ROADWAY LIGHTING SYSTEMS (2545)
|
|
- Stanley Simmons
- 6 years ago
- Views:
Transcription
1 GENERAL LIGHTING MATERIAL REQUIREMENTS General material requirements must be in accordance with MnDOT SERVICE CABINETS 3850 Lighting service cabinets Type L1, Type L2, Type A, Type B, and Type RLF are on MnDOT s Approved/Qualified Products List (APL) for Roadway lighting. The lighting service cabinets described below can accommodate branch circuits for roadway lighting as indicated. Lighting service cabinets are rated for either 120/240 or 240/480 VAC single phase service. Service Cabinet Type L1 SYSTEMS (2545) This is an equipment pad mounted service cabinet with power distribution blocks, a two pole 100 ampere main circuit breaker and four (4) two pole 20 ampere branch circuit breakers. A 3- wire locking type mounting receptacle is located inside the cabinet at the PEC windows for the photoelectric control device. 14-1
2 Service Cabinet Type L2 This is an equipment pad mounted service cabinet with power distribution blocks, 2 two pole 100 ampere circuit breakers and eight (8) two pole 20 ampere branch circuit breakers. A 3-wire locking type mounting receptacle is located inside the cabinet at the PEC windows for the photoelectric control device. 240/480 service cabinets (Type L1 and L2) may include a cold sequence disconnect (ahead of the meter) that meets the requirements of the electric utility company. Xcel Energy does not allow the use of the cold sequence disconnect. Information on equipment pads for service cabinets can be found in Chapter 10 Foundations & Equipment Pads. 14-2
3 Service Cabinet Type A This pole mounted service cabinet is similar to an equipment pad mounted Type L1, with a two pole 100 ampere main circuit breaker and four (4) two pole 20 ampere branch circuit breakers. This allows for four runs from the cabinet. A 3-wire locking type mounting receptacle is located inside the cabinet at the PEC windows for the photoelectric control device. Service Cabinet Type B This pole mounted service cabinet has a 60 ampere 2 pole main circuit breaker and two (2) two pole 20 ampere branch circuit breakers. This allows for two runs from the cabinet. A 3-wire locking type mounting receptacle is located inside the cabinet at the PEC windows for the photoelectric control device. 14-3
4 14-4
5 Rural Lighting and Flasher (RLF) Cabinet This equipment pad mounted Rural Lighting and Flasher (RLF) 120/240 VAC service cabinet is used for smaller lighting and flasher systems. A 3-wire locking type mounting receptacle is located inside the cabinet at the PEC windows for the photoelectric control device. SERVICE EQUIPMENT INSTALLATION L All wiring within the lighting service cabinets must meet the requirements of the National Electrical Code (NEC). All L1 and L2 lighting service cabinets must have utility termination lugs installed on the line side wire way, unless the cabinets are being installed in the Xcel Energy service area. Lighting service cabinets must include all required wiring, internal and external, for a complete lighting service cabinet installation. All components are to be listed by a National Recognized Testing laboratory (NRTL). Install lighting service cabinets in accordance with MnDOT L. Position the cabinet door from 90 degrees to 180 degrees to the roadway, away from traffic. 14-5
6 The electric utility company must be contacted for information on size of meter socket, exact location of meter, etc. Meters are furnished and installed by others. Lighting service cabinets are large enough for additional equipment to be installed internally if requested by the electric utility company. Lighting service cabinets are rated for either 120/240 or 240/480 VAC single phase service. Circuit breakers must be labeled in accordance with Specification P.2.a. The Contractor is required to fill out an Electric Service Information Form for each lighting service on the project. A sample of this form is included in the Appendix. The contractor is required to calculate available fault current at the meter socket in accordance with the NEC Article Required contractor supplied labels are defined in contract documents. Photoelectric Controls (mounted inside service cabinets) Currently MnDOT uses a photoelectric control inside the service cabinets for turning "ON" and "OFF" the roadway luminaires on signal and roadway lighting systems. The photoelectric controls are installed in a 3-wire locking type mounting receptacle located inside the cabinet at the PEC windows. 14-6
7 MnDOT approved photoelectric controls are listed on MnDOT s Approved/Qualified Products List (APL) for Roadway lighting. Standard photoelectric controls used on MnDOT projects must be an ANSI Multi-volt Volt (colored Blue) photocontrol. Position the photoelectric controls to face north. The photoelectric control may face east or west only if facing it north is not an option due to service cabinet orientation. 14-7
8 DIRECT BURIED LIGHTING CABLE 3815 Most MnDOT lighting projects require direct buried 4 conductor No. 4 AWG cable. Direct buried lighting cable must be in accordance with contract documents. Within 15 days after the Contract approval notice mailing date, the Contractor must furnish evidence to the Engineer, in writing, that orders have been placed for all direct buried lighting cable required for the project. WIRE AND CONDUCTOR INSTALLATION G Underground Wiring Direct Buried Lighting Cable Direct buried lighting cable must be installed in accordance with MnDOT G. The lighting cable must be installed at the same distance behind the bituminous shoulder or back of curb as the light foundations. 14-8
9 When an obstruction has been encountered in the path of the direct buried lighting cable, re-route the direct buried lighting cable around the obstruction away from the roadway. Direct buried lighting cable must be installed in rigid PVC or HDPE conduit under paved surfaces G.2 Install direct buried lighting cable in rigid PVC or HDPE conduit if located under bituminous, concrete, or other material not considered a top soil. Provide 3 in conduit if the contract does not specify size of conduit. Use a vibratory plow with a plow blade chute to reduce stresses on the cable during installation. Place plastic warning tape meeting the following characteristics at least 12 inches (300 mm) above the direct buried lighting cable: 1. 3 inch (75 mm) wide, 2. Permanent Red 3. Stretchable 4. Non-biodegradable 5. Imprinted with the inscription, CAUTION-MnDOT LIGHTING CABLE BELOW Install direct buried lighting cable from the reel or spool immediately into the ground. Do not lay direct buried lighting cable for the new lighting system on the ground and use as temporary. 14-9
10 Provide 2 feet of slack cable in an S pattern (within the width of the foundation) before cable enters the light foundation.. On a project where guardrail is also being installed, locate and/or install the guardrail before placing the lighting cable in order to help reduce or eliminate cable hits. METAL GUARDRAIL POST 14-10
11 Above Ground Splices Where above ground splices are allowed (pole base), the splices must be either split-bolt connectors or insulated wire splice connector blocks. SPLIT-BOLT CONNECTOR Use split-bolt connectors or insulated wire splice connector blocks to splice together the direct buried lighting cable and the light pole wiring in the light pole base in accordance with contract documents. MnDOT approved Insulated Wire Splice Connector Blocks are listed on MnDOT s Approved/Qualified Products List (APL) for Roadway lighting. INSULATED WIRE SPLICE CONNECTOR BLOCK Light Pole Wiring Install light pole wiring in accordance with MnDOT G The wires connecting the luminaire to the direct buried lighting cable must be one continuous length without splice 12-2 UF cable with ground and a breakaway fuse holder installed with a cartridge type fuse. Terminate the individual black Hot conductor of the 12-2 UF cable directly to the barrel terminal on Load side of the fuse holder. Do not use wire nuts for light pole wiring. Place the breakaway fuse holder at the level of the access opening in the pole base. The fuse holder must be a MnDOT approved breakaway fuse holder as listed on MnDOT s Approved/Qualified Products List (APL) for Roadway lighting. Use a 6 Amp 1.5 in X.406 in [38.1mm X 10.31mm] time delay cartridge fuse
12 The Contractor must provide sufficient excess conductor length to allow withdrawal of the connected fuse holder. The fuse holder must be properly orientated with respect to the line side and the load side. The neutral and grounding wires must not be fused. LOAD SIDE (Luminaire) LINE SIDE (Supply Side) Provide a MnDOT approved luminaire wire holder that supports the luminaire cable/conductors within the end of the light pole tenon near the connection point of the luminaire. MnDOT approved Wire Holders are listed on the MnDOT Approved/Qualified Products List (APL) for Roadway lighting. Luminaire Wire Holders 14-12
13 SIGNALS LIGHTING There are two types of MnDOT approved luminaire wire holders. One is designed for traffic control signal systems and the other for roadway lighting systems. Traffic control signal system luminaries require MnDOT approved luminaire wire holders that accommodate a round 3 conductor #14 AWG cable assembly that runs one continuous length without splice from the signal service cabinet to the luminaire atop the signal pole luminaire davit. Roadway lighting system luminaries require a MnDOT approved luminaire wire holder that accommodates a flat 12-2 UF cable
14 Underground Cable Splices No underground splices will be permitted that are not called for in the contract or approved in writing by the District Traffic Engineer. When direct buried cable splices are permitted install in accordance with G.4.b. Two Way Direct Buried Handhole Cable Splice When required, use a two way direct buried handhole cable splice in accordance with contract documents 14-14
15 Three Way Direct Buried Handhole Cable Splice When required use a three way direct buried handhole cable splice in accordance with contract documents. General MnDOT roadway light poles: ROADWAY LIGHT POLES ) Must be in accordance with the current edition of AASHTO Standard Specifications of Structural Supports for Highway Signs, Luminaires, and Traffic Signals. 2) If providing breakaway poles, the poles must be certified from the manufacturer that the pole meets specifications as specified in the current edition of AASHTO Standard Specifications of Structural Supports for Highway Signs, Luminaires, and Traffic Signals. 3) Must have a nominal 2 3/8 in schedule 40 tenon for slip fit luminaire installation. 4) Davit or mast arm must have an upward angle from horizontal of 3 degree +/- 2 degrees. There are several of types of light poles MnDOT uses. The most common types of poles used on MnDOT roadway lighting systems are: Coated (Galvanized) Steel Bridge and Barrier 40 foot and 49 foot nominal height Non- Breakaway Stainless Steel 40 Foot and 49 Foot Breakaway Aluminum Alloy 40 Foot and 49 Foot Breakaway High Mast Light Towers 14-15
16 Bridge and Barrier Poles 40 Foot and 49 Foot Galvanized Steel Non-Breakaway High Base 6-Bolt Base Plate 2 Access Door Assembly Single and Double Davit Mounted on Barrier (Center Median and Bridge Barrier Foundations) 14-16
17 Breakaway Roadway Light Poles 40 Foot and 49 Foot (Stainless Steel and Aluminum Alloy) Aluminum Alloy Pole: Transformer Base (Bolt On) Typically Single Davit (6 FT- 12 FT) Mounts on Design E and H Foundations Stainless Steel Pole: Slip Fit High Base 16 Sided Typically Single Davit (6 FT 12 FT) Mounts on Design E and H Foundations 14-17
18 High Mast Towers COR-TEN Steel (Weathering Steel) H Base Design Typically 100 FT or 120 FT Typically Ring Assembly Holds 3 to 4 Luminaires 14-18
19 A lighting unit is defined as follows: Includes the light pole, internal wiring with fuse holder and fuse to the luminaire, above ground splices, wire holder, stainless steel woven wire cloth, and luminaire. Underpass luminaires are lighting units even though they do not include some of these components. The foundation is not considered as part of this definition. The type of light pole required for each project will be shown in contract documents. Light poles that are specified by MnDOT are fabricated from stainless steel, high strength steel, or aluminum. Light poles fabricated from aluminum must have a factory installed vibration dampener. Light poles must be fabricated in accordance with MnDOT Within 15 days after the contract approval notice mailing date, the contractor must furnish evidence to the Engineer, in writing, that orders have been placed for all components of the lighting units required for the project. The Contractor must submit to the Engineer, for approval by the District s Traffic Engineer, four complete sets of shop detail drawings of the light poles and anchor rods, in accordance with B1 and B3. For high mast lighting installations, the Contractor must submit final reproducible drawings in accordance with B. The drawings must be distributed after approval, to the following: (a) (b) (c) (d) Contractor Contractor s Fabricator Engineer District Traffic Engineer All light poles must be approved before installation
20 Rodent Intrusion Prevention Stainless Steel Light Poles Install stainless steel woven wire cloth in accordance with MnDOT H in stainless steel light poles between the base plate and the foundation and use 100% clear silicone sealant to fill voids between the woven wire cloth and the pole base plate to protect against rodent intrusion. WOVEN WIRE CLOTH AND SILICONE SEALANT Aluminum Light Poles For aluminum light pole bases do not install stainless steel woven wire cloth. Instead, fill any gaps as a result of using leveling shims that exceed 1/8 in between the foundation and the aluminum light pole base with 100% clear silicone sealant. Do not completely seal around the perimeter between the foundation and the aluminum light pole base
21 LUMINAIRES All LED Luminaires listed on MnDOT s APL have a minimum Ten (10) year warranty. These luminaires will operate in a range of VAC (rms) with an integral power supply, pre-wired in the factory with terminal blocks or color coded pigtails for field connections. All MnDOT approved luminaires must have an ANSI C standard 7-terminal twist-lock type photoelectric control mounting receptacle with shorting cap and a dimmable electronic driver (power supply). MnDOT approved luminaires are listed on MnDOT s Approved/Qualified Products List (APL) for Roadway lighting. LED Roadway Luminaires (40 foot mounting height) Light emitting diode (LED) luminaires for mounting at 40 feet are replacements for the existing 250 watt HPS luminaire. The housing must be adaptable to the nominal 2 3/8 inch (50 mm) diameter tenon on the end of the luminaire mast arm. This class of LED luminaire is used in both roadway lighting and at traffic control signal systems. LED Roadway Luminaires (49 foot mounting height) Light emitting diode (LED) luminaires for mounting at 49 feet are replacements for the existing 400 watt HPS luminaire. The housing must be adaptable to the nominal 2 3/8 inch (50 mm) diameter tenon on the end of the luminaire mast arm
22 Vertical Mount Luminaires LED Replacements (Replaces 250 and 400 HPS Luminaires) LED replacements for vertical mount luminaires are LED roadway luminaires for mounting at 49 feet. A 90 degree tenon mount adaptor must also be used. The 90 degree pole adaptor must be MnDOT approved adaptors listed on MnDOT s Approved /Qualified Products List (APL) for Roadway lighting. LED Underpass Luminaires LED underpass luminaires are replacements for 250 watt high pressure sodium luminaires. The housing of the luminaire is anodized aluminum. Underpass luminaires are usually installed on the abutment of a bridge or on a pier a minimum of 17 feet above the traveled roadway. If such mounting would place a luminaire more than about 20 feet from the edge of the traveled roadway, the luminaire is usually mounted on a metal mounting bracket bolted under the bridge deck. Bird spikes are now required to be installed on underpass luminaires. A full size instruction sheet can be found in the appendix
23 LED Luminaires on Signal Poles (40 foot mounting height) Luminaires are mounted on signal poles to provide intersection illumination. They are LED luminaires found on MnDOT s APL under LED Roadway Luminaires for mounting at 40 feet. High Mast Luminaires (Tower Lights) High mast luminaires are 1000 watt high pressure sodium symmetrical or asymmetrical luminaires with ballasts. High mast luminaires must be MnDOT approved luminaires as listed on MnDOT s Approved/Qualified Products List (APL) for Roadway lighting
24 LUMINAIRE INSTALLATION Q Install and level luminaires in accordance with MnDOT Q, the manufacturer s installation requirements and to the satisfaction of the Engineer. Luminaires need to be installed in accordance with manufacturer s installation requirements. Tightening of the bolts that hold the luminaire on the tenon have specific tightening torque requirements that must be followed. Over tightening of these bolts can cause damage to the luminaire or the tenon
25 Place a level on the area provided on the top of the luminaire, and level side to side and front to back direction. Adjust the luminaire as required to completely level the luminaires. Luminaires must be level in order to perform properly. Lighting Controls Lighting controls (smart photocontrols) are becoming more popular with the introduction of the LED Luminaire. MnDOT Luminaires come standard with a 7 pin photocontrol receptacle with shorting cap and a dimmable electronic driver (power supply). These features make the luminaires lighting controls ready by simply replacing the shorting cap with a smart photocontrol. On some MnDOT roadway lighting projects smart photocontrols may be required. The Department may supply the smart photocontrols to the contractor for installation on the 14-25
26 luminaire prior to the luminaire being installed on the pole. Refer to the project s special provsions. It s important that the photocontrol window be faced north as required by the manufacturer. If a north facing node is not achievable then facing east or west is an acceptable alternative. Lighting Control Systems monitor and provide the following; 6. Energy measurement at revenue grade per luminaire 7. Luminaire voltage. 8. Luminaire wattage. 9. Luminaire type LED or HPS. 10. Luminaire dimming (0 to 10 Volts). 11. Dayburner. 12. No communication. 13. Global Positioning System (GPS) location. Smart photocontrols are not listed on the MnDOT s APL for Roadway lighting. There is a state contract in place where CPV members can purchase smart lighting controls. A modification in the lighting service cabinet will be required when lighting controls are installed. The contactor must be bypassed and de-energized. The luminaire and pole wiring will be energized 24 hours a day. Continuous powering of the lighting control allows the lighting control and the luminaire to report their status 24 hours a day 7 days a week. (photocontrols cont. next page) 14-26
27 Since luminaires and wiring in the light pole bases will be energized 24 hours a day, a Hazardous Voltage warning label will be placed on light poles and on the lighting service cabinet. Refer to the special provisions for the project on how to procure and apply the warning labels
28 AIR OBSTRUCTION LIGHTS 3816 MnDOT has Light Emitting Diode (LED) Air Obstruction Lights listed on MnDOT s Approved/Qualified Products List for Roadway lighting. MnDOT approved air obstruction lights include infrared light to aid pilots using night vision goggles. Air Obstruction Light Installation When the project requires air obstruction lights be installed on a roadway light pole the Plans and Special Provisions will require each pole requiring air obstruction lights to have a ¾ inch (N.P.T.) nipple welded to the horizontal portion of the light pole facing skyward. 3 conductor 14 AWG signal control cable must be pulled up from the pole base to the air obstruction light in addition to the required 12-2 UF with ground luminaire conductors. A separate breakaway fuse holder will be required in the pole base for the air obstruction light. NAVIGATION LANTERNS 3817 MnDOT has Light Emitting Diode (LED) navigation lanterns listed on MnDOT s Approved/Qualified Products List for Roadway lighting. Navigation Lantern Installation Install navigation lanterns in accordance with contract documents
29 LIGHT SYSTEM COMPONENT LABELING and NUMBERING P Lighting System Numbering The Contractor must number the light poles or the luminaires when light poles are not required (underpass luminaires, tunnel luminaires, special luminaires, etc.) and lighting service cabinets as specified in contract documents. FEEDPOINT NUMBER ASSETT TAG POLE NUMBER LIGHTING SERVICE CABINET Lighting service cabinets must have two feed point labels 4 feet above the concrete foundation. One label is required on the front door and one on the side of the cabinet that faces the roadway. MnDOT approved labels are listed on MnDOT s Approved/Qualified Products List (APL) for Roadway lighting
30 Labeling Lighting Cable and Conductors Label the direct buried lighting cable in service cabinets and lights pole bases indicating the next termination point in accordance with MnDOT P.2.b
31 Labeling Luminaires LED roadway luminaires require two types of labels be added by the contractor. One label defines the mounting height in feet 40 or 49 for the luminaire. The labels can be found on the MnDOT APL for lighting. Affix a machine printed label showing the month and year the LED luminaire was installed. Two of these labels are required, one on the outside of the luminaire facing the ground and one on the inside of the luminaire. CONTRACTOR SUPPLIED The contractor may also be required to install luminaire asset tags. See contract documents if asset tags are required on the project. LED underpass luminaires do not require a mounting height label be applied however the installation date label and the light unit number are required
32 ELECTRICAL SYSTEM TESTING AND ACCEPTANCE K General testing and acceptance requirements must be in accordance with K. CHECKLIST FOR ELECTRICAL SYSTEMS *The following list is a minimum and does not replace applicable specifications in The National Electrical Code (NEC) All Specification References are from the current Spec Book 1. Check SOP A. Meg all cables. Isolate neutral and ground. (2545.3K) B. All wires must meg greater than 100 meg ohms to earth ground. (2545.3K) C. All breakers labeled to indicate what poles are included in system per (NEC) D. Make sure wiring is neat. (2545.3G) E. Feedpoint number and MnDOT ESS labels should be on the cabinet. (2545.3P) F. Available Fault Current Calculations and Cabinet Label. (2545.3A.1) (2565.3CC) 2. Check Random Poles A. Check no less than 5 poles or up to one-third of system. B. Check fuse holder and fuse. (2545.3G3) C. Conduits right length. (Standard Plates 8127 and 8128) D. Splices insulated as per specs. (2545.3G4) E. Outside jacket of Direct Buried Lighting Cable striped back flush to 4 inches above the conduit opening. (2545.3G2) F. Cable depth consistent no less than 24 inches direct buried and conduit depth no less than 18 inches below finished grade. (2545.3G2) (2565.3D2b) G. Direct buried cable must be approximately 24 inches up into pole. (2545.3G.2) H. Handholes and lighting foundations to finish grade. (2545.3F2 and E) I. Feed point and light poles numbers should be put on all poles. (2545.3P) J. Cable routing changes must be noted on prints. K. Check wiring diagram for accuracy. L. Poles and system must be effectively grounded. (2545.3R) M. Poles plumb and luminaires are level. (2545.3H and Q) I certify that this project has met the above checklist criteria. Locating responsibility will be taken over when final is done and as-built is received. (Name) (Date) 14-32
33 LIGHTING SYSTEM TESTING AND ACCEPTANCE Prior to completion of the work, the Contractor must test the entire system for unwanted grounds and conduct a 12 hour burn test for each feed point (2545 3K). Megohm meter test (Test for unwanted grounds) A megohm meter test, at 500 volts DC, indicating the insulation resistance of each circuit must be made. The Contractor must furnish the Engineer with a written report of the megohm meter readings for the permanent record. The report must contain the following information: (1) PROJECT NUMBER AND LOCATION (2) FEEDPOINT NUMBER - As indicated in the Plans. (3) BRANCH CIRCUIT - Identify each lighting branch circuit being tested by indicating the number of the first light connected to that circuit, as indicated in the Plans. (4) PHASE CONDUCTOR INSULATION RESISTANCE - Measure the resistance between the phase conductors and between each phase conductor and the equipment ground bar in the service cabinet with the fuses removed from the in-line fuse connectors in the lighting poles. The resistance must not be less than 100 megohms. (5) NEUTRAL CONDUCTOR INSULATION RESISTANCE - Measure the resistance between each neutral conductor and the equipment ground bar in the service cabinet with the fuses removed from the in-line fuse connectors in the lighting poles. The resistance must not be less than 100 megohms. (6) CIRCUIT INSULATION RESISTANCE - Measure the resistance between each phase conductor and the equipment ground bar in the service cabinet with all fuses in place in the lighting poles. The resistance must not be less than 5 megohms. The contractor must make sure that the two circuit conductors are connected to the circuit breaker of the opposite phases. All tests must be made at the service cabinet, in the presence of the Engineer, with all grounding connections in place. THE PHASE AND NEUTRAL CONDUCTORS MUST BE DISCONNECTED AT THE SERVICE CABINET FOR THE INSULATION RESISTANCE TESTS
34 12 Hour Burn Test K.2 Upon completion of a lighting system and before no more than 90% of the lighting system cost is paid, the lighting cabinet must be energized and the entire lighting system must operate successfully without interruption for 12 hours, during daylight hours only. The 12 hour burn test is conducted during daylight hours to ensure that the system is fully functional prior to it being placed into service. Where test results indicate faulty insulation or a faulty connection within the circuit, all necessary corrections must be made and the circuit retested, all at no expense to the Department. No additional payment will be made for replacing any part of or the entire circuit as required to make the circuits meet the test requirements
MnDOT Specification Light Emitting Diode (LED) Luminaire For Roadway Lighting Asymmetrical High Mast 04/19/18
1. LISTING REQUIREMENTS MnDOT Specification Light Emitting Diode (LED) Luminaire For Roadway Lighting Asymmetrical High Mast 04/19/18 1.1. The luminaire shall be listed by a National Recognized Testing
More informationSIGNAL HEADS. The LED signal indication must operate on a nominal 120 VAC power source.
SIGNAL HEADS All signal heads and pedestrian signal heads must be Standard ITE black poly-carbonate signal heads. Standard ITE vehicle signal heads must utilize Light Emitting Diodes (LED) units. The vehicle
More informationD9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE
SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More information7. Residential Single-Family and Duplex Buildings (Dwellings)
Sin g le -F a mily a n d Du p le x Bu ild in g s 2016 Electric Service Requirements, 2 nd Edition Section 7 Section 7 Residential Single-Family and Duplex Buildings (Dwellings) Directory Page 7.1 General
More informationFor Conduit Inspections
Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit
More informationUNDERGROUND SERVICES - SECONDARY
UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service
More information10 Commercial, Industrial, Agricultural Services
10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three
More informationELECTRICAL MATERIALS. Hot-dip galvanize the inside and outside surfaces of rigid steel conduit and fittings.
ELECTRICAL MATERIALS 3801 RIGID STEEL CONDUIT 3801.1 SCOPE Provide rigid steel conduit and fittings for electrical systems. 3801.2 REQUIREMENTS Use rigid steel conduit listed and labeled by an NRTL, as
More informationCustomer Requirements Downtown Secondary Network Service
Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard
More information320A Single Phase URD Meter Loop Installations
320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal
More information9. Non-Residential Services (Commercial, Industrial, and Agricultural)
Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect
More informationAPPENDIX B: LISTS OF APPROVED MATERIALS
APPENDIX B: LISTS OF APPROVED MATERIALS APPENDIX B: LISTS OF APPROVED MATERIALS B1 Street Lighting MAY 2016 APPENDIX B1 STREETLIGHTING MATERIAL LIST 1.0 LIGHTING 1.1 Electrical Handholes CSA Precast concrete
More informationRESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS
SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated
More informationUNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.
UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later
More informationPentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION
PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company
More informationMN/DOT Specification Light Emitting Diode (LED) Luminaire 03/20/2012
1. LISTING REQUIREMENTS MN/DOT Specification Light Emitting Diode (LED) Luminaire 03/20/2012 1.1. The Luminaire shall be listed by a National Recognized Testing Laboratory (NRTL) as defined by the U.S.
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to
More informationCONSTRUCTION SPECIFICATION FOR THE INSTALLATION OF ROADWAY LUMINAIRES
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 617 SEPTEMBER 1984 CONSTRUCTION SPECIFICATION FOR THE INSTALLATION OF ROADWAY LUMINAIRES 617.01 SCOPE 617.02 REFERENCES 617.05 MATERIALS TABLE OF CONTENTS
More informationApproved Contractor Construction e-guide Residential Commercial
Approved Contractor Construction e-guide Residential Commercial Clark Public Utilities PO Box 8900 Vancouver, WA 98668 (PAGE 2) TABLE OF CONTENTS PAGE Trenching 3 Wire 8 Single-Phase Transformer Set 13
More informationDISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS
Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.
More informationIMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS
1 AQUALUMIN III NICHELESS POOL LIGHT INSTALLATION GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Section Contents 1. Installing a mounting bracket and light
More informationSECTION 500 METERING AND ASSOCIATED EQUIPMENT
SECTION 500 METERING AND ASSOCIATED EQUIPMENT 500.0 General Meter sockets shall be provided, installed and maintained by Customer. When the ratings of meter sockets are exceeded, transockets shall be used.
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationSentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions
WARNING HIGH VOLTAGE 115V 4 M AP Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions Important: For your protection and the safety of the
More informationQuik-Spec Coordination Panelboard Specifications
Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY
More informationContacts The moveable contact, which is the one affected by the armature is sometimes referred to as the hinge contact.
Relays & Wiring 101 Basically, a relay is an electrically operated, remotely controlled switch. A simple electromagnetic relay is an adaptation of an electromagnet. It consists of a coil of wire surrounding
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationCHAPTER V RESIDENTIAL WIRING
CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this
More informationINSTRUCTION SHEET PRL-97X04 AC AND DC VOLTAGES
INSTRUCTION SHEET PRL-97X04 AC AND DC VOLTAGES Page 1 of 18 The PRL LED Point Rollover Light is used for heliport TLOF and FATO applications where an inset light is required. The thick soda lime glass
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationTable of Contents. Electrical Service Requirements. 1. General Requirements
Table of Contents 1. General Requirements 1.1 General Definition.................................................... 1 1 1.2 Booklet Purpose and Organization....................................... 1-1
More informationSPECIAL SPECIFICATION 6576 Solar Panel Power Supply System
2004 Specifications CSJ 1068-04-126, 0197-02-108 SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System 1. Description. This work shall consist of furnishing and installing an integrated solar Panel
More information7 Single Family Service
7 Single Family Service 7. General The location of the service entrance on the Customer s premises is an important consideration. For clearance and location information see section 5 (Clearances). Consult
More informationCOMMERCIAL QUICK REFERENCE
COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More informationIndianapolis Power & Light Company
Indianapolis Power & Light Company Electric Service and Meter Manual The Electric Service & Meter Manual is not copyrighted and permission is hereby given to reproduce this document. However, the Indianapolis
More information10. METERING General Requirements
10. METERING 10.1 General Requirements A. The Company will not supply service to a Customer whose wiring is designed for resale of electricity through submetering except for recreational campgrounds, marinas,
More informationRESOLUTION NO
RESOLUTION NO. 28068 RESOLUTION OF THE COUNCIL OF THE CITY OF SANTA ROSA AMENDING RESOLUTION NUMBER 20741 ADOPTING REVISED STREET LIGHT DESIGN STANDARDS WHEREAS, the Council of the City of Santa Rosa,
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationLighthouse Power Pedestals,
Lighthouse Power Pedestal One of our most popular units, the all-purpose Lighthouse pedestal has a wide range of features. With units in service around the world, this stylish power pedestal is recognized
More informationSOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS
SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial
More informationRequirements for Secondary Voltage Revenue Metering (750 V and less)
Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationEaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse Power Pedestal
DRILL \ PUNCH OUT TO SIZE REQUIRED DRILL \ PUNCH OUT TO SIZE REQUIRED Lighthouse Power Pedestal - Specifications Lighthouse Power Pedestal Dimensions Height: 44.00" (1117.60 mm) Width: 13.67" (347.22 mm)
More informationTransmission & Distribution Glossary of Electrical Terms
Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationEngineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes
Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer
More informationSINGLE PHASE WIRING SPECIFICATIONS
SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationTHREE PHASE WIRING SPECIFICATIONS
THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationSTATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY SPECIFICATIONS FOR HIGH PRESSURE SODIUM LUMINAIRES HIGH MAST TYPE
STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY 08625 SPECIFICATIONS FOR HIGH PRESSURE SODIUM LUMINAIRES HIGH MAST TYPE N.J. Specification No. Effective Date: July 1, 2001 New Jersey
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationNEC 2011 Code Changes
NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection
More informationSentinel Field Satellite Controller
WARNING HIGH VOLTAGE 115V M AP Sentinel Field Satellite Controller Installation Instructions Important: For your protection and the safety of the product user, please comply with all Caution and Warning
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationOutdoor Power Transmission & Distribution
Description: The purpose of the section is to highlight the current applicable UMCP Design Standards and requirements for Outdoor Power Transmission and Distribution, including but not limited to the following:
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationSECTION LIFT ARM PARKING GATES
St. Anthony of Padua Catholic Church Phase I The Woodlands, Texas JRA Proj. No. 15004 Issued for Bidding - 1/20/2016 SECTION 11 12 33.13 LIFT ARM PARKING GATES PART 1 - GENERAL 1.01 SUMMARY A. Section
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationBUSWAY Low Voltage (Pow-R-Flex)
BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and
More informationPretest Module 24 Three-phase Service Entrance
Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?
More informationOVERHEAD SERVICE. Items to consider
OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must
More informationELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL
INTRODUCTION This policy has been adopted by the Board of Public Works as a guide to obtaining electric service and to set forth the services available, conditions for service, and standards for materials
More informationJandy Pro Series WaterColors LED Lights Underwater Large and Small Light
installation Manual English Jandy Pro Series WaterColors LED Lights Underwater Large and Small Light FOR YOUR SAFETY - This product must be installed and serviced by a contractor who is licensed and qualified
More informationAGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS
Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This
More information2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code
2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationINSTALL SERVICE- ENTRANCE SYSTEMS
SUBCOURSE EN5141 EDITION B US ARMY ENGINEER SCHOOL INSTALL SERVICE- ENTRANCE SYSTEMS INSTALL SERVICE- ENTRANCE SYSTEMS Subcourse Number EN5141 EDITION B United States Army Engineer School Fort Leonard
More informationIN2 Enclosed Switches and Circuit Breakers
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More informationA.C.E.S. Series ACES 3 & 6 MODULE PANELS. System Manual. Touch-Plate Lighting Controls. ACES 3 & 6 Module System Manual
Touch-Plate Lighting Controls ACES 3 & 6 Module System Manual A.C.E.S. Series ACES 3 & 6 MODULE PANELS System Manual Touch-Plate Lighting Controls 1830 Wayne Trace Fort Wayne, IN 46803 Phone: 260-424-4323
More informationEaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse-SS Power Pedestals
Lighthouse-SS Power Pedestal Dimensions Height: 44.00" (1117.60 mm) Width: 9.565" (242.95 mm) Depth: 9.875" (250.83 mm) Lighthouse-SS Base Diagram Ø0.50" MOUNTING HOLE (TYP.) 9.5625" 8.0625" 7.3125" C:\Documents
More informationELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016
DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all
More informationA. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.
SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationGeneral Specifications for Lighthouse Power Pedestal
Dimensions Height: 44.00 11 (1117.60 mm) Width: 13.67" (347.22 mm) Depth: 13.75" (349.25 mm) Lighthou98 Base Diagram ---13,75 1 --- Approximate Weight: 30 lbs. (13.6 kg) Multiply base dimensions by 25.4
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationSection 6 Electric Metering: Residential
Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.
More informationSPECIAL SPECIFICATION 8676 Solar Panel Power Supply System
2004 Specifications CSJ 2552-01-033 SPECIAL SPECIFICATION 8676 Solar Panel Power Supply System 1. Description. This work shall consist of furnishing and installing an integrated Solar Panel Power Supply
More informationRESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS
SECTION II This section discusses the City of Palo Alto's requirements for establishing electric service to new or upgraded residential installations. The same requirements apply to both underground and
More informationFlorham Park, NJ USA Call (ASCO) for sales or service
Operator s Manual 7000 Series ATS Automatic Transfer Switches D design, 30 through 230 A DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious
More informationELECTRICAL METERING RESIDENTIAL
ELECTRICAL METERING RESIDENTIAL 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 UNDERGROUND FED METER SOCKET (226-320 AMPS) 5.0 METER SOCKET (0-320 AMPS, 120/208V) 6.0 UNDERGROUND SERVICE W/CURRENT
More informationSpecial Specification 6058 Battery Back-Up System for Signal Cabinets
Special Specification Battery Back-Up System for Signal Cabinets 1. DESCRIPTION 2. DEFINITIONS Install a Battery Back-Up System (BBU System) for traffic signals that will provide reliable emergency power
More informationSPECIAL SPECIFICATION 1788 Surveillance Cabinet
1993 Specifications CSJ 2266-02-095 SPECIAL SPECIFICATION 1788 Surveillance Cabinet 1. General. This Item shall govern the furnishing and installation of Surveillance Cabinet to include the installation
More informationService Requirements
Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.
More informationClark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.
This page left blank intentionally. 38 Chapter 4: Commercial Metering / January 2011 APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Associated equipment As related to metering
More informationEaton Corp. - Marina Power and Lighting, Inc. General Specifications for Hatteras Light Pedestals
Hatteras Light Power Pedestal Dimensions Height: 31.00" (787.40 mm) Width: (190.50 mm) Depth: (190.50 mm) Hatteras Light Base Diagram Approximate Weight: 14 lbs. (6.4 kg) 1.73" UL FILE # E133781 Ø0.41
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationMetering and Service Installation:
Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationNuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM. Self-Regulating Heating Cable Installation Guide. UV Resistant Polyolefin Outer Jacket
Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM Self-Regulating Heating Cable Installation Guide Tinned Copper Braid UV Resistant Polyolefin Outer Jacket 16 AWG Bus Wire Polyolefin Inner
More informationCustomer Requirements Meter Socket Configurations
Application Information on meter socket configurations available from Tacoma Power. For enclosed meter pedestals, see standard C-MR-0020 Customer Requirements, Enclosed Meter Pedestal. General Requirements
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationSPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION
Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 04/25/18 Specifications for Residential Construction Revision List REVISION Date Page No. Description 03/20/00 6.1-6.2 Added Armorcast
More informationSALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL
SALEM CITY POWER DEPARTMENT TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1 Changes or Conflicts in Requirements and Guidelines...1.1 Application for Service...1.2
More informationChapter 8 Interior Wiring and Lighting
Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific
More information