ELECTRICAL SAFETY INSPECTION REPORT

Size: px
Start display at page:

Download "ELECTRICAL SAFETY INSPECTION REPORT"

Transcription

1 ELECTRICAL SAFETY INSPECTION REPORT APPLE KNITWEAR LTD. House 1, Road 1, Horinchala, Konabari, Gazipur GPS Coordinate: , Factory List: Apple knitwear Ltd. Inspected by Report Generated by : Md. Assaduzzaman : Md. Assaduzzaman Inspected on: October 25, 2016

2 SUMMARY The Factory was surveyed for electrical safety by Stichting Bangladesh Accord Foundation. The purpose of the survey was to identify significant electrical safety issues and to provide recommendations for remediation based on applicable standards specified by the Accord. Electrical Safety Audit is a methodical approach to evaluate potential electrical hazards and to recommend suggestions for improvement. The scope of this initial electrical safety inspection was limited to the review and identification of major electrical safety issues. The inspection did not include identification of minor deficiencies, which would be further dealt with as part of follow-up inspections. The information in this electrical safety inspection report was obtained during a visit to the facility and during discussion with local factory management. Services performed by the auditors are conducted in a manner consistent with that level of care and skill generally exercised by members of the engineering and auditing profession. However, an effort has made to discover all meaningful areas under the stipulated time available. In evaluating subject site, Inspector relies in good faith on information provided by factory management or employees. The Inspector assumes that the information provided is factual, accurate and accepts no responsibility for any deficiency, misstatement or inaccuracies contained in this report as a result of omission or misrepresentation of any person interviewed or contacted. The findings and recommendations in this report are not intended to imply, guarantee, ensure or warrant compliance with any government regulations. Additionally, the results do not imply in any way that compliance with the findings or recommendations as stated in this report will eliminate all risks or exposures not referred to in this report do not exist. Compliance with the findings and recommendations stated in this report does not relieve the factory owner from obligation to comply with specific project requirements, industry standards, or the provisions of any local government regulations. Apple knitwear Ltd. factory is established in its 4 story (G +3) rented building. As reported by the Factory Management, the building was constructed before 2005 and still under construction and the production began in September During the time of the Inspection, the factory accommodated a total of approx. 250 (single shifts) workers working on regular basis. The four storied (G+3) i.e. factory building is 48 feet tall and has a total floor area of approx sqft. Page 2 of 16

3 FINDINGS AND RECOMMENDATIONS The table below summarizes the major electrical hazards identified during the walk through inspection. Recommendations have been provided to each finding. The implementation schedule shall be developed by the factory to remediate each of the findings. The specific timing of improvements, including any requested extensions due to design / installation constraints, shall be submitted to the Accord for an approval. FINDING E - 1 DOCUMENTATION Electrical Single Line Diagram (SLD) is unavailable in the factory As built Electrical SLD must be prepared; it must have factory's whole electrical installation information. FINDING E - 2 LIGHTNING PROTECTION SYSTEM Lightning Protection System (LPS) drawing is unavailable Factory has to design Lightning Protection System (LPS) for the whole factory (where the Risk index is more than 40). Once a LPS is designed properly, installation must be done accordingly. Page 3 of 16

4 FINDING E - 3 TESTING & PERIODIC MAINTENANCE Insulation resistance record (cable information) doesn't match with field Field information must be reflected in the record and significantly lower sized cables' record shall be avoided FINDING E - 4 TESTING & PERIODIC MAINTENANCE Earth Pit resistance record doesn't match with field Adequate number of earth pits must be ensured (if it's lower in numbers) and record must be made accordingly. FINDING E - 5 TESTING & PERIODIC MAINTENANCE Thermography survey record is unavailable. Hot spots have been observed at some points. Thermography survey must be done at least twice in a year. Hot spots must be removed as soon as possible. P1 REMEDIATION TIME FRAME: IMMEDIATE Page 4 of 16

5 FINDING E - 6 DOCUMENTATION Electric safety training program has not initiated/conducted. Electrical safety training and awareness program for the electrical personnel must be initiated. It is a periodic task which factory has to continue to improve overall electrical safety situation for the staffs. FINDING E - 7 DOCUMENTATION 1) Personal Protective Equipment (PPE) for Electrical Work is not available. 2) Uninsulated electrical tools are used for breakdown and preventive maintenance 1) Personal Protective Equipment (PPE) must be arranged by the factory management team for the safety of their employee and worker. 2) For maintenance purposes all the electrical tools shall be properly insulated and these insulations shall be checked periodically. P3 FINDING E - 8 DOCUMENTATION There is no programmed schedule for periodical inspection & testing of electrical equipment. An electrical maintenance program shall be prepared which will include inspections and testing of the electrical systems (preventive and proactive) P3 Page 5 of 16

6 FINDING E - 9 GENERATOR ROOM Generator room is filled with debris (or used as temporary storage) Generator room must be kept neat and clean. REMEDIATION TIME FRAME: 1 MONTH FINDING E - 10 GENERATOR ROOM Lead acid battery terminals are left open & kept on wooden board Lead acid battery terminals must be covered/capped and rust must be checked and cleaned, use non-flammable case/shelf to store battery. FINDING E - 11 GENERATOR ROOM Water spillage has been observed in generator room. Any kind of water spillage/leakage must be stopped; and generator must be kept always dry. Page 6 of 16

7 FINDING E - 12 GENERATOR ROOM Generator body has been earthed by inadequate/improper sized (type) cable Two separate and distinct earth connection must be provided over generator. Equipment earthing cable size must be increased. The earth cable size shall be less than or equal to half of the phase cable (depends on fault clearing time). You may use equivalent sized bare copper conductor. FINDING E - 13 GENERATOR ROOM Mechanical guard is not provided to the rotating part of the generator. Provide adequate mechanical guard on the rotating part. P1 FINDING E - 14 EARTHING SYSTEM Pedestrian fan is using for generator cooling purpose Avoid using pedestrian/ceiling fan in generator room for cooling purpose; ensure adequate ventilation (cross ventilation) for the generator room Page 7 of 16

8 FINDING E - 15 CABLE & CABLE SUPPORTS Service cables from Grid network has inadequate support (or excessively sagged) Power service cables must be draw using cable tray/ladder (in case of overhead drawing); covering is required for LT cables. FINDING E - 16 Panel doors are not connected with earth. All metal installation which are part electrical system must be connected with earth to avoid electrical shock or electrocution. REMEDIATION TIME FRAME: 1 MONTH FINDING E - 17 No/Inadequate rubber (insulation) mat at the working area of distribution board/panel. Electrical insulation (not less than 3 mm thick in case of rubber mat) at the working area of each electrical installation (Transformer/LT panel/mdb/db/sdb/ other manual operated machineries) must be ensured. Page 8 of 16

9 FINDING E - 18 Distribution boards have no clear identification markings. All distribution boards, switchboards, sub main boards and switches shall be marked clearly for proper identification. FINDING E - 19 Loop connection has been used powering multiple circuits through MCB/MCCBs. Any kind of looped power connection must be avoided from electrical installation. REMEDIATION TIME FRAME: 1 MONTH FINDING E - 20 Multiple cables connected/terminated at the bus bar using single cable lug. Each power cable must be terminated at any point using single cable lug. Page 9 of 16

10 FINDING E - 21 Multiple cables (came from different electrical consumers) terminated at MCCB terminals/ Busbar. Each electrical circuit must be terminated at single MCB/MCCB and busbar terminals. FINDING E - 22 Cables terminated at electrical bus bar/mccb without cable lugs Terminate all the power/earth/neutral cable with proper sized cable lug FINDING E - 23 Oversized circuit breakers or Circuit breakers are not adjusted accordingly Adjust or replace all the MCCBs/MCBs according to cable ampacity (connected load). Avoid using different sized cable at the terminals P1 Page 10 of 16

11 FINDING E - 24 Unterminated live wire is kept inside the electrical panel/cable tray. All the unterminated live power cables must be removed as soon as possible. P1 REMEDIATION TIME FRAME: 1 MONTH FINDING E - 25 Cables in service are joined (splicing) between terminations. Splicing in the power cables shall be avoided; in unavoidable cases splicing must be made following proper guidance. FINDING E - 26 Phase barrier/separators are missing in the MCCB/MCB Phases must be separated by insulator (a rubber type no-flammable materials shall be used for it) P3 Page 11 of 16

12 FINDING E - 27 Earth lead cable/earth Continuity Conductor size is inadequate/undersize Earth lead cable/ Earth Continuity Conductor (ECC) must be resized by half of the phase cable. Cable size shall be selected depending on the CB's response time and phase cables' size. FINDING E - 28 Distribution Board's top/bottom is left open (typical issue) Each electrical distribution board/panel must be properly sealed to avoid ingression of fluffs; but an adequate ventilation system must also be ensured. FINDING E - 29 CABLE & CABLE SUPPORTS Power cables entering into or exiting from Distribution board/panel are not properly fixed. Power cables entering into or exiting from distribution board/panel must be fixed through Panel base/top plate using proper sized cable glands (metal/pvc). Page 12 of 16

13 FINDING E - 30 Inadequate working space around (or in front of) board/panels and access to the board/panels is obstacles At least 1 meter (or equal to the width of board/panel, whichever is higher) working clearance must be maintained in front of each electrical board/panel FINDING E - 31 Electrical distribution box/panels are full of fluffs (lint/dirt) Each electrical distribution board/panel must be properly sealed to avoid ingression of fluffs; but an adequate ventilation system must also be ensured. P3 REMEDIATION TIME FRAME: 1 MONTH FINDING E - 32 Combustible materials kept near distribution panel. In front of each distribution board, there shall have at least 1.07 m clearance around it. REMEDIATION TIME FRAME: 1 MONTH Page 13 of 16

14 FINDING E - 33 Distribution panel & PFI are not fixed with base properly. Firmly grout the panels permanently with foundation bolts. REMEDIATION TIME FRAME: 1 MONTH FINDING E - 34 CABLE RACEWAY & TRENCH Cable channel/duct terminals are left open for ingression of lint, dust or fluffs. cable ducts must be properly sealed to avoid ingression of any foreign particles. P3 REMEDIATION TIME FRAME: 1 MONTH FINDING E - 35 CABLE RACEWAY & TRENCH Wooden cable channel/ducts is used for power cable distribution. Metal type cable tray (perforated one is preferred) shall be used for distributing power cables Page 14 of 16

15 FINDING E - 36 CABLE RACEWAY & TRENCH Maintenance movement is obstacled due to improper cable channel/duct. Covered cable duct (close to floor-slab) must be equal to working floor height. If not, extended area must be sloped at both sides to avoid obstacle. P3 FINDING E - 37 CABLE RACEWAY & TRENCH Heat source (or exposed steam line) is adjacent to electrical installations (cable channel/duct) Heat source (or steam line) must be kept at least 0.9 meter apart from any electrical installation. In unavoidable case heat source, shall be covered by proper and adequate insulator. FINDING E - 38 EARTHING SYSTEM Manually operated machines (may have chance to be touched by operator/user) have no earth connection. Each manually operated machine (may have chance to be touched by user/operator) must have earth connection. Cable selection shall be made according to CB response and circuit's power demand. P1 Page 15 of 16

16 FINDING E - 39 WIRING SYSTEM Hazardous lights in store room / storage areas are uncovered. hazardous lights in store room / storage areas shall be covered by proper type material; or non-hazardous lights shall be installed in these areas. P1 FINDING E - 40 BOILER & COMPRESSOR Flexible PVC pipe is used to cover power and signal cable for boiler Power and signal cable for boilers shall be distributed using proper type insulator to avoid damage of cables. Page 16 of 16

ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION

ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION Chanmari, Fatullah, Narayanganj- 1400 GPS Coordinate:23.634239,90.496801 Inspected by Report Generated by : Noman Saber Khan & Shaik Muhammed Wasi

More information

ELECTRICAL SAFETY INSPECTION REPORT

ELECTRICAL SAFETY INSPECTION REPORT ELECTRICAL SAFETY INSPECTION REPORT ABSS HIGH TECH SWEATER LTD. Kalameshar, Board Bazar, Gazipur. Factory List: ABSS HIGH TECH SWEATER LTD. Inspected by Report Generated by : Hossain Shah Aarif : Mobassear

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

CAL/OSHA ELECTRICAL LOW VOLTAGE

CAL/OSHA ELECTRICAL LOW VOLTAGE Preparation: Safety Mgr Authority: CEO Issuing Dept: Safety Page: Page 1 of 7 Purpose The purpose of this program is to prevent injuries due to electrical exposure to low voltage (less than or equal to

More information

Surface Regulations and Policies

Surface Regulations and Policies Surface Regulations and Policies COAL FATALITIES 1970-2002 350 300 250 200 150 100 50 0 1970 1973 1976 1979 1982 1985 1988 1991 1994 1997 2000 From January 1, 1970 through today, a total of 240 coal miners

More information

Powered Industrial Trucks

Powered Industrial Trucks INDIANA UNIVERSITY-PURDUE UNIVERSITY at INDIANAPOLIS IUPUI Department of Environmental Health and Safety 620 Union Drive, Room 043, Indianapolis, Indiana 46202 Powered Industrial Trucks Purpose and Background

More information

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 PREPARED BY: Electricity System Operations Planning and Performance FINAL Disclaimer (a) Purpose - This report

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS

36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS 36-27-1. General. 1.1. Scope. -- Rules and Regulations Governing Surface Areas. 1.2.

More information

CONVEYOR REGULATIONS. AA COUTINHO Director Mine Safety

CONVEYOR REGULATIONS. AA COUTINHO Director Mine Safety CONVEYOR REGULATIONS AA COUTINHO Director Mine Safety CONTENTS 1. Accident» Fatalities» Injuries 2. Conveyor regulations 3. Way forward INJURIES-Fatalities 12 10 8 6 4 2 0 2002 2003 2004 2005 2006 2007

More information

Powered Industrial Vehicle Policy

Powered Industrial Vehicle Policy Powered Industrial Vehicle Policy Policy The Flight Department is committed to protecting employees from the hazards involved in the operation of powered industrial vehicles. This Policy is established

More information

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,

More information

Position Paper. Telehandler Use: Lifting Suspended Loads

Position Paper. Telehandler Use: Lifting Suspended Loads Position Paper Telehandler Use: Lifting Suspended Loads The following paper reflects the considered opinion on the Crane Association of New Zealand (Inc.) This document has been prepared by the Technical

More information

Construction and Wiring Guidelines for Ergon Energy Substation Panels

Construction and Wiring Guidelines for Ergon Energy Substation Panels Construction and Wiring Guidelines for Ergon Energy Substation Panels Table of Contents Purpose and Scope... 1 Responsibilities... 1 Definitions, Abbreviations and Acronyms... 1 References... 1 Panel Wiring...

More information

Technical Specifications

Technical Specifications LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for

More information

Wind and Temperature Tip Over Hazard Do not add notice boards or similar

Wind and Temperature Tip Over Hazard Do not add notice boards or similar Lift & Work Platform Safety Information Safety Information: Boom Lifts Safety Information: Scissor Lifts Safety Information: Boom Lifts Power Lines Electrocution Hazard Maintain safe clearance from Electrical

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons Page 1 Qualified Persons... 1 Safety Information... 2 Procedures... 3 Maintenance... 3 Security Inspection (Exterior)... 3 Verify Securing Devices... 3 Maintaining the Exterior... 3 Replacing Labels...

More information

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL

More information

Electric & Gas Service Requirements (Greenbook) Overview

Electric & Gas Service Requirements (Greenbook) Overview INTRODUCTION The Greenbook contents and standard documents are updated regularly to provide users with the most current information possible. In conjunction with this effort, the 2016 Greenbook was reviewed

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program Medford Area Public School District 124 West State St School District: Medford, WI 54451 715 748 4620 Review Date(s): January 2018 Program Dave Makovsky Coordinator: Purpose and

More information

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:

More information

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY

GUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

TEMPORARY ELECTRICAL SERVICE

TEMPORARY ELECTRICAL SERVICE ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us/energyservices TEMPORARY ELECTRICAL SERVICE A. INTRODUCTION

More information

RUTGERS UNIVERSITY POWERED INDUSTRIAL TRUCK PROGRAM

RUTGERS UNIVERSITY POWERED INDUSTRIAL TRUCK PROGRAM RUTGERS UNIVERSITY POWERED INDUSTRIAL TRUCK PROGRAM 9/01 1 TABLE OF CONTENTS POWERED INDUSTRIAL TRUCK PROGRAM A. PURPOSE AND SCOPE...1 B. LIFE TRUCK REQUIREMENTS...1 C. AREA REQUIREMENTS...2 D. RESPONSIBILITIES...2

More information

MAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT CS-OHS-32

MAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT CS-OHS-32 CS ENERGY OPERATIONS PROCEDURE FOR MAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL CS-OHS-32 Responsible Officer: Electrical Services Engineering Manager Error! Bookmark

More information

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9

2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9 8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

Electrical Hazards in Construction

Electrical Hazards in Construction Electrical Hazards in Construction WELCOME Tim Dawson Presentation developed by Dawson Safety Services - 2013 Dangers of Electrical Shock Currents above 10 ma* can paralyze or freeze muscles. Currents

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

120-ELECTRICAL SAFETY PROGRAM

120-ELECTRICAL SAFETY PROGRAM 120.1 PURPOSE A. To set forth procedures for the safe use of electrical equipment, tools, and appliances at Central New Mexico Community College (CNM). 120.2 SCOPE A. This program applies to all CNM employees

More information

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

1. Division 26 Section Elevator Shunt-Trip Fused Disconnect Switches. SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,

More information

Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition. Compliance Checklist.

Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition. Compliance Checklist. Australian Explosives Industry and Safety Group (AEISG) Code of Practice Mobile Processing Units 4 th edition Compliance Checklist Note: The requirements noted against the various sections in this checklist

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012 POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 PREPARED BY: Electricity System Operations Planning and Performance DATE: 5 June 2012 FINAL

More information

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS... TITLE SPECIFICATION FOR PORTABLE DATE: JULY 2006 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD...3 INTRODUCTION...4 1 SCOPE...4 2 NORMATIVE S...4 3 DEFINITIONS AND ABBIATIONS...4 4 REQUIREMENTS...5 4.1

More information

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0

More information

UNDERGROUND SERVICES - SECONDARY

UNDERGROUND SERVICES - SECONDARY UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service

More information

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1 INTRODUCTION READ AND UNDERSTAND

More information

Grounding Systems. Equipment Grounding & Grounded Conductors

Grounding Systems. Equipment Grounding & Grounded Conductors Grounding Systems Equipment Grounding & Grounded Conductors Definitions A Grounded or Earthed system is one that is connected to the earth Grounded Conductor is a conductor that normally carries current

More information

UC Irvine Environmental Health & Safety SECTION: TITLE: Powered Industrial Truck (Forklift) Safety Program

UC Irvine Environmental Health & Safety SECTION: TITLE: Powered Industrial Truck (Forklift) Safety Program UC Irvine Environmental Health & Safety SECTION: TITLE: Powered Industrial Truck (Forklift) Safety Program INITIATOR: Desirée Villarreal REVISION DATE: 10/17/2014 1. Program Description 2. Scope 3. Definitions

More information

PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE

PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE Page 1 of 6 1. SUMMARY... 3 1.1 USE OF PORTABLE ELECTRICAL EQUIPMENT... 3 1.2 FAULTY EQUIPMENT... 3 2. PURPOSE & SCOPE... 3 3. DEFINITIONS... 3 3.1

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

Approved Contractor Construction e-guide Residential Commercial

Approved Contractor Construction e-guide Residential Commercial Approved Contractor Construction e-guide Residential Commercial Clark Public Utilities PO Box 8900 Vancouver, WA 98668 (PAGE 2) TABLE OF CONTENTS PAGE Trenching 3 Wire 8 Single-Phase Transformer Set 13

More information

Section 02: Pre-Installation Procedures

Section 02: Pre-Installation Procedures Section 02: Pre-Installation Procedures Foundation! WARNING The MUST be placed on a surface that will support the combined weight of the, options, fixtures, and tooling, etc. (refer to the Specifications

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO KV BUSBAR ON 30 OCTOBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO KV BUSBAR ON 30 OCTOBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO.1 275 KV BUSBAR ON 30 OCTOBER 2011 PREPARED BY: Electricity System Operations Planning and Performance

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT All electrical systems and electrically energized equipment

More information

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program. Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative

More information

GETZ EQUIPMENT INNOVATORS SYSTEM DUST 120V ECONOMY PART NUMBER: 4G59542 OPERATING AND INSTRUCTION MANUAL

GETZ EQUIPMENT INNOVATORS SYSTEM DUST 120V ECONOMY PART NUMBER: 4G59542 OPERATING AND INSTRUCTION MANUAL GETZ EQUIPMENT INNOVATORS SYSTEM DUST 120V ECONOMY PART NUMBER: 4G59542 OPERATING AND INSTRUCTION MANUAL 2320 Lakecrest Drive, Pekin IL 61554 PH. (888) 747-4389 Fax (309) 495-0625 Website: www.getzequipment.com

More information

PART 10 ELECTRICAL INSTALLATIONS

PART 10 ELECTRICAL INSTALLATIONS PART 10 ELECTRICAL INSTALLATIONS SECTION SUBJECT 10.1 General 10.2 Cables 10.3 DC systems 10.4 Batteries 10.5 AC systems 10.6 Earthing and bonding 10.7 Motor control 10.8 Lighting 10.9 Remote stops 10.10

More information

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise Arc flash solutions catalogue Australia Safety solutions - Protecting employees and the enterprise The risk of an arc flash event is real An arc flash hazard is a proven significant and dangerous threat

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

RADIATION CONTROL - RADIATION SAFETY REQUIREMENTS FOR PARTICLE ACCELERATORS NOT USED IN THE HEALING ARTS

RADIATION CONTROL - RADIATION SAFETY REQUIREMENTS FOR PARTICLE ACCELERATORS NOT USED IN THE HEALING ARTS DEPARTMENT OF PUBLIC HEALTH AND ENVIRONMENT RADIATION CONTROL - RADIATION SAFETY REQUIREMENTS FOR PARTICLE ACCELERATORS NOT USED IN THE HEALING ARTS 6 CCR 1007-1 Part 09 [Editor s Notes follow the text

More information

Micro-OPLC Installation Guide

Micro-OPLC Installation Guide 4 mm (0.157") 117 mm (4.606") 7.5 mm (0.295") Jazz OPLC Micro-OPLC Installation Guide 6 Digital Inputs, 4 Relay Outputs 6 Digital, 2 Analog/Digital, 2 Analog Inputs, 6 Relay Outputs Before using this product,

More information

The Impact of the 18 th edition (BS 7671:2018)

The Impact of the 18 th edition (BS 7671:2018) The Impact of the 18 th edition (BS 7671:2018) In this article, Geoff Cronshaw looks at some of the proposed changes in the DPC (draft for public comment) for electrical installations, focusing on Section

More information

Load Side PV Connections

Load Side PV Connections Perspectives on PV Load Side PV Connections 705.12(D) in the 2014 NEC by John Wiles Through the exceptional efforts of the members of NFPA NEC Code-Making Panel 4 working with the proposals and comments

More information

CHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations

CHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations Only the Danish version is authentic Notice D II-1 D 1 October 2002 Technical regulation on the construction and equipment, etc. of passenger ships on domestic voyages CHAPTER II-1 D Construction subdivision

More information

The New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016

The New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016 The New 2017 National Electric Safety Code Overview and Significant Changes Presented by Mickey Gunter October 28, 2016 NESC Technical Subcommittees Subcommittee 1 Coordination, Definitions Subcommittee

More information

HI-POT/CONTINUITY TESTER Model PLEP01

HI-POT/CONTINUITY TESTER Model PLEP01 HI-POT/CONTINUITY TESTER Model PLEP01 Instruction Manual MITCHELL INSTRUMENT CO. Dear Customer: Congratulations! Mitchell Instrument Co. is please to present you with your Hipot/Continuity Tester. This

More information

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 REDUNDANT PROPULSION JANUARY 2003 This booklet includes the relevant amendments and corrections

More information

SUBSTATION DESIGN TRAINING

SUBSTATION DESIGN TRAINING 2017 SUBSTATION DESIGN TRAINING ADVANCE ELECTRICAL DESIGN & ENGINEERING INSITUTE (Registered under MSME& An ISO 9001:2008 CERTIFIED) Training Centre: Advance Group of Institutions C-1, Second Floor Near

More information

The Management of Electrical Safety in Quarries, Associated Plant and Equipment

The Management of Electrical Safety in Quarries, Associated Plant and Equipment Quarries National Joint Advisory Committee (QNJAC) Plant Information Sheet 1 (Version 1, November 2015, review date: 2020) The Management of Electrical Safety in Quarries, Associated Plant and Equipment

More information

SECTION VII METERING INSTALLATIONS

SECTION VII METERING INSTALLATIONS SECTION VII METERING INSTALLATIONS 1. GENERAL Outdoor metering is required for all new service installations to one, two, and three family detached, semi-detached and row houses. 2. COMPANY FURNISHES AND

More information

Solar PV General Introduction Guide for Electricians

Solar PV General Introduction Guide for Electricians Solar PV General Introduction Guide for Electricians Important Note: This guide was written to provide a broad guidance for electricians that would like to expand their product knowledge and skills for

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

AXUS AX High Temperature 300 C for 2hr, 400 C for 2 hour

AXUS AX High Temperature 300 C for 2hr, 400 C for 2 hour 1.0 Introduction The Nuaire Axus range of Long Cased Axial Flow Fans are produced in sixteen case sizes from 315mm dia. to 1600mm dia. with duties up to 65m3/s. Impellers are manufactured in aluminium

More information

Engineering Recommendation P26

Engineering Recommendation P26 Engineering Recommendation P26 The Estimation of the Maximum Prospective Short-Circuit Current for Three Phase 415V Supplies Document originally produced by the Electricity Association. 2003 Energy Networks

More information

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976 1 Title Chapter 14:08 Factories and Works (Electrical) Regulations, 1976 2 Interpretation of terms 3 Fencing and enclosure 4 Notices 5 Safety precautions 6 Switch-boards 7 Portable electric tools and lights

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.4 Important Safety Instructions Please save these instructions.

More information

Definitions. Exposed part. Live or energized part. De-energized part

Definitions. Exposed part. Live or energized part. De-energized part Electrical Safety Definitions Exposed part Live or energized part De-energized part 1a Definitions De-energized exposed parts that are not locked/tagged are considered to be energized exposed parts 1b

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

GETZ EQUIPMENT INNOVATORS SYSTEM DUST 120V ECONOMY PART NUMBER: 4G59542 OPERATING AND INSTRUCTION MANUAL

GETZ EQUIPMENT INNOVATORS SYSTEM DUST 120V ECONOMY PART NUMBER: 4G59542 OPERATING AND INSTRUCTION MANUAL GETZ EQUIPMENT INNOVATORS SYSTEM DUST 120V ECONOMY PART NUMBER: 4G59542 OPERATING AND INSTRUCTION MANUAL 2320 Lakecrest Drive, Pekin, Illinois 61554 Telephone: 888-747-4389 Fax: 309-495-0625 Website: www.getzequipment.com

More information

Consumer, Environmental and Health Technologies Biotechnology and Food Supply Chain. GUIDANCE DOCUMENT No. 1

Consumer, Environmental and Health Technologies Biotechnology and Food Supply Chain. GUIDANCE DOCUMENT No. 1 Ref. Ares(2016)5774004-05/10/2016 EUROPEAN COMMISSION Directorate-General for Internal Market, Industry, Entrepreneurship and SMEs Consumer, Environmental and Health Technologies Biotechnology and Food

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012

POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012 POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORT WEST TASMANIA ON 6 APRIL 2012 PREPARED BY: Systems Capability DATE: 28 September 2012 FINAL IN NORT WEST TASMANIA ON 6 APRIL 2012

More information

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI)

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Chapter 5 Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Imagine That Engineering Inc. has adopted this program for equipment

More information

Internal Audit Report. Fuel Consumption Oversight and Coordination TxDOT Internal Audit Division

Internal Audit Report. Fuel Consumption Oversight and Coordination TxDOT Internal Audit Division Internal Audit Report Fuel Consumption Oversight and Coordination TxDOT Internal Audit Division Objective To determine if a process exists to ensure retail fuel consumption is appropriately managed and

More information

Annex I Tested by (name + signature)...: Approved by (name + signature)...: Date of issue... : 22/11/2012. TUV RHEINLAND ITALIA S.r.l.

Annex I Tested by (name + signature)...: Approved by (name + signature)...: Date of issue... : 22/11/2012. TUV RHEINLAND ITALIA S.r.l. TEST REORT Rotating electrical machines art 5: Degrees of protection provided by the integral design of rotating electrical machines (I code) Classification Report Reference No....: 28105442 002 Annex

More information

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK

UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK UNDERSTANDING ELECTRICAL EQUIPMENT AND CONDITIONS OF INCREASED RISK 5 October 2017 John A. Weber Principal Electrical Engineer, Hartford Steam Boiler Inspection and Insurance Company Electrical Power Transmission

More information

KIUC Service Installation Manual

KIUC Service Installation Manual KIUC Service Installation Manual Second Edition (November 2016) This manual provides the general requirements for electric service and metering for Kauaʻi Island Utility Cooperative ("KIUC") and is meant

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

POWERED INDUSTRIAL TRUCK PROGRAM September 2015

POWERED INDUSTRIAL TRUCK PROGRAM September 2015 A. SCOPE AND APPLICATION POWERED INDUSTRIAL TRUCK PROGRAM September 2015 The Powered Industrial Truck Program is established in accordance with 29 CFR 1910.178, Powered Industrial Trucks, and describes

More information

33kV Connection up to 90MVA

33kV Connection up to 90MVA Electricity Specification 217 Issue 2 December 2007 33kV Connection up to 90MVA Contents 1 Scope 2 General 3 Connection Arrangements 4 Equipment Records 5 Documentation 6 Documents Referenced 7 Keywords

More information

Guidelines for Filming in The City of Vernon. General Requirements

Guidelines for Filming in The City of Vernon. General Requirements Guidelines for Filming in The City of Vernon The City of Vernon, a primarily industrial city, provides a wide range of services to the Entertainment Industry as a means of maintaining and expanding the

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

ATTACHMENT #1. TO: Patricia delabruere DATE: May 5, 2015 JNU Airport Manager

ATTACHMENT #1. TO: Patricia delabruere DATE: May 5, 2015 JNU Airport Manager MEMO TO: Patricia delabruere DATE: May 5, 2015 JNU Airport Manager FROM: RE: Catherine Fritz, AIA JNU Airport Architect ARFF Project Formulation The Airport Board s funding authorization on February 11,

More information

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2, THE FSS CODE AND RELATED FIRE TEST PROCEDURES

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2, THE FSS CODE AND RELATED FIRE TEST PROCEDURES INTERNATIONAL MARITIME ORGANIZATION E IMO SUB-COMMITTEE ON FIRE PROTECTION 48th session Agenda item 3 FP 48/3/2 10 October 2003 Original: ENGLISH UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2, THE FSS

More information

CHAPTER 10 ELECTRICAL. Notes:

CHAPTER 10 ELECTRICAL. Notes: CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic

More information

Investigation into UK socket-outlets incorporating USB charging points

Investigation into UK socket-outlets incorporating USB charging points Investigation into UK socket-outlets incorporating USB charging points Electrical Safety First investigated a number of commercially available UK socket-outlets incorporating USB ports, as a repeat of

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service. UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later

More information

Energized Electrical Work

Energized Electrical Work Manitoba STANDARD PROCEDURE INSTRUCTION Title Energized Electrical Work Department Supersedes SPI Dated N/A SPI 32-4 Effective Date MAR 30, 2012 Energized Electrical Work SPI 32-4 Page 1 of 9 STANDARD

More information

Metering and Service Installation:

Metering and Service Installation: Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...

More information

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2

REDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 REDUNDANT PROPULSION JANUARY 2011 CONTENTS PAGE Sec. 1 General Requirements... 4 Sec. 2 System

More information

ACI Hoist & Crane. Festoon System. 689 S.W. 7th Terrace Dania, FL (954) Fax (954) Toll Free A-HOIST ( )

ACI Hoist & Crane. Festoon System. 689 S.W. 7th Terrace Dania, FL (954) Fax (954) Toll Free A-HOIST ( ) ACI Hoist & Crane Festoon System 689 S.W. 7th Terrace Dania, FL 33004 (954) 921-1171 Fax (954) 921-7117 Toll Free 1-888-4-A-HOIST (1-888-424-6478) www.acihoist.com 2 Standard Duty C-Track Index 1. General

More information