Rectangular fire damper TFER 30. pag. C-10
|
|
- Jack Young
- 6 years ago
- Views:
Transcription
1 pag. C-10 Description Rectangular fire damper with CE label in conformity to UNI-EN 15650, certified according to EN , classified EI 120 S in accordance to EN Removable shifted kinematic mechanism in order to simplify the installation and to allow the eventual walled substitution. Release thermo-fuse with melting point certified at 70 C (72 C for motorised versions). Manual starting stick. Symmetric construction (blade in the box centre line) with resistance characteristics independent of fire origin direction. Tests Cold smokes passage seal with 300 Pa depression, on minimum and on maximum dimension damper (max. 200 m/h correct to 20 C, for at least 5 minutes). Thermo-isolation with temperature s increase control on box 4 sides in proximity to device, on device in proximity to box and on extraction duct, on maximum dimension damper (max. 180 C for each point, max. 140 C as points average). Hot smokes passage seal with 300 Pa depression, on maximum dimension damper (max. 360 m/h, correct to 20 C). Starting mechanism s solidity with 50 opening/closing cycles and following cold smokes seal test (first point). Thermo-fuse s intervention rapidity, that must release in two minutes from oven s ignition. Servomotor s solidity with functionality test after opening/closing cycles for each of 4 disposable models (see Accessories section). Construction Galvanised sheet-steel box. Calcium silicate (external layers) and calcium sulphate (intermediate layer). Graphite base s thermo-expander. cold smokes seal s silicone gasket. Mineral fibre s thermo gasket. CE label (UNI-EN 15650) The fire damper TFER 30 is in conformity to UNI-EN and is provided of CE label, issued from legally certified institution. Dimensions B (mm) : (increments of 50) H (mm) : (increments of 50) Versions TFER 30 (basic version) : it disposes from thermo-fuse locally directed release (fusion temperature certified at 70 C), manual starting stick and an end-stroke microinterruptor, signaling if the blade is in closing position (two contacts: NA and NC). As option it may have an interruption-current or currentlaunch electromagnet, for remote control s release (alarm control unit) and another end-stroke micro-interruptor (blade in opening position). Both can be easily added, also with already installed damper. TFER 30 M (version disposed for motor) : to be combined with a serie s ATF 2x servomotor, it disposes from thermo-fuse locally directed release, one internal and one external to the box (fusion temperature certified at 72 C), remote control release with current interruption, motorised starting and two end-stroke micro-interruptors, signaling blade s opening and closing position posizion (each one with two contacts: NA and NC). N.B. - The presence of at least one signaling micro-interruptor is recommended in conformity to UNI art To remember that the damper s running must be anyway guaranteed, also without electric current (art. 4.1 UNI 10365). Specifications Rectangular fire damper with CE label in conformity to UNI-EN 15650, certified according to EN , classified EI 120 S in accordance to EN Suitable to installation on rigid vertical wall (also with two coupled units), light vertical wall (plasterboard) and horizontal slab. Removable shifted kinematic mechanism to simplify the installation. Release thermo-fuse calibrated at 70 C. Micro-interruptor notifying closed damper status. Manual starting stick.
2 pag. C Key to symbols 1 - Symmetric box 2 - Mineral-fibre gasket 3 - Graphite thermo-expander gasket 4 - Cold smokes silicone seal gasket 5 - Activation plate gasket 6 - Multilayered refractory blade 7 - Kinematic mechanism link-control 8 - Thermo-fuse release s system 9 - Closing test button 10 - Thermo-fuse 11 - Security block 12 - Heat-sinks
3 pag. C-12 Installation N.B. A damper s fire resistance depends on device characteristics, that is the damper has not an own class resistance, but it s always depending on considered device. 1 - Rigid vertical wall N.B. Installation s operations (device s perforation, damper s positioning and filling) are completely described in the installation manual. N.B. The minimum distance between two fire dampers installed on two different ducts cannot be less than 200 mm. N.B. The minimum distance between the fire damper and structural elements around (ceiling, floor, walls) cannot be less than 75 mm. N.B. The 4 following installaton typology are allowed, corresponding to the tests conditions employed from certified laboratory. For each one, classification report allows the fire damper s employment in accordance to law, in the same conditions. 1 Rigid vertical wall Wall class REI 120 Wall thickness 100 mm Wall density 500 kg/m 3 Maximum duct dimensions (BxH) 1500x800 mm Damper class EI 120 S (300 Pa) ve i o 2 Rigid vertical wall - 2 vertical units (flange against flange) Wall class REI 120 Wall thickness 100 mm Wall density 500 kg/m 3 Maximum duct dimensions (BxH) 1500x1600 mm Damper class EI 120 S (300 Pa) ve i o 3 Lightweight insulated vertical wall (plasterboard + steel-wool + plasterboard) Wall class REI 120 Wall thickness 100 mm ( mm) Wall density 100 kg/m 3 (steel-wool) Maximum duct dimensions (BxH) 1500x800 mm Damper class EI 120 S (300 Pa) ve i o 4 Horizontal slab Slab class REI 120 Slab thickness 150 mm Slab density 2200 kg/m 3 Maximum duct dimensions (BxH) 1500x800 mm Damper class EI 120 S (300 Pa) ho i o N.B. - As described in the installation manual, the air spaces resulting between the damper and its device must be filled with M10 or upper class mortar (EN 998-2).
4 pag. C Rigid vertical wall - 2 vertical units 3 - Lightweight insulated vertical wall Steel-wool lines Plates ATF 35 Plates ATF 35 N.B. - In case of flange against flange dampers (case 2) the couple must be executed through special plates ATF 35 (see Accessories section ) filling the gap between the two units with 100 kg/m 3 steel-wool lines (see Installation manual). N.B. - This installation typology is the most complicated one and requests to pay more attention : FCR disposes of an alternative solution called TFERS 30, that is a rectangular fire damper that keeps the same characteristics of TFER 30 but purposely conceived for fast assembly on plasterboard.
5 pag. C Horizontal slab Accessories ATF Vdc (normally energised) interruptionelectromagnet. ATF Vac (normally energised) interruptionelectromagnet. ATF Vdc (normally de-energised) launch electromagnet. ATF Vac (normally de-energised) launch electromagnet. ATF 15 Open position blade s signaling micro-interruptor (contact NA/NC). ATF Vdc servomotor - BxH < 0,8 m 2. ATF Vdc servomotor - BxH 0,8 m 2. ATF Vac servomotor - BxH < 0,8 m 2. ATF Vac servomotor - BxH 0,8 m 2. ATF 31 Hatch 140 mm with gasket. Position: upper (kinematic mechanism side). ATF 32 Hatch 140 mm with gasket. Position : opposite side to kinematic mechanism. ATF 33 Hatch 140 mm with gasket. Position : lower (kinematic mechanism side). ATF 34 Fixing brackets (4) for assembly on plasterboard. ATF 35 Plates (4) for dampers coupling (flange against flange).
6 pag. C-15 Aeration and hearing characteristics Correction factors DP for B 400 mm. P (Pa) B=400 mm 30 H= v (m/s) db A B (mm) DP/DP B400 B (mm) DP/DP B , , , , , , , , , , , , , , , , , , , , , , , , , , ,7 Key to symbols v DP L WA Speed = Capacity/gross section BxH (m/s) Open damper pressure drop (Pa) Pressure sound level weighted A (db A - rif W) v L WA - spectral correction - (db A ) (m/s) K 2K 4K 8K Add algebrically to value L WA resulting on diagram (correcting if B 400 mm.), in order to obtain sound power spectrum. Correction factors L WA for B 400 mm. B (mm) DL WA (db A ) B (mm) DL WA (db A ) 200 3, , , , , , , , , , , , , , , , , , , , , , , , , , ,8 Example Consider a rectangular duct with dimensions BxH = 800x400 mm, which crosses a rigid wall REI 120, through a fire damper TFER 30. The capacity in the duct is supposed to be 5000 m 3 /h. It would results : v = 5000 / (3600 * 0,8 * 0,4) = 4,3 m/s DP = 0,7 * Pa L WA = 1, db A
7 pag. C-16
7/S5 FIRE DAMPER FD40. v 2.9 (en)
7/S v.9 (en) FIRE DAMPER FD0 www.klimaoprema.hr 69 FIRE DAMPER - FDC TABLE OF CONTENTS FIRE DAMPER FD0 7 FIRE CLASSIFICATION 7 SELECTION DIAGRAM 7 ORDERING KEY 7 DAMPER MODELS 7 FD0-M rectangular fire
More information7/S1 FIRE DAMPER PPZEN. v 2.5 (en)
7/S1 v.5 (en) FIRE DAMPER PPZEN www.klimaoprema.hr 39 TABLE OF CONTENTS Product description... Range... Fire classification according to EN 13501-3... Operating mechanisms and dimensions... Operating manual...
More information7/S6 FIRE DAMPER FDC40. v 2.9 (en)
7/S6 v.9 (en) FIRE DAMPER FDC0 www.klimaoprema.hr 8 TABLE OF CONTENTS FIRE DAMPER FDC0 87 FIRE CLASSIFICATION 87 SELECTION DIAGRAM 88 ORDERING KEY 88 DAMPER MODELS 89 FDC0-M cylindrical fire damper with
More informationFDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts
Halton FDR Fire Damper for Rectangular and Circular Ducts Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards. Design for installation in separating concrete and masonry walls and ceilings
More informationFIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS
FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS Rectangular fire dampers FIRE DAMPERS PL-12 PL-15 PL-18-1, PL-18-2 Fire dampers are installed in rectangular or circular ventilation ducts, at passages
More information(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.
Fire damper pl-30 General characteristics Application Fire dampers prevent fire and smoke from spreading through ventilation ducts in buildings. The dampers are intended for use inside buildings and are
More informationPKI-C Cartridge Fire Dampers
Fire Safety Products / 7 PKI-C Cartridge Fire Dampers Fire resistance class EI60S, EI90S and EI0S 96 - CPD - 000 Ordering codes Fire resistance class PKI-C-EI - 60S, 90S and 0S Codes section. The thermal
More informationSystemair Fire Dampers
Fire safety products 1 / 7 Systemair Fire Dampers Fire resistance class EI60S; EI90S and EI120S 1396 - CPD - 0061 1396 - CPD - 0062 Ordering codes Ordering Codes for Circular FD: Fire resistance class
More informationTPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB
Valid from //06 EN 5650:00-09 FIRE DAMPER FDMB These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMB. It is valid for production, designing,
More informationM A D E L. FOK-EIS-180 Fire dampers CE
M A D E L EN 60: FOK-EIS-80 Fire dampers CE The fire dampers FOK-EIS-80 work as a separator between two sectors of fire and ensure the same fire resistance that the structural elements of compartmentalisation,
More informationPKIR3G, PKIS, PKIS3G and PKIS3GA
PKIR3G, PKIS, PKIS3G and PKIS3GA Fire Dampers Fire resistance EI60S, EI90S and EI120S 1396 - CPR - 0076 1396 - CPR - 0077 1396 - CPD - 0062 Ordering codes Dimensions Type of activation PKIR3G 1) - ødn
More informationTPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD
FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD TPM 075/09-DK VALID FROM: 15/1/2012 I. CONTENT These technical specifications state a row of manufactured sizes and models of fire dampers and fire dampers
More informationFire damper FK120/FK90 TECHNICAL DATA
Fire damper FK120/FK90 TECHNICAL DATA 2 Fire damper FK120/FK90 Figure 1 ER1 Figure 2 ER3 The rectangular fire damper FK120/FK90 is available both as motorized and with fuse. The damper casing is manufactured
More informationETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE
FIRE SAFETY AIR MANAGEMENT FIRE DAMPERS ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE 2 ETPR-E-1 Fire damper Technical catalogue Fire and smoke damper ETPR-E-1 is used as a closing device for preventing the
More informationFire/smoke damper EKO-JBG2
Fire/smoke damper EKO-JBG2 Description The EKO-JBG2 fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.
More informationSystemair Fire Dampers
Systemair Fire Dampers Fire resistance class EI60S; EI90S and EI120S www.systemair.com As standard, all fire dampers are designed and certified to comply with EI-S performance attributes. fire dampers
More informationFire Dampers. Types FKA FRL FRK 4/1/EN/1
Fire Dampers Types FKA FRL FRK /1/EN/1 Contents Description Description... Construction... Standard Sizes Installation Details... Functional Description Product Range... Accessories... Circuit Diagrams...
More informationDKISMA. Systemair multicompartment rectangular smoke control dampers. Ordering codes. Description. Design. Fire safety products 1 / 8.
Fire safety products 1 / 8 DKISMA Systemair multicompartment rectangular smoke control dampers Resistance class EI120(v ew i o) S1500C mod AAmulti 1396 - CPR - 0112 Ordering codes Nominal dimensions Type
More informationROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE
ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE Roofmaster STEC non-insulated version - Technical Catalogue 3 CONTENTS GENERAL DESCRIPTION Application/specification...4 Features...4
More informationFire/combustion gas damper EKO-JBL
Fire/combustion Description The fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting. The damper is designed
More informationFire/smoke damper EKO-SRBG1
Fire/smoke damper EKO- Description The EKO- fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.
More informationType KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU
Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS Rectangular fire damper for use in extract air and exhaust air ducts of
More informationFire damper ETPR. Specifications. Product code example Fire damper ETPR
Fire damper ETPR ETPR fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 1366-2. ETPR meets the requirements of fire class EI 60 S / EI 90 S.
More informationMULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA
MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA 96 - CPR - 0 ORIGINAL INSTALLATION, MAINTENANCE AND OPERATION MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL! / PP-5_0604 DKISMA
More informationESAS Smoke control damper
ESAS Smoke control damper 1 Rectangular smoke control damper ESAS is specially designed to use in single fire compartment applications as a closing or as an opening damper for smoke extract purposes. ESAS
More informationSmoke damper EKO-SRB1
Smoke damper EKO-SRB1 Description The EKO-SRB1 smoke damper is a CE-approved damper in fire class E60 intended for fire compartmentation or protection against the spread of fire and smoke in ventilation
More informationFire/combustion gas damper EKO-JBG
Fire/combustion EKO-JBG Description The EKO-JBG fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting.
More informationFire damper BKA-EN. with general technical approval Z tested according to DIN EN
Fire damper BKA-EN with general technical approval Z-41.3-667 tested according to DIN EN 1366-2 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Phone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980
More informationVARYCONTROL VAV Dual Duct Terminal Boxes
5/2/B/3 VARYCONTROL VAV Dual Duct Terminal Boxes for variable volume systems Type TVM Trox (U.K.) Ltd Caxton Way GB-Thetford Norfolk IP24 3SQ Telephone +44 (0)1842 754545 Telefax +44 (0)1842 7051 www.troxuk.co.uk
More informationCombustion gas damper EKO-JB
EKO-JB Description The EKO-JB combustion is a Class E6 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment wall or floor
More informationCONSTANTFLOW Volume Flow Controllers
5/9.1/EN/8 CONSTANTFLOW Volume Flow Controllers for constant volume systems Type EN The art of handling air Contents Description Description 2 Application 3 Construction Dimensions Accessories 4 Dimensions
More informationETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance
ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance 07/2013 Fläkt Woods FIFLO EN 2013.07 2 ZU CLOSED AUF OPEN Fire damper ETPS-EI Contents Operation and Maintenance
More informationVU120. Rectangular smoke evacuation damper. V22-EN-G 08/2017
Organisme Certificateur AFNOR Certification - www.marque-nf.com VU120 Rectangular smoke evacuation damper. en 0749 Clapets coupe-feu et Volets de désenfumage D.A.S. Rf-Technologies nv Lange Ambachtstraat
More informationTechnical information
6-8 Application Rectangular NK and NL types are pressure-independent VAV and CAV air volume control terminals. The terminals are designed particularly for systems with large air volumes and duct sizes
More informationVU120. Rectangular smoke evacuation damper. V22-F 07/2015
Organisme Certificateur AFNOR Certification - www.marque-nf.com VU120 Rectangular smoke evacuation damper. en Clapets coupe-feu et Volets de désenfumage D.A.S. Rf-Technologies nv Lange Ambachtstraat 40
More informationHeights up to 1000 mm Fire resistance period up to 120 minutes
Maintenance-free FK90 fire dampers - series FK120 - Heights up to 1000 mm Fire resistance period up to 120 minutes Fire classification: EI 30/60/90/120 (ve - ho, i o) S C10ooo Hygiene certificate Environmental
More informationROOF FAN ROOFMASTER STEC
AIR COMFORT AIR MOVEMENT ROOF FANS ROOF FAN ROOFMASTER STEC INSULATED VERSION» TECHNICAL CATALOGUE 2 STEC Roofmaster - Technical Catalogue CONTENTS GENERAL DESCRIPTION Application/specification... 3 Features...
More informationFD-C Series. Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper B RITAI N
V1175 FD-C Series Circular Single Blade Externally Resettable Combination Fire and Volume Control Damper ES classified fire dampers with reduced smoke leakage characteristics (BS E 1366-2) Aerodynamically
More informationSlot diffusers for ceiling installation
X X testregistrierung Slot diffusers for ceiling installation Type lenum box with damper blade (optional) Alternating horizontal air discharge Concealed screw fixing With wide diffuser face for larger
More informationNEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION
air handling intelligence FIRE SFETY Fire Damper in libraries of EI 10 (v e -i o) S EN 13501-3+1:01 EN 15650:0 Certificate of Conformity 1488-CPD-081/W EUROPEN PTENT PPLICTION EP 01158318 GOLD MEDL MTP
More informationCU2. Wide-ranging rectangular fire damper up to C2-G 08/2015
Organisme Certificateur AFNOR Certification - www.marque-nf.com CU2 Wide-ranging rectangular fire damper up to 120 en Clapets coupe-feu et Volets de désenfumage D.A.S. Rf-Technologies nv Lange Ambachtstraat
More informationTYPE EK-EU SMOKE CONTROL DAMPER
Homepage > PRODUCTS > Fire and Smoke Protection > Smoke Control Damper > Type EK-EU TYPE EK-EU SMOKE CONTROL DAMPER WITH TROXNETCOM AS AN OPTION CE COMPLIANT ACCORDING TO EUROPEAN REGULATIONS EK-EU WITH
More informationA B. Linear cylinder diffuser LC. pag. A-52
pag. A-5 Linear cylinder diffuser LC Description Linear rotating cylinder diffuser for ceiling or wall installation. Each slot houses inside a range of cylinders, that, by rotation, allow differents launch
More informationFK120/FK90 FIRE DAMPER» INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE
FIRE SAFETY AIR ANAGEENT FIRE DAPERS FK120/FK90 FIRE DAPER» INSTRUCTIONS FOR INSTALLATION, OPERATION AND AINTENANCE ZU CLOSED AUF OPEN 2 FK120/FK90 Fire damper Instructions for installation, operation
More informationPressure: Max working 8 bar (116 psi) (acc. to NFPA T ) Burst 16 bar (232 psi) (acc. to NFPA T ) Buna-N (FKM on request)
HYDRAULIC FILTRATION Return filters, tank top mounting, inside-to-outside filtration Technical Information Pressure: Max working 8 bar (116 psi) (acc. to NFPA T 3.10.5.1) Burst 16 bar (232 psi) (acc. to
More informationCombustion gas damper EKO-SRB
Combustion EKO-SRB Description The EKO-SRB combustion is a Class E60 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment
More informationFire dampers ETCE and ETCS TECHNICAL DATA
Fire dampers ETCE and ETCS TECHNICAL DATA 2 Fire dampers ETCE and ETCS Veloduct ETCE fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 13662.
More informationseries CEVH Smoke Evacuation Damper
series CEVH Smoke Evacuation Damper www.koolair.com Series CEVH 1 CONTENTS Description 2 Dimensions 4 Installation 5 Assembly 6 Electrical connections 7 Technical data 8 Coding 10 2 Series CEVH Description
More informationseries FSD-FLD Fire and smoke dampers UL Approval
series FSD-FLD Fire and smoke dampers UL Approval www.koolair.com Series FSD-FLD 1 Fire and smoke dampers UL Approval FSD-B-U / FSD-A-U and FLD-S-U / FLD-S-UD CONTENTS Description FSD-B-U / FSD-A-U 2 Construction
More informationFire Dampers. Type FDF. Compliant to SABS (193:2004) SA/6/1/EN/3
SA/6/1/EN/3 Fire Dampers Type FDF Compliant to SABS (193:2004) TROX (South Africa) (Pty) Ltd. 10 Wigford Road Masons Mill Pietermaritzburg Tel. +27 (0)33 398 1006 Fax. +27 (0)33 398 1100 email : pmb@troxsa.co.za
More informationCR120. Optimized circular fire damper up to 120' C11-I 07/2015
Organisme Certificateur AFNOR Certification - www.marque-nf.com CR120 Optimized circular fire damper up to 120' en Clapets coupe-feu et Volets de désenfumage D.A.S. Rf-Technologies nv Lange Ambachtstraat
More informationThe Straight Way. Rectangular Cabinet Fan. Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans
Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans The Straight Way Rectangular Cabinet Fan Systemair India Pvt. Ltd. certifies that the Rectangular
More informationBevent Rasch BSK Fire /04/2017
Bevent Rasch - Fire - BSK120 10/04/2017 Rectangular Fire resistance class /S Sizes from 200 x 200 mm to 1200 x 1000 mm Prefitted safety actuator 24V or 230V Available in MagiCAD CE-marked building product
More informationCR2. Circular fire damper C1-C 04/2010
Rf-Technologies nv - Lange Ambachtstraat 40-9860 Oosterzele - België - Tel +32 9 362 31 71 - Fax +32 9 362 33 07 - www.rft.be - info@rft.be Table of contents o n t e n t s Pr o d u c t p r e s e n tat
More informationCRE60 XF9499. Røgevakueringsspjæld Ø100-Ø630. AiR Ξ FORCE CRE60 XF9499 FORCE:
AiR Ξ FORCE CRE60 XF9499 Røgevakueringsspjæld Ø100-Ø60 CRE60 XF9499 FORCE: Røgevakueringsspjæld Ø100-Ø60 Super let montage Godkendt for montage væk fra væg Monteres i både tunge og lette vægge/dæk Lavt
More informationBSK-EN Fire damper INSTALLATION, MOUNTING AND OPERATING INSTRUCTIONS
INSTALLATION, MOUNTING AND OPERATING BSK-EN Fire damper Contents Description... 2 Models and dimensions... 3 Mounting information... 5 Installation information... 6 Technical data... 7 Accessories... 9
More informationCU-LT. Optimised rectangular fire damper up to C3-EN-J-06/2018
CU-LT Optimised rectangular fire damper up to 120 en 0749 Rf-Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel +32 9 362 31 71 Fax +32 9 362 33 07 info@rft.be www.rft.be C3-EN-J-06/2018
More informationType VSD35. Nominal length up to 1500 mm: one spigot
Type VSD35 Nominal length up to 1500 mm: one spigot NUMEROUS VARIANTS FOR MANY DIFFERENT INSTALLATION SITUATIONS Slot diffusers with 35 mm diffuser face (nominal width) and adjustable air control elements
More informationActionair A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore Projects
March 06 A-60 Marine Fire Dampers Tests and Approvals A60 Fire Rated. Lloyds Register of Shipping Approved. Marine Equipment Directive compliant. USCG Approved. Germanischer Lloyds Approved. American Bureau
More informationBevent Rasch BSK6. - Fire /04/2017
Bevent Rasch - Fire - BSK6 11/04/2017 Fire resistance class EI60 / EI60S Sizes from 200 x 200 mm to 800 x 800 mm Prefitted safety actuator 24V or 230V Low weight Easy installation CE-marked building product
More informationFire Safety Products. Product Overview
Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans Fire Safety Products Product Overview SAFETY PRODUCTS prevent the spread of
More informationShutter Fire Damper Type FSD GFSD 4/1.1/B/1
Shutter Fire Damper Type FSD GFSD /./B/ Contents Description Description... Construction... Installation Details... Control Accessories... Technical Data... Order Details... 7 8 9 FSD-L GFSD-L FSD Fire
More informationCU2-15. Rectangular fire damper 120' at 1500 Pa. C7-EN-I 06/2018
CU2-15 Rectangular fire damper 120' at 1500 Pa en 0749 Rf-Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel +32 9 362 31 71 Fax +32 9 362 33 07 info@rft.be www.rft.be C7-EN-I 06/2018 2
More informationFire Damper BSK-RPR. with general building supervisory approval Z
Fire Damper BSK-RPR with general building supervisory approval Z-41.3-681 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de
More informationVAV terminal units. Type TVM. For dual duct systems PD TVM 1
X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings
More informationseries Silencers
series SK Silencers www.koolair.com Series SK 1 Silencers CONTENTS ASK-1 and ASK-2 Round Silencers Description 4 ASK-1 Overall Dimensions 5 ASK-2 Overall Dimensions 6 Selection Table and Weights 7 ASK-1
More informationCU2/B. Battery assembly of max. 4 individual dampers. C31-EN-G 06/2018
CU2/B Battery assembly of max. 4 individual dampers en 0749 Rf-Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel +32 9 362 31 71 Fax +32 9 362 33 07 info@rft.be www.rft.be C31-EN-G 06/2018
More informationUTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper
Halton UTK, UTT Multi-blade Damper Temperature operation range up to +100 C, optionally up to +200 C Galvanised steel design Classification of casing leakage EN 1751 class B UTK: Shut-off, adjustment,
More informationCAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)
X X testregistrierung CAV controllers Type Adjustment scale For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) Rectangular, mechanical self-powered
More informationTechnical documentation
VM-PRO Mechanical volumetric flow control- Table of Contents Areas of application... 2 Useable volumetric flow ranges... 2 Function... 3 Processing... 3 Available sizes / -dimensions... 4 Accessories list
More informationVariable Air Volume Dampers
OVAV 2000 SERIES OPTIMA VAV DAMPERS Overview OPTIMA make Variable Air Volume (OVAV) box is a part of an Air Conditioning system. It is located inside the duct work. VAV Dampers are designed to control
More informationSmoke control damper RKI-90 Test certificate Z
Resistance class EK90 within smoke extraction ducts that have a fire resistance time of 90 min Ordering example / dimensions smoke control damper consisting of the housing with cut-off damper designed
More information1/11 29/06/2016 CONTENTS 1. GENERAL DUCTS, AIR VENTS, VALVES MONOBLOCK UNITS FILTRATION CONTROL...
1/11 29/06/2016 VENTILATION AND Buildings & Technical Services Section AIR-CONDITIONING STANDARD CONTENTS 1. GENERAL... 2 2. DUCTS, AIR VENTS, VALVES... 2 3. MONOBLOCK UNITS... 3 4. FILTRATION... 5 5.
More informationTransShield Mode 1/2. Transfer Stainless Steel Sliding Plate Fire Dampers.
TransShield Mode 1/2 Transfer Stainless Steel Sliding Plate Fire Dampers www.actionair.co.uk sales@actionair.co.uk Introduction The TransShield Modes 1 and 2 stainless steels stainless steel sliding plate
More informationCeiling swirl diffusers with perforated face plate
X X testregistrierung Ceiling swirl diffusers with perforated face plate Type Horizontal swirling air discharge Diffuser face plate with perforated circular face style and exposed discharge nozzle Diffuser
More informationROOFMASTER STEF-HT ROOF FAN
fire safety Air movement Roof Fans ROOFMASTER STEF-HT ROOF FAN» Technical CATALOGuE Contents ROOFMASTER STEF-HT...3 Performance Data...4 Performance Table...5 General description...6 Fan Chart-explanation
More informationDCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description
DCV-CF Pressure controlwith airflow measuring 24VAC + Communication Pressure control with airflow measuring DCV-CF DIN 24VAC + Communication AIN AOUT SMART DAMPERS & MEASURING UNITS PRESSURE & FLOW DCV-CF
More informationCYCLONE F 400 smoke extraction casing
Fire protection CYCLONE F smoke extraction casing Presentation of the CYCLONE F range (12) WHY CHOOSE A CYCLONE F? In order to fulfil the requirements of the CE markings (EN 1211-3 and the French governmental
More informationPK-I-Ex. Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S. Systemair Fire Dampers for Explosive Areas.
Systemair Fire Dampers for Explosive Areas Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S www.systemair.com Description Fire damper (hereafter referred to as damper) is a fire
More informationPressure control damper ERPA
Key features Constant pressure Real-time pressure monitoring with FW compact controller Can be connected to Modbus Available in IPSUM compatible version ERPA is a rectangular pressure control damper for
More informationMotorized Fire Dampers
Model : OMFD-611 (Fusible link and spring return actuator) GI steel sheet construction In accordance with UL555 & UL555S suitable for installation in walls and partitions having rating 2 Hrs. Static and
More informationCircular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/
6/5/EN/6 Circular Silencer Rigid and flexible construction Type CA CB CF CS TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn
More informationWDD/WSD - Grille. Halton WDD/WSD. Universal Grille
Halton WDD/WSD Universal Grille Horizontal air supply, suitable also for exhaust Adjustable vertical front vanes, adjustable horizontal rear vanes: WDD, adjustable horizontal vanes: WSD Aluminium construction
More informationDAMPERS LSS - R. N-6230 SYKKYLVEN, NORWAY TEL FAX
DAMPERS LSS - R LSS / SOD circular single blade shut off damper SSVent rectangular multiblade shut off damper S.Ventil R1OVL circular single blade weather tight damper/valve RD circular regulating damper
More information1 AIR HANDLING UNIT TYPE AIR ACCESS 75
SUPPLY 1 AIR HANDLING UNIT TYPE AIR ACCESS 75 Location : EXTERNAL Position : SIDE BY SIDE SLIDING PANELS for COMPLETE ACCESSIBILITY MULTI SERVICE BULKHEAD for HYDRAULIC AND ELECTRICAL CONNECTIONS Self-supporting
More informationBy-pass: 1,7 bar (24.6 psi) setting N.B. Cartridge with integrated bypass valve and antidrainback membrane
HYDRAULIC FILTRATION Spin-on, tank top return filters Technical Information Pressure: Max working 12 bar (175 psi) (acc. to NFPA T 3.10.17) Burst 20 bar (290 psi) (acc. to NFPA T 3.10.17) Connection Ports:
More informationJVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6
1 CONTENTS Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6 2 VAV regulator, model Description The variable air volume regulators
More informationCAV controllers. Type VFL. Volume flow limiter for insertion into ducting K
.1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical
More information2/1/EN/3. Slot Diffuser. Type VSD15. with 15 mm wide diffuser face
2/1/EN/3 Slot Diffuser Type VSD15 with 15 mm wide diffuser face Contents Air Diffuser Discharge Characteristics (horizontal) 2 Description 3 Air Diffuser Discharge Characteristics (alternating) 3 Construction
More informationType MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE
Homepage > Products > Sound attenuators > Splitter sound attenuators > Type MSA Type MSA Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE
More informationSEMI RIGID THE PROFESSIONALS CHOICE
SEMI RIGID THE PROFESSIONALS CHOICE for efficient, high performance MVHR ductwork installations. SAP APPENDIX Q LISTED brookvent.co.uk FITTING OUTLINE THE PROFESSIONALS CHOICE for efficient, high performance
More informationType TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES
Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES Rectangular VAV terminal units for the extract air control in buildings with variable air volume
More informationCAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1
X X testregistrierung CAV controllers Type Adjustment scale ATEX-Zertifizierung For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) Circular, mechanical self-powered
More informationWAY MOTORISED COMPACT ZONE VALVES
2-3 - 4 WAY MOTORISED COMPACT ZONE VALVES CT0736.0_03 EN May 2015 ZONE 2C ZONE 4C ZONE 3C o o o Reduced overall dimensions; Extremely quiet operation; Valve with union connections. PRODUCTION RANGE Valve
More informationMultileaf damper with actuator
JZ Multileaf damper with actuator FOR SHUTTING OFF THE AIRFLOW IN AIR CONDITIONING SYSTEMS Rectangular multileaf dampers for volume flow and pressure control as well as for shutting off ducts and openings
More informationBRC
------------------------------------------------------------- Enclosed climate beam for cooling, heating and ventilation CLIMATE BEAM is an enclosed climate beam with integrated circulation air openings
More informationFiltrec elements are tested according to ISO 2941, ISO 2942 and ISO 23181
Common HYDRAULIC FILTRATION Side wall mounting suction filters Technical Information Connection Ports: 1-1 1/4-1 1/2 BSP (other thread options on request) 1 1/2 SAE J518-3000/M12 Housing Materials: Cover:
More informationRectangular smoke damper (remote controlled)
Clapets coupe-feu et Volets de désenfumage D.A.S. Organisme Certificateur AFNOR Certification - www.marque-nf.com VU10 Rectangular smoke damper (remote controlled) Rf-Technologies nv - Lange Ambachtstraat
More informationAccessories. Balancing plenum PRI For balancing & equalising the airflow and attenuating the duct noise
Halton AWE/AWU Universal Grille Horizontal air supply, suitable also for exhaust Fixed front vanes, stable throw pattern with vertical 15 deflection: AWE, no deflection: AWU Adjustable rear vanes for horizontal
More informationHIGH-POWERED VENTILATORS
HIGH-POWERED VENTILATORS WITH ROOF FANS 400ºC/2h The THT/HATCH series was designed using high-powered ventilator technology for smoke extraction in the event of a fire, and is equipped with THT series
More information