Advantages of SELF POWERED Overcurrent & Earth Fault Relays

Size: px
Start display at page:

Download "Advantages of SELF POWERED Overcurrent & Earth Fault Relays"

Transcription

1 AL Advantages of SELF POWERED Overcurrent & Earth Fault Relays

2 1. INTRODUCTION Figg 1. Transformation center. Self-powered protections arise against the undeniable fact that transformation centers do not have a maintenance routine to ensure that the center is operative. The reasons for this situation are diverse, including: Lack of access to the center. Not all facilities are roadside. Some are buried, or in areas of difficult access. Lack of knowledge. Transformationn centers, ass already indicated, many times (50% or so depending on the country) are purchased by individuals, that ignore the maintenance e routine of these centers. Lack of qualified personnel. Power companies have qualified personnel, but their labors of maintenance are focused in the primary distribution centers, leaving transformation centers as a subsidiary task, since there is not enough qualified staff. Given this reality, the need for electronic equipments maintenance pass from a desire to a necessity. without Fig 2. Breaker with fuse. Within maintenance routines, most of them, or greatest need for them, is derived from the need to verify and check the status of the battery supply. Since the trip of transformation centers are always definitive, and there is no reclose, neither engines for coils reconection, there is the possibility of segregation switchgear, by means of a breaker or circuit breaker, whichh instead of having tripping coils, have tripping strikers.. The strikers are electromagnets that are loaded at the closing of the switchgear, and is required low-energy trigger to releasee them. Different models and tensions, and in general the selection of it is a compromise between mechanical security and tripping energy, but in general are a reliable and high quality element. However, in many installations the use of a striker is not always possible, since it assumes the mechanical modification of the mechanisms for locking and tripping of the breakers, and can usually come standardd with tripping coils. Thus, it is possible the use of accessory equipments whichh act as accumulators of energy to generatee the tripping of the coil. They are accessories that can be loaded prior to installation or on it, if available auxiliary power supply.. Fig 3. Tripping striker 2 / 5

3 This equipment guaranteed to keep tripping energy (30 J) at least 72 hours, it means, a weekend, and also, if found fully dischargedd it has a loading time sufficiently short (less than ten seconds) to have trip in the shortest time possible. Fig 4. TCM coil energy acumulator. Of course, the amount of energy used in thee trip, is directly related to the type of coil used, and how much less energy will require more remaining in the TCM, and thereby increasee the energy storage time. 2. SELF-POWER The main power in a self-powered relay comes from the passing through primary current in transformatiot on center itself. The primary current for feeding the center, besides being measured, is used for obtaining energy to feed the protection relays. This forces inn the other hand, to self-powered protection relays have very low power consumption, so that is not reflected on the line, and thus, the functionality of the equipment may not be as extensive as desired. Fig5.. Self powered relay In this case there are two types of self-powering g: 2.1. Different CTs for measuring and powering: In this case, we have two different cores with different constituent materials. Separating the core allows the relay to be operative with really low primary current levels. Currently, protection relays are getting supply current values of 5 amp single phase primary. In contrast, these devices have the disadvantage that in centers with high primary current levels, the relay must m evacuate more current. Finally it is noteworthy that the CT are specific and must be tuned to protection. Fig 6. Doble core CT for measuring and powering Unique CTs for measuring and powering: In this type of equipment, power comes from standard type CT /1 or /5. In a general way, are considered to be started (it means, be operative), with a level of single phase 0..2xIn. That is, if for example we have a CT 100/1, the relay will be operative from 20 primary amps. In this type of relays the CTs are standard and its only consideration is that a they should have sufficient VA to ensure protection startup. In any case,, this level is not excessive, 2VA usually sufficient, since the protection suits its internal load to passing through current. In the case of using standard CT /1 or /5, it was reported that should provide enough VA to feed the self-powered d protection relay. This also contributes to design relays that provide low resistance to the CT, it means, they charge little to the CT in order to have a technically and economically viable selection. It should be recalled in this section that in self-powered relays is very important to have separate internal power transformer for each phase. In a lot of relays there are savings in this point, grouping several feedings onn the same transformer. This means ncreasing significantly the single-phase starting level, because if you wire the t rest of the circuit, it will cause current circulation that will increase the startup level. Fig 7. Standardd CTs /1 or / / 5

4 In addition to the current powering is normal to have other supplies, which are considered secondary, but they have their importance: Alternate power supply. As being a transformation center is normal to have low voltage. The great advantage of including auxiliary voltage on self-powered relays is that if you have very resistive faults, below 0.2xIn, it is likely that the voltage is not compromised, and thus ensure the trip. Also in telecontrolled centers, powering the protection with auxiliary supply guarantees to have control and management of alarms, even when the passing through current is zero (especially at night or weekends). This is, if auxiliary power supply is guaranteed, this option allows to get lower tripping times. Direct power supply. There are models that have direct power at 24 Vdc. At first sight it seems not to have sense to fit self-powered protections with DC power supplies, but we'll see it has. There are centers that remote management is given by sms systems, and for them there is a small remote that is supplied with these DC levels. Certainly there are protection relays that operate at 24 Vdc, but the difference between a normal and a self-powered relay is consumption. Self-powered relays, operating at 24Vdc consume 20 times less than a normal relay. Also if the battery completely run out of energy, a self-powered relay will keep on tripping and a normal relay will not. Battery power supply. The KitCom is an adapter that allows to feed SIA relays from the front communication port, allowing also to communicate with the relay locally via RS232. Fig 9. Kitcom. 12 Vdc battery supply. The power comes from two AA batteries of 1.5 voltios, located at the bottom of it. The adapter has a small Dc/Dc source that increase the voltage to 12 Vdc required to operate the equipment. It is also worth mentioning the possibility of doing a test to the self-powered relays before putting then ON, to check the proper functioning of the hardware of the relay. Therefore, it is possible to feed the relays with the KitCom battery to access the relay test menu. This, coupled with the possibility of activating the trip contact from the test menu, allows verification of the trip circuit prior to the energization of the transformation center. 4 / 5

5 3. TRIPPING TIME The tripping time is very dependent on the available energy, and how it is designedd the self-powered relay. The energy available to power the relay will alloww to charge the tripping capacitorss in more or less time and, obviously, the sooner the capacitors are charged, the lower trip times. So, working on starting current values (0.2xIn),, the trip canbe delayed a second, while these times are going to be falling fastly while increasing passing through current. Thus, at rated current, this time may be 200 milliseconds, and reaches down to 60 milliseconds with three times the rated current. Logically, if the energy level required is lower, especially because it uses less power striker, these times may be lower. Also consider if the current is three-phase, reducing overall timee in half. Therefore, in a self-powered equipment if a fault occurs during service, the trip times are exactly the same as conventional equipment. So when you set the time of trip is done from the t worst of conditions, itt means, with the relay switched off. The starting time of the electronic is the other part to consider at the time of tripping. A relay in its normal boot sequence can take a considerable time in management and adjustments checking, and therefore self-powered relays have different boot sequences. In general, with low currents, start time is blurred with the energy needs of the trip, and in the other side, with high currents, where tripping energyy is abundant, the tripping time is marked by the startt of the electronic. This leads to design self-powered relays withh differentiated processors accordingg to their starting gear. The consideredd "normal start up" and considered "fast start up", being the t second ones the ones that get the reduction of the tripping times, adding of the boot time of the electronics and the time of accumulation of energy to make a right trip. In the following table can be seen different tripping times of the self-powered equipment /5, with different values of single phase and three phase currents SIAC5 Tiripping time (ms) Time (ms) dual power Time (ms) 3Phase self power & FastModel Time (ms) 3Phase self power Time (ms) 1Phase self power & FastModel Time (ms) 1Phase self power 0, , , x In / 5

6 FANOX ELECTRONIC, S.L. Parque Tecnológico de Bizkaia, Edificio 604 ES Derio SPAIN

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Dual Power. Protection. Protection

Dual Power. Protection. Protection 54 Fault Clearing Systems by Damien Tholomier., AREVA T&D Automation, Canada Dual Power Single Battery What if it? Short circuits and other abnormal power system conditions are very rear, but may result

More information

REVISION HISTORY REVISION HISTORY

REVISION HISTORY REVISION HISTORY FILTER CONTROLLER REVISION HISTORY Filter Flush Controller forms part of the Netafim range of filtration controllers all designed to make filteration more reliable and economical.. Contact any of the Netafim

More information

Transformer Protection

Transformer Protection Transformer Protection Course No: E01-006 Credit: 1 PDH Andre LeBleu, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 info@cedengineering.com

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C s Guide for Primary Injection Testing WL Circuit Breakers Document No. : 11-C-9036-00 Before Beginning... Qualified Person Siemens type WL circuit breakers should only be only be operated, inspected, and

More information

M.V. LIMITING FUSE WITH THERMAL PROTECTION

M.V. LIMITING FUSE WITH THERMAL PROTECTION M.V. LIMITING FUSE WITH THERMAL PROTECTION 1 INDEX 1.- Why Limiting Fuses? 2.- When does those situations happen? 3.- Market Solutions 4.- MERLIN GERIN Thermal Protection 5.- Technical, economical and

More information

Tolerance-Based Time-Current Coordination

Tolerance-Based Time-Current Coordination S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Tolerance-Based Time-Current Coordination Table of Contents Section Page Section Page Overview Background....

More information

Burns & McDonnell ISU Senior Design Project 2010/2011

Burns & McDonnell ISU Senior Design Project 2010/2011 Burns & McDonnell ISU Senior Design Project 2010/2011 STATION DATA BY BTJ DATE 02/04/2013 SHEET 1 OF 10 PROTECTION AND MEASUREMENTS EQUIPMENT SPECIFICATIONS PROJECT SCOPE New substation installaton. Add

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

TIME REQUIREMENT GUIDE (TRG)

TIME REQUIREMENT GUIDE (TRG) CAT SWITCHGEAR TIME REQUIREMENT GUIDE (TRG) This warranty repair time requirement guide is designed to: Provide detailed guidance on troubleshooting Determine possible solutions Guide the technician to

More information

Application Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS

Application Note RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS Application Note GET-8558 RESIDUAL BUS MAIN-TIE-MAIN AUTOMATIC TRANSFER SCHEME USING THREE GE 850 RELAYS REVISION 01 March 17 th, 2016 1 INDEX 1. INTRODUCTION 4 2. RELAY ORDER CODE 5 3. RELAY IO CONNECTIONS

More information

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Mining The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions Reprint Authors: Kurt Tischler Siemens AG, Mining Technologies, Erlangen, Germany Reprint: WORKSHOP SAG

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any

Application Note. First trip test. A circuit breaker spends most of its lifetime conducting current without any Application Note First trip test A circuit breaker spends most of its lifetime conducting current without any operation. Once the protective relay detects a problem, the breaker that was idle for maybe

More information

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers 2 Introduction This discussion describes in detail retrofitting medium voltage circuit

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism R-MAG Features: Low maintenance 10,000 mechanical operations (five times ANSI requirements) Simple magnetic actuator Vacuum interruption Definite

More information

Tattletale Annunciators and Magnetic Switches

Tattletale Annunciators and Magnetic Switches Tattletale Annunciators and Magnetic Switches Tattletale annunciators and magnetic switches are the nerve centers that translate Swichgage contact operations into decisions and operate the alarm or shutdown

More information

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A - 3700 A R-MAG The R-MAG is truly the next generation in vacuum circuit breakers, combining industry recognized magnetic

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION Instruction Bulletin Bulletin No. 44027-017-01 Middletown, OH USA Class 6035 INTRODUCTION This bulletin contains instructions for adding a shunt trip assembly to a manual DS/DSL circuit breaker and modifying

More information

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00 DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations

More information

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD)

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD) Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD) Schneider Electric RCBO Earth Leakage Circuit Breaker (ELCB) An Earth Leakage Circuit Breaker (ELCB) is a device

More information

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80

Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Application Note: Protection of Medium-Power Motors With SIPROTEC Compact 7SK80 Motor settings using the SIPROTEC Compact motor protection relay 7SK80 is explained below. Information is given on how to

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

Application Engineering Europe

Application Engineering Europe Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers DEH41480 Test Cabinet (Inspection Box) for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers Instructions 1 Table of Contents Section 1. Introduction

More information

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No. September, 1990 Supersedes Descriptive Bulletin 41-100, pages 1-4, dated June, 1989 Mailed to: E, D, C/41-100A Hi-Lo co induction-disc type overcurrent relays are activated when the current in them exceeds

More information

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required! DB 750-205 January 2007 Supercedes: December 2006 Now available with Vacuum Interrupter Monitor VBT Switch 15kV - 69kV VBU-T Switch 69kV - 230kV Longest Life Product for Electric Furnace Applications!

More information

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12 16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting

More information

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2 Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2 Table of Contents 1 Introduction... 4 2 Description of retrofit circuit-breaker 8DN8... 5 3 Technical data for retrofit circuit-breaker

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications ABB a global leader ABB is a global leader in power and automation technologies that enable utility and industry customers

More information

PSW102 type CT powered protection unit

PSW102 type CT powered protection unit PSW102 type CT powered protection unit Summary PSW102CT self-powered protection device is a 10Kv feeder protection device which has the function of over current, fast breaking protection and grounding

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers The National Electrical Code makes the following statement regarding ground fault conformance testing:

More information

RAPTOR DEFAULT TEST TEMPLATES

RAPTOR DEFAULT TEST TEMPLATES RAPTOR DEFAULT TEST TEMPLATES www.smcint.com PAGE 1 OF 12 The Raptor Default Test Templates in Raptor HH June 2015 General parts of main screen: TEST TEMPLATES: Default test templates are factory configured

More information

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)

More information

mgard-10 microprocessor-based relay

mgard-10 microprocessor-based relay mgard-10 microprocessor-based relay Ground fault relay mgard-10a mgard-10-a1 mgard-10-a2 C-417EM Instruction Manual, March 2015 ABOUT I-GARD I-Gard s commitment to electrical safety provides both industrial

More information

Control System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G)

Control System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G) Part B, Section 1 This section covers the following unit configurations. Model 3100 3400 3500 Voltage 1, 2 Pump Piston (E, F, or G) Manifold 4-Port (A) 6-Port (B or C) Control UniScan (1) B 1-0 B 1-1 Section

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

Grounding Of Standby & Emergency Power Systems

Grounding Of Standby & Emergency Power Systems July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY Reso-not TM Damping System XCITE Owner s Manual 1502C HYDRAULIC POWER SUPPLY Xcite Systems Corporation 675 Cincinnati RDS Batavia - 1 Pike Cincinnati, Ohio 45245 Tel: (239) 980-9093 Fax: (239) 985-0074

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls UNIT OBJECTIVES After studying this unit, the reader should be able to Describe and identify power- and non-power-consuming Describe

More information

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products Station Automation & Protection Inverse-Time Overcurrent & /F Relays Type ICM, ICM B ABB Substation Automation Products Features the driving solenoid has tappings, corresponding to the seven stages of

More information

400/230 Volt 60Hz UPS Power

400/230 Volt 60Hz UPS Power olt 60Hz Power Using ual Voltage standby generation and in one Nothing protects quite like Piller www.piller.com Contents 1 Abstract...3 2 Introduction...4 3 Alternative Power istribution...6 4 Integrating

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies

Appendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies Engineering Studies Coordination Study Every 5 years and in conjunction with electrical system modifications. Short Circuit Study NETA MTS 6.2 Every 5 years and in conjunction with electrical system modifications.

More information

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy ETAP 17 Goodyear, Suite 100 Irvine, CA 92618 White Paper No.001.14-2016 Albert Marroquin, PE Member

More information

Application Note CTAN #127

Application Note CTAN #127 Application Note CTAN #127 Guidelines and Considerations for Common Bus Connection of AC Drives An important advantage of AC drives with a fixed DC is the ability to connect the es together so that energy

More information

Braking Devices BR 230/ Assembly- and Commissioning Instructions

Braking Devices BR 230/ Assembly- and Commissioning Instructions electronic Braking Devices BR 230/400-10...400 Assembly- and Commissioning Instructions Quality is our Drive. BR 230/400-10...400 1 as per 04/10 11600.10001 Table of Contents Page 1. Safety notes 3 2.

More information

Functions provided by measuring relays in railway equipment

Functions provided by measuring relays in railway equipment Functions provided by measuring relays in railway equipment 1-Current relays -Minimum current relays (During normal operation, if the current is present these relays are in operating position and switch

More information

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Document Requirements for Engineering Review PV Systems v1.0 6/9/2017 Outlined below are the documents and associated minimum details required for Engineering Review of Distributed Energy Resources Interconnection

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

Close-Open (Short-Circuit) Time Results Interpretation

Close-Open (Short-Circuit) Time Results Interpretation Application Note Close-Open (Short-Circuit) Time Results Interpretation Close-Open (C-O, trip-free) cycles simulate closing on a short circuit. In the actual event, the breaker closes first, then the protection

More information

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards Robert P. Hansen, P.E., PhD GE Specification Engineer Introduction Switchboards are a widely used type of equipment

More information

Reference Number PDS 18 - (RIC Standard: EP SP)

Reference Number PDS 18 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Reference Number PDS 18 - (RIC Standard: EP 06 00 00 01 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Jan 05 Standards

More information

CI-TI Contactors - VLT Frequency Converters

CI-TI Contactors - VLT Frequency Converters MN.90.K1.02 - VLT is a registered Danfoss trademark 1 Description This data sheet is based on tests made in co-operation with Contactor Business from Danfoss Automatic Division and Danfoss Drives A/S.

More information

Technical information No. 01. IT systems. The basis for reliable power supply

Technical information No. 01. IT systems. The basis for reliable power supply IT systems The basis for reliable power supply FA01en/01.2004 IT systems The basis for reliable power supply in critical areas The advantages of sophisticated industrial systems can only be of use, if

More information

GP/GPA GROUND FAULT PROTECTION

GP/GPA GROUND FAULT PROTECTION GP/GPA GROUND FAULT PROTECTION GROUND FAULT PROTECTION C-220EM Instruction Manual, June 2015 ABOUT I-GARD I-Gard s commitment to electrical safety provides both industrial and commercial customers with

More information

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay 41-106E Type CO-4 Step-Time Overcurrent Relay A core screw accessible from the top of the switch provides the adjustable pickup range. The IIT contacts are connected in the trip circuit to trip instantaneously.

More information

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

N Daily Weekly Monthly Every 3 months. Every 6 months 1 Remove any materials not related

N Daily Weekly Monthly Every 3 months. Every 6 months 1 Remove any materials not related MV / LV cabins maintenance The operation and maintenance of the cabins are meant to ensure high reliability (i.e. the early detection of anomalies, the failure prevention and monitoring functional) and

More information

Pressure Makeup Jockey Pump Controller

Pressure Makeup Jockey Pump Controller Hubbell Industrial Controls, Inc. A subsidiary of Hubbell Incorporated 4301 Cheyenne Dr. Archdale, NC 27263 Telephone (336) 434-2800 FAX (336) 434-2803 Instruction Manual Pressure Makeup Jockey Pump Controller

More information

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module. Instruction manual Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module Installation operation maintenance E50001-F710-K378-V6-4A00 www.usa.siemens.com/sdv7 Hazardous voltages and stored

More information

OPERATOR TROUBLESHOOTING GUIDE

OPERATOR TROUBLESHOOTING GUIDE OPERATOR TROUBLESHOOTING GUIDE ABOUT THE TROUBLESHOOTING GUIDE This document is provided for the use of qualified operator installers. The installer should familiarize themselves with this guide Options

More information

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus: 1.0 Introduction: This probe is designed to provide an additional help to automotive technicians in trouble shooting of electrical circuits problems in the car. Apart from using the normal multi tester,

More information

Type SOQ Negative Sequence Time Overcurrent Relay

Type SOQ Negative Sequence Time Overcurrent Relay ABB Power T&D Company Inc. Power Automation & Protection Division Coral Springs, FL Allentown, PA April 1998 Supersedes DB dated August 1991 Mailed to: E,D, C/41-100B For Protection of Rotating Machinery

More information

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION ABB Effective: November 1990 This Addendum Supersedes all Previous Addenda Addendum to Instruction Leaflet 41-137.3H Type KRD-4 Directional Overcurrent Ground Relay A - Add New Information C - Change Existing

More information

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

That s how compact transformer protection is today. The customer newsletter of Kries-Energietechnik

That s how compact transformer protection is today. The customer newsletter of Kries-Energietechnik The customer newsletter of Kries-Energietechnik www.kries.com A change of paradigm in distribution network transformer protection: the self-powered and IEC 60255-compliant IKI-35 protection relay 05 17

More information

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker IL 33-LGH-1 Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker SAFETY PRECAUTIONS WARNING POWER CIRCUIT BREAKERS ARE EQUIPPED WITH HIGH SPEED, HIGH ENERGY OPERATING MECHANISMS. THE

More information

Deep Sea Electronics Plc

Deep Sea Electronics Plc Deep Sea Electronics Plc 5120 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL Author: Anthony Manton Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH England Tel: +44 (0) 1723

More information

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 47681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC COMPLEX SOLUTIONS MADE SIMPLE. DEEP SEA ELECTRONICS PLC DSE5110 AUTOSTART CONTROL MODULE OPERATING MANUAL Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44

More information

Motor Protection. Voltage Unbalance & Single-Phasing

Motor Protection. Voltage Unbalance & Single-Phasing For Summary of Suggestions to Protect Three-Phase Motors Against Single-Phasing see the end of this section, page 137. Historically, the causes of motor failure can be attributed to: Overloads 30% Contaminants

More information

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls 11kV Compact Switchgear tec - range Minimum to Zero SF6 Insulation Gas. Outec Controls 1 tec xx - 11kV Switchgear Contents 1 tec CB - SF6 Free Switchgear... 3 1.1 Description:... 3 1.2 1.3 Features the

More information

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B Inverse-Time Overcurrent & E/F Relays Type ICM 21, ICM 21B ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve

More information

APPLICATION NOTES DELOMATIC

APPLICATION NOTES DELOMATIC APPLICATION NOTES DELOMATIC 400 Safety system Document no.: 4189340885B SW version 1.33.3 or later Table of contents 1. ABOUT THIS DOCUMENT... 3 GENERAL PURPOSE... 3 INTENDED USERS... 3 CONTENTS/OVERALL

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

CP Automatic capacitor bank

CP Automatic capacitor bank CP 254 - Automatic capacitor bank STE-CP254_V2_général.doc Page 1 CP 254 - General presentation CP 254 is a range of MV capacitor banks designed to be used in electrical networks up to 36kV. The capacitor

More information

Advanced Protective Relay Training

Advanced Protective Relay Training Advanced Protective Relay Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq A properly designed protection

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 47681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,

More information

Flight Systems. Replacement for KASSEC DESCRIPTION

Flight Systems.   Replacement for KASSEC DESCRIPTION DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 473681 Vari-Green Motor and Controls Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble,

More information

Unit Protection System for Pumped-Storage Power Stations

Unit Protection System for Pumped-Storage Power Stations Unit Protection System for Pumped-Storage Power Stations 1. Introduction In many power systems, pumped-storage power stations are used in addition to run-of-river power stations. These power stations serve

More information

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech The Axpert-CSS is a range of Combination Soft Starter panels offered by AMTECH DRIVES. We also offer the module unit as an individual product, named as Axpert-Opti torque Soft Starter. This is only the

More information

Solid Dielectric, Single Phase Recloser

Solid Dielectric, Single Phase Recloser Solid Dielectric, Single Phase Recloser Catalog O-vsp17 Viper-SP Viper-SP solid dielectric, single phase recloser combines the time-proven reliability of electronically controlled, vacuum fault interrupters

More information