Record of Revision. Sr.No Revision. Technical Guidelines for Grid Tied Distributed Generation (Solar). i
|
|
- Quentin Haynes
- 5 years ago
- Views:
Transcription
1
2 Record of Revision Sr.No Revision Item/Clause No Nature of Change Approved By No 1 R1 D Table Addition DSP/AM 2 R1 E Addition DSP/AM 3 R1 I.VIII Added DSP/AM 4 R1 Anexxure1.1 to 1.8 Added and Edited DSP/AM 5 R1 Annexure 2.1 to 2.7 Added and Edited DSP/AM 6 R1 Annexure5.8 to 5.24 & Note Added and Edited DSP/AM 7 R1 Annexure6 Addition DSP/AM 8 R1 Annexure-3.1 To 3.5 Addition and Edited DSP/AM 9 R1 Annexure-4 (10 th Count) Deletion DSP/AM 10 R1 Annexure-7 Addition DSP/AM Technical Guidelines for Grid Tied Distributed Generation (Solar). i
3 Content: Sr. No. Description Page No A Introduction 1 B Salient Stipulations in MERC Reg C Codes and Standards 2 D E IEEE 519 Harmonic Standards and IEC Flicker Standards Technical requirement of the Grid Connected Roof Top Solar F Equipment Features 6 i Solar PV modules and array 6 ii Module mounting structure 7 iii Power Conditioning Unit/Inverter 7 iv ACDB (LT Panel) 8 v DC & AC Switches 8 vi Cables and installation accessories 8 vii Earthing and lightning protection 8 G Preliminary Site Visit Check List 9 H Pre Commissioning Check List 9 I Safety 9 Annexure 1: SLD for < 8 kw, single-phase 12 Annexure 2: SLD for > 8 kw but < 150 kw, 3-phase 13 Annexure 3: SLD for > 150 kw, 3-phase 15 Annexure 4: Preliminary Survey Check-Sheet 16 Annexure 5: Commissioning Check-Sheet 17 Annexure 6: Dimensions of equipment 17 Annexure---7: Sample Documents Technical Guidelines for Grid Tied Distributed Generation (Solar). ii
4 List of Tables Sr. No. Description Page No 1 Codes and Standards 2 2 Harmonic Voltage Distortion Limits in Percent of Nominal Fundamental Frequency Voltage ( IEEE Standard , table 11.1) 3 Basis for Harmonic Current Limits 2 4 Harmonic Current Distortion limits (I h ) in percent of I L 2 5 Flicker standard IEC Grid Connectivity technical requirement Technical Guidelines for Grid Tied Distributed Generation (Solar). iii
5 List of Figures Sr. No. Description Page No 1 Standard Shutdown Procedure Signage content 10 2 Specification on the Meter Cabin 11 3 Signage on/near the components in the meter cabin 11 4 Signage near Inverter 11 A.1 A.2 A.3 Typical SLD of grid Connected Roof Top PV with capacity below 8kW Typical SLD for grid Connected Roof Top PV with capacity above 8kW and below 150kW Typical SLD grid Connected Roof Top PV with capacity above 150kW Technical Guidelines for Grid Tied Distributed Generation (Solar). iv
6 A. Introduction The depleting sources of fossil fuels, sharp increase in power tariffs to industrialists due to heavy subsidies to Agriculture, very high T&D losses, decrease in reliability of power required, leads one to think of the alternative soco-economic, efficient, environment friendly and reliable sources of energies. The Power crises in Maharashtra is increasing day by day with a peak demand shortfall of 2000 MW. Maharashtra is having a total installed capacity of MW (including Central sector share) of centralized power plants and 623 MW of decentralized non-conventional power plants. Still there is a large potential in the non-conventional energy sources sector which can be tapped. This distributed potential can be harnessed to meet increasing power demand and to improve the techno-economic scenario. Setting up of large solar power projects requires huge land space whereas availability of land is a major constraint in Mumbai city limits. The prevailing scenario of declining trend in solar prices and increasing retail power tariff across most consumer categories like residential, commercial and industrial consumers would encourage consumers to install roof top solar systems.. Therefore, roof top solar is set to witness appreciable scaling of capacities in Mumbai. With the new regulation (Net Metering for Roof-top Solar PV Systems Regulations 2015) issued by MERC, RInfra has decided to issue Technical policy document for NET-metering and LT connectivity. B. Salient Stipulations in MERC (Net Metering for Roof-top Solar PV Systems) Regulations, 2015 at a Glance 1. Shall be permitted on first come first serve basis (Cl. 3.1) 2. Cumulative Capacity of all Roof-top Solar PV (RT-SPV) Systems under Net Metering connected to a particular DT of RInfra shall not exceed 40 % of its Capacity (Cl.4.1) 3. RInfra shall provide information on Website regarding Solar capacity available against each DT within 3 months of this notification (Cl. 4.2) 4. Roof-top Solar PV System Capacity shall not exceed the Consumer s Contract Demand (in kva) or Sanctioned Load (in kw) (Cl. 5.1) 5. AC Voltage level of Solar Injection shall be as below: (Cl. 5.2) a. 230 / 240 V (single-phase) for capacity less than 8 kw / 40 Amp b. 400 / 415 V (three-phase) for cap. less than 150 kw /187 kva c. 11 kv and above for cap. above 150 kw / 187 kva 6. HT (11 kv & above) Consumers may inject at LT Bus-bar, provided that Net Meter is installed on the HT side of Transformer.(Cl.5.4) Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 1 of 24
7 7. Consumer may install RT-SPV with or without Battery back-up provided that if battery is present, separate back-up wiring to prevent the battery Power from flowing into the RInfra Grid in absence of Grid supply. (Cl.6.2) 8. Consumer shall provide adequate protection for Islanding the RT-SPV from RInfra Network in the event of grid supply failure (Cl.6.4) 9. RInfra shall ensure that the inter-connection of the RT-SPV System with it s Network conforms to Specifications, Standards and other provisions specified in the CEA (Technical Standard for Connectivity of the Distributed Generation Resources) Regulations, 2013, the CEA (Measures Relating to Safety & Electric Supply) Regulations 2010 and the MERC (State Grid Code) Regulations 2006 or as may be specified in future.(cl. 6.1) 10. Metering arrangement shall have Net Meter (procured and installed by RInfra) and also Solar Generation Meter (procured & installed by Consumer or RInfra, who desires that such energy be counted towards meeting its RPO) (Cl. 7) C. Codes and Standards The installation shall meet the requirements of Indian Electricity rules, CEA and MERC Guidelines for grid connectivity. The materials, equipment and methods used in the installation shall conform to the latest edition of IS and IEC standards, and other national and international applicable standards including the following. If standard other than IS/IEC are used in design, manufacturing and testing, a copy of the same in English shall be submitted. IEEE IEC Part 1-2 IEEE 519 IEC IEC IEC Recommended Practice for Utility Interface of Photovoltaic (PV) Systems Requirements for construction & requirements for testing, for safety qualification Power Quality Standards Flicker Standard Photovoltaic systems - Power conditioners - Procedure for measuring efficiency Balance-of-system components for photovoltaic systems - Design qualification natural environments EMC EN , EN , EN , EN , EN IEC Safety of power converters for use in photovoltaic power systems - Part 2: Particular requirements for inverters IEC IEC / IS IS IEC IS 1554 IS 2551 Test procedure of islanding prevention measures for utility interconnected photovoltaic inverters Low voltage fuses Testing, Evaluation, Installation and Maintenance of ac Electricity Meters - Code of Practice. Low Voltage Switchgear and Control-gear PVC Insulated Cable for working voltages up to and including 1100V Signage Requirement Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 2 of 24
8 IS 3043 Earthing Standards IEC Lightning Protection IEC Operation, Maintenance and Documentation IS 732 Wiring Rules CEA Technical Standards for connection to grid 2007 ( amendment 2013) CEA-2013 Technical standard for Connectivity of the Distributed generation resources regulation 2013 MERC Maharashtra Electricity Regulatory Commission ( Net Metering for Roof Top Solar Phot0 Voltaic Systems) Regulation 2013 Table 1: Codes and Standards D. IEEE 519 Harmonic Standards and IEC Flicker Standards Bus Voltage at PCC Vn (kv) Individual Harmonic Voltage Total Voltage Distortion, THDVn Distortion (%) (%) Vn Vn Vn > Table 2: Harmonic Voltage Distortion Limits in Percent of Nominal Fundamental Frequency Voltage ( IEEE Standard , table 11.1) Short Circuit ratio at PCC Max individual frequency voltage harmonic (%) Related Assumption Dedicated system Large customer A few relatively large customer medium size customer Many small customer Table 3 Basis for Harmonic Current Limits Isc/I L h<11 11 h h h h TDD < > Table 4: Harmonic Current Distortion limits (I h ) in percent of I L Note: I L : is fundamental component of the maximum demand load current Isc: Short circuit current at PCC Ih: Magnitude of individual harmonic component (rms amps) Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 3 of 24
9 Value Observation Interval Limiting Value Pst (Short term flicker "perceptibility" value) 10 min 1.0 Plt (Long term flicker "perceptibility" value) 2 h 0.65 Table 5: Flicker standard IEC E. Technical requirement of the Grid Connected Roof Top Solar Sr.No Parameter Reference Requirement Overall State Distribution/Supply 1 conditions of Reference to State Distribution Code Code service Overall Grid 2 CEA Regulation 2010 Reference to regulations Standards 3 Equipment BIS / IEC / IEEE Reference to standards 4 Meters Central Electricity authority (Installation & operation of meters) Regulation Safety and supply Harmonic Requirements Harmonic Current 7 Synchronization 8 Voltage 9 Flicker 10 Frequency 11 DC injection Central Electricity authority (measure for safety and electricity supply) Regulation 2010 IEEE 519, CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Reference to regulations and additional conditions issued by the Commission. Reference to regulations Harmonic current Injections from a generating station shall not exceed the limits specified in IEEE 519 (indicated in Section D) Photovoltaic system must be equipped with a grid frequency synchronization device. Every time the generating station is synchronized to the electricity System, It shall not cause voltage fluctuation greater than +/- 5% at point of connection. The voltage-operating window should minimize nuisance tripping and should be lie in operating range 80% to 110% of the nominal connected voltage. Beyond a clearing time of 2 second, the photovoltaic system must isolate itself from the grid. Operation of Photovoltaic system should not cause voltage flicker in excess of the limits stated in IEC standards or other equivalent Indian standards, if any. (indicated In Section C) When the Distribution system frequency deviates outside the specified conditions (50.5 Hz on upper side and 47.5 Hz on Lower side), There should be Over and under frequency trip Functions with a clearing time of 0.2 seconds. Photovoltaic system should not inject DC current more than 0.5% of full rated output. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 4 of 24
10 12 Power Factor Islanding and Disconnection Overload and Overheat Paralleling Device Capacity of Plant Connection Voltage Level 18 Reclosing 19 Manual Isolating Switch between grid and Distributed generation 20 Test Certificate 21 Schematic Diagrams Distributed Generation Resources) Regulations 2013 IEC 61727/ CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 MERC regulation 2015 MERC Regulation 2015 clause 5.2 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 (clause 10) CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 While the output of the inverter is greater than 50%,it should operate in the range of 0.9 lag and lead (IEC)./ The inverter should dynamically operate in the range of 0.95 lag- to lead(cea) The photovoltaic system in the event of fault, voltage or frequency variation must island/disconnect itself as per IEC standard in stipulated period. The inverter should have the facility to automatically switch off in case of overload or overheating and should restart when normal conditions are restored Paralleling device of photovoltaic system shall be capable of withstanding 220% Of the normal voltage at the interconnection point. The total capacity of Solar Power connected to the distribution Transformer should be below 40% of Utility transformer capacity. Moreover, individual Solar Plant capacity should not exceed its customers approved contract demand Solar Capacity below 8KW can be injected at single phase. Moreover above 8kW and below 150kW it should be at three Phase 415 Volt. However above 150kW and below 1MW it should be at 415 V, while net meter will be installed at 11kV. The Reconnection of the Distributed Generation to Grid in the event of disconnection prior, should happen only if frequency and voltage are stable for atleast 1 minute. Capable of being Locked in open position, May not be rated for Load Break nor may have feature of over current protection. It should be reached quickly and conveniently. Should be located at height of at least 2.44 meter above the ground level. Inspection, test, Calibration and Maintenance prior to connection shall be done by applicant in consultation with the appropriate licensee is required. The applicant shall prepare Single Line Schematic Diagram in respect of its system facility and make the same available to the appropriate licensee Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 5 of 24
11 22 Power Quality Measurement 23 Protection Solar meter Location Statutory Approval Certification of Equipments Voltage Standards (clause 9) CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 (clause 8.2) CEA (Technical Standards for Connectivity of the Distributed Generation Resources) Regulations 2013 (clause 7.a,b) MERC Regulation 2015 clause 7.8, Annexure and MERC Regulation 2015 clause Annexure -3.4 MERC Regulation 2015 clause Annexure-3.1 Maharashtra Electricity Regulation Committee Standards of Performance of Distribution Licensees. Table 6: Grid Connectivity technical requirement DC current injection, Flicker and harmonic shall be done with calibrated meters before commissioning of the project and once a year in presence of parties concerned and indicative date shall be communicated. Circuit Breakers or other interrupting equipment shall be suitable for their indented application with the capability of interrupting the maximum available fault current. The DG (distributed generation) and associated equipment shall be designed so that the failure of any single device or component shall not potentially compromise the safety and reliability of the system. The Net Meter and the Solar Generation Meter shall be installed at such locations in the premises of the Eligible Consumer as would enable easy access to the Distribution Licensee for meter reading. Annexure-3 The Licensee shall specify the interface/inter-connection point and metering point. The uni-directional and bidirectional or pair of meters shall be fixed in separate meter boxes in the same proximity. The Eligible Consumer shall obtain any statutory approvals and clearances that may be required, such as from the Electrical Inspector or the municipal or other authorities, before connecting the Roof-top Solar PV System to the distribution Network. The equipment connected to the Licensee s Distribution System shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS), as the case may be, and the installation of electrical equipment shall comply with the requirements specified by the Central Electricity Authority regarding safety and electricity supply. The Grid voltage maximum limit is 250 Volt (i.e. 433 Volt) and ± 6% variation in voltage. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 6 of 24
12 F. Equipment Features I. Solar PV modules and array 1. Crystalline PV modules type. 2. The mechanical structure to withstand gusts of wind / cyclonic wind up to 120km/hr. 3. The offered modules conform to the latest edition of any of the following IEC/ equivalent BIS Standards for PV module design qualification and type approval: - Crystalline Silicon Terrestrial PV Modules : IEC 61215/IS PV modules also qualify Salt Mist Corrosion Testing as per IEC61701/IS PV modules used in solar power plants warranted for output wattage, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. II. Module mounting structure The PV modules will be mounted on fixed metallic structures of adequate strength and appropriate design, which can withstand load of modules and high wind velocities up to 120 km per hour. The support structure used in the power plants will be hot dip Galvanized Iron (G.I). Note: Point F.I and F.II are guidelines for Applicant, it is not RInfra requirement III. Power Conditioning Unit/Inverter 1. The Inverter shall have internal protection arrangement against any sustained fault in the feeder line and against lightning in the feeder line 2. The inverter shall have the required protection arrangements against earth leakage faults 3. DC lines shall have suitably rated isolators to allow safe start up and shut down of the system 4. Circuit breakers used in the DC lines must be rated suitably 5. The inverter shall preferably have provision for galvanic isolation. 6. Each solid state electronic device shall have to be protected to ensure long life of the inverter as well as smooth functioning of the inverter 7. The inverter shall include appropriate self protective and self diagnostic feature to protect itself and the PV array from damage in the event of inverter component failure or from parameters beyond the inverter s safe operating range due to internal or external causes. 8. Maximum Power tracking facility should be present.. 9. Protection against I. Over current II. Sync loss III. Over temp. IV. DC bus over voltage. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 7 of 24
13 V. Cooling Fan failure(if provided) VI. Grid Under/Over voltage and frequency 10. Dynamic Reactive Power Support to be present in inverter. 11. Integrated protection in the DC and three phase system. 12. Ground Fault and Arc protection should be there for DC (PV array). Moreover, insulation monitoring of PV array should be there. 13. AC and DC side disconnect switch / MCCB /ACB should be there for protection/isolation. 14. Power regulation in the event of thermal failure. 15. The Inverter should have functionally to limit the fault current contribution from the Distributed generation to its full load limit. The protection equipments should be designed to protect against system abnormality. IV. ACDB (LT Panel) 1. All outdoor devices/equipment to be IP65 as minimum V. DC & AC Switches 1. DC SIDE a. FUSE /MCB of suitable rating should be provided for array input b. The Input of the Inverter should have DC isolation switch. 2. AC SIDE a. MCB/MCCB /ACB of suitable rating shall be provided for connection and disconnection of Inverter & load. b. Isolating switches (No load Break) should be provided at incoming of the meter cabin. c. Isolating switches should be provided at the output of the inverter. d. The Phase and Earth fault protection embedded switches should be provided at output of the inverter and also in the meter cabins corresponding to solar circuit. VI. Cables and installation accessories The size of the cables between array interconnections, array to junction boxes, junction box to PCU, PCU to AC Distribution Box etc shall be so selected to keep the voltage drop and losses to the minimum. Permissible Wire Drop on DC side shall be <= 2% All cabling on the roof to be provided with suitable mechanical protection (i.e. cable trays with top cover or metal conduits). PVC conduits or pipes are not be used. To minimize the impact of the voltage rise variables such as inverter location, inverter output-circuit length and conductor size are to be selected accordingly. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 8 of 24
14 VII. Earthing and lightning protection Earthing: The array structure of the PV yard shall be grounded properly using adequate number of earthing kits. All metal casing or shielding of the power plants shall be thoroughly grounded to ensure safety of the solar power plants. Lightning: The PV plants shall be provided with lightning & over voltage protection. Lightning protection to be as per Indian or relevant IEC standard. Surge Protection Device Type 1 and 2 to be provided for lightning and surge protection respectively. G. Preliminary Site Visit Check List As given in Annexure 4 H. Pre-Commissioning Check List As given in Annexure - 5 I. Safety I. The equipment connected to the Licensee s Distribution System shall be compliant with relevant International (IEEE/IEC) or Indian Standards (BIS), as the case may be, and the installation of electrical equipment shall comply with the requirements specified by the Central Electricity Authority regarding safety and electricity supply. II. The design, installation, maintenance and operation of the Roof-top Solar PV System shall be undertaken in a manner conducive to the safety of the Roof-top Solar PV System as well as the Licensee s Network. III. If, at any time, the Licensee determines that the Eligible Consumer s Roof-top Solar PV System is causing or may cause damage to and/or results in the Licensee s other consumers or its assets, the Eligible Consumer shall disconnect the Roof-top Solar PV System from the distribution Network upon direction from the Licensee, and shall undertake corrective measures at his own expense prior to re-connection. IV. The Licensee shall not be responsible for any accident resulting in injury to human beings or animals or damage to property that may occur due to back- feeding from the Roof-top Solar PV System when the grid supply is off. The Licensee may disconnect the installation at any time in the event of such exigencies to prevent such accident. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 9 of 24
15 V. The Isolating switches should be provided at output and the input of the Inverter. Moreover, protection switches as indicated in Annexure should have Phase and earth Fault Protection. VI. The Meter cabin and corresponding switchgear should be easily accessible. VII. The Body Earthing of each and every equipment should be followed as per standards. (Atleast at two separate points for each equipment viz. solar panel, inverter etc should be done from two separate connected earth pits). VIII. Standard shutdown procedure to be located close to the inverter. Each circuit switches should be indicated by the red colored signage (Aluminum plate). Fig 1: Standard Shutdown Procedure Near Inverter (Laminated Paper fixed to Wall- Font size 16 Arial) Note: All Signage should be engraved (red color letter and height 7mm) on Aluminum plate with rivet for fitting at relevant locations. Points I-IV Refer MERC Regulation Annexure-3 clause Date Of Commissioning 2. Contact Number responsible for O&M of Plant 3. Peak Plant Capacity (KW) 4. No of Inverters with each rating 5. Inverter AC voltage and current 6. Inverter DC input Voltage and current 7. Short Circuit current fed by Inverter during fault 8. No of PV Panels 9. No of Strings 10. No of PV Panel in each Strings 11. Voc of a PV Panel 12. Isc of a PV panel Fig 2: Specification on the Meter Cabin (Laminated Paper and Fixed in meter cabin-font size 16 Arial) Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 10 of 24
16 CAUTION SOLAR ELECTRIC SYSTEM LOAD SWITCH SOLAR SWITCH NET SWITCH RINFRA SWITCH SOLAR METER NET METER Fig 3: Signage to be fitted near the components in the meter cabin INVERTER AC DISCONNECT SWITCH INVERTER DC DISCONNECT SWITCH Fig 4: Signage near Inverter Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 11 of 24
17 Annexure - 1 SLD are categorized accordingly to Generating capacity of PV(Photo Voltaic) plant and voltage level (Refer: MERC regulation clause 5.2). Case1:: Typical SLD of grid Connected Roof Top PV with capacity below 8kW single-phase DC Solar meter B A Rinfra MCB/Fuse Net Meter Grid Solar Inverter Surge protection Load Load Fig A.1: Typical SLD of grid Connected Roof Top PV with capacity below 8kW 1. The solar circuit switch B should have provision for Phase and earth fault protection. 2. On DC input side and AC output side of the Inverter, should have isolation switch. 3. Rinfra MCB will be of same rating as per existing policy guidelines. 4. The Inverter AC side (as indicated in SLD) and DC side (after DC connector box but input of inverter) should have isolation switch. 5. If applicant needs to operate in islanded mode during grid failure. The provision should be made by the customer to automatically trip switch A (shown in SLD) to avoid flow of power in to the grid/utility. Otherwise, customer should make provision for manual isolation switch A. 6. The separate meter boxes should be there to accommodate solar meter and bidirectional meter. Moreover, both meters should be in close proximity. The Net Meter and the Solar Generation Meter shall be installed at such locations in the premises of the Eligible Consumer as would enable easy access to the Distribution Licensee for meter reading. 7. Rating of all switches viz inverter, consumer and switch A will be selected based upon rating/ capacity of load and generation. It shall be procured by customers only. 8. In case of multiple injections from single-phase DG connected to the same upstream DT, RInfra shall ensure that they are on alternate phases to prevent undue Voltage imbalance. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 12 of 24
18 Annexure 2 Case-2 :: Typical SLD for grid Connected Roof Top PV with capacity above 8kW and below 150kW for Three-phase Solar Panel Inverter Switch Solar Inverter ACDB (AC Distribution Board) Isolating Transformer Star /Delta Switch Solar Meter B A Rinfra Switch Net Meter DC fuse Inverter Surge protection Consumer ACDB Load Switch Load Fig A.2: Typical SLD for grid Connected Roof Top PV with capacity above 8kW and below 150kW 1. Rinfra Switch should be as per our existing policy: 2. The Inverter AC side (as indicated in SLD) and DC side (after DC connector box but input of inverter) should have isolation switch. 3. The isolating Transformer (Galvanic Isolation) is advisable in case of load above 8KW solar generation. 9. If applicant needs to operate in islanded mode during grid failure. The provision should be made by the customer to automatically trip switch A (shown in SLD) to avoid flow of power in to the grid/utility. Otherwise, customer should make provision for manual isolation switch A. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 13 of 24
19 4. The size of the ACDB should be able to accommodate the switch A, and B (along with manual isolation switch, as per MERC Regulation). The ACDB should be provided by the applicant. 5. The Net Meter and the Solar Generation Meter shall be installed at such locations in the premises of the Eligible Consumer as would enable easy access to the Distribution Licensee for meter reading. Moreover they should be in separate boxes and in close proximity. 6. If Isolation transformer is not there, then corresponding solar side transformer switch may not be present. 7. Rating of all switches viz inverter, consumer and switch A will be selected based upon rating capacity of load and generation. Moreover, the inverter switch and switch A, B should have earth fault and phase protection i.e 50-50N and 51-51N relay. Note: N Instantaneous Phase and earth fault relay N Over current Phase and Earth fault relay. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 14 of 24
20 Annexure 3 Case 3:: Typical SLD grid Connected Roof Top PV with capacity above 150kW Three-phase Solar Panel DC fuse Inverter ACB 50-50N and 51-51N Two winding Isolating 415/415 Volt Delta/Star ACB 50-50N and 51-51N Surge protection Solar meter ACDB ACB 50-50N and 51-51N ACB 50-50N and 51-51N 0.415/11kV Star/Delta Load A Net meter Consumer 11kV Breaker 50-50N and 51-51N RInfra RMU Fig A.3:; Typical SLD grid Connected Roof Top PV with capacity above 150kW 1. Rinfra 11kV Switchgear should be as per our existing policy: 2. The Inverter AC (as indicated in SLD) and DC side (after DC connector box but input of inverter) should have isolation switch. 3. Inverter Main SFU/MCCB (switch B) should be in accordance with total capacity of Solar generation (i.e. it may be 110% of the full load rating of the inverter). The ACB should have with 50-50N and 51-51N protection relay. Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 15 of 24
21 4. If applicant needs to operate in islanded mode during grid failure. The provision should be made by the customer to automatically trip switch A (shown in SLD) to avoid flow of power in to the grid/utility. 5. The Net Meter and the Solar Generation Meter shall be installed at such locations in the premises of the Eligible Consumer as would enable easy access to the Distribution Licensee for meter reading. Moreover they should be in separate boxes and in close proximity. Annexure 4 Preliminary Site Survey Check List (after Application) Sr.No Description Y/N/Value Remarks 1 Capacity of the proposed PV Plant 2 Contract Demand (Sanctioned Load) of Consumer 3 Existing Network SLD details up to the Consumers Point of Supply and Last mile connectivity. The SLD should Indicate existing protection equipment (Fuse Rating, Voltage, MCB/MCCB, ACB rating), cable size, transformer size and loading of equipments uptil Point of supply i.e. Upstream network 4 Existing protection (MCB/Fuse/Breaker) details and SLD after Meter of Consumer 5 AC Voltage Level at which connectivity is sought 6 Rated output AC Voltage of the proposed Solar Plant (230,415 Volt). 7 Available cumulative capacity of relevant DT and substation Name Space availability/feasibility to commission new 8 Meter cabin /Panel accommodating Net meter, Solar Meter and Isolating switches. Consumer advised to ensure readiness of the meter cabin of adequate size to accommodate 9 equipment as per relevant SLD along with work completion report (Plant Setup Intimation). Moreover, intimation to furnish the documents prior to commissioning test. Note: Preliminary Site Survey Activity to be done by Divisional Load remark and Business team Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 16 of 24
22 Commissioning Check List Annexure - 5 Sr. Description Y/N/Value Remarks No 1 New Meter Cabin of requisite dimensions ready 2 Automation-compliant motorized Islanding Switch (A as per concept SLD) is installed. (In case Anti-islanding is not there or for Island operation with Battery or Diesel Generator is planned by applicant). 3 Protection switch B (as per SLD) installed is having Phase & Earth Fault protection 4 The switches are there as per SLD shown in Annexure 1,2 and 3 5 Solar /Net Meter is installed 6 Danger Board/Signage as Shown in Section I are incorporated at suitable locations. 7 Voltage magnitude at point of connection with grid. 230V/420 V 8 Full Load output Power of Plant in KW 9 AC and DC side manual isolating switches located near inverter. 10 Surge Protection (Type-II) device is installed on AC/DC side of Inverter 11 Voltage magnitude at the output of inverter 230V/420V 12 The DC/AC Ground Fault monitoring Feature in Inverter 13 Is Isolation Transformer (if applicable) installed -- to avoid DC current injection, harmonic injection and protect inverter from grid disturbances. Under (80%) /Over (110%) Voltage and Under (47.5)/Over (50.5) frequency protection for 14 Islanding is inbuilt in Inverter with minimum clearing time 2 sec(for voltage) and 0.2 sec (for frequency) respectively (as per section C) Power Quality Norms viz. harmonic limits, flicker 15 and DC current (refer Section C). The customer should provide test report from the government/nabl accredited Labs. a TDD Harmonic level in (5%) b DC Injection (0.5 % of FLC) c Flicker Interval / Value (Plt/Pst) Inverter should be configured to provide Dynamic Reactive support. The settings should be Power factor (capacitive and inductive) (for 8KW to 150KW) and 0.90 power factor for (150 KW and above) according to grid voltage variation. 17 The reconnection time should be 1 minute The document indicating details of fault 18 contribution by inverter ( time, voltage and current magnitude in tabular form) 19 Anti-islanding feature available in inverter as tested Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 17 of 24
23 IEC62116 or IEE Is Earthing of Solar PV followed as per IS Is Lightning Protection provided 22 If PV is Single Phase, whether load balancing is required to be done by RInfra. Has Customer provided single document to indicate single line drawing with protection 21 details/ratings, Load Connectivity/Details, earthing details, Lightning protection, Inverter(protection features and make) and Solar PV panel details (ratings and connectivity). Undertaking by applicant for internal Power Quality 22 check every year for the PV output above 150kW and every 2 years for less than 150 kw to 8kW. 23 The Solar Installation approved by PWD Electrical Inspector. Responsibility matrix /ownership of Equipment 24 Maintenance Undertaking furnished by the applicant. Y/N Note: 1. Points 11 to 19 are the inverter features likely to be present /configured. The documents indicating its presence should be submitted to Business team and verified by Load remark team. Moreover, its need should be communicated /explained to consumer during application itself. Furthermore, the compliance of documents indicating the details of inverter from point 11 to 19 should be checked /confirmed prior to commissioning visit. 2. Point s 21, 22, 23 and 24 document compliance need to be checked/confirmed by Business team prior to commissioning visit. After Submission of Test report (harmonics, flicker, DC injection and reactive Support) by the Applicant to Businees team, RInfra Divisional Load remark team may check its validity by performing on site testing. 3. Commissioning Check Activity to be done by Divisional Load remark and Business team. 4. Applicant s Power factor degradation may occur due to lowering Active power import from grid. (it needs to communicated to consumer) Annexure - 6 Dimensions of Equipments Sr.No Description of Equipment Height Width Depth 1 Single phase meter Three Phase meter (in built CT) Single phase MCB Single Phase MCB with casing Neutral Link-63AMp Neutral Link-100AMp Single Phase with Neutral MCB Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 18 of 24
24 8 Three Phase MCB Three Phase Neutral MCB Amp Fuse unit Amp Fuse unit Amp Fuse unit On load sitch Disconnector-400A Amp SDF Amp SDF Amp SDF Amp SDF Amp SDF Amp SDF Amp MCCB Amp MCCB All dimensions in mm Note 1 Wire should be clipped at 50mm interval at regular interval 2 The Height of LT Incoming switchgear shall be 0.9 meters above the ground level. 3 Board wiring shall be carried out only on Fire retardant plywood of 19 mm thickness provided by the applicant. 4 Current capacity for 10sqmm wire is 51A and for 4sqmm is 29A as per IS: Safety operating clearance from the wall on which meters are installed shall be 1.5m 6 LT Switchgear earthing to main GI strip by means of 25X3 GI flat at diagonally opposite ear thing bolts to be provided on FU / SDF 7 Single phase ELCB is twice the width of Single Phase MCB 8 Three phase ELCB size is same for Three phase and Neutral MCB Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 19 of 24
25 Annexure 7 Sample Documents---- NEED NOT BE OF SAME FORMAT Documents 1, 2 and 3 should be Type test report or from NABL accredited lab report 1. Harmonics Report 2. Flicker 3. DC Current Injection 4. Fault current contribution Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 20 of 24
26 5. Voltage and Frequency protection The Routine test report available from inverter manufacturer indicating protection features present in inverter. However, it should be configured as per CEA Guidelines 6. Routine Test report indicating Reconnection time settings, it has to be configured as per CEA Guidelines. 7. Reactive Support routine test report, it should be reconfigured as per CEA guidelines. At 240 volt (Nominal Voltage) to 245 Volt it should operate at unity power factor. However, grid voltage reduces, inverter should operate in leading power factor with linearly increasing trend up to 230 Volt, and then it becomes fixed with 0.95 lead (i.e. 30% capacitive). Similarly, for voltage range from 245 to 255 Volt the Inverter should absorb reactive power gradually with maximum power factor 0.95 (i.e. Inductive 30%). Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 21 of 24
27 8. DC side ground fault monitoring feature in the inverter. It can confirm from datasheet of the inverter. Similar for AC side ground fault monitoring feature. 9. Sample Data Sheet of Inverter Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 22 of 24
28 10. Detail drawing of Plant Setup Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 23 of 24
29 1. Voc =36 Volt 2. Isc =8Amp 3. Vdc =600 Volt 4. Vac=415 volt 5. I= 20 Amp 6. Inverter output=20kw Manual Switch 100 Amp MCCB milliamp Technical Guidelines for Grid Tied Distributed Generation (Solar) Page 24 of 24
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS
Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...
More informationODISHA ELECTRICITY REGULATORY COMMISSION UNIT VIII, BHUBANESWAR
ODISHA ELECTRICITY REGULATORY COMMISSION UNIT VIII, BHUBANESWAR 751012 ORDER No. OERC-Engg. 02/2010/(Vol-III)/1597(A) Dated : 26.11.2014 ON NET METERING/BI-DIRECTIONAL METERING & THEIR CONNECTIVITY WITH
More informationNet +Plus Connection Code
Net +Plus Connection Code LANKA ELECTRICITY COMPANY (PRIVATE) LIMITED 1.0 BACKGROUND The existing Net Metering Concept launched in the year 2010 noticed an exponential growth in the recent year and at
More informationBANGALORE ELECTRICITY SUPPLY COMPANY LIMITED
GUIDELINES FOR EMPANELMENT OF GRID TIED INVERTER MANUFACTURERS FOR IMPLEMENTATION OF SRTPV PROGRAM IN BESCOM. I. NEW EMPANELMENT 1. The grid tied inverter manufacturer shall register their application
More informationCHECK LIST FOR REGISTRATION FORM
NNEXUREII CHECK LIST FOR REGISTRTION FORM S. No. DOCUMENTS REQUIRED SUMITTED 1 Registration form signed by Registered consumer on each page with stamp 2 Detailed SLD of solar plant signed by Registered
More informationNet Metering Interconnection Requirements
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationNet Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland
More informationDISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase
PAGE 1 OF 7 USE: Requirements and guidelines for interconnection of single phase customer owned, (DR) Distributed Resource generation source, to NIPSCO s electric system, configured for. LATEST REVISION:
More informationGuideline for Using IEEE 1547 for Solar PV Interconnection Page 1
Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1 A Guide for Iowa s Municipal Electric Utilities On the How the IEEE 1547 Distributed Generation Interconnection Standard Affects Solar
More informationODISHA ELECTRICITY REGULATORY COMMISSION PLOT NO.4, CHUNOKOLI, SAILASHREE VIHAR, BHUBANESWAR ********
ODISHA ELECTRICITY REGULATORY COMMISSION PLOT NO.4, CHUNOKOLI, SAILASHREE VIHAR, BHUBANESWAR - 751021 ******** ORDER No. OERC-Engg. 02/2010/(Vol-IV)/1131 Dated :19.08.2016 ON NET METERING/BI-DIRECTIONAL
More informationDRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY
DRAFT Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY 2018 1. INTRODUCTION Solar energy has become the most popular renewable energy source
More informationINTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY
INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY Table of Contents Chapter 1. Purpose and scope. Pg 3 Chapter 2. Application
More informationGRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS
GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS Prof. Suryanarayana Doolla Department of Energy Science and Engineering Indian Institute of Technology Bombay OUTLINE Intoduction Grid
More informationGUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM
GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM Page 1 of 19 Table of Contents 1.0 SCOPE...4 2.0 PURPOSE...4 3.0 LIMITATIONS...5 4.0 GENERAL INTERCONNECTION
More informationCity of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW)
City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems
More informationEnquiry Form for Micro and Small Generators 5MW and Less
Enquiry form Enquiry Form for Micro and Small Generators 5MW and Less Connect an embedded generator (incl. solar, wind & micro-hydro) to the TasNetworks Distribution Network Please print and complete relevant
More informationGuidelines for connection of generators:
Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...
More informationTECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT
TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT 1.0 PURPOSE: 1. To charge the battery bank through Solar PV source and AC supply. 2. To invert and produce utility quality sine wave. 3. Inverters
More informationSmall Electrical Systems (Microgrids)
ELG4126: Microgrids Small Electrical Systems (Microgrids) A microgrid is a localized, scalable, and sustainable power grid consisting of an aggregation of electrical and thermal loads and corresponding
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationDefinitions. Scope. Customer Generation Interconnection Requirements
Updated 02/1 Page 1 Scope The purpose of this document is to describe Idaho Power s requirements for the installation and testing of Customer Generation acilities that are interconnected with Idaho Power
More informationComparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010
1 of 5. Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 2 Definitions 2 Not seen the definition for Inspector. But with, - Qualifications,
More informationREQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS
REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS 1. PURPOSE This document describes the general provisions and technical requirements for connecting Renewable Generation Systems (
More informationMinnesota Dept. of Commerce, Division of Energy Resources. Distributed Generation Workshop Interconnection Standards
Minnesota Dept. of Commerce, Division of Energy Resources Distributed Generation Workshop Interconnection Standards Presented by Michael Sheehan, P.E. October 11, 2011 Germans Solar Projected Cost Reductions
More informationLouisville Gas and Electric Company
P.S.C. Electric No. 11, Original Sheet No. 57 APPLICABLE In all territory served. AVAILABILITY OF SERVICE Available to any customer-generator who owns and operates a generating facility located on Customer
More informationTECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008
NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0
More informationRULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 2. SUMMARY OF APPLICATION AND INTERCONNECTION PROCESS
RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 1. PURPOSE This document describes the technical requirements for connecting Renewable Generation Systems ( RGS ) up to 150kW, or larger if approved
More informationGRID CONNECTED 400kWp SOLAR ROOF TOP POWER PLANT NET METERING AT KARNATAKA STATE CRICKET ASSOCIATION M. CHINNASWAMY STADIUM, BENGALURU
MGIRED Journal Volume 2(1) : 125-128 ISSN 2393-9605 GRID CONNECTED 400kWp SOLAR ROOF TOP POWER PLANT NET METERING AT KARNATAKA STATE CRICKET ASSOCIATION M. CHINNASWAMY STADIUM, BENGALURU Punati Sridhar,
More informationSouthern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management
Southern Company Interconnection Process Dexter Lewis Research Engineer Research and Technology Management Southern Company Outline Southern Company GPC Solar Interconnection Process Application requirements
More informationAppendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System
Appendix A2: Technical Requirements for Distributed Generators > 10 kw to be Connected to Kitchener-Wilmot Hydro Inc. s Distribution System A. INTRODUCTION This document outlines the technical requirements
More informationBihar Electricity Regulatory Commission Vidyut Bhawan, J.L.Nehru Marg, Patna
Bihar Electricity Regulatory Commission Vidyut Bhawan, J.L.Nehru Marg, Patna 800 021 ------------------------------------------------------------------------------------------------------------- ROOFTOP
More informationRoof Top Solar Power Net Metering Solution. Guidelines for implementation of Net Metering for Roof Top Solar Power System
Roof Top Solar Power Net Metering Solution Guidelines for implementation of Net Metering for Roof Top Solar Power System 1. Net Metering arrangement is permitted for 3 Phase connections only. The interconnection
More informationPolicy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, DRAFT
Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, 2015- DRAFT 1. PREAMBLE 1.1 To harness the potential of renewable energy resources in the state, Government of Madhya Pradesh
More informationConsumer Guidelines for Electric Power Generator Installation and Interconnection
Consumer Guidelines for Electric Power Generator Installation and Interconnection Habersham EMC seeks to provide its members and patrons with the best electric service possible, and at the lowest cost
More informationA member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.
Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationDocument Requirements for Engineering Review- PV Systems v1.1 12/6/2018
Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)
More informationSOLAR PV INTEGRATION: ISSUES & CHALLENGES with NET METERING
SOLAR PV INTEGRATION: ISSUES & CHALLENGES with NET METERING A.K. Bohra Chief Executive Officer NESCO, WESCO & SOUTHCO Central Service Office, Bhubaneswar DISTRIBUTED RENEWABLE ENERGY GENERATION With the
More informationGeneralised Technical Specifications for Grid Tie Solar Power plants
Generalised Technical Specifications for Grid Tie Solar Power plants The Grid tie Solar Power Plants without battery may be installed for any office buildings. As the office buildings have day time energy
More information045 : 2000 CEB STANDARD
045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.
More informationPOWER PURCHASE AGREEMENT FOR ROOFTOP SOLAR PV PLANTS WITH NET METERING ARRANGEMENT
POWER PURCHASE AGREEMENT FOR ROOFTOP SOLAR PV PLANTS WITH NET METERING ARRANGEMENT This Power Purchase agreement is entered into at (place).. on this. day of between Manipur State Power Distribution Company
More informationNortheastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5
Columbia City, Indiana Page 1 of 5 SCHEDULE DG-2 LARGE POWER DISTRIBUTED GENERATION I. AVAILABILITY This Distributed Generation Rate is available to any member in good standing of Northeastern REMC (Northeastern)
More informationSmall Generator Interconnection Program Interconnection Technical Requirements
General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator
More informationREQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw
REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used
More information3.6 Kwp Solar system Supply, Installation, Commissioning & Maintenance of Solar Systems to YEMAC office in HADDA street, Sana a city
LOT1 3.6 Kwp Solar system Supply, Installation, Commissioning & Maintenance of Solar Systems to YEMAC office in HADDA street, Sana a city 1 LOT 1 3.6 Kwp Solar PV Power Solution with Battery Backup Table
More informationTECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH
TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. PAGE 1 OF 7 TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH 1.0 SCOPE:
More informationJemena Electricity Networks (Vic) Ltd
Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...
More informationGuideline for Parallel Grid Exit Point Connection 28/10/2010
Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND
More informationEnquiry Form (Non-Registered Generator With Capacity less than 5 MW)
Connection Applicant (Embedded Generating Unit Owner/Proponent) Business name: ABN: Contact name: Address: Telephone number: E-mail address: Connection Applicant acting and working on behalf of the above
More informationEXTRA ORDINARY 16 AASHAADHA, 1937(S) BIHAR ELECTRICITY REGULATORY COMMISSION
REGISTERED NO. PT.-40 The B Bihar Gazett te EXTRA ORDINARY PUBLISHED BY AUTHORITY 16 AASHAADHA, 1937(S) (NO.PATNA 737) PATNA, TUESDAY, 7 TH JULY 2015 BIHAR ELECTRICITY REGULATORY COMMISSION NOTIFICATION
More informationNoble County Rural Electric Membership Corporation
Albion, Indiana Page 1 of 5 SCHEDULE NB-1 RESIDENTIAL NET BILLING I. AVAILABILITY This Net Billing Rate is available to any residential member in good standing of Noble REMC (Noble) who owns and operates
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli 620014, TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT ENQUIRY Phone: +91 431 257 79 38 Fax
More informationNOTICE INVITING TENDER
TENDER FOR SUPPLY, INSTALLATION AND COMMISSIONING OF 30kWp On Grid SOLAR POWER PLANT AT FACC/CHRD/LAKE HALL, BIDHAN CHANDRA KRISHI VISWAVIDYALAYA (BCKV), KALYAN, DIST NADIA, WEST BENGAL, INDIA, PIN 741235
More informationGUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR. NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS
GUIDELINES FOR OPERATING, METERING AND PROTECTIVE RELAYING FOR NET METERED SYSTEMS UP TO 50 kw AND BELOW 750 VOLTS 1. INTRODUCTION... 3 1.1 POLICY ON CUSTOMER GENERATION.... 3 1.2 GENERATION SOURCES AND
More informationAS/NZS AS/NZS
TEST REORT AS/NZS 4777.2 AS/NZS 4777.3 Grid connection of energy systems via inverters Grid protection requirements Report reference number... : 13TH0287-AS/NZS 4777_0 Date of issue......: 2014-01-22 Total
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationCIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems
CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,
More informationSummary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System
Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System This document is intended to be a general overview of PG&E s current technical
More informationPolicy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, DRAFT
Policy for Net-Metering based Renewable Energy Applications, Madhya Pradesh, 2015- DRAFT 1. PREAMBLE 1.1 To harness the potential of renewable energy resources in the state, Government of Madhya Pradesh
More information/ I S S : / S T S I
Agenda Electrical Transformers (Quality Control) Order Obtaining BIS Licence Requirements of Guidelines / IS 1180-1: 1: 2014 / STI Concerns in Getting BIS Licence Experience with BEE Regulations Recommendations
More informationRULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY
RULES ENABLING THE NET- METERING PROGRAM FOR RENEWABLE ENERGY Outline 1. Introduction 2. Legal Basis 3. Scope, Applicability & Qualification 4. Interconnection Set-Up 5. Pricing Methodology 6. Net-Metering
More informationRegenerative Utility Simulator for Grid-Tied Inverters
Regenerative Utility Simulator for Grid-Tied Inverters AMETEK s RS & MX Series with the SNK Option provides the solution Testing of grid-tied inverters used in solar energy systems is emerging as a major
More informationAPPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION
APPLICATION FOR INSTALLATION OF SMALL SCALE EMBEDDED ELECTRICITY GENERATION Work Order No: File Reference: 16/2/1 This application form for the connection of small scale embedded generation is for small
More informationPLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION
PLANNING, ELIGIBILITY FOR CONNECTION AND CONNECTION PROCEDURE IN EMBEDDED GENERATION Presentation by Engr. O. C. Akamnnonu Chief Executive Officer, Ikeja Electricity Distribution Company AGENDA WORK THROUGH
More informationDistributed Generation Interconnection Policy
Distributed Generation Interconnection Policy 1 Introduction Carroll Electric Membership Corporation Distributed Generation Interconnection Policy Carroll Electric Membership Corporation (herein after
More informationINTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)
INTER PLANT STANDARD STEEL INDUSTRY I P S S SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION) Corresponding IS does not exist IPSS: 1-10-036-12 0 FOREWORD 0.1 This
More information(i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:-
Revision 3 Date: 28/01/2016 Amendment to Schedule 6 for Induction Motor In the said schedule, (i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:- Effective from 1 st
More informationSA Power Networks Commissioning Witnessing Checklist
SA Power Networks Commissioning Witnessing Checklist CUSTOMER NAME: SOLAR PV APPROVED CAPACITY: BATTERY APPROVED CAPACITY: kw (AC) kw (AC) OPERATING PHILOSOPHY: MAXIMUM EXPORT: Non-Export/Export kw (AC)
More informationInterconnection Feasibility Study Report GIP-226-FEAS-R3
Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power
More information37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS
SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS
More information56-SDMS-07 REV. 01 SPECIFICATIONS FOR
56-SDMS-07 REV. 01 SPECIFICATIONS FOR UNIT SUBSTATIONS UP TO 36 kv ALUMINUM TRANSFORMER ALUMINUM BUS BARS LVDP This specification is property of SEC and subject to change or modification without any notice
More informationLarge Embedded Generation User Guide A
Large Embedded Generation User Guide A For Generating Systems AS4777 compliant and up to 200kW January 2013 SA Power Networks www.sapowernetworks.com.au Table of Contents 1. Introduction... 3 1.1 Embedded
More informationNortheastern Rural Electric Membership Corporation Columbia City, Indiana
Page 1 of 5 SCHEDULE ADG - 1 AGGREGATED DISTRIBUTED GENERATION SERVICE I. AVAILABILITY This Aggregated Distributed Generation Schedule is available to any member in good standing of Northeastern REMC (Northeastern),
More informationUmatilla Electric Cooperative Net Metering Rules
Umatilla Electric Cooperative Net Metering Rules Version: July 2017 Umatilla Electric Cooperative NET METERING RULES Rule 0005 Scope and Applicability of Net Metering Facility Rules (1) Rule 0010 through
More informationGuide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.
Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...
More informationOverview of State Distributed Generation Interconnection Rules
Overview of State Distributed Generation Interconnection Rules Presentation to EPA CHP Webinar Series June 26, 2008 Wayne Shirley Director The Regulatory Assistance Project 50 State Street, Suite 3 Montpelier,
More informationSTATE OF NORTH DAKOTA DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS
STATE OF NORTH DAKOTA DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS Foreword 2 1. Introduction 3 2. References 6 3. Types of Interconnections 7 4. Interconnection Issues and Technical
More informationAPPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
More informationExport limits for Embedded Generators up to 200 kva connected at Low Voltage
Export limits for Embedded Generators up to 200 kva connected at Low Voltage Standard Operating Procedure Document number: SOP 33-06 Issue number: 5 Status: FINAL Approver: J Bridge Date of approval: 3
More informationDAKOTA ELECTRIC ASSOCIATION DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS
DAKOTA ELECTRIC ASSOCIATION DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS Foreword 2 1. Introduction 3 2. References 6 3. Types of Interconnections 7 4. Interconnection Issues and
More informationTechnical Specifications
LT Distribution Box Technical Specifications 1. SCOPE 1.1 This specification covers design, manufacture, testing at manufacturer works before dispatch and supply of L.T. Distribution Cabinet suitable for
More information9.1.4 Troubleshooting of Faults in LCD Screen
User Manual 9 and Maintenance 9.1.2 Arc Detection Self-test An auto-test circuit is included in the module design of the inverter s AFDI function. If a DC arc fault is detected, the corresponding fault
More informationTECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS 1.1 INTRODUCTION In grid-connected Solar Photo-Voltaic (SPV) systems, solar energy is fed into the building loads that are connected to the public electricity grid through a service
More informationELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016
DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all
More informationSOMALI ENERGY TRANSFORMATION (SET) PROJECT
SOMALI ENERGY TRANSFORMATION (SET) PROJECT Solar PV installation BOQ JUNE 2016 School 1. Gob Secondary School- Awdal Region. 2. Godmo Biyo CAS Primary School Sanaag Region. 3. Lafarug Primary School- Sahil
More information201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE
201 S. Anaheim Blvd. Page No. 3.2.1 A. GENERAL 1. The character of electric service available at any particular location should be ascertained by inquiry at the City's Electrical Engineering Division office.
More informationDistinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation
SUN MAGIC + SUN MAGIC + is a state of art PCU product from ENERTECH product basket with Global standards. This unit will give operational flexibility to its customers to enjoy the benefits of advanced
More information2016 Photovoltaic Solar System Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE
More informationTRANSMISSION PLANNING CRITERIA
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing
More informationMadhya Pradesh Policy for Net-Metered Renewable Energy Applications, 2016
Madhya Pradesh Policy for Net-Metered Renewable Energy Applications, 2016 1. PREAMBLE 1.1 To harness the potential of renewable energy resources in the state, Government of Madhya Pradesh wishes to encourage
More informationIn the MERC (Net Metering for Roof-top Solar Photo Voltaic Systems) Regulations, 2015, the Eligible Consumer has been defined as under:
~~ NIAHA VITARAN MaharasIltn< State Electricity Distribution Co. Ltd. (A Govt. of Maharashtra Undertaking) ~IN:U40109MH2005SGC153645 No. Comm/CP/Solar-Net metering/ 3'(\"5/ Office of the Chief Engineer
More informationRenewable sources of electricity a brief overview
Micro generation 11 Renewable sources of electricity a brief overview THE SCOPE of the 17th Edition is wider and contains many new requirements, including additional requirements to ensure the safe connection
More informationThis is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationDistinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation
SUN MAGIC SUN MAGIC is a state of art PCU product from ENERTECH product basket with Global standards. This unit will give operational flexibility to its customers to enjoy the benefits of advanced monitoring
More informationChapter 3.1: Electrical System
Part-I: Objective type Questions and Answers Chapter 3.1: Electrical System 1. The heat input required for generating one kilo watt-hour of electrical output is called as. a) Efficiency b) Heat Rate c)
More informationTechnical Requirements for Renewable Energy Power System
Hotline: 2843 3228 Email address: RE@hkelectric.com Issued on 20 Nov 2018 1. Introduction 1.1. This document aims to provide the technical requirements for renewable energy power system (the REPS) connected
More information