AN INTRODUCTION TO THE USE OF INVERTER POWER SUPPLIES IN GLOBAR APPLICATIONS HOW TO IMPROVE THE POWER FACTOR OF THE SYSTEM.
|
|
- Lauren Nicholson
- 5 years ago
- Views:
Transcription
1 AN INTRODUCTION TO THE USE OF INVERTER POWER SUPPLIES IN GLOBAR APPLICATIONS HOW TO IMPROVE THE POWER FACTOR OF THE SYSTEM. Stanley F. Rutkowski lll, Senior Applications Engineer, RoMan Manufacturing The Challenge Can an IGBT driven inverter power supply power the Globars in resistance heating applications to both improve the Power Factor of the system and use the same amount or less power. The Testing Process In order to test in free air the effects of AC and DC power onto the Globar, RoMan acquired silicon carbide Globars from a world branded manufacturer. Controlled Testing The illustrations shown below indicate the measured temperature on non-energized A/B/C Globar left hand view of the diagram and measured the temperature of a non- energized element next to it at position Z right hand view of the diagram. This was done for all five tests conducted in order to capture Conductive, Convective and Radiant heating. The calibrated current of the tested Globar is 60 Amps. 1
2 Results of Five Tests Test Notes Test #1: AC Three Phase A, B and C connections to the Globar 45.2 V A 3.45 kw C Test #2: AC Single Phase A-C connected to the Globar and B left open 68.2 V 57.9 A 4.0 kw C 62.8 V 54.2 A 3.4 kw C Test #3: DC Single Phase A-C connected to the Globar and B left open 68.4 V 58.6 A 4.0 kw C 63.3 V 55.1 A 3.5 kw C Test #4: DC Single Phase C-A (reversed polarity of Test #3) connected to the Globar and B left open 62.8 V 54.3 A 3.4 kw C Test #5: DC A and C connections Positive and B connection Negative 56.4 V 59.2 A 3.39 kw C During the testing process, connections of A-B and B-C were tested with all the outcomes being similar to A-C connections. As a result, only one set of data is presented. In addition, also 2
3 presented is data for forward and reversed DC connections that confirms there were no radical differences in the connections to determine a polarity on the Globar. Three phase Delta to Delta If we consider at 150 kw zone (40 elements in parallel), we can use a three phase Delta to Delta AC transformer with the ratings of: Tap Primary Secondary Secondary Turns Turns Volts
4 Test #1 indicated that the secondary voltage required is 45.2 volts and the current per Globar is Amps (for 40 Globars it would be Amps). Using tap two of the typical three phase power supply produces 70.2 volts on the secondary, or a margin of 1.5 (70.2 V / 45.2 V) Tap Primary Secondary Secondary Primary Primary Secondary Secondary Turns Turns Volts Phase Line Phase Line Considering an Inverter DC Application Current Current Current Current Test #4 indicated that the secondary voltage required is 62.8 volts and the current per Globar is 54.3 Amps (for 40 Globars it would be 2172 Amps). Tap Primary Secondary Secondary Primary TX TX Turns Turns Volts Phase Primary Secondary Current Current Current
5 Test #5 indicated that the secondary voltage required is 56.4 volts and the current per Globar is 59.2 Amps (for 40 Globars it would be 2368 Amps). This provides a margin of 1.5 (84.78 V / 56.4 V) similar to the AC unit. Comparisons Tap Primary Secondary Secondary Primary TX TX Turns Turns Volts Phase Primary Secondary Current Current Current Comparing the Three Phase AC system to test #4, the primary current per phase was reduced from Amps to Amps (28.3 Amps). This resulted in a 23.5 KVA (28.3 A x 480 V x Square Root (3)) reduction in Power in the application. Comparing the Three Phase AC system to Test #5 the primary current per phase was reduced from Amps to Amps (7.7 Amps) resulting in a 6.4 KVA (7.7 A x 480 V x Square Root (3)) reduction in Power in the application. Conclusions The Real Power of the application with the use of an IGBT system is similar to the existing three phase AC systems A typical power bill consists of five segments (Real Power, Reactive Power, Total Power, Power Factor and Peak Demand). -- The IGBT system will reduce Reactive Power (kvar) because of the DC in the secondary loop eliminating the inductance. -- Total Power (kva) as Reactive Power is a component of the Total Power. -- Power Factor as the wave form is modulated and not chopped as well as the reduction of the Reactive Power. -- Real Power and peak demand will be similar if not slightly reduced as indicated in the previous examples. Present systems employ a three pole (three phase AC System) while DC power is a two pole system. The IGBT system will work with the existing system, however, it would be optimized by a two pole system.* Heat on the pole is less with a DC system (measured with IR gun) however, the Radiant heat at the sample point was the same (what the load will see). 5
6 The Size and Weight of the transformer are reduced. *Tests conducted using the three pole system in order to obtained equitable test results 6
7 Copyright 2014, RoMan Manufacturing 7
Targeted Application of STATCOM Technology in the Distribution Zone
Targeted Application of STATCOM Technology in the Distribution Zone Christopher J. Lee Senior Power Controls Design Engineer Electrical Distribution Division Mitsubishi Electric Power Products Electric
More informationDS-1 (Residential) Customer Charge Per electric service account $ 8.23 $ 8.23 $ 8.23 Meter Charge Per electric service account $ 6.06 $ 6.06 $ 6.
Page 1 of 6 DS-1 (Residential) Customer Charge Per electric service account $ 8.23 $ 8.23 $ 8.23 Meter Charge Per electric service account $ 6.06 $ 6.06 $ 6.06 Distribution Delivery Charge (per kwh) Summer
More informationPSNH INTERCONNECTION REQUEST
PSNH INTERCONNECTION REQUEST Send the completed Interconnection Request and required attachments to: Public Service of New Hampshire Attn: Michael Motta, Senior Engineer Supplemental Energy Sources P.
More informationNon-Summer, First 800 kwh $ $ $ Non-Summer, Over 800 kwh $ $ $
Page 1 of 5 DS1 (Residential) Customer Charge Per electric service account $ 11.95 $ 11.95 $ 11.95 Meter Charge Per electric service account $ 5.00 $ 5.00 $ 5.00 Distribution Delivery Charge (per kwh)
More informationInstallation Planning (or what I didn t learn at meter school)
NWEMS Harris nstitute of echnical raining nstallation Planning (or what didn t learn at meter school) Presented by Brad Harris nstallation #1 A three phase commercial customer has the following installation
More informationWestern Canada BLRBAC Conference Selecting the Right Power Supply and Electrode for a Recovery Boiler ESP
Western Canada BLRBAC Conference Selecting the Right Power Supply and Electrode for a Recovery Boiler ESP April 15, 2015 John A. Knapik Application Engineer B&W Preciptech Overland Park, KS jaknapik@babcock.com
More informationTransmission & Distribution Glossary of Electrical Terms
Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The
More informationHardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance
Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance I Abdulhadi*, A Dyśko *Power Networks Demonstration Centre, UK, ibrahim.f.abdulhadi@strath.ac.uk University of Strathclyde,
More informationGENERATOR INTERCONNECTION APPLICATION
GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW Also Serves as Application for Category 3 Net Metering (Note:
More informationCUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)
GENERATOR INTERCONNECTION APPLICATION Category 2 (Combined) For All Projects with Aggregate Generator Output of More Than 20 kw but Less Than or Equal to 150 kw Also Serves as Application for Category
More informationPower Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com
Power Quality Power Factor Wiring and Service Scope Power factor is a major consideration in efficient building or system operation. It is the measure of how effectively your equipment is converting electric
More informationIntroduction. Systems Specifications
Project Name: MANiFEST Description: Real and Reactive Power Profiles Intended for Calibration of Energy Storage Systems Initial Author(s): SN/DTG The University of Sheffield; AMP/RT The University of Manchester
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)
Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Interconnection Customer Contact Information Name Alternative Contact Information (if different
More informationABB n.v PQF LV Active Filters: Bringing energy savings to you
ABB n.v. - 1-2GCS617011A0070 PQF LV Active Filters: Bringing energy savings to you Key elements of poor LV Power Quality Harmonics Reactive power Load imbalance ABB n.v. - 2 - Energy losses and high running
More informationDocument Requirements for Engineering Review- PV Systems v1.1 12/6/2018
Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)
More informationCATEGORY 2 GENERATOR INTERCONNECTION APPLICATION
CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering
More informationELG4125: Flexible AC Transmission Systems (FACTS)
ELG4125: Flexible AC Transmission Systems (FACTS) The philosophy of FACTS is to use power electronics for controlling power flow in a transmission network, thus allowing the transmission line to be loaded
More informationElectric Utility Contact Information Indiana Michigan Power
CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category 2 Net Metering
More informationPPHVC Power Quality Solutions. ABB PQC-STATCON Benefits and advantages
PPHVC Power Quality Solutions ABB PQC-STATCON Benefits and advantages Reasons for investing in power quality Poor power quality costs Sector Financial loss per incident Semi-conductors production(*) 3
More informationLegal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:
Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah
More informationDry Type Distribution Transformers
Selection Steps A. Use the following steps below to manually select a transformer. B. Find the electrical load requirements. These are: 1. Load operating voltage. 2. Load frequency (expressed in Hz). 3.
More informationLow and High Voltage Power Supplies
Low and High Voltage Power Supplies We work according to ISO 9001: 2008 Since 1994 Fug works according to the quality assurance system ISO 9001. All shipped units are checked and documented in our testing
More informationPower Factor Correction
AE9-1249 R10 August 2008 Power Factor Correction Index Page 1. Introduction... 1 2. Electrical Fundamentals... 1 3. Electrical Formulas... 2 4. Apparent Power and Actual Power... 2 5. Effects of Poor Power
More informationGalapagos San Cristobal Wind Project. VOLT/VAR Optimization Report. Prepared by the General Secretariat
Galapagos San Cristobal Wind Project VOLT/VAR Optimization Report Prepared by the General Secretariat May 2015 Foreword The GSEP 2.4 MW Wind Park and its Hybrid control system was commissioned in October
More informationIntermediate weight at 155kg Peak continuous fields up to 3 T for 15mm pole face diameter at 8mm gap Any mounting orientation Fast cycle times
OVERVIEW The 5405 dipole electromagnet is a fit, form and function upgrade for the 5403 electromagnet system. This upgrade provides approximately 40% more field for a given pole gap. The 5405 is shipped
More informationSECTION PADMOUNT TRANSFORMER - OIL FILLED
SECTION 26 12 19.01 PADMOUNT TRANSFORMER - OIL FILLED PART 1 GENERAL 1.1 DESCRIPTION: Padmount Transformers and Insulating Oil with underground primary and secondary connections for use in distribution
More informationForm G5-1 PACIFIC GAS AND ELECTRIC COMPANY GENERATION PRE-PARALLEL INSPECTION
Form G5-1 Page 1 of 3 PACIFIC GAS AND ELECTRIC COMPANY PG&E LOG WO/GM D&C Name of Project: Location: Transmission Line No. Distance Circuit No. 1. Maintenance Data: Generation Customer s Maintenance Chief
More informationR13 SET - 1. b) Describe different braking methods employed for electrical motors. [8M]
Code No:RT32026 R13 SET - 1 III B. Tech II Semester Regular Examinations, April - 2016 POWER SEMICONDUCTOR DRIVES (Electrical and Electronics Engineering) Time: 3 hours Maximum Marks: 70 Note: 1. Question
More informationSyllabus for the Trade of Electrician Duration : Six Month Second Semester Semester Code: ELE: SEM II
Syllabus for the Trade of Electrician Duration : Six Month Second Semester Semester Code: ELE: SEM II Week Trade practical No. 1-2 Different wave shapes of rectifiers and their values using C.R.O. Identification
More informationPQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads
PQC-STATCON PPHVC-Power Quality Solutions Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads Contents What is poor power quality? Reasons for investing
More informationABB n.v Power Quality in LV installations
ABB n.v. - 1 - Power Quality in LV installations PQ problems in LV installations 750 500 250 Volts 0-250 -500 Amps -750 3000 2000 1000 0-1000 -2000-3000 10:25:43.72 10:25:43.73 10:25:43.74 10:25:43.75
More informationPower Systems Trainer
Electrical Power Systems PSS A self-contained unit that simulates all parts of electrical power systems and their protection, from generation to utilisation Key Features Simulates generation, transmission,
More informationWhite Paper. Application of Resistive/Reactive Load Banks for kva Testing
White Paper Application of Resistive/Reactive Load Banks for kva Testing Application of Resistive/Reactive Load Banks for kva Testing Resistive load banks are the most commonly used load banks for the
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: Alternative Contact Information
More informationPower Factor Correction
Power Factor Correction Power Factor Correction and Voltage Optimisation have been around since the turn of the 20 th century and although in many cases their individual benefits and attributes make them
More informationBulletin Interconnection of electric power production sources Rules 2-010, , , , , , and
Bulletin 84-1-11 Interconnection of electric power production sources Rules 2-010, 64-078, 64-110, 84-004, 84-008, 84-018, 84-022 and 84-030 Scope Issued May 2018 Supersedes Bulletin 84-1-10 1) Requirements
More informationTransforming Energy.. For Advanced Technology
Transforming Energy.. Manufacturers of CE approved Transformers & Reactors Five Decades of Manufacturing Experience Manufacturers of Quality Reliable Transformers. Auto C 201,4 th Cross Peenya Induatrial
More informationPQC - STATCON The ultra fast Power Quality Compensator
PQC - STATCON The ultra fast Power Quality Compensator PQC - STATCON The ultra fast power quality compensator PQC - STATCON is based on IGBT voltage source inverter technology. It is a shunt connected
More information201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE
201 S. Anaheim Blvd. Page No. 3.2.1 A. GENERAL 1. The character of electric service available at any particular location should be ascertained by inquiry at the City's Electrical Engineering Division office.
More informationDC-DC CONVERTER. 5.1 Advantages & Disadvantages of DC-DC Converters
CHAPTER 5 DC-DC CONVERTER As the current trend is to go green research in automobile industry is on a focus to reduce pollution. In this regard fuel cells are gaining prominence and this technology is
More informationIntermediate weight at 155kg Peak continuous fields up to 3 T for 15mm pole face diameter at 8mm gap Any mounting orientation Fast cycle times
OVERVIEW The 5405 dipole electromagnet is a fit, form and function upgrade for the 5403 electromagnet system. This upgrade provides approximately 40% more field for a given pole gap. The 5405 is shipped
More informationELECTRICAL FUNDAMENTALS
ELECTRICAL FUNDAMENTALS PLUG OCTOBER 27, 2016 ARINDERPAL MATHARU IDEAWORKS MOHAWK COLLEGE Introduction Goal: To provide you with the Electrical Fundamentals Early 1800s Timeline 21 ST Century Current Current
More informationDrive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer
Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer This document contains sample specifications for Liquid-Filled Type Drive Transformers You may
More informationGlossary. * Credit for glossary starter: Florida Solar Energy Center. August 2015 PV Installer's Course: Glossary 1
ALTERNATING CURRENT (AC): Electric current (flow of electrons) in which the direction of flow is reversed at constant intervals, such as 60 cycles per second. AMORPHOUS SILICON: silicon with no crystal
More information2 SLR Series Line Reactors... 50
Drive Isolation & Protection Line Reactors Drive Isolation Transformers 2 SLR Series Line Reactors... 50 Drive Isolation Transformers... 51 Selection Table and Design Styles... 52 Electrical Connections...
More informationINSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad
INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad - 500 043 MECHANICAL ENGINEERING ASSIGNMENT Name : Electrical and Electronics Engineering Code : A40203 Class : II B. Tech I Semester Branch :
More informationMeasurement of induction motor characteristics
Measurement of induction motor characteristics ES163 Electrical and Electronic Systems MR TJ KENNAUGH School of Engineering, University of Warwick 27/01/01 Summary The aim of the laboratory is to increase
More informationINDUCTOTHERM INDUCTOTHERM HEADQUARTERS
MAY 11-13, 13, 2010 SHERATON SURREY BC CANADA INNOVATIONS OF MEDIUM FREQUENCY INDUCTION MELTING BY CHFINKJR INDUCTOTHERM CORP INDUCTOTHERM INDUCTOTHERM HEADQUARTERS MEDIUM FREQUENCY MELTING MELT SHOP IN
More informationTypes of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:
Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor.
More informationTABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...
TABLE OF CONTENTS About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... 1 CHAPTER 1 ELECTRICAL THEORY... 7 Unit 1 Electrician s Math and Basic Electrical Formulas...
More informationB BASIC HEAT TREATMENT CONSOLE
Maritime Stress PO Box 2898, 30 Estates Road Dartmouth, NS, B2W 4Y2, Canada Toll Free: 1-877-468-1781 Phone: (902) 468-7873 Fax: (902) 468-2304 Website: E-mail: info@maritimestress.com OPERATION MANUAL
More informationSection 6. Generation Interconnection
Table of Contents Section 6 Generation Interconnection A. Customer-Owned Generation... 6-3 B. Net Metered Generation... 6-4 C. Standby Generation Connections to the District's System... 6-6 D. Closed Transition
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less)
Section 466.APPENIX C Levels 2 to 4 Application Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less) Interconnection Customer Contact Information
More informationtests Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed.
tests ( Partial discharge level from day 1 10 pc Insulation 24 kv : impulse tested at 125 kv Insulation 36 kv : impulse tested at 170 kv, 200 kv indeed. electrical tests These tests verify contractual
More informationSECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS
CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION 100 KVA AND LARGER (CONCRETE PADS ONLY) 27.05-01 CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION
More informationMinnesota Power Systems Conference Insulation Coordination Tutorial November 6, 2014
Minnesota Power Systems Conference Insulation Coordination Tutorial November 6, 2014 Presented By: Steve Brewer Senior Product Manager HPS Arrester Business Unit Traveling Wave Theory/ Overvoltage Protection
More informationCSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:
CSDA Best Practice Title: Hi-Cycle Concrete Cutting Equipment Issue No: CSDA-BP-010 : Oct 1, 2010 Revised : Introduction Hi-cycle/high frequency concrete cutting equipment has become more prevalent in
More informationEst DCM Double Conversion Module 400kVA - 800kVA
Est.1968 DCM Double Conversion Module 400kVA - 800kVA The parallel operation of converters for increased output power or redundancy is commonplace but poses problems for large systems. A new approach is
More informationPVT Series. Peschel Variable Transformer FEATURES BENEFITS APPLICATIONS
PVT Series Peschel Variable Transformer The Peschel Variable Transformer was designed specifically for high power applications. The PVT Series is a simple, economical and high power solution for variable
More informationPower Perfector. Testing for Energy Savings. Undertaken by the Environmental Technology Centre. University of Nottingham.
Undertaken by the Environmental Technology Centre University of Nottingham Data supplied by Woodmead Energy Services On behalf of Bardo Electrical Ltd & Legend Power (UK) Plc 1 CONTENTS 1 EXECUTIVE SUMMARY.
More informationInstallation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor
World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com
More informationAmerican Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module
EFFECTIVE DATE JULY 28 204 OF 8 Dual Hybrid Ship Propulsion System 750V BUS Generator Generator Propulsion Propulsion Bus Capacitorss 50,000µF Total Traction Inverter Dual Inverterr e Power Inverter L
More informationDate: Technical Overview of Power Requirements for Hot Runner Control Systems
Date: 11-06-2008 Ref: By: Technical Overview of Power Requirements for Hot Runner Control Systems Fred Schroeder, Sr. Product Engineer Electronics, DME Company Introduction: Many customers ask often, I
More informationOFF-GRID Hybrid (BI-DIRECTIONAL) SOLAR INVERTER SOLAR INVERTER SOLAR UPS
OFF-GRID Hybrid (BI-DIRECTIONAL) SOLAR INVERTER SOLAR INVERTER SOLAR UPS ITS Power & Infrastructure Pvt. Ltd. is a leading designs, manufacturer & supplier of power product. ITS Power Company is in Bavdhan,
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationFigure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E
Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts
More informationSAM Series Power Inverter
SAM Series Power Inverter OWNER S MANUAL For model: (12 V DC INPUT, 115V AC OUTPUT) SAM-100-12 THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING SAFETY, OPERATION, MAINTENANCE AND STORAGE OF THIS PRODUCT.
More informationConnecting DC-DC Converter to Computer.
Connecting DC-DC Converter to Computer. Tim Wang 11/11/2013 Abstract: This Application note is to provide user an idea of how to connect DC-DC converter to Computer. This will include the use of right
More informationApproved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to
More informationOperating Efficiency of Crankshaft Drive Pumps
By Dr. Scott Veenhuizen, OMAX Corporation Operating Efficiency of Crankshaft Drive Pumps Nozzle output power, electrical input power, and pump crankshaft input power of a 380 MPa variable speed crankshaft
More informationAgility in energy Ahead of the challenge, ahead of the change
European Utility Week Vienna, November 3-5, 2015 Agility in energy Ahead of the challenge, ahead of the change Go-ahead application for existing distribution grids combines availability and efficiency
More informationSOLAR POWER SYSTEMS MANUAL
SOLAR POWER SYSTEMS MANUAL Gordon L.Gibby KX4Z Version 1.00 Friday June 22 2018 Two solar power systems have been constructed as follows: System Solar Panel & Connections 1 250 Watt 30-volt nominal solar
More informationInstruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator
Publication 351-01002-00A, 09/23/05 Instruction Manual Installation Operation Maintenance KCR 760 Voltage Regulator Page 1 Kato Engineering Inc. P.O. Box 8447 Mankato, MN USA 56002-8447 Tel: 507-625-4011
More informationInduction Motor Control
Induction Motor Control A much misunderstood yet vitally important facet of electrical engineering. The Induction Motor A very major consumer of electrical energy in industry today. The major source of
More information2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00
DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations
More informationOSU Rate of Heat Release Apparatus
OSU Rate of Heat Release Apparatus THE BENCHMARK IN FIRE TESTING OSU Rate of Heat Release Apparatus FAR 25.853 (a-1), FAA Fire Test Handbook Chapter 5, ASTM E 906 Configuration A Standard Test Method for
More informationScheme - I. Sample Question Paper
Program Name Program Code Course Title Sample Question Paper : Diploma in Industrial Electronics : IE : Electrical Machines and Transformers Max. Marks : 70 Time : 3 Hrs. Q1. ATTEMPT ANY FIVE OF THE FOLLOWING.
More informationH. J. Arnett Industries, LLC SW Avery Court Tualatin, OR 97062
H. J. Arnett Industries, LLC 20460 SW Avery Court Tualatin, OR 97062 Phone: 503-692-4600 Fax: 503-692-4661 Toll free: 800-684-9844 Web address: www.arnettindustries.com USE OF THE MEGA BEAST SERVICE CONDUCTOR
More informationThree Phase Hermetic Protector Application Process
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 1996 Three Phase Hermetic Protector Application Process J. Petraitis Texas Instruments Follow
More informationTECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT
TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT 1.0 PURPOSE: 1. To charge the battery bank through Solar PV source and AC supply. 2. To invert and produce utility quality sine wave. 3. Inverters
More informationUltravar TM AUTOMATIC POWER FACTOR CORRECTION & HARMONIC SOLUTIONS
AUTOMATIC POWER FACTOR CORRECTION & HARMONIC SOLUTIONS Contents Benefits of Power Factor Improvement... 4 ACCU-VAR Plus - AVC (50 to 600 KVAR) Standard and Optional Features... 5 240, 480, 600 Volt Equipment...
More informationPower Solutions Manager Generac Power Systems, Inc.
Engine Generator Paralleling Concepts Gen. #1 Gen. #2 Gen. #3 Gen. #4 Gen. #5 Presenter: Daniel Barbersek Power Solutions Manager Generac Power Systems, Inc. RUNNING HEADLINE What Topics Will Be Covered
More informationENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER
ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST
More informationCONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES
CONTENTS BY CHAPTER Chapter 1: GENERAL INFORMATION Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES Chapter 3: SERVICE ENTRANCES Chapter 4: METERING INSTALLATION Chapter 5: CUSTOMER-INSTALLED SERVICE
More informationDocument Requirements for Engineering Review PV Systems v1.0 6/9/2017
Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Outlined below are the documents and associated minimum details required for Engineering Review of Distributed Energy Resources Interconnection
More informationEE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION
EE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION 1. What is meant by drive and electric drive? Machines employed for motion control are called drives and may employ any one of the prime movers for
More informationHigh Power Semiconductor Devices and Solid State Switches for Pulsed Discharge Applications
High Power Semiconductor Devices and Solid State Switches for Pulsed Discharge Applications A. Welleman, W. Fleischmann ABB Switzerland Ltd, Semiconductors, Fabrikstrasse 3, CH-5600 Lenzburg / Switzerland
More informationPump ED 101. Power Factor (Part 2) - - Electricity Behaving Better
Pump ED 101 Power Factor (Part 2) - - Electricity Behaving Better Joe Evans, Ph.D http://www.pumped101.com Last month we took a close look at the flow of voltage and current in purely resistive and inductive
More informationEskisehir Light Train- Correcting Capacitive
Case Study-Estram Light Train Eskisehir Light Train- Correcting Capacitive Power Factor Eskisehir, a city in the Anatolia region of Turkey is located in an area inhabited since at least 3500 BCE- the copper
More informationUniversity of California, San Diego Cal (IT) 2 Technical Assignment #2. Brian Smith
University of California, San Diego Cal (IT) 2 Technical Assignment #2 Brian Smith Advisor: Dr. Moeck 31 October 2005 Brian Smith Lighting/Electrical Option University of California, San Diego Cal (IT)
More informationMicro3 Grid Tied Residential Package
Micro3 Grid Tied Residential Package List Price: $6,616.99 Our Price: $5,906.60 Save: $710.39 Model: Micro3 Grid-Tied Package Brand: Greener Energy Our Code: KITONGRIM3 This item is a package made up of
More informationModifiable TITAN Horizontal Motors Accessories and Modifications
36. Rotor, Standard And Optional Construction Standard rotor construction of 449, 5000 and 5800 frame TITAN products is typically die-cast aluminum. 720 RPM and slower is typically fabricated aluminum.
More informationElectric Service Rule No. 2 Description of Service
Page 1 of 6 A. General 1. All electric service described in this Rule is subject to conditions in the applicable Rate Schedule, other pertinent Rules, and the Electric Service Guides. 2. Alternating-current
More informationINESING srl. MOBILE SUBSTATIONS Energy Solution. Energy Innovation. INESING srl Energy Innovation
MOBILE SUBSTATIONS Energy Solution INTERNATIONAL FAIR MOBILE SUBSTATIONS ENERGY SOLUTION Complete design for energy s generations, transmission and distribution Mobile Substations Applications of Inesing
More informationABB central inverters ULTRA-750/1100/ kW to 1560kW
Solar inverters ABB central inverters ULTRA-750/1100/1500 750kW to 1560kW * ABB s utility-scale ULTRA inverters combine high efficiency with a wide input voltage range and multiple maximum power point
More informationOverview of Power Electronics for Hybrid Vehicles
Overview of Power Electronics for Hybrid Vehicles P. T. Krein Grainger Center for Electric Machinery and Electromechanics Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign
More informationAn advisory circular may also include technical information that is relevant to the rule standards or requirements.
Revision 0 Electrical Load Analysis 2 August 2016 General Civil Aviation Authority advisory circulars contain guidance and information about standards, practices, and procedures that the Director has found
More informationPRESENTER PETER NJENGA CHIEF ENGINEER, CUSTOMER SERVICE, KENYA POWER EAST AFRICAN POWER INDUSTRY CONVENTION 2012
PRESENTER PETER NJENGA CHIEF ENGINEER, CUSTOMER SERVICE, KENYA POWER EAST AFRICAN POWER INDUSTRY CONVENTION 2012 Introduction Power reliability Power Quality Harmonics Distortion Poor power factor Circuit
More informationUPS Ratings-Not so Apparent
App Notes ~ Outdoor Power System Design and Cost Considerations Application Notes Outdoor Power System Design and Cost Considerations 1 Authors Peter Nystrom President TSi Power Corp. Jason Marckx Chief
More informationStandby Power Systems
Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to
More information