Q196 Generation Interconnection
|
|
- Clement Charles
- 6 years ago
- Views:
Transcription
1 Q196 Generation Interconnection Interconnection Facilities Study Results APS Contract No By Arizona Public Service Company Transmission Planning April 22, 2015 [Version 1]
2 Q196 FACILITIES STUDY - TECHNICAL REVIEW TABLE OF CONTENTS Contents 1. Introduction Q196 Interconnection Facilities Cost Estimates Summary of Construction Time Estimates at the POI Request For Transmission Service Power Factor Requirements Reactive Support Page i
3 ACC ACSS ANPP APS ATC CAISO CAWCD CCVT COD CSP CT EPE ER ERIS FaS FERC FeS GT IC IID IR LADWP LGIA NEC NERC NR NRIS NTUA OASIS OATT PG&E PNM POI PPA PSLF/PSDS/SCSC PST PV RAS RFP SCE SDG&E SIS SLG fault SPS SRP SSVEC SVC SVD SWTC TEP TPIF WAPA WECC List of Acronyms Arizona Corporation Commission Aluminum Conductor Steel Supported Arizona Nuclear Power Project Arizona Public Service Available Transfer Capability California Independent System Operator Corporation Central Arizona Water Conservation District Coupling Capacitor Voltage Transformer Commercial Operation Date Concentrated Solar Power Combustion Turbine or Current Transformer El Paso Electric Energy Resource Energy Resource Interconnection Service Facilities Study Federal Energy Regulatory Commission Feasibility Study Gas Turbine Interconnection Imperial Irrigation District Interconnection Request Los Angeles Department of Water and Power Large Generator Interconnection Agreement Navopache Electric Cooperative North American Electric Reliability Corporation Network Resource Network Resource Interconnection Service Navajo Tribal Utility Authority Open Access Same Time Information System Open Access Transmission Tariff Pacific Gas & Electric Public Service Company of New Mexico Point Of Interconnection Purchase Power Agreement Positive Sequence Load Flow/Positive Sequence Dynamic Simulation/Short-Circuit Saturation Curve Phase-Shifting Transformer Photovoltaic Remedial Action Scheme (also known as SPS) Request for Proposal Southern California Edison Company San Diego Gas & Electric Company System Impact Study Single Line-to-Ground fault Special Protection System (also known as RAS) Salt River Project Sulphur Springs Valley Electric Cooperative, Inc. Static VAR Compensator Static VAR Device Southwest Transmission Cooperative Tucson Electric Power Transmission Provider s Interconnection Facilities Western Area Power Administration Western Electricity Coordinating Council Page ii
4 1. Introduction Arizona Public Service Company (APS) performed this Generator Interconnection Facilities Study (FaS) in response to a 161 MW hybrid wind/solar photo-voltaic interconnection request by the Interconnection (IC). The IC originally submitted a MW interconnection request that was reduced to 161 MW, with 101 MW of wind production and 60 MW for Solar. The is listed in APS s Active Generator Interconnection Queue as queue number 196 (Q196). The purpose of the study is to provide cost and construction schedule estimates for the facilities needed to interconnect the IC s proposed 161 MW hybrid wind/solar photo-voltaic generation facility into the jointly owned Navajo Southern Transmission System (NSTS) Moenkopi Cedar Mountain 500kV line. The generation facility would be located on the Moenkopi Cedar Mountain line approximately 26 miles from the Moenkopi substation. APS retained Utility System Efficiencies (USE) to perform the technical analysis portion of this FaS. The Interconnection submitted an interconnection request to APS, which was accepted on May 5, 2011 and has already completed a System Impact Study. This Project is a FERC jurisdictional large interconnection request. The IC s orginally requested Commercial Operation Date for Q196 was November 1, The Interconnection submitted a revised requested Commercial Operation Date, as per the Facilities Study Agreement for Q196 for November 1, The IC s requested date to have the interconnection initially energized in order to take back feed power is October 1, The projected construction duration for Q196 is 30 months. Due to the original in-service and commercial operation dates not being able to be met, APS will utilize the first available dates as shown in the construction milestones found in table 2 below. Please note that the Commercial Operation Date must be within the seven (7) years of the APS acceptance of the Interconnection s Interconnection Request. All reasonable efforts will be used by APS to meet the Interconnection s proposed project dates. The IC has requested interconnection along the Moenkopi Cedar Mountain 500 kv line. The Point of Interconnection (POI) for this project will therefore be at the tap on the Moenkop Cedar Mountain 500 kv line. For this specific interconnection request only, the NSTS owners have decided to allow the usage of a tap to the Moenkopi Cedar Mountain 500 kv line. The owners expressly states that the usage of a tap for this interconnection does not set precedent for any future proposed interconnections. No new interconnection will be allowed to degrade the protection scheme for any NSTS facilities. The IC has chosen to interconnect with the Energy Resource Interconnection Service option. Delivery of the Q196 output beyond the POI would be on an as-available basis only. The delivery of the Q196 output would be subject to the firm or non-firm transmission capacity that may be available when a Transmission Service Request is made. Figure 1 shows a general depiction of the EHV system around Q196 s proposed POI. Page 3
5 Figure 1. Transmission System in the Q196 vicinity Moenkopi 500 kv 26 miles 30 miles Cedar Mountain 500 kv 500 kv R=0.002 X= kv R= X= R= X= kv R= X= Pmax=100.8 MW Qrange=+/ MVAR kv kv kv kv Pmax=15 MW Qrange=+/-4.93 MVAR Pmax=15 MW Qrange=+/-4.93 MVAR Pmax=15 MW Qrange=+/-4.93 MVAR Pmax=15 MW Qrange=+/-4.93 MVAR Disclaimer Nothing in this report constitutes an offer of transmission service or confers upon the Interconnection ( IC ) any right to receive transmission service. APS and other interconnected utilities may not have the Available Transmission Capacity to support the interconnection described in this report. It should also be noted that all results for the FaS are highly dependent upon the assumed topology and timing of new projects in the vicinity of the interconnection, which are subject to change. Page 4
6 2. Q196 Interconnection Facilities In order to connect the Q196 project, facilities will be required for substation, line work, communications, land, and siting. The facilities required include: Substation Installation of a new 500 kv switchyard for a single breaker tap on the 500 kv Cedar Mountain Moenkopi line. The switchyard will consist of: o (1) 3 pole 500 kv breaker o (2) 500 kv switches o (1) 500 kv single phase SSVT o (1) single pole 500 kv breaker o (1) single pole 500 kv switch o (1) single pole 500 kv CT o (1) control house and associated relays, batteries, and chargers o (1) pad mount station power transformer feed from customer transformer tertiary o (1) diesel generator o (1) site security monitoring equipment o Associated structures / bus supports / fence Station power will be provided by a 500 kv SSVT, with backup station power from customer transformer tertiary and standby generator. New relays will need to be installed at Moenkopi and Cedar Mountain to support new 3-point relaying. Line work materials, structures and construction activities needed to do the line drop from the Moenkopi Cedar Mountain line tap to the new 500 kv switchyard. Communications Substation communications for high voltage substations requires two physically diverse communication paths. There will be one microwave path and one fiber optic path with fiber on the 500 kv line from Q196 to the Cedar Mountain substation. The communications costs for the Q196 project has been deemed network upgrades as these costs are required for the revised line protection schemes to function. The communications costs are on the transmission system and therefore beyond the POI. Thus the communications perform a network function and are deemed network upgrades rather than transmission provider s interconnection facilities. Relays Work needed to replace the existing relays (L1, L2, L3) at Moenkopi and Cedar Mountain to support the 3 point relaying that will be required for the tapped interconnection. Land There would need to be land acquired for a substation site north of the 500 kv corridor near Valle, Arizona. Five (5) acres of land would be needed for the substation from the surrounding private and State-owned lands. Potential studies or permits that would need to be acquired includes title reports, appraisals, and environmental studies. Property purchase could range from 6 to 12 months. If condemnation is necessary the property purchase could be up to 2 years. Siting A certificate of Environmental Compatibility (CEC) will be required to interconnect the switchyard with the Moenkopi Cedar Mountain 500 kv line. Completing the CEC will require cooperative efforts from both customer and APS and the CEC process is likely to take 8 to 12 months. The total cost for the facilities required to interconnect the Q196 project is $9,270,719. Page 5
7 Figure 2 is a one-line diagram of the proposed configuration and interconnection of Q196 s project. In Figure 2, the Moenkopi Cedar Mountain 500 kv line shown in black are the existing facilities. Figure 2 also depicts the s Interconnection Facilities which are shown in green. In Figure 2, the facilities shown in red are the Transmission Provider s Interconnection Facilities (TPIF). APS will operate and maintain all the facilities shown in red up to the first structure outside of the substation fence, at which point the IC would pick-up ownership and responsibility for the line. Ownership of the TPIF shall be held by the Navajo Project Participants in proportion to their ownership in the Moenkopi Cedar Mountain 500 kv transmission line. The IC is responsible for providing the full cost for the TPIF. Figure 2. New Q196 Switchyard one-line Page 6
8 There is one type of upgrade associated with this Project: Network Upgrades. Network Upgrades only apply to some upgrades to the system at or above 69kV. Network Upgrades do not include Distribution Upgrades. Network upgrades are defined by FERC as: Network Upgrades The additions, modifications, and upgrades to the Transmission Provider s Transmission System required at or beyond the point at which the Small Generating Facility Interconnects with the Transmission Provider s Transmission System to accommodate the interconnection with the Small Generating Facility to the Transmission Provider s Transmission System. Network Upgrades do not include Distribution Upgrades. APS estimates the following with regards to Network Upgrades: Installation of new relays at Cedar Mountain switchyard and Moenkopi substation to support the new 3 point relaying scheme. Communications Substation communications for high voltage substations requires two physically diverse communication paths. There will be one microwave path and one fiber optic path with fiber on the 500 kv line from Q196 to the Cedar Mountain substation. Network upgrades for the Q196 project include: To install new relays at Moenkopi and Cedar Mountain to support new 3 point relaying Labor $ 249,707 Equipment $ 92,842 Total Relay Network Upgrades $ 342,549 Communications for Q196 Project 3. Cost Estimates Equipment at Q196 site $ 688,045 Equipment at microwave sites $ 96,462 Fiber optic cable & other substation equipment $ 2,387,687 Labor & travel $ 899,566 Total Communications Network Upgrades $ 4,071,761 Total Q196 Network Upgrades $ 4,414,310 The desired in-service date to begin testing for the interconnection facilities is October 1, This date cannot be met so APS will build to the first available date given the construction duration depicted below in the Table 2 construction milestone. The estimated cost of the Q196 interconnection is allocated into two categories, Network Upgrades and Transmission Provider s Interconnection Facilities and is summarized in Table 1 below. Construction schedule estimates are from the date the Interconnection provides written authorization to proceed, provided all interconnection agreements and funding arrangements are in place. Page 7
9 Interconnection construction costs and timelines were estimated for Q196 based on the approximate location described above. These good faith non-binding cost estimates are applicable only to the APS system. This study reviewed all capacity, construction, flicker, protection and communications requirements to interconnect this FERC-jurisdicitional generation project. NERC (North American Reliability Corporation) requires that generation facilities provide a primary and secondary (back-up) communications path for data and control. This study does not specifically address any requirements for the Interconnection Generating Facilities. However, the Interconnection shall comply with all APS requirements for a generator operating in parallel with APS s electrical system. Assumptions: The following assumptions were utilized in compiling the cost estimates for Q196: I) Site Civil will include grounding, foundations and conduit only Land and civil engineering will be performed by the IC II) Design Full scope of work attained Engineering and design activities will be performed by contractor Once drawing package is IFC, no drawings will need to be updated (i.e. modifications from other construction/maintenance activities which occur following issue of package) III) Construction A mobile transformer will not be needed All substation construction and P&C activities will be performed by APS crew Per diem was added Will need to rent equipment, such as manlift; therefore, add equipment rental costs Account for some personnel going to Substation during construction or possible design. APS construction crew will be comprised of a 4-person crew, working 10 hour days, 4 days per week; no overtime APS P&C crew for wiring will be comprised of a 2-person crew, working 10 hour days, 4 days per week; no overtime IV) P&C P&C will stay after the construction crews are done to finish all wiring and will put station in service V) Exclusions Any construction outside of substation wall/fence is not included in this estimate. (i.e. overhead, underground, communications, etc ) Page 8
10 Table 1. Cost Estimates for Q196 - POI Equipment Description Network Upgrades Transmission Provider's Interconnection Facilities Q196 Substation Work $0 $3,556,433 Q196 Line Work $0 $ 925,476 Relay Cedar Mountain, $ 342,549 $ 0 Moenkopi Communications $4,071,761 $ 0 Siting $0 $ 352,000 Land $0 $ 22,500 Subtotal $4,414,310 $4,856,409 Grand Total $9,270,719 All Network Upgrade costs are subject to repayment in accord with FERC rules. It will be the responsibility of the interconnection customer to work with each of the NSTS owners individually to determine the specifics of how, if, when and under what circumstances the allocated share of Network Upgrades will be repaid. Costs for these Network Upgrades are estimated to be $4.41M. The estimate for the Transmission Provider s Interconnection Facilities is $4.86M, none of which is subject to refund. The total estimated cost for the interconnection is $9.27M. Figure 2 identifies additions that are needed for the interconnection request. The owners of the NSTS are the United States of America ( US ), Arizona Public Service Company ( APS ), Department of Water and Power for the City of Los Angeles( LADWP ), Nevada Power Company ( NVE ), Salt River Project Agricultural Improvement and Power District ( SRP ), and Tucson Electric Power Company ( TEP ). The ownership percentages for the Navajo Southern Transmission System Moekopi Cedar Mountain 500kV line are: APS: 24.7% SRP: 38.3% *SRP for U.S: 23.7% TEP: 13.3% * SRP holds title for the use and benefit of the United States. Network Upgrades are typically repaid by APS via transmission service credits over a twenty year period. Any amount remaining at the end of the twenty years are repaid to the Interconnection, including such interest as defined by FERC. PLEASE NOTE: The cost estimates exclude Interconnection costs associated with obtaining permits, easements or income tax or other tax effect and and the cost associated with any Interconnection -owned equipment required for the interconnection of the generators, including protective relaying and a visible open utility disconnect switch. In addition to the construction costs described above, there will be annual operation and maintenance expenses. The estimated cost of annual operation and maintenance expenses is as follows: Common Equipment/ Line Inspections - $3,000 annually - Two inspections per year Page 9
11 - Relay maintenance (estimated at every 4-6 years) - Weed abatement spraying (estimated at 2 times per year) Breaker Maintenance - $6,000 each time for: - Overhaul (estimated once every 6 years) Additional actual costs will be charged for: - Emergency maintenance and repair work such as breaker failure-to-close 3.1. Summary of Construction Time Estimates at the POI The IC s requested date to energize the interconnection facilities to receive back feed power is December 1, Table 2 is a preliminary design and construction timeline. Table 2 estimates that it will take approximately 30 months in order to site, certificate, design, permit, procure, and construct the required facilities to interconnect the Q196 project; putting the earliest possible date for the IC s project to be energized at 30 months from the date all the appropriate agreements are signed and funded. Due to the original in-service and commercial operation dates not being able to be met, APS will utilize the first available dates as shown in the construction milestones found below. High level interconnection construction cost estimates for the facility interconnection are tabulated above. Construction schedule estimates are from the date the Interconnection provides written authorization to proceed, provided all interconnection agreements and funding arrangements are in place. Table 2. Q196 Construction Time Estimates at POI LGIA Milestones This Milestone table represents APS s best effort at targeting a high level construction and In-Service schedule per Interconnection s requested In-Service Date. Please note that the Commercial Operation Date must be within the seven (7) years of the APS acceptance of the Interconnection s Interconnection Request. This Schedule and its projected In-Service Date are subject to change due to potential issues with weather, permitting and other required criteria and activities which may cause unforeseen timing delays. Upon commencement of Project, a construction schedule will be negotiated and adjusted accordingly. This Milestone Table represents APS s Standard Option as defined in of this LGIA. MILESTONE RESPONSIBLE DATE PARTY LGIA Signed & Filed at FERC: Generator interconnect agreement signed and Both Parties 04/01/2015 filed at FERC subject to Federal Regulatory requirements. LGIA Funded: s Submittal of Provision of Security (Article and Interconnection 04/15/2015 Article 5.6.4). Kick-off Meeting Both Parties 04/20/2015 Notice to Proceed: to provide APS with written authorization to Interconnection 04/27/2015 proceed with design and procurement of materials (Article 5.5.2). APS Engineering: APS begin engineering activities. APS 05/04/2015 ROW Acquisition: APS to secure Right Of Way for Overhead Line Route APS 08/03/2015 Page 10
12 Materials: APS begin procurement of materials. APS 07/06/2015 Site Information: Substation site Topo, Geotech, and Soil Resistivity sent to APS. Civil Information: Civil grading/drainage and site access plan submittal to APS APS acceptance of Civil Submittal: APS acceptance of civil grading/drainage site plan submittal after final civil site plan submittal (APS requires unrestricted and adequate site access) Environmental Compliance: Interconnection complete all required Environmental and Archaeological Surveys and provide copy to APS. Civil Construction: Interconnection begin site below grade construction of APS and IC interconnection substation ( site prep ) Site Acceptance of Civil Construction: Interconnection submit certified site as-built drawings of below grade construction and certified documents showing that site was built to APS Specifications Land Transfer: Interconnect ensures land transfer and easements are complete (if applicable) Notice to Proceed with Construction: to provide APS with written authorization to proceed with construction of facilities (Article 5.6.3). APS Overhead Line Construction: APS to begin construction of Overhead Line APS Substation Construction: APS begin interconnection substation construction APS Communications Construction: Complete communications and other activities required for APS Substation Operating Agreement: APS and Interconnection execute the APS standard Operating Agreement at least 90 days prior to synchronization Outage Window: APS outage for substation cut-in (Subject to change based on System Conditions) Interconnection 06/08/2015 Interconnection 06/08/2015 APS 07/06/2015 Interconnection Interconnection Interconnection 05/04/ /02/ /01/2016 Interconnection 01/04/2016 Interconnection 04/04/2016 APS 08/01/2016 APS 08/01/2016 APS 07/07/2017 Both Parties 08/04/2017 APS 10/01/2017 to 11/01/2017 Installation and Proving Relays: Complete line/relay work for substation cut-in APS 10/06/2017 Metering: Metering installed, tested and released for use Both Parties 10/06/2017 Inspection Test Report Submitted and Acknowledged: to provide APS with written test report when testing and inspection is complete. APS to acknowledge that written test report has been received (Article 2.1) In-Service/Back Feed: APS substation cut-in complete and released to APS Operations for IC to obtain back feed power Initial synchronization: The date upon which the Generating Facility is initially synchronized and upon which Trial Operation begins. Commercial Operation: Interconnection Commercial Operation Date (C.O.D.) Both Parties 10/13/2017 APS 10/27/2017 Both Parties 11/03/2017 Interconnection 11/17/2017 Page 11
13 4. Request For Transmission Service Transmission service was not studied in the Facilities Study. Such a request is required to be made through the APS OASIS site to the APS Transmission Services Trading Group or the other NSTS participants OASIS site and is outside the scope of the generator Interconnection Request study process. 5. Power Factor Requirements The APS Open Access Transmission Tariff (OATT) policy regarding power factor requires all Interconnection s, with the exception of wind generators, to maintain an acceptable power factor (typically near unity) at the Point of Interconnection (POI), subject to system conditions. The APS OATT also requires Interconnection s to be able to achieve +/ power factor at the POI, with the maximum "full-output" VAR capability available at all outputs. Furthermore, APS requires Interconnection s to have dynamic voltage control (operational time of less than 5 seconds) and maintain the voltage as specified by the transmission operator within the limitation of +/ power factor, as long as the Project is online and generating. If the Project s equipment is not capable of this type of response, a dynamic reactive device will be required. APS has the right to disconnect the Project from the power grid if system conditions dictate the need to do so in order to maintain system reliability. The method for determining whether or not the generator meets these requirements is to first record the pre-project POI bus voltage. Next, model the generator with zero reactive capabilities at full output. Any shunt devices are turned off. Two synchronous condensers are added to the case with infinite reactive capability. One is at the terminal bus of the unit regulating the bus voltage to 1.0 pu. The other is one bus away from the POI regulating the POI to the pre-project voltage level. The amount of plant losses can be determined by recording the MVAR flow at the POI and adding that to the sum of the synchronous condenser output. Based on the maximum output of the plant, determine the minimum reactive capabilities required to meet the +/-0.95 power factor range. The sum of the two numbers determines the maximum amount of reactive support the project must provide. 5.1 Reactive Support The project is required to meet the minimum power factor capability under all operating conditions. Three scenarios were analyzed that model the possible operating conditions. The project must be able to achieve +/-0.95 power factor at the point of interconnection when only the wind portion is online, only solar portion is online, and the wind and solar portion are both at full output. All Wind No Solar Power Factor Capability (100.8 MW) The project satisfies the minimum power factor requirement when only the wind portion of the project is operating. The wind turbines online at 101 MW require a minimum of +/-33.2 MVAR capability at the POI to meet the +/-0.95 power factor requirement. The calculated plant losses are 14.4 MVAR. The aggregated wind turbine dynamic capability is +/ MVAR. This results in MVAR of capability at the POI. No additional reactive support is required to offset the internal plant losses and meet the APS power factor requirement. All Solar No Wind Power Factor Capability (60 MW) The project does not satisfy the minimum power factor requirement when only the solar portion of the project is operating. The solar inverters online at 60 MW require a minimum of +/ MVAR capability at the POI to meet the +/-0.95 power factor requirement. The calculated plant losses are 7.1 MVAR. The aggregated solar inverter dynamic capability is +/ MVAR. This results in MVAR s of capability at the POI. An additional +/-7.1 MVAR of reactive support is required to offset the internal plant losses and meet the APS power factor requirement. The deficiency can be made up by switched capacitor banks. Page 12
14 Full Solar Full Wind (60 MW MW) The project does not satisfy the minimum power factor requirement when the solar portion of the project is operating at full output (60 MW) and the wind portion operating at full output (100.8 MW). The combined output of MW requires a minimum of +/ MVAR capability at the POI to meet the +/-0.95 power factor requirement. The calculated plant losses are 29.9 MVAR. The aggregated wind turbine and solar inverter dynamic capability is +/ MVAR. This results in MVAR s of capability at the POI. An additional +/-14.2 MVAR of reactive support is required to offset the internal plant losses and meet the APS power factor requirement. The deficiency can be made up by switched capacitor banks. The worst case scenario for this project is when the solar and wind are at full output. Therefore, as shown above, the project needs to add a minimum of 14.2 MVAR of reactive support to meet the APS minimum power factor requirement for all operating conditions. Smaller step sizes will make the caps more useful under a wide range of operating conditions. Page 13
Q137 Generation Interconnection
Q137 Generation Interconnection Interconnection Facilities Study Results APS Contract No. 52675 By Arizona Public Service Company Transmission Planning July 28, 2014 Q137 FACILITIES STUDY - TECHNICAL REVIEW
More informationFour Corners Queue Transmission Interconnection Study
Four Corners Queue Transmission Interconnection Study Facility Study Results By Arizona Public Service Company Transmission Planning & Interconnection Development March 22, 2016 Version 1 FACILITIES STUDY
More informationQ51 Generation Interconnection
Q51 Generation Facilities Study Results APS Contract No. 52395 By Arizona Public Service Company Transmission Planning September 4, 2013 [Version 1.0] Q51 FACILITIES STUDY TABLE OF CONTENTS Contents 1.
More informationInterconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado
Executive Summary Interconnection Feasibility Study Report Request # GI-2016-6 Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Public Service Company of Colorado Transmission
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More informationQ85 Generation Interconnection
A subsidiary of Pinnacle West Capital Corporation Q85 Generation Interconnection Interconnection Facilities Study AMENDED APS Contract No. 52386 By Arizona Public Service Company Transmission Planning
More informationMILLIGAN SOLAR PROJECT
February 16, 2009 Page 1 of 18 A subsidiary of Pinnacle West Capital Corporation MILLIGAN SOLAR PROJECT FINAL Feasibility Study Report APS Contract 52115 Prepared by: Arizona Public Service Company Transmission
More informationINTERCONNECTION FACILITIES STUDY REPORT
INTERCONNECTION FACILITIES STUDY REPORT Interconnection Request No. TI-12-0217 8 MW Hydropower Generating Facility POI on the Dallas Creek to South Canal 115kV Line in SW Colorado FINAL REPORT February
More informationPUD ELECTRIC SYSTEM INTERCONNECTION
APPENDIX A PROCEDURES & REQUIREMENTS for OKANOGAN PUD ELECTRIC SYSTEM INTERCONNECTION Version 4.0 December 2011 Version 4.0 12/28/2011 Page 1 of 15 TABLE OF CONTENTS DEFINITIONS 1.0 Introduction 2.0 Procedures
More informationElbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI
Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility
More informationMemorandum. This memorandum requires Board action. EXECUTIVE SUMMARY
California Independent System Operator Memorandum To: ISO Operations (MRTU) Committee From: Armando J. Perez, Director of Grid Planning cc: ISO Board of Governors ISO Officers Date: April 29, 2005 Re:
More informationInterconnection System Impact Study Report Request # GI
Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010
More informationCity of Palo Alto (ID # 6416) City Council Staff Report
City of Palo Alto (ID # 6416) City Council Staff Report Report Type: Informational Report Meeting Date: 1/25/2016 Summary Title: Update on Second Transmission Line Title: Update on Progress Towards Building
More informationInterconnection Feasibility Study Report GIP-226-FEAS-R3
Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power
More informationQ87 Generation Interconnection
A subsidiary of Pinnacle West Capital Corporation Version 1.0 Q87 Generation Interconnection Interconnection Facilities Study APS Contract No. 52365 By Arizona Public Service Company Transmission Planning
More informationCUSTOMER/ TWIN ARROWS PROJECT
A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset
More informationUpdates and Modifications to Report
QUARTERLY COMPLIANCE REPORT (OCTOBER 2016) OF SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) REGARDING STATUS OF TRANSMISSION PROJECTS AND GENERATION INTERCONNECTION PROJECTS Pursuant to Commission Decision
More informationInterconnection Process for Generation Systems
Interconnection Process for Generation Systems I. INTRODUCTION...1 II. GENERAL INFORMATION...2 A. Definitions...2 B. Nodak Electric Cooperative, Inc. Generation Interconnection Contacts...3 C. Engineering
More informationQ95 Vicksburg 69kV. System Impact Study. APS Contract No Arizona Public Service Company Transmission Planning.
A subsidiary of Pinnacle West Capital Corporation Q95 Vicksburg 69kV System Impact Study APS Contract No. 52246 By Arizona Public Service Company Transmission Planning December 1, 2010 Version 2.6 Final
More informationManaging California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station
Managing California s Electrical Supply System after the shut down of San Onofre Nuclear Generating Station East Asian Alternative Energy Futures Workshop By the Nonproliferation Policy Education Center
More informationRe: Comments on the 12/7/09 Dynamic Transfer Stakeholder Meeting
Joseph H. Rowley Vice President Project Development 101 Ash Street, HQ14A San Diego, CA 92101-3017 Tel: 619.696.4455 Fax: 619.696.2911 JRowley@SempraGeneration.com December 15, 2009 Ms. Anjali Sheffrin
More informationTransmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015
No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the
More informationGuide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.
Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...
More informationPREPARED DIRECT TESTIMONY
Application No.: A.0-04- Exhibit No.: SDG&E-4 Witness: William V. Torre In the Matter of San Diego Gas & Electric Company s Application for Authorization to (1) to Participate in the Steam Generator Replacement
More informationQ217 Generator Interconnection Project
Q217 Generator Interconnection System Impact Study APS Contract No. 52588 By Arizona Public Service Company Transmission Planning November 25, 2013 Version 2.0 Prepared by Utility System Efficiencies,
More informationUpdates and Modifications to Report
QUARTERLY COMPLIANCE REPORT (JULY 2015) OF SOUTHERN CALIFORNIA EDISON COMPANY (U 338-E) REGARDING STATUS OF TRANSMISSION PROJECTS AND GENERATION INTERCONNECTION PROJECTS Pursuant to Commission Decision
More informationSYSTEM IMPACT RESTUDY H252W ERIS REPORT. El Paso Electric Company
SYSTEM IMPACT RESTUDY H252W ERIS REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This report
More informationProject #148. Generation Interconnection System Impact Study Report
Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection
More informationWholesale Power Supply Socorro Electric Cooperative, Inc. Rob Wolaver, P.E. Senior Manager, Energy Resources
Wholesale Power Supply Socorro Electric Cooperative, Inc. Rob Wolaver, P.E. Senior Manager, Energy Resources Outline Tri-State Background Tri-State Generation Mix Power Delivery Wholesale Electricity Markets
More informationFINAL FACILITY STUDY. 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1. September 10, 2010
FINAL FACILITY STUDY 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1 September 10, 2010 I. Introduction This is a revised facility study performed for Transmission Queue Request 2009
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements
Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner
More informationSYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT. El Paso Electric Company
SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This
More informationQ64. Photovoltaic Solar Generation Project Interconnection. Facilities Study. APS Contract No
A subsidiary of Pinnacle West Capital Corporation Q64 Photovoltaic Solar Generation Project Interconnection Facilities Study APS Contract No. 52215 By Arizona Public Service Company Distribution Planning
More informationJEA Distributed Generation Policy Effective April 1, 2018
Summary This JEA Distributed Generation Policy is intended to facilitate generation from customer-owned renewable and non-renewable energy generation systems interconnecting to the JEA electric grid. The
More informationTHE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS
THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive
More informationInterconnection Feasibility Study Report GIP-084-FEAS-R2
Interconnection Feasibility Study Report GIP-084-FEAS-R2 System Interconnection Request #84 50 MW Wind Generating Facility Pictou County (L-7004) August 17, 2007 Control Centre Operations Nova Scotia Power
More informationEL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS
EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS El Paso Electric Company System Operations Department System Planning Section May 2004
More informationQ164 Photovoltaic Solar GenerationProject Interconnection
A subsidiary of Pinnacle West Capital Corporation Q164 Photovoltaic Solar GenerationProject Interconnection System Impact Study APS Contract No. 52425 By Arizona Public Service Company Distribution Planning
More informationSmall Generator Interconnection Program Interconnection Technical Requirements
General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator
More informationHigh Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007
High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM-2006-02) Interconnection Facility Study Final Report November 2, 2007 Prepared by: Public Service Company of New Mexico Electric Services
More informationHONORABLE CHAIRPERSON AND MEMBERS OF THE AZUSA UTILITY BOARD
SCHEDULED ITEM TO: FROM: HONORABLE CHAIRPERSON AND MEMBERS OF THE AZUSA UTILITY BOARD GEORGE F. MORROW, DIRECTOR OF UTILITIES DATE: JANUARY 28, 2013 SUBJECT: APPROVAL OF POWER SALES AGREEMENT ( PSA ) WITH
More informationUmatilla Electric Cooperative Net Metering Rules
Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through
More informationTransmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202
Transmission and Distribution Substation Projects Operating Company: Entergy Gulf States - Texas Customer: PID # 202 Funding Project Number: F4PPGS0386 Facility Study for PID # 202: Study for 146 MW Revision
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationQ92 Asarco Interconnection
A subsidiary of Pinnacle West Capital Corporation Q92 Asarco Interconnection Feasibility Study APS Contract No. 52239 By Arizona Public Service Company Transmission Planning July 29, 2010 Prepared by Utility
More informationInterconnection Feasibility Study Report GIP-222-FEAS-R3
Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.
More informationCHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.
25.211. Interconnection of On-Site Distributed Generation (DG). (a) (b) (c) Application. Unless the context indicates otherwise, this section and 25.212 of this title (relating to Technical Requirements
More informationMerger of the generator interconnection processes of Valley Electric and the ISO;
California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson Vice President, Policy & Client Services Date: August 18, 2011 Re: Decision on Valley Electric
More informationConsulting Agreement Study. Completed for Transmission Customer
Completed for Transmission Customer Proposed Resource & Transmission Carbon County, MT & 230 kv Transmission in North Wyoming August 2016 Table of Contents 1.0 Description... 1 2.0 Overall Assumptions...
More informationAPPENDIX I: Description and Functional Specifications for Transmission Facilities Eligible for Competitive Solicitation
APPENDIX I: Description and Functional Specifications for Transmission Facilities Eligible for Competitive Solicitation Intentionally left blank F1 Description and Functional Specifications of Proposed
More informationA member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.
Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative
More informationTABLE OF CONTENTS FIGURES: MAP EXHIBITS: TABLES:
TransWest Express Transmission Project TABLE OF CONTENTS 7.0 DESIGN OPTIONS... 7-1 7.1 OVERVIEW OF DESIGN OPTIONS... 7-1 7.2 DESIGN OPTIONS PURPOSE AND NEED AND DESIGN CHARACTERISTICS... 7-4 7.2.1 Design
More informationPlease Refer to Attached Sample Form
Pacific Gas and Electric Company San Francisco, California U 39 Revised Cal. P.U.C. Sheet No. 32105-E Cancelling Revised Cal. P.U.C. Sheet No. 28313-E Electric Sample Form No. 62-0686 Application for Service
More informationGeorgia Transmission Corporation Georgia Systems Operations Corporation
Georgia Transmission Corporation Georgia Systems Operations Corporation Reactive Power Requirements for Generating Facilities Interconnecting to the Georgia Integrated Transmission System with Georgia
More informationbest to you all Gail Carbiener Page 1 of 5
Please accept this attachment as my up dated response to the B2H DEIS. If this is not acceptable, please let me know. Nice meeting last Monday in Boardman. 300316 best to you all Gail Carbiener 2 Page
More informationProject #94. Generation Interconnection System Impact Study Report Revision
Project #94 Generation Interconnection System Impact Study Report Revision October 2, 2009 Electric Transmission Planning Table of Contents Table of Contents...2 Executive Summary...3 Energy Resource Interconnection
More informationFeasibility Study Report
Report For: Fresh Air Energy II, LLC ( Customer ) Queue #: Service Location: Chester County, SC Total Output Requested By Customer: 74.5 MW Commercial Operation Date Requested By Customer: 1/7/2019 Feasibility
More informationRULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES
RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES Last Revised Date: October 15, 2015 Contents Chapter 1 - Purpose and Scope 2 Chapter 2 - Application of Rules 2 Chapter 3 - Definitions
More informationfor DRECP Alternatives
Transmission Technical Group Conceptual Transmission Plan for DRECP Alternatives DRECP WebEx Meeting January 9, 2013 Overview Purpose, Participants, and Timeline Generation Assumptions Transmission Assumptions
More informationMarch 18, Subject: Imperial Irrigation District 2014 Annual Progress Report - Rev 1
Energy Division P.O. Box 937 333 E. Barioni Blvd. Imperial, CA 92251 www.iid.com March 18, 2014 Mr. Tracy Rolstad Chair, WECC Technical Studies Subcommittee Senior Power System Consultant Avista System
More informationTransWest Express Transmission AC and DC Project Interregional Transmission Project Submittal
TransWest Express Transmission AC and DC Project 2018 2019 Interregional Transmission Project Submittal Submittals to California Independent System Operator, WestConnect and Northern Tier Transmission
More informationSupplemental Report on the NCTPC Collaborative Transmission Plan
Supplemental Report on the NCTPC 2007-2017 Collaborative Transmission Plan May 16, 2008 1 Table of Contents I. Executive Summary...1 II. Richmond-Fort Bragg Woodruff Street 230 kv Line...2 II.A. Need for
More informationINTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY
INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application
More informationCITY OF PASADENA APPLICATION FOR PARTICIPATING TRANSMISSION OWNER STATUS
CITY OF PASADENA APPLICATION FOR PARTICIPATING TRANSMISSION OWNER STATUS July 15, 2004 TABLE OF CONTENTS Page No. 1. Description of Pasadena s Transmission Lines and Facilities...1 A. Overview:... 1 B.
More informationInterconnection Feasibility Study Report GIP-369-FEAS-R1
Interconnection Feasibility Study Report GIP-369-FEAS-R1 System Interconnection Request #369 50 MW Wind Generating Facility Cumberland County (L-6513) 2012-02-09 Control Centre Operations Nova Scotia Power
More informationDecision on Merced Irrigation District Transition Agreement
California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson, Vice President Policy & Client Services Date: March 13, 2013 Re: Decision on Merced Irrigation
More informationFeasibility Study Report
Generator Interconnection Request Feasibility Study Report For: Customer --- Service Location: Rutherford County Total Output: 79.2 MW Commercial Operation Date: 9/1/2014 In-Service Date (if given): 9/1/2014
More informationTOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY
TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY January 7, 2002 Prepared by Jorge Chacon (Consultant) Tucson Electric Power Company Ed Beck ii EXECUTIVE SUMMARY
More informationEl Paso Electric Company
Feasibility Study XXXXXX Solar Generation Prepared for El Paso Electric Company Prepared by TRC Engineers, LLC 249 Eastern Avenues Augusta, ME 04330 (207) 621-7000 Project Number: 202327 May 2013 FOREWORD
More informationXXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan
XXXXX Kokish River Hydroelectric Project Interconnection Facilities Study and Project Plan March 16, 2011 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All
More informationPJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report
PJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report 155697 September 2001 Table of Contents DESCRIPTION PAGE 1.0 Introduction 3 2.0 Description of Facilities Included
More informationTable of Contents. Purpose. Eldorado Intertie and System (Eldorado- Moenkopi) Scheduling at Willow Beach. Operating Procedure
No. 6930 Table of Contents Purpose... 1 1. Limits, Ratings, & Effectiveness Factors... 2 2. Contingency Operations... 2 2.1 Transmission Lines Outages... 2 2.2 APS Terminal Equipment Outages... 2 2.3 SCE
More informationSouthern California Edison Rule 21 Storage Charging Interconnection Load Process Guide. Version 1.1
Southern California Edison Rule 21 Storage Charging Interconnection Load Process Guide Version 1.1 October 21, 2016 1 Table of Contents: A. Application Processing Pages 3-4 B. Operational Modes Associated
More informationHydroGenerations PROGRAM HANDBOOK
HydroGenerations PROGRAM HANDBOOK TABLE OF CONTENTS Please ensure you are reading the most recent version of this handbook by visiting the NV Energy website, www.nvenergy.com/hydro. Contents HydroGenerations
More informationCustomer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone Number:
Please print the following information. Interconnect Customer Information Customer Name : Account Number: Customer Service Address (Street, City, State, ZIP Code): Customer Mailing Address: Customer Telephone
More informationInterconnection Feasibility Study Report GIP-157-FEAS-R2
Interconnection Feasibility Study Report GIP-157-FEAS-R2 System Interconnection Request #157 100.5 MW Wind Generating Facility Guysborough County (L-6515) 2009 09 14 Control Centre Operations Nova Scotia
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationInterconnection Feasibility Study
Interconnection Feasibility Study Mount Mabel Wind Energy Project Report No: T&S Planning 2015-054 December 2015 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2015.
More informationSOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT
SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & INTERCONNECTION AGREEMENT INTERCONNECTION AGREEMENT FOR SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION THIS AGREEMENT MUST ACCOMPANY
More informationNew Mexico Transmission Expansion Concepts For Wind Resources
New Mexico Transmission Expansion Concepts For Wind Resources May 2008 Update Electric Services Transmission Operations FOREWORD This document contains PNM s latest concepts for expanding the transmission
More informationArizona Transmission Challenges
Power Task Force Agenda Number 2. Arizona Transmission Challenges Central Arizona Water Conservation District Power Committee Presentation May 18, 2017 Transmission Planning Efforts NATIONAL Section 368
More informationInterconnection Feasibility Study Report GIP-IR373-FEAS-R1
Interconnection Feasibility Study Report GIP-IR373-FEAS-R1 Generator Interconnection Request 373 109.5 MW Wind Generating Facility South Canoe Lake, NS Mar. 2, 2012 Control Centre Operations Nova Scotia
More informationCalifornia s RPS Program: Progress Towards California s 33% RPS Goal and the Role of Concentrating Solar Power CSP Conference
California s RPS Program: Progress Towards California s 33% RPS Goal and the Role of Concentrating Solar Power CSP Conference Presented by Edward Randolph Energy Division Director, California Public Utilities
More informationWestConnect Regional Planning Update
WestConnect Regional Planning Update WRP Energy Committee May 4, 2015 Webinar Outline WestConnect Overview Membership, Structure & Footprint Planning process and regulatory status Order 890 Update (2014)
More informationAlberta Electric System Operator Needs Identification Document Application. Mowat 2033S Substation
Decision 21781-D01-2016 Alberta Electric System Operator Needs Identification Document Application Facility Applications September 7, 2016 Alberta Utilities Commission Decision 21781-D01-2016: Alberta
More informationINTERCONNECTION REQUIREMENTS POLICY
Issue Date: January 8, 2018 Resolution No. 2097-18 INTERCONNECTION REQUIREMENTS POLICY 1. Purpose and Scope A. The purpose of these Interconnection Requirements is to establish rules for determining the
More informationAPPENDIX F: Project Need and Description
APPENDIX F: Project Need and Description California ISO/MID F-1 Intentionally left blank California ISO/MID F-2 Name Brief Description Type Lugo Victorville 500 kv Upgrade (SCE portion) The project was
More informationLLC FACILITIES STUDY TRANSMISSION SERVICE REQUEST
Cleco Power LLC FACILITIES STUDY TRANSMISSION SERVICE REQUEST OASIS 71956063 0 Rev Issue Date Description of Revision Table of Contents 1. Purpose...3 2. System Impact Study Conclusions...3 2.1 The Pineville
More informationCalifornia Independent System Operator Corporation Fifth Replacement Electronic Tariff
Table of Contents 41. Procurement Of RMR Generation... 2 41.1 Procurement Of Reliability Must-Run Generation By The CAISO... 2 41.2 Designation Of Generating Unit As Reliability Must-Run Unit... 2 41.3
More informationREQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw
REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used
More informationReactive Power Compensation for Solar Power Plants. Andy Leon IEEE PES Chicago Chapter December 12 th, 2018
1 Reactive Power Compensation for Solar Power Plants Andy Leon IEEE PES Chicago Chapter December 12 th, 2018 2 Objectives Refresh the basics of reactive power from a generator s perspective Regulatory
More informationINTERCONNECTION for GENERATING FACILITIES Up to 20 MW
PROGRAM REQUIREMENTS Important Information from Your Local Non-Profit Utility INTERCONNECTION for GENERATING FACILITIES Up to 20 MW Interconnecting to the Electrical Distribution System of Public Utility
More informationREQUEST FOR PROPOSALS FOR THE ESTABLISHMENT OF SOLAR PV POWER PLANT ON BUILD, OWN AND OPERATE BASIS. International Competitive Bidding (ICB)
REQUEST FOR PROPOSALS FOR THE ESTABLISHMENT OF SOLAR PV POWER PLANT ON BUILD, OWN AND OPERATE BASIS International Competitive Bidding (ICB) Polonnaruwa Solar PV Power Project (10 MWp) Tender No: CEB/EPT/SP/RFP1
More informationRequest for Payment Instructions Rule 21 Export Submittal Instructions
Grid Interconnection & Contract Development Request for Payment Instructions Rule 21 Export Submittal Instructions Prior to submitting your application and fee or deposit, please complete and submit this
More informationFeasibility Study for the Q MW Solar Project
Feasibility Study for the Q171 74.5 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC
More informationSTORAGE TECHNOLOGIES
ENERGY STORAGE STORAGE TECHNOLOGIES SOLID STATE BATTERIES Solid state batteries are the original battery, originally invented in 1800. Each contains a positive and negative terminal Electrolytes allow
More informationGeneration Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX MW generator at new Western Refinary Substation
Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX 131-250 MW generator at new Western Refinary Substation System Planning Section April, 2005 TABLE OF CONTENT 1 EXECUTIVE SUMMARY
More informationTransmission Planning & Engineering P.O. Box MS 3259 Phoenix, Arizona
Transmission Planning & Engineering P.O. Box 53933 MS 3259 Phoenix, Arizona 85072-3933 March 9, 2016 Mr. Philip Augustin Chair, WECC Technical Studies Subcommittee Mr. Enoch Davies WECC Technical Staff
More informationENERGY RESOURCE INTERCONNECTION SERVICE STUDY DRAFT REPORT
ENERGY RESOURCE INTERCONNECTION SERVICE STUDY DRAFT REPORT ART320W 320 MW Wind Powered Project Prepared for: El Paso Electric Company Prepared by: TRC Engineers, LLC 249 Western Avenue Augusta, ME 04330
More informationSunZia Southwest Transmission Project
SunZia Southwest Transmission Project SunZia Project Update for the Southern Arizona Economic Development Group September 12, 2017 SUNZIA SOUTHWEST TRANSMISSION PROJECT SEPTEMBER 12, 2017 0 SouthWestern
More information