1 INSTRUCTION PAMPHLET U-5623-A MASTER RELAY FOR AMPLIFIER FOR UNION CODED CAB SIGNAL EQUIPMENT February, UNION SWITCH & SIGNAL COMPANY Swissvale, Pa.

2 ..

3 U. S. & S. Co. U-5623-A contact adjustments are outside the limits indicated, the adjustment should be corrected and the heat treatment repeated. Fig. 3 is a schematic view of the relay from the top, showing the nominal values of adjustment of the armature, pole pieces, and contacts. 5. Calibration - With i:he permanent magnet attached and using the circuit of Fig. 4, the relay should be energized at the charge value of 100 ma. and pole changed several times, allowing the current to build up to its full value in each direction. It should be noted that wlth positive voltage applied to the 18 terminal of the relay, the armature goes to the right, closing the right-hand contact. This wm check that the permanent magnet has been applied in the proper direction. POLE CHANGING SWITCH D. C. MILLIAMMETER 100 MA. SCALE ~---, A i Fig Ci:rcuit fo:r Testing Master Relay. In calibrating the rela.v-., ~t should first be charged to 100 ma. The carrent should then be gradually w zero and gradually increased with the opposite polarity until the arm.2j;.1:;:e ::'e.verses. This is the pick-up current and should meet the following limits: Right to LefJ:. 14 ma. ± 0.5 ma. Left to Right 18 ma. ± 0.5 ma. The pick-up value shouid bs taken for both an armature movement from left to right and right to left. When the armature starts to move away from one pole piece, it should continue its travel until it comes to rest against the opposite pole piece. The relay should be adjusted to meet calibration values by adjusting rear pole pieces. In no case shall the rear air gaps from pole piece to armature be less than inch, or more than inch with the armature in that position which provides the smallest air gap. In case pick-up values are too high with rear air gaps at the minimum value, the strength of the permanent :magnet should be decreased. In case the armature will not make a complete stroke at the pick-up value, the magnet strength should be increased.

4 U.S. & S. Co U-5623-A After the relay has been adjusted to meet the calibration values, the armature holding force should be measured by applying a gram gauge to the free end of the armature and measuring the force. required to pull the armatu re away from each pole piece. The force required to pull the armature away from the left pole piece should not be less than 30 grams and the force required to pull it away from the right pole piece should not be less than 25 grams. 6. Breaking-in Run - The relay should now be placed on an operation run for 48 hours at 180 code and at approximately 33 ma., using the suggested circuit shown in Fig. 5. At the conclusion of this run, the calibration should be measured. H it is found that during the breaking-in run the calibration has changed more than 5% or is not within the limits specified in the preceding section, it will be necessary to readjust the relay and repeat the breaking-in run. H any bending of the contacts, springs, or spring stops is necessary, the relay heat treatment must also be repeated. MASTER RELAY #1 LJ ~ MASTER RELAY #2 [g MASTER RELAY #3 [g ;:::- BATTERY -;:::- 12 VOLTS T 25 l CD 15 J- - -}" 25 l co l CD 15 CD 25 } 15 TO OTHER MASTER RELAYS 180 CODE TRANSMITTER CONTACT (MUST BE SILVER-PLATINUM TYPE) Fig Suggested Circuit for Breaking-In Run. IV. FINAL INSPECTION AND TESTS Before the relay is assembled to its cover and sealed, it should be checked to insure that all nuts and screws are tight. All contacts should be examined to see that they are aligned both vertically and horizontally and that they are making squarely. Particular care should be taken to remove any dirt or foreign matter from the relay and cover before they are assembled together. Should any loose iron particles be left inside the relay, they are likely to eventually be drawn into the magnetic field between the two front pole pieces, thus reducing the stroke of the armature. To guard against such an occurrence, all tools used in the assembly and adjustment of the relay should be kept as clean as possible by frequently wiping them with a clean cloth moistened with carbon tetra-

5 ltniou ~tttitr4 & ~igunl <!!ttmpauy SWISSVALE, PA. Subject: MASTER RELAY For Amplifier for Union Coded Cab Signal Equipment Catalog Plate N-llC INSTRUCTION PAMPHLET Number U-5623-A Date February 11, Sheets TABLE OF CONTENTS Page I. General Description n. Maintenance and Inspection tii. Instructions for Shop Repair Relay Assembly Pole Piece Adjustment Permanent Magnet... ; 2 4. Contact Adjustment Calibration Breaking-in Run IV. Final Inspection and Tests V. List of Gauges for Adjustment I. GENERAL DESCRIPTION This relay is a single-point polar-stick type relay designed for operation with low-voltage code amplifiers and so adjusted that its armature will remain in the position to which it was last energized. Thus when positive voltage is applied to the 18 terminal of the relay, the armature will move to close the right-hand contact. When opposite polarity is applied, the armature will move to the left. The relay mechanism consists essentially of a long, thin, narrow armature of high quality magnetic material located on the axis of an operating coil and free at one end to move to right and left between pole pieces in the field of a permanent magnet. Contacts are mounted on an extension of the free end of the armature. The opposite end of the armature is fixed to the supporting bracket through a flat spring hinge. In order to obtain the plug-in feature, the relay is used with the top plate down and when calibrated or operated, the relay should be in this position. See Catalog Plate N-llC. Il. MAINTENANCE AND INSPECTION The master relays in locomotive service should be inspected at regular intervals for proper operation and the condition of the contacts should be observed. The contacts should not show excessive pitting or loss of material, although a small amount of roughening is to be expected and is not harmful.

6 U.S. & S. Co U-5623-A At least once every three years, the calibration values of the relay should be measured. If these values do not fall within the limits shown on Page 7 under "Calibration", the relay should be readjusted in accordance with the procedure hereinafter described. III. INSTRUCTIONS FOR SHOP REPAIR Since the contacts are the only wearing parts in this relay, in most cases the relay can be restored to proper operation by dressing and readjusting them. In such a case, the relay should be readjusted and calibrated in accordance with the procedure outlined in subsequent paragraphs. H for any reason it is necessary to completely dismantle and reassemble the relay, it should be r~assembled in the following manner: 1. Relay Assembly - Catalog Plate N-11C shows the assembled relay and references for the detail parts. First, the coil and magnetic structure should be assembled to the mounting fra-i:ne as shown on the catalog plate. It should be checked that the armature has sufficient clearance to prevent it from binding on the coil spool for any armature position. The relay mechanism and top plate assembly should be completed with the exception of the permanent magnet and its clamping strap which should be applied later after certain other adjustments have been made. The armature should be set to take a free position in the approximate center of the opening. The spring at the base of the armature should be bent only as absolutely necessary to bring the armature into its proper position. 2. Pole Piece Adjustment - The rear pole pieces (those nearest armature hinge spring) should be set first so that the air gap between the armature in its center position and each pole piece is approximately inch. The rear pole pieces should not be locked in place as they may be readjusted in calibrating the relay. The right front pole piece should be adjusted so that the distance from the pole piece to the armature is inch with the armature free. The left front pole piece should then be adjusted for a total armature stroke of inch at the pole pieces. 3. Permanent Magnet - The strength of the permanent magnet can be measured by applying it to the magnet tester, Pc This tester is essentially a master relay magnet structure with a graduated dial by means of which the force in grams required to pull the armature of the tester away from the pole face of the permanent magnet under test can be determined. (See Fig. 1) The permanent magnet should be applied at the front of the testing device, across the. two vertical members or "backstraps" of the magnetic structure, and resting also against the small stop member near the bottom of each backstrap. The north pole of the magnet should be at the left side of the testing device. The north pole is marked "N" in red ink and is that pole of the magnet which attracts the south seeking pole of a magnetic comµtss needle..

7 U.S. & S. Co U-5463-A 0 0 PERMANENT MAGNET \-r I I I I LJ Fig. 1.. Magnet Tester. Starting with the spring at zero on the dial and the armature resting against the left-hand pole piece, the dial should be moved gradually to the right. The spring will indicate the correct "grams" on the dial at the instant when the armature breaks free from the pole piece. Before using this device, it should be checked that with the spring free of the armature and no permanent magnet applied, the spring stands at zero on the dial. This adjustment may be corrected, if necessary, by carefully bending the spring just enough to bring it back to zero on the dial. It should also be checked occasionally that with the spring free of the armature and no magnet applied, the armature stands in such a position. that light is just visible between its core pin and the left-hand pole piece. If necessary, this adjustment may be corrected by pressing a screw driver, or

8 U.S. & S. Co U-5623-A other such implement, against the center rivet at the base of the armature. Only enough pressure should be exerted to bring the top of the armature into its proper position. The permanent magnet used in the master relay is made of Alnico steel, and when properly handled it will retain its magnetic strength indefinitely. If the permanent magnet is removed from a relay for any length of time, it should be protected against loss of strength by a piece of soft iron, or ''keeper'', applied against both poles of the magnet. A permanent magnet should never be dropped or hammered in any way as this tends to reduce its strength. The strength of the permanent magnet when measured on the testing device shown in Fig. 1 should be between 1l and 13 grams. If the strength of the permanent magnet meets these limits, it should be reapplied to the relay magnet structure, first making certain that the pole marked "N" is applied against the left-hand backstrap as shown in Fig. L If the' strength of the permanent magnet does not fall within the limits of 11 to 13 grams, it should first be recharged and then aged on the Magnet Charger, Pc , shown in Fig. 2. To charge the permanent magnet, place it in the position shown in Fig. 2 so that it forms a bridge between the left and center legs of the core. The "N" pole of the permanent magnet should rest on the left-hand leg of the core, i.e., the leg surrounded by the larger of the two coils. Now close the switch DC for approximately one second, then open for one second, repeating PERMANENT MAGNET "" LEFT CORE NOTE:-WHERE ONLY 230 VOLTS D. C. IS AVAILABLE, MAGNET CHARGER PC SHOULD BE USE D. RIGHT HAND (ID...--,e.- CORE LEG ~ CHARGING COIL (LARGE} ~ AGING COIL (small} (ID (ID VARIABLE AUTO-TRANS. 32V. + D.C. 110V. 60"' SWITCH D.C AMPS. A.C. Fig Magnet Charger. SWITCH A.C.

9 U.S. & S. Co U-5623-A until three operations of opening and closing have been made, ending with the switch in the open position. To "age" the permanent magnet, that is, to reduce its strength, it should be shifted to the center and right-hand legs of the core. In the aging operation, the "N" pole of the magnet may rest on either the center or righthand leg of the core. Now proceed as follows: (a) Set the variable transformer to its zero or no-voltage position. See Fig. 2. (b) Close switch AC. (c} Increase the alternating current by means of variable transformer to approximately 4.0 amps. and then slowly reduce the current again to zero. This completes an aging cycle. (d) Measure the strength of the permanent magnet on the tester shown in Fig. 1 and in the manner l)reviously described. If the strength is greater than 13 grams, the aging cycle must be repeated, this time with a somewhat higher value of alternating current. The aging coil, in conjunction with the meter, thus provides a means for measuring the comparative amount of magnetism in the magnet during the calibration process. (e) If during the aging procedure the magnet strength is reduced below 11 grams, the magnet must again be charged to full strength and again aged. The above procedure must be repeated until the magnet strength lies between 11 and 13 grams. To prevent overheating the magnet charger coil or discharging the battery, switch DC should be closed only during the short time required for charging. Switch DC and the wiring between battery and charger must be of sufficient size to carry the required current without excessive voltage drop. 4. Contact Adjustment - If the contacts show evidence of burning or pitting, they should first be dressed with an abrasive strip such as "Rimac Flextone" (Rimak-McLwaine, Inc., 16 Hudson St., New York, N.Y.) and finished by drawing a strip of bond paper between them. Now attach the permanent magnet teml)orarily to the backstraps, making sure that the magnet pole marked "N" is against the left-hand backstrap. As it will later be necessary to remove the permanent magnet, the magnet clamp may be left off for the present. Adjust the spring stops to obtain 2 0 grams initial pressure in each contact spring. Then with the armature held against a inch spacer between the core pin and the right-hand pole piece, adjust the right-hand contact assembly about the center line of the hex. head screw Pc until the contact tips line up and until light is just visible between them. With a inch core pin spacer the contact should be closed. Then tighten screw Pc securely and check that the contact remains in proper adjustment. Repeat the same procedure for the left-hand contact assembly.

10 U. S. & S. Co U-5623-A -j L,, MIN:..._)' MIN. o.01s"max " MAX. "N" POLE OF PERMANENT MAGNET AGAINST THIS BACK STRAP GRAMS PRESSURE Fig Nominal Values of Adjustments for Armature, Pole Pieces, Contacts, and Contact Springs. After the above adjustments have been completed, the relay without permanent magnet) should be heat treated for at least 16 hours at 200 F. After the heat treatment, with the permanent magnet still removed, a check should be made to see that the armature is still centered between the front pole pieces. H there has been a change of the armature from this central position, a corrective adjustment of the front pole pieces should be made as called for under "POLE PIECE ADJUSTMENT". The permanent magnet should now be permanently put back in place and the clamp applied. A check should be made to see that the contact compression has not changed by more than inch and that the initial pressure as measured by a gram gauge is between 19 and 21 grams. In case any of these

11 U.S. & S. Co~ U-5623-A contact adjustments are outside the limits indicated, the adjustment should be corrected and the heat treatment repeated. Fig. 3 is a schematic view of the relay from the top, showing the nominal values of adjustment of the armature, pole pieces, and contacts. 5. Calibration - With the permanent magnet attached and using the circuit of Fig. 4, the relay should be energized at the charge value of 100 ma. and pole changed several times, allowing the current to build up to its full value in each direction. It should be noted that with positive voltage applied to the 18 terminal of the relay, the armature goes to the right, closing the right-hand contact. This will check that the permanent magnet has been applied in the proper direction. POLE CHANGING SWITCH D.C. MILLIAMMETER 100 MA. SCALE A Fig Circuit for Testing Master Relay. In calibrating the relay, it should first be charged to 100 ma. The current should then be gradually reduced to zero and gradually increased with the opposite polarity until the armature reverses. This is the pick-up current and should meet the following limits: Right to Left Left to Right 14 ma.± 0.5 ma. 18 ma.± 0.5 ma. The pick-up value should be taken for both an armature movement from left to right and right to left. When the armature starts to move away from one pole piece, it should continue its travel until it comes to rest against the opposite pole piece. The relay should be adjusted to meet calibration values by adjusting rear pole pieces. In no case shall the rear air gaps from pole piece to armature be less than inch, or more than inch with the armature in that position which provides the smallest air gap. In case pick-up values are too high with rear air gaps at the minimum value, the strength of the permanent magnet should be decreased. In case the armature will not make a complete stroke at the pick-up value, the magnet strength should be increased.

12 U.S. & S. Co U-5623-A After the relay has been adjusted to meet the calibration values, the armature holding force should be measured by applying a gram gauge to the free end of the armature and measuring the force required to pull the armatu re away from each pole piece. The force required to pull the armature away from the left pole piece should not be less than 30 grams and the force required to pull it away from the right pole piece should not be less than 25 grams. 6. Breaking-in Run - The relay should now be placed on an operation run for 48 hours at 180 code and at approximately 33 ma., using the suggested circuit shown in Fig. 5. At the conclusion of this run, the calibration should be measured. H it is found that during the breaking-in run the calibration has changed more than 5% or is not within the limits specified in the preceding section, it will be necessary to readjust the relay and repeat the breaking-in run. Jf any bending of the contacts, springs, or spring stops is necessary, the relay heat treatment must also be repeated =:- BATTERY -=:- 12 VOLTS T MASTER RELAY #t CD 15,_ ')" MASTER RELAY #2 CJ 1 CD 2S CODE TRANSMITTER CONTACT (MUST BE SILVER-PLATINUM TYPE) MASTER RELAY # I C-D IS CD 25 } 15 TO OTHER MASTER RELAYS Fig Suggested Circuit for Breaking-In Run. IV. FINAL INSPECTION AND TESTS Before the relay is assembled to its cover and sealed, it should be checked to insure that all nuts and screws are tight. All contacts should be examined to see that they are aligned both vertically and horizontally and that they are making squarely. Particular care should be taken to remove any dirt or foreign matter from the relay and cover before they are assembled together. Should any loose iron particles be left inside the relay, they are likely to eventually be drawn into the magnetic field between the two front pole pieces, thus reducing the stroke of the armature. To guard against such an occurrence, all tools used in the assembly and adjustment of the relay should be kept as clean as possible by frequently wiping them with a clean cloth moistened with carbon tetra-

13 U. S. & S. Co U-5623-A chloride and then wiping them dry with a clean cloth. The chromium plated surfaces of the front pole pieces and the armature, where it strikes them, should be cleaned by rubbing with a small camel's hair brush moistened with carbon tetrachloride and immediately wiping with a clean dry lintless cloth. The cover should be blown out with compressed air before the relay mechanism is enclosed within it. All parts of the relay, when not being assembled, should be kept in dust-free containers. The assembled relay should be given an insulation test between the various terminals and the case. The insulation resistance should be not less than 50.0 megohms. The relay calibration should be rechecked after the relay is sealed. V. LIST OF GAUGES FOR ADJUSTMENT Thickness in Inches Piece No

14 ..

15

16 PLATE N-1 lc nzlf 15 II S o 0 4" II 4-8 "I.) SECTION "Z-Z" """""" ,...,~ ttW...~~~~~~- 22 LEAD CONNECTION TO PERMANENT MAGNET i :,{lltliil~~====l~'"""'rr:a.~ = ~~l:t"" WIRING DIAGRAM 65 A MASTER RELAY 47

17 PLATE N-llC UNION SWITCH & SIGNAL Co. AUTOMATIC TRAIN CONTROL DETAIL PARTS MASTER RELAY Order by Plate, Piece, Reference and Abbreviated Description Given in Heavy Face Type Only... PIECE REF. DESCRIPTION lj A MASTER RELAY COMPLETE, lf-lb H.V. Contacts DWG.REF. C TOP PLATE C TERMINAL POST WITH SCREW, NUT AND WASHERS (Inc.l-3a, 1-4, 1-5, 1-6 and 1-7) a TERMINAL POST ONLY NUT BOLT LOCK SCREW WASHER TERMINAL POST WITH SCREW, NUT AND WASHERS (Inc.l-3a, 1-4, 1-5, 1-6, 1-7 and 2-9) WASHER TERMINAL POST WITH SCREW AND WASHER (Inc.1-lOa, 1-7 and 1-11) loa TERMINAL POST ONLY SCREW GASKET FRONT SUPPORT BRACKET C REAR SUPPORT BRACKET C MACHINE SCREW, NO x 3/4 in. Rd.Hd.S. (Tin Pl.) with No.10 Pl. S.Lock Washer (1/16 in. x 3/64 in.) (Tin Pl.) and Washer Ref WASHER MACHINE SCREW, NO x 1-1/8 in. Fil.Hd.S. (Tin Pl.) with No.10 Pl.S.Lock Washer (1/16 in. x 3/64 in.) (Tin Pl.) and Washer Ref CONTACT SPRING BOARD SCREW

18 UNION SWITCH & SIGNAL Co. PLATE N-llC -{CONTINUED) PIECE REF. DESCRIPTION DWG. REF. 20 SCREW Ref.20a with No.8 Pl.S.Lock Washer (1/16 in. x 3/64 in.) (Tin Pl.) and Washer Ref a SCREW ONLY WASHER L.H. CONTACT SPRING COMPLETE as shown a R.H. CONTACT SPRING COMPLETE CONTACT BRACKET TERMINAL for Ref , I a TERMINAL for Ref.22a RIVET CONTACT SPRING WITH TUNGSTEN TIP TUNGSTEN TIP.for Refs.26 and CONT ACT SPRING STOP , LEAD COMPLETE B-9991~20 30 SCREW Ref.30a with Washer Ref a SCREW ONLY BOLT LOCK MOUNTING FRAME..... : C SCREW BRACKET MACHINE SCREW, NO x 2-1/8 in. Fil.Hd.S. (Tin Pl.) with No.6 Pl. S.Lock Washer (3/64 in. x 1/32 in.) (Tin Pl.), Nut Ref.36 and Washer Ref NUT WASHER RESISTOR STOP MACHINE SCREW; NO x 5/16 in. Fil.Hd.S. (Tin Pl.) with No. 6 Pl. S.Lock Washer (3/64 in. x 1/32 in.) (Tin Pl.) BOLT LOCK C.N RESISTOR, 300-0hm, 10-Watt BACK STRAP SCREW SCREW

19 PLATE N-llC UNION SWITCH & SIGNAL Co. -(CONTINUED) PIECE REF. DESCRIPTION OWG. REF BOLT LOCK COIL COMPLETE, 30-0hm.s ARMATURE WITH TUNGSTEN TIPS CLAMP PLATE SCREW Ref.49a with No. 4 Ph. Bz. Lock Washer (Int.Teeth) (N.P.) a SCREWONLY PIN PERMANENT MAGNET PERMANENT MAGNET CLAMP SCREW Ref.53a with No. 6 Ph.Bz.Lock Washer (Int.Teeth) (N.P.) , 53a SCREW ONLY CASE C DOOR C GLASS SHIELD GASKET MACHINE SCREW, NO x 5/8 in. Flat Hd.S. (Tin Pl.) for attaching Door to Case (Not shown) NAME PLATE MACHINE SCREW, NO x 3/16 in. Rd.Rd.Br. (N.P.) SPACER LOCKING INSULATION SCREW Ref.53 with Washer Ref WASHER CLAMP PLATE COIL RETAINING SPRING POLE PIECE POLE PIECE LEAD COMPLETE B LEAD COMPLETE B

20 ,.,,,

FN-27 FLASHER RELAY SERVICE MANUAL 4519 * * * * * * * * * * * * * * * *

FN-27 FLASHER RELAY SERVICE MANUAL 4519 * * * * * * * * * * * * * * * * An American-Standard Company SERVICE MANUAL 4519 FN-27 FLASHER RELAY * * * * * * * * * * * * * * * * This manual contains information for shop repair, adjustment and calibration of FN-27 Flasher Relays

More information

UNION SERVICE SPECIFICATION NUMBER SU A

UNION SERVICE SPECIFICATION NUMBER SU A UNION SERVICE SPECIFICATION NUMBER SU-1862 -A UNION SWITCH & SIGNJU,.,... SWISSVALE, PAe DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY DN-10 TRAIN CONTROL SPECIAL SLOW DROP-AWAY RELAYS ********************

More information

SERVICE MANUAL

SERVICE MANUAL DN-18 SLOW PICK-UP. SLOW DROP-AWAY RELAYS SERVICE MANUAL 2 3 9 0 Supplemental Service Specifications: SU-2390-A SU-2390-B SU-2390-C DN-18 Slow Pick-Up, Ordinary Drop-Away Relay DN-19 Slow Drop-Away Relay

More information

- ~SERVICE SPECIFICATION SU-4549 ~

- ~SERVICE SPECIFICATION SU-4549 ~ ,i -' WRBCC - SERVICE SPECIFICATION SU-4549 STYLE PL-59 RELAY GROUPS FOR AUTOMATIC TRAIN CONTROL ***************** This specification covers shop adjustment and testing of the Style PL-59 Relay Groups

More information

CHEC"'- INSTRUCTION UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY

CHEC'- INSTRUCTION UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY CHEC"'- INSTRUCTION JUL S PA.MPH LET NUMBER U- 565 UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY j ELECTRO-PNEUMATIC CUT-OUT RELAY For Automatic Speed Control Car-Carried

More information

PAMPBLIT NUMBER U- 8474

PAMPBLIT NUMBER U- 8474 NSTRUCTON PAMPBLT NUMBER U- 8474 UNON SWTC:B a SGNAi. SWVJU, Pa. DVSON or WESTNGHOUSE AR BRAKE COMPANY,t :1,1 f l ' STYLE CDD THREE POSTON CODE FOLLOWNG RELAY Catalog Plate W-23 ******************* TABLE

More information

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC 29006 Service Manual 3011 SL-6 & SL-6A Outlying Switch Lock Field and Shop Maintenance April, 1979 A-79-500-1496-3 1979, Union Switch & Signal

More information

PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT *****************

PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT ***************** SERVICE MANUAL 4 5 7 8 PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT ***************** This service specification provides information required for repair and adjustment of PT-150 thermal

More information

STYLE PN-59 SLOW PICK-UP PLUG IN D.C. NEUTRAL RELAYS FOR CODED CAB SIGNAL EQUIPMENT. WABCO PART NUMBERS N436928, N and N

STYLE PN-59 SLOW PICK-UP PLUG IN D.C. NEUTRAL RELAYS FOR CODED CAB SIGNAL EQUIPMENT. WABCO PART NUMBERS N436928, N and N SERVICE MANUAL 5624-C STYLE PN-59 SLOW PICK-UP PLUG IN D.C. NEUTRAL RELAYS FOR CODED CAB SIGNAL EQUIPMENT WABCO PART NUMBERS N436928, N436928-001 and N451130-0301 * * * * * * * * * * * * CONTENTS SECTION

More information

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay 41-106E Type CO-4 Step-Time Overcurrent Relay A core screw accessible from the top of the switch provides the adjustable pickup range. The IIT contacts are connected in the trip circuit to trip instantaneously.

More information

B CW POWER RELAY

B CW POWER RELAY 41-241.31B CW POWER RELAY nected in such a way that current, (I A ), leads voltage, (V BA ), by 150 degrees when the motor is operating at unity power factor. Loss of excitation to the motor causes a large

More information

~ SERVICE SPECIFICATION SU-4522-A ~

~ SERVICE SPECIFICATION SU-4522-A ~ WRBCC ~ ~ SERVICE SPECIFICATION SU-4522-A ~ ORP-66 PLUG-IN D. C. SWITCH OVERLOAD RELAY I. GENERAL The ORP-66 D. C. switch overload relay is furnished primarily for the overload protection of high voltage

More information

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay 41-100K 2.0 CONSTRUCTION AND OPERATION The type CO relays consist of an overcurrent unit (CO), either an Indicating Switch (ICS) or an ac Auxiliary Switch (ACS) and an Indicating Instantaneous Trip unit

More information

41-747G. Figure 1: Type DGF Relay without case (Photo)

41-747G. Figure 1: Type DGF Relay without case (Photo) Figure 1: Type DGF Relay without case (Photo) 2 183A113 EDSK 205342 Figure 2: Internal Schematic of the Type DGF Relay in the FT21 Case. When a ground appears in the generator field, the dc milliammeter

More information

P. Sub 4 184A404. Sub 3 876A220

P. Sub 4 184A404. Sub 3 876A220 Figure 1. Type CRN-1 Relay Without Case. 1 = Directional Unit (D). 2 = Timer Unit (T). 3 = Indicating Contactor Switch (ICS). Sub 4 184A404 Sub 3 876A220 Figure 2. Internal Schematic of the Single Trip

More information

COM Overcurrent Relay

COM Overcurrent Relay 41-102.1B COM Overcurrent Relay Figure 1: COM-5 Class 1E Relay (Front View) 9664A28 Photo Figure 2: COM-5 Class 1E Relay (Rear View) 9664A29 Photo Photo needed here 2 COM Overcurrent Relay 41-102.1B 3

More information

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES Hubbell Industrial Controls, Inc. Instructions 5210 SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N 59364 SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N 59345 SERIES Publication

More information

Contacts The moveable contact, which is the one affected by the armature is sometimes referred to as the hinge contact.

Contacts The moveable contact, which is the one affected by the armature is sometimes referred to as the hinge contact. Relays & Wiring 101 Basically, a relay is an electrically operated, remotely controlled switch. A simple electromagnetic relay is an adaptation of an electromagnet. It consists of a coil of wire surrounding

More information

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

Type CRN-1 Reverse Power Relay 50 and 60 Hertz ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-251.2P Effective: June 1991 Supersedes I.L. 41-251.2N Dated April 1988 ( )Denotes Change

More information

PP-151. Service Manual 4551 G. An Ansaldo Signal Company. IUNION SWITCH & SIGNALl[fil] Magnetic Stick DC Plug-In Relay

PP-151. Service Manual 4551 G. An Ansaldo Signal Company. IUNION SWITCH & SIGNALl[fil] Magnetic Stick DC Plug-In Relay IUNION SWITCH & SIGNALl[fil] 645 Russell Street Batesburg, SC 29006 Service Manual 4551 G PP-151 Magnetic Stick DC Plug-In Relay October, 1980 D-79-100-2306-5 1980, Union Switch & Signal Inc. Printed in

More information

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet ABB Instruction Leaflet 41-137.2E Effective: February 1994 Supersedes I.L. 41-137.2D, Dated February 1973 ( )Denotes Change Since Previous Issue. Type KRV Directional Before putting relays into service,

More information

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES Hubbell Industrial Controls, Inc. SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N 59495 SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N 59675 SERIES Instructions 5210 Publication

More information

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View 41-503.21A TYPE KF Front View Rear View Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) 2 TYPE KF 41-503.21A lower pin bearing, which is mounted on the frame, with respect to the

More information

UNIT VIBRATOR MODELS 60U AND 70U

UNIT VIBRATOR MODELS 60U AND 70U VM-3560B Installation, Operation and Maintenance Instructions UNIT VIBRATOR MODELS 60U AND 70U ERIEZ MAGNETICS HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 16506 1440 U.S.A. WORLD AUTHORITY IN ADVANCED TECHNOLOGY

More information

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center

More information

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION ABB Effective: November 1990 This Addendum Supersedes all Previous Addenda Addendum to Instruction Leaflet 41-137.3H Type KRD-4 Directional Overcurrent Ground Relay A - Add New Information C - Change Existing

More information

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION ABB Instruction Leaflet 41-163.2B Effective: January 1977 Supersedes I.L. 41-137.3A, Dated September 1974 ( ) Denotes Change Since Previous Issue Type CRQ Directional Negative Sequence Relay for Ground

More information

PN-250BE D.C. HIGH EFFICIENCY BIASED PLUG-IN RELAY. (li to 007) TABLE OF CONTENTS ARMATURE AIR GAP ADJUSTMENT CHECK OF CONTACT OPENINGS

PN-250BE D.C. HIGH EFFICIENCY BIASED PLUG-IN RELAY. (li to 007) TABLE OF CONTENTS ARMATURE AIR GAP ADJUSTMENT CHECK OF CONTACT OPENINGS SERVICE MANUAL 4563 PN-250BE D.C. HIGH EFFICIENCY BIASED PLUG-IN RELAY (li322550-001 to 007) TABLE OF CONTENTS Section I II III IV v VI VII VIII ARMATURE AIR GAP ADJUSTMENT PERMANENT MAGNET INDICATOR CONTACT

More information

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC INSTRUCTIONS GEI-38974A Supersedes GEI 38974 INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC 2 DESCRIPTION APPLICATION MOUNTING SERVICING RENEWAL PARTS 10 PICKUP AND RESET ELECTRICAL TESTS ELECTRICAL

More information

4.0 OPERATION Type ITH-T Relay

4.0 OPERATION Type ITH-T Relay 41-771.2 Type ITH-T Relay 3.3 OPERATION INDICATOR This operation indicator is a small solenoid coil connected in the trip circuit. When the coil is energized a spring-restrained armature releases the white

More information

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES BELL SYSTEM Plant Series PRACTICES SECTION 040-811-701 Issue 1, June, 1962 AT&TCo Standard RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION I I!

More information

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) 41-242.5E 2 Typical 60 Hertz time product curves for the type CWP-1 relay are shown in Figure 4 with 100 volts

More information

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view) Figure 1: Types CA-16 Relay (front view) Photo Figure 2: Types CA-16 Relay (rear view) Photo 2 Sub 5 185A419 Sub 6 185A443 Figure 3: Internal Schematic of the Type CA-16 bus Relay or CA-26 Transformer

More information

1000 Technology Drive, Pittsburgh, PA Russell Street, Batesburg, SC Plug-In Replacement for the PF256 Flasher Relay

1000 Technology Drive, Pittsburgh, PA Russell Street, Batesburg, SC Plug-In Replacement for the PF256 Flasher Relay SM 9080 1000 Technology Drive, Pittsburgh, PA 15219 645 Russell Street, Batesburg, SC 29006, PN-250F Relay Plug-In Replacement for the PF256 Flasher Relay STS USA Part No. N40116101 Installation Operation

More information

CR193 Vacuum Limitamp* Contactors

CR193 Vacuum Limitamp* Contactors GE Electrical Distribution GEH-5306C Maintenance Instructions CR193 Vacuum Limitamp* Contactors Contents Section 1 Introduction... 3 General... 3 Section 2 Description... 4 Principle of Operation... 4

More information

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY CLOSED, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY CLOSED, P/N SERIES

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY CLOSED, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY CLOSED, P/N SERIES Hubbell Industrial Controls, Inc. SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY CLOSED, P/N 58900 SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY CLOSED, P/N 59501 SERIES Instructions 5210 Publication

More information

ADDE STYLE "H" AND "H-2" D.C. SEARCHLIGHT SIGNAL OPERATING UNIT WITH ALNICO PERMANENT MAGNETS

ADDE STYLE H AND H-2 D.C. SEARCHLIGHT SIGNAL OPERATING UNIT WITH ALNICO PERMANENT MAGNETS . SEE AT ADDE l,\ WABCC "V'" SERVICE MANUAL 2377 STYLE "H" AND "H-2" D.C. SEARCHLIGHT SIGNAL OPERATING UNIT WITH ALNICO PERMANENT MAGNETS For Installation and Maintenance see Service Manual 5034 Section

More information

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes February, 2013 s Installation Sheet January, 016 Supersedes February, 013 E87010-A0104-T003-A6-CLM0 Lighting and Heating Contactor 30 Amp, 3, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere . L. 41-793 NSTALLATON OPERATON MANTENANCE NSTRUCTONS TYPE CRN REVERSE POWER RELAY FOR MARNE SERVCE CAUTON Before putting relays into service remove all blocking which may have been inserted for the purpose

More information

A Practical Guide to Free Energy Devices

A Practical Guide to Free Energy Devices A Practical Guide to Free Energy Devices Part PatD11: Last updated: 3rd February 2006 Author: Patrick J. Kelly Electrical power is frequently generated by spinning the shaft of a generator which has some

More information

CYLINDER HEAD OVERHAUL

CYLINDER HEAD OVERHAUL ENGINE OVERHAUL PROCEDURES - GENERAL INFORMATION -2011 Mercedes-... Page 1 of 20 CYLINDER HEAD OVERHAUL * PLEASE READ THIS FIRST * Examples used in this article are general in nature and do not necessarily

More information

CLASSIFIED 5 MAGNETISM ELECTROMAGNETIC INDUCTION GENERATOR MOTOR - TRANSFORMER. Mr. Hussam Samir

CLASSIFIED 5 MAGNETISM ELECTROMAGNETIC INDUCTION GENERATOR MOTOR - TRANSFORMER. Mr. Hussam Samir CLASSIFIED 5 MAGNETISM ELECTROMAGNETIC INDUCTION GENERATOR MOTOR - TRANSFORMER Mr. Hussam Samir EXAMINATION QUESTIONS (5) 1. A wire perpendicular to the page carries an electric current in a direction

More information

Control Relays Overview

Control Relays Overview Control Relays Overview DESIGN FEATURES Among the advances Agastat Control Relays offer over existing designs is a unique contact operating mechanism. An articulated arm assembly amplifies the movement

More information

Abbeon Cal, Inc. Model BD-50E HIGH FREQUENCY GENERATOR OPERATING MANUAL

Abbeon Cal, Inc. Model BD-50E HIGH FREQUENCY GENERATOR OPERATING MANUAL Abbeon Cal, Inc. Model BD-50E HIGH FREQUENCY GENERATOR OPERATING MANUAL DESCRIPTION. The Model BD-50E is a rugged tester designed for testing tank lining and other applications where extended use is necessary.

More information

PN-lSOB D.C. PLUG-IN RELAYS (Having Part Number Suffixes Under O 11 )

PN-lSOB D.C. PLUG-IN RELAYS (Having Part Number Suffixes Under O 11 ) SERVICE MANUAL 4551 PN-lSOB D.C. PLUG-IN RELAYS (Having Part Number Suffixes Under 11-10 O 11 ) Supplementary Specifications: SM-4551-A; PN-150B Biased Track Relay SM-4551-B; PN-lSON, Neutral Relay SM-4551-C;

More information

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax Network Protector Instruction Manual Type 137NP 800 to 3500 Amperes ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ 07111 Phone 973-371-1771 Fax 973-371-9538 IM 1224-001B DISCLAIMER

More information

Basic Instruments Introduction Classification of instruments Operating principles Essential features of measuring

Basic Instruments  Introduction Classification of instruments Operating principles Essential features of measuring Basic Instruments www.worldwebsites8.blogspot.com Introduction Classification of instruments Operating principles Essential features of measuring instruments PMMC Instruments Moving Iron instruments Introduction

More information

U STYLE "TP" TIME RELEASE UNION SWITCH & SIGNAL DIVISION OF WESTINGHOUSE AIR BRAKE CO. INSTALLATION AND MAINTENANCE AUGUST, 1951

U STYLE TP TIME RELEASE UNION SWITCH & SIGNAL DIVISION OF WESTINGHOUSE AIR BRAKE CO. INSTALLATION AND MAINTENANCE AUGUST, 1951 INSTALLATION AND MAINTENANCE j... STYLE "TP" TIME RELEASE '" INSTRUCTION PAMPHLET U--5029 AUGUST, 1951 UNION SWITCH & SIGNAL DIVISION OF WESTINGHOUSE AIR BRAKE CO. SWISSVALE, PA. 2M-B-51-2 PRINTED IN U.

More information

PV-250 Track Relay. Operating Values For Hz PV-250 Track Relay With 115 Volt Local 440 Turn Track Coil

PV-250 Track Relay. Operating Values For Hz PV-250 Track Relay With 115 Volt Local 440 Turn Track Coil [UNION SWITCH & SIGNAL IL~j 645 Russell Street Service Manual 4574-M Batesburg, SC 29006 PV-250 Track Relay Operating Values For 90183.3 Hz PV-250 Track Relay With 115 Volt Local 440 Turn Track Coil Installation,

More information

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A Service Instructions Syntron Light-Capacity Electromagnetic Vibrating Feeders Models: F-T01-A and DF-T01-A Contents Page

More information

Fig There is a current in each wire in a downward direction (into the page).

Fig There is a current in each wire in a downward direction (into the page). 1 (a) Two straight, vertical wires X and Y pass through holes in a horizontal card. Fig. 8.1 shows the card viewed from above. card wire in hole X Y wire in hole Fig. 8.1 There is a current in each wire

More information

Parts of an atom. Protons (P + ) Electrons (e - ) Neutrons. Have a positive electric charge. Have a negative electric charge

Parts of an atom. Protons (P + ) Electrons (e - ) Neutrons. Have a positive electric charge. Have a negative electric charge Electricity Parts of an atom Protons (P + ) Have a positive electric charge Electrons (e - ) Have a negative electric charge Neutrons Are neutral Have no charge Electric Charge In most atoms, the charges

More information

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet Effective: October 1999 Supersedes I.L. 41-133R, Dated August 1998 ( ) Denotes Changed Since

More information

Relay. for Experiments with the fischertechnik Expansion Kit. Order No

Relay. for Experiments with the fischertechnik Expansion Kit. Order No Relay for Experiments with the fischertechnik Expansion Kit Order No. 30075 About the Relay A relay is an electromagnetic switch. It consists essentially of two assemblies. 5 6 7 3 2 1. Technical Data

More information

Thomas Disc Couplings Installation and Maintenance Series 52 Sizes with classical disc pack TM (Page 1 of 10) DANGER!

Thomas Disc Couplings Installation and Maintenance Series 52 Sizes with classical disc pack TM (Page 1 of 10) DANGER! Thomas Disc Couplings Installation and Maintenance Series 52 Sizes 125-925 with classical disc pack TM (Page 1 of 10) This is the Original Document in English Language Figure 1-1. General Information Thomas

More information

PV Element AC Vane Relay

PV Element AC Vane Relay SM 4574B 1000 Technology Drive, Pittsburgh, PA 15219 645 Russell Street, Batesburg, SC 29006 PV-250 2-Element AC Vane Relay 25 Hz Part Number N322555-002 Installation Operation Maintenance Copyright 2019

More information

IGNITION COIL - 2.4L SPARK PLUG

IGNITION COIL - 2.4L SPARK PLUG TJ IGNITION CONTROL 8I - 13 IGNITION COIL - 2.4L DESCRIPTION - 2.4L The coil assembly consists of 2 different coils molded together. The assembly is mounted to the top of the engine (Fig. 21). REMOVAL

More information

Hermetically Sealed Power Contact

Hermetically Sealed Power Contact Hermetically Sealed Power Contact What is Bestact? Sealed switches in glass tube with inert gas Q: What is Bestact? A : Briefly, it is a hermetically sealed contact in a glass tube that can be used in

More information

OPERATOR, PARTS AND INSTALLATION MANUAL. BX7330 AVENTA TM Tow Bar TOWING PRODUCTS DIVISION

OPERATOR, PARTS AND INSTALLATION MANUAL. BX7330 AVENTA TM Tow Bar TOWING PRODUCTS DIVISION A V E N T A TM OPERATOR, PARTS AND INSTALLATION MANUAL BX7330 AVENTA TM Tow Bar TOWING PRODUCTS DIVISION SAFETY DO NOT INSTALL, OPERATE OR USE THIS EQUIPMENT UNTIL THE FOLLOWING OPERATING AND SAFETY INSTRUCTIONS

More information

WIRING THE HEATER POWER SUPPLY

WIRING THE HEATER POWER SUPPLY WIRING THE HEATER POWER SUPPLY Fig. 14 13/14 Take the longer PS board (with the 47R resistors and the fuse) and, using M3x6 screws, fix it to the chassis to the left of the mains transformer. The diodes

More information

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com Instructions for Parcel-Line Type DH-P Circuit Breakers with Post Insulator Type Pole Units (Supplements I. B. 32-253-2) Westinghouse Electric Corporation Switchgear Division, East Pittsburgh, Pa. 15112

More information

INFORMATION. covering use of Ammeter and Voltmeter ON and 1915 Model Six-54 Electrical System

INFORMATION. covering use of Ammeter and Voltmeter ON and 1915 Model Six-54 Electrical System INFORMATION covering use of Ammeter and Voltmeter ON- 1914 and 1915 Model Six-54 Electrical System Hudson Motor Car Company Detroit, Michigan, IX S. A USE OF AMMETER ON 1914 AND 1915 MODEL SIX-54 With

More information

7.9.8 Elctromagnetism

7.9.8 Elctromagnetism 7.9.8 Elctromagnetism 71 minutes 86 marks Page 1 of 25 Q1. The diagram shows an electromagnet used in a door lock. (a) The push switch is closed and the door unlocks. Explain in detail how this happens.

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS ASTRO ENVELOPE FEEDER AMC-2000 INSTALLATION AND OPERATING INSTRUCTIONS INTRODUCTION Thank you for purchasing the Astro Envelope Feeder. It is fast, efficient, reliable, and designed to provide many years

More information

DT-10 TIME ELEMENT RELAYS

DT-10 TIME ELEMENT RELAYS VUABCCJ An American-Standard Company DT-10 TIME ELEMENT RELAYS SERVICE MANUAL 2366 This revised service specification supersedes all earlier editions and supplements of Service Specification 2365. Information

More information

LEXUS IS 250 Front Performance Brake Kit Section I - Installation Preparation

LEXUS IS 250 Front Performance Brake Kit Section I - Installation Preparation LEXUS IS 250 Front 2006- Performance Brake Kit Section I - Installation Preparation Part Number: PTR09-53080 Kit Contents Item # Quantity Reqd. Description 1 1 Brake Rotor, LH Front 2 1 Brake Rotor, RH

More information

Installation, Operation and Maintenance Instructions

Installation, Operation and Maintenance Instructions VM-3015F Installation, Operation and Maintenance Instructions Vibratory feeder model 15A ERIEZ MAGNETICS HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 16506 1402 U.S.A. WORLD AUTHORITY IN ADVANCED TECHNOLOGY

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS ASTRO ENVELOPE FEEDER AMC-2000 INSTALLATION AND OPERATING INSTRUCTIONS INTRODUCTION Thank you for purchasing the Astro Envelope Feeder. It is fast, efficient, reliable, and is designed to give you many

More information

Right Hand Groomer Kit Left Hand Groomer Kit Reelmaster 5500 D, 6500 D & 6700 D

Right Hand Groomer Kit Left Hand Groomer Kit Reelmaster 5500 D, 6500 D & 6700 D Right Hand Groomer Kit Left Hand Groomer Kit Reelmaster 00 D, 600 D & 6700 D Model No. 08 Model No. 080 Form No. 7 Rev B Installation Instructions Note: The Right and Left Groomer Kits can be used on Reelmaster

More information

SCION tc BIG BRAKE KIT Section I - Installation Preparation

SCION tc BIG BRAKE KIT Section I - Installation Preparation SCION tc 2005- BIG BRAKE KIT Section I - Installation Preparation Part Number: PTR09-21080 Kit Contents Item # Quantity Reqd. Description 1 1 Brake Rotor, LH Front 2 1 Brake Rotor, RH Front 3 1 Brake Caliper

More information

I UNION SWITCH & SIGNAL llfilj

I UNION SWITCH & SIGNAL llfilj I UNION SWITCH & SIGNAL llfilj 645 Russell Street Batesburg, SC 29006 SERVICE MANUAL 3225 SL-20, SL-21, and SL-21A Electric Switch Locks Description, Installation and Maintenance Part N um hers: N241331

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS ASTRO ENVELOPE FEEDER AMC-2000-5 FOR RYOBI 3302 / ITEK 3985 (2 COLOR) INSTALLATION AND OPERATING INSTRUCTIONS INTRODUCTION Thank you for purchasing the Astro Envelope Feeder. It is fast, efficient, reliable,

More information

Commissioning & Maintenance Instructions. for. COBRA linear stepping motors

Commissioning & Maintenance Instructions. for. COBRA linear stepping motors Commissioning & Maintenance Instructions for COBRA linear stepping motors ACP&D Limited. 86 Rose Hill Road, Ashton-under-Lyne, Lancashire, OL6 8NS. Tel : +44 (0)161 343 1884 Fax: +44 (0)161 343 7773 e-mail:

More information

Installation, Operation and Maintenance Instructions

Installation, Operation and Maintenance Instructions VM-3153B Installation, Operation and Maintenance Instructions Vibratory feeder model 26C ERIEZ MAGNETICS HEADQUARTERS: 2200 ASBURY ROAD, ERIE, PA 16506 1402 U.S.A. WORLD AUTHORITY IN ADVANCED TECHNOLOGY

More information

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K GE Protection and Control 205 Great Valley Parkway Malvern, PA 19355-1337 GEK-41931 CONTENTS PAGE DESCRIPTION 3 APPLICATION 3 TABLE I 3

More information

MODEL 600LB 600 POUND SINGLE MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR SPECIFICATIONS

MODEL 600LB 600 POUND SINGLE MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR SPECIFICATIONS MODEL 600LB 600 POUND SINGLE MAGNETIC LOCK WITH LED, BOND SENSOR & STATUS SENSOR SPECIFICATIONS U.L. LISTED, LISTING NUMBER R16759 600 POUND MINIMUM HOLDING FORCE MAGNET SIZE 9-7/8 L x 1-11/16 H x1 W SIZE

More information

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F Instructions for De-Ion Air Circuit s Types DM2R, DM2F (Formerly Westinghouse Electric Corporation) 820 Washington Boulevard Pittsburgh, PA 15206 E-Mail: sales@homewoodsales.com Website: www.homewoodsales.com

More information

SimplePAT. Battery Powered Portable Appliance Tester. User Manual Issue 1.0

SimplePAT. Battery Powered Portable Appliance Tester. User Manual Issue 1.0 SimplePAT Battery Powered Portable Appliance Tester User Manual Issue 1.0 CONTENTS SAFETY 4 GETTING STARTED 5 INTRODUCTION 6 FEATURES 7 PLANNING THE TESTS Determining the Class of construction 9 Type

More information

Al-Saudia Virtual Academy Online Tuition Pakistan Pakistan Online Tutor Magnet and Electromagnetism

Al-Saudia Virtual Academy Online Tuition Pakistan Pakistan Online Tutor Magnet and Electromagnetism Al-Saudia Virtual Academy Online Tuition Pakistan Pakistan Online Tutor Magnet and Electromagnetism DEFINITION: A substance having ability to attract magnetic materials is called magnet. The properties

More information

COLLATOR REFERENCE CONTENTS. Copyright 1947, ADJUSTMENTS. FeedHoppers... Feed Knives... FeedKnifeGuides... Card Guides... FeedRolls..-.. rn...

COLLATOR REFERENCE CONTENTS. Copyright 1947, ADJUSTMENTS. FeedHoppers... Feed Knives... FeedKnifeGuides... Card Guides... FeedRolls..-.. rn... IBM CUSTOMER ENGINEERING REFERENCE U A L COLLATOR T Y P E CONTENTS ADJUSTMENTS FeedHoppers................... Feed Knives................... FeedKnifeGuides............ Card Guides............... FeedRolls..-..

More information

PROCESS ELECTRONICS CORPORATION

PROCESS ELECTRONICS CORPORATION MINIVERTER MANUAL PROCESS ELECTRONICS CORPORATION 100 BRICKYARD ROAD MOUNT HOLLY, NORTH CAROLINA 28120 TELEPHONE (800) 421-9107 FAX (704) 827-9595 SALES@PECRECTIFIER.COM WWW.PECRECTIFIER.COM SOLID STATE

More information

2510, AND 2712 COM PACT TRACTORS CHAPTER 3 STARTER GENERATORS

2510, AND 2712 COM PACT TRACTORS CHAPTER 3 STARTER GENERATORS COLT 2310, 2510, AND 2712 COM PACT TRACTORS CHAPTER 3 STARTER GENERATORS WASHER CENTER STARTER SCREW VISE JAWS DOG\ LEVER ACTION PLIERS Figure 3-A-l 3-A-l ROPE REPLACEMENT. Prepare the rope, place a thin

More information

Service Manual. Climate Control Inc.

Service Manual. Climate Control Inc. SECTION 2 Service - Clutch Servicing (Removal & Installation) - Shaft Seal Servicing (Removal & Installation) - Head & Valve Plate Servicing (Removal & Installation) - Baseplate Servicing (Removal & Installation)

More information

The galvanic separation of the primary or actuating circuit and the load circuits

The galvanic separation of the primary or actuating circuit and the load circuits RELAY BASICS Relays are electro magnetically operated switches. An actuating current on a coil operates one or more galvanically separated contacts or load circuits. The electro mechanical relay is a remote

More information

Troubleshooting Bosch Proportional Valves

Troubleshooting Bosch Proportional Valves Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves

More information

Maintenance Instructions

Maintenance Instructions General Note These instructions contain information common to more than one model of Bevel Gear Drive. To simplify reading, similar models have been grouped as follows: GROUP 1 Models 11, 0, 1,, (illustrated),,

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet I.L. 41-661.1B Effective: June 1997 Supersedes I.L. 41-661.1A, Dated February 1994 Type

More information

EXPERIMENT 13 QUALITATIVE STUDY OF INDUCED EMF

EXPERIMENT 13 QUALITATIVE STUDY OF INDUCED EMF 220 13-1 I. THEORY EXPERIMENT 13 QUALITATIVE STUDY OF INDUCED EMF Along the extended central axis of a bar magnet, the magnetic field vector B r, on the side nearer the North pole, points away from this

More information

SECTION 1E ENGINE ELECTRICAL

SECTION 1E ENGINE ELECTRICAL SECTION 1E ENGINE ELECTRICAL CAUTION: Disconnect the negative battery cable before removing or installing any electrical unit or when a tool or equipment could easily come in contact with exposed electrical

More information

Installation Sheet January, 2016 Supersedes June 2013

Installation Sheet January, 2016 Supersedes June 2013 s Installation Sheet January, 016 Supersedes June 01 E87010-A0105-T00-A6-CLM0 Lighting and Heating Contactor 60, 100, 00 Amp,, 4, 5 Pole Magnetically Latched Description Magnetically latched CLM lighting

More information

Syntron EB-00 Vibratory Parts Feeder GENERAL MANUAL

Syntron EB-00 Vibratory Parts Feeder GENERAL MANUAL Syntron EB-00 Vibratory Parts Feeder GENERAL MANUAL INSTALLATION OPERATION MAINTENANCE Thank you for buying your equipment from Homer City Automation Inc. This manual will help you to understand how your

More information

Door Operator Conversion Package: Type M to PM/SSC or HPM/SSC with Board 1Ø4

Door Operator Conversion Package: Type M to PM/SSC or HPM/SSC with Board 1Ø4 SPARES CENTER Door Operator Conversion Package: Type M to PM/SSC or HPM/SSC with Board 1Ø4 PAA8-606 (4/98) 63113-418 (R0) Type M to PM/SSC or HPM/SSC Purpose This product instruction provides a brief description

More information

Primary Clutch/Brake Pin Drive, Spline Drive PCB-825, PCB-1000, PCB-1225 Primary Clutch/Brake Coupling PCBC-825, PCBC-1000, PCBC-1225

Primary Clutch/Brake Pin Drive, Spline Drive PCB-825, PCB-1000, PCB-1225 Primary Clutch/Brake Coupling PCBC-825, PCBC-1000, PCBC-1225 Primary Clutch/Brake Pin Drive, Spline Drive PCB-825, PCB-1000, PCB-1225 Primary Clutch/Brake Coupling PCBC-825, PCBC-1000, PCBC-1225 P-205 819-0474 Installation Instructions Contents Installation Instructions

More information

DC MOTOR MAINTENANCE ALL ELECTRIC LIFT TRUCKS PART NO SRM 294

DC MOTOR MAINTENANCE ALL ELECTRIC LIFT TRUCKS PART NO SRM 294 DC MOTOR MAINTENANCE ALL ELECTRIC LIFT TRUCKS PART NO. 897076 620 SRM 294 SAFETY PRECAUTIONS MAINTENANCE AND REPAIR When lifting parts or assemblies, make sure all slings, chains, or cables are correctly

More information

MOREHOUSE INSTRUMENT COMPANY, INC. 60,000 LBS CAPACITY AIRCRAFT PART NUMBER SCALE S FORCE CALIBRATION PRESS PART NO.

MOREHOUSE INSTRUMENT COMPANY, INC. 60,000 LBS CAPACITY AIRCRAFT PART NUMBER SCALE S FORCE CALIBRATION PRESS PART NO. INDEX 1. GENERAL SPECIFICATION AND DRAWING 804000-03... 2 2. ASSEMBLY INSTRUCTIONS... 5 3. OPERATING INSTRUCTIONS... 6 4. MAINTENANCE INSTRUCTIONS... 7 5. CERTIFICATE OF CAPACITY LOAD TEST AND OVERLOAD...

More information

Chapter 22: Electric motors and electromagnetic induction

Chapter 22: Electric motors and electromagnetic induction Chapter 22: Electric motors and electromagnetic induction The motor effect movement from electricity When a current is passed through a wire placed in a magnetic field a force is produced which acts on

More information

PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT

PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT Sheet 1 of 6 Order Number Serial Number PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT Issue Date Level A 22/10/02 Initial issue. Summary of changes Due to RMS continuous product improvement policy

More information

Electropneumatic Timing Relays Series 7000 Industrial

Electropneumatic Timing Relays Series 7000 Industrial DESIGN FEATURES Available in On-Delay, True Off-Delay, and On/Off-Delay. Timing from 0.1 seconds to 60 minutes, fully calibrated in linear increments. Oversize time-calibrated adjustment knobs, serrated

More information

Instructions for Replacing

Instructions for Replacing e Instructions for Replacing Vacuum Bottle Subassemblies a on Type SJA, SJS and SJO 360 Amp Contactors l.l. 16-200-348 This l.l. includes illustrations and instructions for replacing vacuum bottle subassemblies

More information

Magnetism and Electricity ASSIGNMENT EDULABZ. the mere presence of magnet, is called...

Magnetism and Electricity ASSIGNMENT EDULABZ. the mere presence of magnet, is called... Magnetism and Electricity ASSIGNMENT 1. Fill in the blank spaces by choosing the correct words from the list given below. List : magnetic field, magnetic keepers, electric bell, stop, magnetic induction,

More information