Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters
|
|
- Berenice Smith
- 5 years ago
- Views:
Transcription
1 S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters Table of Contents Section Page Section Page Introduction Qualified Persons Read this Instruction Sheet Retain this Instruction Sheet Proper Application Warranty Warranty Qualifications Safety Information Understanding Safety-Alert Messages Following Safety Instructions... 4 Replacement Instructions and Labels Safety Precautions Tools Needed Ampere Bushing-Well Adapters Removal Installation Ampere Bushing-Well Adapters Removal Installation October 17, 2016 S&C Electric Company , all rights reserved Instruction Sheet
2 Introduction Qualified Persons Read this Instruction Sheet Retain this Instruction Sheet Proper Application WARNING The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of underground electric power distribution equipment along with the associated hazards. A qualified person is one who is trained and competent in: The skills and techniques necessary to distinguish exposed live parts from non-live parts of electrical equipment. The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed. The proper use of the special precautionary techniques, per sonal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment. These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. This instruction sheet covers the replacement of 600-ampere bushing adapters or 200-ampere bushing-well adapters used in S&C Vista SD Underground Switchgear. Read this instruction sheet thoroughly and carefully before replacing 600-ampere bushing adapters or 200-ampere bushing-well adapters. Familiarize yourself with the safety information and precautions on pages 4 and 5. The latest version of this publication is available online in PDF format at sandc.com/support/product-literature.asp This instruction sheet is a permanent part of your S&C Vista SD Underground Distribution Switchgear. Designate a location where you can easily retrieve and refer to it. CAUTION The equipment in this publication must be selected for a specific application. The application must be within the ratings furnished for the equipment. 2 S&C Instruction Sheet
3 Introduction Warranty Warranty Qualifications The warranty and/or obligations described in S&C s standard conditions of sale, as set forth in Price Sheet 150, plus any special warranty provisions, as set forth in the applicable product-line specification bulletin, are exclusive. The remedies provided in the former for breach of these warranties shall constitute immediate purchaser s or end user s exclusive remedy and a fulfillment of all seller s liability. In no event shall seller s liability to immediate purchaser or end user exceed the price of the specific product which gives rise to immediate purchaser s or end user s claim. All other warranties whether express or implied or arising by operation of law, course of dealing, usage of trade or otherwise, are excluded. The only warranties are those stated in Price Sheet 150, and THERE ARE NO EXPRESS OR IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY EXPRESS WARRANTY OR OTHER OBLIGATION PROVIDED IN PRICE SHEET 150 IS GRANTED ONLY TO THE IMMEDIATE PURCHASER AND END USER, AS DEFINED THEREIN. OTHER THAN AN END USER, NO REMOTE PURCHASER MAY RELY ON ANY AFFIRMATION OF FACT OR PRIMISE THAT RELATES TO THE GOODS DESCRIBED HEREIN, ANY DESCRIPTION THAT RELATES TO THE GOODS, OR ANY REMEDIAL PROMISE INCLUDED IN PRICE SHEET 150. Seller s standard warranty does not apply to components not of S&C manufacture that are supplied and installed by the purchaser, or to the ability of seller s equipment to work with such components. S&C Instruction Sheet
4 Safety Information Understanding Safety-Alert Messages There are several types of safety-alert messages which may appear throughout this instruction sheet as well as on labels and tags attached to the S&C Vista SD Underground Distribution Switchgear. Familiarize yourself with these types of messages and the importance of the various signal words, as explained below. DANGER DANGER identifies the most serious and immediate hazards which will likely result in serious personal injury or death if instructions, including recommended precautions, are not followed. WARNING WARNING identifies hazards or unsafe practices which can result in serious personal injury or death if instructions, including recommended precautions, are not followed. CAUTION CAUTION identifies hazards or unsafe practices which can result in minor personal injury or product or property damage if instructions, including recommended precautions, are not followed. NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed. Following Safety Instructions If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor. Their telephone numbers are listed on S&C s website sandc.com Or call the S&C Global Support and Monitoring Center at NOTICE Read this instruction sheet thoroughly and carefully before replacing 600-ampere bushing adapters or 200-ampere bushing-well adapters. Replacement Instructions and Labels If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office, S&C Authorized Distributor, S&C Head quarters, or S&C Electric Canada Ltd. It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distrib utor, S&C Headquarters, or S&C Electric Canada Ltd. 4 S&C Instruction Sheet
5 Safety Precautions DANGER S&C Vista SD Underground Distribution Switchgear operates at high voltage. Failure to observe the precautions below will result in serious personal injury or death. Some of these precautions may differ from your company s operating procedures and rules. Where a discrepancy exists, follow your company s operating procedures and rules. 1. Qualified Persons. Access to the Vista SD underground distribution switchgear must be restricted only to qualified persons. See Qualified Persons on page Safety Procedures. Always follow safe operating procedures and rules. Always maintain proper clearance from energized components. 3. Personal Protective Equipment. Always use suitable protective equipment such as rubber gloves, rubber mats, hard hats, safety glasses, and arc-flash clothing in accordance with safe operating procedures and rules. 4. Doors. High-voltage compartment doors must be securely closed and latched, with padlocks in place at all times unless work is being performed inside the enclosure. 5. Key Interlocks. Optional key interlocks, if furnished, must be in place. Check the operating sequence of key interlocks to verify proper sequencing. After the switchgear is installed, destroy all duplicate keys or make them accessible only to authorized persons so that the keyinterlock scheme will not be compromised. 6. Opening Doors. Do not apply any undue force when attempting to open a door. The use of undue force may damage the door-latching mechanism. 7. Safety Labels. Do not remove or obscure any of the DANGER, WARNING, CAUTION, or NOTICE labels. 8. Energized Bushings. Always assume that the bushings are energized unless proven otherwise by test, by visual evidence of an open-circuit condition at the load-interrupter switch or fault interrupter, or by observing that the loadinterrupter switch or fault interrupter is grounded. 9. Backfeed. Bushings, cables, load-interrupter switches, and fault interrupters may be energized by backfeed. 10. Grounding. Vista SD Switchgear must be connected to a suitable earth ground before energizing, and at all times when energized. The ground wire(s) must be bonded to the system neutral, if present. If the system neutral is not present, proper precautions must be taken to ensure that the local earth ground cannot be severed or removed. After the switchgear has been completely disconnected from all sources of power and tested for voltage, prop-erly ground the load-interrupter switches and fault interrupters before touching any bushings or components that are to be inspected, replaced, serviced, or repaired. 11. Load-Interrupter Switch or Fault Interrupter Position. Always confirm the open/closed position of the load-interrupter switch or fault interrupter by visually observing the position of the isolating disconnect. Load-interrupter switch or fault interrupter may be energized by backfeed. Load-interrupter switch or fault interruper may be energized in any position. 12. Maintaining Proper Clearance. Always maintain proper clearance from energized components. S&C Instruction Sheet
6 Tools Needed The following tools are needed to remove and install 600-ampere bushing adapters or 200-ampere bushing-well adapters used on S&C Vista SD Underground Distribution Switchgear. See Figures 1 and 2 on page 7. S&C Bushing and Bushing-Well Adapter Assembly Tool. See Figure 3 on page 7. Socket wrench 1-inch socket with extension ⅞-inch socket with extension Torque wrench (10-60 ft.-lbs.) Silicone grease (Dow Corning Molykote 111 or Novagard G661 or equivalent) Isopropyl alcohol (to clean bushings). CAUTION Isopropyl alcohol is the only solvent approved for cleaning 600-ampere bushing adapters or 200-ampere bushing-well adapters used on S&C Vista SD Underground Distribution Switchgear. Petroleum-based solvents should not be used on or around Vista SD underground distribution switchgear. Failure to follow these precautions can result in damamge to the bushing or bushing-well adapters. 6 S&C Instruction Sheet
7 Tools Needed Figure Ampere Bushing Adapter (CHA-1522). Figure Ampere Bushing-Well Adapter (CHA-1732). Figure 3. S&C Bushing and Bushing-Well Adapter Assembly Tool (CHA-2728). S&C Instruction Sheet
8 200-Ampere Bushing-Well Adapters Removal Step 1 De-energize and ground the cables following user s operating procedures and rules. Then remove the cables from the switchgear assembly. DANGER Before touching the bushing to be replaced, always disconnect load-interrupter switches and fault interrupters from all power sources (including backfeed), test for voltage, and properly ground them. Failure to observe these precautions will result in serious personal injury or death. Step 2 Using a socket wrench with a ⅞-inch socket and socket extension, remove the threaded stud at the center of the bushing-well adapter. Rotate the stud counterclockwise. See Figure 4. Threaded stud Figure Ampere bushing-well adapter with threaded stud installed. Step 3 Fully insert the S&C Bushing and Bushing-Well Adapter Assembly Tool (CHA-2728) into the bushing-well adapter. By hand, rotate the tool a few degrees in either direction to engage the hex feature of the tool with the bushing-well adapter attachment bolt. Step 4 Using a socket wrench with a 1-inch socket and socket extension, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool counterclockwise to loosen the bushing-well adapter. See Figure 5. Figure 5. Loosening the bushing-well adapter. Step 5 Grasp the bushing-well adapter, and continue rotating the S&C Bushing and Bushing-Well Adapter Assembly Tool counterclockwise until the bushing-well adapter can be pulled off of the bushing interface. See Figure 6. Figure 6. Removing the bushing-well adapter. 8 S&C Instruction Sheet
9 200-Ampere Bushing-Well Adapters Installation Step 1 Thoroughly clean the light-gray conical bushing interface on the switchgear assembly using a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Step 2 Clean the inside of the larger diameter end of the replacement bushing-well adapter with a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Figure 7. Orientation features aligned. Figure 8. Orientation features misaligned. Step 3 To attach the bushing-well adapter to the bushing interface on the switchgear assembly, insert the S&C Bushing and Bushing-Well Adapter Assembly Tool into the bushing-well adapter. By hand, rotate the tool a few degrees in either direction to engage the hex feature of the tool with the bushing-well adapter attachment bolt. Holding the tool and the bushing-well adapter as an assembly, position the bushing-well adapter on the bushing interface while aligning the orientation features. See Figures 7 and 8. Step 4 While pushing on the bushing-well adapter, by hand, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool clockwise to engage the bolt in the bushing-well adapter with the bushing interface on the switchgear assembly. See Figure 9. Continue rotating the wrench clockwise until the bushing-well adapter is fully attached to the bushing interface of the switchgear assembly; tighten and torque to a value of ft.-lbs. Figure 9. Tightening the bushing-well adapter. Check that the bushing-well adapter is positioned under the ground clip. See Figure 16 on page 11. Step 5 Insert the threaded stud into the bushing-well adapter, with the larger diameter end facing inwards. Using a socket wrench with a socket extension and a ⅞-inch socket rotate the stud clockwise; tighten the stud to a value of 12 ft.-lbs. of torque. See Figure 10. Larger diameter Smaller diameter Step 6 Clean the bushing-well adapter interface using a soft lint-free cloth dipped in isopropyl alcohol. Allow the alcohol to thoroughly evaporate. Apply a smooth, even coating of silicone grease before attaching the cables to the switchgear assembly. Figure 10. Larger diameter of threaded stud faces into bushing-well adapter. S&C Instruction Sheet
10 600-Ampere Bushing Adapters Removal Step 1 De-energize and ground the cables following user s operating procedures and rules. Then remove the cables from the switchgear assembly. DANGER Before touching the bushing to be replaced, always disconnect load-interrupter switches and fault interrupters from all power sources (including backfeed), test for voltage, and properly ground them. Failure to observe these precautions will result in serious personal injury or death. Figure 11. Loosening the bushing adapter. Step 2 Fully insert the S&C Bushing and Bushing-Well Adapter Assembly Tool (CHA-2728) into the bushing adapter. By hand, rotate the tool a few derees in either direction to engage the hex feature of the tool with the bushing adapter attachment bolt. Step 3 Using a socket wrench with a 1-inch socket and socket extension, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool counterclockwise to loosen the bushing adapter. See Figure 11. Step 4 Grasp the black portion of the bushing adapter, NOT the dark gray portion (see Figure 12), and continue rotating the S&C Bushing and Bushing- Well Adapter Assembly Tool counterclockwise until the bushing adapter can be pulled off the bushing interface. Do NOT grasp the gray tapered portion of the bushing adapter, as it is covered with silicone grease. See Figure 13. Figure 12. Correct method for removal of the bushing adapter. Figure 13. Incorrect method for removal of the bushing adapter. 10 S&C Instruction Sheet
11 600-Ampere Bushing Adapters Installation Step 1 Thoroughly clean the light-gray conical bushing interface on the switchgear assembly using a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Step 2 Clean the dark-gray recessed cone on the inside of the bushing adapter with a clean lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Then apply a smooth, even coating of silicone grease. Figure 14. Orientation features aligned. Figure 15. Orientation features misaligned. Step 3 To attach the bushing adapter to the bushing interface on the switchgear assembly, insert the S&C Bushing and Bushing-Well Adapter Assembly Tool into the bushing adapter. By hand, rotate the tool a few degrees in either direction to engage the hex feature of the tool with the bushing adapter attachment bolt. Holding the tool and the bushing adapter as an assembly, position the bushing adapter on the bushing interface while aligning the orientation features. See Figures 14 and 15. Check that the bushing adapter is positioned under the ground clip. See Figure 16. Figure 16. Bushing adapter should be positioned under the groud clip. Step 4 While pushing on the bushing adapter, by hand, rotate the S&C Bushing and Bushing-Well Adapter Assembly Tool clockwise to engage the bolt in the bushing adapter with the bushing interface on the switchgear assembly. See Figure 17. Continue rotating the wrench clockwise until the bushing adapter is fully attached to the bushing interface of the switchgear assembly; tighten and torque to a value of ft.-lbs. Step 5 Clean the dark gray conical section of the bushing adapter using a soft lint-free cloth dipped in isopropyl alcohol. Allow alcohol to thoroughly evaporate. Apply a smooth, even coating of silicone grease before attaching the cables to the switchgear assembly. Figure 17. Tightening the bushing adapter. S&C Instruction Sheet
Installation and Operation
S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction
More informationS&C Vista Underground Distribution Switchgear
S&C Vista Underground Distribution Switchgear Pad-Mounted, Vault-Mounted, and UnderCover Styles Instructions For Installation and Operation of Portable Motor Operator TABLE OF CONTENTS Section Page Section
More informationInstallation, Operation, and Maintenance
S&C Regulator Bypass Switches Outdoor Distribution (14.4 kv through 25 kv) Type XL (Sequenced) and Type NL (Non-sequenced) Installation, Operation, and Maintenance Table of Contents Section Page Section
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Three-Pole Side-Break Heavy-Duty Style Reciprocating Operating Mechanism 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section Page Section Page INTRODUCTION
More informationInstructions for Installation
S&C Vista Underground Distribution Switchgear Wind Turbine Style Instructions for Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet....
More informationInspection and Maintenance
Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv, 27 kv, and 34.5 kv) Inspection and Maintenance Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this
More informationInstallation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet
Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet....
More informationCleaning Flooded Gear
S&C Manual PMX Modular Metal-Enclosed Switchgear Outdoor Distribution (13.8 kv and 25 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding
More informationPAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons
Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...
More informationInstructions for Installation and Operation
S&C Alduti-Rupter Switches Outdoor Distribution Three-Pole Vertical-Break Style Reciprocating Operating Mechanism 25/34.5 kv and 34.5 kv Instructions for Installation and Operation TABLE OF CONTENTS Section
More informationInstallation and Operation
S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Installation and Operation Table
More informationCleaning Flooded Gear
S&C Manual Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 kv through 34.5 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding
More informationInstallation and Operation
S&C Alduti-Rupter Switches Outdoor Distribution (46 kv) Three-Pole Double-Break Integer Style Reciprocating Operating Mechanism No Catalog Number Supplement and Operation Table of Contents Section Page
More informationOperation. S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles. Table of Contents
S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Operation Table of Contents Section Page Section Page Introduction Operation Qualified Persons..............................
More informationInstructions for Installation
S&C Circuit-Switchers Mark VI Outdoor Transmission 69 kv through 138 kv Option U, User-Furnished Mounting Structure Instructions for Installation TABLE OF CONTENTS Section Page Section Page INTRODUCTION
More informationS&C Source-Transfer Vista Underground Distribution Switchgear
S&C Source-Transfer Vista Underground Distribution Switchgear Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles Instructions For Installation Section Page Section Page INTRODUCTION
More informationS&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv)
S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv) Installation Table of Contents Section Page Section Page
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650023EN Effective October 2016 Supersedes March 2012 (IS550-60-1) COOPER POWER SERIES DTS1242 Deadbreak Bolted Tee Connector: Interface C for Single Core Cable with Copper
More informationInstallation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv
S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Hookstick-Operated Vertical and Tiered-Outboard Mounting Configurations Catalog Number Supplement R3
More informationSM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety
SM-1700 Secondary Shunt Trip Coil Assembly Powered by Safety SM-1700 Secondary Shunt Trip Coil Assembly SM-1700 Contact Information Powell Electrical Systems, Inc. www.powellind.com info@powellind.com
More informationCOOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )
Screened Separable Connectors MN650024EN Effective October 2016 Supersedes March 2012 (IS550-61-1) COOPER POWER SERIES DTB1242 Deadbreak Bolted Companion Tee Connector: Interface C for Single Core Cable
More informationIB PowlVac ITE-HK Remote Racking Device
IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking
More informationGWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004
Installation Instructions Series I Encapsulated Current Limiting Fuse GWI 701-4 Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004 TABLE OF CONTENTS Section Page 1. Introduction 2 2. Safety Information
More informationCOOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN
Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information,
More informationCOOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN
Loadbreak/Deadbreak Connectors MN650016EN Effective July 2018 Supersedes January 2018 COOPER POWER SERIES 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions DISCLAIMER
More informationInstallation And Operation
S&C Series 2000 Circuit-Switchers Outdoor Transmission Model 2020 With Vertical Interrupters and Side-Break Power-Operated Disconnect 69 kv through 138 kv Installation And Operation Table of Contents Section
More informationEffective November 2016 Supersedes February 2012 (S )
Fusing Equipment MN132033EN Effective November 2016 Supersedes February 2012 (S240-97-2) 200 A Fused Loadbreak Elbow Connector Shorting Bar (solid link) Installation Instructions COOPER POWER SERIES Pulling
More informationibusway for Data Center
ibusway for Data Center PBPQOD Plug-In Units with 15 60 A Circuit Breakers for Use On Busway Straight Sections Class 5600 Installation S1B99523 06/2012 Hazard Categories and Special Symbols Read these
More informationCOOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN
Loadbreak Connectors MN650015EN Effective December 2015 Supersedes S500-15-1 October 2013 COOPER POWER SERIES 200 A loadbreak junction 15 and 25 kv class installation instructions DISCLAIMER OF WARRANTIES
More informationOperator's Manual. Storage System. Ultrasound Probe Cabinet. Manufactured by:
Storage System Ultrasound Probe Cabinet Operator's Manual Manufactured by: CIVCO Medical Solutions 102 First Street South Kalona, IA 52247 USA 319.248.6757 / 800.445.6741 WWW.CIVCO.COM Copyright 2018 All
More informationEffective November 2016 Supersedes September 1998 (S )
Fusing Equipment MN132018EN Effective November 2016 Supersedes September 1998 (S240-84-1) X-Limiter Hinge-Mount for S&C SMD -20 Fuse Mounting Assembly and Installation Instructions COOPER POWER SERIES
More informationInstallation and Operation
S&C Series 2000 Circuit-Switchers Outdoor Transmission Model 2030 With Vertical Interrupters and Without Disconnect 69 kv through 230 kv Installation and Operation Table of Contents Section Page Section
More informationOperation. S&C Source-Transfer Vista Underground Distribution Switchgear. Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles
S&C Source-Transfer Vista Underground Distribution Switchgear Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles Operation This publication contains instructions for manual and pushbutton
More informationDeZURIK 2 20" BOS BUTTERFLY VALVES
2 20" BOS BUTTERFLY VALVES Instruction D10459 October 2013 2-20 BOS Butterfly Valves Instructions These instructions provide information about BOS Butterfly Valves. They are for use by personnel who are
More informationCOOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions
Voltage Regulators MN225025EN Effective March 2016 Supersedes S225-50-48 November 2008 COOPER POWER SERIES QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit 5791646A26 installation
More informationEffective March 2015 Supersedes S August 2012
Fusing Equipment MN132003EN Effective March 2015 Supersedes S240-40-2 August 2012 COOPER POWER SERIES 23 and 38 kv sidewall-mounted and 23 kv cover-mounted Bay-O-Net fuse assembly installation instructions
More informationCOOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN
Fusing Equipment MN132011EN Effective January 2016 Supersedes KS1.1-01-1 May 2003 HX-CB loadbreak fuse cutout installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationCOOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN
Deadbreak Apparatus Connectors MN650048EN Effective May 2017 Supersedes April 2008 (S600-12-3) 600 A 15/25 kv class T-OP II connector assembly installation instructions COOPER POWER SERIES DISCLAIMER OF
More informationCOOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN
Fusing Equipment MN132014EN Effective November 2016 Supersedes July 2005 (S240-61-1) Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND
More informationCOOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN
Fusing Equipment MN132017EN Effective November 2016 Supersedes October 1998 (S240-82-1) ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION
More informationCOOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN
Fusing Equipment MN132010EN Effective February 2016 Supersedes S240-64A-1 October 1998 COOPER POWER K-Limiter back-up current-limiting fuse installation instructions SERIES DISCLAIMER OF WARRANTIES AND
More informationCOOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN
Fusing Equipment MN132032EN Effective September 2018 Supersedes November 2016 COOPER POWER SERIES CMU Medium voltage power fuse installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationCOOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN
Fusing Equipment MN132031EN Effective November 2016 Supersedes July 2008 (S240-92-1) COOPER POWER Edison Modular Fuse (EMF) Installation Instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationWARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation
PAGE 1 TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV QUALIFIED PERSONS...1 SAFETY INFORMATION...2 INTRODUCTION...3 Receiving...3 Handling...3 Storage...3 GENERAL DESCRIPTION...3
More informationEffective June 2016 New Issue
Voltage Regulators MN225035EN Effective June 2016 New Issue COOPER POWER SERIES QD8 Quik-Drive Tap-Changer Switch Assembly Kit 5740785B13 and Switch Neutral Stationary Assembly Kit 5791646A48 Installation
More informationInstallation Instructions For Motor Control Center (MCC) Units
s Page 1 of 8 Installation Instructions December, 2013 Installation Instructions For Motor Control Center (MCC) Units Hazardous voltage. Will cause death or serious injury. Always de-energize and ground
More informationInstructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
IB131018EN Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version Contents Description Page 1. Introduction...2 2. Description...2
More informationInstallation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv
S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv Three-Pole Side-Break Integer Style Upright and Triangular Mounting Configurations Catalog Number Supplement R3 and Earliern Installation
More informationREAD AND SAVE THESE INSTRUCTIONS. ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner. Trion
READ AND SAVE THESE INSTRUCTIONS ComfortBreeze UV360-1 SYSTEM 24V Ultra-Violet Air Cleaner Trion www.trioniaq.com Installation, Operation, & Maintenance Manual 1. Warranty 2. Safety & Warnings ComfortBreeze
More informationSecoVac * Ground & Test Device
GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6
More informationType 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear
Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the
More informationNor East. Instructions Safety Messages. Inspection. Parts. DeZURIK Service. Type 05 Pneumatic Actuator Used With Globe Valves
Instructions Safety Messages These instructions are intended for personnel who are responsible for installation, operation and maintenance of your DeZURIK Actuator. All safety messages in the instructions
More informationGE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System
GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...
More informationCOOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN
Reclosers MN280070EN Effective May 2017 Supersedes July 2014 (S280-80-23) COOPER POWER Dielectric grease application to recloser cable instructions SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More informationWELDING HELMET INSTRUCTIONS. Part #20520
WELDING HELMET INSTRUCTIONS Part #20520 EASTWOOD WELDING HELMETS are specifically designed to provide maximum eye and face protection from harmful UV and IR radiation emitted when welding, in a lightweight,
More informationTONS. Before each shift: Before operating: Before initial operation of hoist:
LEVER HOIST 0.25 9 TONS Manual Notice It is the responsibility of the owner/user to install, inspect, test, maintain, and operate these lever hoists in accordance with ASME B30.21, Safety Standard for
More informationBEFORE YOU BEGIN LIST OF COMPONENTS. Isopropyl SWITCH SCOTCH-BRITE PAD ALCOHOL PREP PAD SWITCH HARNESS REVOLVER PCM COVER STICKER
User Manual TABLE OF CONTENTS BEFORE YOU BEGIN...3 LIST OF COMPONENTS... 3 REVOLVER INSTALLATION 95-97 Trucks...4 REVOLVER INSTALLATION 98-03 Trucks...7 SWITCH INSTALLATION...12 SAFETY WARNING & CAUTION...14
More informationrechargeable umbrella light
rechargeable umbrella light Model 98154 assembly And Operation Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly
More informationItem #21484 XL VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS
Item #21484 XL VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS EASTWOOD WELDING HELMETS are specifically designed to provide maximum eye and face protection from harmful UV and IR radiation emitted when
More informationItem #21483 LARGE VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS
Item #21483 LARGE VIEW AUTO DARKENING WELDING HELMET INSTRUCTIONS EASTWOOD WELDING HELMETS are specifically designed to provide maximum eye and face protection from harmful UV and IR radiation emitted
More informationp.t.o. Slip clutch Read this material before using this product. Failure to do so can result in serious injury. Save this manual.
p.t.o. Slip clutch 65517 Installation Instructions Distributed exclusively by Harbor Freight Tools. 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our website at: http://www.harborfreight.com Read
More informationOPERATOR S AND PARTS MANUAL PALLET FORKS. Part Number: MODEL NUMBER: Rev. 4
OPERATOR S AND PARTS MANUAL PALLET FORKS SERIAL NUMBER: Manual Number: OM642 Part Number: 75542 MODEL NUMBER: Rev. 4 800-456-7100 I www.paladinlcg.com 503 Gay Street, Delhi, IA 52223, United States of
More informationSIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3
SIEMENS XJ-L Busway Systems Storage, Installation and Maintenance Instructions for... Piece No. 32-J-1010-01 Rev 3 ~DANGER Hazardous voltages and exposed electrical conductors will cause death, serious
More information1000-LB. MOTORCYCLE LIFT TABLE OWNER S MANUAL
1000-LB. MOTORCYCLE LIFT TABLE OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety
More informationInstallation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission.
S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission Installation Table of Contents Section Page Section Page Introduction Qualified Persons....2 Read this
More informationGHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel
Gas-Insulated Switchgear GHA Gas-Insulated Switchgear Switchgear extension and replacement of a panel During this work, essential parts of the switchgear remain in operation No. AGS 535 066-01 Edition
More informationTRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS
TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS 33220900 DECEMBER 2011 Caution: The equipment covered by these installation instructions should be installed and serviced only by properly trained
More informationOperating Instructions & Parts Manual. Fuel Tank Adapter
Operating Instructions & Parts Manual Fuel Tank Adapter Model Number 40080 Capacity 80 lb.! This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety
More informationInstruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod
Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND
More informationManufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN
Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180 ST Series Service Tester Phase Identifier Operating Instructions ST500PGN REV. ED. 101229 CONTENTS Limitation of Warranty and Liability
More information580RK SERVICE GUIDELINES For coupling models: 580 & 580J
580 Coupling THE FIRST NAME IN QUALITY COUPLINGS 580RK SERVICE GUIDELINES For coupling models: 580 & 580J BEFORE GETTING STARTED: This procedure should only be performed by a qualified mechanic. Measure
More informationFigure 1. Kearney Type HX cutout.
Fusing Equipment Kearney Open Distribution Cutouts Type HX Installation Instructions Service Information KS010-01-1 CONTENTS Product Information...........................1 Safety Information............................2
More informationNor East. Instructions. Safety Messages. Inspection. Parts Nor East Controls. Service. Type 05 Air-O-Motor Actuator Used With Globe Valves
Instructions Safety Messages These instructions are intended for personnel who are responsible for installation, operation and maintenance of your Nor East Controls Actuator. All safety messages in the
More informationUniTorq UTQ Quarter-Turn Actuator Installation and Operation Manual
UniTorq UTQ 1.5 6.4 Quarter-Turn Actuator Installation and Operation Manual Thank you for purchasing our UTQ 1.5-6.0 Electric Actuators Before installation or operation of the actuator carefully review
More informationTwo-way cable interlock kit for Magnum drawout circuit breakers
iwarning (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK
More informationCOOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.
Fault Indicators MN320011EN Effective March 2017 Supersedes August 2004 (S320-80-1) COOPER POWER S.T.A.R. Hot line voltage indicator installation instructions SERIES Indicator boot Internal sleeve Pulling
More informationHydraulic Wheel Dolly
Hydraulic Wheel Dolly Operating Instructions & Parts Manual Model Number HW93766 Capacity 3/4 Ton Made in the U.S.A. This is the safety alert symbol. It is used to alert you to potential personal injury
More informationCOOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing
Fusing Equipment MN132028EN Effective November 2016 Supersedes June 2012 (S240-66-1) COOPER POWER SERIES ELF Current-Limiting Dropout Fuse Installation Instructions Pull ring Housing Lifting eye Identification
More informationVacuum Circuit Breaker (Vehicle)
Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationMFG. CO. INC. DODGE CITY, KANSAS (620) Electric Truck Auger. Owners Manual
MFG. CO. INC. DODGE CITY, KANSAS 67801 (620) 225-0263 4 Electric Truck Auger Owners Manual Sept. 2005 The Farm And Industrial Equipment Institute Safety Alert Symbol BE ALERT! Your Safety is Involved Be
More informationInstruction Manual PC104/PC105 3-PHASE SOCKET TESTER. Check out what else you can get from Martindale:
Check out what else you can get from Martindale: 17th Edition Testers Accessories Calibration Equipment Continuity Testers Electricians Kits Environmental Products Full Calibration & Repair Service Fuse
More informationInstallation. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Table of Contents
S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons.............................. 2 Read this
More informationS Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES
Fault Indicators S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions Service Information S320-40-1 Contents Product Information...........................1 Safety Information............................2
More information1250 LB. CAPACITY MECHANICAL WHEEL DOLLY
1250 LB. CAPACITY MECHANICAL WHEEL DOLLY 67287 SET-UP AND OPERATING INSTRUCTIONS Visit our website at: http://www.harborfreight.com Read this material before using this product. Failure to do so can result
More informationCOOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN
Reclosers MN280014EN Effective September 2015 Supersedes S280-10-6 April 2003 COOPER POWER SERIES Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits DISCLAIMER OF WARRANTIES AND
More informationInstallation Power Management Unit Battery Cables and Battery Harness
Installation Power Management Unit Battery Cables and Battery Harness Important Safety Messages SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation
More information60 Series End-Mount Brake Instructions Standard Housing
Bulletin No. BK4655 (04/18) 60 Series End-Mount Brake Instructions Standard Housing Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and
More informationCOOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN
Fusing Equipment MN132024EN RTE EL-BAY-O-NET FUSE Re-Fusing Instructions Effective November 2016 Supersedes June 1991 (S240-72-1) COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY
More information37SCENE 46SCENE 79SCENE
Installation and Operation Instructions LED SCENE LIGHT LED SCENE LIGHT 37SCENE 46SCENE 79SCENE 37SCENE 46SCENE Introduction The 37SCENE, 46SCENE, 79SCENE LED Scene Lights are designed for the emergency
More informationDeZURIK AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators
AFR3 Filter Regulator Used on Pneumatic Cylinder Actuators Instructions D11033 August 2013 Instructions These instructions provide information about AFR3 Filter Regulators. They are for use by personnel
More informationCOOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN
Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION
More informationCOOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )
Pad-mounted Switchgear MN285019EN Effective March 2017 Supersedes February 2007 (S285-10-6) COOPER POWER Type VFI fault interrupter with tri-phase control single-phase trip to three-phase trip conversion
More informationINSTALLATION INSTRUCTIONS
Safety Notices... 1... 3 Specifications... 3 General... 3 Electrical... 3 Hydraulic Connections... 3 Components... 4 Assembly... 4 Implement Installation... 7 Hydraulic Connections... 9 Closed-Center Hydraulics...
More informationELB ELB
ELB-35-600 ELB-35-610 600A T-Body Elbow Connectors for Copper Tape (CT), Jacketed Concentric Neutral (JCN), and Concentric Neutral (CN) cables up to 35kV class Safety Instructions When installing electrical
More informationCOOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )
Capacitors MN230005EN Effective November 2016 Supersedes November 2001 (S230-30-3) Expulsion fuse installation instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The
More informationGalaxy Receiving and Unpacking 09/
Galaxy 5500 20 120 kva 400 V Receiving and Unpacking 09/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS
More informationOPERATOR S MANUAL SINGLE PORT UNIVERSAL CAR CHARGER
OPERATOR S MANUAL SINGLE PORT UNIVERSAL CAR CHARGER P130 Fits Ryobi 7.2 volt-18 volt battery packs BATTERIES SOLD SEPARATELY Your battery charger has been engineered and manufactured to Ryobi s high standard
More information7.3L POWERSTROKE BANJO BOLT KIT Fits L Powerstroke Diesel. Installation Guide
7.3L POWERSTROKE BANJO BOLT KIT Fits 94-03 7.3L Powerstroke Diesel Installation Guide INSPECT CONTENTS OF THIS KIT THOROUGHLY BEFORE STARTING THE INSTALLATION PROCESS! IF YOU FIND A PROBLEM WITH YOUR PACKAGE:
More informationTechnical Manual. DLM Module. This manual should remain with the unit.
Technical Manual DLM Module This manual should remain with the unit. Safety Rules SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this
More informationOnBoard Drum Major Podium
Assembly and Owner s Manual OnBoard Drum Major Podium CONTENTS CONTENTS................................................................................. 1 SAFETY...................................................................................
More information