ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION
|
|
- Allan Hunt
- 5 years ago
- Views:
Transcription
1 ELECTRICAL SAFETY INSPECTION REPORT WARN KNIT FASHION Chanmari, Fatullah, Narayanganj GPS Coordinate: , Inspected by Report Generated by : Noman Saber Khan & Shaik Muhammed Wasi : Noman Saber Khan & Shaik Muhammed Wasi Inspected on: December 4, 2016
2 SUMMARY The Factory was surveyed for electrical safety by Stichting Bangladesh Accord Foundation. The purpose of the survey was to identify significant electrical safety issues and to provide recommendations for remediation based on applicable standards specified by the Accord. Electrical Safety Audit is a methodical approach to evaluate potential electrical hazards and to recommend suggestions for improvement. The scope of this initial electrical safety inspection was limited to the review and identification of major electrical safety issues. The inspection did not include identification of minor deficiencies, which would be further dealt with as part of follow-up inspections. The findings and recommendations in this report are not intended to imply, guarantee, ensure or warrant compliance with any government regulations. Additionally, the results do not imply in any way that compliance with the findings or recommendations as stated in this report will eliminate all risks or exposures not referred to in this report do not exist. Compliance with the findings and recommendations stated in this report does not relieve the factory owner from obligation to comply with specific project requirements, industry standards, or the provisions of any local government regulations. Warn Knit Fashion factory is established in its 6 storied (G +5) building and a separate utility shed. The building is rented by Factory Management for 2 years and owned as personal property as reported by building management. Right now, 3 rd and 4 th is used as Warn Knit Fashion. 5 th Floor is used by difference factory named ARS Printing. Ground, 1 st and 2 nd floor is occupied by another factory named as Sun Knitwear. The building was constructed in 2004 as personal properties and the production began in November During the time of the Inspection, the factory accommodated a total of approx. 100 (Regular shift) workers working on regular basis. 1. FINDINGS AND RECOMMENDATIONS The table below summarizes the major electrical hazards identified during the walk-through inspection. Recommendations have been provided to each finding. The implementation schedule shall be developed by the factory to remediate each of the findings. The specific timing of improvements, including any requested extensions due to design / installation constraints, shall be submitted to the Accord for an approval. Page 2 of 12
3 FINDING E - 1 DOCUMENTATION Electrical Single Line Diagram (SLD) is unavailable in the factory As built Electrical SLD must be prepared; it must have factory's whole electrical installation information. FINDING E - 2 TESTING & PERIODIC MAINTENANCE Insulation resistance test of electrical power cables is not performed Insulation resistant test of all the cables must be performed once every 2-year cycle and recorded (this must require a complete power shut off) FINDING E - 3 TESTING & PERIODIC MAINTENANCE Thermography survey record is unavailable. Hot spots have been observed at some points. Thermography survey must be done and recorded at least twice in a year. Hot spots must be removed. Page 3 of 12
4 FINDING E - 4 TESTING & PERIODIC MAINTENANCE Earth Pit resistance record is unavailable. Number of earth pits must be increased; and all those shall be identifiable. And all earthing systems shall be tested for resistance on any dry day not less than once in every two years. A record of every earth test made and the result shall be kept for not less than two years and shall be available to the Inspector when required. FINDING E - 5 DOCUMENTATION Electric safety training program is not initiated/ conducted. Electrical safety training and awareness program for the electrical personnel must be initiated. It is a periodic task which factory has to continue to improve overall electrical safety situation for the staffs. FINDING E - 6 LIGHTNING PROTECTION SYSTEM Lightning Protection System (LPS) installation is not done. Factory has to design Lightning Protection System (LPS) for the whole factory (where the Risk index is more than 40). Once a LPS is designed properly, installation must be done accordingly asap. Page 4 of 12
5 FINDING E - 7 SUBSTATION ROOM Lead acid battery terminals are filled with rust and left open. Lead acid battery terminals must be covered/capped and rust must be cleaned. P3 FINDING E - 8 SUBSTATION ROOM Wooden cable channel/ducts are used for power cable distribution. Metal type cable tray (perforated one is preferred) shall be used for distributing power cables P3 FINDING E - 9 Cable channels are filled with fluffs (Lint/ dust). Cable channels must be kept neat and clean; these must be sealed properly thus no scope of ingression of fluffs. Page 5 of 12
6 FINDING E - 10 Power Cables are hanging without proper support. Power cables must be supported by cable tray (ladder- where needed). Outdoor arrangement must be covered. FINDING E - 11 Service cables from Grid network has inadequate support (or excessively sagged) Power service cables must be draw using cable tray/ladder (in case of overhead drawing); covering is required for LT cables. FINDING E - 12 Cables in service are joined (splicing) between terminations. Splicing in the power cables shall be avoided; in unavoidable cases splicing, must be made following proper guidance. Page 6 of 12
7 FINDING E - 13 Power cables entering or exiting from Distribution board/ panel are not properly fixed. Power cables entering or exiting from distribution board/panel must be fixed through Panel base/top plate using proper sized cable glands (metal/ PVC). P3 FINDING E - 14 Generator output cables (laid on floor) are not protected and supported Service cables from generator must be supported at its own breaker's terminal and with cable tray. FINDING E - 15 Magnetic ballast found inside the cable channel. Magnetic ballast shall not be kept inside of cable channel. Page 7 of 12
8 FINDING E - 16 MCCBs are not adjusted per load demand. All the MCCBs must be adjusted per cable current ampacity/load current; if adjustment is not possible, replacement will be the only way. FINDING E - 17 Panel doors are not connected with earth. All metal installation which are part of electrical system must be connected to earth to avoid electrical shock or electrocution. FINDING E - 18 Phase barrier/separators are missing in MCCBs Phases must be separated by insulator (a rubber type no-flammable materials shall be used for it) Page 8 of 12
9 FINDING E - 19 Distribution Board's top/bottom are not properly sealed (typical issue) Each electrical distribution board/panel must be properly sealed to avoid ingression of fluffs; but an adequate ventilation system must also be ensured. FINDING E - 20 Multiple cables (came from different electrical consumers) terminated at MCCB terminals Each electrical circuit must be terminated at single MCB/MCCB terminals. FINDING E - 21 No/ Inadequate rubber (insulation) mat at the working area of distribution board/panel. Electrical insulation (not less than 3 mm thick in case of rubber mat) at the working area of each electrical installation (LT panel / MDB / DB / SDB/ other manual operated machineries) must be ensured. Page 9 of 12
10 FINDING E - 22 Loop connection has been used powering multiple circuits through MCB/ MCCBs. Loop Connections shall be removed from entire electrical system. FINDING E - 23 Multiple cables connected in the MCCB terminal bus bar through single lugs. Each cable must be connected in the MCCB terminal / bus bar through single lugs. FINDING E - 24 Instruction for CPR (Cardiopulmonary Resuscitation) or Electrical shock restoration is not present CPR instruction shall be hanged near all electrical installations (LT panel, MDB, FDB, DB, SDB) at visible location Page 10 of 12
11 FINDING E - 25 Distribution boards have no clear identification markings. All distribution boards, switchboards, sub main boards and switches shall be marked clearly for proper identification. FINDING E - 26 EARTHING SYSTEM Manually operated machines (may have chance to be touched by operator/user) have no earth connection. Each manually operated machine (may have chance to be touched by user/operator) must have earth connection. Cable selection shall be made per CB response and circuit's power demand. FINDING E - 27 EARTHING SYSTEM Earth lead cable/earth Continuity Conductor size is inadequate/undersize Earth lead cable/ Earth Continuity Conductor (ECC) must be resized by half of the phase cable. Cable size shall be selected depending on the CB's response time and phase cables' size. Page 11 of 12
12 FINDING E - 28 BOILER & COMPRESSOR Flexible PVC pipe is used to cover power and signal cable for boiler Power and signal cable for boilers shall be distributed using proper type insulator to avoid damage of cables. FINDING NO: E - 29 BOILER & COMPRESSOR Electric boiler. motor has inadequate /no earthing connection Each electrical installation must have proper earth connection. REMEDIATION TIME FRAME: 1 MONTH FINDING NO: E - 30 GENERATOR ROOM Generator Body and neutral has no earth connection. Adequate earthing connection for generator/ transformer body and generator neutral (consult with your generator supplier) shall be ensured. Page 12 of 12
ELECTRICAL SAFETY INSPECTION REPORT
ELECTRICAL SAFETY INSPECTION REPORT APPLE KNITWEAR LTD. House 1, Road 1, Horinchala, Konabari, Gazipur GPS Coordinate:24.010091, 90.319184 Factory List: Apple knitwear Ltd. Inspected by Report Generated
More informationELECTRICAL SAFETY INSPECTION REPORT
ELECTRICAL SAFETY INSPECTION REPORT ABSS HIGH TECH SWEATER LTD. Kalameshar, Board Bazar, Gazipur. Factory List: ABSS HIGH TECH SWEATER LTD. Inspected by Report Generated by : Hossain Shah Aarif : Mobassear
More informationTechnical Specifications
LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for
More informationComparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010
1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,
More information33kV Connection up to 90MVA
Electricity Specification 217 Issue 2 December 2007 33kV Connection up to 90MVA Contents 1 Scope 2 General 3 Connection Arrangements 4 Equipment Records 5 Documentation 6 Documents Referenced 7 Keywords
More informationGUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES
MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:
More information1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".
SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,
More informationConstruction and Wiring Guidelines for Ergon Energy Substation Panels
Construction and Wiring Guidelines for Ergon Energy Substation Panels Table of Contents Purpose and Scope... 1 Responsibilities... 1 Definitions, Abbreviations and Acronyms... 1 References... 1 Panel Wiring...
More information56-SDMS-07 REV. 01 SPECIFICATIONS FOR
56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice
More informationGuideline for Parallel Grid Exit Point Connection 28/10/2010
Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND
More informationSUBSTATION DESIGN TRAINING
2017 SUBSTATION DESIGN TRAINING ADVANCE ELECTRICAL DESIGN & ENGINEERING INSITUTE (Registered under MSME& An ISO 9001:2008 CERTIFIED) Training Centre: Advance Group of Institutions C-1, Second Floor Near
More informationSCHEDULE OF QUANTITY
SCHEDULE OF QUANTITY ELECTRICAL WORKS PM PALEM BRANCH, VISAKHAPATNAM SL NO. DESCRIPTION OF ITEM / WORK UNIT Qty RATE AMOUNT PART - A : ELECTRICAL WORKS 1 Energy Meter Cubicle : 2 Emergency Off Box (Red
More informationSurface Regulations and Policies
Surface Regulations and Policies COAL FATALITIES 1970-2002 350 300 250 200 150 100 50 0 1970 1973 1976 1979 1982 1985 1988 1991 1994 1997 2000 From January 1, 1970 through today, a total of 240 coal miners
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationIT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii)
IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The
More informationA member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.
Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative
More informationGuidance for Low Voltage Electrical Installations
Guidance for Low Voltage Electrical Synopsis This document provides information in support of GI/RT7007 Low Voltage Electrical. Signatures removed from electronic version Submitted by Anne E Blakeney Standards
More informationSiemens Com www.alfazalengineering.com Company Introduction Al-Fazal Engineering is Authorized Dealer of Siemens Components supply and Services also we are electrical construction material manufacturing
More information36CSR27 TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS
TITLE 36 LEGISLATIVE RULE BOARD OF COAL MINE HEALTH AND SAFETY SERIES 27 RULES AND REGULATIONS GOVERNING SURFACE AREAS 36-27-1. General. 1.1. Scope. -- Rules and Regulations Governing Surface Areas. 1.2.
More informationGC108: EU Code: Emergency & Restoration: Black start testing requirement
Stage 01: Modification Proposal Grid Code GC108: EU Code: Emergency & Restoration: Black start testing requirement Purpose of Modification: This modification seeks to align the GB Grid Code with the European
More informationGC108: EU Code: Emergency & Restoration: Black start testing requirement
Stage 01: Modification Proposal Grid Code GC108: EU Code: Emergency & Restoration: Black start testing requirement Purpose of Modification: This modification seeks to align the GB Grid Code with the European
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax
More informationNEC REQUIREMENTS FOR GENERATORS
PROFESSIONAL DEVELOPMENT SEMINAR SERIES NEC REQUIREMENTS FOR GENERATORS (Based on NEC 2005 with limited 2008 commentary) AIA certified Continuing Education Units (CEU) Available GPS-140 National Electric
More informationThe Management of Electrical Safety in Quarries, Associated Plant and Equipment
Quarries National Joint Advisory Committee (QNJAC) Plant Information Sheet 1 (Version 1, November 2015, review date: 2020) The Management of Electrical Safety in Quarries, Associated Plant and Equipment
More informationSTATISTICS ELECTRICAL INCIDENTS IN ALBERTA. January 1 to December 31, 2012
Safety Services 16 th floor, Commerce Place Tel: 1-866-421-6929 10155 102 nd Street Fax: 780-427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS ELECTRICAL INCIDENTS IN ALBERTA January 1 to December 31,
More informationElectric & Gas Service Requirements (Greenbook) Overview
INTRODUCTION The Greenbook contents and standard documents are updated regularly to provide users with the most current information possible. In conjunction with this effort, the 2016 Greenbook was reviewed
More informationEXTENSIVELY READ THE MANUALS AND HAVE SOME TRAINING. THIS TYPE OF CONNECTION IS NOT EVEN LISTED IN THE TM
IN THIS SLIDE, THE INDIVIDUAL / S WHO MADE THIS CONNECTION NEEDs TO EXTENSIVELY READ THE MANUALS AND HAVE SOME TRAINING. THIS TYPE OF CONNECTION IS NOT EVEN LISTED IN THE TM s AND THE CECOM GROUNDING BOOK.
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More information2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9
8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection
More informationElectrical Testing Company Pty Ltd / download at electricaltestingcompany.com.au / AS/NZS 3003:2011 Cardiac (Rev C)
AS/NZS 3003:2011 Cardiac Protected Electrical Areas (shall comply with Section 2 and Section 4 of the standard) The following is a guide for electricians involved with electrical installations for patient
More informationData Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?
Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationTender Schedule. Sl. No. Particulars Quantity Unit Rate `
Tender Schedule Estimate for Electrical Works at Savalyapuram Branch(18901) Guntur(District). Sl. No. Particulars Quantity Unit Rate ` 1 Wiring for light point/ fan point/ exhaust fan point/ call bell
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationPowered Industrial Trucks
INDIANA UNIVERSITY-PURDUE UNIVERSITY at INDIANAPOLIS IUPUI Department of Environmental Health and Safety 620 Union Drive, Room 043, Indianapolis, Indiana 46202 Powered Industrial Trucks Purpose and Background
More information1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.
More informationSTANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011
Page 1 of 6 STANDARD SPECIFICATION FOR LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs Rev No. Issue Date Pages Rev Description Prepared By Checked By Approved By 0 15.07.2008 6 Issued for FEED MSJ VDV VDV
More informationGuidelines for Filming in The City of Vernon. General Requirements
Guidelines for Filming in The City of Vernon The City of Vernon, a primarily industrial city, provides a wide range of services to the Entertainment Industry as a means of maintaining and expanding the
More informationUnderground Distribution Construction Manual
Underground Distribution Construction Manual Section E7 Earthing Approved by: A Smith de Perez Energex Limited 2014 ABN 40 078 849 055 MANUAL 00305 1. INSTALLATION Detailed earthing information may be
More informationMAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT CS-OHS-32
CS ENERGY OPERATIONS PROCEDURE FOR MAINTENANCE AND TESTING OF ENTITY WORKS, ELECTRICAL INSTALLATIONS AND ELECTRICAL CS-OHS-32 Responsible Officer: Electrical Services Engineering Manager Error! Bookmark
More informationPORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE
PORTABLE ELECTRICAL EQUIPMENT SAFE OPERATING PROCEDURE Page 1 of 6 1. SUMMARY... 3 1.1 USE OF PORTABLE ELECTRICAL EQUIPMENT... 3 1.2 FAULTY EQUIPMENT... 3 2. PURPOSE & SCOPE... 3 3. DEFINITIONS... 3 3.1
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA TENDER FOR
GUJARAT ENERGY TRANSMISSION CORPORATION LIMITED SARDAR PATEL VIDYUT BHAVAN RACE COURSE, VADODARA - 390 007 TENDER FOR Design,Engineering, manufacturing, supply, erection, testing & commissioning of 66
More informationLIST OF EDD DESCRIPTION/ SPECIFICATION AS 19 TH OCTOBER 2016
No Description/ Specification Amendment 1 EDD 1 :2008 11/0.415 kv Distribution Transformer, Oil Filled - 2 ED 2 :1987 The Galvanization of Iron and Steel, Articles Other Than Steel Wire - 3 ED 3 :1979
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY NOTICE INVITING TENDER Phone:
More informationVP, Facilities and Construction Management
Title: Effective Date: November 2005 Revision Date: January 12, 2017 Issuing Authority: Responsible Officer: VP, Facilities and Construction Management Director Environmental Health and Safety PURPOSE
More informationElectrical Safety. Presented By- C S Chakraverty. L&T Construction ( MMH ) Head- E&I Operation
Electrical Safety Presented By- C S Chakraverty Head- E&I Operation L&T Construction ( MMH ) Objective of the session Create an awareness about importance of electrical safety in our day today activities,
More informationBSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012
BSS Examination Checking Procedures Part 3 - Electrical systems Recommendations for change May 2012 3.1.2 re batteries secure against excessive movement in any direction? R Check by visual assessment the
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationContents. 1 Introduction. 2. Advisory and Information Systems. 3. Supply. 3.1 Quality of Electric Supply. 3.2 Interference with other Customers
DISTRIBUTION CODE Contents 1 Introduction 2. Advisory and Information Systems 3. Supply 3.1 Quality of Electric Supply 3.2 Interference with other Customers 3.3 Application for the Supply of Electricity
More informationPortable Ladder Safety
Portable Ladder Safety Disclaimer This training material presents very important information. Your organization must do an evaluation of all exposures, applicable codes and regulations, and establish proper
More informationNLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX
NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX Dr. Rajendra Prasad Road,Block-27,Neyveli-607807.Tamilnadu,India.
More informationSECTION 300 OVERHEAD SERVICE
SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to
More informationV. Design, Application, Maintenance & Operation Technical Requirements
V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented
More informationEstimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount
Estimate For The Electrical Works At Pittakayagulla Branch Sl.N Particulars Quantity Unit Rate Amount 1 2 Writing for light point/ fan point/ exhaust fan point /call bell point with 1.5 sq.mm FR PVC insulated
More informationPRIVATELYOWNED POWER POLES AND POWERLINES
PRIVATELYOWNED POWER POLES AND POWERLINES Privately-owned power poles and powerlines Privately-owned power poles and overhead powerlines must be properly maintained to ensure that they do not pose a serious
More information34-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES
More information2015 WDC Disturbance and Protection Standards Overview
NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and
More informationLouisville Gas and Electric Company
P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationHOLY SPIRIT RCSRD NO.4 BUS DRIVER S GUIDE
HOLY SPIRIT RCSRD NO.4 BUS DRIVER S GUIDE Updated May 2017 Holy Spirit RCSRD No.4 Bus Driver s Guide TABLE OF CONTENTS INTRODUCTION... 3 CARRIER PROFILE... 4 BUS DRIVERS... 5 Authorized Driver... 5 Un-authorized
More informationNETWORK ELECTRICAL TECHNOLOGY LLC
2016 NETWORK ELECTRICAL TECHNOLOGY LLC Sameh Al-Sinani Network Electrical Technology 12/1/2016 Network Electrical Technology established in 2010 as Electrical Services Company. In 2014 NET registered in
More informationPosition Paper. Telehandler Use: Lifting Suspended Loads
Position Paper Telehandler Use: Lifting Suspended Loads The following paper reflects the considered opinion on the Crane Association of New Zealand (Inc.) This document has been prepared by the Technical
More informationStandards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.
FOREWORD This Standard is intended to be used within and for Iranian Ministry of Petroleum (N.I.O.C, N.I.G.C, N.P.C., N.I.O.R.D.C. and other affiliate organizations and companies) and has been prepared
More informationRULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS CHAPTERS APPROACH
PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS TITLE 47 SUPPLY VESSELS SECTION 6 PIPING CHAPTERS A B C D E F G H T APPROACH MATERIALS AND MANUFACTURE - See
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationElectrical Workplace Safety
Electrical Workplace Safety Alan Kelly 23 rd September 2015 Objectives To provide an understanding of Electrical terms and the concepts of electricity To introduce Electrical Protective Devices and provide
More informationWind and Temperature Tip Over Hazard Do not add notice boards or similar
Lift & Work Platform Safety Information Safety Information: Boom Lifts Safety Information: Scissor Lifts Safety Information: Boom Lifts Power Lines Electrocution Hazard Maintain safe clearance from Electrical
More informationINDIAN INSTITUTE OF TECHNOLOGY KANPUR
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Tender Notice No. 40/Elect./2018 SCHEDULE OF QUANTITY Name of Work: Electrical work for the Clean Room at NCFlexE IIT Kanpur. Name of the Contractor S. No Description
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationDEVELOPMENT OF DRAFT GUIDELINES FOR CONSISTENT IMPLEMENTATION OF REGULATION OF MARPOL ANNEX VI
E INTERSESSIONAL MEETING ON CONSISTENT IMPLEMENTATION OF REGULATION 14.1.3 OF MARPOL ANNEX VI Agenda item 2 25 May 2018 ENGLISH ONLY DEVELOPMENT OF DRAFT GUIDELINES FOR CONSISTENT IMPLEMENTATION OF REGULATION
More informationPrinciple Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act ZEK
-GB-2017-01: Defining the requirements for a GS mark approval Principle Decision by the Central Experience Exchange Circle of the Notified Bodies and the GS Bodies according to the Product Safety Act about
More informationCONVEYOR REGULATIONS. AA COUTINHO Director Mine Safety
CONVEYOR REGULATIONS AA COUTINHO Director Mine Safety CONTENTS 1. Accident» Fatalities» Injuries 2. Conveyor regulations 3. Way forward INJURIES-Fatalities 12 10 8 6 4 2 0 2002 2003 2004 2005 2006 2007
More informationREDUNDANT PROPULSION SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2
RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS PART 6 CHAPTER 2 REDUNDANT PROPULSION JANUARY 2003 This booklet includes the relevant amendments and corrections
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationLIGHTING JUNCTION BOX
Channels Max. No. of Terminals Cat No. Max. Max. 4 10 16 35 50 70 95 Size Length No. mm 2 mm 2 mm 2 mm 2 mm 2 mm 2 mm 2 DB 6006 260 x 160 L 245 1 30 20 16 B 145 2 32 22 18 6 DB 6024 300 x 225 L 285 2 72
More informationPOWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011
POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL
More informationInstallation and Construction Notes for EVSE4
Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process
More informationThermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:
Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: 27-10-2006 Reference Number: 2710061 Thermographer: John Crawford Thermal Imaging
More informationPRODUCT DATA. Parking Automat P kg 1
- Car KLAUS Multiparking Systems Pvt. Ltd. /, Prashant Apartments, Erandwane, Pune INDIA Phone +9-- 78 / 866 Fax +9-- 66 E-mail info@klausmultiparking.in Website www.klausindia.com PRODUCT DATA Parking
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationCLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001
CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS
More informationPowered Industrial Vehicle Policy
Powered Industrial Vehicle Policy Policy The Flight Department is committed to protecting employees from the hazards involved in the operation of powered industrial vehicles. This Policy is established
More informationSolar PV General Introduction Guide for Electricians
Solar PV General Introduction Guide for Electricians Important Note: This guide was written to provide a broad guidance for electricians that would like to expand their product knowledge and skills for
More informationEU TOY DIRECTIVE 2009/48/EC: OVERVIEW - REGULATORY CONTEXT AND MAJOR CHANGES
EU TOY DIRECTIVE 2009/48/EC: OVERVIEW - REGULATORY CONTEXT AND MAJOR The EU Toy Directive was revised in order to take into account the new technological developments and increasing child safety requirements.
More informationSTATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA to
Safety Services th 16 floor, Commerce Place Tel 1-866/421-6929 10155 102 nd Street Fax 780/427-8686 Edmonton, Alberta Canada T5J 4L4 STATISTICS RE: ELECTRICAL INCIDENTS IN ALBERTA 01 01 to 12 31 Regulations
More informationCHAPTER II-1 D. Construction subdivision and stability, machinery and electrical installations
Only the Danish version is authentic Notice D II-1 D 1 October 2002 Technical regulation on the construction and equipment, etc. of passenger ships on domestic voyages CHAPTER II-1 D Construction subdivision
More informationTender Schedule for Electrical Works at Varagani Branch. Sl. No. Particulars Quantity Unit Rate Amount
Tender Schedule for Electrical Works at Varagani Branch Sl. No. 1 Particulars Quantity Unit Rate Amount SITC of following rated Indoor operated wall/floor mounted, cubicle type MV cum APFC Panel suitable
More informationTask Force on Electro-magnetic Compatibility (TF EMC) Status report of TF to GRE-75 Friday, 8 April 2016
Submitted by TF EMC Informal document GRE-75-18 (75 th GRE, 5-8 April 2016, agenda item 7(c)) Task Force on Electro-magnetic Compatibility (TF EMC) Status report of TF to GRE-75 Friday, 8 April 2016 TF
More informationGENERAL HOUSEKEEPING. 1. Are all aisles, passageways, stairways and stairwells kept clear of tools, hoses, and trash?
Inspection Checklist GENERAL HOUSEKEEPING 1. Are all aisles, passageways, stairways and stairwells kept clear of tools, hoses, and trash? 2. Is oil, grease, or other liquids, when spilled on the floor
More informationB kv T&D GAS INSULATED SWITCHGEAR
GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission
More information9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.
Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution
More informationMICROCARE 3 PHASE INVERTER MANUAL
3 PHASE INVERTER MANUAL 1 Contents 1. INTRODUCTI... 3 2. SAFETY INSTRUCTI... 4 3. SYSTEM DESCRIPTI... 6 4. WIRING DIAGRAM... 9 5. INVERTER OPERATI... 10 6. INVERTER CLUSTER PROGRAMMING... 13 7. CLUSTER
More informationFAQ s. Designing metering switchboards as per Victorian service installation rules
FAQ s Designing metering switchboards as per Victorian service installation rules Designing metering switchboards as per Victorian service installation rules Q: Who develops the Victorian service installation
More informationPrepared for: BP-Husky Refining LLC 4001 Cedar Point Road Oregon, Ohio Prepared by:
BP-HUSKY REFINING LLC REVISION TO FCCU WET GAS COMPRESSOR RECONSTRUCTION PERMIT TO INSTALL (04-01482) TO INCORPORATE FINAL FCCU NO X EMISSIONS LIMITS Prepared for: BP-Husky Refining LLC 4001 Cedar Point
More informationTABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...
TITLE SPECIFICATION FOR PORTABLE DATE: JULY 2006 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD...3 INTRODUCTION...4 1 SCOPE...4 2 NORMATIVE S...4 3 DEFINITIONS AND ABBIATIONS...4 4 REQUIREMENTS...5 4.1
More informationElectric Vehicle Charging Safety Guidelines Part 2: Selection and Installation
86 Customhouse Quay PO Box 165, Wellington 6140 New Zealand Date of publication: 1 November 2016 Issued by: Mark Wogan, Manager Energy Safety WorkSafe New Zealand Electric Vehicle Charging Safety Guidelines
More informationCONTENT 1 PICTURE GENERAL... 3
IP67 CONTENT 1 PICTURE... 3 1.1 GENERAL... 3 2 DIMENSIONS... 4 2.1 SYMBOLS... 5 2.2 PROTECTION FROM ELECTRIC SHOCK... 6 2.3 PROTECTIONS FROM FIRE AND BURNS... 6 2.4 PROTECTION FROM INJURY... 7 2.5 DISPOSING
More informationCAL/OSHA ELECTRICAL LOW VOLTAGE
Preparation: Safety Mgr Authority: CEO Issuing Dept: Safety Page: Page 1 of 7 Purpose The purpose of this program is to prevent injuries due to electrical exposure to low voltage (less than or equal to
More informationSubstation Lightning Protection. Document Number: 1-11-FR-11
Substation Lightning Protection Document Number: 1-11-FR-11 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-11 Substation Lightning Protection Asset
More information