SE-703 MANUAL EARTH-LEAKAGE MONITOR

Size: px
Start display at page:

Download "SE-703 MANUAL EARTH-LEAKAGE MONITOR"

Transcription

1 3714 Kinnear Place Saskatoon, Saskatchewan Canada S7P 0A6 Ph: (306) Fx: (306) SE-703 MAUAL EARTH-LEAKAGE MOITOR April 2, 2012 REVISIO 9 Copyright 2012 by Littelfuse Startco All rights reserved. Publication: SE-703-M Document: S95-C Printed in Canada.

2 This page intentionally left blank.

3 Page i TABLE OF COTETS PAGE 1. General Operation Configuration-Switch Settings Relay Operating Mode Filter Selection Front-Panel Controls Earth-Leakage Trip Level Earth-Leakage Trip Time Reset Test Front-Panel Indication Power Trip CT Verification Analog Output Self Diagnostics Installation SE-703 Compatibility Technical Specifications Ordering Information Warranty FIGURE LIST OF FIGURES PAGE 1. SE-703 Outline and Mounting Details Typical Connection Diagrams Typical Three-Phase-Starter Connection EFCT-1 Outline and Mounting Details EFCT-2 Outline and Mounting Details EFCT-26 Outline and Mounting Details PMA-55 Panel-Mount Adapter PMA-60 Panel-Mount Adapter PGA-0500 Analog Percent Current Meter Earth-Fault-Test Circuit TABLE LIST OF TABLES PAGE 1. Trip-Feature Comparison Earth-Fault-Test Record DISCLAIMER Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. 8. Performance Test... 13

4 Page ii This page intentionally left blank

5 Page 1 1. GEERAL The SE-703 is a microprocessor-based earth-leakage monitor for ac power supply systems incorporating earthfault current limitation. Its output relay can operate in the fail-safe or non-fail-safe mode for undervoltage or shunt-trip applications. The SE-703 has one output relay with isolated normally open and normally closed contacts for use in independent control circuits. Additional features include LED trip and power indication, latching trips with front-panel and remote reset, trip memory, test switch, self diagnostics, 0 to 5-V analog output, CT verification with LED indication, digital selector switches, and switch-selectable algorithms for fixed-frequency or variable-frequency applications. Earth-leakage current is sensed by an EFCT-series core-balance, earth-fault current transformer. The trip level of the earth-leakage circuit is digital-switch selectable from 25 to 500 ma. Trip time is digitalswitch selectable from 50 to 500 ms. The SE-703 is AS/ZS 2081:2002 compliant. 2. OPERATIO 2.1 COFIGURATIO-SWITCH SETTIGS See Fig RELAY OPERATIG MODE Switch 1 is used to set the operating mode of the output relay. In the fail-safe mode, the output relay energizes when the earth-leakage circuit is not tripped. In the fail-safe mode, non-volatile memory retains the trip status of the SE-703. If tripped, and the supply voltage is cycled, the SE-703 will remain tripped, with the trip relay de-energized and the TRIP LED on, until reset. In the non-fail-safe mode, the output relay energizes when an earth-leakage trip occurs. In the non-fail-safe mode, trip status is not retained in non-volatile memory FILTER SELECTIO Switch 2 is used to select the filtering algorithm for a fixed-frequency (50/60 Hz) or variable-frequency application. The FIXED FREQUECY setting uses a DFT filter that allows lower trip levels to be used by rejecting harmonics that can cause nuisance tripping. The VARIABLE FREQUECY setting uses a peakdetection algorithm with a wider bandwidth for fault detection in variable-frequency drive applications. 2.2 FROT-PAEL COTROLS EARTH-LEAKAGE TRIP LEVEL The LEVEL (ma) selector switch is used to set the earth-leakage trip level. For earth-leakage detection, the earth-leakage trip level must be substantially below the prospective earth-fault current. To avoid sympathetic tripping, the trip level must be above the charging current of the protected feeder EARTH-LEAKAGE TRIP TIME The SE-703 has a definite-time trip characteristic. The TIME (ms) selector switch is used to set the earthleakage trip time for coordination with upstream and downstream earth-fault devices. Coordination requires the same trip level for all earth-leakage devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first earth-leakage device to operate is the one immediately upstream from the fault RESET A trip remains latched until the RESET switch is pressed or the remote-reset terminals (6 and 7) are momentarily connected. In the non-fail-safe relay operating mode, cycling the supply voltage will also reset the SE-703. The reset circuit responds only to a momentary closure so that a jammed or shorted switch will not prevent a trip. The front-panel RESET switch is inoperative when the remote-reset terminals are connected TEST The TEST switch is used to test the earth-leakage circuit, the indication, and the output relay. When the TEST switch is pressed for one second, a test signal is applied to the earth-leakage-detection circuit, the circuit will trip, the TRIP LED will light, and the output relay will operate. 2.3 FROT-PAEL IDICATIO POWER The green LED labeled PWR indicates presence of supply voltage TRIP The red LED labeled TRIP indicates a trip. A solid red LED indicates an earth-leakage trip and a flashing LED indicates a trip initiated by a CT fault. Two fast flashes of the TRIP LED indicate a diagnostic trip. See Section CT VERIFICATIO The green LED labeled CT indicates that an EFCTseries sensor is connected.

6 Page 2 AS/ZS 2081:2002 COMPLIAT ASSOCIATED CURRET TRASFORMERS EFCT-1 EFCT-5RF EFCT-8RF EFCT-2 EFCT-6RF EFCT-9RF EFCT-26 EFCT-7RF EFCT-10RF COFIGURATIO SWITCHES UUSED 5 OFF UUSED OFF UUSED OFF FILTER SELECTIO FIXED FREQUECY RELAY OPERATIG MODE FAIL-SAFE 4 3 KEEP I OFF POS. KEEP I OFF POS. KEEP I OFF POS. 2 VARIABLE FREQUECY 1 O-FAIL-SAFE 8.7 (0.34) 55.0 (2.17) 37.5 (1.48) OTE 2 UUSED OFF UUSED OFF COFIGURATIO SWITCHES 5 KEEP I OFF POS. 4 KEEP I OFF POS (2.41) 75.0 (2.95) UUSED OFF FILTER SELECTIO FIXED FREQUECY RELAY OPERATIG MODE FAIL-SAFE 3 KEEP I OFF POS. 2 VARIABLE FREQUECY 1 O-FAIL-SAFE OTE 5 S1 S2 RS CT RESET AALOG OUTPUT TOP 55.0 (2.17) MOUTIG DETAIL (OTE 3) (4.65) (4.33) 6.3 (0.25) 6.9 (0.27) LITTELFUSE STARTCO EARTH-LEAKAGE MOITOR SE-703 PWR CT TRIP LEVEL (ma) TIME (ms) 75.0 (2.95) TEST RESET FROT OTES: SIDE L2 L1 1. DIMESIOS I MILLIMETRES (ICHES). 2. MOUTIG SCREWS: M4 OR OVERALL DIMESIO WHE MOUTED O DI E mm x 7.5 mm TOP-HAT RAIL. 4. ADJUSTMET KOBS ARE REMOVABLE. BOTTOM 5. COFIGURATIO SWITCHES SHOW I DEFAULT POSITIO. FIGURE 1. SE-703 Outline and Mounting Details.

7 Page AALOG OUTPUT The non-isolated, 0 to 5-V analog output indicates earthleakage current sensed by the EFCT. The output is 5 V when earth-leakage current is 500 ma. Use a PGA-0500 Analog Percent Current Meter to indicate earth-leakage current. See Figs. 2, 3, and SELF DIAGOSTICS A diagnostic trip is indicated by two fast flashes of the TRIP LED. It can be caused by a problem detected by an incorrect reading from non-volatile memory. Press RESET or cycle supply voltage. If the problem persists, consult Littelfuse Startco. 3. ISTALLATIO OTE: Mounting, terminal-block connections and wiring must conform to applicable local electrical codes. Check all applicable codes prior to installation This earth-leakage monitoring system consists of an SE-703 Earth-Leakage Monitor and an EFCT-series current sensor connected as shown in Figs. 2 and 3. An SE-703 can be surface or DI-rail mounted. See Fig. 1. Panel mounting requires a PMA-55 or PMA-60 Panel-Mount Adapter. See Figs. 7 and 8. A PMA-60 meets the AS/ZS 2081:2002 IP53 requirement. Use terminal 11 (L1) as the line terminal on ac systems or the positive terminal on dc systems. Use terminal 10 (L2/) as the neutral terminal on ac systems or the negative terminal on dc systems. Connect terminal 9 ( ) to ground. Pass the phase conductors through the EFCT window and position them in the centre of the opening for 4-wire and single-phase systems, also pass the neutral conductor through the EFCT window, see Figs. 2 and 3. Do not pass earth conductors through the EFCT window. In applications that require shields or drain wires to pass through the EFCT window, return them through the EFCT window before connecting them to earth. Connect the EFCT current sensor to terminals 4 and 5, connect the shield to terminal 5, and earth terminal 5. See Figs. 4, 5, and 6 for EFCT-series current-sensor dimensional drawings. Remove the connection to terminal 9 for dielectricstrength testing. Ø A EFCT Ø A EFCT L EFCT Ø B Ø B Ø C Ø C L 4 5 S1 S2 11 L2 L SE-703 S1 3 PHASE, 4 WIRE COECTIO S2 SE-703 S1 1 PHASE COECTIO S2 15 ISOLATED COTACTS 16 REMOTE RESET 6 LEAKAGE V OPTIOAL PGA RS SE-703 RESET AALOG OUTPUT 3 PHASE, 3 WIRE COECTIO 9 FIGURE 2. Typical Connection Diagrams.

8 Page 4 Ø A EFCT Ø B Ø C L 4 5 S1 S ISOLATED COTACTS 16 STOP START 1M 1M O/L 11 L2 10 L1 REMOTE RESET OPTIOAL PGA LEAKAGE 8 V RS SE-703 RESET AALOG OUTPUT FIGURE 3. Typical Three-Phase Starter Connection. 4. SE-703 COMPATIBILITY The current SE-703 has been enhanced with the addition of non-volatile trip memory for the fail-safe relay operating mode. Prior to hardware revision 04, a mechanical flag was used instead of non-volatile trip memory. The current revision of the SE-703 can directly replace previous revision units. The hardware-revision number is listed on the SE-703 model/serial-number label affixed to the SE-703 enclosure. Both generations of SE-703 are compared in Table 1. The SE-703 was previously available with SE Vac and SE Vac control-voltage options. These have been discontinued. An SE-703-0U universal 120/240-Vac/Vdc unit can directly replace an SE or SE Device state after supply voltage cycled when tripped (earth-fault removed) 9 TABLE 1. TRIP-FEATURE COMPARISO HARDWARE REVISIO LED trip indication Yes Yes Mechanical flag trip indication Yes o on-volatile trip memory o Yes Trip LED: Off Fail-safe Trip relay: Energized Trip flag: Red on-fail-safe Trip LED: Off Trip relay: De-energized Trip flag: Red Trip LED: On Trip relay: De-energized Trip LED: Off Trip relay: De-energized

9 R R Page 5 P 1 S 1 S 2 OTES: 1. DIMESIOS I MILLIMETRES (ICHES). 2. MOUTIG SCREWS: M4 OR PRESS MOUTIG FEET I PLACE USIG ISTALLATIO TOOL PROVIDED (0.81) (4.76) (4.76) 80.0 (3.15) 30.0 (1.18) 56.0 (2.21) 46.0 (1.81) OTE 2 M5 SCREWS TOP 25.0 (0.98) MOUTIG DETAIL 30.0 (1.18) EFCT-1 EARTH FAULT CT 600 V CLASS, ISULATIO CLASS A C LR US MAX (5.43) 82.0 (3.23) 69.8 (2.75) EFCT - 1FC FLUX CODITIOER (OPTIOAL) 5.0 (0.20) Ø RECESSED FOR 8-mm HEX UT 1.0 (0.04) DEEP 22.0 (0.87) (4.96) 5.5 (0.22) (4.33) FROT 5.5 (0.22) 56.0 (2.21) SIDE FIGURE 4. EFCT-1 Outline and Mounting Details.

10 Page 6 LR C R US OTES: 1. DIMESIOS I MILLIMETRES (ICHES) 2. MOUTIG SCREWS: M5 OR EFCT-2 EARTH FAULT CT 600 V CLASS, ISULATIO CLASS A R (8.46) 26.5 (1.04) (8.46) (6.38) 64.0 (2.52) 31.0 (1.22) P2 S1 S P (2.06) M5 OR TAP TOP 25.0 (0.98) M5 SCREWS MOUTIG DETAIL 31.0 (1.22) S1 P1 236 MAX (9.29) (5.50) FLUX CODITIOER (ICLUDED) BODIG SCREW 5.0 (0.20) DIA 60.0 (2.36) (8.46) 8.5 (0.33) (7.80) 8.5 (0.33) FROT SIDE FIGURE 5. EFCT-2 Outline and Mounting Details.

11 R R Page (0.67) 68.0 (2.68) 68.0 (2.68) 34.0 (1.34) 26.5 (1.04) P2 S1 S P (2.07) 42.6 (1.68) M4 OR 8-32 TAP M5 SCREWS MAX (0.43) TOP 25.0 (0.98) MOUTIG DETAIL 26.5 (1.04) EFCT-26 EARTH FAULT CT 600 V CLASS, ISULATIO CLASS A LR C US 72.0 (2.83) 26.0 (1.02) 4.0 (0.16) Ø RECESSED FOR 7-mm HEX UT 3.0 (0.12) DEEP 34.0 (1.34) 7.0 (0.87) 5.0 (0.20) 58.0 (2.28) FROT 5.0 (0.20) 52.5 (2.07) SIDE MOUTIG FOOT ISTALLATIO TOOL OTES: 1. DIMESIOS I MILLIMETRES (ICHES). 2. PRESS MOUTIG FEET I PLACE USIG ISTALLATIO TOOL PROVIDED (DETAIL A ) 3. MOUTIG SCREWS: M4 OR DETAIL A FIGURE 6. EFCT-26 Outline and Mounting Details.

12 Page (3.35) PAEL THICKESS 1.6 (0.06) TO 4.8 (0.19) (4.33) (1.67) LITTELFUSE STARTCO EARTH-LEAKAGE MOITOR PWR CT TRIP SE LEVEL (ma) TIME (ms) 85.0 (3.35) (2.95) TEST RESET FROT VIEW BRACKET SIDE VIEW 55 mm (2.2) WIDE MOITOR 6.0 (0.24) 85.0 (3.35) 72.0 (2.83) 60.0 (2.36) 6.0 (0.24) 9.5 (0.37) ISTALLATIO ISTRUCTIOS: 42.5 (1.67) 30.0 (1.18) 2.0 (0.08) RAD MAXIMUM 4.0 (0.16) DIA 8.7 (0.34) DIA 4.3 (0.17) RAD ALTERATE COFIGURATIOS 60.0 (2.36) 79.0 (3.11) 1. REMOVE BEZEL AD LATCH MOITOR TO BRACKET 2. ISERT BRACKET THROUGH FROT OF PAEL CUTOUT AD SECURE WITH FLAT WASHERS AD LOCKUTS PROVIDED. 3. COECT WIRIG TO TERMIALS. 4. ISTALL BEZEL USIG 6-32 x 0.31 SCREWS PROVIDED. OTE: 9.5 (0.37) 1. DIMESIOS I MILLIMETRES (ICHES). PAEL CUTOUT DETAIL FIGURE 7. PMA-55 Panel-Mount Adapter.

13 Page (3.90) (4.57) PAEL THICKESS 1.6 (0.06) TO 4.8 (0.19) M (1.73) LITTELFUSE STARTCO EARTH-LEAKAGE MOITOR SE-703 PWR CT TRIP LEVEL (ma) TIME (ms) 88.0 (3.46) M (2.95) TEST RESET FROT VIEW TRASPARET COVER (OTE 2) BRACKET SIDE VIEW 55 mm (2.2) WIDE MOITOR 6.0 (0.24) 99.0 (3.90) 72.0 (2.83) 60.0 (2.36) 6.0 (0.24) 9.5 (0.37) ISTALLATIO ISTRUCTIOS: 2.0 (0.08) RAD MAXIMUM 1. WITH COVER REMOVED LATCH MOITOR TO BRACKET 44.0 (1.73) 30.0 (1.18) 4.5 (0.18) DIA 8.7 (0.34) DIA 4.3 (0.17) RAD 60.0 (2.36) 79.0 (3.11) 2. ISERT BRACKET THROUGH FROT OF PAEL CUTOUT AD SECURE WITH FLAT WASHERS AD LOCKUTS PROVIDED. 3. COECT WIRIG TO TERMIALS. ALTERATE COFIGURATIOS 4. ATTACH COVER USIG THUMB SCREWS PROVIDED. OTE: PAEL CUTOUT DETAIL 9.5 (0.37) 1. DIMESIOS I MILLIMETRES (ICHES). 1. MEETS EMA3, IP53. FIGURE 8. PMA-60 Panel-Mount Adapter.

14 Page (2.657) R1.25(0.049) MAXIMUM 48.0 (1.890) 66.0 (2.598) 67.5 (2.657) OTES: 1. COVERSIO KIT FOR 0-5 V AALOG OUTPUT. SEE PGA-0500 DOCUMETATIO. 2. DIMESIO I MILLIMETRES (ICHES). TOP MOUTIG CUTOUT % OTE (2.795) 65.0 (2.559) 0 PGA-0500 AALOG % CURRET METER 1 ma FROT FIGURE 9. Analog Percent Current Meter. SIDE REAR 5. TECHICAL SPECIFICATIOS Supply: 0U Option VA, 120 to 240 Vac, (+20, -55%) 50/60 Hz, 2.0 W, 100 to 240 Vdc, (+20, -25%) 0D Option W, 12 to 30 Vdc, (+20, -25%) 0T Option W, 40 to 55 Vdc, (+20, -25%) 03 Option VA, 24 Vac, (+15%, -40%), 50/60 Hz Trip-Level Settings... 25, 30, 45, 60, 80, 110, 150, 200, 300, and 500 ma Trip-Time Settings... 50, 100, 150, 200, 250, 300, 350, 400, 450, and 500 ms Accuracies: (1) Trip Level (2) , -20% of setting Trip Time (3)... +0, -20 ms or +0, -20% of setting, whichever is larger Discrimination Time (4)... 75% of trip time setting, Minimum off time 25 ms Input: Algorithms... DFT Digital or Peak DFT 3 db Frequency Resp.. 32 to 86 Hz Peak 3 db Frequency Resp.. 20 to 420 Hz CT... EFCT Series Thermal Withstand: Continuous A Earth-Fault Current 1-Second A Earth-Fault Current Analog Output: Range... 0 to 5 V, 10 mv per ma Output Impedance OTES: (1) (2) (3) (4) At 50 or 60 Hz. Maximum lead resistance of 2. Trip Time at 1.5 x trip-level setting. Per AS/ZS :2002 Clause

15 Page 11 Reset... Front-Panel Switch and Remote,.O. Contact Functional Test... Front-Panel Switch Output Relay: Contact Configuration... Isolated.O. and.c. Operating Mode... Fail-Safe or on-fail-safe CSA/UL Contact Rating... 8 A General Use, 250 Vac, 8 A Resistive, 30 Vdc Supplemental Contact Ratings: Carry Current... 8 A, maximum Break: 30 Vdc W Resistive, 170 W Inductive (L/R = 7 ms) 120 Vdc W Resistive, 17 W Inductive (L/R = 7 ms) ac... 2,000 VA Resistive, 875 VA Inductive (PF = 0.4) Subject to maximums of 8 A and 250 Vac/30 Vdc or 200 ma at 120 Vdc Operating Mode...Latching only Terminals...Wire Clamping, 0.2 to 2.5 mm 2 conductors (24 to 12 AWG) Dimensions: Height mm (3.0") Width mm (2.2") Depth mm (4.5") Shipping Weight kg (1 lb.) Environment: Operating Temperature C to 60 C Storage Temperature C to 80 C Humidity... 85% on-condensing Surge Withstand... ASI/IEEE (Oscillatory and Fast Transient) EMC Tests: Verification tested in accordance with E 50263:2000 Conducted & Radiated Emissions CISPR 22: / E55022:2010 Class A Electrostatic Discharge... IEC , IEC , 6 kv Contact Discharge 8 kv Air Discharge Radiated RF Immunity... IEC , IEC V/m, MHz, 80% AM (1 khz) 10 V/m, 900 MHz, 200 Hz Pulse Modulated Fast Transient... IEC , IEC kv on AC Mains and I/O lines Surge Immunity... IEC , IEC kv Common Mode on AC Lines 1.0 kv Differential Mode on AC lines 2.0 kv Common Mode on I/O ports Conducted RF Immunity... IEC , IEC Vrms, MHz, 80% AM (1 khz) Magnetic Field... IEC , E Hz and 60 Hz, 30 A/m 300 A/m Voltage Interruption... IEC ,IEC % for 5, 10, 20, 50, 100 & 200 ms 3x each 1 MHz Burst... E kv Differential Mode 2.5 kv Common Mode Power Frequency... IEC , IEC Class A 150V Differential Class A 300V Common Current Harmonics and Voltage Fluctuation IEC and IEC Class A RFI Compliance... FCC Part 15, Subpart B, Class A Unintentional Radiators Compliance... AS/ZS 2081:2002

16 Page 12 Certification... CSA, Canada and USA UL Listed Australia CE, European Union Complies to IEC :2001 (2 nd Edition); E :2001 (2 nd Edition) Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use Part ORDERIG IFORMATIO SE703-0 EFCT-9RF... Earth-Fault Current Transformer, 160-mm (6.3 ) window EFCT-10RF.. Earth-Fault Current Transformer, 200-mm (7.9 ) window For additional information and to order contact: sales@startco.com.au. 7. WARRATY The SE-703 Earth-Fault Monitor is warranted to be free from defects in material and workmanship for a period of five years from the date of purchase. Littelfuse Startco will (at Littelfuse Startco s option) repair, replace, or refund the original purchase price of an SE-703 that is determined by Littelfuse Startco to be defective if it is returned to the factory, freight prepaid, within the warranty period. This warranty does not apply to repairs required as a result of misuse, negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse Startco does not warrant products repaired or modified by non-littelfuse Startco personnel. U Universal 120/240- Vac/Vdc Supply D 12/24- Vdc Supply T 48-Vdc Supply 3 24-Vac Supply EFCT-1...Earth-Fault Current Transformer, 82-mm (3.2 ) window EFCT-2...Earth-Fault Current Transformer, with Flux Conditioner 139-mm (5.5 ) window EFCT Earth-Fault Current Transformer, 26-mm (1.0 ) window EFCT-1FC... Flux Conditioner, 70 mm (2.7 ) Window PGA Analog Percent Current Meter PMA Panel-Mount Adapter, EMA 1 PMA Panel-Mount Adapter, EMA 3, IP53 PMA-3... Adapter Plate, GEC/MCGG PMA-6... Adapter Plate, FPL-GFRM PMA Adapter Plate, MGFR Consult factory for custom mounting adapters. Startco Pty. Australian Current Transformers EFCT-5RF...Earth-Fault Current Transformer, 60-mm (2.4 ) window EFCT-6RF...Earth-Fault Current Transformer, 85-mm (3.3 ) window EFCT-7RF...Earth-Fault Current Transformer, 112-mm (4.4 ) window EFCT-8RF...Earth-Fault Current Transformer, 140-mm (5.5 ) window

17 Page PERFORMACE TEST Some jurisdictions require periodic earth-fault performance tests. A test-record form is provided for recording the date and the results of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel: a) Evaluate the interconnected system in accordance with the overall equipment manufacturer s detailed instructions. b) Verify proper location of the earth-fault current transformer. Ensure the cables pass through the earth-fault-current-transformer window. This check can be done visually with knowledge of the circuit. The connection of the current-transformer secondary to the SE-703 is not polarity sensitive. c) Verify that the system is correctly earthed and that alternate earth paths do not exist that bypass the current transformer. High-voltage testers and resistance bridges can be used to determine the existence of alternate earth paths. d) Verify proper reaction of the circuit-interrupting device in response to a simulated or controlled earth-fault current. To simulate earth-fault current, use CT-primary current injection. Fig. 10 shows a test circuit using an SE-400 Ground-Fault-Relay Test Unit. The SE-400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Fig. 10 shows the use of resistors that reduce the injected current to 10% of the SE-400 setting. Set the test current to 120% of the SE-703 setting. Inject the test current through the current-transformer window for at least 2.5 seconds. Verify that the circuit under test has reacted properly. Correct any problems and re-test until the proper reaction is verified. e) Record the date and the results of the test on the attached test-record form. FROM POWER SOURCE REMOTE TEST I TEST 11 R1 L 10 R L EFCT 4 5 S1 S2 L1 L2/ OP1 L1 L2 RMT1 RMT2 SE-703 SE-400 R1 = 10 Ω, 10 W, 1% R2 = 0.1 Ω, 10 W, 1% I TEST = 1/10 SE-400 SETTIG OP2 FIGURE 10. Earth-Fault-Test Circuit. DATE 12 LOAD TABLE 2. EARTH-FAULT-TEST RECORD TEST RESULTS OTE: Do not inject test current directly into CT-input terminals 4 and 5. Retain this record for the authority having jurisdiction.

18 Page 14

SE-100T MANUAL GROUND-FAULT-RELAY TESTER

SE-100T MANUAL GROUND-FAULT-RELAY TESTER 3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols SE-100T MAUAL GROUD-FAULT-RELAY TESTER REVISIO 5-A-120513 C HI LO RMT L1 L2 OUTPUT

More information

SE-400 MANUAL GROUND-FAULT-RELAY TEST UNIT

SE-400 MANUAL GROUND-FAULT-RELAY TEST UNIT 3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols SE-400 MANUAL GROUND-FAULT-RELAY TEST UNIT Revision 1-A-072115 LITTELFUSE STARTCO

More information

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR FEBRUARY 14, 2001 REVISION 3 Publication: SE-125-M Document: S95-C125-00000 Printed in Canada. Copyright 2001 by Startco Engineering Ltd. All rights reserved.

More information

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER 3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.littelfuse.com/relayscontrols SE-3SCR-LM MANUAL MOTOR LOAD MANAGER MARCH 5, 2013 REVISION 4 MOTOR LOAD MANAGER

More information

POWR-GARD Relay Testing Equipment PGT-0400 Series Ground-Fault Relay Test Unit PGT Ground-Fault Relay Test Unit

POWR-GARD Relay Testing Equipment PGT-0400 Series Ground-Fault Relay Test Unit PGT Ground-Fault Relay Test Unit POWR-GARD Relay Testing Equipment Series Ground-Fault Relay Test Unit Ground-Fault Relay Test Unit AUGUST 7, 2009 REVISION 0 POWR-GARD GROUND-FAULT RELAY UNIT SERIES AMPERES THERMAL LIMIT USE SWITCHES

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

A419ABG-3C Electronic Temperature Control

A419ABG-3C Electronic Temperature Control Installation Instructions Issue Date June 16, 2003 A419ABG-3C Electronic Temperature Control Application IMPORTANT: Use this A419ABG-3C Electronic Temperature Control only as an operating control. Where

More information

201A-9 INSTALLATION INSTRUCTIONS. Revision A1 Rapid City, SD, USA, 01/2010

201A-9 INSTALLATION INSTRUCTIONS. Revision A1 Rapid City, SD, USA, 01/2010 INSTALLATION INSTRUCTIONS Revision A1 Rapid City, SD, USA, 01/2010 MODELS 201A 201A-9 2880 North Plaza Drive, Rapid City, South Dakota 57702 (800) 843-8848 (605) 348-5580 fax (605) 348-5685 BE SURE POWER

More information

Three-Phase Soft Starters

Three-Phase Soft Starters Submittal Data English Language/IP Units 04/14 Contact Information: Hyper Engineering, Pty. Ltd. 4 / 14 Ralph Black Dr Wollongong Nth, NSW 2500 AUSTRALIA www.hypereng.com sales@hypereng.com (+61) 2 4229

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC Characteristics time delay relay 2 functions - 0.02 s..300 h - 24..240 V AC - 2 OC Complementary Product front plate size Control type Housing material Main Range of product Product or component type Electrical

More information

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h) Mechatronic Analog Timer H3AM Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to Warranty and

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Special Specification 6058 Battery Back-Up System for Signal Cabinets Special Specification Battery Back-Up System for Signal Cabinets 1. DESCRIPTION 2. DEFINITIONS Install a Battery Back-Up System (BBU System) for traffic signals that will provide reliable emergency power

More information

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Installation Instructions Issue Date April 8, 2008 A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures Application IMPORTANT: The A419 Series Electronic Temperature

More information

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DN Digital Reduced Voltage Motor Starter RVS-DN Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

Model Number Structure

Model Number Structure Solid State Relays (Single-phase) G3PB New Single-phase Solid State Relays with Compact Size for Heater Control Slim models with a thickness of only 22.5 mm are also available. Compact design achieved

More information

i3000s/i2000 Flex AC Current Probe

i3000s/i2000 Flex AC Current Probe i3000s/ AC Current Probe Instruction Sheet Introduction The i3000s 24 Flex, i3000s 36 Flex, and AC Current Probes (the Probe) are used with oscilloscopes, digital multimeters, recorders or data loggers.

More information

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC

RE48AML12MW time delay relay 2 functions s..300 h V AC - 2 OC Characteristics time delay relay 2 functions - 0.02 s..300 h - 24..240 V AC - 2 OC Main Range of product Product or component type Electrical connection Discrete output type Contacts type and composition

More information

RVS-DX Digital Reduced Voltage Motor Starter

RVS-DX Digital Reduced Voltage Motor Starter RVS-DX Digital Reduced Voltage Motor Starter Specification Guide Specification Guide Contents 1.0 Introduction 2.0 Specifications 2.1 Standard Performance Features 2.2 Standard Protection Features 2.3

More information

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Dycon D2430 EN54-4 Fire Alarm Power Supply Series Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product

More information

A21M. Introduction: Functional Overview: Key Protection & Control Functions:

A21M. Introduction: Functional Overview: Key Protection & Control Functions: Introduction: ASHIDA has designed economical & reliable Multifunction A21M Protection & Control System. The simple and compact construction of A21 series, A21M relay provides integrated Protection, Control

More information

Time scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal)

Time scale: from 0.05 s to 100 h Multi-function Plug-in for use with 96 series sockets. Relay + socket. Wiring diagram (without control signal) 86 Timer modules 86 Timer modules for use in conjunction with relay & socket. 86.00T - Multi-function & multi-voltage timer module 86.30T - Bi-function & multi-voltage timer module Complies with EN 45545-2:2013

More information

3. Input KJ: Thermocouple P: Platinum resistance thermometer G: Thermistor T: Thermocouple/platinum resistance thermometer (universal-input)

3. Input KJ: Thermocouple P: Platinum resistance thermometer G: Thermistor T: Thermocouple/platinum resistance thermometer (universal-input) Authorised Distributors:- Intech Systems Chennai Pvt. Ltd, Chennai- Ph: + Fax: E-mail: info@intechchennai.com Website: www.intechchennai.com Temperature Controllers ECS CSM_ECS_DS_E Simple Functi ons in

More information

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION! INSTALLATION INSTRUCTIONS FOR SYMCOM S MOTORSAVER MODEL 460 BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide Retain for future use. 30072-450-47A July 2002 Raleigh, NC, USA HAZARDOUS VOLTAGE Read and understand

More information

Single & Three-Phase Soft Starters

Single & Three-Phase Soft Starters Submittal Data English Language/IP Units 11/13 Contact Information: Hyper Engineering, Pty. Ltd. 9000 Conservation Way Fort Wayne, IN 46809 www.hypereng.com sales@hypereng.com (877) 304-0724 Model Nomenclature

More information

GB60S 60W Single Output General Purpose Series

GB60S 60W Single Output General Purpose Series Features 2 x 3 x 1.0 Package Operates to 80 C Ambient For 1U Applications 60W convection cooled Universal Input 90-264Vac Optional Power ON LED Approved to CSA/EN/IEC/UL60950-1, 2 nd Edition Efficiency

More information

Security Plus Online Uninterruptible Power Supply

Security Plus Online Uninterruptible Power Supply Security Plus Online Uninterruptible Power Supply 1 2 GENERAL SAFETY INSTRUCTIONS Warnings in this manual appear in any of four ways: DANGER Danger- The danger symbol is a lightning bolt mark enclosed

More information

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Product Overview. Product Identification. Amps One CT Two CTs Three CTs AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

Features. LED Driver. RACT09 9 Watt. TRIAC Dimmable. Single Output RACT09- AC/DC Converter

Features. LED Driver. RACT09 9 Watt. TRIAC Dimmable. Single Output RACT09- AC/DC Converter Features TRIAC Dimmable LED Driver Triac dimmable with leading or trailing edge dimmers Class II with SELV output (no earth required) Extra-large screw terminals and integrated cable clamps for easy installation

More information

Protection and control VIP30, VIP35. Relays technical manual

Protection and control VIP30, VIP35. Relays technical manual Protection and control VIP30, VIP35 Relays technical manual contents 1. presentation of the VIP30 and VIP35...3 2. use and settings...4 3. sensors and operating ranges... 4. connection scheme...9 5. assembly

More information

Reverse power relay and protection assemblies

Reverse power relay and protection assemblies Reverse power relay and protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE980053) (SE980054) Features Micro-processor based time directionalcurrent relay/protection

More information

Indoor Linear 50W Driver SI-CU WW

Indoor Linear 50W Driver SI-CU WW Product Data Sheet Rev.2.0 2016. 5. 27 1# LED Driver Indoor Linear 50W Driver SI-CU1425001WW Constant Current LED Driver Features & Benefits Output Current Range: 500~1400 ma (adjustable via R-set) Output

More information

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Dycon D1532SM EN50131/PD6662 Grade 3, 12V 2A Power Supply Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD Tel: +44 (0)1443 471 900 Unit A Cwm Cynon Business Park Mountain

More information

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC. INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL INS120P TASCO, INC. THIS TESTER IS DESIGNED FOR USE ONLY BY QUALIFIED ELECTRICIANS. IMPORTANT SAFETY WARNINGS mwarning Read and understand this material

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

SPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W

SPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W Page 1 / 7 Full operation without need of battery Two independent 48Vdc outputs for switching and control Local monitoring with 8 LEDs Remote monitoring with 4 alarm relays Monitoring and configuration

More information

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. Introduction OPERATING INSTRUCTIONS: MCD REMOTE OPERATOR Order Codes: 175G94 (for MCD 2) 175G361 + 175G9 (for MCD 5) 175G361 (for MCD 3) 1. Introduction 1.1. Important User Information Observe all necessary

More information

mgard-10 microprocessor-based relay

mgard-10 microprocessor-based relay mgard-10 microprocessor-based relay Ground fault relay mgard-10a mgard-10-a1 mgard-10-a2 C-417EM Instruction Manual, March 2015 ABOUT I-GARD I-Gard s commitment to electrical safety provides both industrial

More information

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report Test report Type VRLTC load tap changer VRLTC 1500A Type test summary report Date: 10 October 2012 Type Test Summary Report Type VRLTC Vacuum/Reactance Load Tap Changer ABB has tested the Type VRLTC, vacuum

More information

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL PHASETEC digital power conditioners are designed to safely operate electrical equipment in the harshest power quality environments. With a wide

More information

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY CONNECTIONS INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!! FOLLOW NATIONAL, STATE AND LOCAL CODES! READ THESE INSTRUCTIONS

More information

825-P Modular Protection System for motors Specification Guide

825-P Modular Protection System for motors Specification Guide Specification Guide 1.0 General 1.01 The motor protection relay shall have a current operating range of 0.5 and 5000 amperes. 1.02 The motor protection relay shall provide current measurement-based protection

More information

Industrial Power Supplies

Industrial Power Supplies , Features Switch Mode Power Supplies for DIN-rail Mounting 6 Power Ranges with 2, 3, 6, 12, 20 and 24 A Current (24 VDC Models) Selectable 115/ 230 VAC Input Very low Ripple and Noise EMI complies with

More information

1587 FC/1587/1577. Insulation Multimeter. Safety Information. Warnings

1587 FC/1587/1577. Insulation Multimeter. Safety Information. Warnings 1587 FC/1587/1577 Insulation Multimeter Safety Information Go to www.fluke.com to register your Product and find more information. A Warning identifies conditions and procedures that are dangerous to the

More information

DALI 650mA LED Driver

DALI 650mA LED Driver Installation Guide DGLC650C18DD PATENT PENDING REGISTERED DESIGN Designed in Australia to meet Australian Standards and installation conditions DIGINET.NET.AU Diginet Control Systems Pty Ltd ABN 89 095

More information

RU BMS Power Supply and Battery Management System Owners Guide

RU BMS Power Supply and Battery Management System Owners Guide RU2-4012- BMS Power Supply and Battery Management System Owners Guide (These instructions are intended for use by a technician familiar with electronic products) RU2-4012- BMS is a continuous duty power

More information

Solid State Relays contactor with Integrated Fuse Type RGC1F

Solid State Relays contactor with Integrated Fuse Type RGC1F Solid State Relays contactor with Integrated Fuse Type RGC1F Solid State Contactor with integrated fuse Zero Cross Switching Operational voltage: 230 VAC and 600 VAC 35mm width Control voltage: 4-32 VDC

More information

Low Amp Probe EETA308A

Low Amp Probe EETA308A Low Amp Probe EETA308A Reference Manual First Edition SAFETY WARNING DO NOT APPLY OVER 150V AC (RMS) OR DC. DISCONNECT LEADS BEFORE REMOVING THE BATTERY COVER. DO NOT ALLOW THE CABLE TO BECOME ENTANGLED

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

USERS MANUAL MCD REMOTE OPERATOR

USERS MANUAL MCD REMOTE OPERATOR USERS MANUAL MCD REMOTE OPERATOR Order Code: 175G9004, 175G3061 Contents Contents Introduction...2 Important User Information...2 General Description...2 Symbols Used in this Manual...2 Installation...3

More information

Three-phase 200 V series: FRN0025 to 0060C2S-2U Three-phase 400 V series: FRN0013 to 0030C2S-4U

Three-phase 200 V series: FRN0025 to 0060C2S-2U Three-phase 400 V series: FRN0013 to 0030C2S-4U Instruction Manual Supplement for FRN-C2S-2U/4U (7.5 to 20 HP) Compact Inverter 200 V series: FRN0025 to 0060C2S-2U series: FRN0013 to 0030C2S-4U Thank you for purchasing our FRENIC-Mini series of inverters.

More information

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

Video & Power Over Coax Kit

Video & Power Over Coax Kit VPoC User Manual Video & Power Over Coax Kit 1CH Video Power over Coax w/ 12V DC Receiver Device VPoC24DC-01K VPoC24DC-01 N-42-1 x1 N-41C 4CH / 8CH / 16CH Video Power over Coax Server Kit VPoC24DC-04K

More information

Surface mounting, flush mounting, and DIN track mounting

Surface mounting, flush mounting, and DIN track mounting Solid-state Timer H3JA Economical, Compact, Plug-in Timer Time limit, ON-delay, operation with automatic resetting. DIN size (36 x 36 mm), fits standard 8-pin sockets. Wide choice of supply voltages: 24,

More information

Sorensen XG 1700 Series 1700 W A Watt, 1U Programmable DC Power Supplies V. Key Features. Key Modes

Sorensen XG 1700 Series 1700 W A Watt, 1U Programmable DC Power Supplies V. Key Features. Key Modes Sorensen XG 1700 Series 1700 W 1700 Watt, 1U Programmable DC Power Supplies 6 600 V Industry Leading Power Density Up to 1700 Watts in 1U Standard Digital Interfaces USB&RS232/485 LXI Ethernet and Isolated

More information

i400s Calibration Information Introduction

i400s Calibration Information Introduction i400s AC Current Clamp Introduction XWWarning To avoid electric shock or injury, do not perform the performance tests or calibration procedures unless you are qualified to do so. The information provided

More information

Time scale: from 0.05s to 100h Multi-function Plug-in for use with 90.02, 90.03, and sockets

Time scale: from 0.05s to 100h Multi-function Plug-in for use with 90.02, 90.03, and sockets 86 Series - Timer modules Features 86.00 86.30 Timer modules for use in conjunction with relay & socket. 86.00 - Multi-function & multi-voltage timer module 86.30 - Bi-function & multi-voltage timer module

More information

XM1 - Motor protection relay

XM1 - Motor protection relay XM1 - Motor protection relay Contents 1 Applications and features 1 Applications and features 2 Design 3 Working principle 3.1 Overload protection 3.2 Stalling protection 3.3 Earth fault protection 3.4

More information

USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER

USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER Item # 1002 153 664 Model #CE-VD7504GFI USE AND CARE GUIDE DUALCHECK CIRCUIT TESTER Questions, problems, missing parts? Before returning to the store, call Commercial Electric Customer Service 8 a.m. 7

More information

Sola/Hevi-Duty S3K Series Mini-Tower UPS

Sola/Hevi-Duty S3K Series Mini-Tower UPS Sola/Hevi-Duty S3K Series Mini-Tower UPS GUIDE SPECIFICATIONS 700VA to 1600VA 120V models Single - Phase Uninterruptible Power Supply Systems 1.1 SUMMARY 1.0 GENERAL This specification defines the electrical

More information

Presentation Soft starters 0 Altistart 48 soft start - soft stop units

Presentation Soft starters 0 Altistart 48 soft start - soft stop units Presentation Soft starters 5 6 7 65_Ver.-EN.fm/ Presentation (continued) Soft starters Applications The Altistart 8 soft start - soft stop unit is a controller with 6 thyristors which is used for the torque-controlled

More information

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals 25 to 55 A culus CE Application AF09... AF38 4-pole contactors are used for controlling power circuits up to 600 V AC and 240 V DC.

More information

Technical data for manual motor starters Type MS325

Technical data for manual motor starters Type MS325 for manual mor starters Type MS325 General data Rated voltage 600 V Rated current 25 A (14 setting ranges, 0.1 25A) Rated frequency 50-60 Hz Electrical and mechanical life endurance 100,000 operations

More information

S4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General

S4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General S4562C 1085 COMBI BOARD APPLICATION PRODUCT HANDBOOK The S4562C 1085 combi board is an integration of an on/off temperature control and an electronic ignition control. The S4562C 1085 combi board is intended

More information

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

User Manual. T6 Tachometer. Online:   Telephone: P.O. Box St. Petersburg, Florida 33736 User Manual T6 Tachometer Online: www.phareselectronics.com Telephone: 727-623-0894 P.O. Box 67251 St. Petersburg, Florida 33736 Table of Contents Overview... 1 Description... 1 Wiring... 1 T6 Tachometer

More information

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor World Leader in Modular Torque Limiters Installation and Maintenance Instructions PTM-4 Load Monitor 1304 Twin Oaks Street Wichita Falls, Texas 76302 (940) 723-7800 Fax: (940) 723-7888 E-mail: sales@brunelcorp.com

More information

INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS.

INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS. INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS. Before installing and/or using this product, please check for any visual damage of the enclosure, power

More information

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2 Solid-state Contactor (New Heat Sink Construction) G3PB Space and working time saved with new heat sink construction. Series now includes 480-VAC models to allow use in a greater range of applications.

More information

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Made in the U.S.A. NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors Nema Enclosed DC Control Specifications Catalog Number BC140 or Features BC138 BC139 BC140-FBR BC154 BC160 BCWD140

More information

ISO-TECH IPS1810H and IPS1603D DC power supply ISO-TECH IPS 1810H et IPS 1603D Alimentation électrique c.c.

ISO-TECH IPS1810H and IPS1603D DC power supply ISO-TECH IPS 1810H et IPS 1603D Alimentation électrique c.c. ISO-TECH IPS1810H and IPS1603D DC power supply ISO-TECH IPS 1810H et IPS 1603D Alimentation électrique c.c. ISO-TECH IPS 1810H 204-713 ISO-TECH IPS 1603D 204-729 82IP-1810HME Ei Statement of Compliance

More information

The following table shows the symbols used on the product and/or in this manual. Hazardous Voltage. Risk of electric shock.

The following table shows the symbols used on the product and/or in this manual. Hazardous Voltage. Risk of electric shock. i6000s Flex AC Current Probe Instruction Sheet Introduction The i6000s 24 Flex and i6000s 36 Flex AC Current Probes (hereafter referred to as the Probes ) are used with oscilloscopes, digital multimeters,

More information

MCD 200 Series Soft Starters

MCD 200 Series Soft Starters MCD 200 Series Soft Starters AC motors often cause one or more serious problems during startup acceleration. MCD 200 Series electronic soft starters control motor current to provide a smooth start. When

More information

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings 1662/1663/1664 FC Electrical Installation Tester Safety Information Go to www.fluke.com to register your Product and find more information. A Warning identifies conditions and procedures that are dangerous

More information

Max. Output Power. Efficiency (1) 110Vac 220Vac. 450 ma 90 ~ 305 Vac 445 Vdc 200 W 92% EUC-200S045ST

Max. Output Power. Efficiency (1) 110Vac 220Vac. 450 ma 90 ~ 305 Vac 445 Vdc 200 W 92% EUC-200S045ST LED Driver EUC200SxxxST 20110114 D Features Ultra High Efficiency (Up to ) Active Power Factor Correction (0.99 Typical) Constant Current Output Lightning Protection AllRound Protection: SCP, OTP, OVP

More information

OWNER S MANUAL Please read this manual before operating your power supply

OWNER S MANUAL Please read this manual before operating your power supply AC-DC POWER SUPPLY Switch Mode AC-DC Power Supply Model No. PSU-1210 PSU-1223 PSU-1230 OWNER S MANUAL Please read this manual before operating your power supply Table of Contents Precautions 2 Description

More information

P445 Series Electronic Lube Oil Control

P445 Series Electronic Lube Oil Control FANs 125, 121 s Section P Product/Technical Bulletin P445 Issue Date 0100 P445 Series Electronic Lube Oil The P445 Series Electronic Lube Oil is designed for use on refrigeration compressors equipped with

More information

Speed Sensor. Inputs: Safety Information. Outputs. Wiring Diagram. Electrical Data: NOTICE

Speed Sensor. Inputs: Safety Information. Outputs. Wiring Diagram. Electrical Data: NOTICE Speed Sensor ã Read and understand equipment operators manual before operating or performing maintenance. Failure to do so could result in serious injury or death. Safety Information Failure to follow

More information

INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS.

INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS. INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS. Before installing and/or using this product, please check for any visual damage of the enclosure, power

More information

Application Description

Application Description -14 Type, Intelligent Technologies (IT.) Soft Starters February 2007 Contents Description Page Type, Intelligent Technologies (IT.) Soft Starters Product Description....... -14 Application Description....

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL

DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL 72-7570 DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL Table of Contents Specification 1 Safety 3 EMC 4 Installation 5 Connections 5 Operation 6 Maintenance 8 Specification General specifications

More information

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL 72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com

More information

Rental Industry Safety Tester Safe Check 5s

Rental Industry Safety Tester Safe Check 5s Rental Industry Safety Tester Safe Check 5s Feb 2006 2006 Clare Instruments Inc. Issue 2.0 Firmware Version : 1.2a Limited Warranty & Limitation of Liability Clare Instruments Inc, guarantees this product

More information

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM672 LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI 4000 AUGUST

More information

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1 BellMega BM-510 Operation Manual Ver: 1.0 Rev: 1 CONTENTS Page Description 1 Operation 2 Safety 2 Charging 3 Service / Calibration 3 Specifications 4 Description The BellMega is a continuity tester for

More information

DALI Emergency LED Driver - 350/700/1000mA Constant Current

DALI Emergency LED Driver - 350/700/1000mA Constant Current User and Installation Guide DGLCEM035CD-AU DGLCEM070CD-AU DGLCEM100CD-AU - 350/700/1000mA Constant Current PATENT PENDING/REGISTERED DESIGN Designed in Australia to meet Australian Standards and installation

More information

AS/NZS AS/NZS

AS/NZS AS/NZS TEST REORT AS/NZS 4777.2 AS/NZS 4777.3 Grid connection of energy systems via inverters Grid protection requirements Report reference number... : 13TH0287-AS/NZS 4777_0 Date of issue......: 2014-01-22 Total

More information

Autoranging Industrial Multimeter

Autoranging Industrial Multimeter Owner's Manual Autoranging Industrial Multimeter Model No. 82005 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation

More information

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option MODEL NUMBER: SUT30K Highlights On-line double-conversion topology, VFI operation

More information

ampcontrol s Hard rock relay range

ampcontrol s Hard rock relay range ampcontrol s Hard rock relay range TABLE OF CONTENTS Introduction 1 Earth fault lockout and frozen contactor protection EFL 3 Integrated protection PF1 5 IPM V2 7 Earth continuity MEC-1 9 ECM3 11 Earth

More information

EPS/ELA-Series User Manual EPS/ELA 250W

EPS/ELA-Series User Manual EPS/ELA 250W EPS/ELA-Series User Manual EPS/ELA 250W EPS Stromversorgung GmbH Tel: +49 (0)821 570451 0 Index 3 Page: 1 Table of contents: Page 1. Features of ELA-Series... 3 1.1 Basic Functions... 3 1.2 Options...

More information

1100 Series Piston Type Differential Pressure Gauges

1100 Series Piston Type Differential Pressure Gauges 1100 Series Piston Type Differential Pressure Gauges 1. Safety Before installing, check the Series Number and verify compatibility to the process media and temperature in contact with the wetted parts.

More information

ELECTRONIC SOFT STARTER

ELECTRONIC SOFT STARTER ELECTROIC SOFT STARTER V2 Voltage range from 230V - 400V and power from 2.2kW - 37kW Multiple built-in motor protections Wide temperature range from 0 to +50 C (IP54)/40 C (IP00) Available with internal

More information

Versatile and Rugged Industrial LIthium/LiPO Charger Series

Versatile and Rugged Industrial LIthium/LiPO Charger Series Versatile and Rugged Industrial LIthium/LiPO Charger Series Description The M-series is an environmentally robust and sophisticated battery chargers with models supporting Lithium or LiPo batteries. With

More information

C B. Operating up to 5000m altitude 5 year product warranty Models

C B. Operating up to 5000m altitude 5 year product warranty Models DC/DC Converter Wide 2:1 input voltage 6 W DC/DC converter in a compact DIP-24 plastic case I/O isolation 5000 VACrms rated for 250 VACrms working voltage Certification according to IEC/EN/ES 60601-1 3rd

More information

XMLRM01G1P25 Pressure sensors XMLR -1 bar - G 1/4-24VDC ma - PNP - M12

XMLRM01G1P25 Pressure sensors XMLR -1 bar - G 1/4-24VDC ma - PNP - M12 Characteristics Pressure sensors XMLR -1 bar - G 1/4-24VDC - 4..20 ma - PNP - M12 Complementary Current consumption Electrical connection Type of output signal Analogue output function Discrete output

More information