Rosemount 3095FC MultiVariable Mass Flow Transmitter
|
|
- Rose Sanders
- 6 years ago
- Views:
Transcription
1 Quick Start Guide , Rev CA Rosemount 3095FC MultiVariable Mass Flow Transmitter with Modbus Protocol
2 Quick Start Guide NOTICE This guide provides basic guidelines for the Rosemount 3095FC with Modbus Protocol. It does not provide instructions for configuration, diagnostics, maintenance, service, or troubleshooting. Refer to the Rosemount 3095FC MultiVariable Mass Flow Transmitter Reference Manual for more instruction. The manuals are also available electronically on EmersonProcess.com/Rosemount. WARNING Explosions could result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Before connecting communications in an explosive atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices. In an Explosion-Proof/Flame-Proof installation, do not remove the transmitter covers when power is applied to the unit. Process leaks may cause harm or result in death. To avoid process leaks, only use the o-ring designed to seal with the corresponding flange adapter. Electrical shock can result in death or serious injury. Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause electrical shock. Contents Mount the transmitter Connect wiring Set jumpers and apply power Establish communication Verify configuration Trim the transmitter Product Certifications
3 Quick Start Guide 1.0 Mount the transmitter 1.1 Installing the Rosemount 3095FC on a pipestand The following steps must be taken to install the Rosemount 3095FC on a 2-in. pipestand: 1. Install the pipestand using the pipestand documentation. 2. Remove the orifice/meter run from service. 3. Install the Rosemount 3095FC on a pipestand using clamps or mounting brackets. 4. Connect the impulse lines. 1.2 Installing the Rosemount 3095FC on an orifice plate (direct mount) The following steps must be taken to install the Rosemount 3095FC on an orifice plate: 1. Remove the orifice/meter run from service. 2. Install the Rosemount 3095FC on the meter run using a manifold and hardware to secure the Rosemount 3095FC to the orifice flanges. Figure 1. Gas Flow Application 3
4 Quick Start Guide 1.3 Bolting considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 2 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly. Figure 2. Common Transmitter Assemblies A C in. (57 mm) D in. (44 mm) B in. (44 mm) in. (38 mm) in. (73 mm) A. Transmitter with coplanar flange B. Transmitter with coplanar flange and optional flange adapters C. Transmitter with traditional flange and optional flange adapters D. Transmitter with coplanar flange and optional manifold and flange adapters in. (44 mm) Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 1. If bolt material is not shown in Table 1, contact the local Emerson Process Management representative for more information. Use the following bolt installation procedure: 1. Carbon steel bolts do not require lubrication and the stainless steel bolts are coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt. 2. Finger-tighten the bolts. 3. Torque the bolts to the initial torque value using a crossing pattern. See Table 1 for initial torque value. 4. Torque the bolts to the final torque value using the same crossing pattern. See Table 1 for final torque value. 5. Verify that the flange bolts are protruding through the isolator plate before applying pressure. 4
5 Quick Start Guide Table 1. Torque Values for the Flange and Flange Adapter Bolts Bolt material Head Markings Initial Torque Final Torque B7M Carbon Steel (CS) 300 in-lb 650 in-lb 316 B8M 316 Stainless Steel (SST) 150 in-lb 300 in-lb 316 R STM 316 SW O-rings with flange adapters WARNING Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury. The two flange adapters are distinguished by unique O-ring grooves. Only use the O-ring that is designed for its specific flange adapter, as shown below: Rosemount 3051S/3051/2051/3095 A B Rosemount 1151 A C D B A. Flange adapter B. O-ring C. PFTE D. Elastomer Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the o-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o-ring. C D 5
6 Quick Start Guide 2.0 Connect wiring Use the following steps to wire the transmitter: 1. Remove the electronics housing cover on the side marked FIELD TERMINALS. 2. Wire the RTD. Temperature is input through the Resistance Temperature Detector (RTD) probe and circuitry. The Rosemount 3095FC provides terminations for a 2- or 3-wire 100-ohm platinum RTD with a IEC 751 curve. The RTD has an alpha (α) equal to The RTD mounts directly to the piping using a thermowell. RTD wires should be protected by a metal sheath or by a conduit connected to a conduit wiring fitting on the enclosure. The RTD wires connect to the three screw terminals designated RTD on the Termination Board. Wiring between the RTD and Rosemount 3095FC should be shielded wire, with the shield grounded only at one end to prevent ground loops. Ground loops cause RTD input signal errors. Table 2 displays the RTD terminal connections for the various RTD probes. Table 2. RTD Signal Routing Terminal Designation 3-wire RTD 2-wire RTD RTD + Signal positive input RTD + RTD + RTD + Signal positive input RTD + Jumper to RTD + RTD RET Return reference RTD RET RTD RET 3. Wire the power supply. The terminals are labeled CHG+ for positive power connection and CHG- for negative power connection on a label on the termination board. These connections provide the input voltage and power for the battery charging circuit. The maximum voltage that can be applied to the CHG+/CHGterminals is 28 Volts dc. Pin Signal Description 1 CHG+ Battery 8.0 to 28 V Power 2 CHG- Battery Common 4. Communications wiring The Local Operator Interface (LOI) port provides direct communications between the Rosemount 3095FC and the serial port of an operator interface device, such as an IBM compatible PC using an EIA-232 (RS-232) link. The interface allows access to the Rosemount 3095FC (using Rosemount User Interface Software) for configuration and transfer of stored data. 6
7 Quick Start Guide Using the prefabricated operator interface cable, physically connect the Rosemount 3095FC to the PC running the Rosemount User Interface Software. One end of the cable (a 9-pin, D-shell, female connector) plugs into a serial communications port on the PC. The other end of the cable plugs into the Rosemount 3095FC. Figure 3. Operator Interface Wiring White TX Red TX Black TX To screw terminals Connection at PC COM port White TX Red TX Black TX Connection at LOI port Table 3. Local Operator Interface Port Wiring Signal Common LOI Power (1) Common Ready to Send Receive Transmit Label COM TX + V COM RTS RX TX 1. Do not use the LOI to power external devices. 7
8 Quick Start Guide Figure 4. Rosemount 3095FC Terminal Block and Wiring Diagram E 2 OR 3 WIRE RTD A LOI + + RET B - + C RTD D CHG F POWER SUPPLY OPERATOR INTERFACE CABLE H G. PC A. LOI B. RET C. RTD D. CHG E. 2 or 3 wire RTD F. Power supply G. PC H. Operator interface cable 3.0 Set jumpers and apply power To prevent unnecessary battery drainage, the Rosemount 3095FC is delivered with the reset jumper in the OFF position. To apply power to the Rosemount 3095FC: 1. Complete the necessary wiring. 2. Unscrew the front end cap cover (LCD display end). 3. Place the power jumper in the ON position. The jumper is located on the LCD display (if installed) or at J1 on the Battery Charger Board. 4. Screw the front-end cap cover (LCD display end). After the Rosemount 3095FC completes start-up diagnostics (RAM and other internal checks), the optional LCD display shows the date and time to indicate that the Rosemount 3095FC completed a valid reset sequence. 8
9 Quick Start Guide 4.0 Establish communication 1. Open the Rosemount 3095FC User Interface Software 2. Enter the factory-assigned User ID and Password: User ID: LOI Password: Select Direct Connect, located on the software toolbar. 5.0 Verify configuration 1. Select Device > Clock from the menu tab. 2. Verify the correct time and date for the transmitter s memory logs, and click OK to exit the screen. 3. Select Device > Information from the menu tab. 4. Verify the correct station name, address number, group number, and contract hour. Select OK to exit the screen. 5. Select Meter > Set Up from the menu tab. 6. Verify values of pipe and orifice diameter by selecting the General tab. 7. Select Inputs from the top of the screen and verify the correct range and units of measure for the analog inputs. 8. Select the Gas Quality tab from the top of the screen and verify the correct gas composition for your process. 9. Select the Advanced tab from the top of the screen. Verify the correct values for FPV method, units of measure, and all geographical parameters. Select OK to exit the screen. 6.0 Trim the transmitter Note Transmitters are shipped from Emerson Process Management, Emerson fully calibrated per request or by the factory default of full scale. 6.1 Zero trim A zero trim is a single-point adjustment used for compensating mounting position effects. When performing a zero trim, ensure the low side block valve is closed, the equalize valve is open, the high side block valve is open, and all wet legs are filled to the correct level. To check or adjust for zero shift, leave the sensor by-pass valve open (to simulate a no-flow condition), with either line pressure or a normal operating SP from the calibrator applied to the sensor. This applies the same pressure to both sides of the DP diaphragm to give a zero DP reading. 9
10 Quick Start Guide Perform the following steps: 1. Connect the Rosemount User Interface Software to the Rosemount 3095FC and run the calibration procedure. 2. Select Meter>Calibration >Freeze. 3. Under the Diff Press input, click Zero Shift to open the Set Zero Shift window. 4. Verify Reading to determine if a Zero Sift correction is required. 5. If the reading is not zero, select Set Zero Shift to adjust the Zero and select Done. If the reading is zero, select Done. 6. Select Done to close the calibration window and cancel the freeze values to begin using live readings for the flow calculations. 7. Once the zero trim is complete, verify that the high side block valve is open, close the equalize valve tightly, then open the low side block valve. 10
11 7.0 Product Certifications 7.1 Approved Manufacturing Locations Rosemount Inc. Chanhassen, Minnesota USA 7.2 European Directive Information Quick Start Guide The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at EmersonProcess.com/Rosemount. A hard copy may be obtained by contacting our local sales office. ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive. European Pressure Equipment Directive (PED) (97/23/EC) Rosemount 3095F_2/3,4/D Flow Transmitters QS Certificate of Assessment - EC No. PED-H-100 Module H Conformity Assessment All other 3095_ Transmitters/Level Controller Sound Engineering Practice Transmitter Attachments: Process Flange - Manifold Sound Engineering Practice Electro Magnetic Compatibility (EMC) (2004/108/EC) Rosemount 3095F Flow Transmitters - EN : A1, A2, and A3 Ordinary Location Certification for Factory Mutual As standard, the Rosemount 3095FB Transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). 7.3 Hazardous Locations Certifications North American Certifications Canadian Standards Association (CSA) - U.S. and Canada M Explosion-Proof for Class I, Division 1, Groups C and D including optional solar panel: mast option: Suitable for use in Class I, Division 2, Groups A, B, C, D, and T3. CSA Enclosure Type 4. European Certifications H ATEX Flame4proof Certificate: LCIE05ATEX6057X EEx d IIB T5 V max = 28V dc IP II 2 G Special Conditions for Safe Use (x): 1. Operating ambient temperature: 40 C to 75 C. 2. The users have to make sure that the thermal fluid transfer doesn t overheat the equipment to a temperature corresponding to the spontaneous combustion temperature of surrounding gas. 11
12 Quick Start Guide Figure 5. Rosemount 3095FC Declaration of Conformity 12
13 Quick Start Guide 13
14 Quick Start Guide 14
15 Quick Start Guide 15
16 Quick Start Guide China RoHS Rosemount 3095FC List of Rosemount 3095FC Parts with China RoHS Concentration above MCVs / Hazardous Substances Part Name Lead (Pb) Mercury (Hg) Cadmium (Cd) Hexavalent Chromium (Cr +6) Polybrominated biphenyls (PBB) Polybrominated diphenyl ethers (PBDE) Electronics Assembly X O O O O O Housing Assembly X O O X O O Sensor Assembly X O O X O O SJ/T11364 This table is proposed in accordance with the provision of SJ/T O: GB/T O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T X: GB/T X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T
17 Quick Start Guide 17
18 * * Quick Start Guide , Rev CA Global Headquarters Emerson Process Management 6021 Innovation Blvd. Shakopee, MN 55379, USA or North America Regional Office Emerson Process Management 8200 Market Blvd. Chanhassen, MN 55317, USA or Latin America Regional Office Emerson Process Management 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA Europe Regional Office Emerson Process Management Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland +41 (0) (0) Asia Pacific Regional Office Emerson Process Management Asia Pacific Pte Ltd 1 Pandan Crescent Singapore Enquiries@AP.EmersonProcess.com Middle East and Africa Regional Office Emerson Process Management Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates RFQ.RMTMEA@Emerson.com Linkedin.com/company/Emerson-Process-Management Twitter.com/Rosemount_News Facebook.com/Rosemount Youtube.com/user/RosemountMeasurement Google.com/+RosemountMeasurement Standard Terms and Conditions of Sale can be found at The Emerson logo is a trademark and service mark of Emerson Electric Co. MultiVariable, Rosemount, and Rosemount logotype are trademarks of Emerson Process Management. Modbus is a registered trademark of Gould Inc. All other marks are the property of their respective owners Emerson Process Management. All rights reserved.
Rosemount 3095FC MultiVariable Mass Flow Transmitter with MODBUS Protocol
Quick Installation Guide Rosemount 3095FC Rosemount 3095FC MultiVariable Mass Flow Transmitter with MODBUS Protocol Step 1: Mount the Transmitter Step 2: Connect Wiring Step 3: Set Jumpers and Apply Power
More informationRosemount 405 Compact Primary Element. Quick Start Guide , Rev HA June 2016
Rosemount 405 Compact Primary Element 00825-0100-4810, Rev HA NOTICE This guide provides basic guidelines for Rosemount 405. It does not provide instructions for configuration, diagnostics, maintenance,
More informationRosemount 3095FT MultiVariable Flow Data Logger
Quick Installation Guide Rosemount 3095FT Rosemount 3095FT MultiVariable Flow Data Logger Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Set Jumpers and Switches Step 4: Connect
More informationQuick Start Guide , Rev FB June Rosemount 485 Annubar Flanged Flo-Tap Assembly
Quick Start Guide 00825-000-809, Rev FB Rosemount 85 Annubar Flanged Flo-Tap Assembly Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 85 Annubar. It does not provide instructions
More informationQuick Start Guide , Rev AB June Rosemount 585 Annubar Flanged Assembly
Quick Start Guide 00825-0100-585, Rev AB Rosemount 585 Annubar Flanged Assembly Quick Start Guide NOTICE This guide provides basic guidelines for Rosemount 585 Annubar Assembly. It does not provide instructions
More informationRosemount Manifolds. Product Data Sheet April , Rev PC. Factory assembled, leak-tested, and calibrated
Product Data Sheet pril 2015 00813-0100-4733, Rev PC Rosemount Manifolds Factory assembled, leak-tested, and calibrated Full breadth of offering including integral, conventional, and in-line designs Integral
More informationQuick Start Guide , Rev CB March Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems
Quick Start Guide 00825-0100-4016, Rev CB Rosemount DP Level Transmitters and 1199 Diaphragm Seal Systems Quick Start Guide NOTICE This guide provides basic guidelines for the Rosemount DP Level Transmitters
More informationRosemount Smart Pressure Gauge
Rosemount Smart Pressure Gauge Product Data Sheet September 2017 00813-0100-4145, Rev AA The Rosemount Smart Pressure Gauge from Emerson utilizes industry-proven Rosemount pressure sensor technology to
More informationRosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev NB January Contents
Product Data Sheet Factory assembled, leak-tested, and calibrated Full breadth of offering including integral, conventional, and inline designs Integral design enables flangeless valve integration 2, 3,
More informationRosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev MA August Contents
Product Data Sheet Factory assembled, leak-tested, and calibrated Full breadth of offering including integral, conventional, and inline designs Integral design enables flangeless valve integration 2, 3,
More informationRosemount Manifolds. Product Data Sheet October , Rev PB. Factory assembled, leak-tested, and calibrated
Product Data Sheet October 2014 00813-0100-4733, Rev PB Rosemount Manifolds Factory assembled, leak-tested, and calibrated Full breadth of offering including integral, conventional, and in-line designs
More informationRosemount Manifolds. Product Data Sheet September , Rev PA. Factory assembled, leak-tested, and calibrated
Product Data Sheet September 2014 00813-0100-4733, Rev PA Rosemount Manifolds Factory assembled, leak-tested, and calibrated Full breadth of offering including integral, conventional, and in-line designs
More informationRosemount 485 Annubar Pak-Lok Assembly
Quick Installation Guide 00825-0300-809, Rev EA Pak-Lok 85 Annubar Rosemount 85 Annubar Pak-Lok Assembly Start Step 1: Location and Orientation Step 2: Drill Holes into Pipe Step 3: Weld Mounting Hardware
More informationRosemount 485 Annubar Threaded Flo-Tap Assembly
Quick Installation Guide 00825-0500-809, Rev DB Threaded Flo-Tap 85 Annubar Rosemount 85 Annubar Threaded Flo-Tap Assembly Step 1: Location and Orientation Step 2: Weld Mounting Hardware Step 3: Install
More informationRosemount 485 Annubar Flanged Assembly
Quick Installation Guide 00825-0100-809, Rev DB Flanged 85 Annubar Rosemount 85 Annubar Flanged Assembly Start Step 1: Location and Orientation Step 2: Drill Holes into Pipe Step 3: Assemble and Check
More informationRosemount 1810 Flush Mount Pressure Transmitter ROSEMOUNT 1810 FEATURES:
Rosemount 1810 Rosemount 1810 Flush Mount Pressure Transmitter ROSEMOUNT 1810 FEATURES: A cleanable and compact stainless steel design An innovative patented venting configuration that prevents gauge reference
More informationRosemount 3051CFA Annubar Flowmeter
December 2013 Rosemount 3051 Rosemount 3051CFA Annubar Flowmeter The Rosemount 3051CFA Annubar Flowmeter utilizes the patented T-shaped sensor design that delivers best in class accuracy and performance.
More informationRosemount 2051 Pressure Transmitter with HART 4-20 ma and HART 1-5 Vdc Low Power Protocol
Quick Installation Guide 00825-0100-4101, Rev EA June 2010 Pressure Transmitter with HART 4-20 ma and HART 1-5 Vdc Low Power Protocol CF Series Flowmeter Transmitter with HART 4-20 ma and HART 1-5 Vdc
More informationRosemount Pipe Clamp RTD Sensor
Product Data Sheet Platinum RTD Temperature Sensors with silver or nickel tip Non intrusive design for measurement on pipe applications Temperature-sensor matching provides increased measurement accuracy
More informationRosemount 585 Annubar Flanged Flo-Tap Assembly
Quick Installation Guide 00825-0200-585, Rev AA Flanged Flo-Tap 585 Annubar Rosemount 585 Annubar Flanged Flo-Tap Assembly Start Step 1: Location and Orientation Step 2: Weld Mounting Hardware Step 3:
More informationInstallation/Start-up Manual CMB_MAN_ABR_CH88 September CH88 In-Situ Combustion O2. Analyzer System
CH88 In-Situ Combustion O2 Analyzer System Section 1: Section 2: Section 3: Section 4: Section 5: Section 6: Contents General Information Essential Instructions... 2 Symbols used... 3 Overview... 4 System
More informationRosemount 285 Annubar Pak-Lok Assembly
Quick Installation Guide 0025-0100-02, Rev AA Pak-Lok 25 Annubar Rosemount 25 Annubar Pak-Lok Assembly Start Step 1: Location and Orientation Step 2: Drill Holes into Pipe Step 3: Weld Mounting Hardware
More informationEndurance TM Conductivity Sensors
Endurance TM Conductivity Sensors For additional information, please visit our website at EmersonProcess.com/LiquidAnalysis. Quick Start Guide Part Number: 51A-400/400VP, Rev. S March 2016 Sensor/process
More informationRosemount 3051T In-Line Pressure Transmitter
Rosemount 3051T In-Line Pressure Transmitter Rosemount 3051T In-line Pressure Transmitters are the industry standard for Gage, and Absolute pressure measurement. The in-line, compact design allows the
More informationRosemount 228. Toroidal Conductivity Sensor. Product Data Sheet July Series LIQ-PDS-228
LIQ-PDS-228 Product Data Sheet Rosemount 228 Toroidal Conductivity Sensor A Versatile Conductivity Sensor for Solving Diverse Application Challenges Rosemount 228 toroidal conductivity sensors reliably
More informationRosemount Manifolds. Rosemount Manifolds. Product Data Sheet , Rev LA Catalog Contents
Product Data Sheet Factory assembled, leak-tested, and calibrated Full breadth of offering including integral, conventional, and inline designs Integral design enables flangeless valve integration 2, 3,
More informationRosemount 4088 MultiVariable Transmitter
Product Data Sheet May 2015 00813-0100-4088, Rev AC Rosemount 4088 MultiVariable Transmitter With the innovative Rosemount 4088 MultiVariable Transmitter, you can maximize your measurement accuracy and
More informationModel 8800C Vortex Flowmeter
Vortex Flowmeter Start Step 1: Mount the Flowmeter Step 2: Consider Housing Rotation Step 3: Set the Jumpers Step 4: Connect the Wiring and Power Up Step 5: Review Flowmeter Configuration Product Certifications
More informationInnovation in actuation.
Innovation in actuation. Keystone EPI-2 Quarter Turn Electric Actuators Control your low-torque quarter turn valves and dampers more effectively, even in the largest plants. A world of experience Keystone
More informationRosemount 4088 MultiVariable Transmitter
Product Data Sheet January 2018 00813-0100-4088, Rev BA Rosemount 4088 MultiVariable Transmitter With the innovative Rosemount 4088 MultiVariable Transmitter, you can maximize your measurement accuracy
More informationProduct Data Sheet , Rev GA Catalog Content
HIGHLY ACCURATE SMALL-BORE FLOW MEASUREMENT CAPABILITY WITH MINIMAL INSTALLATION AND MAINTENANCE REQUIREMENTS Improves accuracy and repeatability in 1 /2-in., 1-in., and 1 1 /2-in. line sizes Reduces leak
More informationRosemount Compact Vibrating Fork Liquid Level Switch. Product Data Sheet July , Rev EA
Product Data Sheet 00813-0100-4029, Rev EA Compact Vibrating Fork Liquid Level Switch Virtually unaffected by turbulence, foam, vibration, coating, or changing liquid properties Built in diagnostics continuously
More informationRosemount Product Data Sheet , Rev GA Catalog FIELDBUS PROTOCOL. Hazardous Locations Certifications
Product Data Sheet Rosemount 3051 FIELDBUS PROTOCOL Hazardous Locations Certifications North American Certifications FM Approvals E5 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof
More informationRosemount 8700 Series Magnetic Flowmeter Sensors
Quick Installation Guide Magnetic Flowmeter Sensors Start Step 1: Pre-Installation Step 2: Handling Step 3: Mounting Step 4: Installation (Flanged Sensors) (Wafer Sensors) (Sanitary Sensors) Step 5: Grounding
More informationRosemount Multipoint Thermocouple and RTD Profiling Sensors
Product Data Sheet FEATURES Efficiently monitor a temperature profile for a wide range of applications, including hot-spot detection in reactors Single process insertion for up to 60 independent measurement
More informationRosemount 2160 Wireless Vibrating Fork Liquid Level Switch
Technical Note Communicate Rosemount 2160 Rosemount 2160 Wireless Vibrating Fork Liquid Level Switch The Rosemount 2160 Wireless Level Switch is based on vibrating short fork technology, and is designed
More informationProductDiscontinued Contents
Product Data Sheet THE PROVEN LEADER IN MULTIVARIABLE MASS FLOW MEASUREMENT 1.0% Mass Flow rate accuracy over 10:1 Flow Range Ten year stability under actual process conditions Unprecedented reliability
More informationRosemount 285 Annubar Primary Element Series
0013-0100-02, Rev CA Rosemount 25 Annubar Primary Element Series Designed for general purpose applications Increased plant uptime with the maintenance-free design Energy savings gained through minimal
More informationRosemount 1067 Compact Sensor and 1097 Thermowell
Product Data Sheet Rosemount 1067 and 1097 Rosemount 1067 Compact Sensor and 1097 Thermowell RTD and Thermocouple single and dual sensor models (1067 Model) Wide selection of materials available for thermowells
More informationRosemount Orifice Series Differential Pressure Flow
Rosemount Orifice Series Differential Pressure Flow Innovative Offering for Better Measurement Revolutionizing the Industry Workhorse Orifice Plate Technology It s no coincidence that orifice plates are
More informationRosemount 3095 MultiVariable Mass Flow Transmitter and Flowmeters
Product Data Sheet THE PROVEN LEADER IN MULTIVARIABLE MASS FLOW MEASUREMENT. 1.0% Mass Flow rate accuracy over 10:1 Flow Range Ten year stability under actual process conditions Unprecedented reliability
More informationRosemount 3051S Electronic Remote Sensor (ERS) System
Rosemount 3051S Electronic Remote Sensor (ERS) System The Rosemount 3051S ERS System is a flexible, 2-wire 4-20 ma ART architecture that calculates differential pressure (DP) electronically using two pressure
More informationFlow Computer Installation
Flow Computer Installation WARNING: Only personnel who are experienced with field wiring should perform these procedures. All field wiring must conform to the National Electrical Code, NFPA 70, Article
More informationMobrey MLT100. Displacer Level Transmitter. Product Data Sheet February 2015 IP119, Rev CA. Level, contents or interface measurement transmitter
Product Data Sheet February 2015 IP119, Rev CA Displacer Level Transmitter Level, contents or interface measurement transmitter Direct or external chamber mounting 4 20 ma HART output ATEX Intrinsically
More informationRosemount 3051S Series of Instrumentation
Product Data Sheet 3051S Series delivers highest field performance and reliability SuperModule Platform provides a foundation for integrated pressure, flow, and level solutions IEC 62591 (WirelessHART
More informationSmart Pressure Transmitter
DOC. NO.: C3100L-E16B Smart Pressure Transmitter with Diaphragm Seal MODEL APT3100L DUON System Co., Ltd. 298-29, GONDAN-RO, GUNPO-SI, GYEONGGI-DO, KOREA 15809 Tel : +82-31-3-6100 Fax : +82-31-29-7200
More informationSmart Pressure Transmitter
DOC. NO.: C3500L-E16A Smart Pressure Transmitter with Diaphragm Seal MODEL APT3500L 298-29, GONDAN-RO, GUNPO-SI, GYEONGGI-DO, KOREA 15809 Tel : +82-31-3-6100 Fax : +82-31-29-7200 E-mail: autrol@duon.co.kr,
More informationRosemount 3051S Series of Instrumentation
Product Data Sheet January 2013 00813-0100-4801, Rev RA Rosemount 3051S Series of Instrumentation Scalable Pressure, Flow, and Level Solutions Innovation Reaching Across Your Operation With the Rosemount
More informationOPERATIONS MANUAL M-520. Please take the time to read these instructions before starting to use the scales. Page 1
OPERATIONS MANUAL M-520 Please take the time to read these instructions before starting to use the scales Page 1 Contents Power supply 3 Specifications 3 Maintenance and general care 3 Key functions 4
More informationModel 3051 Sensor Module Replacement
Model 3051 Sensor Module Replacement 00809-0400-4001 English Rev. BA SAFETY MESSAGES Procedures and instructions in this manual may require special precautions to ensure the safety of the personnel performing
More informationRosemount Magnetic Flowmeter Systems (Transmitter and Flowtube)
November 2003 Rosemount 8712D / 8700 Series Rosemount Magnetic Flowmeter Systems (Transmitter and Flowtube) ProductDiscontinued Start Step 1: Pre-Installation Step 2: Wiring Step 3: Basic Configuration
More informationRosemount 3051 Pressure Transmitter
Rosemount 3051 Pressure Transmitter Product Data Sheet April 2014 00813-0100-4001, Rev RC With the Rosemount 3051 Pressure Transmitter, you ll gain more control over your plant. You ll be able to reduce
More informationFB1100/FB1200 Flow Computer Battery Field Replacement Guide
FB1100/FB1200 Flow Computer Battery Field Replacement Guide For Part Numbers (Kits): 399103-01-5 Battery Pack (lithium) 399186-01-8 Battery Pack (lead Acid) 399457-00-0 Battery Pack (lead acid-enersys)
More informationStart FINAL. Step 8: Process Leak Protection (Optional) Step 9: Power up the Transmitter. Step 10: Check Process Connections
Rosemount Magnetic Flowmeter System (Transmitter and Flowtube) with FOUNDATION fieldbus ProductDiscontinued Start Step 1: Pre-Installation Step 2: Handling Step 3: Mounting Step 4: Installation (Flanged
More informationTrue Fail-Safe Technology and Precision Control for Reliable Shutdown
True Fail-Safe Technology and Precision Control for Reliable Shutdown RTS Series Compact Fail-Safe Electric Actuators Reliable, Accurate, Compact Electric Actuation Technology for Critical Fail-Safe and
More informationRosemount TM 222 Toroidal Flow-Through Conductivity Sensor. Instruction Manual LIQ-MAN-222 Rev.D June 2017
Rosemount TM 222 Toroidal Flow-Through Conductivity Sensor Instruction Manual LIQ-MAN-222 Rev.D June 2017 SPECIFICATIONS Wetted Materials: Teflon-lined carbon steel pipe, with carbon steel outer flanges.
More informationRosemount 3051S Series of Instrumentation
Product Data Sheet May 2014 00813-0100-4801, Rev SA Rosemount 3051S Series of Instrumentation Scalable pressure, flow, and level solutions Innovation reaching across your operation With the Rosemount 3051S
More informationAnnubar Flowmeter Series
00813-0100-809, Rev CA Catalog 200 Annubar Flowmeter Series Best-in-Class integrated DP flowmeters are created when Annubar primary elements are packaged with Rosemount pressure transmitters Improved performance
More informationTriple offset technology for lower pressures.
Triple offset technology for lower pressures. Vanessa Series 30-RS Triple Offset Valves A triple offset valve designed for the specific needs of general applications in lower pressure classes. Emerson.com/FinalControl
More informationRosemount 3051 Pressure Transmitter
Product Data Sheet Rosemount 3051 Rosemount 3051 Pressure Transmitter THE PROVEN INDUSTRY LEADER IN PRESSURE MEASUREMENT Best-in-Class performance with up to 0.04% reference accuracy Industry first installed
More informationCertificate of Compliance
Certificate of Compliance (033332_0_000) Issued to: Rosemount Inc. 6021 Innovation Blvd. Shakopee, Minnesota 55379-9795 USA Attention: Glen Edwards The products listed below are eligible to bear the CSA
More information, General Instructions for Handling and Installation of Rosemount 1199 Seal Systems
Quick Installation Guide August 2011 Rosemount 1199 General Instructions for Handling and Installation of Rosemount 1199 Seal Systems Start Introduction Preface General Handling Overview Mechanical Installation
More informationLead-free glass Nickel plated brass 62 ma 1.25 A Over 1.25 A 3 A Epoxy resin 62 ma less than 1 A. Tube: End-cap: Solder: Adhesive: Marking: 1 A 3 A
RoHS Pb Dimensions and construction: (mm) Tube: End-cap: Solder: Adhesive: Marking: Lead-free glass Nickel plated brass 62 ma 1.25 A Over 1.25 A 3 A Epoxy resin 62 ma less than 1 A 1 A 3 A Sn-0.7Cu Sn-3.0Ag-0.5Cu
More informationLead-free glass Nickel plated brass Ceramic 100 ma 15 A. Tube: End-cap: Core: Solder: 200 A. Marking: 100 ma 8 A Over 8 A 20 A. Rated breaking current
* RoHS Dimensions and construction: (mm) Tube: End-cap: Core: Solder: Marking: Lead-free glass Nickel plated brass Ceramic 100 ma 15 A 20 A 100 ma 8 A Over 8 A 20 A Sn-1.5Cu Pb87.5-Sn10.0-Ag2.5* Pb90-Cu*
More informationSmart Pressure Transmitter
DOC. O.: C3700-L-E16A Smart Pressure Transmitter with Diaphragm Seal MODEL APT3700-L 298-29, GODA-RO, GUPO-SI, GYEOGGI-DO, KOREA 15809 Tel : +82-31-3-6100 Fax : +82-31-29-7200 E-mail: autrol@duon.co.kr,
More informationInstallation Manual Type DDR DIN rail power supply Series DDR-120, DDR-240
Type:DDR DIN rail power supply(series:ddr-120, DDR-240) DDR-120A-12 INPUT: 9~18VDC 13.5A OUTPUT: 12V 7.1A (9~10.8Vin) 12V 8.3A (10.8~18Vin) DDR-120A-24 INPUT: 9~18VDC 13.5A OUTPUT: 24V 3.6A (9~10.8Vin)
More informationTube: End-cap: Core: Solder: Lead-free glass Nickel plated brass Ceramic Sn-1.5Cu. Pb87.5-Sn10-Ag2.5* ma less than 1 A.
* 1 RoHS Dimensions and construction: Tube: End-cap: Core: Solder: Lead-free glass Nickel plated brass Ceramic Sn-1.5Cu (mm) Marking: Pb87.5-Sn10-Ag2.5* 1 100 ma less than 1 A 1 A 15 A SOC [rated current]
More informationRosemount 3051S Series of Instrumentation
Product Data Sheet 00813-0100-4801, Rev UK December 2018 Rosemount 3051S Series of Instrumentation Innovation reaching across your operation With the Rosemount 3051S Series of Instrumentation, operations
More information1495 Orifice Plate 1496 Flange Union 1497 Meter Section Installation & Operation Manual
00809-0100-4792 DS-4127 English Rev. AA 1495 Orifice Plate 1496 Flange Union 1497 Meter Section Installation & Operation Manual COMPLETE POINT SOLUTIONS PRINTED Product Manual Model 1495 Orifice Plate
More informationMicro Motion. CMF400 Sensor. Installation Instructions. Quick Reference Guide P/N , Rev. D May 2003
Quick Reference Guide P/N 3006075, Rev. D May 2003 Micro Motion CMF400 Sensor Installation Instructions For online technical support, use the EXPERT 2 system at www.expert2.com. To speak to a customer
More informationThe Annubar Flowmeter Series. Rosemount 3051SFA ProBar Flowmeter. Product Data Sheet , Rev EA Catalog
00813-0100-809, Rev EA Rosemount 3051SFA ProBar Flowmeter SPECIFICATIONS Performance System Reference Accuracy Percentage (%) of volumetric flow rate Classic Ultra Ultra for Flow (8:1 flow turndown) (8:1
More informationRosemount Annubar Flowmeter Series
Product Data Sheet 00813-0100-809, Rev EA Rosemount Annubar Flowmeter Series Industry leading integrated DP flowmeters are created when Annubar primary elements are packaged with Rosemount pressure transmitters
More informationMiniature I/P, E/P Transducer
Miniature I/P, E/P Transducer Accurate and economical electronic pressure control The Type 550X is an electronic pressure regulator that converts a variable signal (current or voltage) to a proportional
More informationSentinel. Panametrics Custody Transfer Gas Ultrasonic Flowmeter. GE Sensing. Applications. Features
Applications The Sentinel flowmeter is a complete ultrasonic flowmeter system for the measurement of natural gas flow applications such as: Custody transfer Transmission and distribution Underground storage
More informationMicro Motion 7827 Digital Viscosity Meter
Product Data Sheet PS-001217, Rev. C April 2013 Micro Motion 7827 Digital Viscosity Meter Micro Motion viscosity meters are built to tackle the most demanding process and control applications. Rugged and
More informationRosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries
Product Data Sheet January 214 813-1-475, Rev FA Rosemount 875WA Magnetic Flowmeter System For Water and Wastewater Industries THE 875WA MAGNETIC FLOWMETER Rosemount reliability in a customized offering
More informationLow Cost, Low Maintenance Air, Compressed Air and Nitrogen Flow Measurement for Process and Plant Applications
FCI ST50 Series Flow Meters Low Cost, Low Maintenance Air, Compressed Air and Nitrogen Flow Measurement for Process and Plant Applications FCI ST50 FLOW METER Wastewater Treatment Aeration Control Blower
More informationMCF3 25CT Inrush-withstand
RoHS Pb Dimensions and construction: (mm) Case: End-cap substrate metal: End-cap primary plating: End-cap surface plating: Adhesive: Marking: Ceramic Copper t=0.25 mm Nickel plated, 0.5 μm or more Tin
More informationSentinel Panametrics Custody Transfer Gas Ultrasonic Flowmeter
GE Measurement & Control Sentinel Panametrics Custody Transfer Gas Ultrasonic Flowmeter Applications The Sentinel flowmeter is a complete ultrasonic flowmeter system for the measurement of natural gas
More informationDräger X-am 5100 Single-Gas Detection Device
Dräger X-am 5100 Single-Gas Detection Device For manufacturing petrochemical products, aseptic packing, or handling of rocket fuel: the Dräger X-am 5100 portable single-gas detector guarantees that you
More informationMCF3 DC86V11CT Inrush-withstand
RoHS Pb Dimensions and construction: (mm) Case: Cover: Terminal substrate metal: Terminal primary plating: Terminal surface plating: Adhesive: Marking: Ceramic Ceramic Copper t=0.1 mm Nickel plated copper,
More informationTop Mount Installation for DP Flowmeters in Steam Service
00870-0200-4809 July 2009 Page 1 Top Mount Installation for DP Flowmeters in Steam Service This paper discusses installation of Rosemount Annubar and Compact Primary Element products above the pipe in
More informationRosemount 3051 Pressure Transmitter
Product Data Sheet Rosemount 3051 Rosemount 3051 Pressure Transmitter THE PROVEN INDUSTRY LEADER IN PRESSURE MEASUREMENT Best-in-Class performance with 0.04% High Accuracy option Industry first installed
More informationCertificate of Compliance
Certificate of Compliance Certificate: 70054084 Issued to: Emerson - Rosemount, Micro Motion Inc. 12001 Technology Dr. Eden Prairie, Minnesota 55344 USA Attention: Paul Schilke The products listed below
More informationLead-free glass Nickel plated brass Ceramic Tin plated copper Sn-1.5Cu Pb87.5-Sn10.0-Ag2.5* SOC NSD9 D32V [rated current]
* RoHS Dimensions and construction: (mm) Tube: End-cap: Core: Lead wire: Solder: Marking: Lead-free glass Nickel plated brass Ceramic Tin plated copper Sn-1.5Cu Pb87.5-Sn10.0-Ag2.5* SOC NSD9 D32V [rated
More informationRosemount 1195 Integral Orifice Primary Element
September 2014 Rosemount DP Flow Rosemount 1195 Integral Orifice Primary Element Rosemount 1195 Integral Orifice Primary Element utilizes a self centering orifice plate design to eliminate installation
More informationRosemount 1151 Pressure Transmitter
Product Data Sheet Rosemount 1151 Rosemount 1151 Pressure Transmitter Proven field performance and reliability Commitment to continuous improvement Reference accuracy of 0.075% Two-year stability of 0.1%
More informationRosemount DP Flowmeters and Primary Elements
meters and Primary Elements Multivariable capabilities allow for real time fully compensated mass and energy flow Fully-Integrated Wireless Flowmeters allow for easy installation Minimize permanent pressure
More informationInstallation, Operation and Maintenance Manual RGS Rev. 0 November Bettis RGS F-Series Spring-Return Actuators
Installation, Operation and Maintenance Manual RGS011110-3 Rev. 0 November 2015 Bettis RGS F-Series Spring-Return Actuators Installation, Operation and Maintenance Manual RGS011110-3 Rev. 0 Table of Contents
More informationMultiport Flow Selector. Compact And Economical Production Test Manifold
Multiport Flow Selector Compact And Economical Production Test Manifold Design and Construction Emerson Process Management Valve Automation provides a broad product offering of automation and control solutions
More informationCBA300 Series Pneumatic Actuators Improved Design - Compact, Lightweight To Suit All Applications And Environment
CBA300 Series Pneumatic Actuators Improved Design - Compact, Lightweight To Suit All Applications And Environment Design and Construction Emerson is the global leader in valve automation, providing reliable
More informationLEDEEN SEF. Smart electric fail-safe actuator and control systems
LEDEEN SEF Smart electric fail-safe actuator and control systems The Cameron portfolio of LEDEEN* actuators includes a new compact, modular, onboard hydraulic power unit (HPU). This new technology is operated
More informationRosemount 9901 Chamber for Process Level Instrumentation
Product Data Sheet Rosemount 9901 Rosemount 9901 Chamber for Process Level ation Allows external mounting of process level instrumentation Enables live maintenance Designed to ASME 31.3 Process Piping
More informationManual No: Revision: B. CCVP Rain Shield. Installation Guide
Manual No: 577013-978 Revision: B CCVP Rain Shield Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties
More informationRosemount 405 Compact Orifice Series
Reference Manual Rosemount 405 Compact Rosemount 3051SFC Compact Orifice Flowmeter Rosemount 3095MFC Compact Orifice Mass Flowmeter www.rosemount.com Reference Manual Rosemount 405 Compact Rosemount 405
More informationMicro Motion F-Series Coriolis Flow and Density Sensors. Installation Manual , Rev CC December 2010
Micro Motion F-Series Coriolis Flow and Density Sensors Installation Manual 20002298, Rev CC December 2010 Safety and approval information This Micro Motion product complies with all applicable European
More informationRosemount 2051 Pressure Transmitter
Product Data Sheet Rosemount 2051 Rosemount 2051 Pressure Transmitter Reference Accuracy of 0.075% Rangeability of 100:1 Protocols available include 4-20 ma HART, FOUNDATION fieldbus, 1-5 Vdc HART Low
More informationRosemount DP Flowmeters and Primary Elements
Product Data Sheet Rosemount DP Flowmeters and Primary Elements Rosemount DP Flow Multivariable capabilities allow for real time fully compensated mass and energy flow Fully-Integrated Wireless Flowmeters
More informationQVT MULTIVARIABLE TRANSMITTER
QVT MULTIVARIABLE TRANSMITTER QVT INSTALLATION & OPERATION MANUAL REV 8/16 REVISION VERSION 0.3.4 ORIGINAL LANGUAGE Copyright 2016 Eastern Instrument Laboratories, Inc. All Rights Reserved. TABLE OF CONTENTS
More informationTypes 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators
Instruction Manual Form 5116 Types 1808 and 1808A July 2010 Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators! Warning Failure to follow these instructions or to properly install
More information