MOLD INSPECTION REPORT. UCD Anschutz Medical Campus Building E. 19 th Ave. Aurora, CO 80045

Size: px
Start display at page:

Download "MOLD INSPECTION REPORT. UCD Anschutz Medical Campus Building E. 19 th Ave. Aurora, CO 80045"

Transcription

1 MOLD INSPECTION REPORT For the Subject Property: UCD Anschutz Medical Campus Building E. 19 th Ave. Aurora, CO Report Date: August 7, 2015 Inspection/Testing Date: SET Project: Prepared by: Michael Schaan, WLS Colorado Certified Asbestos Building Inspector, Certified Mold Inspector and Assessor

2 Limited Scope of Report The mold inspection performed for client was a non-intrusive examination designed to identify suspect areas and conditions of the above-referenced primary building as it existed at the time of the inspection. Suspect conditions are those conditions defined by the Indoor Environmental Standards Organization (IESO) inspection standards having potential for mold contamination. The International Institute of Inspection, Cleaning and Restoration (IICRC) guidelines S520 are used to determine the appropriate Condition of the building materials on site and the remediation strategy. The inspection was limited to those areas that were visually and physically accessible. The inspection was not a risk assessment, physical inspection of systems, structure, or components of the primary building and its primary parking structure being inspected, as it relates to their serviceability. The inspection was performed in accordance with the Standards of Practice of the IESO and the IICRC in effect at the time of this Inspection. A copy of these standards is available upon request. This inspection is not intended to be technically exhaustive. The inspector has prepared this written Mold Inspection Report for the sole use and benefit of the client. The Mold Inspection Report shall identify, report, and make recommendation for future evaluation. Client agrees to read the entire Mold Inspection Report when received and shall promptly call the inspector with questions or concerns regarding the Report. Purpose and Scope The purpose of this assessment was to conduct a visual mold survey and to collect and evaluate the necessary samples in order to determine the presence or absence of mold and moisture within the subject affected areas and/or in the air. The scope of this assessment included a visual inspection of all affected areas in the subject property for visible mold and or water staining. Thirty-nine (39) Air Samples, Four (4) Wall Cavity Samples, and Five (5) Surface Samples were collected and analyzed by the Inspector. The results are incorporated into this report. Schaan Environmental Testing (SET) used a moisture meter and a Thermal Imaging Camera where necessary to identify any elevated moisture within the subject property s building materials. The assessment was executed in accordance with the authorized scope of work. This report is solely a record of activities, observations, analytical results and recommendations performed to date.

3 Air Samples SET considers an indoor space to have satisfactory fungal ecology based on the following criteria: 1. The total indoor concentration is less than the total outdoor control concentration. 2. The absence of water indicator mold types, in any quantity. 3. Visible suspect microbial growth (SMG) is not observed on any surface. For brevity, the following office spaces did not indicate an elevated fungal concentration and will not be specifically addressed in this report. SET considers the following offices to have satisfactory indoor mold concentrations: S S S S S S S S S S S S S S S S S East Stairwell S S S S S S S S S S S S S S S The following wall cavity samples are considered satisfactory: S North Wall S West Wall

4 The following spaces indicate an elevated fungal concentration in the air samples and are unsatisfactory: West Stairwell (aspergillus/penicillium, paeciliomyces) S (aspergillus/penicillium) S (stachybotrys) S (aspergillus/penicillium) S (chaetomium) The following wall cavity samples indicate an elevated fungal concentration and are unsatisfactory: S North Wall (aspergillus/penicillium, nigrospora) S West Wall (aspergillus/penicillium) Room S is situated in the southwest portion of the first floor and houses several file cabinets. A 4 hole was noted in the southwest corner of this room and is open to the crawlspace.

5 Surface Samples Visible mold was observed in the following crawlspace areas: 1. Small crawlspace under west stairwell heavy growth on drywall and wood framing members. 2. Large crawlspace heavy growth on joists and sub-flooring south of the small crawlspace. 3. Large crawlspace sporadic growth, primarily on cross bracing between floor joists.

6 S Hole in Floor View from Crawlspace into S09-117

7 Small Crawlspace Example of Visible Mold on Drywall Small Crawlspace Example of Visible Mold on Sub-flooring

8 Large Crawlspace Example of Mold (South of Small Crawlspace) Large Crawlspace Example of Mold (South Central Area)

9 Inspector's Site Specific Recommendations S09-117: 1. Close the floor penetration into the crawlspace. 2. Conduct air sampling to ensure asbestos fibers have not migrated out of the crawlspace. 3. Erect containment and critical barriers to isolate this office from the remainder of the spaces. 4. Place this room under negative air pressurization. Ensure the negative air machine (NAM) is of sufficient capacity to provide a minimum of 4 10 air changes per hour. 5. Ensure workers wear the correct PPE to include full face respirators and disposable suits and gloves. 6. Apply an anti-microbial solution to all surfaces inside the office containment area. 7. Thoroughly clean all surfaces inside the contained work area. Cleaning should include ceilings, walls, floors, fixtures, and contents. 8. After all cleaning has been completed and in preparation for the post-remediation verification inspection and sampling, allow the NAM to continuously operate for 24 hours. 9. After 24 hours of continuous operation, turn off the NAM. Do not allow access into the contained area. The air must rest for 24 hours. 10. After 24 hours of air rest, allow SET into the site to conduct post-remediation verification (PRV) sampling. 11. Refer to the following additional guidelines regarding mold remediation services.

10 S (Files): Reference: IICRC S-520: Standard and Reference Guide for Professional Mold Remediation SET classifies this room and its contents as a Condition 2 Environment (settled spores). Refer to Chapter 13 of the IICRC S-520 (Mold Remediation) standard. Several specific items from the standard are attached: Condition 1 (normal fungal ecology): an indoor environment that may have settled spores, fungal fragments or traces of actual growth whose identity, location and quantity are reflective of a normal fungal ecology for a similar indoor environment. Condition 2 (settled spores): an indoor environment which is primarily contaminated with settled spores that were dispersed directly or indirectly from a Condition 3 area, and which may have traces of actual growth. Condition 3 (actual growth): an indoor environment contaminated with the presence of actual mold growth and associated spores. Actual growth includes growth that is active or dormant, visible or hidden Paper Goods: Books, Documents, Manuscripts, Family Records, Scrapbooks, Photographs, and similar items. o o Condition 2 - Porous contents with Condition 2 contamination are usually restorable using appropriate cleaning methods, based on material composition. Air washing can be effective. However, air washing should be performed only in a properly controlled work area, or using controlled techniques, where massive aerosolization will not pose a health risk to workers or occupants. Valuable or irreplaceable documents that cannot be cleaned or decontaminated may be encased, laminated or otherwise sealed. Condition 3 - Porous contents with Condition 3 contamination are usually unrestorable, based on material composition. Cleaning may require a specialized conservation process, and might not be successful. Valuable or irreplaceable documents that cannot be cleaned or decontaminated may be encased, laminated or otherwise isolated.

11 Paper Goods: books, documents, manuscripts, family records, scrapbooks, photographs, and similar items Most cleaning processes should start and end with HEPA - vacuuming. Clean by HEPA-vacuuming and dry brushing or other surface cleaning method, while on a downdraft cleaning table. Air washing can be effective. However, air washing should be performed only in a properly controlled work area, or using controlled techniques, where massive aerosolization will not pose a health risk to workers or occupants. Rapid drying after wet cleaning and appearance enhancement, as necessary, follows most cleaning methods. Valuable or irreplaceable documents that cannot be cleaned or decontaminated may be encased, laminated or otherwise sealed

12 S09-112: 1. Investigate this room for the presence of a small or hidden water intrusion source. 2. Thoroughly clean all surfaces inside the office. Cleaning should include ceilings, walls, fixtures, and contents. 3. HEPA vacuum and steam clean the carpet. Speed dry the carpet with carpet drying fans. S : 1. Investigate this room for the presence of a small or hidden water intrusion source. 2. Thoroughly clean all surfaces inside the office. Cleaning should include ceilings, walls, fixtures, and contents. 3. HEPA vacuum and steam clean the carpet. Speed dry the carpet with carpet drying fans. S09-217: 1. Investigate this room for the presence of a small or hidden water intrusion source. 2. Thoroughly clean all surfaces inside the office. Cleaning should include ceilings, walls, fixtures, and contents. 3. HEPA vacuum and steam clean the carpet. Speed dry the carpet with carpet drying fans.

13 West Stairwell: 1. Containment and negative air pressurization are already installed in this space. 2. Remove and discard vinyl flooring down to the wood sub-flooring. NOTE: This will require asbestos abatement. 3. Starting at the floor, remove the lower 2 feet of the west and south walls. Continue with wall removal to a point at least 2 feet beyond the last visible mold growth. Wall assembly removal will most likely require removal in adjoining offices S and S Remove wall insulation from the west and south wall cavities in the same areas as where drywall/plaster were removed. 5. Apply an anti-microbial solution to all surfaces inside the containment area. 6. Thoroughly clean all surfaces inside the contained work area. Cleaning should include ceilings, walls, floors, and fixtures. 7. Dry all impacted materials to a moisture content of at least After all cleaning has been completed and in preparation for the post-remediation verification inspection and sampling, allow the NAM to continuously operate for 24 hours. 9. After 24 hours of continuous operation, turn off the NAM. Do not allow access into the contained area. The air must rest for 24 hours. 10. After 24 hours of air rest, allow SET into the site to conduct post-remediation verification (PRV) sampling. 11. Refer to the following additional guidelines regarding mold remediation services.

14 Crawlspace: It is understood that the crawlspace contains asbestos. All work in this space should be performed by a Colorado asbestos certified and licensed contractor. 1. Erect containment and critical barriers to isolate the crawlspace from the remainder of the structure. 2. Place the space under negative air pressurization. Ensure the negative air machines (NAMs) are of sufficient capacity to provide a minimum of 4 10 air changes per hour. 3. Ensure workers wear the correct PPE to include full face respirators and disposable suits and gloves. 4. Remove and discard all drywall in the small crawlspace. 5. HEPA vacuum/wipe/sand as necessary to remove mold from wood framing members. 6. Apply an anti-microbial solution to all surfaces inside the crawlspaces. 7. After all cleaning has been completed, allow the NAMs to continuously operate for a minimum of 72 hours. 8. Refer to the following additional guidelines regarding mold remediation services. Clearance Criteria The following criteria will be used to evaluate and assess remediation services: 1. All surfaces must be visually clean and free of mold. 2. All surfaces must not positively react with IAQ-1000, a strong hydrogen peroxide solution, which indicates the presence of organic growth. 3. Surface samples must not contain mold in any quantity. 4. Air sample mold concentrations must be equal to or lower than the outdoor control sample. No water indicator mold types can be in the indoor air sample. Even the presence of 1 water indicator mold type mold spore will cause the project to fail.

15 Remediation Protocol A certified remediation contractor shall perform remediation under controlled conditions. The remediation contractor shall perform the work according to the guidelines and requirements specified in: The accepted remediation practices of the Indoor Air Quality Association, IICRC S500 and S520. The U.S.E.P.A. document, Mold Remediation in Schools and Commercial Buildings, March, 2001, EPA 402-K ; and Chapter 15 of the book Bioaerosol: Assessment and Control, 1999, by the American Conference of Governmental Industrial Hygienists. 1. General remediation specifications include as follows: All workers must wear proper protective gear at all times when doing mold and/or bacterial remediation in the subject property. Proper protective gear includes the following: 3M brand 6001 or equivalent full-face mask, hooded tyvec suit with builtin shoe covers, and construction grade rubber gloves. 2. The entire work area must be ventilated with negative air pressure and HEPA filtration during the remediation process. 3. Each area of known or suspected contamination must be thoroughly sprayed with a high pressure airless sprayer using an EPA approved disinfectant like IAQ1000, Sporicidin, Shock Wave or equivalent. The spraying should be allowed to dry naturally because the disinfectant kills while it is wet. 4. When treating visibly contaminated areas, the remediator must treat 2 feet beyond the contamination in each direction by spraying and removing the affected building product. 5. After demolition and removal of affected building materials, all remaining affected building materials (wood, green board and drywall surfaces) must have the remaining mold or bacterial staining removed by sanding, grinding, wire brushing or scraping. The sawdust or removed wood shavings must be vacuumed with a HEPA vacuum and the contents removed from the area by placing in a 6 mill plastic bag. The remediated area must be re-sprayed a second time with a high pressure airless sprayer using an EPA approved disinfectant as described in 4 above. 6. All contaminated building materials must be removed from the remediated area in 6 mill plastic bags. 7. No antimicrobial may be applied before the material to be treated is less than 28 moisture content as measured by a moisture meter. 8. All contents in the area under containment must be removed prior to demolition and remediation. Contents too large to remove must be cleaned as noted below and completely wrapped in plastic prior to the start of demolition. 9. All affected contents must be cleaned or replaced. These goods must be removed from the affected area after containment and negative air are in place. 10. All hard goods must be HEPA vacuumed and then wiped with an antimicrobial that will not damage the materials. Soft goods that need to be cleaned must be cleaned by soft goods and fabric specialists that use processes that will clean the entire item (typically this involves submerging in cleaning liquids). 11. All contents that are removed from containment must be sealed in 3 mil plastics bags or equivalent. These bags must be wiped down with antimicrobial prior to removal. Care must be taken to not cross contaminate traffic areas or other unaffected areas of the building.

16 12. The remediated area must be wiped down and HEPA vacuumed using the 5- step method before the final inspection and air assessment. HEPA vacuum from the contaminated areas toward the HEPA air scrubber and /or negative air machine, allowing 15 minutes for the dust to settle. Wet wipe with a disinfectant from the contaminated area toward the HEPA negative machine, allowing time for the dust to settle 15 min. HEPA vacuum from the contaminated areas toward the HEPA negative air machine, allowing time for the dust to settle 15 min. Wet wipe with a disinfectant from the contaminated area toward the HEPA negative machine, allowing time for the dust to settle 15 min. Final HEPA Vacuum from the HEPA negative machine toward the remediation area exit. (Remember to always 5-step the polypropylene containment, micron sized particles will collect on the negatively charged surface.) 13. After the contaminated areas are cleaned, they can be sprayed with a non-pigmented antimicrobial like IAQ 6000 or equivalent. 14. Upon completion of the remediation work but before the antimicrobial coating is applied and the containment system is removed, the property must be inspected and sampled by an Indoor Environmental Professional familiar with the project who is independent of the remediation company in order to receive Post Remediation Verification. Special Cases If a moisture barrier or conditioned air system is required the following protocol must be followed: 1. Crawlspace conditioned air if required. Install a continuous running exhaust fan to the outside and a vent to provide conditioned air supply from the floor above. Exhaust fan must supply 1 ACH when crawlspace floor is covered by moisture barrier and the passive exterior vents blocked. For example, for a 1000 sq. ft. crawlspace with 3.5 feet between ground and floor deck, a fan should exhaust 58 cfm.. There must be one vent providing the supply of conditioned air per 250 sq ft of crawl space. Each vent requires a minimum of 3.6 sq. in. and maximum 4.4 sq. in. hole sizes. 2. Sealed moisture barrier installation when specified will be performed as follows. Use only materials equivalent or better than Ravines Industries, 15 mill polypropylene, ASTM #E1745 Class C Requirements. Double sealing all 3 foot overlaps with two sided approved tape, run the polypropylene 12 inches up the foundation walls, seal to wall using two sided tape and mechanical fasteners through C channel 2 foot on center. Cut and remove excess poly at the top of the C channel.

17 References The following reference materials were used to develop this report: Institute of Inspection Cleaning and Restoration Certification, (3 rd Edition April 2006) IICRC S500 Standards of Reference for Professional Water Damage Restoration Institute of Inspection Cleaning and Restoration Certification, Vancouver, WA. Institute of Inspection Cleaning and Restoration Certification, (1 st Addition December 2003) IICRC S520 Standard and Reference Guide for Professional Mold Remediation Institute of Inspection Cleaning and Restoration Certification, Vancouver, WA. Indoor Environmental Standards Organization, (2 nd Edition June 2003) Standards of Practice for the Assessment of Indoor Environmental Quality, Volume 1: Mold Sampling; Assessment of Mold Contamination. Indoor Environmental Standards Organization, Rockville, MD. United States Environmental Protection Agency (2001). Mold Remediation in schools, and Commercial buildings (EPA Publication No ). Washington, DC: US Environmental Protection Agency. New York City Department of Health (2000) Guidelines on Assessment and Remediation of Fungi in Indoor Environments. New York City Department of Health. Institute of Inspection Cleaning and Restoration Certification (2003) Standard and Reference Guide for Professional Mold Remediation (IICRC S520 Publication) Vancouver, WA: Institute of Inspection Cleaning and Restoration Certification. Macher, J. (Ed.). (1999). Bioaerosols: Assessment and Control. Cincinnati: America Conference of Governmental Industrial Hygienists. Dillion, H.K., Heinsohn, P.A. & Miller, J.D. (Eds.). (1996). Field Guide for the Determination of Biological Contaminates in Environmental Samples> Fairfax, VA: American Industrial Hygiene Association. ASRAE Standard , Ventilation for Acceptable Indoor Air Quality, American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc., Atlanta, GA The Case for Conditioned, Unvented Crawlspaces by Peter Yost and Ann Edminster, Building Safety Journal, May 2003 Recommended Moisture Control Amendments to the IRC from the Colorado ICC Chapter (Sept 2003 draft); and Guidelines for Design and Construction of New Homes with Below-Grade Underfloor Spaces from the Moisture Management Task Force, September 2003 draft. Colorado Amendments to the IRC: Require a fan rated for 44,000 hours (5 years) of continuous operation with flex connections or other installation detailing to reduce vibration and noise associated with the fan. The fan must be connected to a trouble light or an alarm to signal occupants when the fan fails.

18 Schaan Environmental Testing (SET) assumes no liability for any loss, injury, claim or damages arising directly or indirectly from any use or reliance on this report or the opinions expressed herein. SET makes no risk assessment, warranty, guarantee or insurance policies of any kind, express or implied. This report is limited only to the samples taken and locations sampled. There are no risk assessments, warranties, guarantees, or insurance available or provided by SET. Additional sampling may be needed to further identify other pollutants, or other mold/fungus affected areas inside the property. This report was prepared pursuant to the contract SET has with the client. That contractual relationship included an exchange of information about the subject property that was unique and between SET and its client and serves as the basis upon which this report was prepared. Because of the importance of the communication between SET and its client, reliance or any use of this report by anyone other than the client, for whom it was prepared, is prohibited and therefore not foreseeable to SET. No warranty is made. SET liability and that of contractors and subcontractors arising from any service rendered hereunder shall not exceed the total fee paid by the client to SET. Thank you for the opportunity to work with you on this project. Please call me at if you have any questions. Sincerely, Michael Schaan, WLS Schaan Environmental Testing Water Loss Specialist #0043 Certified Mold Inspector and Assessor

19 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc August 4, 2015 Mike Schaan Schaan Environmental Testing 9795 Quay Loop Westminster CO Laboratory Code: RES Subcontract Number: NA Laboratory Report: RES Project # / P.O. # Project Description: UCD AMC Building 402 Dear Customer, Reservoirs Environmental, Inc. is an analytical laboratory accredited for the analysis of pathogenic, non-pathogenic and environmental microorganisms by the American Industrial Hygiene Association, Lab ID Accreditation Certificate #480. The laboratory is currently proficient in both EMPAT and FOODLAP programs. Reservoirs has analyzed the following sample(s) per your request. The analysis has been completed in general accordance with the appropriate methodology as stated in the analysis table. Reported sample results were not blank corrected. Results have been sent to your office. RES is the job number assigned to this study. This report is considered highly confidential and the sole property of the customer. Reservoirs Environmental, Inc. will not discuss any part of this study with personnel other than those of the client. The results described in this report only apply to the samples analyzed. This report shall not be reproduced except in full, without written approval from Reservoirs Environmental, Inc. Samples will be disposed of after sixty days unless longer storage is requested. If you have any questions about this report, please feel free to call Sincerely, Jeanne Spencer President P: F: Logan Street, Suite 100 Denver, CO Page 1 of RESI-ENV

20 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: A1 Outdoor Control Sample M1 West Stairwell M2 S M3 S M4 S Lab ID Number: Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 8 ND 100 ND 100 ND 100 ND Alternaria ND 100 ND 100 ND Arthrinium 100 ND 8 ND 100 ND 100 ND 100 ND Ascospores - Non-Specified ND 100 ND Aspergillus/Penicillium - Like ND 100 ND 100 ND Basidiospores - Non-Specified ND Bipolaris/Drechslera - Like 100 ND 8 ND 100 ND 100 ND 100 ND Botrytis 100 ND 8 ND 100 ND 100 ND 100 ND Cercospora-like 100 ND 8 ND 100 ND 100 ND 100 ND Chaetomium 100 ND 8 ND 100 ND 100 ND 100 ND Cladosporium ND 100 ND Curvularia 100 ND 8 ND 100 ND 100 ND 100 ND Epicoccum 100 ND 8 ND 100 ND 100 ND 100 ND Fusarium 100 ND 8 ND 100 ND 100 ND 100 ND Ganoderma 100 ND 8 ND 100 ND 100 ND 100 ND Memnoniella 100 ND 8 ND 100 ND 100 ND 100 ND Myxomycetes / Periconia / Smuts / Rusts ND Nigrospora 100 ND 8 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 8 ND 100 ND 100 ND 100 ND Pestalotiopsis / Pestalotia 100 ND 8 ND 100 ND 100 ND 100 ND Pithomyces 100 ND 8 ND 100 ND 100 ND 100 ND Paeciliomyces 100 ND ND 100 ND 100 ND Spegazzinia 100 ND 8 ND 100 ND 100 ND 100 ND Stachybotrys 100 ND 8 ND 100 ND 100 ND 100 ND Tetraploa 100 ND 8 ND 100 ND 100 ND 100 ND Torula 100 ND 8 ND 100 ND 100 ND 100 ND Trichoderma-like 100 ND 8 ND 100 ND 100 ND 100 ND Ulocladium / Stemphylium 100 ND 8 ND 100 ND 100 ND 100 ND Non-specified spore 100 ND 8 ND 100 ND 100 ND 100 ND Hyphal Fragments 100 ND 8 ND 100 ND 100 ND 100 ND Pollen 100 ND 8 ND 100 ND 100 ND 100 ND Analytical Sensitivity Background Debris Total Spores/M Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 2 of RESI-ENV

21 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: A1 Outdoor Control Sample M5 S M6 S M7 S M8 S M9 S Lab ID Number: Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Alternaria ND 100 ND 100 ND 100 ND Arthrinium 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Ascospores - Non-Specified ND 100 ND ND Aspergillus/Penicillium - Like ND 100 ND 100 ND 100 ND Basidiospores - Non-Specified Bipolaris/Drechslera - Like 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Botrytis 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Cercospora-like 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Chaetomium 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Cladosporium ND Curvularia 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Epicoccum 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Fusarium 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Ganoderma 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Memnoniella 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Myxomycetes / Periconia / Smuts / Rusts ND Nigrospora 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Pestalotiopsis / Pestalotia 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Pithomyces 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Scopulariopsis 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Spegazzinia 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Stachybotrys 100 ND 8 ND 100 ND 100 ND ND Tetraploa 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Torula 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Trichoderma-like 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Ulocladium / Stemphylium 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Non-specified spore 100 ND 8 ND ND 100 ND Hyphal Fragments 100 ND 8 ND 100 ND 100 ND 100 ND 100 ND Pollen 100 ND 8 ND ND 100 ND 100 ND Analytical Sensitivity Background Debris Total Spores/M , Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 3 of RESI-ENV

22 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: A1 Outdoor Control Sample M10 S M11 S M12 S M13 S M14 S Lab ID Number: Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Count Spores/M 3 Alternaria ND 100 ND 100 ND 100 ND 100 ND Arthrinium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ascospores - Non-Specified ND 100 ND 100 ND Aspergillus/Penicillium - Like ND 100 ND 100 ND 100 ND 100 ND Basidiospores - Non-Specified ND Bipolaris/Drechslera - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Botrytis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cercospora-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Chaetomium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cladosporium ND ND Curvularia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Epicoccum 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Fusarium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ganoderma 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Memnoniella 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Myxomycetes / Periconia / Smuts / Rusts Nigrospora 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pestalotiopsis / Pestalotia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pithomyces 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Scopulariopsis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Spegazzinia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Stachybotrys 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Tetraploa 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Torula 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Trichoderma-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ulocladium / Stemphylium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Non-specified spore 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Hyphal Fragments 100 ND 100 ND ND ND Pollen 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Analytical Sensitivity Background Debris Total Spores/M Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 4 of RESI-ENV

23 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: A1 Outdoor Control Sample M15 S M16 S M17 S M18 S M19 S Lab ID Number: Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Alternaria ND 100 ND ND 100 ND Arthrinium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ascospores - Non-Specified ND 100 ND ND Aspergillus/Penicillium - Like ND 100 ND 100 ND 100 ND 100 ND Basidiospores - Non-Specified Bipolaris/Drechslera - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Botrytis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cercospora-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Chaetomium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cladosporium ND 100 ND Curvularia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Epicoccum 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Fusarium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ganoderma 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Memnoniella 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Myxomycetes / Periconia / Smuts / Rusts Nigrospora 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pestalotiopsis / Pestalotia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pithomyces 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Scopulariopsis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Spegazzinia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Stachybotrys 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Tetraploa 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Torula 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Trichoderma-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ulocladium / Stemphylium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Non-specified spore 100 ND 100 ND 100 ND 100 ND ND Hyphal Fragments 100 ND ND 100 ND 100 ND Pollen 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Analytical Sensitivity Background Debris Total Spores/M Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 5 of RESI-ENV

24 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: A1 Outdoor Control Sample M20 S M21 East Stairwell M22 S M23 S M24 S Lab ID Number: Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Alternaria ND ND 100 ND Arthrinium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ascospores - Non-Specified ND Aspergillus/Penicillium - Like ND 100 ND 100 ND 100 ND Basidiospores - Non-Specified Bipolaris/Drechslera - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Botrytis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cercospora-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Chaetomium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cladosporium ND Curvularia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Epicoccum 100 ND 100 ND ND 100 ND 100 ND Fusarium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ganoderma 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Memnoniella 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Myxomycetes / Periconia / Smuts / Rusts ND Nigrospora 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pestalotiopsis / Pestalotia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pithomyces 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Scopulariopsis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Spegazzinia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Stachybotrys 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Tetraploa 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Torula 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Trichoderma-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ulocladium / Stemphylium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Non-specified spore 100 ND 100 ND 100 ND 100 ND 100 ND Hyphal Fragments 100 ND 100 ND ND ND Pollen 100 ND 100 ND 100 ND 100 ND 100 ND Analytical Sensitivity Background Debris Total Spores/M ,240 Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 6 of RESI-ENV

25 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: Lab ID Number: A1 Outdoor Control Sample M25 S M26 S M27 S M28 S M29 S Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Alternaria ND Arthrinium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ascospores - Non-Specified ND 100 ND ND Aspergillus/Penicillium - Like ND 100 ND 100 ND 100 ND Basidiospores - Non-Specified Bipolaris/Drechslera - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Botrytis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cercospora-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Chaetomium 100 ND 100 ND 100 ND ND 100 ND Cladosporium Curvularia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Epicoccum 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Fusarium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ganoderma 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Memnoniella 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Myxomycetes / Periconia / Smuts / Rusts Nigrospora 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pestalotiopsis / Pestalotia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pithomyces 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Scopulariopsis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Spegazzinia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Stachybotrys 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Tetraploa 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Torula 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Trichoderma-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ulocladium / Stemphylium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Non-specified spore 100 ND ND ND 100 ND Hyphal Fragments 100 ND 100 ND 100 ND 100 ND 100 ND Pollen 100 ND 100 ND ND 100 ND 100 ND Analytical Sensitivity Background Debris Total Spores/M , Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 7 of RESI-ENV

26 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: Lab ID Number: A1 Outdoor Control Sample M30 S M31 S M32 S M33 S M34 S Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Alternaria ND 100 ND ND 100 ND Arthrinium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ascospores - Non-Specified ND 100 ND 100 ND 100 ND 100 ND Aspergillus/Penicillium - Like ND 100 ND 100 ND ND Basidiospores - Non-Specified ND Bipolaris/Drechslera - Like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Botrytis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cercospora-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Chaetomium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Cladosporium ND ND Curvularia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Epicoccum 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Fusarium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ganoderma 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Memnoniella 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Myxomycetes / Periconia / Smuts / Rusts Nigrospora 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pestalotiopsis / Pestalotia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Pithomyces 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Scopulariopsis 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Spegazzinia 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Stachybotrys 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Tetraploa 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Torula 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Trichoderma-like 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Ulocladium / Stemphylium 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Non-specified spore 100 ND 100 ND 100 ND ND 100 ND Hyphal Fragments 100 ND 100 ND ND 100 ND Pollen 100 ND 100 ND 100 ND 100 ND 100 ND 100 ND Analytical Sensitivity Background Debris Total Spores/M Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 8 of RESI-ENV

27 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: Lab ID Number: A1 Outdoor Control Sample M35 S M36 S M37 S M38 S WC-1 S North Wall Sample Volume (liters) 5 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Alternaria ND 100 ND 100 ND 100 ND 5 ND Arthrinium 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Ascospores - Non-Specified ND 100 ND ND Aspergillus/Penicillium - Like ND 100 ND 100 ND 100 ND Basidiospores - Non-Specified ND Bipolaris/Drechslera - Like 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Botrytis 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Cercospora-like 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Chaetomium 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Cladosporium ND ND 5 ND Curvularia 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Epicoccum 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Fusarium 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Ganoderma 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Memnoniella 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Myxomycetes / Periconia / Smuts / Rusts ND Nigrospora 100 ND 100 ND 100 ND 100 ND 100 ND Oidium (powder mildew) 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Pestalotiopsis / Pestalotia 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Pithomyces 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Scopulariopsis 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Spegazzinia 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Stachybotrys 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Tetraploa 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Torula 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Trichoderma-like 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Ulocladium / Stemphylium 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Non-specified spore 100 ND ND ND Hyphal Fragments 100 ND ND 100 ND 5 ND Pollen 100 ND 100 ND 100 ND 100 ND 100 ND 5 ND Analytical Sensitivity Background Debris Total Spores/M ,000 Total Comments * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 9 of RESI-ENV

28 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Spore Trap Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Spore Trap, Non-Viable Methodology Allergenco D 48 Hour JOE Client ID Number: Lab ID Number: A1 Outdoor Control Sample WC-2 S West Wall WC-3 S North Wall WC-4 S West Wall Sample Volume (liters) Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Count Spores/M 3 Acremonium - Like 100 ND 100 ND 100 ND ND Alternaria ND 100 ND ND Arthrinium 100 ND 100 ND 100 ND ND Ascospores - Non-Specified ND 100 ND ND Aspergillus/Penicillium - Like ND ND Basidiospores - Non-Specified ND 100 ND Present Bipolaris/Drechslera - Like 100 ND 100 ND 100 ND ND Botrytis 100 ND 100 ND 100 ND ND Cercospora-like 100 ND 100 ND 100 ND ND Chaetomium 100 ND 100 ND 100 ND ND Cladosporium ND 100 ND Present Curvularia 100 ND 100 ND 100 ND ND Epicoccum 100 ND 100 ND 100 ND ND Fusarium 100 ND 100 ND 100 ND ND Ganoderma 100 ND 100 ND 100 ND ND Memnoniella 100 ND 100 ND 100 ND ND Myxomycetes / Periconia / Smuts / Rusts ND 100 ND Present Nigrospora 100 ND 100 ND 100 ND ND Oidium (powder mildew) 100 ND 100 ND 100 ND ND Pestalotiopsis / Pestalotia 100 ND 100 ND 100 ND ND Pithomyces 100 ND 100 ND 100 ND ND Scopulariopsis 100 ND 100 ND 100 ND ND Spegazzinia 100 ND 100 ND 100 ND ND Stachybotrys 100 ND 100 ND 100 ND ND Tetraploa 100 ND 100 ND 100 ND ND Torula 100 ND 100 ND 100 ND ND Trichoderma-like 100 ND 100 ND 100 ND ND Ulocladium / Stemphylium 100 ND 100 ND 100 ND ND Non-specified spore 100 ND 100 ND 100 ND ND Hyphal Fragments 100 ND 100 ND 100 ND Present Pollen 100 ND 100 ND 100 ND ND Analytical Sensitivity Background Debris Total Spores/M ND N/A Total N/A Comments CBR-Excessive Debris CBR=Cannot be Read due to excessive Debris analyzed Presence/Absence * Sample analyses have not been blank corrected. ND = Not Detected NA = Not Common Allergen TNTC = Too Numerous To Count Water Loss Indicator Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 10 of RESI-ENV

29 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc RESERVOIRS ENVIRONMENTAL, INC Logan St. Suite 100, Denver CO, AIHA EMPAT # RES Job Number: Client: Client Project Number / P.O.: Client Project Description: Date Samples Received: Date Samples : Date Sampled: Analysis Type: Turnaround: Analyst: RES Schaan Environmental Testing UCD AMC Building 402 August 4, 2015 Direct Examination, Non-Viable Methodology 48 Hour JOE Client ID Number: Swab 1 Swab 2 Swab 3 Swab 4 Swab 5 Lab ID Number: Sample Type: Swab Swab Swab Swab Swab Description/Location Small Crawlspace East Crawlspace East Crawlspace East Crawlspace East Crawlspace Observations: Observations: Observations: Observations: Observations: Alternaria Ascospores - Non-Specified Few Aspergillus Moderate (Aspergillis Niger) Basidiospores - Non-Specified Bipolaris / Drechslera / Helminthosporium / Exserohilium Cladosporium Few Few Infrequent Myxomycete / Periconia / Smust / Rusts Few Few Penicillium Stachybotrys Abundant Hyphal Fragments Abundant Few Few Few Chaetomium Few Petreilla Few Other Other Comments: Evidence of Fungal Growth No Evidence of Fungal Growth No Evidence of Fungal Growth Possible Fungal Growth in Vicinity No Evidence of Fungal Growth Common Allergen Water Loss Indicator * Sample analyses have not been blank corrected. ND = Not Detected NA = Not TNTC = Too Numerous To Count Minimum Reporting Limit (MRL) = 1 Cell Analyst / Data QA: P: F: Logan Street, Suite 100 Denver, CO Page 11 of RESI-ENV

30 Reservoirs Environmental, Inc. Reservoirs Environmental QA Manual ANALYTICAL INFORMATION Effective January 1, 2014 T:\QAQC\Lab\Reservoirs Environmental QA Manual.doc Spore traps are a sampling devices that collect aeroallergens such as pollens, mold and fungal spores, fibers, dander, insect components and other air-borne contaminates. Samples are analyzed using light microscopy at 600X magnification with the entire sample trace or a percentage of the trace is counted. The results include both viable and non-viable fungal spores. This technique does not allow for the differentiation between Aspergillus and Penicillium spores. Small (1-3um) spherical fungal spores that cannot be identified and may included Aspergillus, Penicillium and Paecilomyces and others. Sample traces with greater than 500 spores per slide are difficult to count accurately due to overcrowding and should be considered estimations. Excessive nonmicrobial particulate debris can mask the presence of fungal spores, thereby reducing counting accuracies. All samples are graded with the following debris scale for data qualification. Background Debris Rating Description 0 No Particles Detected 1 2 Minimal non-microbial debris present. Up to 25 of the slide occluded with particulate debris AIHA EMPAT # Interpretation No particles were observed on slide. The absence of particulates could indicate improper sampling, as most air samples typically contain some particulate Reported values are not affected by debris Particulate debris could mask the presence of spores but do not provide significant interference with the analyses 3 4 CBR 26 to 50 of the slide occluded with particulate debris 51 to 90 of the slide occluded with particulate debris Cannot Be Read Particulate debris could mask the presence of spores and begin to interfere with the analytical count. As a result actual values could be somewhat higher than reported. Particulate debris are heavy and would mask the presence of some fungal spores if present. As a result, the count could be higher than reported. Sample could not be read due to excessive debris. Spores observed on the perimeter of debris are reported as present or abundant. The sample should be collected at shorter time interval or other measures taken to reduce the collection of nonmicrobial debris. P: F: Qualitative Reporting Limits Infrequent Occasional Moderate Abundant Description 1 to 5 Structures per 22 x 22 mm 5 to 50 Structures per 22 x 22 mm 1 to 10 Structures per Field of View 10+ Structures per Field of View 5801 Logan Street, Suite 100 Denver, CO Page 12 of RESI-ENV

31

32

33

34

35

BADLANDS ENVIRONMENTAL CONSULTANTS, INC E. Central Ave. Bismarck, ND (701) AIR MONITORING & SAMPLE ANALYSIS REPORT

BADLANDS ENVIRONMENTAL CONSULTANTS, INC E. Central Ave. Bismarck, ND (701) AIR MONITORING & SAMPLE ANALYSIS REPORT BADLANDS ENVIRONMENTAL CONSULTANTS, INC. 1006 E. Central Ave. Bismarck, ND 58501 (701) 223-7335 AIR MONITORING & SAMPLE ANALYSIS REPORT CLIENT: LOCATION: ND DOT ND DOT Admin Building Bismarck, ND BEC #:

More information

2. provide data indicating what types and sizes of particles are not removed by used PHEAF devices, and

2. provide data indicating what types and sizes of particles are not removed by used PHEAF devices, and Comparison of In-Field Efficiency of 3 Different Types of Portable HEPA filter Equipment by Laser Particle Counter, Condensation Particle Counter and Light Microscopy Particle Counting. This study was

More information

TAM International, Inc. QI Visible Magnetic Particle Inspection

TAM International, Inc. QI Visible Magnetic Particle Inspection TAM International, Inc. QI-8.2.4-12 Visible Magnetic Particle Inspection Approved by Quality Assurance Manager Signature/Date: Greg Fletcher Reviewed by Sr. Quality Analyst Signature/Date: Thomas Young

More information

User Guide. Pall Laboratory Manifold. For laboratory use. Not for use in a manner other than indicated. Introduction. Regulatory References

User Guide. Pall Laboratory Manifold. For laboratory use. Not for use in a manner other than indicated. Introduction. Regulatory References www.pall.com/lab User Guide Pall Laboratory Manifold For laboratory use. Not for use in a manner other than indicated. Introduction Application and Intended Use The membrane filtration (MF) technique is

More information

<800> Hazardous Drugs Handling in Healthcare Settings. Jeanne Sun, PharmD

<800> Hazardous Drugs Handling in Healthcare Settings. Jeanne Sun, PharmD Hazardous Drugs Handling in Healthcare Settings Jeanne Sun, PharmD Purpose of Approximately 8 million healthcare workers in the United States are potentially exposed to hazardous drugs (HDs)

More information

To facilitate the extension of departmental services through third party testing organizations as provided for by CRS (b)

To facilitate the extension of departmental services through third party testing organizations as provided for by CRS (b) DEPARTMENT OF REVENUE Division of Motor Vehicles MOTORCYCLE RULES AND REGULATIONS FOR ALMOST ORGANIZATIONS 1 CCR 204-20 [Editor s Notes follow the text of the rules at the end of this CCR Document.] A.

More information

Renewable Fuels Association One Massachusetts Ave. NW Suite 820 Washington, DC Telephone: (202) Fax: (202)

Renewable Fuels Association One Massachusetts Ave. NW Suite 820 Washington, DC Telephone: (202) Fax: (202) Guidelines for Establishing Ethanol Plant Quality Assurance and Quality Control Programs Renewable Fuels Association One Massachusetts Ave. NW Suite 820 Washington, DC 20001 Telephone: (202) 289-3835 Fax:

More information

City of Hammond Purchasing Department RFP # General Maintenance and Repair Service Contract City Generators

City of Hammond Purchasing Department RFP # General Maintenance and Repair Service Contract City Generators 1 City of Hammond Purchasing Department RFP # 15-33 General Maintenance and Repair Service Contract City Generators Proposals Shall Be Received by the Purchasing Department, City of Hammond 310 East Charles

More information

Installation and Maintenance Manual CORRUGATED RIVETED GALVANIZED STEEL WATER STORAGE TANKS

Installation and Maintenance Manual CORRUGATED RIVETED GALVANIZED STEEL WATER STORAGE TANKS BH TANK A Division Of American Tank Co., Inc. Installation and Maintenance Manual CORRUGATED RIVETED GALVANIZED STEEL WATER STORAGE TANKS American Tank Co., Inc. P.O. Box 340 Windsor CA 95492 www.bhtank.com

More information

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume PennBarry Fan Guide Specification Laboratory Exhaust System: Model vplume This document 2018 PennBarry vplume is a commercial lab exhaust fan that ensures a greater margin of safety by effectively dispersing

More information

Denver Office 8361 S. Sangre De Cristo Road, Suite 120 Littleton, CO Phone Fax May 28, 2013

Denver Office 8361 S. Sangre De Cristo Road, Suite 120 Littleton, CO Phone Fax May 28, 2013 Denver Office 8361 S. Sangre De Cristo Road, Suite 120 Littleton, CO 80127 Phone 303.468.8763 Fax 303.904.2038 May 28, 2013 Mr. Moe Alcaron Denver Public Schools 1350 E. 33 rd Avenue Denver, Colorado 80205

More information

DEPARTMENT OF STATE POLICE TRAFFIC SAFETY DIVISION TESTS FOR BREATH ALCOHOL

DEPARTMENT OF STATE POLICE TRAFFIC SAFETY DIVISION TESTS FOR BREATH ALCOHOL DEPARTMENT OF STATE POLICE TRAFFIC SAFETY DIVISION TESTS FOR BREATH ALCOHOL (By authority conferred on the department of state police by section 190 of 1945 PA 327, MCL 259.190, and section 625a of 1949

More information

---:...-- Environmental Health & Safety RADIATION PROCEDURES MANUAL. Procedure Cover Sheet. Procedure Number: EHS REV 2

---:...-- Environmental Health & Safety RADIATION PROCEDURES MANUAL. Procedure Cover Sheet. Procedure Number: EHS REV 2 Environmental Health & Safety RADIATION PROCEDURES MANUAL Procedure Cover Sheet Procedure Title: Fume Hoods Procedure Number: EHS-08-03-REV 2 Effective Date: 18 September, 2018 ---:...-- Approved By_-=--------::.--...l~---

More information

SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING CLASS SCHEDULE

SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING CLASS SCHEDULE SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING CLASS SCHEDULE CVOP Day Class 2013 Monday through Thursday 7AM to 6PM -6 weeks PTD/DDC Day Defensive Driving Course Schedule January 7 - February 14 February

More information

Bench fume hood with horizontal sash - 14" working sash height. Bench fume hood with vertical sliding doors 14" working gap between doors

Bench fume hood with horizontal sash - 14 working sash height. Bench fume hood with vertical sliding doors 14 working gap between doors UNIVERSITY OF HOUSTON ENVIRONMENTAL HEALTH AND SAFETY POLICIES AND PROCEDURES SECTION: SUBJECT: ENVIRONMENTAL HEALTH AND SAFETY LABORATORY FUME HOODS I. PURPOSE These laboratory fume hood survey procedures

More information

AIR FILTRATION DEVICE

AIR FILTRATION DEVICE AIR FILTRATION DEVICE Operating instructions (ENG) MODEL: 10079020 Read these instructions before using the machine. 86337980-F 01/12/12 Machine Data Label Overview The Triad AFD (Air Filtration Device)

More information

Underground Storage Tank Guidance for Commercial Building Inspectors

Underground Storage Tank Guidance for Commercial Building Inspectors National Association of Commercial Building Inspectors & Thermographers Contributor/Author: John Bowman The content provided in these white papers is intended solely for general information purposes only,

More information

SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 *

SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 * SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 * PRODUCT: Polymer (Foam-Filled) Fuel Cells 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards

More information

microns microns 70% 85%

microns microns 70% 85% For over 30 years the KETCHaire Filter has been recognized regionally for its premium high efficiency multi pleat and disposable panel air filtration products and its support of the ASHRAE Standard 52.2

More information

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-PL18398-02-01 according to DIN EN ISO/IEC 17025:2005 Period of validity: 26.02.2018 to 25.02.2023 Holder of certificate: SAL

More information

SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING CLASS SCHEDULE

SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING CLASS SCHEDULE SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING CLASS SCHEDULE CVOP Day Class 2013 Monday through Thursday 7AM to 6PM -6 weeks PTD/DDC Day Defensive Driving Course Schedule January 7 - February 14 February

More information

Omniaire 1000V Instruction Manual-8/05

Omniaire 1000V Instruction Manual-8/05 The OMNIAIRE 1000V HEPA Air Filtration system is a variable speed HEPAfiltered negative air machine designed for removal of toxic mold, asbestos or other airborne contaminants during construction, renovation

More information

6/18/2015. USP <800> Update. USP <800> - What is it? What are HDs? John Voliva, R.Ph. Director of Legislative Relations PCCA

6/18/2015. USP <800> Update. USP <800> - What is it? What are HDs? John Voliva, R.Ph. Director of Legislative Relations PCCA USP Update John Voliva, R.Ph. Director of Legislative Relations PCCA USP - What is it? Proposed Chapter Published April 2014, Revised and Re-Published December 2014 Covers the handling of hazardous

More information

Multistage Air Filtration Systems Instruction Manual

Multistage Air Filtration Systems Instruction Manual Multistage Air Filtration Systems Instruction Manual Be sure to read through this manual for proper use and safety. You must be familiar with the Safety Instructions before using this product. Please keep

More information

SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING 2018 CLASS SCHEDULE

SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING 2018 CLASS SCHEDULE SAN JACINTO COLLEGE COMMERCIAL TRUCK DRIVING 2018 CLASS SCHEDULE CVOP Day Class 2018 Monday through Thursday 7AM to 6PM -6 weeks PTD/DDC Day Defensive Driving Course Schedule January 2 - February 8 January

More information

WSB clean: Installation Manual

WSB clean: Installation Manual WSB clean: Installation Manual Models: WSB 400 WSB 1250 WSB 500 WSB 1500 WSB 600 WSB 1600 WSB 750 WSB 1800 WSB 1000 TABLE OF CONTENTS 1 INTRODUCTION...3 2 SAFETY INFORMATION...3 3 WSB CLEAN SYSTEM OPERATION...4

More information

DEPAUL UNIVERSITY. Fume Hoods Manual. Environmental Health & Safety. April 2017

DEPAUL UNIVERSITY. Fume Hoods Manual. Environmental Health & Safety. April 2017 DEPAUL UNIVERSITY Fume Hoods Manual Environmental Health & Safety April 2017 1 TABLE OF CONTENTS SECTION PAGE NO. 1. INTRODUCTION 2 2. TYPES OF FUME HOODS 2 2.1 CONVENTIONAL FUME HOODS 2 2.2 HIGH PERFORMANCE

More information

Miracle State Of The Art Air Filtration System!

Miracle State Of The Art Air Filtration System! I N D O O R A I R Q U A L I T Y S O L U T I O N S Miracle State Of The Art Air Filtration System! High efficiency particulate (HEPA) filter combined with optimized sorbent media provides the ultimate solution

More information

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST

FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL WHO CAN PERFORM THE TEST FACTS ABOUT: MARYLAND CONTAINMENT SUMP TESTING PROTOCOL On January 26, 2005, the Maryland Department of the Environment (the Department) implemented, in the Code of Maryland Regulations (COMAR) 26.10,

More information

GUIDELINE FOR GLOVEBOXES THIRD EDITION AGS-G001 February 2007

GUIDELINE FOR GLOVEBOXES THIRD EDITION AGS-G001 February 2007 GUIDELINE FOR GLOVEBOXES THIRD EDITION AGS-G001 February 2007 AMERICAN GLOVEBOX SOCIETY STANDARDS DEVELOPMENT COMMITTEE All Rights Reserved Copyright 2007 No portion may be duplicated without written consent

More information

Wash Facility Assessment

Wash Facility Assessment Business Name Operator's Name Assessment Date Assessor's Name Area validated, select (Site) (Bay) Describe Wash Facility Assessment Staff and Training high risk practice recommendation for risk management

More information

Position Paper. Telehandler Use: Lifting Suspended Loads

Position Paper. Telehandler Use: Lifting Suspended Loads Position Paper Telehandler Use: Lifting Suspended Loads The following paper reflects the considered opinion on the Crane Association of New Zealand (Inc.) This document has been prepared by the Technical

More information

Forensic Sciences Chapter ALABAMA DEPARTMENT OF FORENSIC SCIENCES ADMINISTRATIVE CODE CHAPTER IGNITION INTERLOCK RULES

Forensic Sciences Chapter ALABAMA DEPARTMENT OF FORENSIC SCIENCES ADMINISTRATIVE CODE CHAPTER IGNITION INTERLOCK RULES Forensic Sciences Chapter 370-3-1 ALABAMA DEPARTMENT OF FORENSIC SCIENCES ADMINISTRATIVE CODE CHAPTER 370-3-1 IGNITION INTERLOCK RULES TABLE OF CONTENTS 370-3-1-.01 Ignition Interlock Rules 370-3-1-.01

More information

ecognition of Prior Learning (RPL)

ecognition of Prior Learning (RPL) ecognition of Prior Learning (RPL) EVIDENCE GUIDE FOR INSPECT AND LUBRICATE AN AUTOMOTIVE SYSTEM Evidence Guide inspect and lubricate an automotive system Page 1 of 15 National Certificate in Professional

More information

Protector Glove Boxes.

Protector Glove Boxes. Protector Glove Boxes www.labconco.com Glove Boxes, An Overview The purpose of a glove box is to provide a physical barrier. Depending on the type of glove box, the physical barrier may be: Isolating a

More information

MODEL 950C-NP-UV Installation and Owners Manual

MODEL 950C-NP-UV Installation and Owners Manual MODEL 950C-NP-UV Installation and Owners Manual Further Information: BERRIMAN ASSOCIATES 1-800-480-3630 www.berriman.com Thank you for purchasing the MODEL 950-C-NP-UV medical grade air purification system

More information

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA

SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA August, 2018 Infrared Inspection Report SYSCO Oklahoma LLC 1350 West Tecumseh Road Norman, Oklahoma, 73069 Company Contact Chris Hill Project: 03210818 2605 CHARTER

More information

S02. MAGNETIC PARTICLE TESTING

S02. MAGNETIC PARTICLE TESTING S02.1 Scope This procedure is for the examination of ferromagnetic surface and near surface indications in stressed areas of welds, drilling or production equipment, or as a prove up technique. Both wet

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program Medford Area Public School District 124 West State St School District: Medford, WI 54451 715 748 4620 Review Date(s): January 2018 Program Dave Makovsky Coordinator: Purpose and

More information

MERV Filter Models for Aerobiological Applications. W.J. Kowalski, PE, PhD W.P. Bahnfleth, PE, PhD The Pennsylvania State University

MERV Filter Models for Aerobiological Applications. W.J. Kowalski, PE, PhD W.P. Bahnfleth, PE, PhD The Pennsylvania State University MERV Filter Models for Aerobiological Applications W.J. Kowalski, PE, PhD W.P. Bahnfleth, PE, PhD The Pennsylvania State University Recent concerns about bioterrorism and existing concerns about indoor

More information

FAN POWERED HEPA FILTER UNIT

FAN POWERED HEPA FILTER UNIT READ COMPLETELY AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE FAN POWERED HEPA FILTER UNIT (MOTOR ACCESSIBLE) SSLFHFD-FP-MA INSTALLATION AND SERVICE MANUAL 2 Critical operation conditions of the Fan

More information

Compressed Natural Gas Vehicle Fuel System Inspection Guidance

Compressed Natural Gas Vehicle Fuel System Inspection Guidance Prepared by NGVAmerica Technology & Development Committee Fuel System Inspection Working Group Compressed Natural Gas Vehicle Fuel System Inspection Guidance Disclaimer LEGAL NOTICE: NGVAmerica makes great

More information

Pennsylvania DEP Aboveground Storage Tank Facility Visits NISTM PA CONFERENCE Washington, PA May 18, 2017

Pennsylvania DEP Aboveground Storage Tank Facility Visits NISTM PA CONFERENCE Washington, PA May 18, 2017 Pennsylvania DEP Aboveground Storage Tank Facility Visits 2017 NISTM PA CONFERENCE Washington, PA May 18, 2017 What one may expect Documentation review Tank system visual assessment Follow-up PADEP AST

More information

HEPA FILTERED AIR FILTRATION EQUIPMENT MAY NOT BE HEPA FILTERED

HEPA FILTERED AIR FILTRATION EQUIPMENT MAY NOT BE HEPA FILTERED HEPA FILTERED AIR FILTRATION EQUIPMENT MAY NOT BE HEPA FILTERED I recently attended the EIA meeting in LV. During this meeting, there was a very interesting presentation on in field testing of HEPA filters

More information

WELCOME TO THE FAMILY OF GENESIS SUPREME RV OWNERS!

WELCOME TO THE FAMILY OF GENESIS SUPREME RV OWNERS! WELCOME TO THE FAMILY OF GENESIS SUPREME RV OWNERS! This Owner s Guide describes many features and components of your RV. It is intended to help you operate, care for and maintain your RV. We have tried

More information

CYCLO OIL LLC Used Oil Re-refining Plant

CYCLO OIL LLC Used Oil Re-refining Plant CYCLO OIL LLC Used Oil Re-refining Plant Several countries have put in place policies and plans to manage the disposal of their used oil to product their environment. Unfortunately the appropriate management

More information

Submittal Requirements for Product Evaluation - Doors

Submittal Requirements for Product Evaluation - Doors TEXAS DEPARTMENT OF INSURANCE Engineering Services / MC 103-3A 333 Guadalupe Street P.O. Box 149104 Austin, Texas 78714-9104 Phone No. (512) 322-2212 Fax No. (512) 463-6693 Submittal Requirements for Product

More information

Revision 4, Maine Yankee s License Termination Plan

Revision 4, Maine Yankee s License Termination Plan October 15, 2004 MN-04-051 RA-04-095 UNITED STATES NUCLEAR REGULATORY COMMISSION Attention: Document Control Desk Washington, DC 20555 References: 1. License No. DPR-36 (Docket No. 50-309) 2. MYAPC Letter

More information

ENGINEERING STANDARD STANDARD NO: PAGE 1 OF 9 DATE: 4/15/04 REVISION: 4 HEPA FILTER REQUIREMENTS

ENGINEERING STANDARD STANDARD NO: PAGE 1 OF 9 DATE: 4/15/04 REVISION: 4 HEPA FILTER REQUIREMENTS HEPA FILTER REQUIREMENTS ENGINEERING STANDARD STANDARD NO: 15888 PAGE 1 OF 9 DATE: 4/15/04 REVISION: 4 FILTRATION TECHNICAL COMMITTEE Approved by: T. M. Monahon, Signature on File Chairman, Engineering

More information

Nilfisk-CFM SS Vapor Vacuum Instructions for Use and Spare Parts Manual

Nilfisk-CFM SS Vapor Vacuum Instructions for Use and Spare Parts Manual Nilfisk-CFM SS Vapor Vacuum Instructions for Use and Spare Parts Manual Caution: This Nilfisk-CFM vacuum cleaner is not to be used in explosion hazardous areas as serious injury could result. Your new

More information

SFI SPECIFICATION 6.3 EFFECTIVE: FEBRUARY 26, 2014 *

SFI SPECIFICATION 6.3 EFFECTIVE: FEBRUARY 26, 2014 * SFI SPECIFICATION 6.3 EFFECTIVE: FEBRUARY 26, 2014 * PRODUCT: Containment Bellhousing for SFI Clutch Assemblies for supercharged and nitrous-oxide applications 1.0 GENERAL INFORMATION 1.1 This SFI Specification

More information

QUEENS LIBRARY BUILDINGS AND GROUNDS COMMITTEE THURSDAY, DECEMBER 21, Central Library Merrick Blvd., Jamaica, NY AGENDA

QUEENS LIBRARY BUILDINGS AND GROUNDS COMMITTEE THURSDAY, DECEMBER 21, Central Library Merrick Blvd., Jamaica, NY AGENDA QUEENS LIBRARY BUILDINGS AND GROUNDS COMMITTEE THURSDAY, DECEMBER 21, 2017 Central Library 89-11 Merrick Blvd., Jamaica, NY 11432 AGENDA 6:00 PM BUILDINGS AND GROUNDS COMMITTEE REGULAR MEETING I. Call

More information

PIP REEE003 Guidelines for General Purpose Non-Lubricated Flexible Couplings

PIP REEE003 Guidelines for General Purpose Non-Lubricated Flexible Couplings September 2016 Machinery PIP REEE003 Guidelines for General Purpose Non-Lubricated Flexible Couplings PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry

More information

2-1/4 Gallon Sprayer

2-1/4 Gallon Sprayer 2-/4 Gallon Sprayer 94008 ASSEMBLY AND OPERATING INSTRUCTIONS 349 Mission Oaks Blvd., Camarillo, CA 930 Visit our Web site at http://www.harborfreight.com Copyright 2005 by Harbor Freight Tools. All rights

More information

DYNAMIC PILE TESTING 10/26/ General.

DYNAMIC PILE TESTING 10/26/ General. te: The MoDOT LRFD Bridge Design Manual indicates that the frequency of dynamic pile testing should be 1 to 10% of the number of piles. Additionally, the frequency of initial driving tests and restrike

More information

Bioprocessing Equipment

Bioprocessing Equipment ASME BPE-2007 (Revision of ASME BPE-2005) Bioprocessing Equipment A N I N T E R N A T I O N A L S T A N D A R D ASME BPE-2007 (Revision of ASME BPE-2005) Bioprocessing Equipment AN AMERICAN NATIONAL STANDARD

More information

WELCOME. Important Safety Instructions...2. Technical Specifications...2. Parts Description...3. Operating Instructions...4

WELCOME. Important Safety Instructions...2. Technical Specifications...2. Parts Description...3. Operating Instructions...4 WELCOME Congratulations! You are now the proud owner of one of the most advanced and effective room air cleaners available. Your new Defender helps reduce the many problem-causing pollutants and allergens

More information

SECTION 1 - APPLICANT INFORMATION. 1) Legal Name: 2) Mailing Address: 3) Physical Address (if different from mailing address):

SECTION 1 - APPLICANT INFORMATION. 1) Legal Name: 2) Mailing Address: 3) Physical Address (if different from mailing address): 150 CSR 27 FORM 1 Application for CRTS Permit (PSC Use Only) January1, through December 31, PSC Permit No.: ProcessedBy: SECTION 1 - APPLICANT INFORMATION 1) Legal Name: 2) Mailing Address: 3) Physical

More information

CompoundingToday.com. GAP ANALYSIS - USP <800> Effective Date: 7/1/18

CompoundingToday.com. GAP ANALYSIS - USP <800> Effective Date: 7/1/18 CompoundingToday.com GAP ANALYSIS - USP Effective Date: 7/1/18 2 - Hazardous Drug (HD) List A list of hazardous drugs based on NIOSH List has been created. A process is in place to review this list

More information

1301: Out-of-service, closure-in-place, permanent removal, change-in-service, and closure assessment of UST systems.

1301: Out-of-service, closure-in-place, permanent removal, change-in-service, and closure assessment of UST systems. 1301:7-9-12 Out-of-service, closure-in-place, permanent removal, change-in-service, and closure assessment of UST systems. (A) Purpose and scope. For the purpose of prescribing rules pursuant to section

More information

Northeast Autonomous and Connected Vehicle Summit

Northeast Autonomous and Connected Vehicle Summit Northeast Autonomous and Connected Vehicle Summit June 12, 2018 Cathie Curtis, Director, Vehicle Programs AAMVA 1 1 Founded in 1933, the American Association of Motor Vehicle Administrators (AAMVA) represents

More information

Risk Management of Rail Vehicle Axle Bearings

Risk Management of Rail Vehicle Axle Bearings Railway Group Standard Risk Management of Rail Vehicle Axle Bearings Synopsis This Railway Group Standard mandates that there shall be riskbased processes to minimise and detect failures of rail vehicle

More information

SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA

SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA November, 2017 Infrared Inspection Report Sysco Indianapolis LLC. 4000 West 62nd Street Indianapolis, Indiana, 46268 Company Contact: Trevor Gray Project: 05161117

More information

X-3400A, X-3500, X-3700 OWNER S MANUAL PLEASE READ AND SAVE THESE INSTRUCTIONS

X-3400A, X-3500, X-3700 OWNER S MANUAL PLEASE READ AND SAVE THESE INSTRUCTIONS X-3400A, X-3500, X-3700 OWNER S MANUAL XPOWER MANUFACTURE, INC. 220 Clary Avenue San Gabriel, CA 91776, USA Tel: 626-285-3301, Fax: 626-285-330 PLEASE READ AND SAVE THESE INSTRUCTIONS 1 Index Introduction...2

More information

SFI SPECIFICATION 27.1 EFFECTIVE: OCTOBER 11, 2006 *

SFI SPECIFICATION 27.1 EFFECTIVE: OCTOBER 11, 2006 * SFI SPECIFICATION 27.1 EFFECTIVE: OCTOBER 11, 2006 * PRODUCT: Window Nets 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards for evaluating and

More information

TRADE EXPERIENCE LOG BOOK CANADIAN PETROLEUM CONTRACTORS ASSOCIATION. Petroleum Mechanic Training & Certification

TRADE EXPERIENCE LOG BOOK CANADIAN PETROLEUM CONTRACTORS ASSOCIATION. Petroleum Mechanic Training & Certification CANADIAN PETROLEUM CONTRACTORS ASSOCIATION Petroleum Mechanic Training & Certification TRADE EXPERIENCE LOG BOOK PM1 - Service & Maintenance PM2 - Underground Installation PM3 - Aboveground Installation

More information

Annex to the accreditation certificate D-PL according to DIN EN ISO/IEC 17025: and council directives 90/385/EWG 2 and 93/42/EWG 3

Annex to the accreditation certificate D-PL according to DIN EN ISO/IEC 17025: and council directives 90/385/EWG 2 and 93/42/EWG 3 Deutsche Akkreditierungsstelle GmbH Annex to the accreditation certificate D-PL-13422-01-02 according to DIN EN ISO/IEC 17025:2005 1 and council directives 90/385/EWG 2 and 93/42/EWG 3 Period of validity:

More information

Energized Electrical Work

Energized Electrical Work Manitoba STANDARD PROCEDURE INSTRUCTION Title Energized Electrical Work Department Supersedes SPI Dated N/A SPI 32-4 Effective Date MAR 30, 2012 Energized Electrical Work SPI 32-4 Page 1 of 9 STANDARD

More information

INVESTIGATION REPORT PREPARED FOR: UNIVERSITY OF NORTHERN IOWA CEDAR FALLS, IA

INVESTIGATION REPORT PREPARED FOR: UNIVERSITY OF NORTHERN IOWA CEDAR FALLS, IA INVESTIGATION REPORT PREPARED FOR: UNIVERSITY OF NORTHERN IOWA CEDAR FALLS, IA Prepared By: HBK Engineering, LLC. 921 West Van Buren Street, Suite 100 Chicago, IL HBK PROJECT # 18 0788 October 2, 2018

More information

SFI SPECIFICATION 1.2 EFFECTIVE: FEBRUARY 9, 2006* PRODUCT: Multiple Disc Clutch Assemblies for Vehicles with Naturally Aspirated Engines

SFI SPECIFICATION 1.2 EFFECTIVE: FEBRUARY 9, 2006* PRODUCT: Multiple Disc Clutch Assemblies for Vehicles with Naturally Aspirated Engines SFI SPECIFICATION 1.2 EFFECTIVE: FEBRUARY 9, 2006* PRODUCT: Multiple Disc Clutch Assemblies for Vehicles with Naturally Aspirated Engines 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes

More information

NAVSEA REVIEWED ASTM F-718. Part A: MS-200 / MS209R D. Gray / MS207R Green / MS205R Red / MS201R White / MS203R Yellow / MS218H Part B

NAVSEA REVIEWED ASTM F-718. Part A: MS-200 / MS209R D. Gray / MS207R Green / MS205R Red / MS201R White / MS203R Yellow / MS218H Part B ASTM F-718 ITW Engineered Polymers, American Safety Technologies (AST) MS-200 Acrylic Epoxy Color Topping PRODUCT DESIGNATIONS Part A: MS-200 / MS209R D. Gray / MS207R Green / MS205R Red / MS201R White

More information

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c.

56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM. Test Report EN : TA11/0004c. 56 LESLIE HOUGH WAY SALFORD GREATER MANCHESTER M6 6AJ UNITED KINGDOM Email: testing@inspec-international.com Website: www.inspec-international.com Tel: +44 (0) 16 17 37 06 99 Fax: +44 (0) 16 17 36 01 01

More information

THIS BULLETIN MODIFIES THE A4A BULLETIN , DATED DECEMBER 11, 2017

THIS BULLETIN MODIFIES THE A4A BULLETIN , DATED DECEMBER 11, 2017 Bulletin 2018.1 Update on ATA103 Requirements June 5, 2018 THIS BULLETIN MODIFIES THE A4A BULLETIN 2017.2, DATED DECEMBER 11, 2017 Based on feedback from the industry, A4A is modifying the deadlines for

More information

Industry guidance on monitoring and control of microbial contamination in the aviation fuel supply chain

Industry guidance on monitoring and control of microbial contamination in the aviation fuel supply chain Industry guidance on monitoring and control of microbial contamination in the aviation fuel supply chain DLA Energy Worldwide Energy Conference Gaylord Convention Center April 11th 2017 Leon O Malley,

More information

Model G14SD Vapor Management System

Model G14SD Vapor Management System Instruction Manual Model G14SD Vapor Management System (For Models: DSD and SSD 110/115v) Manufactured in USA for Medivators Reprocessing Systems by: PCI Medical Inc. 12 Bridge Street, PO Box 188 Deep

More information

Fume Hood Program. Program originated: 08/2008 Updated: 06/2016. Gordon Krueger Environmental Safety Specialist

Fume Hood Program. Program originated: 08/2008 Updated: 06/2016. Gordon Krueger Environmental Safety Specialist Fume Hood Program Program originated: 08/2008 Updated: 06/2016 Gordon Krueger Environmental Safety Specialist 1 TABLE OF CONTENTS I. INTRODUCTION 3 II. LABORATORY VENTILATION 3 A. Chemical Fume Hood Types

More information

Important Safety Instructions...2. Technical Specifications...2. Parts Description...3. Operating Instructions...4. Programming Instructions...

Important Safety Instructions...2. Technical Specifications...2. Parts Description...3. Operating Instructions...4. Programming Instructions... Welcome Congratulations! You are now the proud owner of one of the most advanced and effective medical recirculating air cleaners available. Your new FilterQueen Defender helps reduce the many problem-causing

More information

SFI SPECIFICATION 4.2 EFFECTIVE: OCTOBER 26, 1994*

SFI SPECIFICATION 4.2 EFFECTIVE: OCTOBER 26, 1994* SFI SPECIFICATION 4.2 EFFECTIVE: OCTOBER 26, 1994* PRODUCT: Tractor Blankets 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards for evaluating

More information

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: G4212.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight with Curb SERIES/MODEL: Specials Dome Skylight 0.118 thickness PC smooth/0.118 thickness

More information

Internal Audit Report. Fuel Consumption Oversight and Coordination TxDOT Internal Audit Division

Internal Audit Report. Fuel Consumption Oversight and Coordination TxDOT Internal Audit Division Internal Audit Report Fuel Consumption Oversight and Coordination TxDOT Internal Audit Division Objective To determine if a process exists to ensure retail fuel consumption is appropriately managed and

More information

Guidelines for Filming in The City of Vernon. General Requirements

Guidelines for Filming in The City of Vernon. General Requirements Guidelines for Filming in The City of Vernon The City of Vernon, a primarily industrial city, provides a wide range of services to the Entertainment Industry as a means of maintaining and expanding the

More information

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA

Lorri Grainawi Steel Tank Institute. PA NISTM April 25, 2013 Harrisburg, PA Lorri Grainawi Steel Tank Institute PA NISTM April 25, 2013 Harrisburg, PA PEI/RP1200-12 ------------------------------------------------------ 1. Introduction 2. Definitions 3. Safety 4. Tank Secondary

More information

Tissue Master. User Manual

Tissue Master. User Manual Tissue Master User Manual This page left blank intentionally This manual is a guide for the use of the Omni International Tissue Master and accessories. Data herein has been verified and validated. It

More information

USP 800: Quick Summary

USP 800: Quick Summary SCSHP 2014 Fall Meeting Why USP 800: Quick Summary Natasha Nicol, Pharm D, FASHP Director, Medication Safety Cardinal Health Chapter builds on the standards established by existing compounding chapters

More information

Speed Evaluation Saw Mill Drive

Speed Evaluation Saw Mill Drive Speed Evaluation Saw Mill Drive Prepared for: Mount Laurel Township Burlington County, New Jersey Prepared by: Dana Litwornia Litwornia & Associates, Inc. Transportation, Traffic & Environmental Engineering

More information

Powered Industrial Trucks

Powered Industrial Trucks INDIANA UNIVERSITY-PURDUE UNIVERSITY at INDIANAPOLIS IUPUI Department of Environmental Health and Safety 620 Union Drive, Room 043, Indianapolis, Indiana 46202 Powered Industrial Trucks Purpose and Background

More information

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING Third Revised Sheet 55a Cancels Second Revised Sheet 55a A. ELIGIBLE CUSTOMER-GENERATOR RULE NO. 17 NET ENERGY METERING Net energy metering is available to eligible customer-generators, defined as, permanent

More information

SFI SPECIFICATION 6.1 EFFECTIVE: FEBRUARY 26, 2014 *

SFI SPECIFICATION 6.1 EFFECTIVE: FEBRUARY 26, 2014 * SFI SPECIFICATION 6.1 EFFECTIVE: FEBRUARY 26, 2014 * PRODUCT: Containment Bellhousing for SFI 1.1 & 1.2 Clutch Assemblies for limited normally aspirated applications, and forced induction applications

More information

AstroCel. Better Air is Our Business ss. High Efficiency Particulate Air Filters (HEPA) Ultra Low Penetration Air Filters (ULPA)

AstroCel. Better Air is Our Business ss. High Efficiency Particulate Air Filters (HEPA) Ultra Low Penetration Air Filters (ULPA) AstroCel I High Efficiency Particulate Air Filters (HEPA) Ultra Low Penetration Air Filters (ULPA) Available with Antimicrobial Better Air is Our Business ss AstroCel I High Efficiency Particulate Air

More information

PSPC Guideline & its effect

PSPC Guideline & its effect 1 Guideline & its effect 2007. 10. 19. Guideline 2 Content 3 History & Progress Inspector Primary Surface Preparation Edge grinding Steel preparation Secondary Surface Preparation Surface Preparation after

More information

Policy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620

Policy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620 Policy Bulletin No. 25 Net Metering Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620 Interconnection Standards For Residential Net Energy Metering With Electric

More information

CRYSTAL-AIRE. concealed commercial air cleaners

CRYSTAL-AIRE. concealed commercial air cleaners CRYSTAL-AIRE concealed commercial air cleaners CRYSTAL-AIRE A Customized CONCEPT IN Concealed AIR CLEANING. Using a variety of accessories, Crystal-Aire can be adapted to most building configurations and

More information

UC Irvine Environmental Health & Safety SECTION: TITLE: Powered Industrial Truck (Forklift) Safety Program

UC Irvine Environmental Health & Safety SECTION: TITLE: Powered Industrial Truck (Forklift) Safety Program UC Irvine Environmental Health & Safety SECTION: TITLE: Powered Industrial Truck (Forklift) Safety Program INITIATOR: Desirée Villarreal REVISION DATE: 10/17/2014 1. Program Description 2. Scope 3. Definitions

More information

MIFACE INVESTIGATION #06MI209

MIFACE INVESTIGATION #06MI209 MIFACE INVESTIGATION #06MI209 SUBJECT: Heavy Equipment Operator Dies After Being Pinned Between the Boom and Cab of an Excavator Summary On December 4, 2006, a 51-year-old male heavy equipment operator

More information

Appendix C: Biosafety Cabinet Specifications C-2. Product Service

Appendix C: Biosafety Cabinet Specifications C-2. Product Service Appendix C: Biosafety Cabinet Specifications C-2 102 Appendix C: Biosafety Cabinet Specifications C-3 103 Appendix C: Biosafety Cabinet Specifications C-4 104 Appendix C: Biosafety Cabinet Specifications

More information

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: Sept 27, 2013 REVISED DATE: NA

REPORT NUMBER: MID-001 ORIGINAL ISSUE DATE: Sept 27, 2013 REVISED DATE: NA REPORT NUMBER: 101351744MID-001 ORIGINAL ISSUE DATE: Sept 27, 2013 REVISED DATE: NA TEST REPORT EVALUATION CENTER Intertek Verification Center 8431 Murphy Dr Middleton, WI 53562 x RENDERED TO Marc Doheny

More information

SECTION 14: AERIAL LIFT PROGRAM

SECTION 14: AERIAL LIFT PROGRAM SECTION 14: AERIAL LIFT PROGRAM Fisher Auto Parts is committed to promoting a safe and healthy environment for all employees and customers. Protection from accidental loss of any resources, especially

More information

SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 *

SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 * SFI SPECIFICATION 35.2 EFFECTIVE: DECEMBER 29, 2014 * PRODUCT: Heavy Duty Stock Car Steel Wheels 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards

More information

Fixed Ladder: A ladder that cannot be readily moved or carried because it is an integral part of a building or structure

Fixed Ladder: A ladder that cannot be readily moved or carried because it is an integral part of a building or structure Ladder Safety University of Tennessee Safety Guide GS-045 Document Contact: EHS-General Safety Date effective: May 1, 2013 Revision Date: May 1, 2013 Purpose The purpose of this procedure is to ensure

More information

Investigation into UK socket-outlets incorporating USB charging points

Investigation into UK socket-outlets incorporating USB charging points Investigation into UK socket-outlets incorporating USB charging points Electrical Safety First investigated a number of commercially available UK socket-outlets incorporating USB ports, as a repeat of

More information