ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE

Size: px
Start display at page:

Download "ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE"

Transcription

1 ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE

2

3 Roofmaster STEC non-insulated version - Technical Catalogue 3 CONTENTS GENERAL DESCRIPTION Application/specification...4 Features...4 Material and design...4 Motor and impeller...4 Wiring charts...4 Speed control...4 EC controller...4 Easy installation and service... 5 Demand controlled ventilation... 5 Accessories... 5 PERFORMANCE DATA AND TABLES... 6 FAN CHART EXPLANATION AND DEFINITIONS...7 TECHNICAL DATA INCL. DIMENSIONS STEC STEC STEC STEC STEC STEC STEC STEC ACCESSORIES INCLUDED IN FAN PACKAGES SAFE Safety switch...24 EC controller...24 ACCESSORIES TO BE ORDERED SEPARATELY BOGA Roof curb with insulation EI STEZ-01 Flat roof socket STEZ-02 Flexible connection...27 STEZ-04 Mounting plate...27 STEZ-05 Back draught shutter...27 STEZ-07 Inlet sound attenuator...28 STYZ Potentiometer...28 WIRING DIAGRAMS Wiring diagram A, STEC Wiring diagram B, STEC PRODUCT AND ACCESSORY CODES...31

4 4 Roofmaster STEC non-insulated version - Technical Catalogue GENERAL DESCRIPTION APPLICATION/SPECIFICATION STEC non-insulated roof fan is designed to be used for the extraction of exhaust air and other non-aggressive gases where low energy consumption, simple construction and demand controlled ventilation are required. It can be installed directly on the concrete or alternatively on a roof curb. The existing unit can be exchanged by using an installation frame, which is always included as standard in the delivery of STEC roof fan (sizes ). STEC is equipped with high efficiency EC-motors with integrated speed controller. The plastic impeller is optimized for high efficiency. The casing and motor-impeller-combination can be opened for easy service and maintenance. The fan is discharging vertically. SPECIFICATION Product type: Impeller type: Insulation: Discharge: Temperature: STEC non-insulated roof fan Plastic impeller with integrated EC motor Fan casing is non-insulated Vertical Ambient temperature up to + 60 C (see motor table for each size) Environment class: C4 (EN ISO ) Motor: Electrical supply Speed control: Regulations complied: EC outer rotor motor Sizes : 1~230 VAC 50 Hz Sizes : 3~400 VAC 50 Hz 0-10 V signal Using separate control accessories 1253/2014 for roof fan as NRVU/UVU 327/2011 for motorized impeller inside All components are designed and manufactured in accordance with quality assurance system ISO 9001 and the environmental management system ISO The roof fan is CE marked. FEATURES 8 sizes Volume flow rate up to 4.5 m 3 /s ( m 3 /h) Max pressure rise up to Pa MATERIAL AND DESIGN The casing is made of black pre-painted galvanized sheet metal or aluminum and zinc coated sheet metal. Surface treatment meets requirements for environmental class C4. The fan discharges upwards. MOTOR AND IMPELLER The fans use external rotor EC motors with integrated speed controller. The motor is in the airstream and is cooled by the exhaust air. The impeller is made of plastic and has backward curved blades. The IP class for the motor is IP 54, insulation class is B and all motors are equipped with thermal overload protector (TOP) that is internally connected. Fan can be equipped with an EC controller. All fans are balanced to meet the vibration level of 4.5 mm/s RMS ISO WIRING CHARTS Wiring charts are presented on pages SPEED CONTROL Motor speed can be controlled using analog 0-10 V signal or using an EC controller. EC CONTROLLER The EC controller is installed inside the casing (not available for size 190). It can be ordered as a ready-to-be-used part, in which case it is included in the fan ordering code (see codes on page 31). The EC controller is, however, not automatically included in the standard version of STEC so please check the ordering codes. The EC controller includes the following operations: Single-speed use: speed is set using Low potentiometer Two-speed operation is set using Low and High potentiometers Relay output can be selected for either alarm or running indication 0-10 V control from BMS (Building Management System)

5 Roofmaster STEC non-insulated version - Technical Catalogue 5 EASY INSTALLATION AND SERVICE Installation is presented in the installation manual and various control possibilities in a separate section of this catalogue. DEMAND CONTROLLED VENTILATION Demand controlled ventilation, DCV, is required by ErP Regulations. In practise this means that all roof fans shall be equipped with a speed controller. STEC roof fan range with EC motor has an integrated speed controller and thus the whole fan range is fully ErP compliant also in this sense. Using DCV it is easy to adjust the correct fan speed and optimize the energy consumption. Different sensors and controllers can be connected to the speed control system. STEC can be installed on the concrete or on a roof curb using an installation frame. The existing unit can be exchanged by using an installation frame, which is always included as standard in the delivery of STEC roof fan (except the smallest size 190). The fan is equipped as standard with an opening mechanism that can be locked to open position. The impeller can be easily cleaned, if necessary. REPLACING THE EXISTING ROOF FAN ACCESSORIES INCLUDED IN FAN PACKAGES See the roof fan product code: accessory package (bbb) on page = STEC fan basic version 1 = STEC fan including safety switch (not wired, the cable is not included in delivery) 2 = STEC fan including EC controller (connected, the cable included) and safety switch (not wired, the cable is not included in delivery). Not available for size 190. ACCESSORIES TO BE ORDERED SEPARATELY BOGA Roof curb STEZ-01 Flat roof socket STEZ-02 Flexible connection STEZ-04 Mounting plate STEZ-05 Back draught shutter STEZ-07 Inlet sound attenuator STYZ Potentiometer Size 190 Sizes STEC roof fans in sizes are equipped with a mounting frame as standard. The mounting frame can be installed on the existing base made of concrete or on a roof curb. STEC roof fan size 190 is delivered without the mounting frame. The fan can be installed on the concrete or on a roof curb. As the fans have as standard the possibility to adjust the fan speed it is easy to replace the existing fan and adjust the air flow.

6 6 Roofmaster STEC non-insulated version - Technical Catalogue PERFORMANCE DATA AND TABLES NON-INSULATED ROOFMASTER STEC Static Pressure (Pa) STEC-225 STEC-355 STEC-190 STEC-310 STEC-400 STEC-450 STEC-500 STEC m 3 /h MAX VOLUME FLOW RATE m 3 /s AS FUNCTION OF STATIC PRESSURE Size 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 m 3 /s 5 Pressure (Pa) STEC STEC STEC STEC STEC Volume flow rate STEC STEC STEC Volume flow rate m 3 /s MAX VOLUME FLOW RATE m 3 /h AS FUNCTION OF STATIC PRESSURE Size Pressure (Pa) STEC STEC STEC STEC STEC STEC STEC STEC Volume flow rate m 3 /h

7 Roofmaster STEC non-insulated version - Technical Catalogue 7 FAN CHART EXPLANATION AND DEFINITIONS SYMBOLS v Δp s (Pa) q v (m³/h) w 1550 r/min u 55 46% 60 db(a) y x z 30 u q v Volume flow rate m 3 /s, m 3 /h v Dp s Fan static pressure Pa w Fan max speed r/min x h Overall static efficiency at max r/min % y L wa A-weighted total sound level to surroundings L Woct Sound power level by octave bands (without A-weighting) K oct ΔL Correction when diving into different octave bands Remote attenuation (given values calculated for an ideal case in a halfspace) z q nom Nominal flow rate See Example on this page db(a) db db db (m³/s) 0 0 0,1 0,2 0,3 0,4 0,5 0,6 q v (m 3 /s) u SOUND DATA The total A-weighted sound power level to surroundings, L wa, can be read in the fan chart. The correction coefficients K oct by octave bands can be read in the table below the fan chart. The sound power level by octave band to the duct or to the surroundings (without A-weighting) can be obtained by using the following formula: L woct = L wa + K oct SOUND PRESSURE LEVEL AND REMOTE ATTENUATION Distance L (m) Attenuation L (db) The total sound pressure level to surroundings at different distances can be estimated using the following formula: THE SYMBOLS USED: Fan code = fan type and size. Min r/min = minimum fan speed where the sound power level correction K oct is still applicable. Max r/min = maximum fan speed where the sound power level correction K oct is still applicable. Correction = Sound power level correction factors K oct for the octave bands 63 to 8000 Hz. FAN DATA The fan data is presented using fan-motor-speed controller combination. For nominal flow rate, see each size. The fan data is presented at density 1.2 kg/m 2 and tested according to ISO 5801 and ISO L pa = L wa L EXAMPLE Sound pressure level L pa at 10 m distance: Operation point 0,3 m 3 /s / 150 Pa L wa = 61 db(a) according to fan chart L pa at 10 m: 61 db(a) 28 db(a) = 33 db(a) The operation point and L wa are presented in the above fan chart and table.

8 8 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-190 FAN DATA q v (m³/h) r/min % Δ p s (Pa) db(a) ,05 0,1 0,15 0,2 q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is m³/s. The fan is classified as NRVU-UVU. SOUND DATA Fan code Sound path Min r/min Max r/min Correction K oct (db) in octave band mid-frequency (Hz) Surroundings Surroundings Surroundings STEC-190 Surroundings Inlet duct Inlet duct Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

9 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-190 DIMENSIONS AND WEIGHT Weight: 8 kg Roof free outlet area: m 2 No mounting frame is included for size 190. PRODUCT CODE Roof Fan Size (a) 245 Motor type (bbb) 1 = 1-phase motor Insulation (bbb) 1 = non-insulated version STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Potentiometer Nom. power kw STEC Supply voltage 1~ VAC 50/60 Hz Max Speed r/min BOGA c-2 STYZ Nom. current A Temperature range C Accessory package (bbb) 0 = basic 1 = including safety switch Material (c) 1 = painted galvanised sheet metal, black Construction (d) 0 = standard Generation (e) WIRING A STEC c-0-1 (fan packages 0 & 1) See corresponding wiring diagram on pages

10 10 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-225 FAN DATA q v (m³/h) r/min % Δp s (Pa) db(a) ,05 0,1 0,15 0,2 0,25 q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is m 3 /s. The fan is classified as NRVU-UVU. SOUND DATA Correction K oct (db) in octave band mid-frequency (Hz) Fan code Sound path Min r/min Max r/min Surroundings Surroundings STEC-225 Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

11 Roofmaster STEC non-insulated version - Technical Catalogue 11 TECHNICAL DATA - STEC-225 DIMENSIONS AND WEIGHT Ø Weight: 10 kg Roof free outlet area: m 2 Mounting frame (included in delivery). PRODUCT CODE Roof Fan Size (a) Motor type (bbb) 1 = 1-phase motor Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Construction (d) 0 = standard Generation (e) STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Flat roof socket Flexible connecton Adapter plate Back draught shutter Inlet sound attenuator Potentiometer Nom. power kw STEC WIRING Supply voltage 1~ VAC 50/60 Hz BOGA-01-1-c-2 STEZ-01-1 STEZ-02-1 STEZ-04-1 STEZ-05-1 STEZ-07-1 Max Speed r/min STYZ A STEC c-0-1 (fan packages 0 & 1) B STEC c-0-1 (fan package 2) Nom. current A Temperature range C See corresponding wiring diagram on pages

12 12 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-310 FAN DATA q v (m³/h) r/min % Δp s (Pa) db(a) ,1 0,2 0,3 0,4 0,5 0,6 q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is m³/s. The fan is classified as NRVU-UVU. SOUND DATA Correction K oct (db) in octave band mid-frequency (Hz) Fan code Sound path Min r/min Max r/min Surroundings Surroundings STEC-310 Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

13 Roofmaster STEC non-insulated version - Technical Catalogue 13 TECHNICAL DATA - STEC-310 DIMENSIONS AND WEIGHT Ø Weight: 16 kg Roof free outlet area: m 2 Mounting frame (included in delivery). PRODUCT CODE Roof Fan Size (a) Motor type (bbb) 1 = 1-phase motor Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Construction (d) 0 = standard Generation (e) STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Flat roof socket Flexible connecton Adapter plate Back draught shutter Inlet sound attenuator Potentiometer Nom. power kw STEC WIRING Supply voltage 1~ VAC 50/60 Hz BOGA-02-1-c-2 STEZ-01-2 STEZ-02-2 STEZ-04-2 STEZ-05-2 STEZ-07-2 Max Speed r/min STYZ A STEC c-0-1 (fan packages 0 & 1) B STEC c-0-1 (fan package 2) Nom. current A Temperature range C See corresponding wiring diagram on pages

14 14 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-355 FAN DATA q v (m³/h) r/min % Δp s (Pa) db(a) ,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is m³/s. The fan is classified as NRVU-UVU. SOUND DATA Correction K oct (db) in octave band mid-frequency (Hz) Fan code Sound path Min r/min Max r/min Surroundings Surroundings STEC-355 Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

15 Roofmaster STEC non-insulated version - Technical Catalogue 15 TECHNICAL DATA - STEC-355 DIMENSIONS AND WEIGHT Ø Weight: 22 kg Roof free outlet area: m 2 Mounting frame (included in delivery). PRODUCT CODE Roof Fan Size (a) Motor type (bbb) 1 = 1-phase motor Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Construction (d) 0 = standard Generation (e) STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Flat roof socket Flexible connecton Adapter plate Back draught shutter Inlet sound attenuator Potentiometer Nom. power kw STEC WIRING Supply voltage 1~ VAC 50/60 Hz BOGA-03-1-c-2 STEZ-01-3 STEZ-02-3 STEZ-04-3 STEZ-05-3 STEZ-07-3 Max Speed r/min STYZ A STEC c-0-1 (fan packages 0 & 1) B STEC c-0-1 (fan package 2) Nom. current A Temperature range C See corresponding wiring diagram on pages

16 16 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-400 FAN DATA q v (m³/h) r/min % 1200 Δp s (Pa) db(a) ,2 0,4 0,6 0,8 1 1,2 q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is m³/s. The fan is classified as NRVU-UVU. SOUND DATA Correction K oct (db) in octave band mid-frequency (Hz) Fan code Sound path Min r/min Max r/min Surroundings Surroundings STEC-400 Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

17 Roofmaster STEC non-insulated version - Technical Catalogue 17 TECHNICAL DATA - STEC-400 DIMENSIONS AND WEIGHT Ø Weight: 27 kg Roof free outlet area: m 2 Mounting frame (included in delivery). PRODUCT CODE Roof Fan Size (a) Motor type (bbb) 1 = 1-phase motor Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Construction (d) 0 = standard Generation (e) STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Flat roof socket Flexible connecton Adapter plate Back draught shutter Inlet sound attenuator Potentiometer Nom. power kw STEC WIRING Supply voltage 1~ VAC 50/60 Hz BOGA-04-1-c-2 STEZ-01-4 STEZ-02-4 STEZ-04-4 STEZ-05-4 STEZ-07-4 Max Speed r/min STYZ A STEC c-0-1 (fan packages 0 & 1) B STEC c-0-1 (fan package 2) Nom. current A Temperature range C See corresponding wiring diagram on pages

18 18 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-450 FAN DATA q v (m³/h) r/min % Δp s (Pa) db(a) ,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is m³/s. The fan is classified as NRVU-UVU. SOUND DATA Correction K oct (db) in octave band mid-frequency (Hz) Fan code Sound path Min r/min Max r/min Surroundings Surroundings STEC-450 Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

19 Roofmaster STEC non-insulated version - Technical Catalogue 19 TECHNICAL DATA - STEC-450 DIMENSIONS AND WEIGHT Ø Weight: 36 kg Roof free outlet area: m 2 Mounting frame (included in delivery). PRODUCT CODE Roof Fan Size (a) Motor type (bbb) 3 = 3-phase motor Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Construction (d) 0 = standard Generation (e) STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Flat roof socket Flexible connecton Adapter plate Back draught shutter Inlet sound attenuator Potentiometer Nom. power kw STEC WIRING Supply voltage 3~ VAC 50/60 Hz BOGA-05-1-c-2 STEZ-01-5 STEZ-02-5 STEZ-04-5 STEZ-05-5 STEZ-07-5 Max Speed r/min STYZ A STEC c-0-1 (fan packages 0 & 1) B STEC c-0-1 (fan package 2) Nom. current A Temperature range C See corresponding wiring diagram on pages

20 20 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-500 FAN DATA q v (m³/h) r/min % Δp s (Pa) db(a) ,5 1 1,5 2 2,5 3 q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is m³/s. The fan is classified as NRVU-UVU. SOUND DATA Correction K oct (db) in octave band mid-frequency (Hz) Fan code Sound path Min r/min Max r/min Surroundings Surroundings STEC-500 Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

21 Roofmaster STEC non-insulated version - Technical Catalogue 21 TECHNICAL DATA - STEC-500 DIMENSIONS AND WEIGHT Ø Weight: 56 kg Roof free outlet area: m 2 Mounting frame (included in delivery). PRODUCT CODE Roof Fan Size (a) Motor type (bbb) 3 = 3-phase motor Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Construction (d) 0 = standard Generation (e) STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Flat roof socket Flexible connecton Adapter plate Back draught shutter Inlet sound attenuator Potentiometer Nom. power kw STEC WIRING Supply voltage 3~ VAC 50/60 Hz BOGA-06-1-c-2 STEZ-01-6 STEZ-02-6 STEZ-04-6 STEZ-05-6 STEZ-07-6 Max Speed r/min STYZ A STEC c-0-1 (fan packages 0 & 1) B STEC c-0-1 (fan package 2) Nom. current A Temperature range C See corresponding wiring diagram on pages

22 22 Roofmaster STEC non-insulated version - Technical Catalogue TECHNICAL DATA - STEC-630 FAN DATA q v (m³/h) r/min % 600 Δp s (Pa) db(a) q v (m 3 /s) Nominal flow rate according to Regulation 1253/2014 is 4.0 m³/s. The fan is classified as NRVU-UVU. SOUND DATA Correction K oct (db) in octave band mid-frequency (Hz) Fan code Sound path Min r/min Max r/min Surroundings Surroundings STEC-630 Inlet duct Inlet duct For information how to calculate sound data, sound pressure level and remote attenuation, see page 7.

23 Roofmaster STEC non-insulated version - Technical Catalogue 23 TECHNICAL DATA - STEC-630 DIMENSIONS AND WEIGHT Ø Weight: 82 kg Roof free outlet area: m 2 Mounting frame (included in delivery). PRODUCT CODE Roof Fan Size (a) Motor type (bbb) 3 = 3-phase motor Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Construction (d) 0 = standard Generation (e) STEC b-c-0-1 FAN AND MOTOR DATA Fan code ACCESSORIES Roof curb Flat roof socket Flexible connecton Adapter plate Back draught shutter Inlet sound attenuator Potentiometer Nom. power kw STEC WIRING Supply voltage 3~ VAC 50/60 Hz BOGA-07-1-c-2 STEZ-01-7 STEZ-02-7 STEZ-04-7 STEZ-05-7 STEZ-07-7 Max Speed r/min STYZ A STEC c-0-1 (fan packages 0 & 1) B STEC c-0-1 (fan package 2) Nom. current A Temperature range C See corresponding wiring diagram on pages

24 24 Roofmaster STEC non-insulated version - Technical Catalogue ACCESSORIES INCLUDED IN FAN PACKAGES SAFE - SAFETY SWITCH The safety isolation switch has been tested according to IEC It can be ordered and supplied as a part of the roof fan, not wired. The cable is not included in the delivery. See corresponding wiring diagram on pages Please see the fan ordering codes. EC CONTROLLER With a speed controller it is possible to get a single-speed or a two-speed operation. The relay output provides with alarm or running indication that can be selected by the DIP switch. Speed can also be controlled by 0-10 V via BMS (Building Management System). The EC controller can be ordered and supplied as a part of the roof fan, connected to cable. It is not available for size 190. Please see the fan ordering codes. Internal cabling is carried out at the factory. Information for the user is available in the installation manual. Modbus RTU communication with EC motor is still possible in fan sizes

25 Roofmaster STEC non-insulated version - Technical Catalogue 25 ACCESSORIES TO BE ORDERED SEPARATELY Ø B E C C / 1250 A Size 07 (for STEC-630) F D Height of the duct connection: 60 mm Ø160 Size 005 (for STEC-190) G Sizes (for STEC ) BOGA - ROOF CURB WITH INSULATION EI30 The BOGA consists of a sheet metal duct, insulated inside with 50 mm thick mineral wool mat. The insulation is backed with perforated sheet metal. The roof curb is equipped with two cable glands and one built-in conduit, which can accommodate two cables for electrical connection to the roof fan. Adjustable mounting brackets, which can be set to suit the pitch of the roof, are fitted to the outside of the roof curb. There are shutter plates located inside the roof curb. Roof fan can be installed on the roof curb using the mounting frame that is included in the roof fan delivery as standard. The roof curb is made of aluminum and zinc coated sheet metal. DIMENSIONS AND WEIGHT Roof curb, EI30 Fan size (aa) 005, 01, 02, 03, 04, 05, 06, 07 Back draught shutter (b) 1 = with shutter Height and insulation class (c) 1 = 980 mm, EI30, 50 mm insulation 2 = 1230 mm, EI30, 50 mm insulation Generation (d) 2 BOGA-aa-1-c-2 Model A (c = 1) A (c = 2) B C D E F G W1 (kg) W2 (kg) BOGA-01-1-c BOGA-02-1-c BOGA-03-1-c BOGA-04-1-c BOGA-05-1-c BOGA-06-1-c BOGA-07-1-c ) ) See separate illustration for size 630. W1 = Weight in kg for A (c = 1) W2 = Weight in kg for A (c = 2)

26 26 Roofmaster STEC non-insulated version - Technical Catalogue ACCESSORIES TO BE ORDERED SEPARATELY BOGA SOUND ATTENUATION SOUND ATTENUATION WHEN USING BOGA EI30, L = 980 Model Octave band mid frequency (Hz) BOGA BOGA BOGA BOGA BOGA BOGA BOGA SOUND ATTENUATION WHEN USING BOGA EI30, L = 1230 Model Octave band mid frequency (Hz) BOGA BOGA BOGA BOGA BOGA BOGA BOGA FLAT ROOF SOCKET STEZ-01 The roof socket STEZ-01 is made of corrosion resistant fibre glass. It is designed for mounting on flat roofs or roofs with a maximum pitch of 15. For saddle roofs a BOGA roof duct is available. The roof socket is equipped with a connection flange according to DIN , part 1. The roof is secured to the flat roof socket by means of 4 screws. z x d ØD1 ØD Model D D1 B B1 H H1 z x d Weight (kg) STEZ x7 4.5 STEZ x7 4.5 STEZ x STEZ x STEZ x STEZ x STEZ x B B1 H1 H

27 Roofmaster STEC non-insulated version - Technical Catalogue 27 ACCESSORIES TO BE ORDERED SEPARATELY FLEXIBLE CONNECTION STEZ-02 The flexible connection STEZ-02 is used to disconnect the fan from the ductwork. The flanges are according to DIN , part 1 z x d ØD1 Model D D1 D2 H z x d Weight (kg) STEZ x7 0.7 STEZ x7 2.0 STEZ x STEZ x STEZ x STEZ x STEZ x H ØD2 ØD STEZ-04 - MOUNTING PLATE To be used under the BOGA roof curb to enable a circular duct connection. STEZ-04 Mounting plate can be used with BOGA EI30 and inlet sound attenuator STEZ-07 but not together with BOGA EI120. ØD1 ØD Model ØD ØD1 B z x d Weight, kg STEZ x M8 2.2 STEZ x M8 2.2 STEZ x M8 3.6 STEZ x M8 4.6 STEZ x M8 6.1 STEZ x M8 9.5 STEZ x M z x d B BACK DRAUGHT SHUTTER STEZ-05 Back draught shutter prevents outdoor air to stream into the duct system while the roof fan is off. The back draught shutter is made of aluminium and zink coated sheet steel and the flanges are according to DIN , part 1. z x d ØD2 ØD1 Model D D1 D2 H z x d Weight (kg) STEZ x7 1.9 STEZ x7 3.4 STEZ x STEZ x STEZ x STEZ x STEZ x H ØD

28 28 Roofmaster STEC non-insulated version - Technical Catalogue ACCESSORIES TO BE ORDERED SEPARATELY STEZ-07 - INLET SOUND ATTENUATOR The STEZ-07 sound attenuator is used to attenuate the sound level to the duct on the inlet side. It is made of aluminium and zinc coated sheet metal. The baffles inside are made of mineral wool and they are covered by fibre class film. The inlet of the sound attenuator is square. If the sound attenuator is supposed to be connected to a circular duct, a separate mounting plate STEZ-04 can be used under the STEZ-07. Size 07 U E Model B B1 E U H Weight (kg) STEZ STEZ STEZ STEZ STEZ STEZ STEZ ) ) See separate illustration for size 7. B B1 H Sizes SOUND ATTENUATION WHEN USING STEZ-07 Model Octave band mid frequency (Hz) STEZ STEZ STEZ STEZ STEZ STEZ STEZ PRESSURE LOSS IN PA p t, Pa STEZ-07-1, STEZ-07-2 Q v, m 3 /s STEZ-07-3 STEZ STEZ-07-5 STEZ-07-6 STEZ STYZ POTENTIOMETER The potentiometer is used to control the speed of the EC-motor. The potentiometer needs a supply 10 VDC and gives a stepless output signal of 0-10 V DC. TECHNICAL FEATURES: Supply voltage: 10 VDC Output signal: 0-10 VDC Resistance: 10 kω (ohm) IP rating: IP 20

29 Roofmaster STEC non-insulated version - Technical Catalogue 29 WIRING DIAGRAM A (FOR FAN PACKAGES 0 & 1) STEC STEC STEC

30 30 Roofmaster STEC non-insulated version - Technical Catalogue WIRING DIAGRAM B (FOR FAN PACKAGE 2) STEC

31 Roofmaster STEC non-insulated version - Technical Catalogue 31 PRODUCT AND ACCESSORY CODES PRODUCT CODE Roof Fan STEC-aaa-bbb-c-d-1 ACCESSORIES Roof curb with insulation EI30 BOGA-aaa-b-c-d Fan size (a) 190, 225, 310, 355, 400, 450, 500, 630 Size (aaa) 005, 01, 02, 03, 04, 05, 06, 07 Motor type (bbb) 1 = 1-phase motor (sizes ) 3 = 3-phase motor (sizes ) Back draught shutter (b) 1 = with shutter Insulation (bbb) 1 = non-insulated version Accessory package (bbb) 0 = basic 1 = including safety switch 2 = including safety switch and EC controller Not available for size 190 Height and insulation class (c) 1 = 980 mm, EI30, 50 mm insulation 2 = 1230 mm, EI30, 50 mm insulation Generation (d) 2 Flat roof socket STEZ-01-b Material (c) 1 = painted galvanised sheet metal, black 2 = Al/Zn coated sheet metal Size (a) 1, 2, 3, 4, 5, 6, 7 Construction (d) 0 = standard Generation (e) Flexible connection Size (a) 1, 2, 3, 4, 5, 6, 7 STEZ-02-b Mounting plate STEZ-04-b Size (a) 1, 2, 3, 4, 5, 6, 7 Back draught shutter STEZ-05-b Size (a) 1, 2, 3, 4, 5, 6, 7 Inlet sound attenuator STEZ-07-b Size (b) 1, 2, 3, 4, 5, 6, 7 Potentiometer STYZ

32 FG_DC_10076GB_Roofmaster STEC non insulated_te_ _r0 Copyright 2017 FläktGroup FläktGroup is the European market leader for smart and energy efficient Indoor Air and Critical Air solutions to support every application area. We offer our customers innovative technologies, high quality and outstanding performance supported by more than a century of accumulated industry experience. The widest product range in the market, and strong market presence in 65 countries worldwide, guarantee that we are always by your side, ready to deliver Excellence in Solutions. STEC PRODUCT FUNCTIONS BY FLÄKTGROUP Air Treatment Air Movement Air Diffusion Air Distribution Air Filtration Air Management Air Conditioning & Heating Controls Service» Learn more on or contact one of our offices ROOFMASTER STEC

ROOF FAN ROOFMASTER STEC

ROOF FAN ROOFMASTER STEC AIR COMFORT AIR MOVEMENT ROOF FANS ROOF FAN ROOFMASTER STEC INSULATED VERSION» TECHNICAL CATALOGUE 2 STEC Roofmaster - Technical Catalogue CONTENTS GENERAL DESCRIPTION Application/specification... 3 Features...

More information

ROOFMASTER STEF-ATEX ROOF FAN

ROOFMASTER STEF-ATEX ROOF FAN Air Comfort Air movement Roof fans ROOFMASTER STEF-ATEX ROOF FAN» Technical CATALOGuE 2 STEF-ATEX Roofmaster - Technical Catalogue Contents General description Application/specification... 3 Features...

More information

ROOFMASTER STEF ROOF FAN

ROOFMASTER STEF ROOF FAN Air Comfort Air movement Roof fans ROOFMASTER STEF ROOF FAN» Technical CATALOGuE Contents ROOFMASTER STEF...3 Performance Data...4 Performance Table...6 General description...8 Fan Chart-explanation and

More information

ROOFMASTER STEF-HT ROOF FAN

ROOFMASTER STEF-HT ROOF FAN fire safety Air movement Roof Fans ROOFMASTER STEF-HT ROOF FAN» Technical CATALOGuE Contents ROOFMASTER STEF-HT...3 Performance Data...4 Performance Table...5 General description...6 Fan Chart-explanation

More information

ROOFMASTER STEF-HT ROOF FAN

ROOFMASTER STEF-HT ROOF FAN fire safety Air movement Roof Fans ROOFMASTER STEF-HT ROOF FAN» Technical CATALOGuE Contents ROOFMASTER STEF-HT...3 Performance Data...4 Performance Table...5 General description...6 Fan Chart-explanation

More information

Kitchen exhaust fan GLEB

Kitchen exhaust fan GLEB Kitchen exhaust fan GLEB Contents General description...3 Quick selection...5 Design description...5 Material and design...6 Fan impeller...6 Motor...6...6 Quality...6 Specification...6 Technical data

More information

CENTRIFLOW 3D WITH AC MOTOR >> Technical catalogue

CENTRIFLOW 3D WITH AC MOTOR >> Technical catalogue CENTRIFLOW 3D plug fan WITH AC MOTOR >> Technical catalogue air comfort Centriflow 3D 2 GMEB CentriFlow 3D - Technical Catalogue Contents GENERAL Description and survey chart Application... 3 General Survey

More information

CENTRIFLOW 3D WITH AC MOTOR >> Technical catalouge

CENTRIFLOW 3D WITH AC MOTOR >> Technical catalouge CENTRIFLOW 3D plug fan WITH AC MOTOR >> Technical catalouge air comfort Centriflow 3D 2 GMEB CentriFlow 3D - Technical Catalouge Contents GENERAL Description and survey chart Application... 3 General Survey

More information

External grilles USAV, USVN, USSV and SVN TECHNICAL DATA

External grilles USAV, USVN, USSV and SVN TECHNICAL DATA External grilles, U, and TECHNICAL DATA 2 External grilles, U, and U External grilles are used as covering grilles in air supply and exhaust openings. and U are moulded of aluminium. and are deep drawn

More information

Wall diffuser SVQC / Supply air unit SVQC + ATVA TECHNICAL DATA

Wall diffuser SVQC / Supply air unit SVQC + ATVA TECHNICAL DATA Wall diffuser SVQC / Supply air unit SVQC + ATVA TECHNICAL DATA Wall diffuser SVQC / Supply air unit SVQC + ATVA SVQC is a quiet supply air diffuser intended for mounting on a wall. The device is particularly

More information

CENTRIFLOW 3D WITH EC MOTOR >> Technical catalogue

CENTRIFLOW 3D WITH EC MOTOR >> Technical catalogue CENTRIFLOW 3D Plug Fan WITH EC MOTOR >> Technical catalogue air comfort CentriFlow 3D 2 GMEC CentriFlow 3D - Technical Catalogue Contents GENERL Description and survey chart pplication... 3 General Survey

More information

Conical diffuser KHAA TECHNICAL DATA

Conical diffuser KHAA TECHNICAL DATA Conical diffuser AA TECNICAL DATA Conical diffuser AA Supply conical diffuser AA is recommended to be used either in commercial application buildings such as shops or industrial buildings with a large

More information

Fire damper FK120/FK90 TECHNICAL DATA

Fire damper FK120/FK90 TECHNICAL DATA Fire damper FK120/FK90 TECHNICAL DATA 2 Fire damper FK120/FK90 Figure 1 ER1 Figure 2 ER3 The rectangular fire damper FK120/FK90 is available both as motorized and with fuse. The damper casing is manufactured

More information

Centriflow Plus EC. Technical data

Centriflow Plus EC. Technical data Technical data Centriflow Plus CTLOGUE Contents General description...3 General survey chart...4 Design description Fan Impeller...5 Inlet cone and supporting frame...5 EC motor...5 ir flow sensor...6

More information

Fire dampers ETCE and ETCS TECHNICAL DATA

Fire dampers ETCE and ETCS TECHNICAL DATA Fire dampers ETCE and ETCS TECHNICAL DATA 2 Fire dampers ETCE and ETCS Veloduct ETCE fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 13662.

More information

RECTANGULAR VAV DAMPER TECHNICAL CATALOGUE

RECTANGULAR VAV DAMPER TECHNICAL CATALOGUE RECTANGULAR VAV DAPER ERVA TECHNICAL CATALOGUE Rectangular VAV damper ERVA - Technical catalogue 2 KEY FEATURES Variable airflow Constant airflow Real-time airflow measurement with FläktGroup compact controller

More information

DTV, DTH and VVR Roof- and wall fans DTV Roof fan DTH Roof fan VVR Wall fan

DTV, DTH and VVR Roof- and wall fans DTV Roof fan DTH Roof fan VVR Wall fan Product information - Version 3 DTV, DTH and VVR Roof- and wall fans DTV Roof fan DTH Roof fan VVR Wall fan Overskrift placering Table of contents Choice of motor... 4 DTV roof fans... 5 - Technical specifications

More information

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE FIRE SAFETY AIR MANAGEMENT FIRE DAMPERS ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE 2 ETPR-E-1 Fire damper Technical catalogue Fire and smoke damper ETPR-E-1 is used as a closing device for preventing the

More information

Plenum box ATTD TECHNICAL DATA

Plenum box ATTD TECHNICAL DATA Plenum box ATTD TECNICAL DATA 2 Plenum box ATTD Marine version ATTD is a plenum box for all types of air diffusers and is applicable for supply and exhaust air alike. The diffuser connection collar is

More information

CTVK Supply air diffuser

CTVK Supply air diffuser CTVK Supply air diffuser The CTVK is a very quiet supply air diffuser designed for wall mounting. The diffuser is suitable for use in small premises, such as offices, houses and hotel rooms. The air discharged

More information

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig CENTRIFUGAL FANS HV VAC &

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig CENTRIFUGAL FANS HV VAC & hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE CENTRIFUGAL FANS ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 73-16 CENTRIFUGAL FANS CONTENT PAGE 1. CENTRIFUGAL

More information

VKAP 100 MD/LD 3.0 Product version Motor power level (M higher power level, L lower power level) Diameter Product name. Guard grille.

VKAP 100 MD/LD 3.0 Product version Motor power level (M higher power level, L lower power level) Diameter Product name. Guard grille. Application Features Power supply Circular duct fans are used in low-to medium-pressure ducted systems. Fans are suitable for air supply or exhaust of residential buildings, warehouses, bathrooms, lavatories,

More information

Sky Wing. Contents. Power Roof Ventilator

Sky Wing. Contents. Power Roof Ventilator Power Roof Ventilator Contents Quick Guide... 14 General, Advantages of the... 15 Specification... 16 Technical Description of the... 17 LTSA Roof duct... 19 Electrical and Control Equipment, Control Functions...

More information

The Straight Way. Rectangular Cabinet Fan. Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans

The Straight Way. Rectangular Cabinet Fan. Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans The Straight Way Rectangular Cabinet Fan Systemair India Pvt. Ltd. certifies that the Rectangular

More information

BOX BLB Centrifugal Box Fan

BOX BLB Centrifugal Box Fan Centrifugal Box Fan Select models available for next day delivery Product Overview 3 sizes from 260mm to 400mm Air volume flow rates up to 0.751m³/s Static pressures up to 733 Pa Suitable for operating

More information

MIRUVENT. Power roof ventilator with 27 different airflow variants up to 24,000 m 3 /h

MIRUVENT. Power roof ventilator with 27 different airflow variants up to 24,000 m 3 /h MIRUENT Power roof ventilator with 27 different airflow variants up to 24, m 3 /h General MIRUENT is a power roof ventilator with a casing made of corrosion-resistant aluminium The power roof ventilator

More information

Regulation and shut-off damper SPB and SPC

Regulation and shut-off damper SPB and SPC SPB / SP -type multi leaf damper is a robust and reliable regulation and shut-off device to be used for different purposes in air handling systems. SPB SP.01.13 Area of application Multi leaf dampers are

More information

Device can be connected to pull air directly from ventilated room or air duct system. Not suitable for polluted air or volatile and explosive gases.

Device can be connected to pull air directly from ventilated room or air duct system. Not suitable for polluted air or volatile and explosive gases. VSV VSVI Features Power supply Temperature range Sizes Construction Installation Speed control options 9 sizes; Airflow up to 5300 m 3 /h; Vertical exhaust; Backward-curved plastic or galvanized steel

More information

MAJAX-2 GENERAL SPECIFICATION

MAJAX-2 GENERAL SPECIFICATION MAJAX-2 GENERAL SPECIFICATION Majax-2 axial flow fans are manufactured in diameters ranging from 315mm to 2000mm (available in 2250mm on request), and incorporate manually adjustable pitch aluminium bladed

More information

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

VAV terminal units. Type TVM. For dual duct systems PD TVM 1 X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings

More information

STI Supply air valve. Specifications. Quick Selection. Product code example Supply air valve STI-160-C

STI Supply air valve. Specifications. Quick Selection. Product code example Supply air valve STI-160-C STI Supply air valve STI supply air valve for wall mounting covers a wide air volume area from 5 to 70 l/s, for duct sizes 100-200 mm. The valve can be quickly installed directly into the duct without

More information

BPF. Centrifugal Plug Fans

BPF. Centrifugal Plug Fans BPF Centrifugal Plug Fans Introduction INTRODUCTION Plug Fans S&P - THE COMPANY Soler & Palau was founded in 1951 in Ripoll (Spain) and since this date has become one of the world s leading companies engaged

More information

OPTIVENT Housing HVSA, HVSL

OPTIVENT Housing HVSA, HVSL OPTIVENT Housing HVSA, HVSL Key features Variable air flow Constant air flow Real time air flow display with compact controller 227VM The HVSA and the HVSL are apartment-specific room ventilation regulators

More information

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1 X X testregistrierung CAV controllers Type For the precise control of normal and high constant volume flows Rectangular self-powered volume flow controllers for the control of supply air or extract air

More information

CODE MODEL 1RC9020 REC PRO 90 S RC9021 REC PRO 90 S RC9022 REC PRO 90 S RC9023 REC PRO 90 S

CODE MODEL 1RC9020 REC PRO 90 S RC9021 REC PRO 90 S RC9022 REC PRO 90 S RC9023 REC PRO 90 S REC PRO 9S High efficiency Heat Recovery Units Non residential applications EFFICIENCY 9% Comply with ErP Directive 125/29/CE and EU Regulation 1253/214. Classification: Non Residential Ventilation Unit

More information

ROOF MOUNTED AXIAL FLOW FANS HCTB / HCTT Series

ROOF MOUNTED AXIAL FLOW FANS HCTB / HCTT Series asy to install Supports to facilitate installation in the roof. XTRACTION (type B) SUPPLY (type A) High quality steel sleeve nsuring the long life of the fan. Range of axial roof fans with horizontal air

More information

Circular Box Fans - DAISHO EC Range DAISHO EC 125. Features. Electrical Supply. Product Code. Sizes 125, 150, 200, 250, 315, 450, 630 and 1000.

Circular Box Fans - DAISHO EC Range DAISHO EC 125. Features. Electrical Supply. Product Code. Sizes 125, 150, 200, 250, 315, 450, 630 and 1000. Circular Box Fans - DAISHO EC Range Features 125mm to 1mm Air flow 1,25 m 3 /h (3.5m 3 /s) Static pressures up to 125 Pa Maximum temperature range 6ºC Suitable for variable or constant pressure systems

More information

HIGH-POWERED VENTILATORS

HIGH-POWERED VENTILATORS HIGH-POWERED VENTILATORS WITH ROOF FANS 400ºC/2h The THT/HATCH series was designed using high-powered ventilator technology for smoke extraction in the event of a fire, and is equipped with THT series

More information

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/ 6/5/EN/6 Circular Silencer Rigid and flexible construction Type CA CB CF CS TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn

More information

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1 X X testregistrierung Circular silencers Type For the reduction of noise in circular ducts, galvanised sheet steel construction Circular silencers Type for the reduction of noise in the circular ducts

More information

BESB and BESF Box fans for extraction and air supply jobs BESB - backward curved vanes BESF - forward curved vanes

BESB and BESF Box fans for extraction and air supply jobs BESB - backward curved vanes BESF - forward curved vanes Product information - Version 4 BESB and BESF Box fans for extraction and air supply jobs BESB - backward curved vanes BESF - forward curved vanes Table of contents Economic considerations... 4 Choice

More information

Pressure control damper ERPA

Pressure control damper ERPA Key features Constant pressure Real-time pressure monitoring with FW compact controller Can be connected to Modbus Available in IPSUM compatible version ERPA is a rectangular pressure control damper for

More information

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM 1 Lmf Clima 216 FERRARO GROUP HPR Heat recovery units HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM from 7 to 23. m³/h Supporting structure in extruded aluminium profiles and curtain

More information

ErP POWERBOX EC FANS - ESTOC EC FEATURES ELECTRICAL SUPPLY TEMPERATURE RANGE SIZES FEATURES AND CONSTRUCTION PRODUCT CODE IMPELLER MOTOR

ErP POWERBOX EC FANS - ESTOC EC FEATURES ELECTRICAL SUPPLY TEMPERATURE RANGE SIZES FEATURES AND CONSTRUCTION PRODUCT CODE IMPELLER MOTOR 13 POWERBOX EC FANS - ESTOC EC FEATURES Sizes from 3 to 3 mm diameter Air flow up to.1 m 3 /s Static pressures up to Pa Controllable EC motors Multiple outlet orientations ELECTRICAL SUPPLY 22-2V/Hz/1f

More information

Thermo fans. Systemair range Systemair thermo fans are available in three different executions. The Multibox MUB-K ASF/KB. Flexible connection

Thermo fans. Systemair range Systemair thermo fans are available in three different executions. The Multibox MUB-K ASF/KB. Flexible connection General Systemair thermo fans have been developed for the use in exhaust air systems where media with increased temperatures have to be transported. The special design allows a reliable operation also

More information

FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA

FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA Fresh Breeze Fan-Filter Unit Range of Application... 3 Sizes... 3 Characteristics... 3 Fresh Breeze product line... 3 Areas of application... 3 Technical Data

More information

TSAT: Single inlet, belt-driven centrifugal fans fitted with electric motors. CJTSA: Ventilation units with a forward-curved impeller.

TSAT: Single inlet, belt-driven centrifugal fans fitted with electric motors. CJTSA: Ventilation units with a forward-curved impeller. TSA TSAT CJTSA TSA: Single inlet, belt-driven centrifugal fans with shaft outlet and forward-curved impeller. TSAT: Single inlet, belt-driven centrifugal fans fitted with electric motors, a set of pulleys

More information

In-line rectangular fans. Technical Catalogue

In-line rectangular fans. Technical Catalogue In-line rectangular fans Technical Catalogue Overview IN-LINE RECTANGULAR FANS IRB / IRBS IRB and IRBS are a compact series of centrifugal type exhaust and supply in-line duct fans for air conditioning

More information

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) X X testregistrierung CAV controllers Type Adjustment scale For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) Rectangular, mechanical self-powered

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K .1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1 X X testregistrierung CAV controllers Type For the precise control of constant volume flow rates Circular self-powered volume flow controllers for the control of supply air or extract air in constant air

More information

ACOUSTIC CABINET FANS CVAB / CVAT Series

ACOUSTIC CABINET FANS CVAB / CVAT Series Range of in-line cabinet fans, manufactured from galvanised steel sheet with double thickness side panels internally lined with 17 mm thickness of fireproof fibreglass acoustic insulation (M). All models

More information

Short casing. Long casing (L version) Commercial premises

Short casing. Long casing (L version) Commercial premises CYLINDRICAL CASED AXIAL FLOW FANS TGT Series Adjustable Pitch Fans Long casing (L version) Short casing A P P L I C A T I O N S Range of adjustable pitch cased axial flow fans. Casings formed from rolled

More information

Circular silencers. Type CS. For the reduction of noise in circular ducts, aluminium construction PD CS 1. 02/2017 DE/en

Circular silencers. Type CS. For the reduction of noise in circular ducts, aluminium construction PD CS 1. 02/2017 DE/en X X testregistrierung Circular silencers Type For the reduction of noise in circular ducts, aluminium construction Circular silencers, in rigid aluminium construction, for the reduction of noise in the

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

CVAB / CVAT Series ACOUSTIC CABINET FANS CVAB / CVAT. Acoustic cabinet fans. Backward curved centrifugal impellers.

CVAB / CVAT Series ACOUSTIC CABINET FANS CVAB / CVAT. Acoustic cabinet fans. Backward curved centrifugal impellers. ACOUSTIC CABINET FANS Series Range of in-line cabinet fans, manufactured from galvanised steel sheet with double thickness side panels internally lined with 17 mm thickness of fireproof fibreglass acoustic

More information

series Silencers

series Silencers series SK Silencers www.koolair.com Series SK 1 Silencers CONTENTS ASK-1 and ASK-2 Round Silencers Description 4 ASK-1 Overall Dimensions 5 ASK-2 Overall Dimensions 6 Selection Table and Weights 7 ASK-1

More information

ACOUSTIC CABINET FANS CVB / CVT Series

ACOUSTIC CABINET FANS CVB / CVT Series Cabinet fans manufactured from heavy gauge galvanised steel sheet and internally lined with melamine foam flame retardant acoustic insulation (M1). All models incorporate double inlet single phase direct-drive

More information

CRH RANGE - TECHNICAL DATA CENTRIFUGAL ROOF FANS

CRH RANGE - TECHNICAL DATA CENTRIFUGAL ROOF FANS ge 2 CENTRIFUGAL CRH RANGE - TECHNICAL ROOF DATA FANS FOR INDUSTRIAL / COMMERCIAL USE CRH - Horizontal Discharge CRV - Vertical Discharge CRL - Low Profile Uniclass L7534 Tel: +44 ()1494 522333 Fax: Vectaire

More information

Acoustic Twin Fans (ATQ)

Acoustic Twin Fans (ATQ) Acoustic Twin Fans (ATQ) Features and Benefits Available in sizes from 100 to 500mm dia 50mm Acoustically treated housing, Class O rated, self extinguishing, zero burn rate, resists ignition, no toxic

More information

IN-LINE CENTRIFUGAL DUCT FANS VT Series

IN-LINE CENTRIFUGAL DUCT FANS VT Series IN-LINE CENTRIFUGAL DUCT FANS VT Series DESCRIPTION The VT series of circular in-line duct centrifugal fans consists of model variations within nominal model sizes of,,,,, and mm respectively. The VT range

More information

Device can be connected to pull air directly from ventilated room or air duct system. Not suitable for polluted air or volatile and explosive gases.

Device can be connected to pull air directly from ventilated room or air duct system. Not suitable for polluted air or volatile and explosive gases. VSA 3. ROOF FAS Features Power supply Temperature range 4 sizes; Airflow up to 117 m 3 /h; Horizontal exhaust; Backward-curved impeller; ost-effective. 23V/5Hz/1f. From -4 up to 4/65. Sizes 19 S, 19, 22

More information

KSOF Fire damper valve

KSOF Fire damper valve KSOF Fire damper valve KSOF is developed for use as a fire damper valve in exhaust ventilation systems. Fire damper valve KSOF is CE marked based on product standard EN 156: and tested according to test

More information

TD-MIXVENT Series IN-LINE MIXED FLOW DUCT FANS TD-MIXVENT. In-Line duct fans

TD-MIXVENT Series IN-LINE MIXED FLOW DUCT FANS TD-MIXVENT. In-Line duct fans IN-LINE MIXED FLOW DUCT FANS Series Range of low profile in-line mixed flow duct fans manufactured in tough reinforced plastic (from 160 to 800 models) or with metal casing steel finished in a tough epoxy-polyester

More information

IN-LINE RECTANGULAR FANS IRB / IRBS IRB

IN-LINE RECTANGULAR FANS IRB / IRBS IRB IN-LINE RECTANGULAR FANS IRB / IRBS IRB IN-LINE RECTANGULAR FANS IRB / IRBS IRB and IRBS are a compact series of centrifugal type exhaust and supply in-line duct fans for air conditioning systems. They

More information

AXIAL FANS Catalogue CN0050C01 May 2008

AXIAL FANS Catalogue CN0050C01 May 2008 ADTA AXIAL FANS Catalogue CN0050C01 May 2008 ADTA AXIAL FANS Catalogue CN0050C01 May 2008 Construction Specifications Impellers: Breezax aerfoil blades are available in four types of material: Glass Reinforced

More information

Roof Extract Fans DV Ventilation Hoods DLH Smoke Extract Fans ER

Roof Extract Fans DV Ventilation Hoods DLH Smoke Extract Fans ER Roof Extract Fans DV Ventilation Hoods DLH Smoke Extract Fans ER Roof Extract Fans Ventilation Hoods Smoke Extract Fans DV DLH ER Summary... Seite Roof Extract Fans DV Product review... Summary data sheet...

More information

VKAP 100 MD/LD 3.0 Product version Motor power level (M higher power level, L lower power level) Diameter Product name. Guard grille.

VKAP 100 MD/LD 3.0 Product version Motor power level (M higher power level, L lower power level) Diameter Product name. Guard grille. VKAP 3. Features Power supply Temperature range Diameter - 1 mm to 315 mm; Airflow up to 137 m 3 /h; Easily mounted in any position; Backward-curved impeller; Low ambient temperatures; Cost-effective.

More information

NEW Slimpak EC Box Fan (SLPT EC)

NEW Slimpak EC Box Fan (SLPT EC) NEW Slimpak EC Box Fan (SLPT EC) Compact low profile design Duct Sizes 100 500mm Performance - Airflow 0.01 to 1.2m 3 /s, Pressure up to 650Pa Latest energy saving EC/DC motors Internal mounting IPX2 Manufactured

More information

Duct mounted fans. axial flow. Pacific HVAC Engineering Tel. Australia NZ

Duct mounted fans. axial flow. Pacific HVAC Engineering Tel. Australia NZ Duct mounted fans axial flow Pacific HVAC Engineering 215 www.pacifichvac.com Tel. Australia 13 733 833 NZ 8 1 326 6 5 4 3 2 1 5 1 15 2 7 6 5 4 3 2 1 3 2.5 2 1.5 1.5 1 15.5 1 1.5 2 2.5 3 3.5 Volume m 3

More information

THT/HATCH THT/HATCH. Order code THT/HATCH 40 2T 1 N 1 G

THT/HATCH THT/HATCH. Order code THT/HATCH 40 2T 1 N 1 G THT/HATCH High-powered ventilators with motorised opening and equipped with a roof fan, for smoke extraction in the event of a fire, 400ºC/2h High-powered ventilators with roof fan and motorised opening.

More information

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1 X X testregistrierung CAV controllers Type Adjustment scale ATEX-Zertifizierung For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) Circular, mechanical self-powered

More information

KSOM Control exhaust valve

KSOM Control exhaust valve KSOM Control exhaust valve KSOM is ideal for rooms which require forced exhaust air flow. KSOM consists of exhaust valve, control motor and controller card, which are installed in the valve cone. KSOM

More information

400ºC/2h centrifugal roof fans with horizontal or vertical air outlet CHT 200 4T BS. Installed capacity

400ºC/2h centrifugal roof fans with horizontal or vertical air outlet CHT 200 4T BS. Installed capacity 400ºC/2h centrifugal roof fans with horizontal or vertical air outlet : 400ºC/2h centrifugal roof fans with horizontal air outlet, hood in aluminium : 400ºC/2h centrifugal roof fans with vertical air outlet,

More information

CJBX CJBX/AL. Options. Order code CJBX 15/15 4. Technical characteristics

CJBX CJBX/AL. Options. Order code CJBX 15/15 4. Technical characteristics CJBX CJBX/AL CJBX: Belt-driven acoustically-insulated ventilation units. CJBX/AL: Belt-driven ventilation units with aluminium profiles and prefinished sheet steel and acoustic insulation. CJBX Options

More information

KF T120. Kitchen fans. Wentylatory kuchenne KITCHEN FANS

KF T120. Kitchen fans. Wentylatory kuchenne KITCHEN FANS KF T120 Kitchen fans Wentylatory kuchenne Kitchen exhaust units are used for installation where the air is slightly greasy or the air temperature is up to 120 C. Unit has a swing-out door for easy inspection

More information

Fire damper ETPR. Specifications. Product code example Fire damper ETPR

Fire damper ETPR. Specifications. Product code example Fire damper ETPR Fire damper ETPR ETPR fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 1366-2. ETPR meets the requirements of fire class EI 60 S / EI 90 S.

More information

CSXRT: Single inlet, belt-driven centrifugal fans fitted with electric motors. CJSXR: Ventilation units with a backward-curved impeller

CSXRT: Single inlet, belt-driven centrifugal fans fitted with electric motors. CJSXR: Ventilation units with a backward-curved impeller CSXR CSXRT CJSXR CSXR: Belt-driven single inlet centrifugal fans with shaft outlet and backward-curved impeller CSXRT: Belt-driven single inlet centrifugal fans fitted with electric motors, a set of pulleys

More information

VARYCONTROL VAV Dual Duct Terminal Boxes

VARYCONTROL VAV Dual Duct Terminal Boxes 5/2/B/3 VARYCONTROL VAV Dual Duct Terminal Boxes for variable volume systems Type TVM Trox (U.K.) Ltd Caxton Way GB-Thetford Norfolk IP24 3SQ Telephone +44 (0)1842 754545 Telefax +44 (0)1842 7051 www.troxuk.co.uk

More information

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm. Fire damper pl-30 General characteristics Application Fire dampers prevent fire and smoke from spreading through ventilation ducts in buildings. The dampers are intended for use inside buildings and are

More information

Powerful centrifugal fans for universal use: The product ranges TEM and REM

Powerful centrifugal fans for universal use: The product ranges TEM and REM Powerful centrifugal fans for universal use: The product ranges TEM and REM The fan ranges TEM and REM offered by Nicotra Gebhardt do present a large fan programme of single inlet centrifugal fans which

More information

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1. X X testregistrierung Shut-off dampers Type ATEX-compliant parts and units For low-leakage shut-off of volume flows in potentially explosive atmospheres (ATEX) Circular shut-off dampers for shutting off

More information

CENTRIFUGAL IN-LINE FANS VENT Series

CENTRIFUGAL IN-LINE FANS VENT Series Range of in-line duct centrifugal fans, manufactured from high grade corrosion resistant pressed galvanised steel and supplied as standard with a prewired wiring junction box and a robust mounting foot.

More information

Sound attenuators. Sound attenuators, Sound attenuating louvres. Sound attenuators. Rectangular sound attenuators DZ-2, DZ-3

Sound attenuators. Sound attenuators, Sound attenuating louvres. Sound attenuators. Rectangular sound attenuators DZ-2, DZ-3 , Sound attenuating louvres Rectangular sound attenuators DZ-2, DZ-3 Application are designed to attenuate noises of fans and air-conditioning devices in ventilation and air-conditioning installations.

More information

Bevent Rasch BSK Fire /04/2017

Bevent Rasch BSK Fire /04/2017 Bevent Rasch - Fire - BSK120 10/04/2017 Rectangular Fire resistance class /S Sizes from 200 x 200 mm to 1200 x 1000 mm Prefitted safety actuator 24V or 230V Available in MagiCAD CE-marked building product

More information

GigaBox centrifugal fans Product specific information

GigaBox centrifugal fans Product specific information GigaBox centrifugal fans Product specific information GigaBox and accessories Wall bracket GB-WK (ccessories) Outdoor cover hood GB-WSD (ccessories) Included in delivery: a) Flexible sleeve b) Outlet spigot,

More information

MegaBox Product-specific information

MegaBox Product-specific information MegaBox Product-specific information Application Noise-encapsulating centrifugal fans with retractable motor impeller unit and motor located outside the air flow Suitable for rough operating conditions

More information

VAV terminal units. Type TVZ. For supply air systems with demanding acoustic requirements PD TVZ 1

VAV terminal units. Type TVZ. For supply air systems with demanding acoustic requirements PD TVZ 1 X X testregistrierung VAV terminal units Type Easy controller Compact controller Rectangular connection on the room end Circular connection on the fan end For supply air systems with demanding acoustic

More information

Explanation of AR Series Ventilator Products. Fan type code D S AR AE

Explanation of AR Series Ventilator Products. Fan type code D S AR AE Series Axial Fan Explanation of Series Ventilator Products Fan type code 450-7 /26 D -2 F400 Smoke Extract Fan 400 C, 300 C Number of Poles D S Three Phase Single Phase AE AE Features and construction

More information

CENTRIFLOW 3D PLUG FAN WITH PM-MOTOR TECHNICAL CATALOGUE

CENTRIFLOW 3D PLUG FAN WITH PM-MOTOR TECHNICAL CATALOGUE CENTRIFLOW 3D PLUG FN WITH PM-MOTOR TECHNICL CTLOGUE 2 CentriFlow 3D GMPM - Technical Catalogue CONTENTS GENERL DESCRIPTION ND SURVEY CHRT pplication... 3 General Survey Chart... 3 Quality and environment...4

More information

GV In Line Circular Duct Fan Circular Ducting High/Low Speed Performance

GV In Line Circular Duct Fan Circular Ducting High/Low Speed Performance GV In Line Circular Duct Fan Circular Ducting High/Low Speed Performance GENERAL VENTILATOR A quality product suitable for general residential application. proprietary made and compact design fan is designed

More information

VENT Series CENTRIFUGAL IN-LINE FANS VENT. In-Line duct fans. Mounting foot

VENT Series CENTRIFUGAL IN-LINE FANS VENT. In-Line duct fans. Mounting foot CENTRIFUGAL IN-LINE FANS Series Range of in-line duct centrifugal fans, manufactured from high grade corrosion resistant pressed galvanised steel and supplied as standard with a pre-wired wiring junction

More information

Duct Fans - ESTOC EC Range. Estoc EC Features. Electrical Supply. Sizes 355, 400, 450, 500, 560 and 630. Product Code

Duct Fans - ESTOC EC Range. Estoc EC Features. Electrical Supply. Sizes 355, 400, 450, 500, 560 and 630. Product Code Tubes and ox Fans Duct Fans - ESTOC EC Range Features Sizes from 55 to 6 mm diameter ir flow 19, m /h (4. m /s) Static pressures up to 84 Pa Maximum temperature up to 6 C Controllable external rotor motors

More information

Square Duct Fans - ESTOC Range. Estoc Features. Electrical Supply. Product Code. Sizes 355, 400, 450, 500, 560, 630 and 710.

Square Duct Fans - ESTOC Range. Estoc Features. Electrical Supply. Product Code. Sizes 355, 400, 450, 500, 560, 630 and 710. Square Duct Fans - ESTOC Range Features Sizes from 355 to 71 mm diameter Air flow 1,9 m 3 /h (5.2 m 3 /s) Static pressures up to 115 Pa Maximum temperature from +4 C to +7` C (depending on the model) Adjustable

More information

Type MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE

Type MSA. Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE Homepage > Products > Sound attenuators > Splitter sound attenuators > Type MSA Type MSA Splitter thickness 200 mm FOR INCREASED INSERTION LOSS AND BROADBAND ATTENUATION EVEN IN THE LOW FREQUENCY RANGE

More information

AC Commercial Fans Edition. ErP ready

AC Commercial Fans Edition. ErP ready AC Commercial Fans 213 Edition ErP ready AC Commercial Fans Axair Fans UK Ltd / 1782 34943 About Axair Fans UK Axair is an independent industrial fan manufacturer and distributor. What we offer : Application

More information

Type CS FOR THE REDUCTION OF NOISE IN CIRCULAR DUCTS, ALUMINIUM CONSTRUCTION

Type CS FOR THE REDUCTION OF NOISE IN CIRCULAR DUCTS, ALUMINIUM CONSTRUCTION Homepage > Products > Sound attenuators > Circular silencers > Type CS Type CS FOR THE REDUCTION OF NOISE IN CIRCULAR DUCTS, ALUMINIUM CONSTRUCTION Circular silencers, in rigid aluminium construction,

More information

Powerful centrifugal fans for universal use: The product ranges TEM and REM

Powerful centrifugal fans for universal use: The product ranges TEM and REM Powerful centrifugal fans for universal use: The product ranges TEM and REM The fan ranges TEM and REM offered by Nicotra Gebhardt do present a large fan programme of single inlet centrifugal fans which

More information

HIGH TEMPERATURE TWIN SQUIF FANS

HIGH TEMPERATURE TWIN SQUIF FANS HIGH TEMPERATURE FANS HIGH TEMPERATURE FOR SMOKE EXTRACT CERTIFIED TO EN12101-3-2002. 374 029 2085 8200 BENEFITS QUIET AND POWERFUL SOLUTIONS High performance centrifugal motor/impeller combination providing

More information

ESAS Smoke control damper

ESAS Smoke control damper ESAS Smoke control damper 1 Rectangular smoke control damper ESAS is specially designed to use in single fire compartment applications as a closing or as an opening damper for smoke extract purposes. ESAS

More information