1 S&C Switch Operators - Type AS-1A For nstallation TABLE OF CONTENTS Section Page Number NTRODUCTON... 1 SAFETY NFORMATON LJnderst,anding Safety-Alert Messages Following Safety nstructions... 4 Replacement nstructions and Labels NSTALLATON... 5 MANUALOPERATON... 8 ADJUSTMENTS Section Page Number NSPECTON SCHEDCLE AND PROCEDURES CHECKNG SWTCH OPERATOR AND ALD~~T-RLPTER@ SWTCH POSTONS APPENDX Amended Travel-Limit AGustment Procedure for Switch Operators Furnished with Source-Transfer Control Compatibility NTRODUCTON Qualified Persons 1 A ' The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of overhead electric power distribution equipment along with the associated hazards. A qualified person is one who is trained and competent in: The skills and techniques necessary to distinguish exposed live parts from non-live parts of electrical equipment. The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed. The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment. These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this tme of equipment. The S&C Switch Operator--?Srpe AS-A is a high-speed operator, with an operating time not exceeding,75 second. t is expressly designed for power operation of S&C Alduti-Rupter Switches-Outdoor Distribution and S&C Alduti-Rupter Switches with Power Fuses-Outdoor Distribution, having rotating type operating mechanisms. The high operating speed of the S&C Switch Operator-me AS-1A provides sufficient moving-contact velocity in the Alduti-Rupter Switch interrupters to ensure full interrupting capability and long operating life. The operator's high operating speed also provides adequate closing velocity for 25/34.5-kv and 34.5-kv Three-Pole Side-Break nteger Style and Three-Pole Vertical-Break nteger Style switches such that the Side-Break nteger Style switches have a one-time duty-cycle fault-closing rating of 15,000 amperes rms asymmetrical, and the Vertical-Break nteger Style switches have one-time duty-cycle fault-closing ratings of 20,000 or 30,000 amperes rms asymmetrical for switches rated 600 amperes or 1200 amperes, respectively. power For operation of S&C Alduti-Rupter Switches-Outdoor Distribution and S&C Alduti-Rupter Switches with Power Fuses-Outdoor Distribution, having reciprocating type operating mechanisms, the S&C Switch Operator-me AS-0 is offered. Supersedes lnstructlon Sheet dated NSTRUCTON SHEET ELECTRC S&C COMPANY Page Chicago 1 of 23 LTD. CANADA ELECTRC S&C Toronto

2 S&C Switch Operators - Type AS- A NTRODUCTON -Continued For power operation of S&C (lircuit-switchers, S&C Switch Operators-Qpes CS-1A and CS-10 are available. For power operation of S&C Line-Ruptersrbl, the S&C Switch Operator--Type LS-2 is available. For switches of other manufacture, the S&C, Switch Operator-Qpe LS-1 is available. The LS-1 is a low-speed operator, with an operating time of 4 to 7 seconds. t is designed for power operation of outdoor high-voltage disconnects and interrupter switches for which this low operating speed is appropriate. S&C Switch Operators--Type AS-1A include the following features as standard: 0 Built-in internal decoupling mechanism, operable by integral external selector handle, with padlocking provisions and automatic mechanical locking of output shaft. Laminated safety-plate window permits "bisible air-gap" verification of complete disengagement of output shaft. Open-close pushbuttons, externally operable, with padlockable cover. Built-in nonremovable, foldaway manual operating handle. Mechanical position indicators for both switch operator and Alduti-Rupter Switch "open" and "closed" positions. Non-reset electric operation counter. Laminated safety-plate window for inspection of built- in internal decoupling mechanism, mechanical position indicators, and operation counter (and position-indicating lamps, if furnished as accessories). Foolproof recoupling. mpossible with position-indexing drums to couple the switch operator and the Alduti-Rupter Switch "unsynchronized." Fingertip precision adjustment of output-shaft rotation using self-locking spring-biased cams. Eight-pole auxiliary switch, coupled to motor, with fingertip precision adjustnwnt of individual contacts using self-locking spring-biased cams. Antifriction bearings throughout; tapered roller bearings for all high-torque gear-train shafts. Two-pole pull-out fuseholders for space heater and (except for 12-volt dc models) motor circuit. (For lholt dc models, a two-pole disconnect switch is used in series with a motor-circuit, fuse.) Weatherproof, dustproof enclosure. equipped with 120/240-volt ac space heater, factory-connected for 240-volt ac operation. Can readily be field reconnected for 120-volt ac operation. Tamper-resistant design-welded enclosure; baffled louvers; gasketed. flanged door openings; camaction door latch; provisions for padlocking. Foul-weather accessibility t,o interior of enclosure. Access is by door rather than by removal of entire enclosure. SWTCH OPERATORS-Type AS-1A Application Rating of High-Voltage Device High-Voltage Device Motor and Control Voltage Maximum Operating Time, Accelerating M~~~~or',"u"e""a:'. Rated Control Current, Voltage, nch-lbs. Amperes Catalog Number Schematic Wiring Diagram Drawing Number NSTRUCTON SHEET Page 2 of 23 COMPANY ELECTRC S&C S&C CANADA ELECTRC Chicago LTD. Toronto

3 ~~~ ~ ~~ NTRODUCTON -Continued S&C, Operator Switch Catalog Number 38854R4 suffix Voltage includes a 12-volt dc battery and constant-burden battery charger for connection to an S&C 30-Volt-Ampere Potential Device or other 120-volt 60-hertz source. -A dc 48 volts -B 125 volts dc -D 115 volts 60 hertz Switch operator catalog numbers are suffixed one with -E 230 volts 60 hertz or more letters. The first letter following the catalog number designates the motor and control voltage (except Other suffix letters which may be added to the switch for Catalog Number 38854R4): operator catalog number indicate the inclusion of optional accessories as follows: ACCESSORES tem Suffix Added to Switch Operator Catalog Number Deletlon of Externally Operable Open-Close Pushbuttons -J Space Heater Thermostat -K Key nterlock wlth Switch, locks Aldutl-Rupter Swttch open and dlsconnects motor-control clrcult@ -L Posltlon-ndicating Lamps (one red, one green), mounted lnslde the enclosure Extra Auxihary Swltch (ndlvldually adjustable contacts), 4-PST (coupled to motor)@@ -Q Source-Transfer Control Compatibility Permlts use of swltch operator wlth S&C Mlcro-AT Source-Transfer Control in Weatherproof Enclosure@@ - Duplex Receptacle and Conventence-Light Lampholder wlth Swltch -V Extra Auxlhary Switch (indivldually adpstable contacts), 8-PST (coupled to Aldutl-Rupter Switch)@ -W Remote-Control Blocking Swltch, prevents remote operation of swltch operator when the protectwe cover for the externally mounted open-close pushbuttons S open@ Extra Auxthary Swltch (mdlvldually adlustable contacts), 12-PST (coupled to Aldutl-Rupter Switch)@ - 0 Qpe ASA Swltch Operators speclfied wlth source-transfer Avadable as an optional accessory only w~th Type AS-1A Switch trol compatlbllity (suffix -U1 ) cannot be furnished wlth key inter- Operator Catalog Numbers 38847R4-D and 3884iR4-E. utilizlng 115-volt lock wlth switch (suffix -L ), extra auxiliary swltch coupled to motor 60-hertz or 230-volt 60-hertz motor and control voltage (suffix -Q ), or remote-control blockmg swltch (suffix -P Rrqulred for some automatic-transfer and sectionalmng schemes. The 8-PST extra auxiliary swtch (suffix -W ) cannot be furnished if 12-PST verslon (suffix -Z ) S speclfied, and vice versa -u 1-2 NSTRUCTON SHEET COMPANY ELECTRC S&C 3 Page Chicago of 23 LTD. S&C CANADA ELECTRC 22, April Toronto 1996

4 S&C Switch Operators - Type AS-A SAFETY NFORMATON Understanding Safety-Alert Messages There are several types of safety-alert messages which may appear throughout this instruction sheet as well as on labels and tags attached to the bpe ASA Switch Operat,or. Familiarize yourself with these types of messages and the importance of the various signal words, as explained below. Following Safety nstructions Thoroughly and carefully read this instruction sheet before installing your S&C Type AS-1A Switch Operator. hazards which will likely result in serious personal injury or death if instructions, including recomnwnded instruct,ions, including recommended precautions, are which cm result in minor personal injury or product or property damage if instructions, including recom- f you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor, or call S&C Headquarters at (312) , Monday through Friday between 8:30 AM and 5:OO PM Central Standard Time. (n C,anada, call S&C Electric Canada at (416) ) Replacement nstructions and Labels f you need additional copies of this instruction sheet, contact your nearest S&C Sales Office or S&C Authorized Distributor, or call S&C Headquarters. t is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C, Aut,horized Distributor, S&C Headquarters, or S&C Electric Canada. ments that, if not followed, can result in product or property damage if instructions are not followed NSTRUCTON SHEET Page 4 of 23 COMPANY ELECTRC S&C LTD. CANADA ELECTRC S&C Chicago Toronto

5 Step 1 Mount the switch operator as indicated on the erection drawing. Then attach a flexible coupling to the output shaft of the switch operator. See Figure 1. Thread the attachment bolts through the flexible coupling plate and through the coupling flange on the output shaft. Tighten the bolts to draw the flexible plate flush against the flange; this will deform the threads in the flexible plate, resulting in a binding, nonslip connection. nstall and tighten the self-locking nuts. Do not use lockwashers with the flexible coupling attachment bolts. Remove the clamp bolts and set aside the detachable half of the flexible coupling. Attachment bolt Vertical operating pipe \ Flexible couplino \. -.. mi,..ri..r..a+ C..,...,C Clamp bolts Alduti-Rupter switch position indicators Alignment arrow Coupling flange Self-locking nut A Manual operating Pushbutton / protective cover / \ Switch operator nameplate Figure 1. txterlor view 01 Swncn operaror. S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto NSTRUCTON SHEET () Page 5 of 23

6 S&C Switch Operators - Type AS-A NSTALLATON - Continued Step 2 Make certain that the cutting tips of the piercing set screws do not protrude through (1) the body of the flexible coupling on the switch operator output shaft and (2) the body of the universal coupling and thrust bearing at the upper guide bearing and universal coupling groups (or the body of the rigid coupling if an intermediate guide bearing assembly is used). Pass the lowest section of vertical operating pipe up through the guide bearing and then through the thrust bearing and insert the pipe section into the universal coupling (or, if an intermediate guide bearing assembly is used, pass the vertical-operating-pipe section up through the guide bearing and insert the pipe section into the rigid coupling). Do not tighten the coupling clamp or piercing set screw at this time. (The lower end of the lowest section of vertical operating pipe will, of course, be cradled in the open flexible coupling attached to the output shaft of the switch operator.) While holding the pipe section in this position, and with the thrust bearing resting on the guide bearing, tighten the piercing set screw in the thrust bearing, piercing the pipe, and continue turning until a firm resistance is felt. At the universal coupling, tighten the clamp bolt to final tightness, then tighten the associated piercing set screw, piercing the pipe, and continue turning until a firm resistance is felt. (f an intermediate guide bearing assembly is used, tighten the clamp bolt on the rigid coupling to permanent tightness; then tighten the associated piercing set screw, piercing the pipe, and continue turning until a firm resistance is felt.) Pushbutton protective cover (open) Operation counter (optional on earlier models) Remote-control blocking switch (Catalog Number Suffix -Y ) Open/close pushbuttons Extra auxilliary switch, 8-PST (Catalog Number Suffix W ); 12-PST version (Catalog Number Suffix -Z ) is similar Arrow plate Position-indexing drums (not visible in photo) -Auxiliary switch, 8-PST - Extra auxiliary switch, 4-PST (Catalog Number Suffix -Q ) Motor contactor, opening Motor-circuit two-pole pull-out fuseholder Motor contactor,/ closing igure 2. nterior views of switch operator. P Conduit-entrance plate Manual operating handle interlock switch and mechanical blocking rods Page 6 of 23 NSTRUCTON SHEET S&C ELECTRC COMPANY Chicago - S&C ELECTRC CANADA LTD. Toronto!m

7 NSTALLATON - Continued Step 3 Mark the conduit-entrance location for the control-circuit wiring on the conduit-entrance plate in the bottom of the switch operator enclosure. See Figure 2. Remove the conduit-entrance plate and cut out the required opening. Replace the plate and make up the entrance fittings. Apply sealing compound (provided with each switch operator) when replacing the conduitentrance plate. Verify that the entrance fittings are properly sealed to prevent water ingress. Step 4 two-pole pull-out fuseholders for the motor circuit and space-heater circuit. See Figure 2. Failure to remove these fuseholders can result in accidental energizing of the operator after the external connections have been completed. Reinsert the fuseholders only when directed to do so in the steps that follow. Remove the blocking from the motor contactors. Connect the external control-circuit wiring (including space-heater source leads) to the terminal blocks of the switch operator in accordance with the wiring diagram furnished. For 12-volt dc models, mount the battery in the battery compartment and connect it to the battery cables which are located at the rear of the battery compartment. Pushbutton protective cover (close uplex receptacle and convenienceght lampholder with switch (Catalog umber Suffix -V) tstructions, switch operator.avel-limit adjustment Motor, Brake-release solenoid \ Tel*minal block nstruction manual and holden Door latch -- Spare fuses (6)A Filter holder/- Space-heater circuilt two-pole pull-out fuseholder \ Space heater These illustrations are not applicable to 12-volt dc models. Those models utilize a number of different component parts and a different internal layout. Among the differences is inclusion of a constant-burden battery charger mounted on a swingout panel, as well as the use of a separate two-pole control-source disconnect switch in series with control-source fuses (located on the inside rear wall) in lieu of the motor-circuit twooole pull-out fuseholder. Those modsls, further, include a separate comoartment beneath the enclosure, Nhich houses the 12-volt dc battery. NSTRUCTON SHEET 76&5()0 S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto Page 7 of 23

8 S&C Switch Operators - Type AS-1A NSTALLATON - Continued Direct-current switch operators are furnished with polarity-sensitive motors. Observe the polarities indicated on the wiring diagram for switch operator motor when making external control-circuit connections. requirements, as specified in S&C Data Bulletin and on the switch operator wiring diagram furnished. Do not make unauthorized changes in the wiring of this switch operator. Unauthorized changes may result in equipment damage or personal injury. To make a control-circuit modification, request a revised wiring diagram from S&C Electric Company. Diagram must meet with the approval of both the user and S&C Electric Company. 1 MANUAL OPERATON 1 Before proceeding further, familiarize yourself with the operation of the manual operating handle and the selector handle, as described on the switch operator nameplate on the right-hand side of the enclosure and in the following Steps 5, 6, and 7. See Figures 3 and 4. Piercing set screws Flexible Coupling Manual ooeratina handle J) Latch knob/ Vertical operating pipe-,_._ (in coupled position) Switch operator nameplate Page 8 of 23 NSTRUCTON SHEET S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto

9 1 MANUAL OPERATON -Continued 1 Do not manually open or close the switch operator while the Alduti-Rupter Switch is energized. Operating the switch under reduced operating speed may cause excessive arcing, resulting in shortened interrupter life, or damage to the interrupters. f switch operator control voltage is not available and emergency manual opening is absolutely required, crank the manual operating handle rapidly throughout its full travel. Do not stop or hesitate part way. To avoid closing into a fault, never close the switch manually. Step 5 To operate manually: Pull the latch knob on the hub of the manual operating handle and pivot the handle forward slightly from its storage position. Release the latch knob while continuing to pivot the handle forward to lock it into the cranking position. See Figure 3. (As the handle is pivoted forward the motor brake is mechanically released, both leads of the control source are automatically disconnected, and-except for 12-volt de models-both the opening and closing motor contactors are mechanically blocked in the open position.) f desired, during manual operation, the switch operator may also be disconnected from the control source by removing the motor-circuit two-pole pull-out fuseholder, located on the right-hand inside wall of the enclosure. To return the manual operating handle to its storage position, pull the latch knob and pivot the handle approximately 90 degrees. The handle will then be disengaged from the switch operator and may be rotated freely in either direction to its storage position. Complete the handle storage by pivoting the operating handle backward approximately 90 degrees until it latches in the storage position. Note that the manual operating handle may be disengaged from the switch operator mechanism at any position of the handle. Always padlock the handle in its storage position. operated either manually or electrically without operating the Alduti-Rupter Switch. When the selector handle is in the decoupled position, the output shaft is prevented from moving by a mechanical locking device located within the switch operator enclosure. During the intermediate segment of the selector handle travel, which includes the position at which actual disengagement (or engagement) of the internal decoupling mechanism occurs, the motorcircuit source leads are momentarily disconnected and (except for 12-volt de models) both the opening and closing motor contactors are mechanically blocked in the open position. Visual inspection, through the observation window, will verify whether the internal decoupling mechanism is in the coupled or decoupled position. See Figure 5. Padlock the selector handle in-either position. Selector handle (being turned to decoupled position) Lpcking tabs Step 6 To decouple: The integral external selector handle, for operation of the built-in internal decoupling mechanism, is located on the right-hand side of the switch operator enclosure. See Figure 3. Swing the selector handle upright and slowly rotate it clockwise 50 degrees to the decoupled position. See Figure 4. This decouples the switch operator mechanism from the switch operator output shaft. Then lower the selector handle to engage the locking tab. When thus decoupled, the switch operator may be Figure 4. Selector handle operation. Decoupled NSTRUCTON SHEET S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto Page 9 of 23

10 S&C Switch Operators - Type AS-A MANUAL OPERATON - Continued Step 7 To couple: Manually operate the switch operator to bring it to the same position (open or closed) as the Alduti- Rupter Switch. The switch operator position indicator, seen through the observation window, will show when the approximate open or closed position has been attained. See Figure 5. (The position indicator for the Alduti-Rupter Switch, located on the output-shaft collar of the switch operator, will be aligned later.) To move the switch operator to the exact position for coupling, turn the manual operating handle slowly until the position-indexing drums are numerically aligned. Then swing the selector handle upright and rotate it counterclockwise to the coupled position. Lower the handle to engage the locking tab. The selector handle is now in the coupled position. 1 ADJUSTMENTS Remove the two-pole pull-out fuseholders for the motor circuit and space-heater circuit. See Figure 2. Failure to remove fuseholders can result in accidental energizing of the operator after the external connections have been completed. Reinsert fuseholders only when directed to do so in the steps that follow. Make certain that the main contacts on all three switch poles are fully closed and, where applicable, the switch toggle mechanisms are in an overtoggle position against their respective closed stops. Refer to the instruction sheet furnished with the Alduti-Rupter Switch. With the selector handle in the coupled position, manually crank the switch operator to the fully closed position, as indicated by the switch operator position indicator. See Figure 5. At the switch operator output shaft, replace the detachable portion of the coupling clamp. Make certain that the cutting tips of the piercing set screws do not protrude through the body of the coupling. Torque the flexible coupling clamp bolts equally to fmal tightness so that the clamp pulls down evenly on the vertical-operating-pipe section. Then tighten the associated piercing set screws, piercing the pipe, and continue turning until a firm resistance is felt. See Figure 3. Step 9 With the selector handle in the coupled position, crank the Alduti-Rupter Switch to the fully open position, then to the fully closed position, and in each position accurately align the switch position indicators on the outputshaft collar of the switch operator with the alignment arrow below. See Figure 1. Each Alduti-Rupter Switch position indicator can be shifted after loosening the hexhead screws which fasten it to the output-shaft collar. Tighten these screws after making the above alignments. For Type AS-A Switch Operators furnished with Source-Transfer Control Compatibility instead, follow the step-by-step procedure out- Position-indicating lamps (Catalog Number Suffix -Ml ) \ w nternal decoupling mechanism (in decoupled tion) / m Operation d-22,/ counter Arrow plate i Position-indexing drums / position indicators gure 5. Views of switch operator through observation windo\ Page 10 of 23 April 22,1996 NSTRUCTON SHEET \ Selprtnr hnnrib (in decoupled position) L nternal decoupling mechanism (in coupled position) S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto

11 Step 10 The cranking direction to close the Alduti-Rupter Switch is indicated by an arrow plate located near the hub of the manual operating handle. See Figure 5. This direction is normally predetermined from the erection drawing for the specific installation and factory set accordingly. The direction of rotation of the switch operator motor is also normally set at the factory. n the event that the cranking direction required to close the Alduti-Rupter Switch is opposite to that indicated by the arrow plate, remount the arrow plate, exposing its opposite side. (Direction of motor rotation will be checked in Step 12. j advances roller engagement Temporarily mark on the top of the switch operator enclosure the direction in which the output shaft rotates to close the Alduti-Rupter Switch. Step 11 Place the selector handle in the decoupled position in preparation for electrical operation. Step 12 With the manual operating handle in its storage position and the selector handle in the decoupled position, reinsert the motor-circuit fuseholder. Open the pushbutton protective cover* and operate the switch operator by means of the externally mounted Open-Close pushbuttons, if protided, or, in their absence, by momentarily jumpering terminals 1 and 8 to open, and 1 and 9 to c1ose.a Note the direction in which the travel-limit cams rotate when the switch opwa,tor closes. This direction should agree with the temporary direction mark previously made on the top of the enclosure. (As a matter of information, the direction of rotation of the travel-limit cams is always the same as the direction of rotation of the output shaft. j n the event that the direction of rotation of the travellimit cams (as noted above) is opposite to the temporary direction mark previously made on the top of the enclosure, a reversal of the motor direction will be necessary. Remove the motor-circuit fuseholder to avoid accidental oremote energization of the control circuit. nterchange the Sl and S2 motor leads connected to terminals 4 and 5 on the terminal block in the switch operator enclosure. (On 12-volt dc switch operators, interchange the Sl and S2 motor leads connected to the motor terminals.) t should be noted particularly that reversal of the motor direction reverses only the direction of rotation of the output shaft and travel-limit cams. The identity of the opening-stroke and closing-stroke travel-limit cams (which will be adjusted later) will remain unaffected. Step 13 The travel-limit switch (coupled to the motor), which governs the extent of output-shaft rotation in the opening and closing directions, includes two contacts that are operated by cam-actuated rollers. See Figure 6. The cams (upper one is the opening-stroke travel-limit cam; and the one immediately below is the closing-stroke travel-limit cam) are individually adjustable in 4.5-degree increments. Therefore, each cam can be adjusted to advance or retard engagement with its roller and thus open or close the corresponding switch contact, as desired, during motor operation. Advancing a cam to de-energize the corresponding motor contactor earlier and thus decreases the extent of output-shaft rotation. Conversely, retarding a cam retards engagement with its roller to delay de-ener- gization of the corresponding motor contactor and thus increases the extent of output-shaft rotation. The travel-limit cams (aswell as the auxiliary-switch cams) are to be adjusted as directed in Steps 14 through 19 using the following procedure (do not make any aaustments at this time): (a) Remove the motor circuit fuseholder. (b) Raise (or lower) the cam toward its adjacent spring until the cam is separated from the teeth of the inner gear. (c) Rotate the cam to advance or retard engagement with its roller. See Figures 6 and 7. Advance the cam to decrease travel. Retard the cam to increase travel. (d) Lower (or raise) the cam making sure that the teeth are in mesh with the inner gear. Preliminary Adjustment of Travel-Limit Cams Step 14 The adjustments described in this step are necessary only in the event that a reversal of the motor direction was required, as described in Step 12. f such motor reversal was not required, proceed to Step 15. Closing-Stroke Travel-Limit Cam. Place the selector handle in the coupled position. Manually operate the switch operator in the closing direction and observe the closing-stroke travel-limit cam. At the completion of the switch operator closing stroke, the leading edge of the closing-stroke travel-limit cam should be engaged with its associated roller. f the leading edge is not engaged with its roller, adjust the closing-stroke travel-limit cam (as described in Step 13) so that its leading edge touches (or nearly touches) the roller. * For switch operators wlth optional remote-cont,rol blocking switch (sufflx -Y ), opening the pushbutton protective cover prevents remote operatlon of the switch operator A Termmal designations may differ n special wiring dlagrams n such cases, refer to the specific wiring diagram for the correct terminal deslgnatlons. NSTRUCTON SHEET ELECTRC S&C COMPANY Chicago Page 11 of 23 LTD.. CANADA ELECTRC S&C 22, 1996

12 S&C Switch Operators - Type AS-1A 1 ADJUSTMENTS -Continued Switch onerator position indicator Use when direction of output shaft rotation is clockwise to open. Adjacent spring Cxc;g-stroke Aj il Opening-stroke travel-limit cam (n raised posrtion) Opening-stroke d roller Opening-stroketravel-limit 412 cam (with switch operator in / / J fully closed position-raise, - : and turn cam counterclockwise to increase travel of nner gear switch operator) and travel-limit cam Switch operator position indicator Closing-stroke roller Closing-stroke travel-limit cam ii b? Closing-stroke travellimit cam (with switch operator in fully open pcsition-lower and turn cam clockwise to increase travel of switch operator) Use when direction of output shaft and travel-limit cam rotation is counterclockwise to open. Opening-stroketravel-limit cam (with switch operator in fully closed position-raise and turn cam clockwise to increase travel of switch operator) Closing-stroke travel-limit cam (with switch operator in fully open position-lower and turn cam counterclockwise to increase travel of switch operator) Figure 6. Adjustment of travel-limrt cams Page 12 of 23 April 22,1996 NSTRUCTON SHEET S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto

13 ADJUSTMENTS -Continued Opening-Stroke Travel-Limit Cam. With the selector handle in the coupled position, manually operate the switch operator in the opening direction and observe the opening-stroke travel-limit cam. At the completion of the switch operator opening stroke, the leading edge of the opening-stroke travel-limit cam should be engaged with its roller. f the leading edge is not engaged with its roller, adjust the opening-stroke travel-limit cam (as described in Step 13) so that its leading edge touches (or nearly touches) the roller. Return the manual operating handle to its storage position. ntermediate Adjustment of Travel-Limit Cams Step 15 The adjustments described in this step are required to obtain a close approximation of the correct travel of the switch operator in the decoupled position-i.e., in a noload condition, in order to avoid inadvertently overdriving the Alduti-Rupter Switch when the switch operator is first used for power opening or closing of the switch. Closing-Stroke Travel-Limit Cam. With the selector handle in the coupled position, manually crank the Alduti- Rupter Switch to its fully closed position. Return the manual operating handle to its storage position. Then place the selector handle in the decoupled position and replace the motor-circuit fuseholder. Operate the switch operator electrically to open, and then to close. f the position-indexing drums are not numerically aligned, operate the switch operator electrically to open. Remove the motor-circuit fuse holder. Then adjust the closing-stroke travel-limit cam, as described in Step 13, the necessary number of increments to attain numerical alignment of the position-indexing drums at the completion of a switch operator closing stroke. Opening-Stroke Travel-Limit Cam. With the selector handle in the coupled position, manually crank the Alduti-Rupter Switch to its fully open position. Return the manual operating handle to its storage position. Then place the selector handle in the decoupled position and replace the motor-circuit fuseholder. Operate the switch operator electrically to close, and then to open. f the position-indexing drums are not numerically aligned, operate the switch operator electrically to close. Remove the motor-circuit fuseholder. Then adjust the opening-stroke travel-limit cam, as described in Step 13, the necessary number of increments to attain numerical alignment of the position-indexing drums at the completion of a switch operator opening stroke. ni gear /Contact (closed) Roller --- Cam (lowered toward adjacent spring) h Adjacent spring Figure 7. Adjustment of cams on auxiliary switch. S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto NSTRUCTON SHEET 76gm5()() Page 13 of 23

14 S&C Switch Operators - Type AS-A 1 ADJUSTMENTS - Continued Final Adjustment of Travel-Limit Cams Step 16 The adjustments described in this step are necessary to ensure complete opening and closing of the Alduti-Rupter Switch. Therefore, attention must now be directed to the open and closed stops of the switch. Operate the switch operator electrically to open and close the Alduti-Rupter Switch. Observe the toggle mechanisms (if applicable) and the open stops on the switch. t is likely that full opening and closing travel will not have been attained. This is because the travel-limit cams were adjusted to limit the extent of output-shaft rotation while the switch operator was in the decoupled position-le., in a no-load condition. To attain full stop positions (and over-toggle positions, where applicable) of the Alduti- Rupter Switch, refer to Figure 6 and proceed as described below. Closing-Stroke Travel-Limit Cam. f full closing of the Alduti-Rupter Switch was not attained, replace the motor-circuit fuseholder and operate the switch operator electrically to open the Alduti-Rupter Switch. Remove the motor-circuit fuseholder. To increase travel in the closing direction, retard the closing-stroke travel-limit cam one 4.5-degree increment (1) in the clockwise direction if the travel-limit cam and output shaft rotate clockwise to open the Alduti-Rupter Switch; or (2) in the counterclockwise direction if the travel-limit cam and output shaft rotate counterclockwise to open the Alduti-Rupter Switch. Replace the motor-circuit fuseholder and operate the switch operator electrically to close. f full closing travel has not been attained, repeat the procedure described above until full closing travel is attained. Opening-Stroke Travel-Limit Cam. f full opening of the Alduti-Rupter Switch was not attained, operate the switch operator electrically to close the switch. Remove the motor-circuit fuseholder. To increase travel in the opening direction, retard the opening-stroke travel-limit cam one 4.5-degree increment (1) in the counterclockwise direction if the travel-limit cam and output shaft rotate clockwise to open Alduti- the Rupter Switch; or (2) in the clockwise direction if the travel-limit cam and output shaft rotate counterclockwise to open the Alduti-Rupter Switch. Replace the motor-circuit fuseholder and operate the switch operator electrically to open. f full opening travel has not been attained, repeat the procedure described above until full opening travel is attained. Step 17 When travel-limit cam adjustments have been completed, it may be necessary to realign the Alduti-Rupter Switch position indicators on the switch operator output-shaft collar with the alignment mow. With the switch operator in the fully open position and then in the fully closed position, check the corresponding switch operator position indicator. n each position, the corresponding position indicator should be readily visible from the front of the enclosure. f adjustment of either position indicator is necessary, remove the motor-circuit fuseholder, loosen the two set screws on the position indicator, and rotate the position indicator to the desired position. Retighten the set screws. See Figure 8. Step 18 The auxiliary switch, which is permanently coupled to the motor, includes eight contacts (terminals 11 through 26). f the optional position-indicating lamps are included, six contacts are available (terminals 13 through 18 and 21 through 26). These contacts are provided so that external circuits can be established to monitor switching operations. Each contact is operated by a cam-actuated roller. The cams are individually adjustable in 4.5-degree increments. Adjustment of the cams is accomplished in a manner identical to that indicated Step 13 for the travellimit cams NSTRUCTON SHEET Page 14 of 23 COMPANY ELECTRC S&C S&C CANADA ELECTRC Chicago LTD. Toronto

15 ADJUSTMENTS -Continued The standard configuration for the auxiliary switch consists of four al contacts (terminals 11 through 18) and four bl contacts (terminals 19 through 26). Thus, with the switch operator in the open position, the al contacts are open and the bl contacts are closed. Conversely, with the switch operator in the closed position, the al contacts are closed and the bl contacts are open. A contact is closed if its roller is disengaged from a cam and, conversely, a contact is open if its roller is engaged by a cam. See Figure 8. Any auxiliary-switch contact being used must be checked for proper operation after the switch operator travel-limit cams have been adjusted. Check the auxiliaryswitch contacts for both the open and closed positions of the Alduti-Rupter Switch. f necessary, adjust the cams as described in Step 13 so that the auxiliary-switch contacts are in the desired open or closed position (Le., cam engaged with roller, or cam disengaged from roller). See Figure 7. Since each cam can be individually adjusted in 4.5- degree increments, any al contact can be changed to a bl contact, or vice versa. Also, because of the many positions to which the cams can be adjusted, the various rollers can be engaged or disengaged to respectively open or close their contacts simultaneously, sequentially, randomly, or in various combinations. Adjustment of the auxiliary-switch contacts for other than the standard configuration is left to the user. Remember that the motorcircuit fuseholder should be removed when adjusting these contacts. (Switch operators having catalog numbers with the suffix -Q are equipped with an extra auxiliary switch, terminals 27 through 34, having four contacts-two al and two b1 -which may be adjusted as described in Step 13(a) through (d). See Figure 8.) Step 19 Switch operators having catalog numbers with either the suffix -W or -Z are equipped with an extra auxiliary switch which is permanently coupled to the Alduti-Rupter Switch. The suffix -W auxiliary switch consists of eight contacts (terminals 35 through 50). The suffix -Z auxiliary switch consists of twelve contacts (terminals 35 through 50 plus terminals 80 through 87). These contacts are provided so that external circuits can be established to monitor Alduti-Rupter Switch operation. Each contact is operated by a cam-actuated roller and the cams are individually adjustable in 4.5-degree increments. The standard configuration for the suffix -W extra auxiliary switch consists of four a2 contacts (terminals 35 through 42) and four b2 contacts (terminals 43 through 50). The standard configuration for the suffix -Z extra auxiliary switch consists of six a2 contacts (terminals 35 through 42 and terminals 80 through 83) and six b2 contacts (terminals 43 through 50 and terminals 84 through 87). Thus, with the Alduti-Rupter Switch in the fully closed position, the a contacts should be closed and the b2 contacts should be open. Conversely, with the Alduti-Rupter Switch in the fully open position, the a2 contacts should be open and the b2 contacts should be closed. See Figure 8. Any suffix -W or -Z auxiliary-switch contact being used must be checked for proper operation after satisfactory electrical operation of the Alduti-Rupter Switch has been achieved. Check the auxiliaryswitch contact engagement for both the open and closed positions of the Alduti-Rupter Switch. Adjustment of the suffix -W or -Z extra auxiliary switch is identical to the adjustment performed for the travel-limit switch, the auxiliary switch, and the suffix -Q extra auxiliary switch. Therefore, if adjustment of the suffix -W or -Z auxiliary switch is needed, refer to Step 13 and Figures 7 and 8. Step 20 Reinsert the fuseholders for the motor circuit and spaceheater circuit. COMPANY ELECTRC S&C CANADA ELECTRC S&C NSTRUCTON SHEET Page Chicago 15 of 23 LTD. April Toronto 22, 1996

16 S&C Switch Operators - Type AMA ADJUSTMENTS - Continued Extra auxiliary switch (Catalog Number Suffix -vv or -Z?) Travel-limit switch, auxiliary switch, and extra auxiliary switch (Catalog Number Suffix -a ) gure 8. Standard contact configurations Page 16 of 23 NSTRUCTON SHEET S&C ELECTRC COMPANY Chicago V S&C ELECTRC CANADA LTD. Toronto i

17 ADJUSTMENTS - Continued Set screw (2 per indicator) :n Travel-limit switch Travel-limit switch al contacts closed bl contacts open Auxiliary ) switch, 8-PST al contacts open bl contacts closed Auxiliary switch, &PST al contacts closed bl contacts open -( Extra auxiliary switch, - 4-PST (Catalog Number Suffix -a ) al contacts open bl contacts closed Extra auxiliary switch, 4-PST (Catalog Number Suffix -Q ) Switch operator in fully closed position Swftch operator in fully open position a2 contacts closed b2 contacts open a2 contacts closed b2 contacts open Extra auxiliary switch, 8-PST (Catalog Number Suffix -W) a2 contacts open b2 contacts closed a2 contacts open b2 contacts closed Extra auxiliary switch, 8-PST (Catalog Number Suffix -W) Extra auxiliary switch, 12-PST (Catalog Number Suffix l-z ) Alduti-Rupter Switch in fully closed position Alduti-Rupter Switch in fully open position NSTRUCTON SHEET S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD. Toronto Page 17 of 23

18 S&C Switch Operators - Type ASA NSPECTON SCHEDULE AND PROCEDURES To assure continued proper performance of the Type (e) Using a 3/32" Allen wrench, loosen the pad assem- AS-1A Switch Operator, it should be inspected every bly socket-head set screw on the side of the cali- 5 years. De-energize the associated Alduti-Rupter per assembly approximately one-half turn. See Switch and perform the following switch operator Detail A. inspection procedures: (f) Then, using a 5/6" Allen wrench, rotate the pad 1. Check for evidence of water ingress, damage, and assembly clockwise until the free play at the end of excessive corrosion or wear. the brake lever is vi''to 3/4", as shown in Detail B. 2. Check ease of operation during slow, manual cranking Now tighten the 3/32" pad assembly socket-head set using the switch operator manual operating handle. screw. 3. Check electrical operation, coupled and decoupled. 4. Check for loose wiring inside enclosure and proper functioning of position-indicating lamps, operation counter, convenience lamp, etc. 5. Check operation of brake and readjust if necessary. The procedure for doing this is as follows. See Figure 9. (a) Place the selector handle in the decoupled position. (b) Remove the two-pole pull-out fuseholders for the motor circuit and space-heater circuit. (c) Disconnect the linkage rod by removing the W-20 x 1%" hex-head screw, lockwasher, flat washer, and spacer-bushing from the end of the brake lever, as shown in Detail A. Be careful not to lose these parts. Then raise the brake lever and measure the vertical free play, as shown in Detail B. This dimension should be %" to 3/4'! Should the measurement be outside this range, brake-wear compensation is required; proceed to Step (d). f the measurement is within this range, reattach the linkage rod and tighten the '/4"-20 X11/4" hex-head screw securely; proceed to Step (i). (d) Remove the four %6"-18 Xl?h'' screws used to attach the motor, withdraw the motor, and carefully rest its shaft on the floor of the enclosure. Be careful not to lose the square key or tubular spacer (if furnished), which may remain on the motor shaft. Note: 115-volt ac and 230-volt ac motors utilize a?4"-20 socket-head set screw on the side of the brake disc hub, as shown in Detail C. Loosen this set screw approximately one-half turn, using a W Allen wrench, before removing the motor. (g) nsert the spacer-bushing through the angle bracket and brake lever, and reattach the linkage rod using the 1/4"-20 X1%" hex-head screw, lockwasher, and flat washer. Tighten the screw securely. (h) nsert the square key in the keyway, as shown in Detail A. Slip the tubular spacer (if furnished) over the motor shaft and reinstall the motor. Position the motor such that the two weep holes on the side of the housing face downward. Replace the four 5/8-18 x11/4" screws used to attach the motor and tighten them securely. On 115-volt ac and 230-volt ac motors, further, retighten the l/4"-20 sockethead set screw on the side of the brake disc hub. (i) Check the operation of the brake linkage as follows: Pull the latch knob on the hub of the manual operating handle and slowly pivot the handle forward from its storage position toward its cranking position until the brake disc can be rotated by hand. Be ccweful not to get grease on the brake disc. Now measure the distance that the end of the brake lever travels from the point of initial brake release to the bottom of its stroke (which occurs when the handle locks into the cranking position). This dimension should be '/8" to Y4". See Detail D. Should the measurement be outside this range, refer to the nearest S&C Sales Office. Since the Type AS-1A Switch Operator may be conveniently decoupled from the Alduti-Rupter Switch, elective exercising of the operator may be performed at any time without requiring an outage or switching to an alternate source NSTRUCTON SHEET Page 18 of 23 COMPANY ELECTRC S&C Chicago S&C ELECTRC CANADA LTD. Toronto

19 NSPECTON PROCEDURES SCHEDULE AND - Continued DETAL C Location of motor shaft set screw (115- & 230-vac operator only) DETAL A Brake assembly Operating linkage dlsconnected from brake lever % -% vertical free play DETAL B Measuring brake lever free play Brake lever Operating linkage connected to brake lever DETAL D Measuring brake \ Brake lever at bottom of its stroke (manual operating lever stroke handle in cranking position) Figure 9. Brake inspection procedure. NSTRUCTON SHEET COMPANY ELECTRC S&C Chicago Page 19 of 23 LTD. CANADA ELECTRC S&C April Toronto 22, 1996

20 S&C Switch Operators - Type AS-1 A CHECKNG SWTCH OPERATOR AND ALDUT-RUPTER SWTCH POSTONS 1 Do not assume that the switch operator position necessarily indicates the open or closed position of the Alduti- Rupter Switch. Upon completion of an opening or closing operation (electrical or manual), check to be sure that the following conditions exist: The switch operator position indicator, Figure 5, signals OPEN or CLOSED to indicate that the switch operator has moved through a complete operation. Also note the position-indicating lamps, Figure 5, if furnished. The Alduti-Rupter Switch position indicator, located on the switch operator output shaft. F igure 1, is in agreement with the switch operator position indicator. That is, both indicators should simultaneously show OPEN or CLOSED. The blades on all three poles of the Alduti-Rupter Switch are fully open or fully closed (by visual verification). APPENDX For wpe AS-1A Switch Operators furnished with Source-Transfer Control Compatibility (suffix -Ul ), follow the step-by-step procedure outlined below after having completed Step 9. Step A The cranking direction to close the Alduti-Rupter Switch is indicated by an arrow plate located near the hub of the manual operating handle. See Figure 6. This direction has been predetermined from the erection drawing for the specific installation and has been factoly-set accordingly. The direction of rotation of the switch operator motor has also been set at the factory. Verify that these directions of rotation are correct as follows: (a) With the selector handle in the coupled position, manually crank the Alduti-Rupter Swit,ch to the fully open position and then to the fully closed position. Temporarily mark on the top of the switch operator enclosure the direction in which the output shaft rotates to close the Alduti-Rupter Switch. (b) f the cranking direction required to close the Alduti- Rupter Switch is opposite to that indicated by the arrow plate, remove the arrow-plate mounting screws and remount the arrow plate, exposing the opposite side. Then tag and padlock the switch operator in accordance with standard system operating procedures. n all cases, make certain that the switch operator is padlocked before walking away. To restore to normal operation So that the switch operator is ready for normal power operation of the Alduti-Rupter Switch by remote automatic or supen+sory control, be sure that the following conditions exist: The selector handle is in the coupled position. The manual operating handle is in its storage position. The two-pole pull-out fuseholders for the motor circuit and space-heater circuit are inserted. The pushbutton protective cover is closed. The switch operator is tagged and padlocked in accordance with standard system operating procedures. (e) With the manual operating handle in its storage position and the sebector handle n he decmupled position, reinsert the motor-circuit fuseholder. Open the pushbutton protective cover and operate the switch operator by means of the externally mounted operdclose pushbuttons, if probided, or in their absence, by momentarily jumpering terminals 1 and 8 to open, and 1 and 9 to c1ose.a Note the direction in which the travel-limit discs mtate whew th,e switch operator closes. The direction should agree with the temporary direction mark previously made on the top of the enclosure and with the direction displayed in the cutaway section on the outer ring of the travel-limit discs. See Figure 10. (As a matter of information, the direction of rotation of the travel-limit discs is always the same as the direction of rotation of the output shaft.) (d) n the event that the direction of rotation of the travellimit discs noted in (c) above is opposite to the temporary direction mark prekiously made in (a) above, a reversal of the motor direction will be necessary. Remove the,motor-circu,it juseholder to avoid accidental or remote energization of the control circuit. nterchange the Sl and 32 mot,or leads connected to terminals 4 and 5 on the terminal block in the switch operator enclosure. A Termlnal deslgnatlons may dlffer n special wring dlagrams. n such cases, refer to the speclfic wiring dlagram for the correct, termnal designatlons NSTRUCTON SHEET Page 20 of 23 S&C COMPANY ELECTRC CANADA ELECTRC S&C Chicago LTD. Toronto

21 APPENDX - Continued t should be noted particularly that reversal of the motor direction reverses only the direction of rotation of the output shaft and travel-limit discs. The identity of the opening-stroke and closing-stroke travel-limit discs (which will be adjusted later) will remain unaffected. (e) n the event that the direction of rotation of the travellimit discs noted in (c) above is opposite to the direction displayed in the cutaway section on the outer ring of the closing-stroke travel-limit disc, remove the positioning screws on the outer ring of the closing-stroke travel-limit disc. See Figure 10. Rotate the outer ring until the desired direction is displayed in the cutaway section. Replace the positioning screws. (f) Reinsert the motor-circuit fuseholder and operate the switch operator to the open position. (g) f the direction of output-shaft rotation to open the Alduti-Rupter Switch is opposite to that displayed in the cutaway section on the outer ring of the openingstroke travel-limit disc, change the direction displayed as indicated in (e) above. - Positioning screws A Opening-stroke travel-limit disc (in raised position) < A Cutaway section (on outer ring) \ Arrow (on cutaway section) ndicator plate (with numbers) Aatustment or openmg-stroke navel-umn aisc. Switch operator position indicator r ndicator plate (with numbers) osing-stroke travel-limit SC (in lowered position) Cutway section (on outer ring) Arrow (on cutway section) Adjustment of closing-stroke travel-limit disc. Figure 10. Adjustment of travel-limit discs. fi S&C ELECTRC COMPANY Chicago S&C ELECTRC CANADA LTD.. Toronto NSTRUCTON SHEET Page 21 of 23

S&C Switch Operators Types AS-1A and AS-10

S&C Switch Operators Types AS-1A and AS-10 S&C Switch Operators Types AS-1A and AS-10 Page 1 of 11 S&C Switch Operators - Types AS-1A and AS-10 Types AS-1A and AS-10 Switch Operators are high-speed operators expressly designed for power operation

More information

INSTRUCTIONS. 1 Schematic. I Device ' I. S8C Switch Operators - Type CS-24. For Operation

INSTRUCTIONS. 1 Schematic. I Device ' I. S8C Switch Operators - Type CS-24. For Operation Number 38840R1-B. The NSTRUCTON S8C Switch Operators - Type CS-24 NSTRUCTONS For Operation CAUTON: The equipment covered by this publication must be operated and maintained by qualified persons who are

More information

INSTRUCTIONS For Installation

INSTRUCTIONS For Installation S&C Switch Operators - Types LS- and LS-2 NSTRUCTONS For nstallation TABLE OF CONTENTS i Section Page Number Section Page Number NTRODUCTON... 1 NSPECTON SCHEDULE AND PROCEDURES....16 NSTALLATON... 3 CHECKNG

More information

Specifications. S&C Switch Operators Types AS-1A and AS-10a. Conditions of Sale

Specifications. S&C Switch Operators Types AS-1A and AS-10a. Conditions of Sale a Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: INCLUSIONS: S&C Switch Operators Types AS-1A and AS-10 are

More information

INSTRUCTIONS. S&c Circuit-Switchers - Mark v Grounding Switches - 70,000 Amperes Momentary Outdoor Transmission I INTRODUCTION INSTRUCTION SHEET 7 1 1

INSTRUCTIONS. S&c Circuit-Switchers - Mark v Grounding Switches - 70,000 Amperes Momentary Outdoor Transmission I INTRODUCTION INSTRUCTION SHEET 7 1 1 S&c Circuit-Switchers - Mark v Grounding Switches - 70,000 Amperes Momentary With 90-degree opening blades NSTRUCTONS - - - - - - - - - - - - - - For Field Assembly and nstallation NTRODUCTON CAUTON: The

More information

INSTRUCTIONS For Installation

INSTRUCTIONS For Installation S&C Switch Onerators - TyDe CS-PA NSTRUCTONS For nstallation TABLE OF CONTENTS i Section Page Number Section Page Number NTRODUCTON... 1 NSPECTON SCHEDULE AND PROCEDURES... 11 NSTALLATON....3 CHECKNG SWTCH

More information

INSTRUCTIONS. S&C Switch Operators - Type CS-1 A. For Operation INTRODUCTION

INSTRUCTIONS. S&C Switch Operators - Type CS-1 A. For Operation INTRODUCTION S&C Switch Operators - Type CS-1 A NSTRUCTONS For Operation NTRODUCTON CAUTON: The equipment covered by this puelication must be operated and maintained by qualified persons who are thoroughly trained

More information

Instructions for Installation and Operation

Instructions for Installation and Operation S&C Alduti-Rupter Switches Outdoor Distribution Three-Pole Vertical-Break Style Reciprocating Operating Mechanism 25/34.5 kv and 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section

More information

INSTRUCTIONS. Operating Lever4 Maximum Operating

INSTRUCTIONS. Operating Lever4 Maximum Operating S&C Switch Operators - Type CS-10 NSTRUCTONS 1 NTRODUCTON CAUTON: The equipment covered by this publication must be operated and maintained by qualified persons who are thoroughly trained and who understand

More information

S&C Vista Underground Distribution Switchgear

S&C Vista Underground Distribution Switchgear S&C Vista Underground Distribution Switchgear Pad-Mounted, Vault-Mounted, and UnderCover Styles Instructions For Installation and Operation of Portable Motor Operator TABLE OF CONTENTS Section Page Section

More information

INSTRUCTIONS For Field Assembly and Installation

INSTRUCTIONS For Field Assembly and Installation S&C Line-Rupters" Outdoor Transmission (115 kv through 230 kv) I For Line and Cable Switching INSTRUCTIONS For Field Assembly and Installation ITABLE OF CONTENTS I Section Page Number Section Page Number

More information

Instructions for Installation and Operation

Instructions for Installation and Operation S&C Alduti-Rupter Switches Three-Pole Side-Break Heavy-Duty Style Reciprocating Operating Mechanism 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section Page Section Page INTRODUCTION

More information

Instructions for Installation

Instructions for Installation S&C Circuit-Switchers Mark VI Outdoor Transmission 69 kv through 138 kv Option U, User-Furnished Mounting Structure Instructions for Installation TABLE OF CONTENTS Section Page Section Page INTRODUCTION

More information

Cleaning Flooded Gear

Cleaning Flooded Gear S&C Manual PMX Modular Metal-Enclosed Switchgear Outdoor Distribution (13.8 kv and 25 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding

More information

Installation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission.

Installation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission Installation Table of Contents Section Page Section Page Introduction Qualified Persons....2 Read this

More information

Cleaning Flooded Gear

Cleaning Flooded Gear S&C Manual Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv)

S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv) S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv) Installation Table of Contents Section Page Section Page

More information

Installation and Operation

Installation and Operation S&C Alduti-Rupter Switches Outdoor Distribution (46 kv) Three-Pole Double-Break Integer Style Reciprocating Operating Mechanism No Catalog Number Supplement and Operation Table of Contents Section Page

More information

Installation and Operation

Installation and Operation S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Installation and Operation Table

More information

Installation and Operation

Installation and Operation S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction

More information

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Catalog Number Supplement R3

More information

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Upright and Triangular Mounting Configurations Catalog Number Supplement R3 and Earliern Installation

More information

Interrupter Replacement INSTRUCTIONS. For Replacement of Interrupters. A Cypo.qdated is the S&C trademark for devices employing the S&C Cypoxfl

Interrupter Replacement INSTRUCTIONS. For Replacement of Interrupters. A Cypo.qdated is the S&C trademark for devices employing the S&C Cypoxfl - - - S&C Alduti-Rupters Switches* Outdoor and ndoor Distribution nterrupter Replacement NSTRUCTONS - ~~~ - ~~ ~~ For Replacement of nterrupters [TABLE OF CONTENTS Page Section Section Number Page NTRODUCTON...

More information

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance S&C Regulator Bypass Switches Outdoor Distribution (14.4 kv through 25 kv) Type XL (Sequenced) and Type NL (Non-sequenced) Installation, Operation, and Maintenance Table of Contents Section Page Section

More information

INSTRUCTIONS. Section Page Number Section Page Number REMOVING THE MECHANICAL ANTIPARALLELING S&C ELECTRIC COMPANY 0 Chicago

INSTRUCTIONS. Section Page Number Section Page Number REMOVING THE MECHANICAL ANTIPARALLELING S&C ELECTRIC COMPANY 0 Chicago SBC Source-Transfer PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Replacing Type AT-1 2 Control With Micro-AT Control n Gear Having Rl or R2 Supplement to the Catalog Number TABLE OF CONTENTS

More information

Valtek Auxiliary Handwheels and Limit Stops

Valtek Auxiliary Handwheels and Limit Stops Valtek Auxiliary s and Limit Stops Table of Contents Page 1 General information 2 Installation 2 Side-mounted handwheels, size 25 and 50 (linear actuators) 3 Side-mounted handwheels, size 100 and 200 (linear

More information

INSTRUCTIONS For Field Assembly and Installation

INSTRUCTIONS For Field Assembly and Installation nteger Style NSTRUCTONS For Field Assembly and nstallation [TABLE OF CONTENTS Section Page Number Section Page Number NTRODUCTON... 1 NSTALLATON... 7 BEFORE STARTNG NSTALLATON....5 FNA1,CHECKS... 10 1

More information

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Supersedes IL 33-858-4 Dated 05/02 Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers Digitrip Retrofit System for ITE K-3000, Digitrip Retrofit System for ITE K-3000, K-3000

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv) Inspection Recommendations for Switchgear with Type AT-3 Source- Transfer Controls Table of Contents Section

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version Optimal Series Automatic Transfer Switch Installation and User Manual for the OPT2225 Automatic Transfer Switch Full Version File: OPT2225 Rev2.5.doc November, 2004 2 Thank You For Purchasing This DynaGen

More information

INSTRUCTIONS I INTRODUCTION. S&C Switches Indoor Distribution (4.8 kv through 34.5 kv) I INSTRUCTION SHEET

INSTRUCTIONS I INTRODUCTION. S&C Switches Indoor Distribution (4.8 kv through 34.5 kv) I INSTRUCTION SHEET S&C Alduti-Rupter@ Switches ndoor Distribution (4.8 kv through 34.5 kv) NSTRUCTONS For nstallation NTRODUCTON CAUTON: The equipment covered by this publication mustbeselected for a specific application

More information

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC 29006 Service Manual 3011 SL-6 & SL-6A Outlying Switch Lock Field and Shop Maintenance April, 1979 A-79-500-1496-3 1979, Union Switch & Signal

More information

INSTRUCTIONS I INTRODUCTION I TABLE OF CONTENTS. %!kc TypeAT-2,TypeAT-3,orTypeAT-12Source- S8C Type AT Source-Transfer Controls I Field Replacement

INSTRUCTIONS I INTRODUCTION I TABLE OF CONTENTS. %!kc TypeAT-2,TypeAT-3,orTypeAT-12Source- S8C Type AT Source-Transfer Controls I Field Replacement S8C Type AT Source-Transfer Controls Field Replacement NSTRUCTONS TABLE OF CONTENTS Section Page Number Section Page Number NTRODUCTON... 1 RE LACNG TYPE AT-2 SOURCE-TRANSFER CONTROL N REPLACNG TYPE AT-2

More information

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL The High Performance Company Table Of Contents: page Safety instructions: Definitions of Terms... 2 Introduction principle of operation...

More information

INSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET

INSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3 Outdoor Transmission Mountings Rated 34.5, 46, and 69 kv INSTRUCTIONS For Field Assembly and Installation TABLE OF CONTENTS Section Page Number INTRODUCTION........................................1

More information

Introduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv)

Introduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv) S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv) Inspection Recommendations for Switchgear Equipped with Type AT-2 Source-Transfer Controls Table of Contents

More information

Installation And Operation

Installation And Operation S&C Series 2000 Circuit-Switchers Outdoor Transmission Model 2020 With Vertical Interrupters and Side-Break Power-Operated Disconnect 69 kv through 138 kv Installation And Operation Table of Contents Section

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious

More information

Florham Park, NJ USA Call (ASCO) for sales or service

Florham Park, NJ USA Call (ASCO) for sales or service Operator s Manual 4000 Series ATS Automatic Open-Transition Transfer Switches D design 30 230A, J design 260 600A, H-design 800 1200A, G-design 1600 4000A, F-design 4000A DANGER is used in this manual

More information

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...

More information

Installation and Operation

Installation and Operation S&C Series 2000 Circuit-Switchers Outdoor Transmission Model 2030 With Vertical Interrupters and Without Disconnect 69 kv through 230 kv Installation and Operation Table of Contents Section Page Section

More information

SPECIFICATION BULLETIN

SPECIFICATION BULLETIN SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS on page 3. SPECIAL TO THIS PRODUCT:

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual Series 70 Operation and Maintenance Manual TABLE OF CONTENTS 1. Definition of Terms............................................. 1 2. Safety................................................... 1 3. Storage..................................................

More information

Contents. Section 5: Adjustments Ball Detect Adjustment Transport Band Tension Adjustment

Contents. Section 5: Adjustments Ball Detect Adjustment Transport Band Tension Adjustment Contents Section 5: Adjustments... 5-3 1. Ball Detect Adjustment... 5-3 2. Transport Band Tension Adjustment... 5-5 3. Transport Band Drive Belt Tension Adjustment... 5-7 4. Ball Cushion Adjustment...

More information

INSTRUCTIONS For Field Replacement

INSTRUCTIONS For Field Replacement SLC Source-Transfer PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Replacing Type AT-12 Control With Micro-ATT Control In Gear Having R4 Supplement to the Catalog Number INSTRUCTIONS For

More information

COOKSON OWNER'S MANUAL

COOKSON OWNER'S MANUAL COOKSON OWNER'S MANUAL FDO-A10 INDUSTRIAL DUTY FIRE DOOR OPERATOR R L I S T E D 3040233 US CONTROL PANEL SERIAL# OPERATOR SERIAL# 9001.DWG ECN 0959 REV 4 SPECIFICATIONS MOTOR TYPE:...INTERMITTENT HORSEPOWER:...1/8

More information

Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems

Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems Instruction Sheet 408-8040 30 NOV 17 Rev H Ram Assembly Ram Post Locking Screw Stock Drag Drag Release

More information

Installation & Maintenance Instructions for FSQC 100 Ampere Receptacle

Installation & Maintenance Instructions for FSQC 100 Ampere Receptacle 303359 INSTRUCTION SHEET Installation & Maintenance Instructions for FSQC 100 Ampere Receptacle RETAIN THIS INSTRUCTION SHEET FOR FUTURE REFERENCE. For safe installation and operation, please read these

More information

Fisher 1051 and 1052 Style H and J Sizes 40, 60 and 70 Rotary Actuators

Fisher 1051 and 1052 Style H and J Sizes 40, 60 and 70 Rotary Actuators Instruction Manual 1051 and 1052 H & J Actuators Fisher 1051 and 1052 Style H and J Sizes 40, 60 and 70 Rotary Actuators Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications...

More information

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv) Outdoor Distribution (4.4 kv through 46 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 50 apply, except as modified under WARRANTY QUALIFICATIONS

More information

Crestline Altra Series TM Dampener. Installation Instructions. Heidelberg GTO. X /98 Rev-A

Crestline Altra Series TM Dampener. Installation Instructions. Heidelberg GTO. X /98 Rev-A Crestline Altra Series TM Dampener Installation Instructions Heidelberg GTO X88-63 7/98 Rev-A GENERAL INFORMATION ATTENTION CRESTLINE ALTRA SERIES TM DAMPENER OWNER! Accel Graphic Systems provides parts

More information

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited. SERVICE MANUAL ELECTRIC BRAISING PANS (30 & 40 GALLON) VE30 VE40 ML-126849 ML-126850 VE40 SHOWN - NOTICE - This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used

More information

OPERATION INSTRUCTONS MODEL SG 05.1 SG Quarter-Turn Actuators

OPERATION INSTRUCTONS MODEL SG 05.1 SG Quarter-Turn Actuators OPERATION INSTRUCTONS MODEL SG 05.1 SG 12.1 Quarter-Turn Actuators AUMA Actuators, Inc. USA 100 Southpointe Boulevard Canonsburg, PA 15317 724-743-2862 Fax: 724-743-4711 www.auma-usa.com email: mailbox@auma-usa.com

More information

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label. Operator s Manual 7000 Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes TABLE OF CONTENTS Note: Refer to the outline and wiring drawings provided with your 7000 Series

More information

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual Your Global Flow Control Partner Series 70 Table of Contents 1. Definition of Terms.......................................2 2. Safety............................................. 2 3. Storage............................................2

More information

70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing

70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing Bulletin No. BK4773-3 (08/2016) 70 Series 8700 End Mount Three Phase Brake Instructions IP56 (NEMA 4) Housing Read carefully before attempting to assemble, install, operate or maintain the product described.

More information

70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing

70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing Bulletin No. BK4772S-3 (6/2017) 70 Series 8700 End Mount Three Phase Brake Instructions IP43 (NEMA 2) Housing Read carefully before attempting to assemble, install, operate or maintain the product described.

More information

INSTRUCTIONS For Installation

INSTRUCTIONS For Installation S&C Mini-Rupter@Switches ndoor Distribution (4.16 kv through 25 kv) NSTRUCTONS For nstallation NTRODUCTON CAUTON: The equipment covered by this publication mustbeselected for a specific application and

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL Cornell RG Operator RGRL Series (w/ Internal Interlock sensor) ES 10-288 GENERAL NOTES TO REDUCE THE RISK OF SEVERE INJURY OR DEATH, READ AND FOLLOW ALL INSTALLATION

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

S&C Mini-Rupter Switches Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter Switches Typical ED, reduced from full 11 size.

S&C Mini-Rupter Switches Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter Switches Typical ED, reduced from full 11 size. S&C Mini-Rupter es Indoor Distribution (4.16 kv through 25 kv) Selecting Standard Mounting Arrangements for Manually Operated Styles Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

Transmission Overhaul Procedures-Bench Service

Transmission Overhaul Procedures-Bench Service How to Assemble the Lower Reverse Idler Gear Assembly Special Instructions In 1996 Eaton changed the reverse idler system design. In the nut design, the reverse idler bearing was lubricated through a hole

More information

S&C Source-Transfer Vista Underground Distribution Switchgear

S&C Source-Transfer Vista Underground Distribution Switchgear S&C Source-Transfer Vista Underground Distribution Switchgear Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles Instructions For Installation Section Page Section Page INTRODUCTION

More information

Type 1051 and 1052 Size 33 Diaphragm Rotary Actuator

Type 1051 and 1052 Size 33 Diaphragm Rotary Actuator Instruction Manual Type 1051 and 1052 Size 33 Diaphragm Rotary Actuator 1051 & 1052 Actuator Contents Introduction............................. 1 Scope of Manual........................... 1 Description................................

More information

Fisher 1061 Pneumatic Piston Rotary Actuator with Style H & J Mounting Adaptations

Fisher 1061 Pneumatic Piston Rotary Actuator with Style H & J Mounting Adaptations Instruction Manual 1061 H & J Actuator Fisher 1061 Pneumatic Piston Rotary Actuator with Style H & J Mounting Adaptations Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications...

More information

Installation Instructions LINK---C

Installation Instructions LINK---C IS---LINK---C Page 1 of 10 Installation Instructions LINK---C DEADBREAK CAM LINK OPERABLE CONNECTOR SYSTEM The is a 600 amp, connector designed to: 1.) provide a fully shielded, fully submersible hot stick

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL FS Series Rolling Fire Door Operators CORPORATION GENERAL NOTES TO REDUCE THE RISK OF SEVERE INJURY OR DEATH, READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT Supersedes Form145.10-IOM1 (810) Form 145.10-IOM1 (910) LOW-AMBIENT KIT MODELS DSH/KSH/DSV/KSV R-410A AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS IMPORTANT!

More information

S&C Manual PME Pad-Mounted Gear

S&C Manual PME Pad-Mounted Gear S&C Manual PME Pad-Mounted Gear Outdoor Distribution,. kv and 5 kv S&C Manual PME Pad-Mounted Gear... Featuring Elbow-Connected Encased Components. S&C Manual PME Pad-Mounted Gear brings in-air insulation,

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL - 1/3, 1/2, 3/4hp UL325-2010 Compliant Commercial and Industrial Door Operator Logic Control Duty Cycle 20 Cycles per Hour IMPORTANT INSTALLATION INSTRUCTIONS

More information

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL INSTALLATION INSTRUCTIONS AND OPERATION MANUAL UL325-2010 Compliant Commercial and Industrial Door Operator Logic Control Continuous Duty IMPORTANT INSTALLATION INSTRUCTIONS WARNING To reduce the risk

More information

MODEL ELC-12/40-CVM-D BATTERY CHARGER

MODEL ELC-12/40-CVM-D BATTERY CHARGER NATIONAL RAILWAY SUPPLY MODEL ELC-12/40-CVM-D BATTERY CHARGER Installing, Operating and Service Instructions for the ELC-12/40-CVM-D Solid State Charger PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING

More information

Heavy Duty Miniature Quick-Change Applicator (End-Feed Type) with Mechanical or Air-Feed Systems

Heavy Duty Miniature Quick-Change Applicator (End-Feed Type) with Mechanical or Air-Feed Systems Heavy Duty Miniature Quick-Change Applicator (End-Feed Type) with Mechanical or Air-Feed Systems Instruction Sheet 408-8039 02 JUN 16 Rev G Ram Post Wire Disc Insulation Disc Insulation Crimper Stripper

More information

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

section-page Table 1. Transfer switching device ratings. Conditional short circuit current Operator s Manual 7000 Series ATS Automatic Transfer Switching Equipment D design 30 through 200 amperes TABLE OF CONTENTS section-page INSTALLATION... 1-1 Enclosures and Mounting... 1-1 Power Connections...

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com INSTRUCTIONS INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE r \ FIG. 1. Cutaway View of Typical Switch. I.L. 46-723-1 DESCRIPTION INSTALLATION MAINTENANCE INSTRUCTIONS THE INERTEEN AND OIL INSULATED FEEDER SWITCH provides complete switching facilities in a minimum

More information

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by

More information

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 Installation Instructions Series I Encapsulated Current Limiting Fuse GWI 701-4 Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 TABLE OF CONTENTS Section Page 1. Introduction 2 2. Safety Information

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

CENTERLINE 2100 Motor Control Centers 600A, 800A, and 1200A Bolted Pressure Contact Switch

CENTERLINE 2100 Motor Control Centers 600A, 800A, and 1200A Bolted Pressure Contact Switch Instructions CENTERLINE 2100 Motor Control Centers 600A, 800A, and 1200A Bolted Pressure Contact Switch CENTERLINE 2100 Motor Control Centers Introduction The intent of this publication is to provide field

More information

IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation.

IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation. Industrial Turbo Meters Sizes 2" through 6" Installation & Operation Manual IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation. BadgerMeter,Inc. IOM-003-15 Part No.

More information

Installation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet

Installation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet....

More information

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label. Operator s Manual 7000 Series ACTS Automatic Closed Transition es 150 through 4000 amps TABLE OF CONTENTS section-page INSTALLATION... 1-1 Mounting and Line Connections... 1-1 Auxiliary Circuits and Harness...

More information

920 Remote Control Switches

920 Remote Control Switches 920 Remote Control Switches REMOTE CONTROL SWITCHES Service Bulletin This service bulletin for ASCO 920 Remote Control Switches explains how to replace the main s, operator coil, control s, and how to

More information

OLYMPIAN MODEL 740 Operation and Service Manual

OLYMPIAN MODEL 740 Operation and Service Manual OLYMPIAN MODEL 740 Operation and Service Manual P/N 133911-102 FCI MANUAL P/N 133865-001 Data herein has been verified and validated and believed adequate for the intended use. If the machine or procedures

More information

TM-1620 OPERATING INSTRUCTIONS AND OWNERS MANUAL

TM-1620 OPERATING INSTRUCTIONS AND OWNERS MANUAL TM-1620 OPERATING INSTRUCTIONS AND OWNERS MANUAL tracopackaging.com 800-284-WRAP 620 SOUTH 1325 WEST OREM, UT. PHONE 800-284-WRAP (9727) IMPORTANT: READ ALL INSTRUCTIONS BEFORE OPERATING EQUIPMENT Your

More information

'99-03 CHEVROLET/GMC IFS 4WD 6" SUSPENSION SYSTEM P/N INSTALLATION INSTRUCTIONS

'99-03 CHEVROLET/GMC IFS 4WD 6 SUSPENSION SYSTEM P/N INSTALLATION INSTRUCTIONS 1/16/04 '99-03 CHEVROLET/GMC IFS 4WD 6" SUSPENSION SYSTEM P/N. 10-41099 INSTALLATION INSTRUCTIONS NOTE: Each Lift Kit and options to Lift Kits are packaged separately. Therefore, installation procedures

More information

Installation Instructions

Installation Instructions Page 6300-S-1 Installation Instructions 1. Read complete instructions before proceeding and do not discard packing materials until any/all loose items are located. Also, make sure that the installation

More information

MODEL A OLD NORCROSS ROAD LAWRENCEVILLE, GA (770) TEL (770) FAX (877) TOLL FREE

MODEL A OLD NORCROSS ROAD LAWRENCEVILLE, GA (770) TEL (770) FAX (877) TOLL FREE USER MANUAL RAPID-ROLL DOOR OWNER S MANUAL MODEL 230 975-A OLD NORCROSS ROAD LAWRENCEVILLE, GA 30045 (770) 338-5000 TEL (770) 338-5034 FAX (877) 925-2468 TOLL FREE Part # 6410T0009 Architectural Drawing

More information

WARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation

WARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation PAGE 1 TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV QUALIFIED PERSONS...1 SAFETY INFORMATION...2 INTRODUCTION...3 Receiving...3 Handling...3 Storage...3 GENERAL DESCRIPTION...3

More information

Model DFR 070/156/220 Rotary Actuator

Model DFR 070/156/220 Rotary Actuator Figure 1 DFR 156 TABLE OF CONTENTS General 2 Actuator Assembly 18 Scope 2 Bushing / Yoke Assembly 18 Principles of Operation 2 Spring Barrel Assembly 18 Safety Caution 2 Diaphragm Plate Assembly 20 Specifications

More information