1 Automation, Inc. Model EAC1100 /A QUICK INSTALL GUIDE Advanced Outdoor Airflow Control, DCV Control and Alarm Solution Enhancer QUICK INSTALL GUIDE for ENHANCER Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A QG_EAC1100A_R3A Part Number: GreenTrolAutom ation,inc. 156 Holly View Lane Loris, SC Toll Free: 877-4GN-TROL ( ) Website: GreenTrol.com

2 Automation, Inc. INTRODUCTION This Quick Install guide provides only the information necessary to install the Enhancer Transmitter, Probes and related wiring. Refer to the Enhancer Installation Guide IG_EAC1100 /A under separate cover for information on initial Set up and normal operation. For application or installation questions, contact the GreenTrol Applications team Toll Free at 877-4GN-TROL ( ). 1. ENHANCER UNPACKING Unpack the EAC1100 /A and verify that all components have been supplied as shown in the List of Items Supplied below. Inspect for damage. If damage is noted, immediately notify carrier. LIST OF ITEMS SUPPLIED Qty Description Part Number 1 Enhancer EAC1100 Transmitter S111 probes and integral mounting brackets Wiring bulkhead, flanged black SLP x SLP bulkhead threaded Wiring bulkhead gasket Wiring bulkhead nut QG_EAC1100_A Quick Install Guide (this document) IG_EAC1100_A Installation Guide EAC1100 Mounting Template LIST OF ITEMS REQUIRED (NOT SUPPLIED) Qty Description inch (38.1mm) sheet metal hole saw 6 #8 Hardware for mounting transmitter (#6 can be substituted if #8 is unavailable) 1 Drill A/R Drill bit suitably sized for hardware selected A/R Screw driver suitable for hardware selected NOTE: The 1.5-inch (38.1mm) hole size is critical to ensure a weather-tight seal at the rear of the Transmitter 2

3 2. AIRFLOW PROBE INSTALLATION Installation Overview and Probe Placement Recommendations: Probes are equipped with universal mounting brackets (Figure 1) that permit installation in a wide variety of field applications. Study Figure 2 for the recommended placement of probes for your application. The objective is to have the airflow probes mounted within the economizer hood on each side (left and right) such that each probe sensor center is positioned at the following location: A minimum distance of 2.5 (63.5 mm) upstream of the OA damper blade edge when at 100% open; and: Universal Mounting Bracket provides complete installation flexibility at a distance of ¼ of the unobstructed probe mounting width (X) from the left and right edges; and: at a distance of ½ of the unobstructed probe mounting height (Y). (continued) Figure 1. Universal Mounting Bracket LEFT SENSOR CENTER LOCATION Probe Sensor Center Location Detail PLANE OF THE EDGE OF OA DAMPER BLADES AT 100% OPEN RIGHT SENSOR CENTER LOCATION 2 ½ UPSTREAM OF OA DAMPER BLADE EDGE AT 100% OPEN Y UNOBSTRUCTED PROBE MOUNTING HEIGHT ½ Y ¼ X ½ Y 2 ½ UPSTREAM OF OA DAMPER BLADE EDGE AT 100% OPEN AIRFLOW ¼ X ¼ X X UNOBSTRUCTED PROBE MOUNTING WIDTH Note: Left probe installation detail is shown in all illustrations. Mirror for right probe detail. Figure 2. Enhancer Probe Sensor Center Location and Placement Detail 3

4 Automation, Inc. 2. AIRFLOW PROBE INSTALLATION (continued) CAUTION: Handle probes carefully. The glass bead thermistor sensors within the airflow openings of the probe are fragile and can be damaged by impact. 1. Examine the planned probe installation location on the left and right sides of the economizer hood opening to ensure that there will be no interference with damper blade operation. In addition, confirm that the planned routing of the probe cables will not interfere with damper linkage. 2. Position and mark the left (PRB1) and right (PRB2) bracket locations for each probe to ensure that the sensor center locations will meet the probe Placement Recommendations detailed in Figure Drill suitable pilot holes for the hardware to be used for each bracket. NOTE: Steps 4 and 5 may be reversed to permit probe installation and adjustment. 4. Adjust the position of the probe within the bracket to meet the recommended installation requirements as described in step 2 and Figure 2. Verify that the airflow direction sticker on each probe is in the direction of actual airflow. Tighten the probe to bracket hardware to secure the probes in this position. 5. Secure each probe bracket and probe through each bracket in two places using suitable mounting hardware. 6. Probes are factory marked PRB1 and PRB2 on the probe cables. Note the positions on the economizer panel where they have been mounted to facilitate diagnostics in the event of a problem later on. Their location will not be apparent once the equipment is assembled and placed into operation. 7. Route each sensor probe cable to the planned EAC1100 /A Transmitter site and install transmitter as outlined in the EAC1100 /A Transmitter Installation procedure that follows. CAUTION: If cable routing holes are required, the recommended minimum diameter is 1". When preparing any cable routing holes and when routing cables, prevent damage to the cables from sharp edges of the prepared holes. 4

5 3. TRANSMITTER INSTALLATION 1. Confirm that the planned mounting location for the Enhancer transmitter (typically on the outside of the air handler unit) will not interfere with any internal air handler unit components directly behind the mounting location. Ensure that the location allows for easy access and installation of the flanged weather tight wiring bulkhead, gaskets and routing of probe cables to transmitter location. 2. Use the supplied Enhancer Enclosure Drill Template (P/N ) to mark the locations of the six transmitter mounting holes (maximum size: #8 screws) and the 1.5 inch (38.1 mm) wiring access hole. 3. If necessary, drill six mounting holes suitable for the transmitter mounting hardware at the six marked transmitter mounting locations (maximum size: #8 screws). 4. Prepare a 1.5 inch (38.1 mm) wiring access hole at the marked wiring access hole location. 5. Remove the Transmitter cover and gasket as shown in the detail of Figure 3. Then, gently squeeze the two board retainers to release the main board and allow it to hinge open to the left as shown in the detail of Figure 3. (continued) Mark these mounting hole locations Remove gasket 2. Squeeze retainers and lift right edge of board to access wiring port and terminals Board retainer Board retainer Mark these mounting hole locations Mounting hole locations and Cover retaining screws (1 to 6) 2. Squeeze retainers and lift right edge of board to access wiring port and terminals Main board retainers, gasket removal and hinge-to-open procedure detail Figure 3. Transmitter cover removal and access to wiring terminals detail 5

6 Automation, Inc. 3. TRANSMITTER INSTALLATION (continued) 6. Refer to Figure 4 and insert the wiring bulkhead with gasket through the EAC1100 wiring access port so that the gasket is seated on the enclosure, and the flange is inside of the enclosure as shown. 7. Insert the flanged wiring bulkhead into the hole prepared in step 4 as shown in Figure Insert remaining flexible gasket seal from the inside of the prepared mounting hole, and secure the wiring bulkhead and transmitter using the wiring bulkhead nut. Line up enclosure to the six mounting holes prepared in step 3, and then tighten the wiring bulkhead nut securely to ensure a weathertight seal and prevent loosening. 9. Secure transmitter at six transmitter mounting holes with suitable hardware. 10. Route cables to transmitter and proceed to 24VAC Wiring in the following steps. Figure 4. Transmitter flanged wiring bulkhead installation detail 6

7 4. 24VAC WIRING 24VAC WIRING PRECAUTIONS: Deactivate 24 VAC power source until all connections are complete. Refer to IG_EAC1100 for additional ESD and wiring precautions. The Enhancer 24 VAC input ground (GND) connection is shared with the Analog I/O signal grounds. If isolated output is required, a dedicated isolation transformer must be provided to power the EAC1100 /A. When other devices are powered by a common 24VAC transformer output, proper phasing of 24V PWR and GND MUST BE OBSERVED. It is recommended that analog input and output interface be connected using separate twisted shielded pairs to eliminate potential voltage drop on the common. 1. Deactivate 24VAC power. 2. Connect 24VAC input power and optional alarm output cables at the ALRM and PWR Terminal Barrier strip as shown in Figure Economizer Control, CO2 Sensor, Damper Actuator and Other Component Wiring Refer to Figure 5 for typical complete Enhancer wiring diagram and detail of external Economizer Control, CO2 Sensor, Damper Actuator and other component wiring. 6. Initial Power Up and Completing the Enhancer Start-Up Wizard 1. Apply power to the Enhancer. The LCD will display a series of dashes followed by the model number and product firmware version. The LCD will then display: START UP WIZARD - Press Enter 2. Press the ENT enter push button key to begin the Start Up Wizard. The Start Up Wizard will guide you through the steps required to properly set up the Enhancer for proper operation in the intended application. The Start Up Wizard must be completed in order to place the Enhancer into normal operation, or to change any of the factory default values. 3. Measure and verify that the Economizer Controller minimum damper actuator voltage when in occupied mode is greater than the factory default Enhancer occupancy trigger set point of 2.2VDC. (If it is NOT greater than 2.2VDC, this value (OCC TRIG= ) can be changed in the Set Up Menu only AFTER completion of the START UP WIZARD). 4. Replace gasket and cover, and secure with the six cover mounting screws (Fig. 3). 5. For additional information on operation and set up of the Enhancer refer to the complete Enhancer Installation Guide IG_EAC1100 /A under separate cover. 7

8 24VAC POWER TRANSFORMER LINE IN 24 VAC OUT 24 VAC / HZ (SEE NOTES 1, 2 AND 3) ENHANCER EAC1100 /A TRANSMITTER 24 VAC GND N.O. COM REAR WIRING SIDE OF MAIN BOARD LED JUMPER (ON FRONT SIDE OF BOARD) SEE NOTE 7 24 VAC IN ALARM OUT PRB1 PRB1 OA S111 AIR FLOW PROBES MOLEX CONNECTORS PRB2 PRB2 OA ENHANCER ALARM STATUS DRY RELAY CONTACTS OR FIELD SUPPLIED ALARM LED INDICATOR ALARM MENU SELECT N.O./N.C. DRY CONTACTS RATED AT 30VDC/ 3A MAX OR EXTERNAL ALARM LED ANODE (15 ma) FROM N.O./N.C. TO GND; LED IS ACTIVE ON ALARM RS-485 BAS NETWORK INTERFACE NETWORK COMMON* (FROM NET COM) NET (FROM NET ) TERM JUMPER (ON FRONT SIDE OF BOARD) SEE NOTE 6 RS-485 ANALOG IN/OUT NET COM NET - NET + GND GND GND AOUT1 AOUT2 AIN1 15VDC AIN2 15VDC FOR FACTORY USE ONLY PRB1 PRB2 NET + (FROM NET +) *FOR NET COMMON CONNECTIONS SEE NOTES 2, 3 OA DAMPER ACTUATOR INTERFACE 24VAC* GROUND* DAMPER CONTROL 2-10VDC ANALOG *FOR POWER AND SEPARATE ANALOG COMMON CONNECTIONS, SEE NOTES 1, 2 AND 4 *FOR ANALOG GROUND CONNECTIONS SEE NOTES 1, 2, 3 AND 4 AOUT2 OPTIONAL OA FLOW OUTPUT (SEE SETUP MENU ITEM AOUT2 = 0-10/2-10/0-5VDC) OPTIONAL ANALOG CO2 SENSOR CO2 DCV SENSOR OUTPUT 2-10VDC, 0-10VDC, 0-5VDC OR 4-20 ma 24VAC* GROUND* *FOR POWER AND SEPARATE ANALOG COMMON CONNECTIONS, SEE NOTES 1, 2 AND 4 ECONOMIZER CONTROLLER INTERFACE OPTIONAL BACNET CO2 SENSOR 24VAC* GROUND* V OUT DAMPER CONTROL OUTPUT 2-10VDC ANALOG *FOR POWER AND SEPARATE ANALOG COMMON CONNECTIONS, SEE NOTES 1, 2 AND 4 TO RS-485 BAS NETWORK INTERFACE 24VAC* GROUND* NET COMMON* NET NET + *FOR POWER AND NET COMMON CONNECTIONS, SEE NOTES 1, 2, 3 AND 5 NOTES: 1. THE EAC1100 IS A NON-ISOLATED DEVICE USING A HALF-WAVE RECTIFIER ON THE 24VAC POWER INPUT. IN ADDITION, THE POWER GND AND ANALOG GND TERMINALS ARE INTERNALLY CONNECTED. 2. THE ECONOMIZER CONTROLLER, ACTUATOR, AND EAC1100 SHOULD ALL BE POWERED FROM A COMMON POWER 24VAC SOURCE AND THEY MUST BE WIRED IN-PHASE TO THE SAME TERMINALS (e.g.: 24VAC to 24VAC, and power GND to power GND). 3. NET COM IS ELECTRICALLY ISOLATED FROM GND TERMINALS. 4. RECOMMENDED WIRING IS SHOWN. WHEN WIRING ANALOG DEVICES EQUIPPED WITH SEPARATE ANALOG SIGNAL AND ANALOG COMMON, USE SHIELDED TWISTED PAIR (STP) WIRING WITH ANALOG COMMONS CONNECTED AT AN ANALOG GROUND TERMINAL GND. 5. CONNECT TWISTED PAIR SIGNAL CABLE DRAINS TO EARTH GROUND AT ONE END OF CABLE ONLY. 6. SET TERM JUMPER (FRONT SIDE OF BOARD) TO ON FOR RS-485 END OF LINE TERMINATION, OR OFF FOR ALL OTHER CONNECTIONS (SEE INSTALLATION GUIDE). 7. SET LED PWR JUMPER (FRONT SIDE OF BOARD) TO ON FOR EXTERNAL ALARM LED, OR OFF FOR RELAY ALARM CONNECCTIONS (SEE INSTALLATION GUIDE). 8. DASHED LINES INDICATE ALTERNATE CONNECTIONS. Figure 5. Typical Enhancer Complete Wiring Diagram Detail 8

Installation Instructions

Installation Instructions H068A00 H069A00 H070A00 POWER EXHAUST ACCESSORY SINGLE PACKAGE ROOFTOP UNITS 12.5to25TONS Installation Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS... 1 GENERAL... 1 INSTALLATION... 2 Power Exhaust

More information

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVC5000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVC5000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare epi Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5 Pa) Electronic

More information

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE:

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE: ACCUVALVE MODEL AVC6000 SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS VALVE HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE 6 = HIGH TEMP 304SS,

More information

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER INSTALLATION INSTRUCTIONS WARNING: The Model 8682 Adaptive Offset Controller must be wired to 24 VAC only. Wiring the unit to 110 VAC will cause serious unit

More information

Pulse Encoder Interface Kit For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 907FK0101

Pulse Encoder Interface Kit For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 907FK0101 Pulse Encoder Interface Kit For Use With FlexPak 3000 and WebPak 3000 DC Drives M/N 907FK0101 Instruction Manual D2-3302-3 The information in this manual is subject to change without notice. Throughout

More information

Silver Series Thermal Dispersion Airflow Measurement Technology

Silver Series Thermal Dispersion Airflow Measurement Technology Thermal Dispersion Airflow Measurement Model STx104-U Unit Ventilator Airflow Measurement System Technical Data Silver Series Thermal Dispersion Airflow Measurement Technology APPLICATIONS Direct outdoor

More information

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017 FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017 Maxi-Tronic, Inc. 417 Wards Corner Road Loveland, OH 45140 513.398.2500 800.659.8250 FAX: 513.398.2536 info@maxitronic.com

More information

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016 PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS v1.1 Revised Table of Contents 1 Common Alarms and Warnings... 1 2 Common Issues... 6 2.1 Communication problems... 6 2.1.1 Controller communication

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions Product Identification Fig 1. BAPI-Com Communication Output Module Fig 2. BAPI-Com Room Sensor, BA/BS4SCOM Operations Overview The BAPI-Com sensor is designed to be used in retrofit applications on just

More information

Accutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks

Accutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks Accutrol, LLC Product Sheet Cage Rack Valve H-AVC5000 US Patents 6,991,177 & 7,543,759 Specially Made for Vivarium Cage Racks Exceptionally Low Pressure Drop Design System Pressure as low as 0.05" (12.5

More information

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare Accutrol, LLC Product Sheet AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare AHR Expo AWARDS WINNER epi Innovative features for the AVC6000! Intuitive Graphical User Interface

More information

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN Hardware Installation Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN February 2004 CNT-SVN02B-EN Tracer AH541

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the CO level and outputs a 4-20 ma signal. The standard product features a 2- wire loop-powered output. Optionally, the device

More information

3143 Production Drive Fairfeild, Ohio Model HA-45. Installation and Service Manual

3143 Production Drive Fairfeild, Ohio Model HA-45. Installation and Service Manual 3143 Production DriveFairfeild, Ohio 45014513-874-3733 Model HA-45 Installation and Service Manual 3143 Production DriveFairfeild, Ohio 45014513-874-3733 Model HA-45 Installation and Service Manual Table

More information

Installation Instructions

Installation Instructions 00A0, 0A0-0A0 080A00 08A00 For Use With Vertical EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY VERTICAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS TO5TON

More information

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE:

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE: ACCUVALVE MODEL AVT6000 SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS VALVE HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE 6 = HIGH TEMP 304SS,

More information

Acid Resistant AVC6000

Acid Resistant AVC6000 Accutrol, LLC Product Sheet Acid Resistant AVC6000 US Patents 6,991,177 & 7,543,759 Laboratories, Life Sciences, Healthcare Innovative features for the AVC6000! AHR Expo AWARDS WINNER Intuitive Graphical

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION SIG DET RDY SND REC PWR INSTALLATION INSTRUCTION MERIDIAN BASIC CONTENTS Fan H E A T I N G C O O L I N G F IL T E R Mixed Air Outside Air Exhaust Air TIPS BEFORE BEGINNING INSTALLATION......... 2 ZONEMANAGER...2

More information

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide Factory Packaged Controls OE377-26-00058 (AAON Part No. V12090) MODGAS-X Controller Table of Contents GENERAL INFORMATION... 3 Overview...3 Features...3 INSTALLATION & WIRING... 4 Supply Air Temperature

More information

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions M9106AGx-2N0x Issue Date 08/31/01 M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation IMPORTANT: The M9106-AGx-2N0x Series actuator is intended to control

More information

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication

More information

Temperature Transmitters

Temperature Transmitters Termination BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger gauge wire may be required for long runs. All wiring must comply with the

More information

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control Product Identification and Overview The BAPI-Stat Quantum style room temperature sensor features a large format LCD and pushbutton setpoint adjustment. Additional options include pushbutton override, fan

More information

VOC Duct and Rough Service Sensor

VOC Duct and Rough Service Sensor Overview and Identification Humans respirate Volatile Organic Compounds (VOCs) as well as CO 2. The BAPI sensor measures these VOCs and indicates space occupancy just as well as a CO 2 sensor. The advantage

More information

TRAC-Station BT Installation Instructions

TRAC-Station BT Installation Instructions TRAC-Station BT Installation Instructions P/N 10103024P1 November 2011 2011 UTC Fire & Security. All rights reserved. Introduction This is the Supra TRAC-Station BT Installation Instructions. Read these

More information

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor Product Identification and Overview Power and Communication on Just Two Wires Available with Temperature Sensing, Temperature Setpoint, Optional Occupant Override, Optional Display and Optional %RH Sensing

More information

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION $5.00 Installation, Operation, and Maintenance Manual CEMLINE CORPORATION CEM-TROL Solid State Control Module and Electronic Control Valves P. O. Box 55, Cheswick, PA, 15024 Phone: (724) 274-5430 FAX (724)

More information

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER UHC 300 22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER OVERVIEW The HVAC building automation controls market requires a DDC controller that provides scalable, consolidated control in a fully programmable,

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw MicroMetl INSTALLATION INSTRUCTIONS for 0637-0311 (CPECOMZR006A00) MicroMetl's 0637 economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions

More information

ACCUSTATION SUBMITTAL MATERIALS

ACCUSTATION SUBMITTAL MATERIALS ACCUSTATION SUBMITTAL MODEL CODE WARNING: NOT FOR USE WITH PERCHLORIC ACID MATERIALS HOUSING MATERIAL 2 = 304SS, 20 GAUGE 3 = 316SS, 20 GAUGE 4 = ALUMINUM, 16 GAUGE SIZE 06 = 06" DIAMETER 08 = 08" DIAMETER

More information

Screw. (Note 4) Spacer for 1" filter ILL. 3. Screw

Screw. (Note 4) Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for (NPECOMZR006A00) ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

Digital/Analog Amplifiers Installation Instructions

Digital/Analog Amplifiers Installation Instructions Digital/Analog Amplifiers Installation Instructions Introduction This publication describes the installation procedure for the 4100U and 4100ES Fire Alarm Control Panels (FACP) family of digital and analog

More information

Lippert Components, Inc. Informational Publication ENTRY DOOR LATCH INFORMATION - SOUTHCO

Lippert Components, Inc. Informational Publication ENTRY DOOR LATCH INFORMATION - SOUTHCO Lippert Components, Inc. Informational Publication LIP Sheet - 0182 revd ENTRY DOOR LATCH INFORMATION - SOUTHCO SOUTHCO, Inc. door latches are used in Lippert s Keyless Entry Door systems. All Southco

More information

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012 COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES 506953-01 3/2014 Supersedes 8/2012 Litho U.S.A. MSAV Supply Air Blower VFD Kit INSTALLATION INSTRUCTIONS FOR MSAV (MULTI-STAGE AIR VOLUME) SUPPLY AIR BLOWER

More information

NJK Precision Product NJK-02 Sensor Installation Guide

NJK Precision Product NJK-02 Sensor Installation Guide Precision -02 Sensor 2017 Product Line Precision Product Table of Contents Precision Company Overview - Page 2-02 Installation Guidelines - Page 3-02 Recommended Installations - Page 5-02 Non-Recommended

More information

Installation Instructions

Installation Instructions CRPWREXH08A0, CRPWREXH09A0, CRPWREXH08A00, CRPWREXH08A00 For Use With Horizontal EconoMi$er IV, EconoMi$er, or EconoMi$er X (W70) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... PACKAGE

More information

GE Sensing & Inspection Technologies

GE Sensing & Inspection Technologies GE Sensing & Inspection Technologies Modus Model RPM-1 Room Pressure Monitor Installation and Setup Guide 1. GENERAL The RPM-1 monitors either positive or negative room pressures (see the Datasheet for

More information

Economizer Controls Package I/O/M manual

Economizer Controls Package I/O/M manual Economizer Controls Package I/O/M manual PD 2/26/2014 - v 1.1 Table of Contents Economizer Controls Package Installation Overview... 3 Tool / Parts... 4 Hardware Included with Controls Package... 4 Economizer

More information

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD Safety Precautions Read this manual thoroughly before proceeding with installation, connections (wiring), or maintenance and inspection. Ensure you

More information

Metasys Zoning Package Installation

Metasys Zoning Package Installation Technical Bulletin Issue Date August 28, 2002 Metasys Zoning Package Installation Metasys Zoning Package Installation...2 Introduction... 2 Key Concepts... 3 Installation Overview... 3 Metasys Zoning Package

More information

3143 Production Drive Fairfeild, Ohio Model HA Installation and Service Manual

3143 Production Drive Fairfeild, Ohio Model HA Installation and Service Manual 3143 Production Drive Fairfeild, Ohio 45014 513-874-3733 Model HA-1000 Installation and Service Manual 3143 Production Drive Fairfeild, Ohio 45014 513-874-3733 Model HA-1000 Installation and Service Manual

More information

ATP-2040 Electric Damper Actuator/Transmitter

ATP-2040 Electric Damper Actuator/Transmitter ATP-2040 Electric Damper Actuator/Transmitter Kit Includes 1. Actuator/Transmitter package: factory assembled Actuator (EDA-2040) and Transmitter (DPT-2000). Product Code Number Coupler Size Differential

More information

Combined Ventilation Controller RVWS-T-224HA

Combined Ventilation Controller RVWS-T-224HA Combined Ventilation Controller RVWS-T-224HA 8-stage Control for Power/Natural Applications 2 variable speed stages, 2 curtain winch stages, 2 fixed speed ventilation stages, 1 thermo/mister cycle stage

More information

AQUAVAR Intelligent Pump Controller TECHNICAL BROCHURE BCPAQIPC R2

AQUAVAR Intelligent Pump Controller TECHNICAL BROCHURE BCPAQIPC R2 AQUAVAR Intelligent Pump Controller TECHNICAL BROCHURE BCPAQIPC R2 INTRODUCTION The Aquavar Intelligent Pump Controller from utilizes an all new Aquavar platform, and combines it with over 20 years of

More information

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION Venturi FX VFX Series v100 Issue Date: 11/22/16 2016 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety Precautions... 1 Caution to Contractors...1

More information

Installation, Start-Up and Configuration Instructions

Installation, Start-Up and Configuration Instructions Installation, Start-Up and Configuration Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 GENERAL.......................................1,2 INSTALLATION................................

More information

Smart Wi-Fi Sprinkler Timer and Flow Meters

Smart Wi-Fi Sprinkler Timer and Flow Meters Smart Wi-Fi Sprinkler Timer and Flow Meters User s Manual Welcome to H2OPro Thank you for purchasing the H2OPro. The H2OPro is a sprinkler timer with a Wi-Fi interface. The system provides sprinkler valve

More information

2520- EC Motor Speed Controller

2520- EC Motor Speed Controller 2520- EC Motor Speed Controller T1 AC Line Voltage From Contactor T2 or Neutral 760-ECM ECM Motor BLACK ORANGE BLACK RED (+) Signal 24VAC (-) GND Features Motor Types: ECM (dc brushless) Motors Motor Speed:

More information

2005 / 2012 / 2035 Series

2005 / 2012 / 2035 Series 005 / 0 / 035 Series Accessories Sandwich Pressure Regulators Accessory Description 0. to bar - 005 Regulator repair kit 0.3 to bar - 0.7 to 9 bar -3 0. to bar 39-909 0 Regulator repair kit 0.3 to bar

More information

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series) Overview The BAPI-Stat 4 Style room unit is available as a humidity only sensor or as a combination temperature and humidity sensor with optional LCD display, temperature setpoint adjustment and occupant

More information

SmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE

SmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE 68507 402-434-9102 email: info@binmaster.com www.binmaster.com OPERATING INSTRUCTIONS PLEASE READ CAREFULLY 925-0312 Rev B TABLE OF

More information

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 1054-7 / 34405 www.onicon.com sales@onicon.com

More information

GE Measurement & Control

GE Measurement & Control GE Measurement & Control Telaire Ventostat 8000 Series CO 2 Sensor User Instructions Installing the Sensor!WARNING! Before performing service or maintenance operations on the systems, turn OFF main power

More information

Air Quality Solutions

Air Quality Solutions Air Quality Solutions Installation & Maintenance Manual Model: IAQ50X Air Measuring Station Indoor Air Quality Damper II-IAQ50X-818/Replaces II-IAQ50X-612 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE

More information

Installation Instructions

Installation Instructions 08A0, 09A0, 08A00, 08A00 For Use With Horizontal EconoMi$ert IV or EconoMi$ert Only SMALL ROOFTOP UNITS ACCESSORY HORIZONTAL EXHAUST GAS HEATING/ELECTRIC COOLING, ELECTRIC COOLING, AND HEAT PUMP UNITS

More information

MODEL RPC30 (-LON) PRESSURA ROOM PRESSURE CONTROLLER

MODEL RPC30 (-LON) PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 (-LON) PRESSURA ROOM PRESSURE CONTROLLER INSTALLATION INSTRUCTIONS WARNING The Model RPC30 (-LON) Room Pressure Controller must be wired to 24 VAC only. Wiring the unit to 110 VAC will cause

More information

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Document number 480938 AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Use this manual when AMS and AMD series dampers were purchased prior

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION MERIDIAN PLUS CONTENTS TIPS BEFORE BEGINNING INSTALLATION......... 2 ZONEMANAGER...3 ZONE MANAGER ADDRESSING.................. 5 COMMUNICATIONSLOOPS...6 COMMUNICATIONS LOOP WIRING

More information

INTECH Micro 2300-RTD6

INTECH Micro 2300-RTD6 INTECH Micro 2300-RTD6 6 Channel RTD Input Station Overview. The Intech Micro 2300 Series is a system of modular I/O Remote Stations, that add an even lower cost option to Intech s already extensive intelligent

More information

W2175 LOAD INDICATOR Calibration (Version cal2175 V2.0)

W2175 LOAD INDICATOR Calibration (Version cal2175 V2.0) W2175 LOAD INDICATOR Calibration (Version cal2175 V2.0) Crane Warning Systems Atlanta 1-877-672-2951 Toll Free 1-678-261-1438 Fax www.craneindicators.com sales@craneindicators.com -1- CALIBRATION DATA

More information

ILL. 1. Horizontal. supply air cover panel shipped on HVAC unit. Access door/ panel

ILL. 1. Horizontal. supply air cover panel shipped on HVAC unit. Access door/ panel ICP INSTALLATION INSTRUCTIONS manual outside air hood / filter (NPMANDPR004A00) (NPMANDPR005A00) and (NPMANDPR006A00) The package includes the outside air hood, the filter access door and the filter. This

More information

J1000. Compact Inverter Series.

J1000. Compact Inverter Series. J1000 Compact Inverter Series www.yaskawa.eu.com Focus on Application Customer orientation and application focus two attributes of machine equipment YASKAWA offers with its J1000 compact inverter drive

More information

Safety & Installation Instructions

Safety & Installation Instructions Model 8120A & 8126A Digital Ventilation Controller Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Safety Instructions... 3 Specifications... 4 Overview... 4 Mounting

More information

MODEL ELC-12/40-CVM-D BATTERY CHARGER

MODEL ELC-12/40-CVM-D BATTERY CHARGER NATIONAL RAILWAY SUPPLY MODEL ELC-12/40-CVM-D BATTERY CHARGER Installing, Operating and Service Instructions for the ELC-12/40-CVM-D Solid State Charger PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING

More information

AD-1251 Probe with Differential Pressure Transducer

AD-1251 Probe with Differential Pressure Transducer AD-1251 Probe with Differential Pressure Transducer Product Bulletin Code No. LIT-12011473 Issued October 31, 2011 Supersedes September 6, 2011 The AD-1251 Probe with Differential Pressure Transducer (DPT)

More information

MP461SC Flex Probes* Installation Instructions

MP461SC Flex Probes* Installation Instructions PNEUMERCATOR Liquid Level Control Systems MP461SC Flex Probes* Installation Instructions Model MP461SC Magnetostrictive Flex Probes For use with the following consoles: TMS2000 TMS3000 NOTE: MP461SC PROBES

More information

OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4)

OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4) MOEL COE UCT SHAPE = Round = Rectangular = Flat Oval PROBE MATERIAL = Aluminum/ABS = CPVC & ABS = 0SS = High Temp SS (50 F / C Max) PROBE QUANTITY = = s = s = s SENSORS PER PROBE = Sensor per = Sensors

More information

Sierra 780S Series Flat-Trak Mass Flow Meter. Instruction Manual

Sierra 780S Series Flat-Trak Mass Flow Meter. Instruction Manual Series 780S Instruction Manual Table of Contents Sierra 780S Series Flat-Trak Mass Flow Meter Instruction Manual Part Number IM-78S 07/99 Revision B 5 Harris Court, Building L Monterey, CA 93940 (831)

More information

RESISTIVITY MONITOR/CONTROLLERS

RESISTIVITY MONITOR/CONTROLLERS RESISTIVITY MONITOR/CONTROLLERS Installation Operation Maintenance User Manual for Models: 750, 752, 753, 762 2450 Impala Drive Carlsbad, CA 92010-7226 USA Tel: 1-760-438-2021 Fax: 1-800-869-7668 / 1-760-931-9189

More information

Expansion Signal (XSIG) Card Installation Instructions

Expansion Signal (XSIG) Card Installation Instructions Expansion Signal (XSIG) Card Installation Instructions Introduction This publication describes the installation procedure for the Expansion Signal (XSIG) Card (4100-5116). This product is compatible with

More information

BAPI-Stat 3 Room Sensor

BAPI-Stat 3 Room Sensor Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read

More information

USERS MANUAL MCD REMOTE OPERATOR

USERS MANUAL MCD REMOTE OPERATOR USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3

More information

Figure 1: WPR2 Dimensions and Hardware

Figure 1: WPR2 Dimensions and Hardware Installation and Operation Instructions WPR2 Series (Max. Line Pressure < 300 PSI) Wet to Wet Differential Pressure Ø0.200" 2.60" 4.47" 5.47" 5.28" 3.00" Precautions Figure 1: WPR2 Dimensions and Hardware

More information

E.S.P. Embedded Sensing Probes for Motor Brushes

E.S.P. Embedded Sensing Probes for Motor Brushes E.S.P. Embedded Sensing Probes for Motor Brushes 2/13 Installation & Operating Manual MN609 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com

More information

SMT-AZC INSTALLATION / OPERATION MANUAL

SMT-AZC INSTALLATION / OPERATION MANUAL SMT-AZC INSTALLATION / OPERATION MANUAL 22o OFF VERSION 2.0 www.smarttemp.com INTRODUCTION The SMT-AZC thermostat is designed to work with the Smart Temp 24Volt Zone Dampers TERMINAL DESIGNATIONS The SMT-AZC

More information

University of Delaware

University of Delaware 25 05 00_ENERGY AND WATER METERING REQUIREMENTS APPLICATION All energy utilities and water shall be metered at the individual building level (at a minimum) and meters shall be connected to UD Energy ing

More information

SECTION FLOW INSTRUMENTS

SECTION FLOW INSTRUMENTS SECTION 230923.14 FLOW INSTRUMENTS Data contained in this guide specification may be placed in either of the following sections, depending on the specifics of the system design, or incorporated within

More information

CAN-Translator. User s guide

CAN-Translator. User s guide User s guide The interface translating CAN-bus information USER GUIDE CAN-TRANSLATOR DEVICE DESCRIPTION Button (searching) - the button, that starts car searching mode or enables LED diode flashing (which

More information

GENUINE PARTS INSTALLATION INSTRUCTIONS

GENUINE PARTS INSTALLATION INSTRUCTIONS GENUINE PARTS 1 DESCRIPTION: 2 APPLICATION: 3 PART NUMBER(S) REQUIRED FOR INSTALLATION: 4 KIT CONTENTS: Remote Engine Start Q60 T99K1 5CH0A (Remote Engine Start Kit) Item Qty. Part Description Service

More information

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m) Installation Instructions D24-53 Issue Date November 4, 23 D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m) Installation IMPORTANT: The D24-53 Series actuator is intended to control

More information

Installation Instructions

Installation Instructions 010A00 011A00 014A00 SMALL ROOFTOP UNITS TWO POSITION OUTDOOR AIR DAMPER 2to15TONS (50/60 Hz) Installation Instructions TABLE OF CONTENTS PACKAGE CONTENTS... 1 PACKAGE USAGE... 1 SAFETY CONSIDERATIONS...

More information

GENUINE PARTS INSTALLATION INSTRUCTIONS

GENUINE PARTS INSTALLATION INSTRUCTIONS GENUINE PARTS INSTALLATION INSTRUCTIONS 1 DESCRIPTION: 2 APPLICATION: 3 PART NUMBER(S) REQUIRED FOR INSTALLATION: 4 KIT CONTENTS: Remote Engine Starter Titan MY16 999K1 W4000 Remote Engine Start Kit (150

More information

The full WeatherTRAK Flow3 Installation and Maintenance Manual is available online at

The full WeatherTRAK Flow3 Installation and Maintenance Manual is available online at Installation Manual INTRODUCTION The full WeatherTRAK Flow Installation and Maintenance Manual is available online at www.weathertrak.com General Description A WeatherTRAK Flow combines a hydraulic master

More information

Instrument Enclosure Assemblies

Instrument Enclosure Assemblies Instrument Enclosure Assemblies Standard instrument enclosure Instrument enclosures offer a simple solution for the customer who doesn t have the time to install Signet meters into panels. Whether it s

More information

Dodge Engineering & Controls, Inc. Toll Free (877) Fax: (978) EN44 and EN88 Non-Spring Return Electronic Actuators

Dodge Engineering & Controls, Inc. Toll Free (877) Fax: (978) EN44 and EN88 Non-Spring Return Electronic Actuators Dodge Engineering & Controls, Inc. EA678R3 45 a b e d c a. Actuator b. Position indicator c. Mounting bracket (for dampers) d. Mounting screws e. 4 mm hex wrench Figure 1. Parts of the EN44 and EN88 Actuators.

More information

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

Blank-off. HVAC unit screws. Spacer for 1 filter ILL. 3. Screw ICP INSTALLATION INSTRUCTIONS for NPECOMZR00A00 ICP's economizer is convertible-it will work in either a down discharge or horizontal discharge application. Read these instructions completely and carefully

More information

Optimized Idle Aftermarket Installation Kits On-Highway Truck Applications (P/N: )

Optimized Idle Aftermarket Installation Kits On-Highway Truck Applications (P/N: ) 18SP655 Optimized Idle Aftermarket Installation Kits On-Highway Truck Applications (P/N: 23538534) KIT DESCRIPTION The Optimized Idle Aftermarket Installation Kit provides the components necessary for

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard 2 2-1/2 Ton Wall Mount T Series Heat Pumps

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard 2 2-1/2 Ton Wall Mount T Series Heat Pumps INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODELS CRVMWH-3 For Use with Bard 2 2-1/2 Ton Wall Mount T Series Heat Pumps Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since

More information

Installation Instructions For Part Number: Intake and Snorkel Kawasaki Teryx Kawasaki Teryx cc

Installation Instructions For Part Number: Intake and Snorkel Kawasaki Teryx Kawasaki Teryx cc Installation Instructions For Part Number: 883-315 Intake and Snorkel 2014-15 Kawasaki Teryx 2012-15 Kawasaki Teryx 4 750 cc Component Identification 1. Airaid Premium Filter 1 2. Top Panel 1 3. Bottom

More information

R81EAA-2 Economizer Circuit Board

R81EAA-2 Economizer Circuit Board FAN 121, 628.1 Motor Actuators Section M Technical Bulletin R81E Issue Date 0993 R81EAA-2 Economizer Circuit Board Applications Setpoint Adjustment Temp T1 T2 S2 1O S 1 8 9 Changeover Relay Refrigeration

More information

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017 R80 REV SERIES SCR POWER CONTROLS NOVEMBER 017 Product overview The Viconics R80 series SCR power controls are designed for cost effective, precise modulation of electric loads for most electric heating

More information

ATOTH-G Series BLDC Motor Controller. User s Manual

ATOTH-G Series BLDC Motor Controller. User s Manual ATOTH-G Series BLDC Motor Controller User s Manual Contents Chapter One Summary...1 Chapter Two Main Features and Specifications.2 2.1 Basic Functions...2 2.2 Features... 5 2.3 Specifications...6 Chapter

More information

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide 32XR 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide RED ALARM LIGHT LEVEL CONTROLLER H-O-A SWITCHES HORN SILENCE INNER DOOR MOTOR STARTERS WITH INTERCHANGEABLE OVERLOAD MODULES

More information

Installation Instructions

Installation Instructions Quick-Mount Visual Instructions for Quick-Mount Visual Instructions 1. Rotate the damper to its failsafe position. If the shaft rotates counterclockwise, mount the CCW side of the actuator out. If it rotates

More information

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration Identification and Overview The BAPI CO 2 Sensor is an accurate and reliable way of incorporating demand controlled ventilation into a building s HVAC strategy. It measures the CO 2 in a range of 0 to

More information

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure Identification and Overview The BAPI CO 2 Sensor is an accurate and reliable way of incorporating demand controlled ventilation into a building s HVAC strategy. It measures the CO 2 in a range of 0 to

More information

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0 Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n 107065-01 Revision 0 May 20, 2016 Contents Introduction 2 Installation Pre-installation 3 Installation Procedure 4 Electrical

More information

FT-10 Network Digital I/O Module Kits and

FT-10 Network Digital I/O Module Kits and Instruction Sheet 10-2004 FT-10 Network Digital I/O Module Kits 541 0771 and 541 0772 PURPOSE OF KIT The Digital I/O Module (DIM) makes provisions for a group of relay contact outputs and discrete inputs

More information

Electric Actuator Instructions

Electric Actuator Instructions BAC IOM Electric Actuator Instructions E024, E025, E026, E029 & E030 TABLE OF CONTENTS Electric Actuator Specifications...2 Overview...3 Actuator Wiring Diagrams...4 VMS-35 Specifications and Wiring Diagram...5

More information