Thermography Report. Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW. Requested By: John Seemore. Date of Inspection:
|
|
- Frank Richardson
- 6 years ago
- Views:
Transcription
1 Thermography Report Inspection Site: Lucky Mining Co. Rocky Rd Smithville, NSW Requested By: John Seemore Date of Inspection: Reference Number: Thermographer: John Crawford Thermal Imaging Camera: Make: FLIR Model: ThermaCAM E45 Serial:
2 INSPECTION GENERAL INFORMATION This thermographic inspection is designed to assess the performance of all switchgear on site and to highlight any areas which require attention. Recommendations listed within this report are given only within our area of expertise and we recommend you discuss the implementation of remedial works with your maintenance service provider. Scope Infrared Thermal Scanning of all electrical switchgear and associated conductors to detect evidence of equipment operating near or above rated temperatures. Load readings are also taken of prospective faults to assist in the accurate diagnosis of the prospective fault. A detailed log of inspected assets is provided which includes a Pass or Fail status. Those items failing the inspection are reported on through a thermal and digital image, a priority rating & possible recommended action. An initial scan of all items is carried out with the Infrared Radiometer set to alarm at temperatures above 40 o C. Items displaying temperatures above 40 o C are further investigated based on application, equipment type, load measurement & spot temperature readings. Overview of Fault Priority Ratings 0 No abnormality No Action 1 Alert To be monitored rescan when recommended 2 Severe Repair at scheduled shutdown, not longer than 30 days 3 Critical Repair immediately or as soon as possible 4 Immediate Notification Shutdown & repair immediately 2
3 Location: Motor Control Room Page: 3 Section: Relay Compartment Priority: 2 Equipment: Mains indicator lamp, white phase Item: C Ar C Ar1: Max 59.2 C Pilot lamp assembly should be replaced. Priority Level 2 Repair at next scheduled shut down, no later than 1 month. 3
4 Location: Motor Control Room Page: 4 Section: MDB-1 Section 1 Priority: 2 Equipment: 1amp Pan A & Pan B Fault Limiting Fuses Item: 10 Ar2 Ar C Ar3 Ar C Ar1: Max 76.4 C Ar2: Max 76.8 C Ar3: Max 72.5 C Ar4: Max 71.1 C The fault current limiting fuses are operating at excessive temeratures considering the operating load of 100 amps per phase. The rating of the fuses are 1amps. Priority level 2, the fuses & fuse carriers should be replaced at the next scheduled shutdown. 4
5 Location: Motor Control Room Page: 5 Section: Cable Zone Priority: 1 Equipment: CR3 sub-main circuit breaker terminations Item: 13 Sp2 Sp C C Sp C Sp C All 3 phases are equally loaded at 540amps per phase, phase temperatures should be equal. Priority Level 1, monitor condition & re-scan in 3 months. 5
6 Location: Workshop Distribution Board Page: 6 Section: D.B.W.S. Priority: 2 Equipment: Precoat plant circuit breaker Item: 15 Ar C Li1 Sp C Sp C Li1: Max 63.5 C Ar1: Max 64.6 C C Cursor Min Max Li Circuit breaker rating is 25amps, sub circuit cable size is 2.5mm, load current is 21amp per phase. The cable size is under rated for the existing load, either the load & circuit breaker size needs to be reduced or the cable size increased. Priority Level 2, remedial work should be carried out next scheduled shutdown. 6
7 Location: Main Switch Board Page: 7 Section: Priority: 2 Equipment: Main Switch MDB-1 Item: C Sp4 Sp2 70 Sp3 Li1 Sp C Sp C Sp C Sp C Sp C Li1: Max 71.9 C C Cursor Min Max Li Blue phase bus bar on the circuit breaker load side is operating approx. 10 deg C higher than the adjacent 2 phases, load per phase is 1180amps & balanced within 4%. The temperature profile indicates the temperature rise origin to be either at the circuit breaker/bus bar termination point or internal to the circuit breaker. It is recommended the circuit breaker be removed, inspected & all termination points dressed. The breaker should then be recommissioned & monitored Priority Level 2, remedial work should be carried out next scheduled shutdown. 7
8 LOG OF INSPECTED ASSETS LOCATION EQUIPMENT ITEM RESULT NUMBER Motor Control Room PLC Cubicle PLC-1 1 P Motor Control Room Cable termination compartment 2 P Motor Control Room Relay Compartment 3 F Motor Control Room MCC-1 4 P Motor Control Room Contactor Compartment No.2 5 P Motor Control Room VSI Crusher CR3 6 P Motor Control Room Crusher Starter CR2 7 P Motor Control Room Crusher Starter CR1 8 P Motor Control Room Circuit Breaker Compartment 9 P Motor Control Room MDB-1 Section 1 10 F Motor Control Room MDB-1 Section 2 11 P Motor Control Room MDB-1 Section 3 12 P Motor Control Room MDB-1 cable zone 13 F Motor Control Room Distribution Board DBX-1 14 P Workshop Workshop Distribution Board DBWS 15 F Main Office Office Distribution Board 16 P Main Switch Board Mains Connection Section 17 P Main Switch Board C.T. Section 18 P Main Switch Board MCR Sub-main connection section 19 P Main Switch Board Main switch MDB-1 20 F Main Switch Board Local D.B. mainswitch 21 P Main Switch Board Local D.B. section 22 P F Failed inspection P Passed Inspection NIO Equipment Not In Operation at time of inspection 8
9 ACTION TAKEN: BY: DATE: 9
2006 Thermographic Inspection. Terrific Towers 1001 Sparks St Sydney. Vol. 9
8/139 Woolooware Rd Burraneer NSW 2230 T. (02) 9544 3588 F. (02) 9544 3688 E. info@thermalimagingservices.com.au W. www.thermalimagingservices.com.au Accredited Thermographers 2006 Thermographic Inspection
More informationTHERMOGRAPHY REPORT ELECTRICAL
LAMBERT CONDITION MONITORING LTD. CERTIFIED THERMOGRAPHER A.I.R. #12-01-243 THERMOGRAPHY REPORT ELECTRICAL Thermographic inspection at: Sample site Inspected by: David Lambert date: 20170701 Customer Sample
More informationFault Summary The following table is a summary of faults or items featured for your information
This document is an annotated sample of a report you receive. following our visit to your premises... We pride ourselves on the quality of the report and submit. this sample for your evaluation.. Report
More informationThermal Imaging Infrared Survey. Report. Report. Thermography Inspection at ABC Company.
Thermal Imaging Infrared Survey Report. Thermal Imaging Infrared Survey Report. Thermography Inspection at ABC Company. Vancouver,BC May 25,2012 www.aiturgroup.com info@aiturgroup.com Rick Turdubay, Certified
More informationSubstation inspection guidelines Mark B. Goff, P.E.
Substation inspection guidelines Mark B. Goff, P.E. Tennessee Valley Authority, Chattanooga, Tennessee ABSTRACT We need to better understand what our infrared camera is really showing us. Without guidelines,
More informationBUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE
BUZZI UNICEM USA PRESIDENT S ISLAND TERMINAL MEMPHIS, TENNESSEE July, 2015 Infrared Inspection Report Buzzi Unicem Terminal Company Contact Randy Miguez Project: 06220715 2605 CHARTER OAK DRIVE, LITTLE
More informationSYSCO INDIANAPOLIS INDIANAPOLIS, INDINA
SYSCO INDIANAPOLIS INDIANAPOLIS, INDINA November, 2017 Infrared Inspection Report Sysco Indianapolis LLC. 4000 West 62nd Street Indianapolis, Indiana, 46268 Company Contact: Trevor Gray Project: 05161117
More informationSYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA
SYSCO CENTRAL CALIFORNIA MODESTO, CALIFORNIA July, 2018 Infrared Inspection Report Sysco Central California 136 South Mariposa Road Modesto, California, 95393 Company Contact: Steve Handel Project: 04110718
More information8803214-8803999 DIODE BOARD The diode board is located inside the lower control box. D15 D8 D7 D14 D5 D13 ART_2181 J1 14 8 D9 D10 7 1 R2 R1 R3 R4 TB1 8601 D11 D3 D12 D4 D1 D2 J1 Plug Pin Identification
More informationDIODE BOARD The diode board is located inside the lower control box. D15 D8 D7 D14 D5 D13 ART_2181 J1 14 8 D9 D10 7 1 R2 R1 R3 R4 TB1 8601 D11 D3 D12 D4 D1 D2 J1 Plug Pin Identification PIN # WIRE # SIGNAL
More informationSIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS
SIDEWINDER DRILLING RIG 219 LA SALLE, TEXAS July, 2015 Infrared Inspection Report Sidewinder Drilling Company Contact Tommy Green Project: 02170715 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE:
More informationELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243
ELECTRIC SCHEMATICS NOTES: (Unless otherwise specified). Switch S BASE/PLATFORM makes contact from the CENTER to the LEFT position when placed in BASE.. Switch S UP/DOWN makes contact from the CENTER to
More informationSubstation Equipment (Bushings)
Substation Equipment (Bushings) Mark B. Goff, P.E. Tennessee Valley Authority ABSTRACT Bushings provide a point of interface such that electrical current can pass to and from an electrical apparatus. Much
More informationINFRARED THERMOGRAPHY:
INFRARED THERMOGRAPHY: X-treme Electrical can now also assist with infrared thermography of various electrical installations. Please take the time to review the following presentation for comprehensive
More informationLow Voltage Systems MNS platform
Low Voltage Systems MNS platform MNS a long successful history ABB is worldwide leader in the production of low voltage switchgears with more than 1.4 million of MNS systems installed since the introduction
More informationSIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS
SIDEWINDER DRILLING RIG 127 MIDLAND, TEXAS November, 2017 Infrared Inspection Report Sidewinder Drilling Rig 127 Pecan Acres 23 PSA 3-3H(WB) Company Contact Colton Chesney Project: 02201117 2605 CHARTER
More informationThermal Patterns Associated with Infrared Inspection of Electrical Systems
Thermal Patterns Associated with Infrared Inspection of Electrical Systems James Brady Level III Certified Infrared Thermographer Brady Infrared Inspections, Inc. 935 Pine Castle Court Stuart, FL 34996
More informationS H A D E S ELECTRICAL DB MANUFATURING
CORPORATE BROCHURE S H A D E S ELECTRICAL DB MANUFATURING S H D E S ELECTRICAL DB MANUFACTURING L.L.C. www.shadesdb.com I N T R O D U C T I O N Welcome to SHADES, this portfolio has been designed to give
More informationSECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2
SECTION 1. 600V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2 Soft Starters SECTION 2. LIQUID COOLED VFD I 3 Liquid Cooled
More informationAppendix C. Interval Every 2 Year. Functional Test Weekly Monthly Quarterly. Semi. Every 3. Engineering Studies
Engineering Studies Coordination Study Every 5 years and in conjunction with electrical system modifications. Short Circuit Study NETA MTS 6.2 Every 5 years and in conjunction with electrical system modifications.
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements
More informationAvid Electrical Services
Avid Electrical Services Thermal Imaging Report To: Mr A. Customer Your Business Australia Pty Ltd Fault Summary The following table is a summary of faults or items featured for your information Grading
More informationATevo SERIES BATTERY CHARGER
PRODUCT OVERVIEW NEXT GENERATION NEW FEATURES: Interactive LCD display Intelligent self diagnostics NERC Compliant ATevo Battery Charger is the next generation SCR-based utility battery charger. The innovative
More informationINFRARED INSPECTION REPORT
REPORT February 13, 2015 Companies Unlimited 1401 Brand St. Los Angeles, CA 90028 Contact: Ron McKinney An Introduction to Infrared Inspection When installed correctly and operated within their ratings,
More informationADVISE DESIGN IMPLEMENT FOR ELECTROTECHNICAL EXCELLENCE
ADVISE DESIGN FOR ELECTROTECHNICAL EXCELLENCE IMPLEMENT ADVISE DESIGN FOR ELECTROTECHNICAL EXCELLENCE Gemitech was founded in 1990 and, in just a few short years, grew to be recognized as medium and IMPLEMENT
More informationJ1 Plug Pin Identification
D D8 D D D D ART_8 J 8 D D0 R R R R TB 80 D D D D D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal 8 INPUT Steer Left
More informationJ1 Plug Pin Identification
D5 D D D D5 D ART_ J D D0 R R R R TB 0 D D D D D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal INPUT Steer Left 5 OUTPUT
More informationJ1 Plug Pin Identification
D5 D8 D7 D4 D5 D ART_8 J 4 8 D D0 7 R R R R4 TB 80 D D D D4 D D J Plug Pin Identification PIN # WIRE # SIGNAL FUNCTION 0 INPUT Drive Reverse INPUT Drive Forward OUTPUT Brake, Decel Valve signal 4 8 INPUT
More informationDSEULTRA DSE6000 Quick Start Guide Document Number
n DSEULTRA DSE6000 Quick Start Guide Document Number 057-102 Author : John Ruddock Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales
More informationBIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL
E13 TEMPERATURE PROBE FAILURE E16 HIGH LIMIT 1 EXCEEDED A. TEMP Probe reading out of range. B. Bad Connection. C. Problem with the temperatur e measuring circuitry including the probe. High limit temperature
More informationThermographic Inspection at SMALLVILLE DPW 123 ANY WAY SMALLVILLE, CA PETER PLEIN
191 BOULEVARD GLEN ROCK, NJ 07452 201-444 444-3620 Thermographic Inspection 123 ANY WAY SMALLVILLE, CA 01234 2006-04-25 By PETER PLEIN SAMPLE 1 (10) April 25, 2006 De: This is the in initial inspection
More informationHGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology
HGM1780 Automatic Genset Controller USER MANUAL Smartgen Technology Smartgen Technology Co., Ltd No. 28 Jinsuo Road Zhengzhou Henan Province P. R. China Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951
More informationCompany Name City, State. Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI
Company Name City, State Thermographic Study (date) Prepared By: L&S Electric, Inc. PO Box 740 Schofield, WI 54476-0740 April 9, 2012 (Customer Name & Address) Attn: Customer Enclosed is a report on the
More information5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application
The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1
More informationChapter 6 Generator-Voltage System
Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals
More informationUninterruptible Power System
USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency UPS 1 st Edition Uninterruptible
More informationSYSCO RDC SOUTH ALACHUA, FLORIDA
SYSCO RDC SOUTH ALACHUA, FLORIDA July, 2018 Infrared Inspection Report Sysco RDC South 12421 NW 173rd Street Alachua, Florida, 32615 Company Contact: Natha Hall Project: 05110818 2605 CHARTER OAK DRIVE,
More informationAT EVO SERIES BATTERY CHARGER
STANDARD FEATURES 5 YEAR WARRANTY EVO AT Series Battery Charger is HindlePower s next generation SCR-based utility battery charger. This evolutionary product is revolutionary in its design and operation
More informationInstruction Manual. Q Series 2 Motor Control Modules - OEM
A382-21-880 Issue B Instruction Manual Q Series 2 Motor Control Modules - OEM Pump/ Q Motor Control Module Item Number pumping system Electrical supply 24 V d.c. control 24 V a.c. control QDP40 200-230
More informationNC PV DG Program SEPA Presentation. December 15, 2011
NC PV DG Program SEPA Presentation December 15, 2011 Agenda PV Industry Background PV Solar Rooftop Incident Root Cause(s) Wiring Diagrams Remedy Fire Safety Brochure Findings/Observations Recommendations
More informationDesigned for ease of integration with automation systems
BAS, 200 ~ 600V, 1/2-30HP BUILDING AUTOMATION STARTER SMARTER AND MORE VERSATILE THAN EVER Smartstart Equipped with advanced I/O including Fireman s Override and damper control, the BAS was designed from
More informationDIN-Rail DC UPS. Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications
DIN-Rail DC UPS Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications Combines all system power functions: power supply, battery charger, UPS circuitry
More informationGUIDE TO MAINTENANCE PRACTICES FOR DISTRIBUTION NETWORKS IN THE DISTRIBUTION SECTOR OF THE NAMIBIAN ELECTRICITY SUPPLY INDUSTRY
PART B-04 TITLE: DISTRIBUTION SUBSTATIONS SPECIFICATION NO: B-04 INCEPTION DATE: AFTER GAZETTING (WORKING DOCUMENT FOR A 2 YEAR PERIOD) AMENDMENTS/REVISIONS DATE PAGE PARAGRAPH DESCRIPTION ORIGINATOR APPROVED
More informationPUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4
PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4 1 2 3 4 5 6 7 8 9 Q. Please describe Hydro s terminal station and substation inspections policies and practices. In
More informationSwitchgear and Distribution Systems for Engineers and Technicians
Switchgear and Distribution Systems for Engineers and Technicians WHAT YOU WILL LEARN: How to identify typical characteristics of an industrial distribution system Become familiar with the main components
More informationFUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1
THE SOUTH AFRICAN INSTITUTE OF ELECTRICAL ENGINEERS FUNDAMENTALS OF POWER DISTRIBUTION SAIEE-1337-V : 2 CPD credits : Category 1 OVERVIEW : 1. Introduction to Distribution, Transmission and Generation
More informationProduct Overview. Soft Starters Motor Protection Control and Measurement. Solcon Industries Ltd.
Product Overview Soft Starters Motor Protection Control and Measurement Solcon Industries Ltd. Medium Voltage Soft Starters HRVS-DN Medium Voltage Soft Starter, 50-2500A, 1500-15000V Incorporating microprocessor
More informationSection 17. Motor Control Centers. Table of Contents. Model 6 Motor Control Centers
Table of Contents Section 7 Model Motor Control Centers Motor Control Centers Structure and Unit Features 7- Merchandised Units General Information 7- Combination Starters with Motor Circuit Protector
More informationSYSCO OKLAHOMA LLC NORMAN, OKLAHOMA
SYSCO OKLAHOMA LLC NORMAN, OKLAHOMA August, 2018 Infrared Inspection Report SYSCO Oklahoma LLC 1350 West Tecumseh Road Norman, Oklahoma, 73069 Company Contact Chris Hill Project: 03210818 2605 CHARTER
More informationAUTOMATION AND CONTROL TRADE 19 TAR SANDS
AUTOMATION AND CONTROL TRADE 19 TAR SANDS Page 1 1.1.1 - General With this challenge, we will assess your: a) ability to analyze technical data. b) quality of wiring. c) capacity to implement an automatic
More informationBattery, Mounting and Cables - Battery and Cables Description and Operation
Battery, Mounting and Cables - Battery and Cables Description and Operation COMPONENT LOCATION - SINGLE BATTERY VEHICLES Item 1 2 3 4 5 6 7 8 9 10 Description Jump start terminal negative (-) Jump start
More informationContinuing Education Course #206 Introduction to Designing Machine Control Systems Part 2
1 of 5 Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2 1. Continuing to answer the following questions indicates that you understands that the presented material
More informationABB Drive Services Your choice, your future
ABB Drive Services Your choice, your future Your choice, your future The future of your drives depends on the service you choose. Whatever you choose, it should be a well-informed decision. No guesswork.
More informationABB Services for Low Voltage equipment Your choice, your future
ABB Services for Low Voltage equipment Your choice, your future You choose, we respond. Globally. The future of your equipment depends on the service you choose Whatever you choose, it should be a well-informed
More informationCode: DEUTZ BF4M 1013 FC MECC-ALTE ECP 34-1L/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP)
Genset with manual control panel. Image for guidance purposes. PRP CONTINUOUS POWER: LTP 130 kva STAND-BY POWER: 145 kva PRP Prime Power norma ISO 8528-1 LTP Limited Time Power norma ISO 8528-1 ENGINE
More informationHGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL
HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD. Chinese trademark English trademark SmartGen make your generator smart SmartGen Technology Co.,
More informationALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks.
ALTERNATOR STARTUP Turning gear to full operation. Procedure initiated by:. 7/03 Before starting procedure, remove all check marks. 1. Check log book for incomplete compliance for further operation. 2.
More informationFlight Systems. Replacement for KASSEC DESCRIPTION
DESCRIPTION The is a universal generator controller that will start, stop, and provide engine protection for most generators. Universal replacement for both the 90353 and 90354 KASSEC Compatible with most
More information30 KW / 40 KVA POWERED by
30 KW / 40 KVA POWERED by MODEL Triton Power is a world leader in the design, manufacture of stationary, mobile and rental generator sets and Power Modules from 10 to 2000 kw. Through our commitment to
More informationPowerware Master Modbus
Powerware Master Modbus Map 164201391 Rev D This document describes the format of the data contained in the Modbus messages. Not all registers apply to all UPS modules. Please consult the individual UPS
More informationThe Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs
[ MV Air-insulated Switchgear Range ] 1 PIX CUSTOMER BENEFITS Compact, versatile and highly reliable designs Choice of vacuum or SF6 switching technology Wide range of applications Enhanced operator safety
More informationCode: VOLVO TAD 731 GE MECC-ALTE ECP 34-2L/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 150,0/120,0 165,0/132,0 238,44
Genset with manual control panel. Image for guidance purposes. PRP CONTINUOUS POWER: LTP 150 kva STAND-BY POWER: 165 kva PRP Prime Power norma ISO 8528-1 LTP Limited Time Power norma ISO 8528-1 ENGINE
More informationV. Design, Application, Maintenance & Operation Technical Requirements
V. Design, Application, Maintenance & Operation Technical Requirements V.L Line & Substation Operation and Maintenance 1.0 General Requirements 1.1 Each facility owner shall have an established and documented
More informationRedundant Control System
Redundant Control System Safety instrumented system applications up to SIL 3 Process reliability Process valve diagnostics COMPLETE FUNCTIONAL SAFETY WITH ENHANCED RELIABILITY The Redundant Control System
More informationIntroduction. Main fuseboard. Circuit breaker. Engine compartment fuses. Luggage compartment fuses Four door cars. Two door cars.
02/07/09 TSD 5002 Fuses Introduction In addition to the main fuseboard, a number of smaller fuseblocks are located in the engine and luggage compartments of the car. The car's electrical system utilizes
More informationCode: FPT F32AM1A MECC-ALTE ECP 28-VL / 4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 30,0/24,0 32,5/26,0 46,97 ESPAÑA
Genset with manual control panel. Image for guidance purposes. PRP CONTINUOUS POWER: LTP 30 kva STAND-BY POWER: 33 kva PRP Prime Power norma ISO 8528-1 LTP Limited Time Power norma ISO 8528-1 ENGINE ALTERNATOR
More informationATA 49 AUXILIARY POWER UNIT
F900EX EASY 02-49-00 CODDE 1 PAGE 1 / 2 TABLE OF CONTENTS 02-49 02-49-00 TABLE OF CONTENTS 02-49-05 GENERAL Introduction Sources APU location 02-49-10 DESCRIPTION Introduction Description Operating principle
More informationEilat, 11/2017. Cost Effective switchgear Modernization solutions
Eilat, 11/2017 Cost Effective switchgear Modernization solutions Asset upgrade Today s situation Aging of install base. Demands for Health & Safety Standards. Demands for improve quality of supply. Lose
More informationLow and medium voltage service. Power Care Customer Support Agreements
Low and medium voltage service Power Care Customer Support Agreements Power Care Power Care is the best, most convenient and guaranteed way of ensuring electrification system availability and reliability.
More informationMODEL SCA Installation and Operation Manual Important:
MODEL SCA Installation and Operation Manual Important: This manual contains specific cautionary statements relative to worker safety. Read this manual thoroughly and follow as directed. It is impossible
More informationAlvin Xu & Johnny Wang, ABB Xiamen Switchgear Co,. Ltd., November, 2016 ABB lead the intelligent revolution Intelligent technology (Part 2)
Alvin Xu & Johnny Wang, ABB Xiamen Switchgear Co,. Ltd., ABB lead the intelligent revolution Intelligent technology (Part 2) Slide 1 Intelligent Monitor and Diagnosis The Expert System for Switchgear Slide
More informationSeries Motor Protection
320-327 Series Motor Protection Relay Physical Address: 298 Soutter Street, Pretoria West Tel: 083 454 6949, +27 12 327 1729 Fax: +27 (0)12 327 1733 Toll Assist: 0860 10 30 41 www.newelec.co.za sales@newelec.co.za
More informationUninterruptible Power System
USER'S MANUAL Emergency Backup Power Supply For Use With Computer Loads Only Power Surge/Noise Protection Intelligent Auto-Shutdown Software Internet Line Protection Cost Efficiency AVR Protection Compact
More informationVC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL
1. INTRODUCTION VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL This MCU controlled Step Down DC-DC Converter has a digitally adjustable output in 0.2V increments. This
More informationAT SERIES EVO BATTERY CHARGER
AT SERIES EVO BATTERY CHARGER AT SERIES BATTERY CHARGER P R O D U C T hindlepowerinc.com 610-330-9000 AT Series evo. A battery charger designed with YOU in mind. AT Series evo is HindlePower s next generation
More informationMaxSG Low Voltage Switchgear
Low Voltage Products & Systems Automation Technology MaxSG Low Voltage Switchgear ABB Automation Technologies MaxSG ABB Slide 2 June 2009 Product verview Key Features and Benefits Construction nstrumentation
More informationSENTINEL BATTERY MONITORING
Protecting your power supply SENTINEL BATTERY MONITORING Helios Power Solutions If you re operating mission critical systems and relying on the protection of a UPS and battery bank, then it has to make
More information64 KW / 80 KVA POWERED by
64 KW / 80 KVA POWERED by MODEL Triton Power is a world leader in the design, manufacture of stationary, mobile and rental generator sets and Power Modules from 10 to 2000 kw. Through our commitment to
More informationConveyor Condition Monitoring. Increase uptime, decrease damage, plan repairs, avoid disaster
Conveyor Condition Monitoring Increase uptime, decrease damage, plan repairs, avoid disaster Reliability through Condition Based Monitoring Benefits: Early identification of potential failures Reduce correction
More information4 Redundant Control System
4 Redundant Control System Introducing the all NEW RCS Configurator Safety Instrumented Systems Process Reliability Process Valve Diagnostics COMPLETE FUNCTIONAL SAFETY WITH ENHANCED RELIABILITY The Redundant
More information130 KW / 165 KVA POWERED by
130 KW / 165 KVA POWERED by MODEL Triton Power is a world leader in the design, manufacture of stationary, mobile and rental generator sets and Power Modules from 10 to 2000 kw. Through our commitment
More informationROBICON W120 enclosed drive
SINAMICS Drives ROBICON W120 enclosed drive 1 HP to 200 HP Introduction This technical data sheet provides a short overview of the most important characteristics of the ROBICON W120 enclosed standard 6-pulse
More informationFunction of Preglow System
15-0705 Function of Preglow System General On a diesel engine, combustion occurs when the fuel is injected into the highly compressed and thus greatly heated combustion air and selfignites. When the engine
More informationControl System. Part B, Section 1. This section covers the following unit configurations. Model Voltage 1, 2 Pump Piston (E, F, or G)
Part B, Section 1 This section covers the following unit configurations. Model 3100 3400 3500 Voltage 1, 2 Pump Piston (E, F, or G) Manifold 4-Port (A) 6-Port (B or C) Control UniScan (1) B 1-0 B 1-1 Section
More informationUBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit
More informationCase Study on On EHV Circuit Breaker Flashover NTPC-SINGRAULI
Case Study on On EHV Circuit Breaker Flashover AUTHORS: B. K. SINGH (AGM-ELECT) S.C.SINGH (SUPDT-ELECT) MANOJ SHARMA (Dy SUPDT-ELECT) ANAND PANDEY (ENGR-ELECT) BREAKER-FLASHOVER There has been a rising
More informationSDS Enclosed Star-Delta Starter User Guide
SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING
More information55 KW / 70 KVA POWERED by
55 KW / 70 KVA POWERED by MODEL TP-P55-T3-60-UL Triton Power is a world leader in the design, manufacture of stationary, mobile and rental generator sets and Power Modules from 10 to 2000 kw. Through our
More information204 KW / 254 KVA POWERED by
204 KW / 254 KVA POWERED by MODEL Triton Power is a world leader in the design, manufacture of stationary, mobile and rental generator sets and Power Modules from 10 to 2000 kw. Through our commitment
More informationPowered by Safety. Powell Service Division Services Overview
Powell Service Division Services Overview 1 Headquartered in Houston, TX Home to Powell s Factory Certified Technicians Breaker Repair Depot Custom Switchgear Fabrication In-house Customer Training Facility
More informationMB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR
MB-3688 120A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR User Manual Warning and Precautions MB-3688 is built with corrosion resistant material and the main electronic assembly is well sealed inside
More informationCode: KOHLER KDI1903M MECC-ALTE ECP 28-M/4. VOLTAGE HZ PHASE COS Ø PRP kva/kw LTP kva/kw AMP. (LTP) 400/ ,8 18,9/15,2 20,8/16,6 30,07
Genset with manual control panel. Image for guidance purposes. PRP CONTINUOUS POWER: LTP 20 kva STANDBY POWER: 22 kva PRP Prime Power norma ISO 85281 LTP Limited Time Power norma ISO 85281 ENGINE ALTERNATOR
More informationNFPA 70E Standard for Electrical Safety Requirements for Employee Workplaces. Table Hazard Risk Category Classification
Table 3-3.9.1 Hazard Risk Classification Table 3-3.9.1 Hazard Risk Classification Panelboards rated 240 V and below Notes 1 and 3 - - - Circuit breaker (CB) or fused switch operation with covers on 0 N
More informationMODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM
MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...
More informationMNS PDUpro Intelligent power distribution unit
MNS PDUpro Intelligent power distribution unit 1 2 3 4 5 1 Low voltage distribution Low voltage circuit-breakers and motor control centers Intelligent electricity distribution center Active harmonic filter
More informationGrounding Systems. Resistance. Resistance Grounding Systems Contents
Resistance Systems.0-1 Resistance Systems Contents Resistance Systems High Resistance System Medium Voltage...............1-1 High Resistance System Low Voltage..................2-1 Specifications See
More informationTwo Recent Case Studies in the Mining Industry
Two Recent Case Studies in the Mining Industry Remote Isolation Arc Flash Remediation David B. Durocher Senior Member, IEEE Global Industry Manager, Mining Eaton Corporation 26850 SW Kinsman Rd Wilsonville,
More informationDASSAULT AVIATION Proprietary Data
F2000EX EASY 02-49-00 CODDE 1 PAGE 1 / 2 TABLE OF CONTENTS 02-49 02-49-00 TABLE OF CONTENTS 02-49-05 GENERAL Introduction Sources Equipment location 02-49-10 DESCRIPTION Introduction Description Operating
More informationMotor Protection. Presented By. Scott Peele PE
Motor Protection Presented By Scott Peele PE Motor Protection Overload on the motor load Fuses Heater Magnetic relay Short Circuit on motor circuit Fuses Breakers Single Phasing Overload Protection NEC
More informationTIME REQUIREMENT GUIDE (TRG)
CAT SWITCHGEAR TIME REQUIREMENT GUIDE (TRG) This warranty repair time requirement guide is designed to: Provide detailed guidance on troubleshooting Determine possible solutions Guide the technician to
More information