Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Size: px
Start display at page:

Download "Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters"

Transcription

1 S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters Table of Contents Section Page Section Page Introduction Qualified Persons Read this Instruction Sheet Retain this Instruction Sheet Proper Application Warranty Warranty Qualifications Safety Information Understanding Safety-Alert Messages Following Safety Instructions... 4 Replacement Instructions and Labels Safety Precautions Tools Needed Ampere Bushing-Well Adapters Removal Installation Ampere Bushing-Well Adapters Removal Installation October 17, 2016 S&C Electric Company , all rights reserved Instruction Sheet

2 Introduction Qualified Persons Read this Instruction Sheet Retain this Instruction Sheet Proper Application WARNING The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of underground electric power distribution equipment along with the associated hazards. A qualified person is one who is trained and competent in: The skills and techniques necessary to distinguish exposed live parts from non-live parts of electrical equipment. The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed. The proper use of the special precautionary techniques, per sonal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment. These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. This instruction sheet covers the replacement of 600-ampere bushing adapters or 200-ampere bushing-well adapters used in S&C Vista SD Underground Switchgear. Read this instruction sheet thoroughly and carefully before replacing 600-ampere bushing adapters or 200-ampere bushing-well adapters. Familiarize yourself with the safety information and precautions on pages 4 and 5. The latest version of this publication is available online in PDF format at sandc.com/support/product-literature.asp This instruction sheet is a permanent part of your S&C Vista SD Underground Distribution Switchgear. Designate a location where you can easily retrieve and refer to it. CAUTION The equipment in this publication must be selected for a specific application. The application must be within the ratings furnished for the equipment. 2 S&C Instruction Sheet

3 Introduction Warranty Warranty Qualifications The warranty and/or obligations described in S&C s standard conditions of sale, as set forth in Price Sheet 150, plus any special warranty provisions, as set forth in the applicable product-line specification bulletin, are exclusive. The remedies provided in the former for breach of these warranties shall constitute immediate purchaser s or end user s exclusive remedy and a fulfillment of all seller s liability. In no event shall seller s liability to immediate purchaser or end user exceed the price of the specific product which gives rise to immediate purchaser s or end user s claim. All other warranties whether express or implied or arising by operation of law, course of dealing, usage of trade or otherwise, are excluded. The only warranties are those stated in Price Sheet 150, and THERE ARE NO EXPRESS OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY EXPRESS WARRANTY OR OTHER OBLIGATION PROVIDED IN PRICE SHEET 150 IS GRANTED ONLY TO THE IMMEDIATE PURCHASER AND END USER, AS DEFINED THEREIN. OTHER THAN AN END USER, NO REMOTE PURCHASER MAY RELY ON ANY AFFIRMATION OF FACT OR PRIMISE THAT RELATES TO THE GOODS DESCRIBED HEREIN, ANY DESCRIPTION THAT RELATES TO THE GOODS, OR ANY REMEDIAL PROMISE INCLUDED IN PRICE SHEET 150. Seller s standard warranty does not apply to components not of S&C manufacture that are supplied and installed by the purchaser, or to the ability of seller s equipment to work with such components. S&C Instruction Sheet

4 Safety Information Understanding Safety-Alert Messages There are several types of safety-alert messages which may appear throughout this instruction sheet as well as on labels and tags attached to the S&C Vista SD Underground Distribution Switchgear. Familiarize yourself with these types of messages and the importance of the various signal words, as explained below. DANGER DANGER identifies the most serious and immediate hazards which will likely result in serious personal injury or death if instructions, including recommended precautions, are not followed. WARNING WARNING identifies hazards or unsafe practices which can result in serious personal injury or death if instructions, including recommended precautions, are not followed. CAUTION CAUTION identifies hazards or unsafe practices which can result in minor personal injury or product or property damage if instructions, including recommended precautions, are not followed. NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed. Following Safety Instructions If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor. Their telephone numbers are listed on S&C s website sandc.com Or call the S&C Global Support and Monitoring Center at NOTICE Read this instruction sheet thoroughly and carefully before replacing 600-ampere bushing adapters or 200-ampere bushing-well adapters. Replacement Instructions and Labels If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office, S&C Authorized Distributor, S&C Head quarters, or S&C Electric Canada Ltd. It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distrib utor, S&C Headquarters, or S&C Electric Canada Ltd. 4 S&C Instruction Sheet

5 Safety Precautions DANGER S&C Vista SD Underground Distribution Switchgear operates at high voltage. Failure to observe the precautions below will result in serious personal injury or death. Some of these precautions may differ from your company s operating procedures and rules. Where a discrepancy exists, follow your company s operating procedures and rules. 1. Qualified Persons. Access to the Vista SD underground distribution switchgear must be restricted only to qualified persons. See Qualified Persons on page Safety Procedures. Always follow safe operating procedures and rules. Always maintain proper clearance from energized components. 3. Personal Protective Equipment. Always use suitable protective equipment such as rubber gloves, rubber mats, hard hats, safety glasses, and arc-flash clothing in accordance with safe operating procedures and rules. 4. Doors. High-voltage compartment doors must be securely closed and latched, with padlocks in place at all times unless work is being performed inside the enclosure. 5. Key Interlocks. Optional key interlocks, if furnished, must be in place. Check the operating sequence of key interlocks to verify proper sequencing. After the switchgear is installed, destroy all duplicate keys or make them accessible only to authorized persons so that the keyinterlock scheme will not be compromised. 6. Opening Doors. Do not apply any undue force when attempting to open a door. The use of undue force may damage the door-latching mechanism. 7. Safety Labels. Do not remove or obscure any of the DANGER, WARNING, CAUTION, or NOTICE labels. 8. Energized Bushings. Always assume that the bushings are energized unless proven otherwise by test, by visual evidence of an open-circuit condition at the load-interrupter switch or fault interrupter, or by observing that the loadinterrupter switch or fault interrupter is grounded. 9. Backfeed. Bushings, cables, load-interrupter switches, and fault interrupters may be energized by backfeed. 10. Grounding. Vista SD Switchgear must be connected to a suitable earth ground before energizing, and at all times when energized. The ground wire(s) must be bonded to the system neutral, if present. If the system neutral is not present, proper precautions must be taken to ensure that the local earth ground cannot be severed or removed. After the switchgear has been completely disconnected from all sources of power and tested for voltage, prop-erly ground the load-interrupter switches and fault interrupters before touching any bushings or components that are to be inspected, replaced, serviced, or repaired. 11. Load-Interrupter Switch or Fault Interrupter Position. Always confirm the open/closed position of the load-interrupter switch or fault interrupter by visually observing the position of the isolating disconnect. Load-interrupter switch or fault interrupter may be energized by backfeed. Load-interrupter switch or fault interruper may be energized in any position. 12. Maintaining Proper Clearance. Always maintain proper clearance from energized components. S&C Instruction Sheet

6 Tools Needed The following tools are needed to remove and install 600-ampere bushing adapters or 200-ampere bushing-well adapters used on S&C Vista SD Underground Distribution Switchgear. See Figures 1 and 2 on page 7. S&C Bushing and Bushing-Well Adapter Assembly Tool. See Figure 3 on page 7. Socket wrench 1-inch socket with extension ⅞-inch socket with extension Torque wrench (10-60 ft.-lbs.) Silicone grease (Dow Corning Molykote 111 or Novagard G661 or equivalent) Isopropyl alcohol (to clean bushings). CAUTION Isopropyl alcohol is the only solvent approved for cleaning 600-ampere bushing adapters or 200-ampere bushing-well adapters used on S&C Vista SD Underground Distribution Switchgear. Petroleum-based solvents should not be used on or around Vista SD underground distribution switchgear. Failure to follow these precautions can result in damamge to the bushing or bushing-well adapters. 6 S&C Instruction Sheet

7 Tools Needed Figure Ampere Bushing Adapter (CHA-1522). Figure Ampere Bushing-Well Adapter (CHA-1732). Figure 3. S&C Bushing and Bushing-Well Adapter Assembly Tool (CHA-2728). S&C Instruction Sheet

8 200-Ampere Bushing-Well Adapters Removal Step 1 De-energize and ground the cables following user s operating procedures and rules. Then remove the cables from the switchgear assembly. DANGER Before touching the bushing to be replaced, always disconnect load-interrupter switches and fault interrupters from all power sources (including backfeed), test for voltage, and properly ground them. Failure to observe these precautions will result in serious personal injury or death. Step 2 Using a socket wrench with a ⅞-inch socket and socket extension, remove the threaded stud at the center of the bushing-well adapter. Rotate the stud counterclockwise. See Figure 4. Threaded stud Figure Ampere bushing-well adapter with threaded stud installed. Step 3 Fully insert the S&C Bushing and Bushing-Well Adapter Assembly Tool (CHA-2728) into the bushing-well adapter. By hand, rotate the tool a few degrees in either direction to engage the hex feature of the tool with the bushing-well adapter attachment bolt. Step 4 Using a socket wrench with a 1-inch socket and socket extension, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool counterclockwise to loosen the bushing-well adapter. See Figure 5. Figure 5. Loosening the bushing-well adapter. Step 5 Grasp the bushing-well adapter, and continue rotating the S&C Bushing and Bushing-Well Adapter Assembly Tool counterclockwise until the bushing-well adapter can be pulled off of the bushing interface. See Figure 6. Figure 6. Removing the bushing-well adapter. 8 S&C Instruction Sheet

9 200-Ampere Bushing-Well Adapters Installation Step 1 Thoroughly clean the light-gray conical bushing interface on the switchgear assembly using a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Step 2 Clean the inside of the larger diameter end of the replacement bushing-well adapter with a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Figure 7. Orientation features aligned. Figure 8. Orientation features misaligned. Step 3 To attach the bushing-well adapter to the bushing interface on the switchgear assembly, insert the S&C Bushing and Bushing-Well Adapter Assembly Tool into the bushing-well adapter. By hand, rotate the tool a few degrees in either direction to engage the hex feature of the tool with the bushing-well adapter attachment bolt. Holding the tool and the bushing-well adapter as an assembly, position the bushing-well adapter on the bushing interface while aligning the orientation features. See Figures 7 and 8. Step 4 While pushing on the bushing-well adapter, by hand, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool clockwise to engage the bolt in the bushing-well adapter with the bushing interface on the switchgear assembly. See Figure 9. Continue rotating the wrench clockwise until the bushing-well adapter is fully attached to the bushing interface of the switchgear assembly; tighten and torque to a value of ft.-lbs. Figure 9. Tightening the bushing-well adapter. Check that the bushing-well adapter is positioned under the ground clip. See Figure 16 on page 11. Step 5 Insert the threaded stud into the bushing-well adapter, with the larger diameter end facing inwards. Using a socket wrench with a socket extension and a ⅞-inch socket rotate the stud clockwise; tighten the stud to a value of 12 ft.-lbs. of torque. See Figure 10. Larger diameter Smaller diameter Step 6 Clean the bushing-well adapter interface using a soft lint-free cloth dipped in isopropyl alcohol. Allow the alcohol to thoroughly evaporate. Apply a smooth, even coating of silicone grease before attaching the cables to the switchgear assembly. Figure 10. Larger diameter of threaded stud faces into bushing-well adapter. S&C Instruction Sheet

10 600-Ampere Bushing Adapters Removal Step 1 De-energize and ground the cables following user s operating procedures and rules. Then remove the cables from the switchgear assembly. DANGER Before touching the bushing to be replaced, always disconnect load-interrupter switches and fault interrupters from all power sources (including backfeed), test for voltage, and properly ground them. Failure to observe these precautions will result in serious personal injury or death. Figure 11. Loosening the bushing adapter. Step 2 Fully insert the S&C Bushing and Bushing-Well Adapter Assembly Tool (CHA-2728) into the bushing adapter. By hand, rotate the tool a few derees in either direction to engage the hex feature of the tool with the bushing adapter attachment bolt. Step 3 Using a socket wrench with a 1-inch socket and socket extension, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool counterclockwise to loosen the bushing adapter. See Figure 11. Step 4 Grasp the black portion of the bushing adapter, NOT the dark gray portion (see Figure 12), and continue rotating the S&C Bushing and Bushing- Well Adapter Assembly Tool counterclockwise until the bushing adapter can be pulled off the bushing interface. Do NOT grasp the gray tapered portion of the bushing adapter, as it is covered with silicone grease. See Figure 13. Figure 12. Correct method for removal of the bushing adapter. Figure 13. Incorrect method for removal of the bushing adapter. 10 S&C Instruction Sheet

11 600-Ampere Bushing Adapters Installation Step 1 Thoroughly clean the light-gray conical bushing interface on the switchgear assembly using a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Step 2 Clean the dark-gray recessed cone on the inside of the bushing adapter with a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Figure 14. Orientation features aligned. Figure 15. Orientation features misaligned. Step 3 To attach the bushing adapter to the bushing interface on the switchgear assembly, insert the S&C Bushing and Bushing-Well Adapter Assembly Tool into the bushing adapter. By hand, rotate the tool a few degrees in either direction to engage the hex feature of the tool with the bushing adapter attachment bolt. Holding the tool and the bushing adapter as an assembly, position the bushing adapter on the bushing interface while aligning the orientation features. See Figures 14 and 15. Check that the bushing adapter is positioned under the ground clip. See Figure 16. Figure 16. Bushing adapter should be positioned under the groud clip. Step 4 While pushing on the bushing adapter, by hand, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool clockwise to engage the bolt in the bushing adapter with the bushing interface on the switchgear assembly. See Figure 17. Continue rotating the wrench clockwise until the bushing adapter is fully attached to the bushing interface of the switchgear assembly; tighten and torque to a value of ft.-lbs. Step 5 Clean the dark gray conical section of the bushing adapter using a soft lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Apply a smooth, even coating of silicone grease before attaching the cables to the switchgear assembly. Figure 17. Tightening the bushing adapter. S&C Instruction Sheet

Installation and Operation

Installation and Operation S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction

More information

S&C Vista Underground Distribution Switchgear

S&C Vista Underground Distribution Switchgear S&C Vista Underground Distribution Switchgear Pad-Mounted, Vault-Mounted, and UnderCover Styles Instructions For Installation and Operation of Portable Motor Operator TABLE OF CONTENTS Section Page Section

More information

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance S&C Regulator Bypass Switches Outdoor Distribution (14.4 kv through 25 kv) Type XL (Sequenced) and Type NL (Non-sequenced) Installation, Operation, and Maintenance Table of Contents Section Page Section

More information

Instructions for Installation and Operation

Instructions for Installation and Operation S&C Alduti-Rupter Switches Three-Pole Side-Break Heavy-Duty Style Reciprocating Operating Mechanism 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section Page Section Page INTRODUCTION

More information

Instructions for Installation

Instructions for Installation S&C Vista Underground Distribution Switchgear Wind Turbine Style Instructions for Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet....

More information

Inspection and Maintenance

Inspection and Maintenance Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv, 27 kv, and 34.5 kv) Inspection and Maintenance Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this

More information

Installation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet

Installation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet....

More information

Cleaning Flooded Gear

Cleaning Flooded Gear S&C Manual PMX Modular Metal-Enclosed Switchgear Outdoor Distribution (13.8 kv and 25 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding

More information

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...

More information

Instructions for Installation and Operation

Instructions for Installation and Operation S&C Alduti-Rupter Switches Outdoor Distribution Three-Pole Vertical-Break Style Reciprocating Operating Mechanism 25/34.5 kv and 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section

More information

Installation and Operation

Installation and Operation S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Installation and Operation Table

More information

Cleaning Flooded Gear

Cleaning Flooded Gear S&C Manual Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding

More information

Installation and Operation

Installation and Operation S&C Alduti-Rupter Switches Outdoor Distribution (46 kv) Three-Pole Double-Break Integer Style Reciprocating Operating Mechanism No Catalog Number Supplement and Operation Table of Contents Section Page

More information

Operation. S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles. Table of Contents

Operation. S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles. Table of Contents S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Operation Table of Contents Section Page Section Page Introduction Operation Qualified Persons..............................

More information

Instructions for Installation

Instructions for Installation S&C Circuit-Switchers Mark VI Outdoor Transmission 69 kv through 138 kv Option U, User-Furnished Mounting Structure Instructions for Installation TABLE OF CONTENTS Section Page Section Page INTRODUCTION

More information

S&C Source-Transfer Vista Underground Distribution Switchgear

S&C Source-Transfer Vista Underground Distribution Switchgear S&C Source-Transfer Vista Underground Distribution Switchgear Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles Instructions For Installation Section Page Section Page INTRODUCTION

More information

S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv)

S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv) S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv) Installation Table of Contents Section Page Section Page

More information

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper

More information

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Catalog Number Supplement R3

More information

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com

More information

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS ) Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable

More information

IB PowlVac ITE-HK Remote Racking Device

IB PowlVac ITE-HK Remote Racking Device IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking

More information

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 Installation Instructions Series I Encapsulated Current Limiting Fuse GWI 701-4 Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 TABLE OF CONTENTS Section Page 1. Introduction 2 2. Safety Information

More information

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,

More information

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER

More information

Installation And Operation

Installation And Operation S&C Series 2000 Circuit-Switchers Outdoor Transmission Model 2020 With Vertical Interrupters and Side-Break Power-Operated Disconnect 69 kv through 138 kv Installation And Operation Table of Contents Section

More information

Effective November 2016 Supersedes February 2012 (S )

Effective November 2016 Supersedes February 2012 (S ) Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling

More information

ibusway for Data Center

ibusway for Data Center ibusway for Data Center PBPQOD Plug-In Units with 15 60 A Circuit Breakers for Use On Busway Straight Sections Class 5600 Installation S1B99523 06/2012 Hazard Categories and Special Symbols Read these

More information

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES

More information

Operator's Manual. Storage System. Ultrasound Probe Cabinet. Manufactured by:

Operator's Manual. Storage System. Ultrasound Probe Cabinet. Manufactured by: Storage System Ultrasound Probe Cabinet Operator's Manual Manufactured by: CIVCO Medical Solutions 102 First Street South Kalona, IA 52247 USA 319.248.6757 / 800.445.6741 WWW.CIVCO.COM Copyright 2018 All

More information

Effective November 2016 Supersedes September 1998 (S )

Effective November 2016 Supersedes September 1998 (S ) Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 (S240-84-1) X-Limiter Hinge-Mount for S&C SMD -20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES

More information

Installation and Operation

Installation and Operation S&C Series 2000 Circuit-Switchers Outdoor Transmission Model 2030 With Vertical Interrupters and Without Disconnect 69 kv through 230 kv Installation and Operation Table of Contents Section Page Section

More information

Operation. S&C Source-Transfer Vista Underground Distribution Switchgear. Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles

Operation. S&C Source-Transfer Vista Underground Distribution Switchgear. Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles S&C Source-Transfer Vista Underground Distribution Switchgear Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles Operation This publication contains instructions for manual and pushbutton

More information

DeZURIK 2 20" BOS BUTTERFLY VALVES

DeZURIK 2 20 BOS BUTTERFLY VALVES 2 20" BOS BUTTERFLY VALVES Instruction D10459 October 2013 2-20 BOS Butterfly Valves Instructions These instructions provide information about BOS Butterfly Valves. They are for use by personnel who are

More information

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions Voltage Regulators MN225025EN Effective March 2016 Supersedes S225-50-48 November 2008 COOPER POWER SERIES QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit 5791646A26 installation

More information

Effective March 2015 Supersedes S August 2012

Effective March 2015 Supersedes S August 2012 Fusing Equipment MN132003EN Effective March 2015 Supersedes S240-40-2 August 2012 COOPER POWER SERIES 23 and 38 kv sidewall-mounted and 23 kv cover-mounted Bay-O-Net fuse assembly installation instructions

More information

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF

More information

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN Fusing Equipment MN132014EN Effective November 2016 Supersedes July 2005 (S240-61-1) Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND

More information

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN Fusing Equipment MN132017EN Effective November 2016 Supersedes October 1998 (S240-82-1) ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND

More information

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN Fusing Equipment MN132031EN Effective November 2016 Supersedes July 2008 (S240-92-1) COOPER POWER Edison Modular Fuse (EMF) Installation Instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

WARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation

WARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation PAGE 1 TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV QUALIFIED PERSONS...1 SAFETY INFORMATION...2 INTRODUCTION...3 Receiving...3 Handling...3 Storage...3 GENERAL DESCRIPTION...3

More information

Effective June 2016 New Issue

Effective June 2016 New Issue Voltage Regulators MN225035EN Effective June 2016 New Issue COOPER POWER SERIES QD8 Quik-Drive Tap-Changer Switch Assembly Kit 5740785B13 and Switch Neutral Stationary Assembly Kit 5791646A48 Installation

More information

Installation Instructions For Motor Control Center (MCC) Units

Installation Instructions For Motor Control Center (MCC) Units s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground

More information

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version IB131018EN Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version Contents Description Page 1. Introduction...2 2. Description...2

More information

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Upright and Triangular Mounting Configurations Catalog Number Supplement R3 and Earliern Installation

More information

READ AND SAVE THESE INSTRUCTIONS. ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner. Trion

READ AND SAVE THESE INSTRUCTIONS. ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner. Trion READ AND SAVE THESE INSTRUCTIONS ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner Trion www.trioniaq.com Installation, Operation, & Maintenance Manual 1. Warranty 2. Safety & Warnings ComfortBreeze

More information

SecoVac * Ground & Test Device

SecoVac * Ground & Test Device GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6

More information

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the

More information

Nor East. Instructions Safety Messages. Inspection. Parts. DeZURIK Service. Type 05 Pneumatic Actuator Used With Globe Valves

Nor East. Instructions Safety Messages. Inspection. Parts. DeZURIK Service. Type 05 Pneumatic Actuator Used With Globe Valves Instructions Safety Messages These instructions are intended for personnel who are responsible for installation, operation and maintenance of your DeZURIK Actuator. All safety messages in the instructions

More information

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...

More information

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN Reclosers MN280070EN Effective May 2017 Supersedes July 2014 (S280-80-23) COOPER POWER Dielectric grease application to recloser cable instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

WELDING HELMET INSTRUCTIONS. Part #20520

WELDING HELMET INSTRUCTIONS. Part #20520 WELDING HELMET INSTRUCTIONS Part #20520 EASTWOOD WELDING HELMETS are specifically designed to provide maximum eye and face protection from harmful UV and IR radiation emitted when welding, in a lightweight,

More information

TONS. Before each shift: Before operating: Before initial operation of hoist:

TONS. Before each shift: Before operating: Before initial operation of hoist: LEVER HOIST 0.25 9 TONS Manual Notice It is the responsibility of the owner/user to install, inspect, test, maintain, and operate these lever hoists in accordance with ASME B30.21, Safety Standard for

More information

BEFORE YOU BEGIN LIST OF COMPONENTS. Isopropyl SWITCH SCOTCH-BRITE PAD ALCOHOL PREP PAD SWITCH HARNESS REVOLVER PCM COVER STICKER

BEFORE YOU BEGIN LIST OF COMPONENTS. Isopropyl SWITCH SCOTCH-BRITE PAD ALCOHOL PREP PAD SWITCH HARNESS REVOLVER PCM COVER STICKER User Manual TABLE OF CONTENTS BEFORE YOU BEGIN...3 LIST OF COMPONENTS... 3 REVOLVER INSTALLATION 95-97 Trucks...4 REVOLVER INSTALLATION 98-03 Trucks...7 SWITCH INSTALLATION...12 SAFETY WARNING & CAUTION...14

More information

rechargeable umbrella light

rechargeable umbrella light rechargeable umbrella light Model 98154 assembly And Operation Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly

More information

Item #21484 XL VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS

Item #21484 XL VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS Item #21484 XL VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS EASTWOOD WELDING HELMETS are specifically designed to provide maximum eye and face protection from harmful UV and IR radiation emitted when

More information

Item #21483 LARGE VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS

Item #21483 LARGE VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS Item #21483 LARGE VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS EASTWOOD WELDING HELMETS are specifically designed to provide maximum eye and face protection from harmful UV and IR radiation emitted

More information

p.t.o. Slip clutch Read this material before using this product. Failure to do so can result in serious injury. Save this manual.

p.t.o. Slip clutch Read this material before using this product. Failure to do so can result in serious injury. Save this manual. p.t.o. Slip clutch 65517 Installation Instructions Distributed exclusively by Harbor Freight Tools. 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our website at: http://www.harborfreight.com Read

More information

OPERATOR S AND PARTS MANUAL PALLET FORKS. Part Number: MODEL NUMBER: Rev. 4

OPERATOR S AND PARTS MANUAL PALLET FORKS. Part Number: MODEL NUMBER: Rev. 4 OPERATOR S AND PARTS MANUAL PALLET FORKS SERIAL NUMBER: Manual Number: OM642 Part Number: 75542 MODEL NUMBER: Rev. 4 800-456-7100 I www.paladinlcg.com 503 Gay Street, Delhi, IA 52223, United States of

More information

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3 SIEMENS XJ-L Busway Systems Storage, Installation and Maintenance Instructions for... Piece No. 32-J-1010-01 Rev 3 ~DANGER Hazardous voltages and exposed electrical conductors will cause death, serious

More information

1000-LB. MOTORCYCLE LIFT TABLE OWNER S MANUAL

1000-LB. MOTORCYCLE LIFT TABLE OWNER S MANUAL 1000-LB. MOTORCYCLE LIFT TABLE OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety

More information

Installation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission.

Installation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission Installation Table of Contents Section Page Section Page Introduction Qualified Persons....2 Read this

More information

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel Gas-Insulated Switchgear GHA Gas-Insulated Switchgear Switchgear extension and replacement of a panel During this work, essential parts of the switchgear remain in operation No. AGS 535 066-01 Edition

More information

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained

More information

Operating Instructions & Parts Manual. Fuel Tank Adapter

Operating Instructions & Parts Manual. Fuel Tank Adapter Operating Instructions & Parts Manual Fuel Tank Adapter Model Number 40080 Capacity 80 lb.! This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN

Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180 ST Series Service Tester Phase Identifier Operating Instructions ST500PGN REV. ED. 101229 CONTENTS Limitation of Warranty and Liability

More information

580RK SERVICE GUIDELINES For coupling models: 580 & 580J

580RK SERVICE GUIDELINES For coupling models: 580 & 580J 580 Coupling THE FIRST NAME IN QUALITY COUPLINGS 580RK SERVICE GUIDELINES For coupling models: 580 & 580J BEFORE GETTING STARTED: This procedure should only be performed by a qualified mechanic. Measure

More information

Figure 1. Kearney Type HX cutout.

Figure 1. Kearney Type HX cutout. Fusing Equipment Kearney Open Distribution Cutouts Type HX Installation Instructions Service Information KS010-01-1 CONTENTS Product Information...........................1 Safety Information............................2

More information

Nor East. Instructions. Safety Messages. Inspection. Parts Nor East Controls. Service. Type 05 Air-O-Motor Actuator Used With Globe Valves

Nor East. Instructions. Safety Messages. Inspection. Parts Nor East Controls. Service. Type 05 Air-O-Motor Actuator Used With Globe Valves Instructions Safety Messages These instructions are intended for personnel who are responsible for installation, operation and maintenance of your Nor East Controls Actuator. All safety messages in the

More information

UniTorq UTQ Quarter-Turn Actuator Installation and Operation Manual

UniTorq UTQ Quarter-Turn Actuator Installation and Operation Manual UniTorq UTQ 1.5 6.4 Quarter-Turn Actuator Installation and Operation Manual Thank you for purchasing our UTQ 1.5-6.0 Electric Actuators Before installation or operation of the actuator carefully review

More information

Two-way cable interlock kit for Magnum drawout circuit breakers

Two-way cable interlock kit for Magnum drawout circuit breakers iwarning (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK

More information

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot. Fault Indicators MN320011EN Effective March 2017 Supersedes August 2004 (S320-80-1) COOPER POWER S.T.A.R. Hot line voltage indicator installation instructions SERIES Indicator boot Internal sleeve Pulling

More information

Hydraulic Wheel Dolly

Hydraulic Wheel Dolly Hydraulic Wheel Dolly Operating Instructions & Parts Manual Model Number HW93766 Capacity 3/4 Ton Made in the U.S.A. This is the safety alert symbol. It is used to alert you to potential personal injury

More information

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification

More information

Vacuum Circuit Breaker (Vehicle)

Vacuum Circuit Breaker (Vehicle) Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment

More information

MFG. CO. INC. DODGE CITY, KANSAS (620) Electric Truck Auger. Owners Manual

MFG. CO. INC. DODGE CITY, KANSAS (620) Electric Truck Auger. Owners Manual MFG. CO. INC. DODGE CITY, KANSAS 67801 (620) 225-0263 4 Electric Truck Auger Owners Manual Sept. 2005 The Farm And Industrial Equipment Institute Safety Alert Symbol BE ALERT! Your Safety is Involved Be

More information

Instruction Manual PC104/PC105 3-PHASE SOCKET TESTER. Check out what else you can get from Martindale:

Instruction Manual PC104/PC105 3-PHASE SOCKET TESTER. Check out what else you can get from Martindale: Check out what else you can get from Martindale: 17th Edition Testers Accessories Calibration Equipment Continuity Testers Electricians Kits Environmental Products Full Calibration & Repair Service Fuse

More information

Installation. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Table of Contents

Installation. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Table of Contents S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons.............................. 2 Read this

More information

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES Fault Indicators S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions Service Information S320-40-1 Contents Product Information...........................1 Safety Information............................2

More information

1250 LB. CAPACITY MECHANICAL WHEEL DOLLY

1250 LB. CAPACITY MECHANICAL WHEEL DOLLY 1250 LB. CAPACITY MECHANICAL WHEEL DOLLY 67287 SET-UP AND OPERATING INSTRUCTIONS Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure to do so can result

More information

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN Reclosers MN280014EN Effective September 2015 Supersedes S280-10-6 April 2003 COOPER POWER SERIES Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits DISCLAIMER OF WARRANTIES AND

More information

Installation Power Management Unit Battery Cables and Battery Harness

Installation Power Management Unit Battery Cables and Battery Harness Installation Power Management Unit Battery Cables and Battery Harness Important Safety Messages SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation

More information

60 Series End-Mount Brake Instructions Standard Housing

60 Series End-Mount Brake Instructions Standard Housing Bulletin No. BK4655 (04/18) 60 Series End-Mount Brake Instructions Standard Housing Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and

More information

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN Fusing Equipment MN132024EN RTE EL-BAY-O-NET FUSE Re-Fusing Instructions Effective November 2016 Supersedes June 1991 (S240-72-1) COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY

More information

37SCENE 46SCENE 79SCENE

37SCENE 46SCENE 79SCENE Installation and Operation Instructions LED SCENE LIGHT LED SCENE LIGHT 37SCENE 46SCENE 79SCENE 37SCENE 46SCENE Introduction The 37SCENE, 46SCENE, 79SCENE LED Scene Lights are designed for the emergency

More information

DeZURIK AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators

DeZURIK AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators Instructions D11033 August 2013 Instructions These instructions provide information about AFR3 Filter Regulators. They are for use by personnel

More information

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION

More information

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S ) Pad-mounted Switchgear MN285019EN Effective March 2017 Supersedes February 2007 (S285-10-6) COOPER POWER Type VFI fault interrupter with tri-phase control single-phase trip to three-phase trip conversion

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Safety Notices... 1... 3 Specifications... 3 General... 3 Electrical... 3 Hydraulic Connections... 3 Components... 4 Assembly... 4 Implement Installation... 7 Hydraulic Connections... 9 Closed-Center Hydraulics...

More information

ELB ELB

ELB ELB ELB-35-600 ELB-35-610 600A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical

More information

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S ) Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The

More information

Galaxy Receiving and Unpacking 09/

Galaxy Receiving and Unpacking 09/ Galaxy 5500 20 120 kva 400 V Receiving and Unpacking 09/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS

More information

OPERATOR S MANUAL SINGLE PORT UNIVERSAL CAR CHARGER

OPERATOR S MANUAL SINGLE PORT UNIVERSAL CAR CHARGER OPERATOR S MANUAL SINGLE PORT UNIVERSAL CAR CHARGER P130 Fits Ryobi 7.2 volt-18 volt battery packs BATTERIES SOLD SEPARATELY Your battery charger has been engineered and manufactured to Ryobi s high standard

More information

7.3L POWERSTROKE BANJO BOLT KIT Fits L Powerstroke Diesel. Installation Guide

7.3L POWERSTROKE BANJO BOLT KIT Fits L Powerstroke Diesel. Installation Guide 7.3L POWERSTROKE BANJO BOLT KIT Fits 94-03 7.3L Powerstroke Diesel Installation Guide INSPECT CONTENTS OF THIS KIT THOROUGHLY BEFORE STARTING THE INSTALLATION PROCESS! IF YOU FIND A PROBLEM WITH YOUR PACKAGE:

More information

Technical Manual. DLM Module. This manual should remain with the unit.

Technical Manual. DLM Module. This manual should remain with the unit. Technical Manual DLM Module This manual should remain with the unit. Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this

More information

OnBoard Drum Major Podium

OnBoard Drum Major Podium Assembly and Owner s Manual OnBoard Drum Major Podium CONTENTS CONTENTS................................................................................. 1 SAFETY...................................................................................

More information