ZONE PRESENCE SENSOR FEATURES SPECIFICATIONS TABLE OF CONTENTS. VAV system using a Zone Presence Sensor.
|
|
- Nelson Gordon
- 5 years ago
- Views:
Transcription
1 ZONE PRESENCE SENSOR Phoenix Controls Zone Presence Sensor (ZPS ) detects the presence of personnel in front of a fume hood. When an operator is present, the ZPS signals the fume hood system into the standard, higher flow, mode. When operators are absent, the ZPS signals the fume hood system into the standby, lower flow, mode, thereby maximizing energy savings and system diversity. FEATURES Used in variable air volume and two-position applications Interfaces to Phoenix Controls fume hood to initiate standard and standby operation ZPS and Phoenix Controls airflow control valves provide less than one-second response time for full-range flow change System fail-safe configured for highest flow set point SPECIFICATIONS General Mounting height field adjustment from -' (.8-. m) above the floor surface [factory default mounting height setting of ' (. m) for a six-foot wide hood] One ZPS for fume hoods up to 8' or. m. Consult factory for larger fume hoods. Detection zone extends approximately 0" (0 cm) from front of fume hood (adjustable) Dimensions 8.8" W x." H x." D ( x 0 x mm) Enclosure Dustproof (NEMA, IP) Color White Operating Range - F (0-0 C) 80 (00 m) altitude Power Requirements Vac, ±%, 0-0 Hz, VA + Vdc, ±%, 0-0 Hz, 0 ma Light Requirements 0-0 foot candles Detection Time < second Setback Time Adjustable C US! See wiring diagrams If the Zone Presence Sensor (ZPS) is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Detection zone VAV system using a Zone Presence Sensor. To detect the presence and motion of fume hood users, the redesigned ZPS uses Charge-Coupled Device (CCD) image sensing technology. CCD arrays are most commonly used in image processing devices. The ZPS does not store, transmit or otherwise make available any optical images. To detect movement, the ZPS cycles through a three-step process, 0 times each second:. The ZPS converts the detection zone image into counts of black and white pixels.. The ZPS comparator circuit s for differences between the previous counts of pixels and the present counts of pixels.. If the pixel count differences are greater than an adjustable sensitivity threshold, the ZPS determines that movement has occurred and the fume hood is then commanded to a higher face velocity set point. The use of a CCD array is strictly for achieving a high resolution pixel count of the detection area in front of the fume hood. TABLE OF CONTENTS Features... Specifications... Ordering Guide... Applications... Installation... Points & Wiring... Maintenance... Troubleshooting... Discovery Way Acton, MA 00 Tel (98) 9-8 Fax (98) Phoenix Controls. Specifications subject to change without notice. Rev. 09/0 MKT-00 MPC-0 ZONE PRESENCE SENSOR OF
2 ORDERING GUIDE ZPS 0 PRODUCT FAMILY ZPS = Zone Presence Sensor SERIES = Second Generation NUMBER OF MODULES 0 = Kit with one ZPS unit and mounting hardware 0 = Kit with two ZPS units and mounting hardware for each 0 = Kit with three ZPS units and mounting hardware for each 0 = Kit with four ZPS units and mounting hardware for each Note: One ZPS for fume hoods up to 8', contact Phoenix Controls for larger fume hoods APPLICATIONS Fume Hood Containment Face Velocity Control: The standard FV set point ranges from 0 fpm to 00 fpm (0.-0. m/s). The most common set point is 00 fpm. Fumes can be contained at a reduced FV (e.g., 0 fpm) after an operator has vacated the hood area (please consult your environmental, health and safety specialist). Variable Air Volume (VAV) Two-position Exhaust Flow (cfm) In Use (00 fpm) Standby (0 fpm) Exhaust Flow (cfm) In-Use (00 fpm) Standby (0 fpm) " Sash Position This graph shows the reduction in flow of a typical VAV fume hood using the ZPS. With no operator present, reductions in airflow are realized throughout the range of sash opening. 0" Time This graph shows the reduction in flow of a typical two-state fume hood using the ZPS. With no operator present, the airflow is reduced to a safe standby level regardless of sash position. The fume hood would require a bypass. OF ZONE PRESENCE SENSOR MKT-00 MPC-0 00 Phoenix Controls. Specifications subject to change without notice. Rev. 09/0
3 INSTALLATION Zone Presence Sensors are surface mounted on the hood by the hood manufacturer or the field controls electrician. Physical Installation Materials required: Two sheet metal screws per ZPS (provided) Level (not provided by Phoenix). Mark a point from -' (.8-. m) above the finished floor centered laterally on the hood.. Remove the ZPS cover and hold the ZPS assembly centered, just above the mark, level to the floor.. Using the assembly as a template, mark the mounting holes at both ends and the cable hole onto the hood panel. Be certain the ZPS assembly is oriented as indicated in the ZPS mounting assembly figure on the following page. Set ZPS aside.. Drill pilot holes at the marked mounting holes (recommended sizes are from.8" to.8", or 0. to 0. cm). Drill a /" ( cm) hole for the cable.. Install ZPS assembly using two sheet metal screws. ft. ( cm) Front View ZPS 8-ft. fume hood (. m) ft. ( cm) ZPS position on an 8-foot (.-m) hood. Retrofit Installation Materials required: Two sheet metal screws per ZPS (provided) Level (not provided by Phoenix). Remove the older model of the ZPS.. Remove the ZPS cover from the new unit and hold the ZPS assembly centered over the old mounting spot.. Follow steps - above. NOTE: Because the ZPS0 had a larger footprint, previous holes may need to be filled for aesthetic purposes. Phoenix Controls offers a plastic barbed plug (white) to fill the holes. Electrical Installation Materials required: Phoenix Controls submittal wiring diagrams Three cable mounts (provided) Cable (not provided by Phoenix). Wire ZPS unit(s) as indicated on wiring diagram (see the following page).. Attach one cable mount behind the ZPS assembly s mounting surface near Mounting hole USB port (CN) ZPS mounting assembly. the cable hole to secure cable and act as a strain relief.. Use the other cable mounts to secure the cable so that the sash will not hit the cable when raised.. Reinstall the cover. JP Optical device TB JP Cable hole Terminal block (TB) Mounting hole 00 Phoenix Controls. Specifications subject to change without notice. Rev. 09/0 MKT-00 MPC-0 ZONE PRESENCE SENSOR OF
4 POINTS & WIRING (see submittal wiring diagram for project-specific details) Wiring Detail for ZPS0 Powered by DC Voltage ZPS0 board. ZPS0 ISO - Vdc + Vdc JP IN To TB Pin To TB Pin To fume hood COMPONENTS Device JP Function Flash programming port + Vdc GND - Vdc To DC power connection Wiring Detail for ZPS0 Powered by AC Voltage JP CN TB Jumper: IN for last ZPS in chain OUT for all others USB port -pin terminal block TERMINAL BLOCK POINTS TB Volts DC/AC Secondary In User Status Isolated (ISO) ZPS0 ISO To TB Pin To TB Pin + Vdc/ Vac JP IN To fume hood Wiring for ZPS0. Vac power connection! Wiring Detail for ZPS0 Powered by AC Voltage SECONDARY ISO +Vdc/Vac TB PRIMARY To TB Pin To TB Pin +Vdc/Vac TB To TB Pin To TB Pin JP IN JP OUT To fume hood Wiring Detail for ZPS0 Powered by DC Voltage Vac power connection SECONDARY ZPS0 PRIMARY ISO - Vdc + Vdc JP IN JP OUT To TB Pin To TB Pin To TB Pin To TB Pin To fume hood + Vdc GND - Vdc To DC power connection Wiring for ZPS0. OF ZONE PRESENCE SENSOR MKT-00 MPC-0 00 Phoenix Controls. Specifications subject to change without notice. Rev. 09/0
5 Phoenix Recommended Cabling. Cable Type Plenum Rated Function Wire Gauge Primary Vendor/Part # Alternate Vendor/Part # Color Code Notes C No Vac power to LOSEA or Pneumatic (0 max at load, ) Vac power to HiSea (88 max at load, ) 8 Belden 909 Belden 9 : Red : Black C Yes Vac power to LOSEA or Pneumatic (0 max at load, ) Vac power to HiSea (88 max at load, ) 8 Belden 80 Windy City NP0090 Windy City NP000 : Red : Black TP No FTT-0 (00 ) TP0 ( ) Windy City 000 FTT-0 (8800 ) Windy City 0900 Connect Air WP-00 : White/Blue : Blue/White For more alternatives visit: echelon.com TP Yes FTT-0 (00 ) TP0 ( ) Windy City 000 FTT-0 (8800 ) Windy City 0900 Connect Air WP-00 : White/Blue : Blue/White For more alternatives visit: echelon.com C No Signal Belden 8 : Red : Black : Green C or Yes Signal Belden 88 Windy City 0080 : Red : Black : Green : White (not used as C) No Signal Belden 8 Manhattan M0 : White : Green : Black : Red C No Signal Belden 8 Manhattan M0 : White : Brown : Black : Red : Green 8C No Signal Belden 9 Manhattan M08 : White : Orange : Black : Red : Green : Yellow : Blue 8: Brown No substitutes 8C Yes Signal Comtran 9 : White : Orange : Black : Red : Green : Yellow : Blue 8: Brown No substitutes 00 Phoenix Controls. Specifications subject to change without notice. Rev. 09/0 MKT-00 MPC-0 ZONE PRESENCE SENSOR OF
6 Cable Type Plenum Rated Function Wire Gauge Primary Vendor/Part # Alternate Vendor/Part # Color Code Notes C No Shielded Belden 0A (0 ohm) : White with Orange : Orange with White : Blue with White Shielded with Yes Armored Shielded Yes Armored Shielded Belden 9A (00 ohm) Belden 0A (00 ohm) Yes Armored Shielded Belden 88 (00 ohm) Yes Shielded Yes Shielded Belden 89 (00 ohm) Belden 880 (00 ohm) : Red : Blue : Black : Yellow : White with Blue : Blue with White : White with Orange : Orange with White : White with Blue : Blue with White : White with Orange : Orange with White : White with Blue : Blue with White : White with Orange : Orange with White : White with Blue : Blue with White : White with Orange : Orange with White Foil and braided shield with Foil and braided shield with Foil and braided shield with Low smoke Shield with Shield with OF ZONE PRESENCE SENSOR MKT-00 MPC-0 00 Phoenix Controls. Specifications subject to change without notice. Rev. 09/0
7 MAINTENANCE Phoenix Controls Zone Presence Sensors require no ongoing preventive maintenance. Once the field engineer has completed the field setup, the s will provide years of continuous operation. Replacement parts are available. Item Part Number ZPS assembly (includes entire assembly and optical device) Enclosure cover Plastic barbed plug to fill hole from ZPS0 footprint (white only) If you use the ZPS Commissioning Software to adjust settings on the ZPS, you will also need to purchase a USB cable to connect your laptop computer to the ZPS. The type of cable you will need is an A-to-B, Male-to-Male Cable Assembly. These cables are available from any store that carries electronic accessories. The recommended cable length is 0 feet or less. If cables are too long, signal degradation and communication loss can occur. Detailed instructions for using the ZPS Commissioning Software are available in the Zone Presence Sensor (ZPS) User s Manual. TROUBLESHOOTING In the event of a circuit failure within the ZPS, indication of user status will be at the fume hood. A trained facilities person may troubleshoot the system using the guide below. Problem Hood does not go into standby operation after operator leaves zone. Possible Cause/Solution A. ZPS cable break or wires have been disconnected. Check cable and termination. B. ZPS has been miscalibrated. Check the calibration settings. 00 Phoenix Controls. Specifications subject to change without notice. Rev. 09/0 MKT-00 MPC-0 ZONE PRESENCE SENSOR OF
SLIM LINE FUME HOOD MONITOR
SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction
More informationBASE UPGRADEABLE VALVES FOR TIERED SOLUTIONS
BASE UPGRADEABLE VALVES FOR TIERED SOLUTIONS As part of Phoenix Controls Upgradeable Control tiered solution, the Base Upgradeable Valve (BxV) with a flow feedback card, pressure switch, and 3 to 5 second
More informationX30 SERIES FUME HOOD MONITORS
X0 SERIES FUME HOOD MONITORS Phoenix Controls X0 Series Fume Hood Monitors (FHMs) are used on fume hoods with Phoenix Controls valves for airflow control. Airflow control on these fume hoods is achieved
More informationSASH SENSORS. part of the sensor bar, closing the magnetic switches it overlaps. The sensor bar changes resistance and a variable
SASH SENSORS Phoenix Controls Sash Sensors detect a fume hood s sash position. Sensors can be configured to operate with the sash configurations found on most VAV fume hoods. The sash sensors are used
More informationLOW PRESSURE CELERIS CONTROLLERS
LOW PRESSURE CELERIS CONTROLLERS Variable air volume (VAV) control schemes are commonly used for fume hoods, general exhaust, and room supply air. For typical fume hood applications, high-speed (< second
More informationSENTRY FUME HOOD DISPLAY
SENTRY FUME HOOD DISPLAY The Sentry Fume Hood Display is a color touch-screen display used on fume hoods with Phoenix Controls valves for airflow controls and monitoring. Airflow on these fume hoods is
More informationLOW-PRESSURE SHUT-OFF CONTROLLERS
LOW-PRESSURE SHUT-OFF CONTROLLERS Valve controllers for Phoenix Conrols low-pressure shut-off venturi valves are determined by the Control Type: Celeris valve controllers for low-speed electric applications.
More informationMEDIUM-PRESSURE SHUT-OFF CONTROLLERS
MEDIUM-PRESSURE SHUT-OFF CONTROLLERS Valve controllers for Phoenix Controls medium-pressure shutoff venturi valves are determined by the Control Type: Celeris valve controllers for low-speed electric applications.
More informationAurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18
Zone Sensors Submittal Data English Language/IP Units SD1582EW 06/18 ZS Series RNet Zone Sensors ZS Series RNet Sensor Overview The ZS Series line of intelligent zone sensors provides the function and
More informationAcid Resistant AVC6000
Accutrol, LLC Product Sheet Acid Resistant AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVC6000! AHR Expo AWARDS WINNER Intuitive Graphical
More informationAccutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare
Accutrol, LLC Product Sheet AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare AHR Expo AWARDS WINNER epi Innovative features for the AVC6000! Intuitive Graphical User Interface
More informationCOMPACT CAGE RACK VALVES
COMPACT CAGE RACK VALVES Phoenix Controls Constant Volume Compact Cage Rack Valve combines a factory-calibrated, field-tunable flow rate setting with a mechanical, pressure-independent flow regulator to
More informationLaboratory Room Controller
Technical Specification Sheet Rev. 5, April, 2001 Laboratory Room Controller Description The APOGEE Automation System Laboratory Room Controller (LRC) provides Direct Control (DDC) for laboratory space
More informationSYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN
SYMBOL LEGEND DANGER THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN WARNING THIS WARNS THAT MATERIALS MAY BE DAMAGED IF APPROPRIATE PRECAUTIONS ARE NOT
More informationBattery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual
Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual 25500181 Rev. A0 415 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification Systems
More informationApplication Engineering
Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor
More informationAurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14
Zone Sensors Submittal Data English Language/IP Units SD1582EW 10/14 ZS Series RNet Zone Sensors ZS Series RNet Sensor Overview The ZS Series line of intelligent zone sensors provides the function and
More informationSelectable ranges and an LCD are a technician s best friend, that s why we make them standard on every dry media differential pressure sensor!
PRESSURE SENSORS PRESSURE PDP3 Series 0-2 32 PDP3 Series 0-10, 0-25 34 PG Gauge Series 36 PW Wet-Wet Series (Cable Version) 38 PW Wet-Wet Series (Conduit Version) 40 PW Series Ordering Guidance 42 Selectable
More informationPowerLogic High Density Metering System 4-Meter Enclosure Installation Guide
PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment
More informationPneumatic Isolation Module
Pneumatic Isolation Module (Cat. 2030-Pxxxxx) ATTENTION: Hazardous Voltage or other forms of energy could be present. To avoid serious injury or death: Prior to beginning the installation and wiring process,
More informationVOC Duct and Rough Service Sensor
Overview and Identification Humans respirate Volatile Organic Compounds (VOCs) as well as CO 2. The BAPI sensor measures these VOCs and indicates space occupancy just as well as a CO 2 sensor. The advantage
More informationVA-7450 Series. Electric Valve Actuators
34-636- 771, Rev. D Installation Instructions VA-7450 Series Issue Date 0216 VA-7450 Series Electric Valve Actuators Applications VA-7450 Series Electric Valve Actuators provide on/off, floating, or proportional
More informationApplication. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203)
TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2600 SASH SENSING VAV FUME HOOD SYSTEM MODEL 2600: Variable volume control based on sash position utilizes microprocessor based electronics and linear air control
More informationContinental Hydraulics Installation Manual CEM-AA-A
Continental Hydraulics Installation Manual CEM-AA-A Description: This power amplifier drives either single or dual solenoid proportional valve coils up to 2.6A. It is suitable to control current to proportional
More informationComfortPoint Programmable Lon, VAV/Unitary Controllers
ComfortPoint Programmable Lon, VAV/Unitary Controllers Controller Model Programmable Type Universal Inputs (UI) Table 1. Controller configurations. Digital Inputs (DI) PRODUCT DESCRIPTION INSTALLATION
More informationFVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description
TEK-AIR TECHNICAL PRODUCT DATA SHEET FVC2100/2200 FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER MODEL 2100: Constant face velocity, variable volume MODEL 2200: Constant face velocity, variable volume
More informationM9106-AGx-2N0x Series Electric Non-spring Return Actuators
Installation Instructions M9106AGx-2N0x Issue Date 08/31/01 M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation IMPORTANT: The M9106-AGx-2N0x Series actuator is intended to control
More informationDC Variable Speed Drive Panel
DC Variable Speed Drive Panel Installation, Operation & Maintenance Instruction Manual Bulletin #: CC-IOM-0103-D Manufacturers of Quality Pumps, Controls and Systems ENGINEERED PUMP OPERATIONS 2883 Brighton
More informationAccutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare
Accutrol, LLC Product Sheet AVC5000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare epi Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5 Pa) Electronic
More informationApplication Engineering
Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the
More informationDusty / Dusty Ex. Low-Cost Broken Bag Detection. Operating Instructions. SWR engineering Messtechnik GmbH
EN Dusty / Dusty Ex Operating Instructions Low-Cost Broken Bag Detection SWR engineering Messtechnik GmbH CONTENTS Page 1. Introduction.............................................................. 3 1.1
More informationBACnet Lab and Pressurized Room Controllers with Off-board Air Modules
Technical Specification Sheet Document No. 149-855 November 04, 2015 BACnet Lab and Pressurized Room Controllers with Off-board Air Modules NOTE: The 570-8xxPA BACnet laboratory controllers have new 67xx
More informationTT /17 INSTALLATION INSTRUCTIONS. Introduction. Required Tools and Equipment
TT-1701 2/17 INSTALLATION INSTRUCTIONS Original Issue Date: 2/17 Model: 15-60REOZK with Decision-Makerr 3000 Controllers Only Market: Industrial Subject: Electronic Governor Kit GM90661-KP1 Introduction
More informationElectric Actuator Instructions
BAC IOM Electric Actuator Instructions E024, E025, E026, E029 & E030 TABLE OF CONTENTS Electric Actuator Specifications...2 Overview...3 Actuator Wiring Diagrams...4 VMS-35 Specifications and Wiring Diagram...5
More informationHoffman Controls. Installation & Operating Instructions. General. Installation. Determining Damper Shaft Rotation. Stop Pin Installation
Hoffman Controls Installation & Operating Instructions General 1. This instruction is a guide for connecting and operating the 200-3 Series Flow Controller with the 207 Series Thermostat and the 241-2
More informationFM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017
FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017 Maxi-Tronic, Inc. 417 Wards Corner Road Loveland, OH 45140 513.398.2500 800.659.8250 FAX: 513.398.2536 info@maxitronic.com
More informationTherm-L-Tec Building Systems LLC. Therm-L-Tech. Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual
Therm-L-Tec Building Systems LLC Therm-L-Tech Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual Rev. A 01/2015 Index Index 1 Electrical Requirements for Therm-L-Tec
More informationCAMS. Combustion Airflow Management System. Proven solutions for a tough industry. Precision Airflow Measurement An ONICON Brand
CAMS Combustion Airflow Management System Proven solutions for a tough industry Precision Airflow Measurement An ONICON Brand CAMS TM Combustion Airflow Management System Product Description The Air Monitor
More information4.1 Functional diagram FM100 fume hood monitor... 4 Functional description FM Interfaces Terminal diagram FM100...
2.0 LabSystem Fume hood monitors Table of contents Section Title Page 1.1 Introduction..................................... 2 2.1 Functional description............................. 2 2.1.1 Actual value
More informationSYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN
SYMBOL LEGEND DANGER THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN WARNING THIS WARNS THAT MATERIALS MAY BE DAMAGED IF APPROPRIATE PRECAUTIONS ARE NOT
More informationTRAC-3 TENSION READOUT AND CONTROL
Magnetic Power Systems, Inc. 1626 Manufacturers Drive. Fenton, MO 63026 Tel: 636.343.5550 Fax: 636.326.0608 magpowr@magpowr.com INSTRUCTION MANUAL TRAC-3 READOUT AND CONTROL For Control of Magnetic Particle
More information3143 Production Drive Fairfeild, Ohio Model HA-45. Installation and Service Manual
3143 Production DriveFairfeild, Ohio 45014513-874-3733 Model HA-45 Installation and Service Manual 3143 Production DriveFairfeild, Ohio 45014513-874-3733 Model HA-45 Installation and Service Manual Table
More informationPower Operated Retrofit Kit for Manual Door 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual
Therm-L-Tec Building Systems LLC Therm-L-Tech Power Operated Retrofit Kit for Manual Door 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual Rev. A 10/2014 Index Index 1 Electrical Requirements
More informationACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE:
ACCUVALVE MODEL AVT6000 SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS VALVE HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE 6 = HIGH TEMP 304SS,
More informationThru-Beam Photo Eye Monitored / Non-Monitored Battery Powered Emitter
Model # IG-2 GUARD-2 TM Thru-Beam Photo Eye Monitored / Non-Monitored Battery Powered Emitter Installation Instructions The Invisi-Guard-2 thru beam photo optic system sends an invisible beam of light
More informationLow Pressure Sensor. Overview. Specifications. Installation and Operation
Overview The Low Pressure Sensor with display measures building pressure, air velocities and volumes. The heart of the unit is a micro-machined silicon pressure sensor. The unit includes a static pressure
More informationDA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators
Datasheet 53lb-in (6 Nm), Non-Spring Return Damper Actuators Overview The direct-coupled fail-safe/failin-place electronic actuators are designed for modulating, two position, and floating control of laboratory
More informationSpyder BACnet Programmable Controllers
Spyder BACnet Programmable Controllers Controller Model Programmable Type Table 1. Controller configurations. INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The PUB and PVB controllers are part of the Spyder
More informationLNII Series Motor and Drives
LNII Series Motor and Drives Operator's Manual PN 04-01805 B PRECISION MOTION CONTROLS 2530 Berryessa Rd. #209 San Jose, CA 95132 10/04/05 2 2 LNII Manual Table of Contents Page Introduction 1. Description
More informationWater Valve Shutoff. WVS Water Valve Shutoff
Water Valve Shutoff Monitors flooding from leaking or broken water line Automatic control of main water supply line Form C Relay output for external monitoring devices Visual and audible status indicators
More informationSERIES PR90H PROGRAMMABLE INCREMENTAL HOLLOW SHAFT ENCODER FOR INDUSTRIAL APPLICATIONS REFERENCE PR90H - C C - C. External diameter 58 mm
PROGRAMMABLE INCREMENTAL HOLLOW SHAFT ENCODER FOR INDUSTRIAL APPLICATIONS Programmable incremental optical encoder from 1 to 65.536 pulses per rotation Programmable via USB, without an additional programming
More informationDMX-A2-DRV Integrated Advanced Step Motor Driver
DMX-A2-DRV Integrated Advanced Step Motor Driver DMX-A2-DRV Manual page 1 rev 3.10 COPYRIGHT 2008 ARCUS, ALL RIGHTS RESERVED First edition, May 2008 ARCUS TECHNOLOGY copyrights this document. You may not
More informationRESISTIVITY MONITOR/CONTROLLERS
RESISTIVITY MONITOR/CONTROLLERS Installation Operation Maintenance User Manual for Models: 750, 752, 753, 762 2450 Impala Drive Carlsbad, CA 92010-7226 USA Tel: 1-760-438-2021 Fax: 1-800-869-7668 / 1-760-931-9189
More information---:...-- Environmental Health & Safety RADIATION PROCEDURES MANUAL. Procedure Cover Sheet. Procedure Number: EHS REV 2
Environmental Health & Safety RADIATION PROCEDURES MANUAL Procedure Cover Sheet Procedure Title: Fume Hoods Procedure Number: EHS-08-03-REV 2 Effective Date: 18 September, 2018 ---:...-- Approved By_-=--------::.--...l~---
More informationELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS
ELECTRIC ACTUATOR E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS 94OE IOM Electric Actuator Specifications...2 Overview...3 Actuator Wiring Diagrams...4
More informationENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER
ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST
More informationELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS
HVAC/BAC ELECTRIC IOM ELECTRIC ACTUATOR E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS Electric Actuator Specifications... 2 Overview... 3 Actuator
More informationBAPI-Stat 3 Room Sensor
Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read
More informationAutomatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit
Instruction Sheet 10-2004 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch.
More informationInstallation Instructions for Remote Mount HMI 211 Display Panel Kit A045J206
Instruction Sheet 7-2013 Installation Instructions for Remote Mount HMI 211 Display Panel Kit A045J206 1 Introduction The information contained within is based on information available at the time of going
More informationSmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE
BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0312 Rev B TABLE OF
More informationMERU Solar Off-Grid Inverters
1 kva / 2 kva Off-Grid Solar Inverters with LCD and LED displays 24 / 48 VDC battery versions for 1 kva and 48 VDC for 2 kva Pure sine wave with highest efficiency Fully configurable (PV / Grid priority
More informationC3000 SIGNAL TRANSMITTER. Introduction
C131-05, Page 1 952-361-3026, INC. (Fax) 952-368-4129 327 LAKE HAZELTINE DRIVE, CHASKA, MN 55318 800-328-0738 C3000 SIGNAL TRANSMITTER Introduction The MAXIGARD C3000 series is designed to convert shaft
More informationProduct Data Sheet. Damper Interface. Features
Damper Interface Product Data Sheet Features Damper Motor drive and limit switch monitoring integrated into a single unit Dual limit switch inputs for confirmation of damper-fully-open and damperfully-closed
More informationINSTRUCTION MANUAL MODEL PS VDC POWER SUPPLY
222 W. Memorial Road, Oklahoma City, OK 73114-2317 Phone: 1-800-624-7697 Fax: 405-755-8425 www.magpowr.com E-mail: magpowr@magpowr.com INSTRUCTION MANUAL MODEL PS-24 24 VDC POWER SUPPLY All of the information
More informationMANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.
MANUAL ECM Motor ECM / ECM-DX Series v100 Issue Date: 08/15/17 2017 Price Industries Limited. All rights reserved. ECM MOTOR TABLE OF CONTENTS ECM Motor Background...1 ECM Motor Power and Control Connectors...2
More informationIOM A-0984E IP68-420DC AUTOMATED PILOT ACTUATOR Installation and Operation Manual
IOM A-0984E IP68-420DC AUTOMATED PILOT ACTUATOR Installation and Operation Manual Please ensure to read and understand the contents of this manual. TABLE OF CONTENTS 1 HEALTH AND SAFETY: READ FIRST...3
More informationIntegrated Control modules
.60.0 Rev. 0 Page of 9 Integrated Control modules QC, QC2 and QC Features: - Basic actuator functions for: - Spring return applications, or - Double acting applications or, - Double acting Fail in Last
More informationCENTRIFLOW METER and ELECTRONICS WIRING and INSTALLATION MANUAL REV 01/16 ORIGINAL LANGUAGE Copyright 2016 Eastern Instrument Laboratories, Inc. All Rights Reserved. TABLE OF CONTENTS SAFETY Safe Operation...
More informationACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS
II 1400-8 Features: ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS Filtered/Regulated 24 Volts DC Up to Full 2 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short Circuit
More informationM-VUE The Intelligent Valve Monitor
M-VUE The Intelligent Valve Monitor www.sense.com.br 1 Monitor M-VUE Overview The M-VUE in an intelligent valve sensor designed specifically for aseptic diafragm valve applications in the Life Science
More informationWoda-Sci System Installation Parts Set
Installation Manual Woda-Sci System Installation Parts Set 5/32 x 3 ½ Drill Bit - 5 Connector Body - 7 3/8 Locking Nut - 8 3/16 x 1 ¼ Concrete Anchors- 4 Mounting Screws - 3 Stainless Steel Hanger - 9
More informationAD-1251 Probe with Differential Pressure Transducer
AD-1251 Probe with Differential Pressure Transducer Product Bulletin Code No. LIT-12011473 Issued October 31, 2011 Supersedes September 6, 2011 The AD-1251 Probe with Differential Pressure Transducer (DPT)
More informationApplication Engineering Europe
Date of last update: Feb-12 Ref: D7.8.4/0112-0212/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS 1/17 1 Introduction CoreSense is an ingredient brand name for
More informationBOILER BLOWDOWN CONDUCTIVITY CONTROLLER (CONTINUOUS METHOD)
LAKEWOOD INSTRUMENTS MODEL 260 SERIES BOILER BLOWDOWN CONDUCTIVITY CONTROLLER (CONTINUOUS METHOD) INSTALLATION & OPERATION MANUAL SERIAL #: Lakewood Instruments 7838 North Faulkner Road, Milwaukee, WI
More informationA419ABG-3C Electronic Temperature Control
Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where
More informationMAXIGARD A2000 SPEED SWITCH. Introduction
A107-05, Page 1 952-361-3026, INC. (Fax) 952-368-4129 327 LAKE HAZELTINE DRIVE, CHASKA, MN 55318 800-328-0738 MAXIGARD A2000 SPEED SWITCH Introduction The Maxigard A2000 Speed Switch is designed to monitor
More informationArtisan Technology Group is your source for quality new and certified-used/pre-owned equipment
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED
More informationCM3000 SIGNAL TRANSMITTER. Introduction. The MAXIGARD CM3000 is designed to convert shaft speed into a 4/20 ma or 0-10 VDC analog output signal.
CM228-03, Page 1 952-935-4201, INC. (Fax) 952-935-9628 3947 MEADOWBROOK ROAD, MINNEAPOLIS, MN 55426 800-328-0738 CM3000 SIGNAL TRANSMITTER Introduction The MAXIGARD CM3000 is designed to convert shaft
More informationINSTALLATION MANUAL. Melink Corporation (513) Revision
INSTALLATION MANUAL Revision 130711 Table of Contents Step Installation Contractor Page 1 Install System Controller Electrical 4 2 Install Variable Frequency Drive Electrical 6 3 Install Touchpad Mechanical
More informationThe Combustex Pilot Pro 900 Ignition System with Pilot Tip and Flame Sensor
OPERATIONS MANUAL The Combustex Pilot Pro 900 Ignition System with Pilot Tip and Flame Sensor KEY FEATURES Strong, Reliable Ignition & Pilot Flame Rapid Flame Response LED Flame Status Indicator Fully
More informationIMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE
USER MANUAL IMI vibration switch INSTALLATION - OPERATION - MAINTENANCE Z0929039_A ISSUED 03/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. contents Overview General
More informationAccutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks
Accutrol, LLC Product Sheet Cage Rack Valve H-AVC5000 US Patents 6,991,177 & 7,543,759 Specially Made for Vivarium Cage Racks Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5
More informationPF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016
PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication
More informationFrom. McCROMETER, INC WEST STETSON AVENUE HEMET, CA Phone (951) Toll Free (800) Fax (951)
SPI Mag MODEL 282L SINGLE POINT INSERTION ELECTROMAGNETIC FLOW METER 2 SENSOR SUBMITTAL PACKAGE From McCROMETER, INC. 3255 WEST STETSON AVENUE HEMET, CA 92545 Phone (951) 652-6811 Toll Free (800) 220-2279
More informationTechnical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER
Technical Specifications Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER Sentinel PRO CONTENTS 1. GENERAL DESCRIPTION... 2 1.1. Main features of the UPS unit... 3 1.2. Standard Versions...
More informationTurbidity and Suspended Solids Transmitter
Data Sheet 5.1 We reserve the right to continuously improve our products and make any change in the stated specifications and dimensions without prior notice. DK: NO: SE: NL: USA: AUS: +45 45 56 06 56
More informationCCS Zone/Bypass Damper Assembly
Code No. LIT-1900539 Issued July 15, 2011 UZR-xx-x, UBR-xx-x, UZD-0xxX0xx-x, UBD-0xxX0xx-x CCS Zone/Bypass Damper Assembly Description The Commercial Comfort System (CCS) Zone/Bypass Damper are zone control
More informationEMUJC Series. Electronic actuator. Technical Data Sheet. WattsIndustries.com
EMUJC Series Electronic actuator Technical Data Sheet WattsIndustries.com Description Watts Water Technologies, Inc. The actuator EMUJC Series is an electronic device with 3-point or proportional control
More informationGTFM IV. Operation / Installation Manual. Gas Turbine Flow Monitor. Computer Weld Technology, Inc. Manual Part Number: A8M5010 Revised: June 26, 2008
Computer Weld Technology, Inc. 10702 Old Bammel N Houston Rd. Houston, TX 77086 Phone: (713) 462-2118 Fax: (713) 462-2503 Email: cwt@cweldtech.com GTFM IV Gas Turbine Flow Monitor Operation / Installation
More informationFT-1005 Air Volume/Velocity Transducer. Operation & Maintenance Manual. Engineered for accuracy, applicability, durability and simplicity
FT-1005 Air Volume/Velocity Transducer Operation & Maintenance Manual Engineered for accuracy, applicability, durability and simplicity TABLE OF CONTENTS TABLE OF CONTENTS... 1 1. INTRODUCTION... 1 1.1.
More information1291BL Series Technical Specification Single Axis Position and Rate Table System
Datasheet 1291BL Series Technical Specification Single Axis Position and Rate Table System DESCRIPTION The Model 1291BL Single Axis Position and Rate Table System is designed to provide precise position,
More informationCLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16
User Manual CLA-VAL Europe www.cla-val.ch cla-val@cla-val.ch 1 - LIN072UE - 04/16 Table of Contents 1 Introduction... 3 1.1 Precautions Before Starting... 3 1.2 Troubleshooting... 3 1.3 General Disclaimer...
More informationAdvanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A
Automation, Inc. Model EAC1100 /A QUICK INSTALL GUIDE Advanced Outdoor Airflow Control, DCV Control and Alarm Solution Enhancer QUICK INSTALL GUIDE for ENHANCER Advanced Outdoor Airflow Control, DCV Control
More informationSTR3. Step Motor Drive. User Manual
STR3 Step Motor Drive User Manual Contents 1 Introduction... 3 1.1 Overview... 3 1.2 Features... 3 1.3 Block Diagram... 4 1.4 Safety Instructions... 5 2 Getting Started... 6 2.1 Mounting Hardware... 6
More informationBT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
More informationInstallation Instructions
BZ-200, BZ-250, BZ-250-347 Power Pack Auto/Manual Mode Switch BZ-250, BZ-250-347 only SPECIFICATIONS Voltages BZ-200, BZ-250... 120 277 VAC, 50/60 Hz, single phase BZ-250-347... 120 347 VAC, 50/60 Hz,
More informationSupreme Air Fume Hood Option Availability
Supreme Air Fume Hood Option Availability Options V05 V06 V07 V15 V16 V25 V26 Kemglass Liner ( 1 /4") G KMER Liner ( 1 /4") K Type 316L Stainless Steel Liner (16 ga) L Type 304L Stainless Steel Liner (16
More informationOPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4)
MOEL COE UCT SHAPE = Round = Rectangular = Flat Oval PROBE MATERIAL = Aluminum/ABS = CPVC & ABS = 0SS = High Temp SS (50 F / C Max) PROBE QUANTITY = = s = s = s SENSORS PER PROBE = Sensor per = Sensors
More informationFAIL-SAFE CONTROL VALVES. Fast Electrically Actuated Control Valves
Fast Electrically Actuated Control Valves FAIL-SAFE CONTROL VALVES FOR MODULATION CONTROL OF INSTANTANEOUS WATER HEATERS & HEAT EXCHANGER APPLICATIONS ARIA Overview At 2mm/sec travel speed (12 seconds/inch),
More information