TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT
|
|
- Rosanna Alexander
- 6 years ago
- Views:
Transcription
1 TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT 1.0 PURPOSE: 1. To charge the battery bank through Solar PV source and AC supply. 2. To invert and produce utility quality sine wave. 3. Inverters will run in Stand By and synchronous mode. 4. To operate connected single phase loads including Computers, Lamps (Florescent / incandescent) and Fans. 5. To transfer the load power form AC to DC and vice-versa in a bump-less mode. 2.0 POWER CONDITIONING UNIT (PCU) Power conditioning unit will be a multi-function device combining the functionality of a gridstand-by solar inverter with a true on-line single/two stage conversion. The required modes of operation would be: Under normal circumstances, solar energy powers the load with the Power Conditioning Unit. The Power Conditioning Unit also charges the battery from Solar. In case of load being greater than the solar power, then the PCU will discharge the power from the battery to a preset condition. Upon availability of AC power and absence of solar power, then the PCU would charge the battery to float levels. The connected loads would see no break in power during the transfer of the unit form one mode to another. The basic system would consist of an integrated built-in Solar Charge controller, Sine-wave Inverter and AC charger. AC & DC DB function shall also be built into this. PCU 2 KVA, 48V DC MPPT/ PWM Solar Charge Controller 1.1 KW 1 No. Sine Wave Inverter VA - 1 No. AC charger 30 Amp - 1 No. Data Acquisition System - 1 No. System is connected with 1.1 KW Solar PV array, 48V, 300 AH Tubular Battery Bank, 2 KVA load & AC Supply (if available) 3.0 CHARGE CONTROLLER 3.1 Charge controller shall receive power from Solar PV array. This array is a single feed to the solar charge controller and a DC rated MCCB or fuse shall be used for terminating SPV array. 3.2 Charge controller shall be MPPT/PWM based to maximize the SPV array output. A microprocessor based control circuit shall be provided in order to ensure delivery of maximum possible energy to the battery and to prevent overcharging. The charge controller shall be MPPT / PWM type, employing IGBT / MOSFET switching elements. The charging sequence from SPV Array shall be as follows: FROM SPV ARRAY: The battery shall be charged in Bulk mode that is at the maximum rate depending on the solar radiation till the battery terminal voltage is 2.4 volts per cell (adjustable in field). After achieving bulk stage charge controller should work in absorption stage and held battery voltage at maximum point of bulk stage for one hour. After one hour of absorption charge, controller should maintain battery voltage in float mode that should be lower than bulk level. Float to boost should be triggered again when battery voltage fall below a predefined value and after a fixed interval of time depending upon battery state.
2 SPECIFICATIONS: Switching elements: Type of charger: Input From PV: Output voltage: Protections: Indications: Dielectric Strength: MOSFET / IGBT PWM 48V DC Nominal Suitable for charging 48V DC nominal battery bank Short circuit, Deep discharge, Input Surge Voltage, Over Charge, High Temperature, Reverse Polarity Battery full, Battery Deep discharge, charging through Solar/ AC 2kV between input/output and Ground with EMI protections removed. Forced, with temperature sensitive Fan 4.0 SINE WAVE INVERTER 4.1 GENERAL FEATURES Inverters should be of very high quality having efficiency and of microprocessor / micro controller / DSP controlled type. The wave form should be pure sine-wave. The inverter shall be capable of monitoring its own parameters. The inverter should be completely compatible with the charge controller, grid charger and other system components. Sine-wave Inverter shall comply with the following: PCU should be able to operate continuously at full load condition for 10 hrs/ day. For DC to AC energy conversion MOSFET / IGBT devices shall be used. Inverter shall be designed for continuous, reliable and efficient operation as specified. Have high conversion efficiency from 25% to full load. The conversion efficiency at 25% of full load shall not be less than 80%. Full load efficiency should be more than 85%. Inverter shall have high overload capability; the overload capability of the inverter shall be a minimum of 150% at rated full load for 1 Min and 200% of full rated output for 10 seconds. During overload conditions, the inverter shall be capable of maintaining the rated voltage and frequency as per specifications. The supplier should specify the overload capacity in the bid. Inverter shall have automatic restart facility after overload Triggered shutdown. Restart shall happen after the removal of fault and resetting. Similarly after under voltage condition. Output voltage of the inverter shall be sinusoidal with harmonic distortion less than 5% THD. PCU must automatically ensure charge level of battery from solar or AC as per battery charge level and power availability The dimension, weight, mounting details etc. of the inverter shall be clearly indicated in the detailed technical specification and the same should be submitted along with the bid.
3 4.2 PROTECTION & SAFETY The inverter shall be robust, reliable and shall offer all the safety and protections features stated in the document. Both AC & DC lines shall have suitable fuses and protections to allow safe start up and shut down of the system. Fuses used in the DC circuit should be DC rated. Inverter output shall be protected against Inverter overload, surge current protection, High Temperature, Over/under voltage and over/under frequency. The inverter shall have provision for input and output isolation (automatic and manual). TECHNICAL SPECIFICATION Rating: AC Input Voltage: AC Input Frequency: DC Input voltage: Output Wave form: Output Regulation: Output Frequency: 2000VA 230V+10% /- 30% (AC charging current should at least be10 Amp at low threshold) Forced, with temperature sensitive Fan 50Hz ± 3 Hz 48 V DC Nominal Sine wave with Less than 5% of THD Maximum 5% against input voltage and load variation 50 Hz ± 0.5 Hz variation Output voltage: 230V AC - ± 2% Rating: No load Consumption: Overload capacity: Power Transfer: Dielectric strength: Short -circuit protection: Battery low voltage: 2000VA 2.5% of total output rating. (Sleep Function Required) 150% for 1 Minutes and 200% for 10 Second From AC to Battery or Vice-versa to be bumpless. Loads to see no break in power 2kV between input / output with Ground with EMI protections and 1.5kV between input and output Circuit breaker cum electronic control Auto shutdown at 1.85 V / Cell, 5.5V/ monoblock Load high voltage: Auto reset shutdown when 10% of Nominal output voltage is exceeded. High battery voltage : AC over current : Indication: Operating Temperature: Enclosure Protection: IP 20 Auto shutdown Auto shutdown LED/ LCD Based for Output OK / System Fault and overload Battery Deep discharge, Battery Over charge, charging on Fan Forced 0 Degree to +55 Degree Operating humidity: 95% non condensing
4 5.0 DATA ACQUISITION SYSTEM The PCU should have provision for monitoring interface thorough a front end communication port /USB/any other technology. The communication interface should facilitate monitoring of all the parameters of inverter and charge controller on local computer available at site. The data logs of the system should be convertible to MS Excel worksheet. The interface software should be windows based and compatible with regular Microsoft applications. The software if required should be supplied without any extra cost. 6.0 INSPECTION/TESTING: REIL or their nominated representative reserves the right to inspect/testing of items before dispatch to site and the quality/progress of job at site. Any alterations/modification required at the site shall be implemented. Vendor shall furnish a detailed schedule of activities. 7.0 CODES AND STANDARDS: The following codes and standards are applicable for the equipment to be supplied: 1. IEEE guide for harmonic control and reactive compensation of static power controllers are equivalent BIS standard. 2. National Electrical Safety code ANSI C (USA) or equivalent BIS code. 3. National Electrical NEPA (USA) or equivalent national BIS code. Note:- All Technical Data must be as per Technical Data sheet provided in Tender and Additional requirements confirmed during sample evaluation as per detail enclosed.
5 Annexure - I 2 KVA UNIT In addition to tender specification & technical data sheet confirmed by supplier, the PCU should also confirm the following as specified during sample evaluation : 1) Supplier name should only be put on the name plate. It should not be on LCD display or other place. REIL name and logo to be put on LCD and data logging software home page. 2) Data logging software CD and data cable should be provided with each unit. 3) Unique Sr no. should be put on each PCU. 4) Temperature sensitive cooling fan to be provided in the unit. 5) Output voltage : 230V + 2% under all variations in I/P voltage and load. 6) The unit should comply to following IEC standards : Efficiency measurements : IEC Environmental : IEC (6,21,27,30,75,78) Design qualification (Charge Controller) : IEC ) LED indications should be as per following: Overload : Red LED Inverter ON : Green LED Battery Low : Yellow LED Solar Charging : Green LED Charged : Green LED DC High Voltagc : Red LED Grid charging : Green LED System fault : Blinking LED s 8) Data Acquisition System : Following Parameters should be available on LCD and same should also be stored in internal memory (with one hour interval for 15 days): 1. Date & Time 2. PV Voltage 3. PV Current 4. PV Power 5. Inverter O/p Voltage 6. Output Current 7. Output Power 8. Solar Accumulated K wh 9. Grid Voltage 9) Terminals should be provided instead of socket for AC output. 10) Terminal quality to be improved for I/p side.
Technical Specifications of Solar PCUs
Solar PCU RATING 100VA 500VA 600VA 600VA/1KVA 2KVA 3KVA 4KVA 5KVA 6KVA 10KVA 10KVA PV CHARGE CONTROLLER RATING 100Wp 500Wp 600Wp 600Wp/1kWp 2kWp 3kWp 4kWp 5kWp 6kWp 10kWp 10kWp Model No. PCU1H24 PCU5H24
More informationDistinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation
SUN MAGIC + SUN MAGIC + is a state of art PCU product from ENERTECH product basket with Global standards. This unit will give operational flexibility to its customers to enjoy the benefits of advanced
More informationDistinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation
SUN MAGIC SUN MAGIC is a state of art PCU product from ENERTECH product basket with Global standards. This unit will give operational flexibility to its customers to enjoy the benefits of advanced monitoring
More informationMERU Solar Off-Grid Inverters
1 kva / 2 kva Off-Grid Solar Inverters with LCD and LED displays 24 / 48 VDC battery versions for 1 kva and 48 VDC for 2 kva Pure sine wave with highest efficiency Fully configurable (PV / Grid priority
More informationSOLAR OFF-GRID MPPT PCU ESM3K/48, ESM5K/96, ESM7K5/120, ESM10K/120
SOLAR OFF-GRID MPPT PCU ESM3K/48, ESM5K/96, ESM7K5/120, ESM10K/120 LCD Advanced MPPT Technology Pure sine wave output LCD screen for user convenience Highest efficiency in its class Temperature compensated
More informationIlluminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System
Illuminator Series CM GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System This description contains all the necessary functional and technical
More informationIlluminator Series CR NEMA 3R
Illuminator Series CR NEMA 3R GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION For 3.0, 4.0, 5.0, 6.5, 8.0kVA / kw Series CR - Single Phase Uninterruptible Power System This description contains all the
More informationSolar inverter AX-series
Power Supplies Inverters Solar inverter AX-series 1-5kVA Multifunctional inverter NEU / NEW PV inverter PV / Battery Charger with 3-stage charge Battery-backed power supply Sine wave inverter with charging
More informationSolar Inverter 3kW-8kW Inverter (off-grid)
Solar Inverter 3kW-8kW Inverter (off-grid) Max. DC Power Data: 5.67kW-11.52kW Max. DC Voltage: 200V-400V Max. AC Power: 3kW-8kW Output AC Voltage: 220V (Range: 209-231V) Frequency: 50, 60Hz (49.5-60.6Hz)
More informationCobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications
Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a stand-by, three-phase, solid state Lighting Inverter System
More informationDefender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications
Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. The Defender Mini CLI specification describes a single phase, online, solid state Lighting
More informationSolar PCU/Inverter 1 KVA to 100 KVA
Solar PCU/Inverter 1 KVA to 100 KVA Megatech Brand The unlimited source of energy. www.consulindia.com Company Profile Consul was founded in 1981 and has over 30 years of experience in power backup and
More informationFortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a single phase, on-line, double conversion, solid state
More informationSupply, testing, installation and commissioning of 5 ky A UPS system as per the following specification:
Supply, testing, installation and commissioning of 5 ky A UPS system as per the following specification: 1 Capacity 5 ky A UPS system with APFC system 2 Input supply Suitable for400±15% Y, 3 phase, 50
More informationPower Lynx 3 Uninterruptible Power System (UPS) Technical Specifications
Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Uninterruptible
More informationMKN-DSP SERIES - THREE PHASE
Output Power Factor 0.9 MKN-DSP SERIES - THREE PHASE Double conversion True On-Line UPS 3 Phase Input - 3 Phase Output 10 KVA 15 KVA 20 KVA 30 KVA 40 KVA 50 KVA 60 KVA Model for: 208/120 V 220/127 V /
More informationEFFEKTA Power Supplies
EFFEKTA GENERAL INFORMATION UPS topology ON LINE - Double Conversion Classification VFI-SS-111 in accordance with IEC 62040-3 Nominal output power (Cos Ø 0,9) - kva 10 15 20 30 40 Nominal output power
More informationR series solar charger inverter 1000W to 6000W
R series solar charger inverter 1000W to 6000W User s Manual Table of Contents: Figures of Unit......3 Line mode specification...3 Inverte mode specification......4 AC charge mode specification..5 Solar
More informationCENTAURI ENERGY SERVER TECHNICAL DATA kw POWER
Chassis Inverter power Rated input Rated output Battery pack Safeties Environment Others Input Voltage Lower Limit Input Voltage Upper Limit Power Input Current Output Voltage Output accuracy Transient
More informationOFF-GRID Hybrid (BI-DIRECTIONAL) SOLAR INVERTER SOLAR INVERTER SOLAR UPS
OFF-GRID Hybrid (BI-DIRECTIONAL) SOLAR INVERTER SOLAR INVERTER SOLAR UPS ITS Power & Infrastructure Pvt. Ltd. is a leading designs, manufacturer & supplier of power product. ITS Power Company is in Bavdhan,
More informationDon't let the shadows of yesterday hide the sunshine of tomorrow Nandina Morris
Don't let the shadows of yesterday hide the sunshine of tomorrow. -------------- Nandina Morris Hybrid MPPT Solar Inverter Main Features Pure sine wave inverter Built-in MPPT solar charge controller Selectable
More informationTECHNICAL DATA SHEET KVA UPS Systemss
Återförsäljare: Tre Röda AB TillingeHagby 7-745 94 ENKÖPING Tel: 08-560 200 22 e-post: info@treroda.nu http: www.treroda.nu When the INSIDE is important make the OUTSIDE Cannon TECHNICAL DATA SHEET 400-500-600-800
More informationLiebert. FP 50Z kva
Liebert FP 50Z 5 250 kva Enabling Tomorrow s CRITICAL EDGE INFRASTRUCTURE We helped some of the largest names in the industry bring new capacity online faster and at a lower cost when search and social
More informationFortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications
Fortress 3 Harsh Emergency Central Lighting Inverter (CLI) Technical Specifications PART 1 GENERAL 1.1 SUMMARY A. This specification describes a three phase, on-line, double conversion, solid state Lighting
More informationAurora Single Phase Emergency Lighting Inverters
Aurora Single Phase Emergency Lighting Inverters True Sine Wave On-Line Single Phase Emergency Lighting Inverters AURORA Series Emergency Lighting AC Inverters are among the most reliable systems available
More informationMPPT Solar Integrated Inverters (500VA~2500VA) User Manual THE SOLAR TECH CO.,LTD. Solar Integrated Inverter Series 500VA~2500VA 13.
MPPT Solar Integrated Inverters (500VA~2500VA) User Manual THE SOLAR TECH CO.,LTD. - 1 - Table of Contents 1. SALIENT FEATURES...3 2.. PRODUCT INSTALLATION & PRECAUTIONS...3 2.1. PRODUCT INSTALLATION &
More informationModel ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase
Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible
More informationOff-Grid Power Solutions EVOLUTION SERIES INVERTER/CHARGERS COMMERCIAL VEHICLES BACKUP POWER
Off-Grid Power Solutions EVOLUTION SERIES INVERTER/CHARGERS REMOTE LOCATIONS COMMERCIAL VEHICLES RV/MARINE BACKUP POWER Do you need reliable AC power in a vehicle, remote location or for emergency backup?
More informationEAST GROUP COMPANY PROFILE. Energy storage solutions. About us. Grid-connected PV systems. Our Products. Our Team. UPS solutions
EAST GROUP Energy storage solutions In this catalogue, you will find all components and services related to energy storage solutions, which include off-grid and hybrid solar systems, GF series single phase
More informationPOWER kva
TECHNICAL DATA SHEET B9000 FXS 60-80-100-125-160kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos φ 0,8) kva 60 80 100 125 160 Nominal output power
More information400W / 600W / 1000W / 1500W DIY Wind Turbine
400W / 600W / 1000W / 1500W DIY Wind Turbine Not for 400W Producing power at remote sites Where the utility grid is not available Hybrid system Combination of solar & wind power Low-Power applications
More informationgimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy
GE Digital Energy Technical data sheet Uninterruptible Power Supply LP11 924 Series 6 & 10 kva gimagination at work GE T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www..com General data Topology VFI,
More informationUSER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4
USER S MANUAL PowerWalker VFI 1000 / 3000VA CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION......... 2 3. SYSTEM DESCRIPTION......... 4 4. CABLE CONNECTION......... 7 5. OPERATION...... 8 6. TROUBLE
More informationPOWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)
TECHNICAL DATA SHEET B9000 FXS 200-250 - 300kVA +44 (0)20 8868 3732 GENERAL INFORMATION UPS Type ON LINE - Double Conversion Nominal output power (Cos φ0,8) kva 200 250 300 Nominal output power (Cos φ1,0)
More informationPOWER kva
+44 (0)20 8868 3732 TECHNICAL DATA SHEET B9600 400-800kVA GENERAL INFORMATION UPS Type ON LINE - Doppia Conversione Nominal output power (Cos φ0,8) kva 400 500 600 800 Nominal output power (Cos φ1,0) kw
More informationThree Phase UPS Systems Range: 10 to 500kVA
Three Phase UPS Systems Range: 10 to 500kVA Three Phase UPS Systems Hitachi Hi-Rel Power Electronics Pvt. Ltd. is in the business of Industrial UPS Systems since 1987 and has rich experience in supplying
More informationTOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS
INSTRUCTION MANUAL TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS September 2000 TOWER UPS DISTRIBUTION (PTY) LTD 1 1. INTRODUCTION T A B L E O F C O N T E N T S 1.1 General Description... 3 1.2 Features...
More informationPure Sine Wave Inverter Charger
Pure Sine Wave Inverter Charger Renogy 1000W 2000W Pure Sine Wave Inverter Charger Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version 1.6 1 Important Safety Instructions Please save
More informationTechnical data sheets
GE Consumer & Industrial Power Protection Technical data sheets Digital Energy Uninterruptible Power Supply LP 11 Series / 3 5 6 8 10 kva A product by: GE Consumer & Industrial SA General Electric Company
More informationApplication. Battery. Public Grid GS HYBRID INVERTER
GS HYBRID SOLAR INVERTER Feed from Solar and Power, Grid backup, Build-in Transfer Switch / Solar Charger/ AC Charger, 500W~3kW, Pure Sine Wave Output GSH-15XX and GSH-30XX are the ideal solutions for
More informationILLUMINATOR LV. Emergency Lighting Inverter System 175VA through 750VA. Illuminator Series LV Single Phase
ILLUMINATOR LV Emergency Lighting Inverter System 175VA through 750VA Illuminator Series LV Single Phase ILLUMINATOR SERIES LV The Illuminator Series LV is a 175VA-750VA fast transfer Emergency Lighting
More informationUSER S MANUAL SOLAR POWER INVERTER KW-6KW
USER S MANUAL ------SOLAR POWER INVERTER------ 1KW-6KW Appliances--------------------------------------------- Content Content Content... 1 1 Figures of unit... 2 2 Specification... 3 3 Front panel...
More informationINVERTER/CHARGERS Off-Grid Power Solutions
EVOLUTION SERIES INVERTER/CHARGERS Off-Grid Power Solutions REMOTE LOCATIONS RV/MARINE COMMERCIAL VEHICLES BACKUP POWER www.samlexamerica.com Do you need reliable AC power in a vehicle, remote location
More informationINVERTER. MECHANICAL DATA Steel with powder paint Dimension (mm) 527 x 228 x 190 Net Weight (kgs) 18 STANDAR. Cont output power at 20ºC. Cos φ 0.
12 Vdc 1500 W 2000 VA Overload >125% 60 s >110% 15 min Efficiency 89% Standby adjustment 0.2% - 2% Rated Power Zero load power 14 W Zero load power (power save mode) 3.5 W 10 A 12 Vdc Max Output current
More informationTechnical Data Sheets
GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply LP 33 Series / 10 20 30 kva 400 VAC CE Series 4 SGT4000_010-020-030 GE_01 Manufactured by: GE
More informationU n i n t e r r u p t i b l e P o w e r S y s t e m
SMART ON-LINE UPS User s Manual U n i n t e r r u p t i b l e P o w e r S y s t e m Smart On-Line UPS 2KVA ~ 20KVA 20KVA Exhaust hole (16)Main breaker (12)Heat exhaust hole (15)Telephone (Rj11) or network
More informationTECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)
TECHNICAL DATA SHEET INFINITY 3300 10 15 20 kva 3Ph(in) 3Ph(out) GENERAL INFORMATION POWER - kva 10 15 20 UPS typology ON LINE Double conversion ACTIVE stand by-operation (Optional) Nominal output power
More informationD Series: UPS UPTO - 300KVA - Three / Three Phase
D Series: UPS UPTO - 300KVA - Three / Three Phase All in one D Series UPS High Power UPS Systems, Now in India Properties : Standard Properties 1GBT rectifier inverter technology Input power factor correction
More informationTECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III
TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III 1. SCOPE A. The Central Lighting Inverter shall be a solid-state three phase system designed to provide
More informationPOWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting
POWER+ PREMIUM CBS CENTRALIZED Battery System BS-EN-50171 Emergency electrical installations Electric power systems Emergency lighting Escape lighting POWER+ PREMIUM CBS 10KVA-40KVA The systems running
More informationPOWERTRONIX QUASAR 5-40 KVA
POWERTRONIX QUASAR 5-40 KVA DT 0251 E00 TECHNICAL DATA Rev. Description Date Checked Released Date Type of doc. Page n Pag. Tot. ISSUED 07.03.2000 E.Borsa 07.03.2000 Approved A.Gorlani Pag.1/6 Cod. DT251
More informationP H O T O V O LTA I C
PHOTOVOLTAIC SOLAR PANEL Crystalline Solar Cells XM-125 (R165) 125 x 125 mm Mono Crystalline Solar Cell XM-156 (R200) 156 x 156 mm Mono Crystalline Solar Cell XP-156 156 x 156 mm Poly/ Quasi Mono Crystalline
More informationRover Series. Rover 20A 40A Maximum Power Point Tracking Solar Charge Controller
Rover Series Rover 20A 40A Maximum Power Point Tracking Solar Charge Controller 0 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version 1.5 Important Safety Instructions Please save these
More informationBANGALORE ELECTRICITY SUPPLY COMPANY LIMITED
GUIDELINES FOR EMPANELMENT OF GRID TIED INVERTER MANUFACTURERS FOR IMPLEMENTATION OF SRTPV PROGRAM IN BESCOM. I. NEW EMPANELMENT 1. The grid tied inverter manufacturer shall register their application
More informationCONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9
USER MANUAL 1 CONTENTS 1. INTRODUCTION... 1 2. SAFTY INSTRUCTION... 3 3. CABLE CONNECTION... 4 4. SYSTEM DESCRIPTION... 5 5. OPERATION... 9 6. TROUBLE SHOOTING GUIDE... 25 7. OPERATION MODES..... 27 8.
More informationUser Manual 1KVA-5KVA (PF1) INVERTER / CHARGER. Version: 1.0
User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER Version: 1.0 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...
More informationHYBRID 5048E. Hybrid Inverter INSTALLATION AND OPERATION MANUAL. Version 2.0E
HYBRID 5048E Hybrid Inverter INSTALLATION AND OPERATION MANUAL Version 2.0E SAFETY INSTRUCTIONS Risk of Electric Shock Alternating Current (AC) and Direct Current (DC) sources are connected to this device.
More informationIMPORTANT. Always connect the batteries first. Use for 12V battery system only 12V (36 cells) solar panel array.
EN Appendix Manual IMPORTANT Always connect the batteries first. Use for 12V battery system only 12V (36 cells) solar panel array. Use for 24V battery system only 24V (72 cells) solar panel array. BlueSolar
More informationUser Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER
User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER CONTENTS ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture... 2 Product Overview...
More informationSolar Inverter Manual
Solar Inverter Manual Introduction SMPS series solar inverter power charging efficiency increased by 30%~60% than traditional controller charging. This inverter has automatic identification, three-stage
More informationSmartOnline 3-Phase In/Out 120/208V 20kVA 16kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, Tower, DB9 Serial, Hardwired
SmartOnline 3-Phase In/Out 120/208V 20kVA 16kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, Tower, DB9 Serial, Hardwired MODEL NUMBER: SU20K3/3 Description Tripp Lite's SU20K3/3 20kVA SmartOnline
More informationSolar Hybrid Inverter SP Brilliant Series
User Manual Solar Hybrid Inverter SP Brilliant Series Version: 1.5 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System
More informationTECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)
TECHNICAL DATA SHEET B8033FXS 10 15 20 kva 3Ph(In) 3Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cosϕ 0.9) kva 10 15 20 Nominal output power (Cosϕ 1.0) kw 9 13.5
More information1KVA/ 2KVA/ 3KVA/ 4KVA/ 5KVA MS, LV MPPT INVERTER / CHARGER. User Manual. Version: 2.3
1KVA/ 2KVA/ 3KVA/ 4KVA/ 5KVA MS, LV MPPT INVERTER / CHARGER User Manual Version: 2.3 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features...
More informationCONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION...
CONTENTS 1. INTRODUCTION...... 1 2. SAFTY INSTRUCTION.......... 2 3. CABLE CONNECTION.......... 4 4. SYSTEM DESCRIPTION............ 5 5. INVERTER OPERATION... 11 6. TROUBLE SHOOTING GUIDE....... 16 7.
More informationSola/Hevi-Duty S3K Series Mini-Tower UPS
Sola/Hevi-Duty S3K Series Mini-Tower UPS GUIDE SPECIFICATIONS 700VA to 1600VA 120V models Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical
More informationUser Manual. Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5
More informationAPC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply
APC Smart-UPS GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous
More information.3 Section Waste Management and Disposal.
Issued 2005/06/01 Section 16261 Uninterruptible Power Systems Static Page 1 of 10 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section
More informationX600. Technical Sheet
X600 Technical Sheet 2 Inverter + Charge Controller + X600 1 Photovoltaic Modules Stand Alone Technical Sheet Electric Diagram 3 Technical Characteristics Contacts X600: Electric Diagram 1 2 3 Photovoltaic
More informationTECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)
TECHNICAL DATA SHEET B8031 FXS 10 15 20 kva 3Ph(In) 1Ph(Out) GENERAL INFORMATION UPS Type ON LINE Double Conversion Nominal output power (Cos 0.9) kva 10 15 20 Nominal output power (Cos 1.0) kw 9 13.5
More informationUser Manual 5KVA/5KW INVERTER / CHARGER. Version: 1.3
User Manual 5KVA/5KW INVERTER / CHARGER Version: 1.3 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...
More informationUPS Sentry HPS. power supply sources - isolation transformers and generators over less sophisticated power systems.
SENTRY HPS HM/HT provides maximum protection for vital mission-critical networks, security applications (electro-medical) and industrial applications thanks to its outstanding mechanical and electrical
More informationTechnical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality
GE Digital Energy Power Quality Technical data sheet Digital Energy Uninterruptible Power Supply VH700-1000 - 1500 2000 UL A product by: GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino
More informationLow Frequency Inverter. User Manual
Pure Sine Wave 220-240V 50-60Hz Low Frequency Inverter User Manual For LK/LW series Power Star inverters only, models: LK2000, LK2000-24, LK3000, LK3000-24, LK3000-48, LK6000-24, LK6000-48 1. Safety precautions
More informationTechnical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER
Technical Specifications Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER Sentinel PRO CONTENTS 1. GENERAL DESCRIPTION... 2 1.1. Main features of the UPS unit... 3 1.2. Standard Versions...
More informationSmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option
SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT20K Highlights On-line double-conversion topology, VFI operation
More informationPhotovoltaics. MPI Hybrid Series
Photovoltaics *Also support parallel feature to 3-phase feedback (3 units) MPI Hybrid Series These hybrid solar inverters combine the features of both grid-tied and off grid operations, and allow users
More informationSOLAR INVERTER/CHARGER 1000VA/1500VA/2000VA. Appliances. PC TV Light Electricfan
SOLAR INVERTER/CHARGER SOLAR INVERTER/CHARGER 1000VA/1500VA/2000VA Appliances 420-00300-02 PC TV Light Electricfan Table Of Contents GENERAL PRECAUTIONS... 1 PERSONNEL PRECAUTIONS... 1 INTRODUCTION...
More informationSolar inverter with MPPT AX II - M series: 4 / 5 kva, AX II - P series: 3 kva. With integrated star point grounding* according to VDE AR-E 2510-
Solar inverter with MPPT AX II - M series: 4 / 5 kva, AX II - P series: 3 kva With integrated star point grounding* according to VDE AR-E 2510- and power factor 1.0 AX-M series: Part numbers: 4000 VA 5000
More informationX400. Technical Sheet
X400 Technical Sheet 2 Inverter + Charge Controller + X400 1 Photovoltaic Modules Stand Alone Technical Sheet Electric Diagram 3 Technical Characteristics Contacts Battery Pack X400: Electric Diagram 1
More informationUser Manual Solar Charge Controller 3KW
User Manual Solar Charge Controller 3KW Version: 1.3 CONTENTS 1 ABOUT THIS MANUAL... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 SAFETY INSTRUCTIONS... 1 2 INTRODUCTION... 2 2.1 Features... 2 2.2 Product Overview...
More informationUser Manual 1.5KVA-3KVA INVERTER / CHARGER. Version: 1.1
User Manual 1.5KVA-3KVA INVERTER / CHARGER Version: 1.1 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...
More informationYOUR POWER STORAGE SOLUTION!
YOUR POWER STORAGE SOLUTON! TECHNCAL DATA MODEL Rated power Maximum charging power HYBRD TOWER 5 KW (single phase) 5000 W 4800 W HYBRD TOWER 0 KW (three phase) 0000 W 9600 W PV NPUT (DC) Maximum DC input
More informationThe Traveler Series: Adventurer
The Traveler Series: Adventurer RENOGY 30A Flush Mount Charge Controller Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version: 2.2 Important Safety Instructions Please save these instructions.
More informationK50. Technical Sheet
K50 Technical Sheet 2 Inverter + Charge Controller + K50 1 Photovoltaic Modules Stand Alone Technical Sheet Electric Diagram 3 Technical Characteristics Contacts Battery Pack K50: Electric Diagram Inverter
More information3 Uninterruptible Power Systems
3 Uninterruptible Power Systems S4K2U and S4K2U-5 Industrial On-Line UPS The true on-line (double conversion) protection offered by the S4K2U Industrial UPS series eliminates a wider range of potential
More informationUser Manual 1KVA-5KVA INVERTER / CHARGER
User Manual 1KVA-5KVA INVERTER / CHARGER Version: 1.7 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...
More informationTLE Series UPS 400/500 kw With eboost Technology
TLE Series UPS 400/500 kw With eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical power
More informationSmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9
SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9 MODEL NUMBER: AL-84111 Specifications OUTPUT Output Volt Amp Capacity (VA) 2200 Output kva Capacity
More informationSECTION MOTORS AND VARIABLE FREQUENCY DRIVES
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal
More informationUser Manual 4KVA/ 5KVA INVERTER / CHARGER. With MPPT Controller
User Manual 4KVA/ 5KVA INVERTER / CHARGER With MPPT Controller CONTENTS ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...
More informationw w w. o p t i - s o l a r. c o m Tel: Catalogue Fax: mail: OPTI-Solar USA: Tel: Fax: OPTI-Solar Europe:
OPTI-Solar Catalogue Solar Market Solar Market OPTI is a world-famous brand. Build a strong relationship with our value customers and partners to strengthen their market. Assist how to grow up and engage
More informationLiebert GXT & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL
GXT4 5000 & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL 1.1 SUMMARY This specification shall define the electrical and mechanical characteristics and requirements for a continuousduty,
More informationTLE Series UPS 160/200/225/250 kw with eboost Technology
TLE Series UPS 160/200/225/250 kw with eboost Technology The new TLE Series Uninterruptible Power Supply (UPS) is a three-phase high power product with best-in-class multi-mode efficiency for global critical
More informationUser Manual 1.5KVA-3KVA INVERTER / CHARGER
User Manual 1.5KVA-3KVA INVERTER / CHARGER Version: 1.0 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...
More informationUser Manual 1KVA-5KVA INVERTER / CHARGER. Version: 2.1
User Manual 1KVA-5KVA INVERTER / CHARGER Version: 2.1 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture...
More informationSmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option
SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT30K Highlights On-line double-conversion topology, VFI operation
More informationFlinSlim Lite Solar Hybrid Inverter 1KVA-5KVA USER MANUAL. Version: 1.3
1KVA-5KVA USER MANUAL Version: 1.3 Table Of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Features... 2 Basic System Architecture... 2 Product Overview...
More informationBattery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.
More information