Symbols 3.1 Definitions Load The external force or torque that an actuator must oppose. This can be specified while either moving or stationary (stalled), and in either drive or return directions. The damper is the source of the load and is due to bearing/seal friction and any unbalanced air loading Rated load [4] The actuator manufacturers stated load for a given amount of time for full stroke at nominal electrical or rated pneumatic power and elevated exposure temperature per UL555S Rated stall load [4] The actuator manufacturer s stated (minimum) torque or force output (in both drive and return directions) at nominal electrical or rated pneumatic power and the rated elevated exposure temperature per UL555S when the actuator output shaft is prevented from rotating at a given position. See Annex C Full stroke The movement of a device from the resting position (end stop, zero position) to its nominal position in its intended application. Example: For a linear actuator with a nominal 55 mm ± 5 mm (2.2 in. ± 0.2 in.) travel, a full stroke would be 0 55mm (2.2 in.). Example: For a rotary actuator with a nominal 105 ± 5 rotation, a full stroke would be Example: For a 360 rotary actuator, a full stroke shall be no less than 90 and not exceed 180 of rotation. These actuators should have an external lever, stops and return spring so as to duplicate an actual application or installation on a damper Full stroke cycle The movement of a device from its resting position (end stop, zero position) to its nominal position in its intended application, and then back to the resting position. Example: For a linear actuator with a nominal 55 mm ± 5 mm (2.2 in. ±.2 in.) travel, a full stroke cycle would be 0 55 (2.2 in.) 0mm. Example: For a rotary actuator with a nominal 105 ± 5 rotation, a full stroke cycle would be Stall torque/force The amount of torque/force that stops the actuator from moving Dynamic stall torque/force The peak torque/force that an actuator, running under nominal conditions (nominal voltage/pressure and rated load), develops when subjected to a hard stop Spring return torque/force The unpowered output at the actuator/damper shaft due to the return spring (or other stored energy source) that returns the actuator to the normal unpowered position Reposition A modulating actuator reposition or repositioning cycle is a minimum rotation of the damper actuator 5 (± 2 ) or 10% in one direction and in the reversed direction Nominal voltage Sometimes referred to as nameplate voltage. A standard value assigned to a circuit for the purpose of conveniently designating a voltage class (i.e. 120 VAC) Sound power level [3] The acoustic power radiating from a sound source Noise criteria A standard for comparison or judgment of sound levels. 3.2 Units of Measure SI units (The International System of Units) are the primary units employed in this standard, with I-P units (Inch-Pound) given as the secondary reference. SI units are based on the fundamental values of the International Bureau of Weights and Measures [1], and I-P values are based on the values of the National Institute of Standards and Technology that are, in turn, based on the values of the International Bureau System of units The unit of length is the meter (m), or millimeter (mm); I-P ANSI/AMCA

6 Table 1 - Symbols and Subscripts Symbol Description SI I-P F Force N lb F s Stall force N lb L Crank arm length mm in L p Sound pressure level db db L w Sound power level db db NC Sound noise criteria dimensionless P Pneumatic pressure kpa PSI T Torque N-m lb-in. t a Ambient temperature C F T s Stall Torque N-m lb-in. 2 ANSI/AMCA

7 units are the foot (ft) or the inch (in.). The unit of mass is the kilogram (kg); the I-P unit is the pound mass (lbm). The unit of time is either the minute (min), or the second (s). The unit of temperature is either the degree Celsius ( C), or the degree Kelvin (K), I-P units are either the degree Fahrenheit ( F), or the degree Rankine ( R). The unit of force is the Newton (N); the I-P unit is the pound (lb) Torque The unit of torque is the Newton-meter (N-m); the I-P unit is the pound-inch (lb-in.). 3.3 Symbols and subscripts See Table Instruments and Methods Of Measurement 4.1 Instrumentation The test instruments used for the rating and testing of actuators for fire/smoke dampers shall be calibrated as required by the manufacturer with the period between calibrations not exceeding one year with calibration standards traceable to the National Institute of Standards and Technology. 4.2 Accuracy [2] The specifications for instruments and methods of measurement that follow include both accuracy requirements and specific examples of equipment that is capable of meeting those requirements. Equipment other than the examples cited may be used provided the accuracy requirements are met or exceeded Instrument accuracy The specifications regarding accuracy correspond to the criteria in Section 6. Instruments shall be set up, calibrated, and read by qualified personnel trained to minimize errors. 4.3 Torque [2] A torque device shall have a static calibration and may have a running calibration through its range of usage. The static calibration shall be made by suspending weights from a torque arm. The weights shall have certified accuracies of ± 2%. The length of the torque arm shall be determined to an accuracy of ± 2%. Applied torque shall be measured with a weight and pulley system, a torque transducer and digital readout with an accuracy of ±1%, or with a torque wrench with an accuracy of ± 4%. 4.4 Meters [2] Electrical meters shall have certified accuracies of ± 1% of the observed reading. 4.5 Chronometers [2] A quality watch, with a sweep second hand or a digital display of seconds that keeps time within two minutes per day is considered a primary instrument. 4.6 Temperature [2] Temperatures shall be measured with thermometers or other instruments with demonstrated accuracies of ± 1 C (± 2 F) and readabilities of 0.5 C (1 F) or finer. 4.7 Air pressure Air pressure shall be measured with a pressure transducer and digital readout or a pressure gauge. These instruments shall have a demonstrated accuracy of ± 1% and a resolution of kpa (0.5 PSI). The air pressure shall be measured in the feed line when the unit under test is stabilized in the full stroke (pressurized) position. 4.8 Force Applied force shall be measured either with a load cell and digital readout, a force gauge, or with a scale. These instruments shall have a demonstrated accuracy of ± 2% of reading and a resolution of 2.28 N (0.5 lb.) 4.9 Linear measurement Linear measurement shall be measured with an instrument with a minimum resolution of 1mm (.04 in.) (this need not be NIST traceable) Angular measurement Angular measurement shall be measured with an instrument having a resolution of 1 (this need not be NIST traceable). 5. Equipment and Setups See Figures 7.1A and 7.1B. ANSI/AMCA

8 Figure 7.1A Rotary Actuator Load Capability Test Setup (Conceptual) Figure 7.1B Linear Actuator Load Capability Test Set-Up (Conceptual) 4 ANSI/AMCA

9 6. Objective, Observations, and Conduct of Test 6.1 Long term holding tests Purpose The purpose of this test is to verify both electrical and pneumatic actuators in two position applications, during periods in extended holding in its nominal position and its intended application Test criteria A sample of thirty-two actuators will be tested for six months to determine their ability to return to the non-powered position. Representative samples of each design or design variation shall be individually tested. An "Un-Interruptible Power Supply" (UPS) should be utilized and monitored to verify the devices were not cycled during the duration of this test. The actuator must return to the normal (fail safe) position each time electrical power is removed. For pneumatic actuators, the actuator must return to the normal (fail safe) position after supply air is removed. All actuators must return to the normal (fail safe) position within their rated time. Normal (fail safe) position must be repeatable within 3 mm for linear actuators or 3 for rotary actuators Method The voltage or pressure to the actuator must be maintained for the duration of this test. Place the actuator in an orientation to simulate mounting on a horizontal damper shaft, undisturbed as much as possible for the duration of the test. Actuators shall have no external load except actuators with external springs, which must be tested at the minimum spring force recommended by the actuator manufacturer. Apply the test voltage specified in Table 2 for an electrically operated actuator, or apply ten percent (10%) above the rated pressure of pneumatically operated actuator, for a period of six months. Following the six month holding test, remove the electrical/pneumatic power and record observations of actuator timing. This test is to be performed at ambient 10 C to 55 C (50 F to 130 F) conditions. Note: Actuators must be pre-tested prior to this procedure in order to demonstrate proper operation. See production test. 6.2 Operational life tests Purpose To verify the actuator produced will perform 20,000 full stroke cycles for two position actuators (100,000 for modulating actuators) under specified load, nominal voltage or PSI range Test criteria (pass/fail criteria) Cycle the actuator continuously through electrical or pneumatic power, and fail-safe return, for the required number of cycles and test parameters, and still be able to perform at rated load and rated stall load. For modulating actuators, 32 samples shall be cycled 20,000 times and repositioned 100,000 times, with a maximum of one failure in 32 samples Method Actuators, of the same design family (example:same drive components, operating time and torque/force output with differing power source requirements), may be mixed for this test. This test is to be performed at ambient 10 C to 55 C (50 F to 130 F) conditions. The electrical or pneumatic power supplied to the actuator shall be at the nominal voltage or specified pressure. The actuator shall have no external load, except for a return spring if external to actuator, and operated in both directions thereby simulating an abrupt stop, with a minimum two second hold period at each end of the stroke. If actuator has an external return spring, the spring shall have the maximum spring load as allowed by the actuator manufacturer. Following the cycling described above, the minimum rated load and rated stall load must be verified in both directions for each actuator. 6.3 Ambient and elevated temperature performance testing Purpose [4] Determine that the rated load and rated stall load can be achieved before (at room ambient) and after being temperature soaked for thirty minutes at the rated elevated exposure temperature per UL555S as specified by the actuator Table 2 Voltage Rating of Product Test Voltage If the device voltage rating does not fall within any of the indicated ranges, it is to be tested at its rated voltage. ANSI/AMCA

10 manufacturer in their product data sheets. Actuators with different input electrical or pneumatic power must be tested separately Test criteria The actuator must be capable of completing three full stroke cycles at the manufacturer's rated load and temperature at nominal nameplate voltage or specified pressure. The time required to complete each stroke shall not exceed the manufacturers rated stroke time or at a maximum of seventy-five seconds. Three actuator samples must be tested and all must deliver the rated load Method Mount the device in the chamber. While still at room ambient temperature apply rated electrical or pneumatic power to the actuator. Apply opposing rated load to the actuator for three complete stroke cycles. The operating time shall not exceed seventy-five seconds for each stroke and shall be recorded. With the device still mounted in the chamber, apply rated electrical or pneumatic power to the actuator, and heat to the rated temperature not to exceed 27.8 C (50 F) per minute. Maintain temperature C / -0 C (50 F / -0 F) for thirty minutes after reaching test temperature. While at elevated temperature, apply the opposing rated load to the actuator for three complete stroke cycles. The operating time shall not exceed seventy-five seconds for each stroke and shall be recorded. After completing the three cycles, the stall torque of the operator shall be determined at 15, 30 and 80 of operation. Note: It is not the intent of this test to verify transformer operation at elevated temperatures when the transformer is not factory mounted internal to the actuator. If the method of driving the actuator when power is removed is external to the device, the actuator manufacturer is required to specify the return spring characteristics for the rated load. 6.4 Periodic maintenance testing Periodic elevated temperature testing Purpose This test is intended to give an indication of performance changes in the product production processes. Three devices shall be submitted for testing every six months. They will be randomly selected from the production line with a minimum of fifty production parts between samples. All models need not be tested (models with the same motor, gear train and bearing design can be grouped together to represent one like sample). A random system of selecting product from each manufacturer is to be established. Actuators shall be obtained from each producing factory Test criteria The actuator must be capable of completing three full stroke cycles at the manufacturer's rated load and temperature at rated electrical or pneumatic power input. The time required to complete each stroke shall not exceed the manufacturers rated stroke time or at a maximum of seventy-five seconds. Three actuator samples must be tested and all must deliver the rated load Method Mount the device in the chamber. While still at room ambient temperature apply rated electrical or pneumatic power to the actuator. Apply opposing rated load to the actuator for three complete stroke cycles. The operating time shall be recorded. After completing the three cycles, the stall torque of the operator shall be determined at 15, 30 and 80 of operation. With the device still mounted in the chamber, apply nominal nameplate voltage or specified pressure to the actuator, and heat the chamber to the elevated exposure temperature at a rate not to exceed 27.8 C (50 F) per minute. Maintain temperature C / -0 C (50 F / -0 F) for thirty minutes after reaching test temperature. While at elevated temperature, apply the opposing rated load to the actuator for three complete stroke cycles. The operating time shall be recorded. After completing the three cycles, the stall torque of the operator shall be determined at 15, 30 and 80 of operation. Note: It is not the intent of this test to verify transformer operation at elevated temperatures when the transformer is not factory mounted internal to the actuator. If the method of driving the actuator when electrical or pneumatic power is removed is external to the device, the actuator manufacturer is required to specify the return spring characteristics for the rated load. 6.5 Production tests Purpose The production test is intended to verify that the actuator being produced meets the product design criteria, as specified by the manufacturer. Each unit must pass the test requirements prior to being released from production Test criteria The final production test must include at least one full stroke cycle of the actuator and test all relevant functions. This test 6 ANSI/AMCA

11 is to be performed at ambient 10 C to 55 C (50 F to 130 F) conditions Method The actuator test apparatus must provide a torque or force load equal to the manufacturers rating. The nominal nameplate voltage or specified pressure supplied to the actuator should be the nominal nameplate voltage (± 5%) or specified PSI range. The actuator operating time, both under electrical or pneumatic power and under fail-safe mode, must meet the standards set by the manufacturer. the motor thirty minutes and after closing and reopening the damper. The damper shall be tested per ANSI/AMCA Standard 300 as a freestanding unit that would be placed entirely in the test room (See ANSI/AMCA Standard 300, Figure 1). After determining the maximum sound power level from the two tests, a NC (noise criteria) number shall be determined by subtracting ten db from each sound power level band test reading, and plotting the results on an NC curve to determine the NC level. If the actuator is electrically powered, the current draw must be measured during the power cycle of the test. The measured current must meet the standards set by the manufacturer. Should the actuator be built with internal auxiliary switches, the operation of the switch(s) must be tested at their designed activation point. The point of activation must be within the range specified by the manufacturer. If the actuator is designed for proportional position control, the test apparatus must be able to measure the modulated position of the actuator. The actual position must be able to be compared to the input signal and be within the design parameters of the actuator. If the actuator provides a proportional feedback signal, the feedback signal must be within the specifications of the manufacturer to actual position. All actuators that meet the above test criteria are identified and contain a date code for trace ability. The electrical or pneumatic power supplied to the actuator shall be recorded at the time of the test. 6.6 Sound level testing [3] Purpose To determine the noise criteria level produced by the actuator in the full stroke position Test criteria The sound power level (L w ) of electrically operated actuators shall be determined by testing the actuator on a 610 mm 610 mm (24 in. 24 in.) triple V groove fire/smoke damper installed in a 432 mm (17 in.) long 0.81 mm (0.032 in.) gauge sleeve in the energized position Method The sound power level (L w ) shall be taken after energizing ANSI/AMCA

12 Annex A References (Normative) [1] NIST Special Publication The International System of Units (SI) National Institute of Standards and Technology, U.S. Department of Commerce [2] ANSI/AMCA Standard 500-D-07 Laboratory Methods for Testing Dampers for Rating AMCA International, Inc., Arlington Heights, IL U.S.A. [3] ANSI/AMCA Standard Reverberant Room Method For Sound Testing of Fans AMCA International, Inc., Arlington Heights, IL U.S.A. [4] UL Standard UL555S Smoke Dampers Standard for Safety, Underwriters Laboratories Inc., Northbrook, IL U.S.A. 8 ANSI/AMCA

13 Annex B Rated Load [4] (Informative) Rated load is the maximum external torque or force that the actuator can reliably* move three full stroke cycles in the time specified by the actuator manufacturer at electrical or pneumatic power ± 2% after one half hour at the rated elevated exposure temperature per UL555S. Notes: 1. The drive (D) and spring return (SR) rated loads does not have to be the same. 2. Rated load performance is to be verified as follows. At least three typical new (not altered) sequentially built or randomly selected new actuators are to be loaded using weights that produce the rated torque or force ± 1% and timed in each direction (D and SR) after one half hour at the rated elevated exposure temperature per UL555S. The average time and conventional standard deviation (SD) for both D and SR times are to be calculated. The average stroke time minus three of their SD must be less than or equal to the time specified for the actuator. Normal ambient temperature timing data may be utilized for comparison in production. Note: If the actuator does not have an internal spring the actuator manufacturer s specified spring(s) must be attached prior to confirming the rated load and specified timing. 3. If the average force or torque required to stroke (D or SR) a given damper at the rated elevated exposure temperature per UL555S is less than or equal to the actuators rated load(s) then the damper will open in the actuator s specified time provided that the stall torque of the actuator is not exceeded at any point in it s stroke. ANSI/AMCA

14 Annex C Rated Stall Load [4] Rated stall load is the torque or force that an actuator will reliably produce at any specified point(s) in it s stroke after one half hour at the rated elevated exposure temperature per UL555S. In the drive (D) direction power is to be at nominal ± 2%. The actuator manufacturer must specify the stall torque or force at the following points (as a minimum): 15 for nominal 90 stroke or 16.7% of stroke, 30 for nominal 90 stroke or 33.3% of stroke, and 80 for nominal 90 stroke or 88.9% of stroke. Note: The rated stall load performance is to be verified as follows. At least three typical new (not altered) sequentially built or randomly selected actuators are to be stopped at the specified points and the dynamic torque or force measured after one half-hour at the rated elevated exposure temperature per UL555S. The average torque or force at each point minus three SD must be greater than or equal to the rated stall load specified for the actuator at that point. Normal ambient stall torque or force data may be utilized for comparison in production. 10 ANSI/AMCA

15 AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL INC. 30 West University Drive Arlington Heights, IL U.S.A. Tel: (847) Fax: (847) info@amca.org Web: The Air Movement and Control Association International Inc. is a not-for-profit international association of the world s manufacturers of related air system equipment, primarily but not limited to fans, louvers, dampers, air curtains, airflow measurement stations, acoustic attenuators and other air system components for the industrial, commercial and residential markets.

Methods of Testing Heavy Duty Dampers for Rating

Methods of Testing Heavy Duty Dampers for Rating Methods of Testing Heavy Duty Dampers for Rating AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL INC. The International Authority on Air System Components AMCA Publications Authority AMCA International

More information

AMCA Publication

AMCA Publication AMCA Publication 311-05 (Rev. 10/10) Certified Ratings Program - Product Rating Manual for Fan Sound Performance AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on

More information

AMCA Publication (R2010)

AMCA Publication (R2010) AMCA Publication 212-07 (R2010) Certified Ratings Program Product Rating Manual for Smoke Management Fan Performance Air Movement and Control Association International 30 W. University Drive Arlington

More information

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AMCA International Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International

More information

SD-1250 and SD-1600 Series Smoke Dampers

SD-1250 and SD-1600 Series Smoke Dampers SD-1250 and SD-1600 Series Smoke Dampers Product Bulletin Code No. LIT-1201592 Issued January 30, 2014 Supersedes October 14, 2013 Johnson Controls provides a leakage-rated damper for life safety smoke

More information

Performance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment

Performance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2011 Standard for Performance Rating of Airto-Air Heat Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does

More information

AMCA Publication

AMCA Publication AMCA Publication 511-13 Certified Ratings Program Product Rating Manual for Air Control Devices AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air System Components

More information

American National Standard for Lighting Equipment Voltage Surge Requirements

American National Standard for Lighting Equipment Voltage Surge Requirements American National Standard for Lighting Equipment Voltage Surge Requirements Secretariat: National Electrical Manufacturers Association Approved: December 21, 2017 American National Standards Institute,

More information

SFI SPECIFICATION 18.1 EFFECTIVE: JUNE 17, 1999 *

SFI SPECIFICATION 18.1 EFFECTIVE: JUNE 17, 1999 * SFI SPECIFICATION 18.1 EFFECTIVE: JUNE 17, 1999 * PRODUCT: Crankshaft Hub Harmonic Dampers 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards for

More information

Central Station Air-Handling Units

Central Station Air-Handling Units 2008 STANDARD FOR Standard 430 Central Station Air-Handling Units ISHRAE ( INDIAN SOCIETY OF HEATING, REFRIGERATING & AIR CONDITIONING ENGINEERS 4100 N. FAIRFAX DR., STE. 200 ARLINGTON, VIRGINIA 22203

More information

E-training. Positioners (Pneumatic, Electro pneumatic, I to P converters) Pneumatically actuated valves can be positioned in a number of ways.

E-training. Positioners (Pneumatic, Electro pneumatic, I to P converters) Pneumatically actuated valves can be positioned in a number of ways. Welcome to the K Controls e-training course designed to deliver useful Pneumatic Valve Actuation application information in small instalments. To unsubscribe or to register a colleague to receive these

More information

VARIABLE RESISTANCE REFERENCE PAR-809C. User Manual

VARIABLE RESISTANCE REFERENCE PAR-809C. User Manual VARIABLE RESISTANCE REFERENCE PAR-809C User Manual Table of Contents PROSTAT PAR-809C VARIABLE RESISTANCE REFERENCE Section Topic Page I. Introduction 4 II. Cautions & Warnings 4 III. Inspection & Preparation

More information

Instruction Manual August milltronics MMI BELT SCALE

Instruction Manual August milltronics MMI BELT SCALE Instruction Manual August 2003 milltronics MMI BELT SCALE Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected

More information

Hand Held Pull Tester Instruction Manual Order No

Hand Held Pull Tester Instruction Manual Order No Instruction Manual Order No. 63801-9700 Doc. No: TM-638019700 Release Date: 02-21-12 UNCONTROLLED COPY Page 1 of 13 Safety Warnings and Information Read and understand all of the instructions and safety

More information

PFI Standard Specification for Residential/Commercial Densified Fuel 18-June-2008

PFI Standard Specification for Residential/Commercial Densified Fuel 18-June-2008 Pellet Fuel Institute (PFI) Standard Specification for Residential/Commercial Densified Fuel 1. Scope 1.1 This specification is applicable for the determination of fuel quality grade for Residential or

More information

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application

More information

Hydraulic Deadweight Tester Model CPB5800

Hydraulic Deadweight Tester Model CPB5800 Calibration technology Hydraulic Deadweight Tester Model CPB5800 Applications Primary standard for ranges up to 20,000 psi hydraulic Pressure reference / calibration standard used in production and calibration

More information

Instruction Manual August milltronics MSI BELT SCALE

Instruction Manual August milltronics MSI BELT SCALE Instruction Manual August 2003 milltronics MSI BELT SCALE Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected

More information

SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 *

SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 * SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 * PRODUCT: Heavy Duty Stock Car Steel Wheels 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards

More information

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF TORQUE METROLOGY (Torque Generating Device Calibration)

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF TORQUE METROLOGY (Torque Generating Device Calibration) CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF TORQUE METROLOGY (Torque Generating Device Calibration) Approved By: Chief Executive Officer: Ron Josias Executive - Accreditation: Mpho Phaloane Author:

More information

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6

MIRUS International Inc. TYPICAL SPECIFICATION ULLTRA & ULLTRA-H1E 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6 I. PART 1 GENERAL 1. SCOPE A. NEMA Premium copper-wound ultra low loss isolation transformer with a higher efficiency than that required by NEMA Std. TP-1. Optimized for energy efficiency over a wide load

More information

CHECK AND CALIBRATION PROCEDURES FOR FATIGUE TEST BENCHES OF WHEEL

CHECK AND CALIBRATION PROCEDURES FOR FATIGUE TEST BENCHES OF WHEEL STANDARDS October 2017 CHECK AND CALIBRATION PROCEDURES FOR FATIGUE TEST BENCHES OF WHEEL E S 3.29 Page 1/13 PROCÉDURES DE CONTRÔLE ET CALIBRAGE DE FATIGUE BANCS D'ESSAIS DE ROUE PRÜFUNG UND KALIBRIERUNG

More information

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators Datasheet 53lb-in (6 Nm), Non-Spring Return Damper Actuators Overview The direct-coupled fail-safe/failin-place electronic actuators are designed for modulating, two position, and floating control of laboratory

More information

STICTION/FRICTION IV STICTION/FRICTION TEST 1.1 SCOPE

STICTION/FRICTION IV STICTION/FRICTION TEST 1.1 SCOPE Page 1 of 6 STICTION/FRICTION TEST 1.0 STICTION/FRICTION TEST 1.1 SCOPE Static friction (stiction) and dynamic (running) friction between the air bearing surface of sliders in a drive and the corresponding

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201705) E-15 Uninterruptible Power Systems (UPS) Issued date: May 9, 2017 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains technical requirements,

More information

LINEA Low Discharge Roof Exhausters

LINEA Low Discharge Roof Exhausters LINEA Low Discharge Roof Exhausters TECHNICAL SPECIFICATIONS BULLETIN LF18 PennBarry Your Single Source for Commercial & Industrial Supply & Exhaust Fans www.pennbarry.com TABLE OF CONTENTS INTRODUCTION

More information

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System Product Bulletin Code No. LIT-12011620 Issued July 2, 2014 RA-1250 Thermal Dispersion Fan Inlet Sensor Airflow Measuring System averages

More information

Passenger Train Brake Inspection and Safety Rules: Guidelines for British Columbia s Heritage Railways

Passenger Train Brake Inspection and Safety Rules: Guidelines for British Columbia s Heritage Railways Passenger Train Brake Inspection and Safety Rules: Guidelines for British Columbia s Heritage Railways Part I: General 1. SHORT TITLE 1.1 For ease of reference, these rules may be referred to as the "Train

More information

N-03 STEERING GEAR CONTROL SYSTEMS

N-03 STEERING GEAR CONTROL SYSTEMS Guideline No.: N-03(201510) N-03 STEERING GEAR CONTROL SYSTEMS Issued date: October 20,2015 China Classification Society Foreword: This Guideline is a part of CCS Rules, which contains technical requirements,

More information

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1. Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations

More information

Federal Railroad Administration, DOT CFR section Description Guideline PART 179

Federal Railroad Administration, DOT CFR section Description Guideline PART 179 Federal Railroad Administration, DOT 210.3 PENALTY ASSESSMENT GUIDELINES Continued 49 CFR section Description Guideline PART 179 179.1(e)... Tank car not constructed according to specifications also cite

More information

SFI SPECIFICATION 7.2 EFFECTIVE: DECEMBER 15, 2006 *

SFI SPECIFICATION 7.2 EFFECTIVE: DECEMBER 15, 2006 * SFI SPECIFICATION 7.2 EFFECTIVE: DECEMBER 15, 2006 * PRODUCT: Sportsman Lower Engine Containment Device 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum

More information

MILLTRONICS UNIVERSAL SCALE NIVERSAL SCALE Rev. 1.2

MILLTRONICS UNIVERSAL SCALE NIVERSAL SCALE Rev. 1.2 MILLTRONICS UNIVERSAL SCALE NIVERSAL SCALE 33455530 Rev. 1.2 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

ISO INTERNATIONAL STANDARD. Tyres Electrical resistance Test method for measuring electrical resistance of tyres on a test rig

ISO INTERNATIONAL STANDARD. Tyres Electrical resistance Test method for measuring electrical resistance of tyres on a test rig INTERNATIONAL STANDARD ISO 16392 First edition 2007-10-15 Tyres Electrical resistance Test method for measuring electrical resistance of tyres on a test rig Pneumatiques Résistance électrique Méthode d'essai

More information

MSI SINGLE IDLER BELT SCALE

MSI SINGLE IDLER BELT SCALE MSI SINGLE IDLER BELT SCALE Instruction Manual PL-319 January 2001 33453190 Rev. 1.2 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect

More information

D-4070 Two Stage Pneumatic Actuator

D-4070 Two Stage Pneumatic Actuator FANs 268.1, 1628.3 Product/Techncial Bulletin D4070 Issue Date 1095 D-4070 Two Stage Pneumatic Actuator The D-4070 Two Stage Pneumatic Actuator is a multipurpose positioning device used to accurately position

More information

Performance Rating of Central Station Air-handling Unit Supply Fans

Performance Rating of Central Station Air-handling Unit Supply Fans AHRI Standard 430 (I-P) With Addendum 1 2014 Standard for Performance Rating of Central Station Air-handling Unit Supply Fans AHRI STANDARD 430 (I-P)-2014 WITH ADDENDUM 1, PERFORMANCE RATING OF CENTRAL

More information

Test Report Project Nr. 2013/020

Test Report Project Nr. 2013/020 PISTON Ltd. 1033 Budapest Szőlőkert u. 4./B HUNGARY Tel: Fax: http: Email: (361)-275-0033 (361)-275-0034 www.pistonmedical.com info@pistonmedical.com Test Report Project Nr. 2013/020 Name and address of

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group Ref No: I15-014 Elevator Equipment No. 20 (Supersedes Elevator Equipment Certification Notice No. 1A, and Informs Elevator Equipment No 1B) Date: January 21, 2015 An Urgent Bulletin from CSA Group Existing

More information

POWERS CONTROL RC 195 Multiple Input Receiver- Controller

POWERS CONTROL RC 195 Multiple Input Receiver- Controller POWERS CONTROL RC 195 Multiple Input Receiver- Controller Document No. 155-036P25 RC 195-1 Description Features Application The RC 195 Multiple lnput Receiver-Controller is a pneumatic instrument which

More information

IMPACT REGISTER, INC. PRECISION BUILT RECORDERS SINCE 1914

IMPACT REGISTER, INC. PRECISION BUILT RECORDERS SINCE 1914 IMPACT REGISTER, INC. PRECISION BUILT RECORDERS SINCE 1914 RM-3WE (THREE WAY) ACCELEROMETER GENERAL The RM-3WE accelerometer measures and permanently records, for periods of 30, 60, and 90 days, the magnitude,

More information

E-Series and EF-Series Systems

E-Series and EF-Series Systems E-Series and EF-Series Systems Site Preparation Guide NetApp, Inc. 495 East Java Drive Sunnyvale, CA 94089 U.S. Telephone: +1 (408) 822-6000 Fax: +1 (408) 822-4501 Support telephone: +1 (888) 463-8277

More information

SFI SPECIFICATION 15.4 EFFECTIVE: JULY 20, 2010 * PRODUCT: Top Fuel and Funny Car Drag Race Drive Beadlock Wheels

SFI SPECIFICATION 15.4 EFFECTIVE: JULY 20, 2010 * PRODUCT: Top Fuel and Funny Car Drag Race Drive Beadlock Wheels SFI SPECIFICATION 15.4 EFFECTIVE: JULY 20, 2010 * PRODUCT: Top Fuel and Funny Car Drag Race Drive Beadlock Wheels 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures

More information

AHRI Standard 1371 (SI) 2017 Standard for Performance Rating of Electronic Expansion Valves

AHRI Standard 1371 (SI) 2017 Standard for Performance Rating of Electronic Expansion Valves AHRI Standard 1371 (SI) 2017 Standard for Performance Rating of Electronic Expansion Valves IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of

More information

ISO :2015/DAM 1

ISO :2015/DAM 1 DRAFT AMENDMENT ISO 19973-2:2015/DAM 1 ISO/TC 131 Voting begins on: 2018-01-15 Secretariat: ANSI Voting terminates on: 2018-04-09 Pneumatic fluid power Assessment of component reliability by testing Part

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

ANSI/AHRI Standard 881 (SI) with Addendum Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 881 (SI) with Addendum Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 881 (SI) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:

More information

SFI SPECIFICATION 1.3 EFFECTIVE: MAY 23, 2000 * PRODUCT: Nitro-Methane Drag Race Multiple Disc Clutch Assemblies

SFI SPECIFICATION 1.3 EFFECTIVE: MAY 23, 2000 * PRODUCT: Nitro-Methane Drag Race Multiple Disc Clutch Assemblies SFI SPECIFICATION 1.3 EFFECTIVE: MAY 23, 2000 * PRODUCT: Nitro-Methane Drag Race Multiple Disc Clutch Assemblies 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and

More information

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available:

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available: Model ABV Tag: Project: Location: Date: Engineer: Contractor: Architect: Submitted by: Application: The ABV Automatic maintains a constant airflow volume in HVAC applications. The highly engineered damper

More information

6.0 SPECIFICATIONS CONTENTS. Calibration. According to factory procedureeeeeeeeeeeeeee Accuracy*

6.0 SPECIFICATIONS CONTENTS. Calibration. According to factory procedureeeeeeeeeeeeeee Accuracy* 6.0 SPECIFICATIONS Calibration According to factory procedureeeeeeeeeeeeeee Accuracy* ± 1% full scale (FS) or ± 1 graduation on scale Scale diameter 41 mm Temperature range 45 to 115 F (10-45 C) Air humidity

More information

ANSI/BIFMA X Desk/Table Products - Tests. American National Standard for Office and Institutional Furnishings

ANSI/BIFMA X Desk/Table Products - Tests. American National Standard for Office and Institutional Furnishings BSR/BIFMA X5.5-201X ANSI/BIFMA X5.5-2014 Desk/Table Products - Tests American National Standard for Office and Institutional Furnishings American National Standard Approval of an American National Standard

More information

three different ways, so it is important to be aware of how flow is to be specified

three different ways, so it is important to be aware of how flow is to be specified Flow-control valves Flow-control valves include simple s to sophisticated closed-loop electrohydraulic valves that automatically adjust to variations in pressure and temperature. The purpose of flow control

More information

E-15 Uninterruptible Power Systems (UPS)

E-15 Uninterruptible Power Systems (UPS) Guideline No.E-15 (201510) E-15 Uninterruptible Power Systems (UPS) Issued date:20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,

More information

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES FAN TERMINAL UNIT SPECIFIABLE FEATURES Galvanized steel casing, mechanically sealed for low leakage construction NEMA TYPE 1 rated hinged control enclosure with standoff to prevent penetration of casing

More information

Umatilla Electric Cooperative Net Metering Rules

Umatilla Electric Cooperative Net Metering Rules Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through

More information

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm Product Data 35K Bypass Terminal 110 to 4400 cfm Carrier s 35K Series bypass terminals offer: 20-gage, galvanized steel casing construction 1/2-in. thick, dual density fiberglass insulation meeting NFPA

More information

VERIFYING THE ACCURACY OF LIQUID ADDITIVE METERING SYSTEMS

VERIFYING THE ACCURACY OF LIQUID ADDITIVE METERING SYSTEMS Test Procedure for VERIFYING THE ACCURACY OF LIQUID ADDITIVE METERING SYSTEMS Texas Department of Transportation TxDOT Designation: Tex-923-K Effective Date: August 1999 1. SCOPE 1.1 Use this method to

More information

UK Weighing Federation Technical Articles

UK Weighing Federation Technical Articles 3.4 WEIGHTS Introduction It normally starts with a phone call from a potential customer, I need some weights. As with any enquiry for any piece of weighing equipment, the first and most important point

More information

POWERS TM CONTROLS LC Pneumatic Damper Actuator

POWERS TM CONTROLS LC Pneumatic Damper Actuator POWERS TM CONTROLS Document No. 155-030P25 AP 331-4 Description Features The LC Actuator is a piston type pneumatic actuator. Air pressure is supplied to both sides of the piston to provide a force balance

More information

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc. ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT 15 Metal Industries, Inc. BENEFITS: Fan powered terminals are typically used for heating and cooling of perimeter zones.

More information

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101) 500-YH SINGLE DUCT AIR TERMINAL UNIT FORM 130.12-EG1 (1101) Table of Contents General Description.......................................................................3 500-YH Features........................................................................4-5

More information

MA-5200 Series MA-5300 Series

MA-5200 Series MA-5300 Series MA-5200 Series MA-5300 Series Two-Position Actuators General Instructions Application The MA-5200 series and MA-5300 series actuators are used for two-position control of valves and dampers which require

More information

Policy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620

Policy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620 Policy Bulletin No. 25 Net Metering Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620 Interconnection Standards For Residential Net Energy Metering With Electric

More information

ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 880 (I-P) 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on 27 October 2011 IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify

More information

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF FORCE METROLOGY:- CALIBRATION OF UNIAXIAL TESTING MACHINES

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF FORCE METROLOGY:- CALIBRATION OF UNIAXIAL TESTING MACHINES CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF FORCE METROLOGY:- CALIBRATION OF UNIAXIAL TESTING MACHINES Approved By: Chief Executive Officer: Ron Josias Executive - Accreditation: Mpho Phaloane

More information

ASTM B117 Testing Quality Control

ASTM B117 Testing Quality Control ASTM B117 Testing Quality Control ASTM B117 Testing, also known as a Standard Practice for Operating Salt Spray (Fog), is used to analyze relative corrosion for specimens of metals and coated metals exposed

More information

Variable Air Volume (VAV) Pressure Independent Control

Variable Air Volume (VAV) Pressure Independent Control VAV Terminal Units Asli Variable Air Volume (Vav) Terminal Units are volume flow rate controller for supply air on variable air volume system. These units are designed to control the airflow rate of conditioned

More information

Control Valves Positioner

Control Valves Positioner Control Valves Positioner HiFlo Valve Positioner Easy calibration Corrosion-resistant cover and base Withstands 150 psi at all parts Two -sided cam for easy field reversibility Optional / NPT for piped

More information

Control Valves Positioner

Control Valves Positioner Control Valves Positioner HiFlo HiFlo Valve Positioner Corrosion-resistant cover and base Easy calibration Withstands 150 psi at all parts Two -sided cam for easy field reversibility Optional / NPT for

More information

Doc:TED 11(794)W 1 September 2012 Draft Standard Automotive Vehicles - Windscreen Wiping System for 3 Wheeler Vehicles - Specification

Doc:TED 11(794)W 1 September 2012 Draft Standard Automotive Vehicles - Windscreen Wiping System for 3 Wheeler Vehicles - Specification For Comments only Doc:TED 11(794)W 1 September 2012 Draft Standard Automotive Vehicles - Windscreen Wiping System for 3 Wheeler Vehicles - Specification Not to be reproduced without permission Last date

More information

OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 24 Vac - Modulating Control

OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 24 Vac - Modulating Control Document No. 155-176P5 EA GBB/GIB-1 OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 4 Vac - Modulating Control Description The OpenAir direct coupled 4 Vac non-spring return (NSR) rotary electric

More information

Powers TM Controls EA 338 Electronic Actuator

Powers TM Controls EA 338 Electronic Actuator Powers TM Controls Technical Instructions Document No. 155-136P25 EA 338-1 Description Features 24 Vac power supply. The s are used with floor mount linkage kits to operate dampers in HVAC installations.

More information

ISO 8710 INTERNATIONAL STANDARD. Motorcycles Brakes and brake systems Tests and measurement methods

ISO 8710 INTERNATIONAL STANDARD. Motorcycles Brakes and brake systems Tests and measurement methods INTERNATIONAL STANDARD ISO 8710 Second edition 2010-04-15 Motorcycles Brakes and brake Tests and measurement methods Motocyles Freins et systèmes de freinage Méthodes d'essai et de mesure Reference number

More information

Pressure Instrument Testing Equipment

Pressure Instrument Testing Equipment Pressure Instrument Testing Equipment BULLETIN TE-1 A Halliburton Company A Durable, Portable Primary Standard Model 1305D Deadweight Tester The Ashcroft 1305D Deadweight Tester is an affordable, portable

More information

SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 *

SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 * SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 * PRODUCT: Polymer (Foam-Filled) Fuel Cells 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards

More information

EB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions

EB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions EB 8313-1 EN Translation of original instructions V2001-IP Control Valve Type 3372 0511/0531 Electropneumatic Actuator with Type 3321 Valve Type 3372 Electropneumatic Actuator Edition July 2013 Note on

More information

ISO INTERNATIONAL STANDARD. Measurement of noise emitted by accelerating road vehicles Engineering method Part 2: L category

ISO INTERNATIONAL STANDARD. Measurement of noise emitted by accelerating road vehicles Engineering method Part 2: L category INTERNATIONAL STANDARD ISO 362-2 First edition 2009-07-15 Measurement of noise emitted by accelerating road vehicles Engineering method Part 2: L category Mesurage du bruit émis par les véhicules routiers

More information

Performance Rating of Single Package Vertical Air-Conditioners And Heat Pumps

Performance Rating of Single Package Vertical Air-Conditioners And Heat Pumps ANSI/AHRI Standard 390 2003 Standard for Performance Rating of Single Package Vertical Air-Conditioners And Heat Pumps IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify

More information

test with confidence HV Series TM Test Systems Hydraulic Vibration

test with confidence HV Series TM Test Systems Hydraulic Vibration test with confidence HV Series TM Test Systems Hydraulic Vibration Experience. Technology. Value. The Difference. HV Series TM. The Difference. Our philosophy is simple. Provide a system designed for optimum

More information

CheckStar In-line Rotary Torque Transducer. Crane Electronics Ltd The force in torque management

CheckStar In-line Rotary Torque Transducer. Crane Electronics Ltd The force in torque management CheckStar In-line Rotary Torque Transducer Crane s CheckStar sets the standard for dynamic torque and angle measurements of all continuous drive and impulse tools, with proven reliable performance in thousands

More information

OPERATOR'S MANUAL AND MAINTENANCE INFORMATION MODEL T-2000 TEXTURE TEST SYSTEM

OPERATOR'S MANUAL AND MAINTENANCE INFORMATION MODEL T-2000 TEXTURE TEST SYSTEM OPERATOR'S MANUAL AND MAINTENANCE INFORMATION MODEL T-2000 TEXTURE TEST SYSTEM This Publication contains information proprietary To Food Technology Corporation The contents of this publication may not

More information

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary Document No. 155-785 OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary Description The OpenAir direct coupled enhanced non-spring return rotary electric actuators are designed

More information

ID-141x 12-Gauge Hat Channel Industrial Damper

ID-141x 12-Gauge Hat Channel Industrial Damper ID-141x 12-Gauge Hat Channel Industrial Damper Product Bulletin Code No. LIT-12011355 Issued June 12, 2013 Supersedes March 13, 2012 Since 1905, Johnson Controls has developed and refined air control products

More information

PRESSURE DIFFERENTIAL AND THERMAL SHOCK/PRESSURE DIFFERENTIAL EVALUATION. B ml Container (Mfg. Date , Lot # 2K15)

PRESSURE DIFFERENTIAL AND THERMAL SHOCK/PRESSURE DIFFERENTIAL EVALUATION. B ml Container (Mfg. Date , Lot # 2K15) PRESSURE DIFFERENTIAL AND THERMAL SHOCK/PRESSURE DIFFERENTIAL EVALUATION B902-10 90 ml Container (Mfg. Date 1210151, Lot # 2K15) TEST REPORT #: 12-1381 TESTING PERFORMED FOR: STARPLEX SCIENTIFIC, INC.

More information

TED50XT EXTREME TEMPERATURE THERMALLY EFFICIENT, INSULATED BLADE DAMPER

TED50XT EXTREME TEMPERATURE THERMALLY EFFICIENT, INSULATED BLADE DAMPER 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 APPLICATION Ruskin model TED50XT is a low leak, thermally efficient damper with insulated extruded aluminum blades specially

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -HS, Vektor -MS and Vektor -CS with Variable Geometry Nozzle September 017 Vektor -HS, Vektor -MS and Vektor -CS Greenheck s Variable Geometry Nozzle exhaust systems allow

More information

Titre / Title HIGH RELIABILITY RF COAXIAL LOADS AND ATTENUATORS GENERIC SPECIFICATION

Titre / Title HIGH RELIABILITY RF COAXIAL LOADS AND ATTENUATORS GENERIC SPECIFICATION Date: December 19 th, 16 ISSUE: 1/B PAGE: 1 / 21 Titre / Title HIGH RELIABILITY RF COAXIAL LOADS AND ATTENUATORS GENERIC SPECIFICATION Rédigé par / Written by Responsabilité / Responsibility Date Signature

More information

SFI SPECIFICATION 49.2 EFFECTIVE: MARCH 22, 2011 *

SFI SPECIFICATION 49.2 EFFECTIVE: MARCH 22, 2011 * SFI SPECIFICATION 49.2 EFFECTIVE: MARCH 22, 2011 * PRODUCT: Top Fuel Front Wing Assemblies 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards for

More information

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS

PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems SECTION 2 GUIDE TO GAS METERING SYSTEMS THE INSTITUTE OF PETROLEUM PETROLEUM MEASUREMENT MANUAL PART XV Metering Systems

More information

SMSIL-4THGU-E ISSUE: 12/12 SIL-SAFETY MANUAL. Upgrade Series Actuators

SMSIL-4THGU-E ISSUE: 12/12 SIL-SAFETY MANUAL. Upgrade Series Actuators SMSIL-4THGU-E ISSUE: 12/12 GB SIL-SAFETY MANUAL FOR AIR TORQUE 4 th Generation Upgrade Series Actuators GB SMSIL-4THGU-E 1) INTRODUCTION 1.1) Scope This manual contains information, safety-related characteristics

More information

PRESSURE DIFFERENTIAL AND THERMAL SHOCK/PRESSURE DIFFERENTIAL EVALUATION. B602-10, V302 and B202-1WNL Vial Variables TEST REPORT #:

PRESSURE DIFFERENTIAL AND THERMAL SHOCK/PRESSURE DIFFERENTIAL EVALUATION. B602-10, V302 and B202-1WNL Vial Variables TEST REPORT #: PRESSURE DIFFERENTIAL AND THERMAL SHOCK/PRESSURE DIFFERENTIAL EVALUATION B602-10, V302 and B202-1WNL Vial Variables TEST REPORT #: 13-1054 TESTING PERFORMED FOR: STARPLEX SCIENTIFIC, INC. 50A Steinway

More information

AD-1251 Probe with Differential Pressure Transducer

AD-1251 Probe with Differential Pressure Transducer AD-1251 Probe with Differential Pressure Transducer Product Bulletin Code No. LIT-12011473 Issued October 31, 2011 Supersedes September 6, 2011 The AD-1251 Probe with Differential Pressure Transducer (DPT)

More information

SFI SPECIFICATION 1.1 EFFECTIVE: NOVEMBER 9, 2001 *

SFI SPECIFICATION 1.1 EFFECTIVE: NOVEMBER 9, 2001 * SFI SPECIFICATION 1.1 EFFECTIVE: NOVEMBER 9, 2001 * PRODUCT: Replacement Flywheels and Clutch Assemblies 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum

More information

Voluntary Specification for Determining Forced Entry Resistance of Side-Hinged Door Systems

Voluntary Specification for Determining Forced Entry Resistance of Side-Hinged Door Systems Task Group Approval Council Approval Product Group Approval Successful Re-ballot 16-1052 Successful Ballot (#17-1011) Out for Ballot #18-1016 AAMA 1304-XX DRAFT #7 DATED 2/21/2018 Voluntary Specification

More information

SERIES 300 PLUNGER VALVES

SERIES 300 PLUNGER VALVES PART 1 - GENERAL 1.01 DESCRIPTION A. This section includes specifications for materials, manufacturing, coating, testing, and shipping of X, XX-inch, 150 lb plunger valve(s). B. Tag Numbers: FCV-XXXX 1.02

More information

Report. PIBCV Tests. Report 52724/1 Edition 2 February 2010

Report. PIBCV Tests. Report 52724/1 Edition 2 February 2010 Report www.bsria.co.uk PIBCV Tests This report supersedes Report 52724/1 Report 52724/1 Edition 2 February 2010 Carried out for: Danfoss Trata d.o.o. Jožeta Jame 16 SI-1210 Ljubljana Šentvid ID DDVS190729587

More information

NCC CODE OF PRACTICE 502

NCC CODE OF PRACTICE 502 NCC CODE OF PRACTICE 502 WHEEL & TYRE CONFIGURATIONS FOR CARAVAN HOLIDAY-HOMES & PARK HOMES ISSUE 1 8 June 1998 FOREWARD This Code of Practice has been drawn up by the National Caravan Council to ensure

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-19459-8 SOUTH AFRICAN NATIONAL STANDARD Verification standards for the verification of volume-measuring instruments, including commercial standards of volume Published by Standards South

More information

SINGLE DUCT AIR TERMINAL UNITS

SINGLE DUCT AIR TERMINAL UNITS SINGLE DUCT AIR terminal units SINGLE DUCT AIR TERMINAL UNITS MODEL NUMBER LEGEND XXXXX XXX -XXXX Model TH TL THECO Inlet Size (04, 05, 06, etc.) Generation 5, 6, 7 The METALAIRE single duct terminal units

More information